Engine Make & Model: Perkins 1306C-E87TAG6
Circuit Breaker Type: 3 Pole MCCB
Fuel Tank Capacity: litres (US gal) 350 (92.5)
Frequency: 50 Hz 60 Hz
Fuel Consumption, Prime: l/hr (US gal/hr) 58.9 (15.6) -
Engine Speed: RPM 1500 -
Alternator Model: LL5014J
Base Frame Type: Heavy Duty Fabricated Steel
Fuel Consumption, Standby : l/hr (US gal/hr) 63.3 (16.7) -
Output Ratings
Generating Set Model Standby*
275.0 kVA
220.0 kW
-
-
Prime*
250.0 kVA
200.0 kW
-
-
380-415V,50Hz
* Refer to ratings definitions on page 4. Ratings at power factor.0.8
GEH275-2
Technical Data
Diesel Generator SetExclusively from your Caterpillar® dealer
6.2 (25.0)
424.2 (14980)
Air Filter Type:
Combustion Air Flow:
m³/min (cfm) -Standby:
-Prime:
Max. Combustion Air Intake
Restriction: kPa (in H2O)
Paper Element
-16.4 (579)
-16.4 (579)
-
Radiator Cooling Air Flow:
m³/min (cfm)
External Restriction to
Cooling Air Flow: Pa (in H2O) -125 (0.5)
-
Air System 60 Hz50 Hz
Moment of Inertia: kg m² (lb. in²) 1.54 (5266)
Governing Type:
Governing Class:
Compression Ratio:Displacement: l (cu.in)
Engine Electrical System:
-Voltage/Ground:
-Battery Charger Amps:
Weight: kg (lb) - Dry:
- Wet:
Cooling Method: Water
Electronic
ISO 8528 G2
16.9:1
8.7 (530.9)
Bore/Stroke: mm (in) 116.6 (4.6)/135.9 (5.4)
24/Negative
45671 (1479)
698 (1539)
Induction:
Manufacturer: Perkins
Model: 1306C-E87TAG6
No. of Cylinders/Alignment: 6 / In Line
Cycle: 4 Stroke
Turbocharged Air To Air Charge Cooled
-20.8Regenerative Power: kW-Prime: 2099.0 (304.5) -
-2306.0 (334.4)-Standby:BMEP: kPa (psi)
-228.5 (306.0) -Prime:
-Standby:Gross Engine Power: kW (hp)
250.9 (336.0) -
-1500Engine Speed: RPM
Oil Pan l (US gal):
Total Oil Capacity l (US gal):
Oil Filter Type:
Oil Type:
Cooling Method:
Spin-On, Full Flow
26.4 (7.0)22.7 (6.0)
API-CH-4
Water
Prime
50 Hz 31.1 (8.2)60 Hz ----
46.1 (12.2)58.9 (15.6)63.3 (16.7)
(based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)
Recommended Fuel:
Fuel Consumption: l/hr (US gal/hr)Class A2 Diesel
110%Load
75%Load
50%Load
100%Load
Fuel Filter Type: Replaceable Element
Standby
50 Hz 34.3 (9.1)50.2 (13.3)63.3 (16.7)
60 Hz ---
Level: dB
Silencer System: kPa (in Hg)
Pressure Drop Across
Silencer Noise Reduction
Silencer Type:
Pressure: kPa (in. Hg)
Max. Allowable Back
-Prime:
m³/min (cfm) -Standby:
Exhaust Gas Flow:
-Prime:
m³/min (cfm) -Standby:
Exhaust Gas Temperature: °C (°F)
SD100 (0)Silencer Noise Reduction
-8.70 (2.569)
-12
-10.7 (3.2)
-44.5 (1572)
-44.5 (1572)
-528 (982)
-500 (932)
Level 1Cooling System Capacity: l (US gal)
Water Pump Type:
Heat Rejected to Water &
Lube Oil: kW (Btu/min)
-Standby:
-Prime:
-Prime:
kW (Btu/min) -Standby:Heat Radiation to Room:
Radiator Fan Load: kW (hp)
110.0 (6256)
-
-45.3 (12.0)Centrifugal
-
-103.0 (5858)
-44.0 (2502)
-40.0 (2275)
10.3 (13.8)
Cooling system designed to operate in ambient conditions up to 50°C (122°F). Contact your local Olympian dealer for power ratings at specific site conditions.
Cooling System 60 Hz50 Hz
Performance 60 Hz50 Hz
Fuel System
Exhaust System
Lubrication systemPhysical Data
Engine Techncial Data
Consult your Olympian representative for more information
60 Hz50 Hz
Data Item50 Hz 60 Hz
Motor Starting Capability* kVA 623 585 536 686 - - - - -
Reactances: Per Unit
Xd
X'd
X''d
2.446 2.633 2.917 2.176 - - - - -
0.112 0.120 0.133 0.100 - - - - -
0.067 0.072 0.080 0.059 - - - - -
Reactances shown are applicable to standby ratings.* Based on 30% voltage dip. Improved motor starting capability is available with optional Permanent Magnet generator or AREP excitation.** With optional Permanent Magnet generator or AREP excitation.
415/240V 400/230V230/115V200/115V
380/220V220/110V
220/127V
Short Circuit Capacity** % 300 300 300 300 300 300 300 300 300
Manufacturer:
Model:
No. of Bearings:
Insulation Class:
Winding Pitch - Code:
Wires:
Ingress Protection Rating:
Excitation System:
AVR Model:
OLYMPIAN
LL5014J
1
H
2/3 - 6
12
IP23
SHUNT
R448
Overspeed: RPM
Voltage Regulation (steady state) (%):
Wave Form NEMA = TIF:
Wave Form IEC = THF:
Total Harmonic Content LL/LN:
Radio Interference:
Radiant Heat: kW (Btu/min)
-50 Hz:
-60 Hz:
Supression is in line with European Standard EN61000-6
-
16.3 (927)
4.0%
2.0%
50
+/- 0.5
2250
Physical Data Operating Data
Alternator Performance Data
Alternator Technical Data
Consult your Olympian representative for more information
220.0275.0
220.0275.0
220.0275.0
220.0275.0
220.0275.0
220.0275.0
220.0275.0
kWkVA
200.0
200.0
200.0
200.0250.0
250.0
250.0
250.0
200.0250.0
250.0 200.0
kWkVA
200/115V
220/110V
220/127V
230/115V
380/220V
415/240V
400/230V
200.0250.0
Technical Data Phase Ratings and Performance at 50 Hz, RPM15003
Voltage Prime Standby
Standby RatingThese ratings are applicable for supplying continuous electricalpower (at variable load) in the event of a utility power failure. Nooverload is permitted on these ratings. The alternator on this modelis peak continuous rated (as de�ned in ISO 8528-3).
Prime RatingThese ratings are applicable for supplying continuous electricalpower (at variable load) in lieu of commercially purchased power.There is no limitation to the annual hours of operation and thismodel can supply 10% overload power for 1 hour in 12 hours.
Standard Reference ConditionsNote: Standard reference conditions 27°C (80°F) air Inlet Temp,152.4m (500ft) A.S.L. 60% relative humidity. Fuel consumptiondata at full laod with diesel fuel with spedci�c gravity of 0.85 andconforming to BS2869: 1998, Class A2.
Definitions
kWkVAkWkVA
Phase Ratings and Performance at 60 Hz, RPM15003
Voltage Prime Standby
Weights & Dimensions
Weights: kg (lb)
Net (+ lube oil)
Wet (+ lube oil & coolant)
Fuel, lube oil & coolant 2548 (5617)
2252 (4965)
2215 (4883)
Dimensions: mm (in)
Height
Width
Length
1718 (67.6)
1003 (39.5)
2960 (116.5)
DocumentsOperation and maintenance manuals provided.Wiring diagrams included.
Quality StandardsBS4999, BS5000, BSEN60034, BSEN61000, IEC60034.
WarrantyAll equipment carried full manufacturer's warranty.
General Data
Market: International
Information contained in this publication may be considered con�dential.Discretion is recommended when distributing.
Materials and speci�cations are subject to change without notice.CAT, CATERPILLAR, their respective logos and ''Caterpillar Yellow'', as well as corporate and product
identity used herein, are trademarks of Caterpillar and may not be used without permission.
www.CAT-ElectricPower.com
© 2007 CaterpillarAll rights reserved.
Printed in U.S.A.
Note: General con�guration not to be usedfor installation. See general dimensiondrawings for detail.
-
LEHF7209-01