Gen Set- Config- Mon

Embed Size (px)

Citation preview

  • 7/27/2019 Gen Set- Config- Mon

    1/49

    Guide Specification

    Dealer Information

    Name:

    Address:

    Phone Number:

    Prepared By:Email:

    Package Generator Set

    1.1 General

    1.1.1 References and StandardsThe generator set covered by these specifications shall be designed, tested, rated, assembled andinstalled in strict accordance with all applicable standards below: CSA C22.2 No14

    CSA 282

    CSA 100

    EN61000-6

    EN55011

    FCC Part 15 Subpart B

    ISO8528

    IEC61000

    UL508

    UL2200

    UL142

    Designed to allow for installed compliance to NFPA 70, NFPA99 and NFPA 110

    1.2 Related Sections

    1.2.1 Division 3 - Concrete

    1.2.2 Division 15 - Mechanical

    1.3 Work Included

    1.3.1 InstallationThe work includes supplying and installing a complete integrated generator system. The systemconsists of a diesel generator set with related component accessories and automatic transfer switchesspecified under a separate section.

    1.3.2 Fuel SystemThe CONTRACTOR shall provide a full tank of diesel fuel for the completion of all testing.

    1.3.3 System TestA complete system load test shall be performed after all equipment is installed. Guidelines in theStart-up Section.

    1.3.4 Requirements, Codes and RegulationsThe equipment supplied and installed shall meet the requirements of the NEC and all applicable local

  • 7/27/2019 Gen Set- Config- Mon

    2/49

    codes and regulations. All equipment shall be of new and current production by a MANUFACTURERwho has 25 years of experience building this type of equipment. Manufacturer shall be ISO9001certified.

    1.4 Substitution

    Proposed deviations from the specifications shall be treated as follows:

    1.4.1 Substitution Time RequirementRequests for substitutions shall be made a minimum of ten (10) days prior to bid date. Manufacturerscatalog data shall accompany each request and authorized acceptance shall be addenda only.

    1.4.2 Substitution ResponsibilityThe power system has been designed to the specified manufacturer's electrical and physicalcharacteristics. The equipment sizing, spacing, amounts, electrical wiring, ventilation equipment, fuel,and exhaust components have all been sized and designed around CATERPILLAR suppliedequipment. Should any substitutions be made, the CONTRACTOR shall bear responsibility for theinstallation, coordination and operation of the system as well as any engineering and redesign costs,which may result from such substitutions.

    1.5 Submittals

    Engine-generator submittals shall include the following information:1. Factory published specification sheet.2. Manufacturer's catalog cut sheets of all auxiliary components such as battery charger, control

    panel, enclosure, etc.3. Dimensional elevation and layout drawings of the generator set, enclosure and transfer

    switchgear and related accessories.4. Weights of all equipment.5. Concrete pad recommendation, layout and stub-up locations of electrical and fuel systems.6. Interconnect wiring diagram of complete emergency system, including generator, switchgear,

    day tank, remote pumps, battery charger, control panel, and remote alarm indications.

    7. Engine mechanical data, including heat rejection, exhaust gas flows, combustion air andventilation air flows, fuel consumption, etc.

    8. Generator electrical data including temperature and insulation data, cooling requirements,excitation ratings, voltage regulation, voltage regulator, efficiencies, waveform distortion andtelephone influence factor.

    9. Generator resistances, reactances and time constants.10. Generator locked rotor motor starting curves.11. Manufacturer's documentation showing maximum expected transient voltage and frequency

    dips, and recovery time during operation of the generator set at the specified site conditionswith the specified loads.

    12. Manufacturer's and dealer's written warranty.

    1.7 System Responsibility

    1.7.1 Generator Set DistributorThe completed engine generator set shall be supplied by the Manufacturer's authorized distributoronly.

    1.7.2 Requirements, Codes and RegulationsThe equipment supplied and installed shall meet the requirements of NEC and all-applicable localcodes and regulations. All equipment shall be new, of current production. There shall be one sourceresponsibility for warranty; parts and service through a local representative with factory trained service

  • 7/27/2019 Gen Set- Config- Mon

    3/49

    personnel.

    1.7.3 Automatic Transfer SwitchThe automatic transfer switch(es) specified in another section shall be supplied by the generator setmanufacturer in order to establish and maintain a single source of system responsibility andcoordination.

    1.8 Warranty

    1.8.1 Two YearStandby (ISO 8528-1: ESP) Generator Set WarrantyThe manufacturer's standard warranty shall in no event be for a period of less than two (2) years fromdate of initial start-up of the system and shall include repair parts, labor, reasonable travel expensenecessary for repairs at the job site, and expendables (lubricating oil, filters, antifreeze, and other serviceitems made unusable by the defect) used during the course of repair. Running hours shall be limited to500 hours annually for the system warranty by both the manufacturer and servicing distributor. Submittalsreceived without written warranties as specified will be rejected in their entirety.

    1.9 Parts and Service Qualifications

    1.9.1 Service FacilityThe engine-generator supplier shall maintain 24-hour parts and service capability within 100 miles ofthe project site. The distributor shall stock parts as needed to support the generator set package forthis specific project. The supplier must carry sufficient inventory to cover no less than 80% partsservice within 24hrs and 95% within 48 hours.

    1.9.2 Service PersonnelThe dealer shall maintain qualified factory trained service personnel.

    1.9.3 Product Support

    1.9.3.1 Preventive Maintenance AgreementThe authorized Caterpillar dealer shall provide a preventive maintenance agreement using qualifiedfactory trained service personnel, for a period of 1-year minimum. The dealer shall provide genuineCaterpillar parts and filters, shall provide all recommended fluids, dealer labor, travel labor and travelmileage to complete the suggested preventive maintenance as defined in the manufacturersOperation and Maintenance Manual.

    2 Product Specifications

    2.1 General Requirements

    2.1.1 Genset RequirementsThe generator set shall be Standby Duty rated at 1,400.0 ekW, 1,750.0 kVA, 1500 RPM, 0.8 powerfactor, 400 V, 3-Phase, 50 hertz, including radiator fan and all parasitic loads. Generator set shall besized to operate at the specified load at a maximum ambient of 104.0F (40C) and altitude of 500.0 feet

  • 7/27/2019 Gen Set- Config- Mon

    4/49

    (152.4 m).

    Standby Power Rating:Power is available for the duration of an emergency outage

    Average Power Output = 70% of standby powerLoad = VaryingTypical Hours/Year = 200 HoursMaximum Expected Usage = 500 hours/yearTypical Application = Standby

    2.1.2 Material and PartsAll materials and parts comprising the unit shall be new and unused.

    2.1.3 Engine

    The engine shall be diesel fueled, four (4) cycle, water-cooled, while operating with nominal speed notexceeding 1800 RPM. The engine will utilize in-cylinder combustion technology, as required, to meetapplicable EPA non-road mobile regulations and/or the EPA NSPS rule for stationary reciprocatingcompression ignition engines. Additionally, the engine shall comply with the State Emission regulations atthe time of installation/commissioning. Actual engine emissions values must be in compliance withapplicable EPA emissions standards per ISO 8178 D2 Emissions Cycle at specified ekW / bHP rating.Utilization of the Transition Program for Equipment Manufacturers (also known as Flex Credits) toachieve EPA certification is not acceptable. The in-cylinder engine technology must not permit unfilteredexhaust gas to be introduced into the combustion cylinder. Emissions requirements / certifications of thispackage: LOW BSFC

    2.1.3.1 Engine Governing

    The engine governor shall be a electronic Engine Control Module (ECM) with 24-volt DC ElectricActuator. The ECM shall be enclosed in an environmentally sealed, die-cast aluminum housing whichisolates and protects electronic components from moisture and dirt contamination. Speed droop shallbe adjustable from 0 (isochronous) to 10%, from no load to full rated load. Steady state frequencyregulation shall be +/- 6 RPM. Speed shall be sensed by a magnetic pickup off the engine flywheelring gear. A provision for remote speed adjustment shall be included. The ECM shall adjust fueldelivery according to exhaust smoke, altitude and cold mode limits. In the event of a DC power loss,the forward acting actuator will move to the minimum fuel position.

    2.2 Generator

    2.2.1 Generator Specifications

  • 7/27/2019 Gen Set- Config- Mon

    5/49

  • 7/27/2019 Gen Set- Config- Mon

    6/49

    designed and built by the engine manufacturer. The control shall provide all operating, monitoring,and control functions for the generator set. The control panel shall provide real time digitalcommunications to all engine and regulator controls via SAE J1939.

    2.4.1 EnvironmentalThe generator set control shall be tested and certified to the following environmental conditions:

    1. 40C to +70C Operating Range2. 100% condensing humidity, 30C to 60C3. IP22 protection for rear of controller; IP55 when installed in control panel4. 5% salt spray, 48 hours, +38C, 36.8V system voltage5. Sinusoidal vibration 4.3G's RMS, 24-1000Hz6. Electromagnetic Capability (89/336/EEC, 91/368/EEC, 93/44/EEC, 93/68/EEC, BS EN 50081-2,

    50082-2)7. Shock: withstand 15G

    2.4.2 Functional RequirementsThe following functionality shall be integral to the control panel.

    1. The control shall include a minimum 33 x 132 pixel, 24mm x 95mm, positive image, transflectiveLCD display with text based alarm/event descriptions.

    2. The control shall include a minimum of 3-line data display3. Audible horn for alarm and shutdown with horn silence switch4. Standard ISO labeling5. Multiple language capability6. Remote start/stop control7. Local run/off/auto control integral to system microprocessor8. Cooldown timer9. Speed adjust10. Lamp test11. Emergency stop push button12. Voltage adjust13. Voltage regulator V/Hz slope - adjustable14. Password protected system programming

    2.4.3 Digital Monitoring CapabilityThe controls shall provide the following digital readouts for the engine and generator. All readings shall beindicated in either metric or English units

    Engine

    1. Engine oil pressure2. Engine oil temperature3. Engine coolant temperature4. Engine RPM5. Battery volts6. Engine hours

    7. Engine crank attempt counter8. Engine successful start counter9. Service maintenance interval10. Real time clock11. Engine exhaust stack temperature12. Engine main bearing temperature

  • 7/27/2019 Gen Set- Config- Mon

    7/49

  • 7/27/2019 Gen Set- Config- Mon

    8/49

  • 7/27/2019 Gen Set- Config- Mon

    9/49

    2. Provide access to all date and events on generator set communications network3. Provide remote control capability for the generator set(s)4. Ability to communicate via Modbus RTU or remote modem

    2.4.8 Local and Remote Annunciation

    Local Annunciator (NFPA 99/110, CSA 282)Provide a local, control panel mounted, annunciator to meet the requirements of NFPA 110, Level 1.

    1. Annunciators shall be networked directly to the generator set control2. Local Annunciator shall include a lamp test pushbutton, alarm horn and alarm

    acknowledge pushbutton3. Provide the following individual light indications for protection and diagnostics

    a. Overcrankb. Low coolant temperaturec. High coolant temperature warningd. High coolant temperature shutdowne. Low oil pressure warningf. Low oil pressure shutdowng. Overspeed

    h. Low coolant leveli. EPS supplying loadj. Control switch not in autok. High battery voltagel. Low battery voltagem. Battery charger AC failuren. Emergency stopo. Sparep. Spare

    Remote Annunciator (NFPA 99/110, CSA 282)Provide a remote annunciator to meet the requirements of NFPA 110, Level 1.

    1. The annunciator shall provide remote annunciation of all points stated above and shallincorporate ring-back capability so that after silencing the initial alarm, any subsequentalarms will sound the horn.

    2. Ability to be located up to 4000 ft from the generator set

    2.5 Cooling System

    The generator set shall be equipped with a rail-mounted, engine-driven radiator with blower fan and allaccessories. The cooling system shall be sized to operate at full load conditions and 110 F* ambientair entering the room or enclosure (If an enclosure is specified). The generator set supplier isresponsible for providing a properly sized cooling system based on the enclosure static pressurerestriction.

    2.6 Fuel System

  • 7/27/2019 Gen Set- Config- Mon

    10/49

    2.6.1 Fuel SystemThe fuel system shall be integral with the engine. In addition to the standard fuel filters provided by theengine manufacturer, there shall also be installed a primary fuel filter/water separator in the fuel inlet lineto the engine. All fuel piping shall be black iron or flexible fuel hose rated for this service. No galvanizedpiping will be permitted. Flexible fuel lines shall be minimally rated for 300 degrees F and 100 psi.

    2.6.2 Fuel Sub Base TankProvide a double wall sub-base tank constructed to meet all local codes and requirements. A fuel tankbase of 24 hour capacity shall be provided as an integral part of the enclosure. It shall be contained in arupture basin with 110% capacity. The tank shall meet UL142 standards. A locking fill cap, a mechanicalreading fuel level gauge, low fuel level alarm contact, and fuel tank rupture alarm contact shall beprovided.

    2.7 Exhaust System (Indoor Installations Only)

    2.7.1 Silencer

    A industrial grade silencer, companion flanges, and flexible stainless steel exhaust fitting properlysized shall be furnished and installed according to the manufacturer's recommendation. Mountingshall be provided by the contractor as shown on the drawings. The silencer shall be mounted so thatits weight is not supported by the engine nor will exhaust system growth due to thermal expansion beimposed on the engine. Exhaust pipe size shall be sufficient to ensure that exhaust backpressuredoes not exceed the maximum limitations specified by the engine manufacturer.

    2.8 Starting System

    2.8.1 Starting MotorA DC electric starting system with positive engagement shall be furnished. The motor voltage shall beas recommended by the engine manufacturer.

    2.8.2 Jacket Water HeaterJacket water heater shall be provided and shall be sized to insure that genset will start within thespecified time period and ambient conditions.

    2.8.3 BatteriesBatteries - A lead-acid storage battery set of the heavy-duty diesel starting type shall be provided.Battery voltage shall be compatible with the starting system.

    2.8.4 Battery ChargerBattery Charger - A current limiting battery charger shall be furnished to automatically rechargebatteries. The charger shall be dual charge rate with automatic switching to the boost rate whenrequired. The battery charger shall be mounted on the genset package or inside the genset

  • 7/27/2019 Gen Set- Config- Mon

    11/49

    enclosure/room.

    2.8.5 Generator Set Start Module

    Supplied with an AC source from a UPS, the Generator Set Start Module will supply 1725 cold cranking

    amps @ 24 VDC to assist and backup the generator set starting batteries for improved system reliability.

    Generator Set Start Module shall have operating temperatures of (-20deg C to 50deg C). Generator SetStart Module to be supplied from generator set equipment supplier. This will ensure system integration.

    2.9 Enclosure

    2.9.1 Standard Weatherproof Enclosure

    The complete diesel engine generator set, including generator control panel, engine starting batteriesand fuel oil tank, shall be enclosed in a factory assembled, weather protective enclosure mounted onthe fuel tank base.

    1. A weather resistant enclosure of steel with electrostatically applied powder coated bakedpolyester paint. It shall consist of a roof, side walls, and end walls. Fasteners shall be

    either zinc plated or stainless steel. Handles shall be key lockable, all doors keyed alike,and hinges shall be zinc die cast or stainless steel. Access doors shall be hinged andcan be lifted off after opening 90 degrees. Intake openings shall be screened to preventthe entrance of rodents or pests.

    2. Lube oil and coolant drains shall be extended to the exterior of the enclosure andterminated with drain valves. Cooling fan and charging alternator shall be fully guarded toprevent injury.

    3 Execution

    3.1 Installation

    Install equipment in accordance with manufacturer's recommendations, the project drawings andspecifications, and all applicable codes.

    3.2 Start-Up and Testing

    Coordinate all start-up and testing activities with the Engineer and Owner. After installation iscomplete and normal power is available, the manufacturer's local dealer shall perform the following:

    Perform a 4 hour load bank test at a 0.8 PF at full nameplate rating. Loadbank, cables and other

    equipment required for this test to be supplied by the genset supplier.

    3.3 Operation and Maintenance Manuals

    Provide two (2) sets of operation and maintenance manuals covering the generator, switchgear, andauxiliary components. Include final as-built wiring interconnect diagrams and recommendedpreventative maintenance schedules.

  • 7/27/2019 Gen Set- Config- Mon

    12/49

    3.4 Training

    3.4.1 On-Site TrainingProvide on-site training to instruct the owner's personnel in the proper operation and maintenance ofthe equipment. Review operation and maintenance manuals, parts manuals, and emergency serviceprocedures.

  • 7/27/2019 Gen Set- Config- Mon

    13/49

  • 7/27/2019 Gen Set- Config- Mon

    14/49

    B. The Emergency Power System consists of the following as applicable:

    1. Generator sets

    2. Generator Control Switchboard (with associated monitoring and distribution equipment)

    3. Automatic Transfer Switches

    4. Uninterruptible Power Supply Systems

    5. Load Banks

    6. Battery Systems

    A. The Emergency Power System Supplier shall be an authorized service provider for allcomponents of the Emergency Power System. In order to assure maximum equipment

    uptime and best service response to the owner, the Emergency Power System Supplier shall

    be an factory-authorized dealer with complete Emergency Power System parts and service

    available on a 24 hour emergency basis within a11__________ mile radius of the project site.

    D. The Generator Control Switchboard specified in this section shall be a dead front type, low

    voltage switchboard construction. The Generator Control Switchboard shall be by the same

    manufacturer as the generator sets and furnished with the generator sets by the Emergency

    Power System Supplier (EPSS) as a total system. The switchboard and circuit breakers

    utilized in the Generator Control Switchboard shall be the same manufacturer as the circuit

    breakers provided in the assemblies for the normal and emergency distribution as specified

    under other sections of the specifications.

    E. The Generator Control Switchboard specified includes overcurrent and protective devices.

    The Emergency Power System Supplier shall provide a Short Circuit and Coordination Study,

    performed by a qualified professional engineer, as specified in the contract documents and

    described in Part 3 below.

    1.02 RELATED SECTIONS

    A. Section 16496 Automatic Transfer Switches

    B. Section 16911 Power Monitoring and Control System

    C. Section12_____ Uninterruptible Power Supply System

    D. Section _____ Generators

    E. Section _____ Load Bank

    F. Section _____ Battery Systems

    G. Section 16015 Short Circuit / Coordination Studies

    H. Section 16016 Arc Flash Study

    1.03 REFERENCES

    A. The low voltage distribution switchboards and all components shall be designed,

    manufactured and tested in accordance with the latest applicable following standards:

    1. NEMA PB-2

    2. UL Standard 891.

    1 Note to Spec. Writer Insert data in blanks

    21

    Note to Spec. Writer Insert data in blanks

  • 7/27/2019 Gen Set- Config- Mon

    15/49

    B. The Emergency Power System shall meet or exceed the applicable requirements for the

    following standards as required:

    1. UL

    2. CSA

    3. IEC

    4. NFPA 70

    5. NFPA 99

    6. NFPA 110

    1.04 SUBMITTALS FOR REVIEW/APPROVAL

    A. The following information shall be submitted to the Engineer:

    1. Master drawing index

    2. Front view elevation

    3. Floor plan

    4. Top view

    5. Single line

    6. Schematic diagram

    7. Nameplate schedule

    8. Component list

    9. Conduit entry/exit locations

    10. Assembly ratings including:

    a. Short-circuit rating

    b. Voltage

    c. Continuous current11. Major component ratings including:

    a. Voltage

    b. Continuous current

    c. Interrupting ratings

    12. Circuit Breaker Schedule

    a. Cable terminal sizes

    13. Product data sheets.

    14. Sequence of operation description

    B. Where applicable, the following additional information shall be submitted to the Engineer:

    1. Busway connection

    2. Connection details between close-coupled assemblies

    3. Composite floor plan of close-coupled assemblies

    4. Key interlock scheme drawing and sequence of operations.

    1.05 SUBMITTALS FOR CONSTRUCTION

  • 7/27/2019 Gen Set- Config- Mon

    16/49

    A. The following information shall be submitted for record purposes:

    1. Final as-built drawings and information for items listed in paragraph 1.04

    2. Wiring diagrams

    3. Certified production test reports

    4. Installation information

    5. Seismic certification and equipment anchorage details.

    B. The final (as-built) drawings shall include the same drawings as the original construction

    drawings and shall incorporate all changes made during the manufacturing process.

    1.06 QUALIFICATIONS

    A. The manufacturer of the assembly shall be the manufacturer of the circuit protective deviceswithin the assembly.

    B. For the equipment specified herein, the manufacturer shall be ISO 9001 or 9002 certified.

    C. The manufacturer of this equipment shall have produced similar electrical equipment for a

    minimum period of ten (5) years. When requested by the Engineer, an acceptable list ofinstallations with similar equipment shall be provided demonstrating compliance with this

    requirement.

    D.3Provide Seismic tested equipment as follows:

    1. The equipment and major components shall be suitable for and certified to meet all

    applicable seismic requirements of International Building Code (IBC) for zone 4

    applications. Guidelines for the installation consistent with these requirements shall be

    provided by the switchboard manufacturer and be based upon testing of representative

    equipment. The test response spectrum shall be based upon a 5% minimum damping

    factor, IBC: a peak of 2.45gs (3.2-11 Hz), and a ZPA of 0.98gs applied at the base of the

    equipment. The tests shall fully envelop this response spectrum for all equipment natural

    frequencies up to at least 35 Hz.

    -- OR --

    1. The equipment and major components shall be suitable for and certified to meet all

    applicable seismic requirements of the California Building Code (CBC) through zone 4

    applications. Guidelines for the installation consistent with these requirements shall be

    provided by the switchboard manufacturer and be based upon testing of representative

    equipment. The test response spectrum shall be based upon a 5% minimum damping

    factor, CBC: a peak of 2.15gs, and a ZPA of 0.86gs applied at the base of the equipment.

    The tests shall fully envelop this response spectrum for all equipment natural frequencies

    up to at least 35 Hz.

    --

    4

    OR --1. The manufacturer may certify the equipment based on a detailed computer analysis of the

    entire assembly structure and its components. Guidelines for the installation consistent

    with these requirements shall be provided by the switchboard manufacturer and be based

    upon testing of representative equipment. The equipment manufacturer shall document

    the requirements necessary for proper seismic mounting of the equipment.

    3 Note to Spec. Writer Optional

    4Note to Spec. Writer Select one

  • 7/27/2019 Gen Set- Config- Mon

    17/49

    2. The following minimum mounting and installation guidelines shall be met, unless

    specifically modified by the above referenced standards.

    a. The Contractor shall provide equipment anchorage details, coordinated with the

    equipment mounting provision, prepared and stamped by a licensed civil engineer in

    the state. Mounting recommendations shall be provided by the manufacturer based

    upon approved shake table tests used to verify the seismic design of the equipment.b. The equipment manufacturer shall certify that the equipment can withstand, that is,

    function following the seismic event, including both vertical and lateral required

    response spectra as specified in above codes.

    c. The equipment manufacturer shall document the requirements necessary for proper

    seismic mounting of the equipment. Seismic qualification shall be considered achieved

    when the capability of the equipment, meets or exceeds the specified response

    spectra.

    1.07 REGULATORY REQUIREMENTS

    A. The low-voltage switchboard shall be UL labeled.

    1.08 DELIVERY, STORAGE AND HANDLING

    A. Equipment shall be handled and stored in accordance with manufacturers instructions. One(1) copy of these instructions shall be included with the equipment at time of shipment.

    B. Each switchboard assembly shall be split into shipping groups for handling as determinedduring the shop drawing phase jointly with the installing contractor. Shipping groups shall be

    designed to be shipped by truck, rail or ship. Shipping groups shall be bolted to skids, and

    covered with tarps for protection from weather. Accessories shall be packaged separately.

    1.09 OPERATION AND MAINTENANCE MANUALS

    A. Equipment operation and maintenance manuals shall be provided with each assemblyshipped and shall include instruction leaflets, instruction bulletins and renewal parts lists

    where applicable, for the complete assembly and each major component.

    PART 2 PRODUCTS

    2.01 MANUFACTURERS

    A. Caterpillar

    B.5_________

    C. __________

    The listing of specific manufacturers above does not imply acceptance of their products that do

    not meet the specified ratings, features and functions. Manufacturers listed above are not relieved

    from meeting these specifications in their entirety.

    2.02 RATINGS

    5

    Note to Spec. Writer Insert data in blanks

  • 7/27/2019 Gen Set- Config- Mon

    18/49

    A. The assembly shall be rated to withstand mechanical forces exerted during short-circuit

    conditions when connected directly to a power source having available fault current of6

    [(65,000) (100,000) (150,000) amperes symmetrical at rated voltage] [as shown on the

    drawings].

    B. Voltage rating to be as indicated on the drawings.

    2.03 CONSTRUCTION

    A. Switchboard shall consist of the required number of vertical sections bolted together to form a

    rigid assembly. The sides and rear shall be covered with removable bolt-on covers. All edges

    of front covers or hinged front panels shall be formed. Provide adequate ventilation within the

    enclosure.

    B. All sections of the switchboard shall be front and rear aligned with depth as shown on

    drawings. All generator main protective devices shall be individually mounted. All distribution

    protective devices shall be group mounted. Devices shall be front removable and load

    connections front and rear accessible. Rear access shall be provided.

    C. The assembly shall be provided with adequate lifting means.

    D. The switchboard shall be equal to Caterpillar utilizing the components herein specified and as

    shown on the drawings.

    E.7The switchboard shall be suitable for use as service entrance equipment and be labeled in

    accordance with UL requirements.

    2.04 BUS

    A. All bus bars shall be [silver-plated copper] [tin-plated aluminum]. Main horizontal bus bars

    shall be mounted with all three phases arranged in the same vertical plane. Bus sizing shall

    be based on NEMA standard temperature rise criteria of 65 degrees C over a 40 degrees C

    ambient (outside the enclosure).

    B. Provide a full capacity neutral bus where a neutral bus is indicated on the drawings.

    C. A copper ground bus (minimum 1/4 x 2 inch) shall be furnished firmly secured to each vertical

    section structure and shall extend the entire length of the switchboard.

    D. All hardware used on conductors shall be high-tensile strength and zinc-plated. All bus joints

    shall be provided with conical spring-type washers.

    2.05 WIRING/TERMINATIONS

    A. Small wiring, necessary fuse blocks and terminal blocks within the switchboard shall befurnished as required. Control components mounted within the assembly, such as fuse

    blocks, relays, pushbuttons, switches, etc., shall be suitably marked for identification

    corresponding to appropriate designations on manufacturers wiring diagrams.

    B. NEMA 2-hole8[mechanical-] [crimp-] type lugs shall be provided for all line and load

    terminations suitable for copper or aluminum cable rated for 75 degrees C of the size

    indicated on the drawings.

    6Note to Spec. Writer Select one

    7Note to Spec. Writer Optional

    8Note to Spec. Writer Select one

  • 7/27/2019 Gen Set- Config- Mon

    19/49

    C. Lugs shall be provided in the incoming line section for connection of the main grounding

    conductor. Additional lugs for connection of other grounding conductors shall be provided as

    indicated on the drawings.

    D. All control wire shall be type SIS, bundled and secured with nylon ties. Insulated locking

    spade terminals shall be provided for all control connections, except where saddle type

    terminals are provided integral to a device. All current transformer secondary leads shall firstbe connected to conveniently accessible short-circuit terminal blocks before connecting to

    any other device. All groups of control wires leaving the switchboard shall be provided with

    terminal blocks with suitable numbering strips. Provide wire markers at each end of all control

    wiring.

    E. Where individual conductors cross switchboard/switchgear shipping splits they shall be fitted

    with plug-together connectors for reliable field assembly.

    2.06 INSULATED CASE CIRCUIT BREAKERS GENERATOR MAIN BREAKERS AND

    CONTROLLED (LOAD SHED) DISTRIBUTION BREAKERS

    A. Protective devices shall be drawout UL1066 low-voltage insulated case circuit breakers.

    Frame ratings shall be 800, 1200, 1600, 2000, 2500, 3000, 4000, 5000, or 6000 amperes. Allbreakers shall be UL1066 listed for application in their intended enclosures for 100% of their

    continuous ampere rating.

    B. Circuit breakers shall be electrically operated and equipped with auxiliary contacts, bell alarm

    contacts, and microprocessor based trip units.

    C. Electrically operated breakers shall be complete with 24VDC shunt trips, and 120V AC motor

    operators, the charging time of the motor shall not exceed 6 seconds.

    D. All circuit breakers shall have a minimum symmetrical interrupting capacity of [50,000]

    [65,000] [85,000] [100,000] [150,000] amperes.

    E. All insulated case circuit breakers shall be provided with trip units as specified in section 2.07.

    F. To facilitate lifting, the insulated case circuit breaker shall have integral handles on the side of

    the breaker. The insulated case circuit breaker shall have a closing time of not more than 3

    cycles. The primary contacts shall have an easily accessible wear indicator to indicate

    contact erosion.

    G. The insulated case circuit breaker shall have three windows in the front cover to clearly

    indicate any electrical accessories that are mounted in the breaker. The accessory shall have

    a label that will indicate its function and voltage. The accessories shall be plug and lock type

    and UL listed for easy field installation. They shall be modular in design and shall be common

    to all frame sizes and ratings.

    H. The breaker control interface shall have color-coded visual indicators to indicate contact open

    or closed positions as well as mechanism charged and discharged positions. Manual controlpushbuttons on the breaker face shall be provided for opening and closing the breaker. The

    insulated case circuit breaker shall have a Positive On feature. The breaker flag will read

    Closed if the contacts are welded and the breaker is tripped or opened.

    I. The current sensors shall have a back cover window that will permit viewing the sensor rating

    on the back of the breaker. A rating plug will offer indication of the rating on the front of the trip

    unit.

  • 7/27/2019 Gen Set- Config- Mon

    20/49

    J. A position indicator shall be located on the faceplate of the breaker. This indicator shall

    provide color indication of the breaker position in the cell. These positions shall be Connect

    (Red), Test (Yellow), and Disconnect (Green). The levering door shall be interlocked so that

    when the breaker is in the closed position, the breaker levering-in door shall not open.

    K. Each insulated case circuit breaker shall offer sixty (60) front mounted dedicated secondary

    wiring points. Each wiring point shall have finger safe contacts, which will accommodate #10AWG maximum field connections with ring tongue or spade terminals or bare wire.

    L. The breaker cell shall be equipped with drawout rails and primary and secondary

    disconnecting contacts. The stationary part of the primary disconnecting devices for each

    insulated case circuit breaker shall consist of a set of contacts extending to the rear through a

    glass polyester insulating support barrier; corresponding moving finger contacts suitably

    spaced shall be furnished on the insulated case circuit breaker studs which engage in only

    the connected position. The assembly shall provide multiple silver-to-silver full floating high-

    pressure point contacts with uniform pressure on each finger maintained by springs.

    1. The secondary disconnecting devices shall consist of plug-in connectors mounted on the

    removable unit and engaging floating plug-in connectors at the front of the compartment.

    The secondary disconnecting devices shall be gold-plated and pin and socket contactengagement shall be maintained in the connected and test positions.

    2. The removable insulated case circuit breaker element shall be equipped with

    disconnecting contacts, wheels and interlocks for drawout application. It shall have four

    (4) positions: CONNECTED, TEST, DISCONNECTED, and REMOVED all of which

    permit closing the compartment door. The breaker drawout element shall contain a worm

    gear levering in and out mechanism with removable lever crank. Mechanical

    interlocking shall be provided so that the breaker is in the tripped position before allowing

    access to the levering mechanism for levering in or out of the cell. Interlock systems

    that trip the breaker when accessing the levering mechanism will NOT be acceptable.

    The breaker shall include an optional provision for key locking open to prevent manual or

    electric closing. Padlocking shall provide for securing the breaker in the connected, test,

    or disconnected position by preventing levering.

    2.07 MICROPROCESSOR TRIP UNITS - INSULATED CASE CIRCUIT BREAKERS

    *Note to Spec. Writer:

    Digitrip RMS trip units are available in four (4) models:

    Digitrip RMS 520 Basic protection select paragraph 2.05 A through I.

    Digitrip RMS 520M Basic protection with local current metering, select paragraph 2.05 Athrough K.

    Digitrip RMS 520MC Basic protection with local current metering and remotecommunications, select paragraph 2.05 L through X.

    Digitrip RMS 1150 Advanced protection, metering, LED display and remotecommunications, select paragraph 2.05 A through E, H through J, and L through X.

    A. Each low voltage insulated case circuit breaker shall be equipped with a solid-state tripping

    system consisting of three current sensors, microprocessor-based trip device and flux-

    transfer shunt trip. Current sensors shall provide operation and signal function. The trip unit

  • 7/27/2019 Gen Set- Config- Mon

    21/49

    shall use microprocessor-based technology to provide the basic adjustable time-current

    protection functions. True RMS sensing circuit protection shall be achieved by analyzing the

    secondary current signals received from the circuit breaker current sensors and initiating trip

    signals to the circuit breaker trip actuators when predetermined trip levels and time delay

    settings are reached. Interchangeable current sensors with their associated rating plug shall

    establish the continuous trip rating of each circuit breaker.

    B. The trip unit shall have an information system that provides LEDs to indicate mode of trip

    following an automatic trip operation. The indication of the mode of trip shall be retained after

    an automatic trip. A reset button shall be provided to turn off the LED indication after an

    automatic trip.

    C. The trip unit shall be provided with a display panel, including a representation of the

    time/current curve that will indicate the protection functions. The unit shall be continuously

    self-checking and provide a visual indication that the internal circuitry is being monitored and

    is fully operational.

    D. The trip unit shall be provided with a making-current release circuit. The circuit shall be armed

    for approximately two cycles after breaker closing and shall operate for all peak fault levels

    above 25 times the ampere value of the rating plug.

    E. Trip unit shall have selectable thermal memory for enhanced circuit protection.

    F. Complete system selective coordination shall be provided by the addition of the following

    individually adjustable time/current curve shaping solid-state elements:

    1. All circuit breakers shall have adjustments for long delay pickup and time.

    2. 9Main circuit breakers shall have individual adjustments for short delay pickup and

    time,and include It settings.

    3. Main circuit breakers shall have an adjustable instantaneous pickup.

    4. [All circuit breakers] [Circuit breakers, where indicated on the drawings,] shall haveindividually adjustable ground fault current pickup and time, and include I22t settings or

    ground alarm only.

    G. The trip unit shall have provisions for a single test kit to test each of the trip functions.

    H. The trip unit shall provide zone interlocking for the short-time delay and ground fault delay trip

    functions for improved system coordination. The zone interlocking system shall restrain the

    tripping of an upstream breaker and allow the breaker closest to the fault to trip with no

    intentional time delay. In the event that the downstream breaker does not trip, the upstream

    breaker shall trip after the present time delay.10Factory shall wire for zone interlocking for the

    insulated case circuit breakers within the switchboard.

    I. The trip unit shall have an information system that utilizes battery backup LEDs to indicate

    mode of trip following an automatic trip operation. The indication of the mode of trip shall be

    retained after an automatic trip operation. The indication of the mode of trip shall be retainedafter an automatic trip. A test pushbutton shall energize a LED to indicate the battery status.

    J. [All circuit breakers] [Circuit breakers, where indicated on the drawings,] shall haveindividually adjustable ground fault alarm only.

    9Note to Spec. Writer Select one

    10Note to Spec. Writer Optional

  • 7/27/2019 Gen Set- Config- Mon

    22/49

    K. The trip unit shall have a 4-character LCD display showing phase, neutral, and ground

    current. The accuracy of these readings shall be +/- 2% of full scale.

    L. The trip unit shall be equipped to permit communication via a network twisted pair for remote

    monitoring and control.

    M. The trip unit shall include a power/relay module which shall supply control to the readout

    display. Following an automatic trip operation of the circuit breaker, the trip unit shall maintain

    the cause of trip history and the mode of trip LED indication as long as its internal power

    supply is available. An internal relay shall be programmable to provide contacts for remote

    ground alarm indication.

    N. The trip unit shall include a voltage transformer module, suitable for operation up to 600V,

    50/60 Hz. The primary of the power relay module shall be connected internally to the line side

    of the circuit breaker through a dielectric test disconnect plug.

    O. The display for the trip units shall be a 24-character LED display.

    P. Metering display accuracy of the complete system, including current sensors, auxiliary CTs,

    and the trip unit, shall be +/- 1% of full scale for current values. Metering display accuracy of

    the complete system shall be +/- 2% of full scale for power and energy values.

    Q. The unit shall be capable of monitoring the following data:

    1. Instantaneous value of phase, neutral and ground current

    2. Instantaneous value of line-to-line voltage

    3. Minimum and maximum current values

    4. Watts, VARs, VA, watt-hours, var-hours, and VA hours.

    R. The energy-monitoring parameter values (peak demand, present demand, and energy

    consumption) shall be indicated in the trip units alphanumeric display panel.

    S. The trip unit shall display the following power quality values: crest factor, power factor, percent

    total harmonic distortion, and harmonic values of all phases through the 31st harmonic.T. An adjustable high load alarm shall be provided, adjustable from 50 to 100% of the long delay

    pickup setting.

    U. The trip unit shall contain an integral test pushbutton. A keypad shall be provided to enable

    the user to select the values of test currents within a range of available settings. The

    protection functions shall not be affected during test operations. The breaker may be tested in

    the TRIP or NO TRIP test mode.

    V. Programming may be done via a keypad at the faceplate of the unit or via the communication

    network.

    W. System coordination shall be provided by the following microprocessor-based programmable

    time-current curve shaping adjustments. The short-time pickup adjustment shall bedependant on the long delay setting.

    1. Programmable long-time setting

    2. Programmable long-time delay with selectable IT or I24T curve shaping

    3. Programmable short-time setting

    4. Programmable short-time delay with selectable flat or I2T curve shaping, and zone

    selective interlocking

  • 7/27/2019 Gen Set- Config- Mon

    23/49

    5. Programmable instantaneous setting

    6. Programmable ground fault setting trip or ground fault setting alarm

    7. Programmable ground fault delay with selectable flat or I2T curve shaping and zoneselective interlocking.

    X. The trip unit shall offer a three-event trip log that will store the trip data, and shall time and

    date stamp the event.

    Y.11The trip unit shall have the following advanced features integral to the trip unit:

    1. Adjustable under voltage release

    2. Adjustable over voltage release

    3. Reverse load and fault current

    4. Reverse sequence voltage alarm

    5. Under frequency

    6. Over frequency

    7. Voltage phase unbalance and phase loss during current detection

    2.08 MOLDED-CASE CIRCUIT BREAKERS NON-CONTROLLED DISTRIBUTION BREAKERS

    A. Protective devices shall be fixed-mounted, molded case circuit breakers with inverse time and

    instantaneous tripping characteristics.

    B. Circuit breakers shall be operated by a toggle-type handle and shall have a quick-make,

    quick-break over-center switching mechanism that is mechanically trip-free. Automatic

    tripping of the breaker shall be clearly indicated by the handle position. Contacts shall be

    nonwelding silver alloy and arc extinction shall be accomplished by means of DE-ION arc

    chutes. A push-to-trip button on the front of the circuit breaker shall provide a local manual

    means to exercise the trip mechanism.

    C. Circuit breakers shall have a minimum symmetrical interrupting capacity12

    [of (65,000)(100,000) (150,000) amperes symmetrical at rated voltage] [as shown on the drawings].

    D. Circuit breakers [250-] [400-] [600-] [800-] ampere frame and below shall be thermal-

    magnetic type trip units and inverse time-current characteristics.

    E. Circuit breakers [400-] [600-] [800-] ampere through 2500-ampere frame shall be

    microprocessor-based RMS sensing type trip units.

    F. 13Ground fault protection shall be provided where indicated.

    G. Where indicated circuit breakers shall be current limiting.

    H. Where indicated provide UL listed circuit breakers for applications at 100% of their

    continuous ampere rating in their intended enclosure.

    2.09 MICROPROCESSOR TRIP UNITS MOLDED-CASE DISTRIBUTION CIRCUIT BREAKERS

    A. Each molded case circuit breaker microprocessor-based tripping system shall consist of three

    (3) current sensors, a trip unit and a flux-transfer shunt trip. The trip unit shall use

    11Note to Spec. Writer Optional

    12 Note to Spec. Writer Select one

    13 Note to Spec. Writer Optional

  • 7/27/2019 Gen Set- Config- Mon

    24/49

    microprocessor-based technology to provide the adjustable time-current protection functions.

    True RMS sensing circuit protection shall be achieved by analyzing the secondary current

    signals received from the circuit breaker current sensors, and initiating trip signals to the

    circuit breaker trip actuators when predetermined trip levels and time-delay settings are

    reached.

    B. An adjustable trip setting dial mounted on the front of the trip unit, or interchangeable ratingsplugs shall establish the continuous trip ratings of each circuit breaker. Rating plugs shall be

    fixed or adjustable as indicated. Rating plugs shall be interlocked so they are not

    interchangeable between frames, and interlocked such that a breaker cannot be closed and

    latched with the rating plug removed.

    C. System coordination shall be provided by the following microprocessor-based time-current

    curve shaping adjustments:

    1. Adjustable long-time setting (set by adjusting the trip setting dial or rating plug)

    2. Adjustable short-time setting and delay with selective curve shaping

    3. Adjustable instantaneous setting

    4. Adjustable ground fault setting and delay.D. The microprocessor-based trip unit shall have both powered and unpowered thermal memory

    to provide protection against cumulative overheating should a number of overload conditions

    occur in quick succession

    E. When the adjustable instantaneous setting is omitted, the trip unit shall be provided with an

    instantaneous override.

    F. Where internal ground fault protection is specified, adjustable settings shall not exceed 1200

    amperes. Provide neutral ground fault sensor for four-wire loads.

    G. Breakers shall have built-in test points for testing the long-time delay, instantaneous, and

    ground fault functions of the breaker by means of a test set. 14[Provide one test set capable

    of testing all breakers 250-ampere frame and above].

    2.10 ACCESSORIES

    A. Provide shunt trips, bell alarms and auxiliary switches as shown on the contract drawings.

    B. Provide a 15 [traveling type circuit breaker lifter, rail-mounted on top of switchgear] [floor

    running portable circuit breaker transfer truck with manual lifting mechanism].

    2.11 MISCELLANEOUS DEVICES

    A. Key interlocks shall be provided as indicated on the drawings.

    B. Control power transformers with primary and secondary protection shall be provided, as

    indicated on the drawings, or as required for proper operation of the equipment. [Controlpower transformers shall have adequate capacity to supply power to the transformer cooling

    fans.]

    C. Each section of the switchboard shall be provided with a space heater [thermostatically

    controlled]. Power for the space heaters shall be obtained [from a control power transformer

    14 Note to Spec. Writer Optional

    15 Note to Spec. Writer Select one

  • 7/27/2019 Gen Set- Config- Mon

    25/49

    within the switchboard] [from a source as indicated on the drawings]. Supply voltage shall be

    [120] [240] volts AC.

    2.12 ENCLOSURES

    A. NEMA 1 Enclosure

    B. Outdoor Walk-in Enclosure

    1. Switchgear shall be enclosed in an outdoor walk-in NEMA 3R enclosure conforming to all

    applicable requirements of UL and designed to withstand wind velocities of [110] [125]

    mph. The enclosure shall have a roof sloping toward the rear. Outer sections shall be the

    same widths as indoor structures except the end sections of a walk-in enclosure shall be

    wider than the inner sections to permit opening the inner door. Each end of the outdoor

    structure shall have an end trim. Front aisle depth for walk-in structures shall be 42

    inches, minimum.

    2. The enclosure shall be provided with rear hinged padlockable doors with wind stops for

    each section. Aisle doors shall be supplied with provisions for padlocking. A steel floor

    shall be provided in walk-in aisle space. [Steel floor plates shall be provided in the rear

    cable compartment.] An anti-skid floor strip shall be provided in the aisle. Ventilatingopenings shall be provided complete with replaceable fiberglass air filters which are

    removable from the exterior of the enclosure. Provide necessary space heaters

    thermostatically controlled for breaker, bus and cable compartments of adequate wattage

    to prevent the accumulation of moisture within the compartments.

    3. Provide panic door hardware on aisle doors at each end of the line-up. External

    padlocking of the aisle doors shall not prevent operation of the panic hardware from the

    interior of the enclosure. The construction of the enclosure shall be modular so future

    sections can be added without affecting NEMA 3R integrity. Provide interior aisle

    fluorescent lights, 3-way switches and GFI protected receptacles.

    4. The enclosure shall be provided with undercoating applied to all members in contact with

    the foundation surface to retard corrosion.

    5. Power for the space heaters, lights and receptacles shall be obtained from a 16[control

    power transformer within the switchgear] [source as indicated on the drawings]. Supply

    voltage shall be 120 volts AC.

    6. An overhead circuit breaker lifter shall be provided in the aisle of the enclosure.

    7. Each shipping section shall be shipped completely assembled.

    C. Outdoor Non-Walk-in Enclosure

    1. Switchgear shall be enclosed in an outdoor non-walk-in NEMA 3R enclosure conforming

    to all applicable requirements of UL and designed to withstand wind velocities of [110]

    [125] mph. The enclosure shall have a roof sloping toward the rear. Outer sections shall

    be the same widths as indoor structures except the end sections of a non-walk-inenclosure shall be wider than the inner sections to permit opening the inner door. Each

    end of the outdoor structure shall have an end trim.

    2. The enclosure shall be provided with front and rear hinged padlockable doors with wind

    stops for each section. Aisle doors shall be supplied with provisions for padlocking.

    16 Note to Spec. Writer Optional

    Note to Spec. Writer Select one

  • 7/27/2019 Gen Set- Config- Mon

    26/49

    [Steel floor shall be provided in the rear cable compartment.] Ventilating openings shall

    be provided complete with replaceable fiberglass air filters which are removable from the

    exterior of the enclosure. Provide necessary space heaters thermostatically controlled for

    breaker, bus and cable compartments of adequate wattage to prevent the accumulation

    of moisture within the compartments.

    3. The construction of the enclosure shall be modular so future sections can be addedwithout affecting NEMA 3R integrity. Provide interior fluorescent lights, switches and GFI

    protected receptacles.

    4. The enclosure shall be provided with undercoating applied to all members in contact with

    the foundation surface to retard corrosion.

    5. Power for the space heaters, lights and receptacles shall be obtained from a [control

    power transformer within the switchgear] [source as indicated on the drawings]. Supply

    voltage shall be 120 volts AC.

    6. A portable overhead circuit breaker lifter shall be provided to assist in removal of the

    circuit breakers from the enclosure.

    7. Each shipping section shall be shipped completely assembled.

    2.13 NAMEPLATES

    A. Engraved nameplates, mounted on the face of the assembly, shall be furnished for all mainand feeder circuits as indicated on the drawings. Nameplates shall be laminated plastic, black

    characters on white background. Characters shall be 3/16-inch high, minimum. Nameplates

    shall give item designation and circuit number as well as frame ampere size and appropriate

    trip rating.

    B. Furnish master nameplate giving switchboard designation, voltage ampere rating, short-circuit rating, manufacturers name, general order number, and item number.

    C. Control components mounted within the assembly, such as fuse blocks, relays, pushbuttons,

    switches, etc., shall be suitably marked for identification corresponding to appropriatedesignations on manufacturers wiring diagrams.

    2.14 FINISH

    A. All exterior and interior steel surfaces of the switchboard shall be properly cleaned and

    provided with a rust-inhibiting phosphatized coating. Color and finish of the switchboard shall

    be ANSI 61 light gray.

    2.15 17TRANSIENT VOLTAGE SURGE SUPPRESSION

    A. Provide transient voltage surge suppression as specified in Section 16671.

    2.16 EMERGENCY POWER SYSTEM (EPS) AUTOMATION & CONTROLS

    A. The automation and control system shall facilitate overall EPS operation including automatic

    standby operation, monitoring and control of the generator sets including start/stop,

    alarm/fault monitoring, synchronizing, generator kW load sharing, generator kVAR load

    sharing, generator loading/unloading, load shed/add, and protective relaying.

    17 Note to Spec. Writer Optional

  • 7/27/2019 Gen Set- Config- Mon

    27/49

    B. The EPS Automation and Controls shall utilize true redundant, distributed processing

    technology to maximize system reliability and fault tolerance. The distributed processing

    system shall include separate processors for each power source, and a separate processor

    dedicated to touchscreen Human/Machine Interface (HMI) operation.

    C. The EPS Automation and Controls shall be by the same manufacturer as the switchgear and

    generator sets. It shall be furnished with the generator sets by the Emergency Power SystemSupplier as a total coordinated and integrated system.

    *Note to Spec. Writer:Choose one of the HMI Options below, depending on usage of PowerLynx 1000,PowerLynx 2000, and PowerLynx 3000 product

    2.17 HMI HUMAN/MACHINE INTERFACE [PowerLynx 1000 HMI]

    A. EPS Automation interface shall be via a touchscreen with the following characteristics:

    1. Monochrome display capable of displaying both text and graphics.

    a. 6 diagonal for EPSs with one (1) Generator Set.

    b. 10 diagonal for EPSs with two (2) or more Generator Sets.

    2. Resistive touchscreen interface.

    a. The display shall support a minimum resolution of 320x240 pixels in 6 diagonal size,

    black and white.

    b. The display shall support a minimum resolution of 640x480 pixels in 10 diagonal

    size, black and white.

    3. Integral Alarm and Event Recording.

    -18OR-

    2.17 HMI HUMAN/MACHINE INTERFACE [POWERLYNX 2000 HMI]

    A. EPS Automation interface shall be via a touchscreen with the following characteristics:

    1. Color, 12 (diagonal) TFT LCD display capable of displaying both text and graphics.

    a. Resistive touchscreen interface.

    b. The display shall support a minimum resolution of 800x600 pixels, 256 displayable

    colors.

    2. Integral Alarm and Event Recording.

    -19OR-

    2.17 HMI HUMAN/MACHINE INTERFACE [POWERLYNX 3000 HMI]

    A. EPS system interface shall be via a touchscreen with the following characteristics:

    18 Note to Spec. Writer Select one

    19 Note to Spec. Writer Select one

  • 7/27/2019 Gen Set- Config- Mon

    28/49

    1. Color, 15 inch (diagonal) TFT LCD industrial display capable of displaying both text and

    graphics.

    2. The touch screen shall be clear glass, with light transmission of 95% or better, furnished

    with a Surface Acoustic Wave touch interface.

    3. The display shall support a minimum resolution of 1024 x 768 pixels, 16 million

    displayable colors, 24~60kHZ horizontal scan rate, 56-75HZ refresh rate.

    4. An EPS Touch Screen Processor shall be provided and shall provide the following

    additional features:

    a. System Report Generation

    1. The EPS Automation shall be capable of displaying and printing the following

    reports:

    i. System Settings Report

    ii. Generator Settings Report

    iii. Plant Test Report including all current operational parameters

    iv. [NFPA compliant JCAHO report]

    v. Alarm Summary Reportb. 20Provide a printer for local printing of system reports.

    c. Integral Alarm and Event Recording

    d. Integral Short Term Trending

    e. alarm Log shall be exportable to floppy disk drive.

    f. The EPS Touchscreen Processor shall operate with the following minimum

    characteristics:

    1. Minimum environmental requirements: temperature 0-55 deg. C, Protection

    Class IP20, Shock resistant up to 5Gs.

    2. Industrial Processor shall have 24 Vdc power supply fed from best source

    system.

    2.18 HMI SCREEN LISTING

    A. The EPS Automation shall provide the following screens. The screens shall provide all of theinformation, metering, control, annunciations settings and indications listed below:

    1. Main Menu Screen with a complete listing of major screens.

    2. System Overview Screen with a dynamic graphic display of the electrical one line.

    3. System Control Screen

    4. System Metering Screen with graphical presentation of all functions.

    5. System Settings Screen.6. Generator Control Screen for each generator

    7. Generator Metering Screen for each generator with graphical presentation of all functions

    specified.

    8. Generator Settings Screen.

    9. Generator Demand Priority Control and Status Screen.

    20 Note to Spec. Writer Optional

  • 7/27/2019 Gen Set- Config- Mon

    29/49

  • 7/27/2019 Gen Set- Config- Mon

    30/49

    Breakers. The System shall include all Processors, HMI (Human / Machine Interface)

    Touchscreens, Power Transducers, Supervisory Network and all ancillary control equipment

    necessary to automatically execute the specified Functional Sequence of Operations.

    B. The EPS Automation shall be provided with an HMI consisting of a Touchscreen display.

    1. The HMI shall provide all metering, status, monitoring, and control information to the

    operator.

    2. The HMI shall serve only as an Operator Interface. The EPS must continue to function

    normally with a complete HMI failure.

    C. The EPS Automation and Controls shall be designed to eliminate single points of failure.

    1. For redundancy, multiple processors shall be utilized.

    2. At a minimum, the EPS Controls shall utilize a separate automation processor for each

    generator power source, each utility power source, and each HMI.

    3. Control systems utilizing a single processor are not acceptable.

    D. For redundancy, all Master Control automation functions shall be capable of being executed

    from any of multiple distributed processors. If the automation processor executing Master

    Control automation functions should fail, the next available automation processor shall

    automatically assume control of all Master Control automation functions shall be equal to the

    number of generators in the system. The redundant automation processors shall each

    consist of a fully redundant power supply and CPU. Transfer of Master Control functions to a

    redundant processor shall be bumpless. The Master Control automation functions shall

    include:

    1. Automatic start of the generator plant when a run request is received

    2. First-up and dead-bus control logic

    3. Automatic synchronizing and paralleling of the generator plant

    4. Automatic generator load and VAR sharing controls5. Automatic generator Demand Priority control logic

    6. Automatic Load Shed / Add control logic

    E. An I/O rack with I/O cards or a distributed I/O block shall be provided for all required Master

    Control I/O including Load Shed relay outputs, annunciation inputs and outputs, etc. [A

    second (redundant) Master Control I/O rack with I/O cards (or a distributed I/O block) shall be

    provided with redundant I/O points for all Master Control I/O requirements.]

    F. A separate Load Shed distributed I/O block shall be provided for each group of up to (7)

    electrically operated distribution circuit breakers (as indicated on the drawings) to control the

    opening and closing of distribution circuit breakers when signaled by the Master Control

    Automatic Load Shed Control Logic and to monitor the open and closed status of distributioncircuit breakers. 22[A second (redundant) Load Shed distributed I/O block shall be provided

    for each group of up to (7) distribution circuit breakers.]

    G. Each Utility Circuit Breaker shall be provided with a separate primary automation processor

    and a redundant automation processor. The redundant automation processor shall consist of

    a fully redundant power supply, CPU and I/O point hardware. Failure of the primary utility

    automation processor shall result in a bumpless transfer to the redundant utility automation

    22Note to Spec. Writer Optional

  • 7/27/2019 Gen Set- Config- Mon

    31/49

  • 7/27/2019 Gen Set- Config- Mon

    32/49

  • 7/27/2019 Gen Set- Config- Mon

    33/49

  • 7/27/2019 Gen Set- Config- Mon

    34/49

    11. Total Engine Hours

    12. Unfiltered Oil Pressure

    13. Coolant Pressure

    14. Fuel Temperature

    15. Air/Fuel Ratio

    16. Inlet Air Pressure

    17. Inlet Air Temperature

    18. Inlet Air Flow

    19. Individual Cylinder Ignition Timing

    20. Individual Cylinder Temperature (where available)

    C. The following metering shall be provided for each distribution breaker:

    1. Voltmeter with 4-position selector switch to select three phases of voltage.

    2. Ammeter with 4-position selector switch.

    3. Kilowatt meter4. Kilovar meter

    5. Frequency Meter

    6. Power Factor Meter

    D. Additional Metering

    1. Where indicated on the drawings, provide a separate customer metering compartment

    with front hinged door.

    2. Furnish and install current transformers for each meter. Current transformers shall be

    wired to shorting-type terminal blocks.

    3. Furnish and install24 [potential transformers including primary and secondary fuses with

    disconnecting means] [fused potential taps as the potential source] for metering as

    shown on the drawings.

    Note to Spec. Writer:See Section 16901 Microprocessor Based Metering for functional descriptions.

    2.22 PROTECTIVE RELAYS

    A. The switchboard manufacturer shall furnish and install, in the metal-enclosed switchboard, the

    quantity, type and rating of protection relays as indicated on the drawings and described

    hereafter in this specification.

    B. Protective Relaying shall be microprocessor, high reliability, as specified below.

    C. GENERATOR PROTECTIVE RELAYING

    1. As a minimum, the following protective functions shall be provided for each Generator:

    a. Under/Over Voltage (27/59) Relay, 3-phase, percent adjustable, percent reset, with

    time delay.

    b. Over/Under Frequency (81 O/U) Relay, single phase, percent adjustable, percent

    reset, with time delay.

    24Note to Spec. Writer Select one

  • 7/27/2019 Gen Set- Config- Mon

    35/49

    c. Reverse Power (32) Relay, 3-phase, percent adjustable with time delay.

    d. Loss of Field (Reverse VAR, 40) Relay, 3-phase, percent adjustable with time delay.

    e. Microprocessor Engine Governor Load Sharing and Soft Loading Control (65).

    f. Automatic Synchronizer (15/25), adjustable sync window and sync window dwell time

    g. Manual Paralleling Synch Check (25).

    h. Var/Power Factor Controller (90 PF).

    D. UTILITY PROTECTIVE RELAYING

    1. As a minimum, the following protective functions shall be provided for each Utility Point of

    Common Coupling (PCC):

    a. Under/Over Voltage (27/59) Relay, 3-phase, percent adjustable, percent reset, with

    time delay.

    b. Over/Under Frequency (81 O/U) Relay, single phase, percent adjustable, percentreset, with time delay.

    c. Phase Sequence/Phase Failure (47) Relay, 3-phase, percent adjustable, with timedelay

    d. Reverse Power (32) Relay, 3-phase, percent adjustable with time delay.e. Reverse Direction Overcurrent (32/51) Relay (Utility Grade), 3-phase, percent

    adjustable, with time delay.

    f. Utility Lock-out (86) Relay (Utility Grade), manual reset

    g. Utility Re-close Lock-out Switch with lockable cover.

    h. Manual Paralleling Synch Check Relay (25), Industrial Grade

    i. Automatic Synchronizer (15/25), adjustable sync window and sync window dwell time.

    j. Manual Paralleling Synch Check (25).

    -OR-

    1. Each Utility Circuit Breaker shall be provided with a [Multilin SR-750],[Schweitzer SEL 351S], [Basler BE1-951],drawout, utility grade, multi-functionprotective relay.

    E. TIE PROTECTIVE RELAYING (Where applicable)

    1. As a minimum, the following protective function shall be provided for each Distribution

    Circuit Breaker:

    a. Instantaneous/Time Overcurrent (50/51) Relay, 3-phase, percent adjustable, lutilizing

    ANSI trip curves.

    b. Lock-out (86) Relay (Utility Grade), manual reset.

    c. Two Manual Paralleling Synch Check Relay (25), Industrial Grade.

    --25OR-

    1. Each Tie Circuit Breaker shall be provided with a [Multilin MIF II], [Schweitzer SEL 551],

    [Basler BE1-851], [Siemens 7SJ602], utility grade, multi-function, protective relay.

    a. Lock-out (86) Relay (Utility Grade), manual reset.

    25Note to Spec. Writer Select one

  • 7/27/2019 Gen Set- Config- Mon

    36/49

    b. Two Manual Paralleling Synch Check Relay (25), Industrial Grade.

    B. DISTRIBUTION PROTECTIVE RELAYING

    1. As a minimum, the following protective function shall be provided for each Distribution

    Circuit Breaker.

    a. Instantaneous/Time Overcurrent (50/51) relay, 3-phase, percent adjustable, utilizingANSI trip curves.

    b. Lock-out (86) Relay (Utility Grade), manual reset.

    --OR-

    a. Each Distribution Circuit Breaker shall be provided with a [Multilin MIF II], [Schweitzer

    SEL 551], [Basler BE1-851], [Siemens 7SJ602], utility grade, multi-function, protective

    relay.

    b. Lock-out (86) Relay (Utility Grade), manual reset.

    2.23 EPS ANNUNCIATION SYSTEM

    A. The EPS shall be provided with Annunciators to monitor and display critical status, fault, and

    shutdown information. Two (2) distinct Annunciator types shall be provided:

    1. Generator Annunciator One (1) shall be provided for each generator.

    2. System Annunciator One (1) shall be provided for each system.

    B. Annunciation shall comply with NFPA 110 requirements and shall conform to Instrument Society

    of America (ISA) F3A standards. The Annunciation System shall be provided with five (5)

    distinct types of annunciation points:

    1. Status Points These annunciation points will show the status of critical system orgenerator set components. Status Annunciation points shall not sound the Annunciation

    System Horn. They will not require acknowledgement.

    2. Generator Pre-Alarm Points These annunciation points shall show fault conditions thatcould jeopardize the ability of the EPS to function properly without immediate attention.

    Generator Pre-Alarm Annunciation points shall sound the Annunciation System Horn.

    They will require acknowledgement. Generator Pre-Alarm Annunciation Points shall

    reset automatically as the alarm condition is cleared.

    3. Generator Shutdown Alarm Points - These annunciation points shall show faultconditions that have caused the shutdown of one (1) or more generator sets. Generator

    Shutdown Annunciation points shall sound the Annunciation System Horn. They shall

    require acknowledgement. Generator Shutdown Annunciation points shall cause the

    generator set to shutdown and the generator main to trip open. The generator main is

    then locked out until the cause of the shutdown is corrected, the Engine Control Switch

    is placed in Off/Reset, and then placed back in Auto or Manual operation.

    4. Utility Alarm Points These annunciation points will indicate Utility related faultconditions. Utility Annunciation points shall sound the Annunciation System Horn. They

    shall require acknowledgement.

    5. EPS Alarm Points These annunciation points will indicate system wide fault conditions.EPS Annunciation points shall sound the Annunciation System Horn. They will require

    acknowledgement.

  • 7/27/2019 Gen Set- Config- Mon

    37/49

    C. The Annunciation System shall be equipped with a fast pulse horn (rated 80-95 dbA at two

    feet), a Horn Silence Push-button and an Acknowledge Push-button. Any Generator Pre-

    Alarm, Generator Shutdown Alarm, or EPS Alarm shall cause the Alarm Horn to sound until

    the Horn Silence button is depressed. Any subsequent alarms shall re-sound the horn. The

    display shall operate such that any alarm point shall flash until acknowledged. One press of

    the Acknowledge button shall return alarm points to steady on except the first in alarm,

    which shall remain flashing. A second press of the Acknowledge button shall return the first

    in alarm point to steady on.

    D. The following Annunciator Points shall be furnished for each generator set:

    1. Status Annunciation Points

    a. Local Engine Control Switch Position

    b. EPS Engine Control Switch Position

    c. EPS Synchronization Selector Switch Position

    d. Emergency Mode

    e. Generator Circuit Breaker Open/Closed

    f. Engine Running/Stopped

    2. Pre-Alarm Annunciation Points

    a. High Coolant Temperature

    b. Low Oil Pressure

    c. Low Coolant Temperature

    d. Engine Battery Low Voltage

    e. Engine Battery High Voltage

    f. Battery Charger Failure

    g. Engine Low Fuel [Applies to Diesel only]

    h. Generator Failed to Synchronize

    i. Local Engine Control Switch not in Auto

    j. EPS Engine Control Switch not in Autok. EPS Synchronization Selector Switch not in Auto

    l. Ground Fault Alarm

    m. Communications Module Alarm

    n. Rupture Basin Alarm [Applies to Diesel only]

    o. Synchronizer block fault

    p. Low controller Battery

    3. Shutdown Alarm Points

    a. Engine Overcrank

    b. Engine Overspeed

    c. Engine Low Oil Pressured. Engine High Coolant Temp

    e. Engine Low Coolant Level

    f. Engine Remote Emergency Shutdown

    g. Generator Circuit Breaker Tripped

    h. Generator Loss of Field

    i. Generator Reverse Power

    j. Generator Undervoltage

  • 7/27/2019 Gen Set- Config- Mon

    38/49

    k. Generator Over voltage

    l. Generator Under frequency

    m. Generator Over frequency

    n. Emergency Stop

    o. Ground Fault

    p. Critical Low fuel shutdown [Applies to Diesel only]q. Hi Winding temperature Trip

    E. The following Annunciator Points shall be furnished for each Utility:

    1. Status Annunciation Points

    a.EPS Synchronization Selector Switch Position

    b.Emergency Mode

    c.Utility Close Lock-out Switch Position

    d.Utility Circuit Breaker Open/Closed

    2. Utility Alarm Points

    a.Utility Failure

    b.Utility Control not in Auto

    c.Utility Circuit Breaker Reverse Power

    d.Utility Fail to Synchronize

    e.Utility Circuit Breaker Failed to Close/Open

    f. Utility Circuit Breaker Tripped

    g.Utility Protective Relay Failure

    F. The following Annunciator Points shall be furnished for each EPS:

    1. Status Annunciation Points

    a. Engine Status (1 for each Engine)

    b. Engine Priority (1 for each Engine)

    c. Master Mode Selector Switch position

    d. EPS Test Switch Position

    e. Load Shed Enabled

    f. Load Shed Active

    g. Load Shed Override

    h. Gen Demand Priority Enabled

    i. Gen Demand Priority Active

    2. EPS Alarm Points

    a. System in Emergency Mode

    b. System not in Auto

    c. Load Shed Overrided. Generator Bus Underfrequency

    e. Master Shutdown

    f. Controller Fault

    g. Low Controller Battery

    h. System Battery Charger Fault

  • 7/27/2019 Gen Set- Config- Mon

    39/49

    2.24 EPS (CONTROL, SYNCHRONIZER, POWER TRANSDUCER AND PROTECTIVE SETTINGS.

    A. EPS Setting changes and adjustments shall be password protected and easily adjustable inselectable increments.

    1. System Settings

    2. Generator Settings3. Generator demand and Load Shed Settings

    4. Utility Settings

    2.25 FUNCTIONAL SEQUENCE OF OPERATIONS

    A. The EPS Automation shall be provided with the following Modes of Operation:

    1. Automatic/Standby Mode

    a. The utility main breaker is closed serving utility power to the generator/load bus.

    b. The generator main breakers are open.

    c. The automation is standing by to act in response to a utility failure.

    2. Emergency Modea. Utility Failure

    1. Utility protective relaying senses utility voltage or frequency out of tolerance.

    2. The utility main breaker is opened.

    3. A run request is sent to the generator plant.

    4. The first generator up to voltage and frequency is closed to the bus.

    5. 26[With Generator Bus Tie Breaker] The generator bus tie breaker is closed.

    6. The remaining generators are synchronized and paralleled to the bus as they

    come up to voltage and frequency.

    7. The system is now in Emergency Mode.

    b. Utility Restoration and Exit from Emergency Mode

    1. Utility protective relaying senses utility voltage and frequency within tolerance.

    2. Following an adjustable time delay (which can be abbreviated by the operator) to

    assure that the utility power source is stable, the generator plant is passively

    synchronized and paralleled to the utility source by closing the utility main breaker.

    3. The generator plant is soft ramp unloaded until the utility source is nominally

    serving the entire system load.

    4. The generator breakers are opened.

    5. The generators are allowed to run for their programmed cool down period.

    6. The system is now back in Automatic/Standby Mode.

    3. Transfer to Emergency Mode

    a. Entry1. The operator places the System Mode Selector Switch into the Closed Xfer to

    Emergency position.

    2. A run request is sent to the generator plant.

    3. The first generator up to voltage and frequency is closed to the bus at no load.

    26 Note to Spec. Writer Optional

  • 7/27/2019 Gen Set- Config- Mon

    40/49

    4. The remaining generators are synchronized and paralleled to the bus at no load as

    they come up to voltage and frequency.

    5. When all generators are on the bus they are soft ramp loaded until the generator

    plant is serving nominally the entire load on the bus and the utility main breaker is

    opened.

    --27OR-

    5. [With Generator Bus Tie Breaker] When all generators are on the bus, they are

    paralleled across the generator bus tie breaker. They are then soft ramp loaded

    until the generator plant is serving nominally all of the load on the bus and the utility

    main is opened.

    6. The system is now running in Emergency Mode.

    b. Exit from Emergency Mode

    1. The operator removes the System Mode Selector Switch from Transfer to

    Emergency position and returns it to the Auto position.

    2. Following an adjustable time delay (which can be abbreviated by the operator), the

    generator plant is passively synchronized and paralleled to the utility source byclosing the utility main breaker.

    3. The generator plant is soft ramp unloaded until the utility source is nominally

    serving the entire system load.

    4. The generator breakers are opened.

    --OR-

    4. [With Generator Bus Tie Breaker] The generator bus tie breaker is opened and then

    all of generator breakers are opened.

    5. The generators are allowed to run for their programmed cool down period.

    6. The system is now back in Automatic/Standby Mode.

    4. Load Management Mode

    a. Entry

    1. Select one of the modes of operation:

    i. Import Limit - The user places the Import/Export toggle switch in the Importposition and places the Base Load/Utility Tracking toggle switch in the Utility

    Tracking position. The user sets the Utility Import Set point to the desired

    amount of kW that they want to import through the Utility Circuit Breaker

    during Load Management Mode.

    ii. Export Limit - The user places the Import/Export toggle switch in the Export

    position and places the Base Load/Utility Tracking toggle switch in the Utility

    Tracking position. The user sets the Utility Export Set point to the desired

    amount of kW that they want to export through the Utility Circuit Breaker

    during Load Management Mode.

    iii. Base Load Import - The user places the Import/Export toggle switch in the

    Import position and places the Base Load/Utility Tracking toggle switch in the

    Base Load position. The user sets the Base Load Set point to the desired

    amount of kW that they want the generator plant to assume during Load

    Management Mode. The controls will not allow the generator plant to export

    27Note to Spec. Writer Select one

  • 7/27/2019 Gen Set- Config- Mon

    41/49

  • 7/27/2019 Gen Set- Config- Mon

    42/49

    1. The Utility Fail Test Switch is placed in the ON position.

    2. Voltage sensing at the utility protective relay is opened, which simulates a loss of

    utility.

    3. The system enters into Emergency Mode as described in the Emergency Mode

    sequence above.

    b. Exit from Utility Fail Test Mode1. The Utility Fail Test Switch is placed in the OFF position.

    2. Voltage sensing at the utility protective relay is restored, which simulates the

    return of utility power.

    3. The system exits from Emergency Mode as described in the Emergency Mode

    sequence above.

    B. When the Generator Sets are carrying the facility load, the EPS Automation shall support two

    (2) sub-modes: Load Shed/Load Add, and Generator Demand Priority.

    1. Load Shed Control

    a. The System Controls shall include a Load Shed Control function to control the loadsserved by the generator plant.

    b. The Load Shed Control shall have one Essential Load Shed Priority Level for eachgenerator in the system plus one Non-Essential Load Shed Priority Level (which is

    always shed in the Emergency Mode of operation).

    c. The Load Shed Control shall control each of the distribution circuit breakers that areshown on the drawings. Distribution circuit breakers to be controlled shall be

    electrically operated. Each electrically operated distribution circuit breaker shall be

    field selectable to be assigned to any of the available Load Shed Priority Levels.

    1. Provide the following controls for each Essential Load Shed Priority Level

    i. Shed Delay Timer, adjustable from 0 to 1024 seconds

    ii. Add Delay Timer, adjustable from 0 to 1024 seconds

    iii. Load Shed Override Selector (shed/auto//add)iv. Status indicators to show whether the Priority Level is Added or Shed

    2. Provide the following controls for each Non-Essential Load Shed Priority

    i. Load Shed Override Selector (shed/auto//add)

    ii. Status indicators to show whether the Priority Level is Added or Shed

    3. Additionally, the Load Shed Controls shall have:

    i. Load Shed Control Switch (On/Off)

    ii. User-settable Load Shed % (as a function of on-line generator capacity)

    iii. User-settable Load Shed Time Delay

    iv. User-settable Load Add % (as a function of on-line generator capacity)

    v. User-settable Load Add Time Delay

    vi. User-settable Bus Under frequency Set point

    vii. User-settable Bus Under frequency time delay

    viii. Bus Under frequency Reset Pushbutton

    ix. Bus Under frequency indicator

    4. Conditional Load Shed: Upon entrance into Emergency Mode of operation, the

    Load Shed Control shall shed all Essential and Non-Essential loads. As

    generators come to the bus, Essential Priority Level loads shall be added

  • 7/27/2019 Gen Set- Config- Mon

    43/49

  • 7/27/2019 Gen Set- Config- Mon

    44/49

    2.26 SPARE PARTS

    A. The Emergency Power System Supplier shall have factory trained technicians that maintain a

    stock of spare parts and programming tools.

    B. Provide a complete listing of available spares parts with O&M Documents.

    C.

    28

    At a minimum, provide the following spare parts for the Generator Control Switchboard:1. One of each type of automation processor (including CPU, Power Supply, and I/O)

    2. One of each component required for synchronization, load control, and VAR control

    3. One of each control relay

    4. (10) of each control fuse

    5. One of each power transducer

    *Note to Spec. Writer:The following options apply to PowerLynx 3000 products only.

    2.27 LONG TERM HISTORICAL TRENDING

    A. Long Term Historical Trending shall log EPS historical data on the system hard drive. This

    data shall be displayed in a strip chart format. Historical data file format shall be dbf to

    facilitate manipulation of these files in other software programs. Long Term Historical

    Trending shall record and display the following for each Generator set:

    1. Battery Volts

    2. Coolant Temperature

    3. Coolant Level Status

    4. Engine RPM

    5. Fuel Pressure

    6. Fuel Usage Rate

    7. Engine Hour Meter8. kW

    9. kVAR

    8. Average 3 phase Current

    9. Average 3 phase Voltage

    10. Local Engine Control Switch Position

    11. Local E-stop Position

    12.Alarm Status

    13. Pre-Alarm Status

    *Note to Spec. Writer:

    The following Trending information is available when using a Caterpillar, B series orhigher, Diesel engine, with ADEM II or III.

    16. Total fuel Used

    17. Fuel Filter Differential Pressure

    18. Oil Pressure

    19. Oil Filter Differential Pressure

    28 Note to Spec. Writer Optional

  • 7/27/2019 Gen Set- Config- Mon

    45/49

    20. Right Air Filter Differential Pressure

    21. Right Turbo Pressure

    22. Left Turbo Pressure

    23. Boost Pressure

    24. Percent Engine Load

    *Note to Spec. Writer:The following Trending information is available when using a Caterpillar, B series orhigher, Natural Gas engine, with ADEM II or III.

    17. Oil Pressure Differential

    18. Gas Flow

    19. Total Engine Hours

    20. Unfiltered Oil Pressure

    21. Coolant Pressure

    22. Fuel Temperature

    23. Air/Fuel Ratio

    24. Inlet Air Pressure25. Inlet Air Temperature

    26. Inlet Air Flow

    27. Individual Cylinder Temperature (where available)

    2.28 29REMOTE NOTIFICATION

    A. The system shall be optionally capable of providing several types of remote notification.

    Notification will be triggered by user specified events and/or alarms. Means of notification

    shall include:

    1. Voice notification via cell phone or land lines.

    2. Fax notification

    3. Pager notification

    4. Email notification

    2.29 30REMOTE ANNUNCIATION

    A. An NFPA compliant remote annunciator shall be provided by the EPSS.

    2.30 EPS SITE MONITORING

    A. The EPS shall be provided with web-based site monitoring services. This service shall be

    capable of monitoring and controlling multiple EPS sites, with no geographical limitation.

    Web-based EPS access shall employ high security to insure against unauthorized EPS

    access.

    B. This monitoring service shall be Caterpillar PointGuard or equal.

    C. The site monitoring service shall support the following means of communications:

    1. Cellular Telephone

    29Note to Spec. Writer Optional

    30 Note to Spec. Writer Optional

  • 7/27/2019 Gen Set- Config- Mon

    46/49

    2. Landline Telephone

    3. Satellite Communications

    4. Virtual Private Network

    5. Cable Modem

    6. Frame Relay

    D. Available services for the EPS shall include:

    1. Continuous monitoring for alarms

    2. Automated alarm notification

    3. Data gathering and management

    4. Report Generation

    5. Site Control

    *Note to Spec. Writer:The following options apply to all PowerLynx products.

    2.31 REMOTE POWER MONITORING SYSTEM

    A. A PC based Remote Power31[Monitoring][Monitoring and Control] System shall be provided

    to monitor breaker status, alarms, metering and other operating parameters. All [control

    functions, displays metering][displays, metering] and other information described previously in

    these specifications shall be available to the operator of the Remote System.

    B. The Remote System shall be designed such that its operation will not in any way impede the

    selected