Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
IntesisBox® Modbus Server Mitsubishi Electric G-50A/GB-50A TCP/IP XML
User Manual Issue date: 05/2018
r19 eng
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
2 / 33
© Intesis Software S.L.U. All Rights Reserved.
Information in this document is subject to change without notice. The software described in
this document is furnished under a license agreement or nondisclosure agreement. The
software may be used only in accordance with the terms of those agreements. No part of
this publication may be reproduced, stored in a retrieval system or transmitted in any form
or any means electronic or mechanical, including photocopying and recording for any
purpose other than the purchaser’s personal use without the written permission of Intesis
Software S.L.U.
Intesis Software S.L.U. Milà i Fontanals, 1 bis 08700 Igualada Spain TRADEMARKS All trademarks and tradenames used in this document are acknowledged to be the copyright of their respective holders.
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
3 / 33
Gateway for integration of Mitsubishi Electric City Multi air conditioning systems into Modbus (RTU
and TCP) systems.
Two models are available for this gateway, with the following Order Codes:
• ME-AC-MBS-50. Model supporting up to 50 City Multi groups.
• ME-AC-MBS-100. Model supporting up to 100 City Multi groups.
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
4 / 33
INDEX
1. Description ......................................................................................................... 5 1.1 Introduction ................................................................................................. 5 1.2 Integration signals ........................................................................................ 6 1.3 Functionality ................................................................................................. 7 1.4 Capacity of IntesisBox ................................................................................... 8
2. Modbus interface of IntesisBox .............................................................................. 9 2.1 Functions supported ...................................................................................... 9 2.2 Modbus RTU ................................................................................................. 9 2.3 Modbus TCP .................................................................................................. 9 2.4 Address Map ................................................................................................. 9 2.5 Available signals ......................................................................................... 10
3. LinkBoxMB. Configuration & monitoring tool for IntesisBox Modbus Server series ...... 11 3.1 Introduction ............................................................................................... 11 3.2 Project definition ......................................................................................... 12 3.3 Connections configuration ............................................................................ 16 3.4 Signals list.................................................................................................. 19 3.5 Sending the configuration to IntesisBox ......................................................... 20 3.6 Signals viewer ............................................................................................ 21 3.7 System commands ...................................................................................... 22 3.8 Files .......................................................................................................... 23
4. Setup process and troubleshooting ...................................................................... 24 4.1 Pre-requisites ............................................................................................. 24 4.2 Setup procedure ......................................................................................... 24
5. Connections ...................................................................................................... 27 6. Functional characteristics ................................................................................... 28 7. Mechanical & Electrical characteristics .................................................................. 29 8. Dimensions ....................................................................................................... 30 9. Annexes ........................................................................................................... 31
9.1 Gateways Mitsubishi Electric G-50A and GB-50A ............................................. 31 9.2 Examples of Modbus addresses ..................................................................... 32
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
5 / 33
1. Description
1.1 Introduction
IntesisBox® Modbus Server - Mitsubishi Electric G50 is a communication gateway for
Mitsubishi Electric City Multi air conditioning systems to Modbus slave (RTU and TCP).
This gateway allows integrating the Mitsubishi Electric City Multi AC inside a
supervision/control/automation system through PLC, SCADA, and in general through any
device or system with Modbus mastering (TCP or RTU) interface.
This integration requires the Mitsubishi Electric City Multi AC system be equipped with the
Mitsubishi Electric G-50A, GB-50A, AG-150A or AE200A gateway. This gateway from
Mitsubishi Electric offers the signals of the City Multi AC system through XML protocol. Every
G50 (G-50A, GB-50A, AG-150A, AE200A) allows access to the signals of up to 50 City Multi
indoor units and 50 groups, no matter the number of outdoor units installed. In the G50,
the group is the control unit, every group can have from 1 to 16 associated indoor units.
This integration supervise and control groups, not indoor units, although if only one indoor
unit is associated to every group then you can supervise and control indoor units
individually.
This G50 gateway is supplied by Mitsubishi Electric. The difference between the G-50A and
GB-50A is that the first incorporates display and keyboard and the second one just blind
cover. The new AG-150A and AE200A is also compatible with IntesisBox (with or without
Expansion Controllers). At integration level, all of them allow the same functionality.
Contact your nearest Mitsubishi Electric distributor for more details about G-50A, GB-50A
AG-150A and AE200A. In this document we will refer to this three gateway models (G-
50A, GB-50A, AG-150A and AE200A, without Expansion Controllers) as just G50.
An AG-150 with 2 EC or an AE200 with one EC would work as 2 G50.
NOTE: Please, remember that Mitsubishi Electric AG-150A requires a
software license, PC-Monitoring license (SW-Mon), that has to be
purchased together with the AG-150A gateway. !
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
6 / 33
1.2 Integration signals
The following list shows the available signals to integrate per every group (of the 50
possible) of the G50:
Property Description / Status
Drive Start/Stop Read/Write: ON, OFF
Mode Operation Mode 0-COOL, 1-DRY, 2-FAN, 3-HEAT, 4-AUTO, 5-HEATRECOVERY, 6-LC_AUTO, 7-BYPASS, 8-AUTOHEAT, 9-AUTOCOOL
PWFY units have special working modes: COOLING, ANTIFREEZE, HEATINGECO, HEATING, HOTWATER
SetTemp Temperature Set Point (in steps of 0.5 °C)
In COOL or DRY: 19..30.0 ºC, in HEAT: 17..28.0 ºC, in AUTO: 19..28.0 ºC
PWFY units have special setpoint limits: All modes: 10 … 70.0 ºC
AirDirection Air output direction (Vane Position) Read/Write: HORIZONTAL, MID1, MID2, VERTICAL, SWING, AUTO
FanSpeed AC fan speed or LOSSNAY Read/Write: HIGH, MIDH, MIDL, LOW, AUTO
RemoCon Prohibition for General control from the local panel Read/Write: PROHIBIT, PERMIT
DriveItem Prohibition for ON/OFF control from the local panel Read/Write: CHK_ON, CHK_OFF
ModeItem Prohibition for Mode control from the local panel Read/Write: CHK_ON, CHK_OFF
SetTempItem Prohibition for Set Point control from the local panel Read/Write: CHK_ON, CHK_OFF
FilterItem Prohibition for Filter Reset control from the local panel Read/Write: CHK_ON, CHK_OFF
Ventilation Operational status for LOSSNAY or OA Read/Write: HIGH, LOW, OFF
FilterSignSts Status for Filter Dirty Read: ON, OFF Write: RESET
ErrorSignSts Error status Read: ON, OFF Write: RESET
InletTemp Ambient Temperature Read: 0.0 to 99.9
FilterSignRst Reset of the Filter Dirty indication Read: Allowed but it is nonsense Write: RESET
ErrorSignRst Communication error with G50 Virtual signal generated by IntesisBox® to indicate the status of the communication
with the G50.
CommErrorGroup Group communication error Virtual signal generated by IntesisBox® to indicate that the group is not configured into the G50.
Polling Active Polling active Virtual signal to indicate or set if the Group is active or not active during the polling process.
SetTemp1 Setpoint1 /COOL-DRY (when Dual Setpoint Cfg) 19..30.0 °C / 19..35.0 °C
SetTemp2 Setpoint2 /HEAT (when Dual Setpoint Cfg) 17..28.0 °C / 4.5..28.0 °C
SetTemp3 Setpoint3 /AUTO (when Dual Setpoint Cfg and separate Auto setpoint)
°C
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
7 / 33
AutoModeSWEx Auto Mode Setpoint Cfg 0-Disabled, 1-Auto with own setpoint (Setpoint3) 2-Auto uses HEAT/COOL Setpoints (Setpoint1/Setpoint2)
AlarmCode M-Net device’s AlarmCode 0..9999 (0 no Alarm)
For more information consult Mitsubishi Electric technical documentation supplied with the
G50.
1.3 Functionality
Every one of the mentioned signals is associated to a predefined fixed Modbus address, with
this, all the system is seen as a single Modbus slave unit with a fixed Modbus address map.
It can only be one Modbus Mode active simultaneously in IntesisBox®, Modbus RTU or
Modbus TCP.
IntesisBox® continuously polls (read) all the signals configured of the G50's and maintains
the updated values to be served in Modbus.
When a write is done from Modbus in a gateway's Modbus address (allowed to be written),
the corresponding order is sent to the City Multi signal associated.
In the continuous polling process of the G50, if there is no answer, it is indicated with a
virtual signal of communication error. The same way, there is a communication error virtual
signal per every City Multi group, which normally will be activated if this group is not
configured in the G50. Note that, although the City Multi indoor units are not physically
connected, the G50 responds as if they were.
The IP address and TCP port (will be always 80) of every G50 to connect to can be also
configured.
The signal's polling cadence (read) can also be configured.
IntesisBox® automatically detects the groups configured in every G50. Those groups not
found during the first poll are deactivated automatically in the polling process. This
behaviour can be disabled in IntesisBox®.
Master
Modbus RTU
G50
RS232/RS485 Ethernet
IntesisBox
LinkBoxMB Configuration
Software Only needed for configuration
G50
Master
Modbus TCP
RS232
LAN TCP/IP
Modbus TCP
XML
Modbus RTU
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
8 / 33
1.4 Capacity of IntesisBox
Element
Max. Notes
Num. of G50 2 Number of independent G50 interfaces
2 x G-50A / GB-50A
2 x AG150 (without Expansion Controllers)
1 x AG150 (with 2 Expansion Controllers)
1 x AE200 (with 1 Expansion Controller)
Number of City Multi groups:
(Number of G50s X 50)
100 Maximum number of groups
Number of variables per group
18 Modbus addresses
Number of variables per G50
901 Modbus addresses
There are 2 different models of IntesisBox® Modbus server - Mitsubishi Electric G50 with
different capacity every one of them. The table above shows the capacity for the top model
(with maximum capacity).
The 2 different models allow integrating respectively: 1 or 2 G50s.
And their order codes are:
• ME-AC-MBS-50. Model supporting up to 50 City Multi groups.
• ME-AC-MBS-100. Model supporting up to 100 City Multi groups.
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
9 / 33
2. Modbus interface of IntesisBox
2.1 Functions supported
This part is common for Modbus RTU and TCP.
Modbus functions 03 and 04 (read holding registers and read input registers) can be used to
read Modbus registers.
Modbus functions 06 and 16 (Single Multiple Holding Registers and Write Multiple Holding
Registers) can be used to write Modbus registers.
If poll records are used to read or write more than one register, it is necessary that the
range of addresses requested contains valid addresses, if not the corresponding Modbus
error code will be returned.
All the registers are of 2 bytes (although its possible values can only be 0..1) and its
content is expressed in MSB..LSB.
Modbus error codes are fully supported, they will be sent whenever a non valid Modbus
action or address is required.
2.2 Modbus RTU
Baud rate can be selected from 1200, 2400, 4800, 9600, 19200, 38400 and 56700 (Data
Bits: 8, parity: none, Stop Bits: 1).
Modbus slave number can be configured. Physical connection (RS232 or RS485) can also be
selected.
Only the lines RX, TX and GND of the RS232 connector are used (TX and RX for RS485).
2.3 Modbus TCP
The TCP port to use can be configured (by default 502 is used).
The IP address, subnet mask and default router address to use by IntesisBox® can be also
configured.
2.4 Address Map
The are 18 signals per every City Multi group plus one more signal per every G50. The
address map is based in a base address for every one of these signals. The Modbus address
for every point is obtained adding an offset (according to the number of groups and number
of G50s) to this base address.
ModBus Address = ( ( (G50 NUMBER – 1) X 50 ) + GROUP NUMBER ) X 100 + SIGNAL NUMBER
Where:
G50 NUMBER: 1..2
GROUP NUMBER: 1..50
SIGNAL NUMBER: 1..18
For the G50's communication error addresses, the following formula is applied:
Modbus Address = G50 NUMBER
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
10 / 33
2.5 Available signals
The following list shows the available signals per every G50's group (of the 50 possible):
SIGNAL #
Property RW Description / Possible Values
0 ErrorComG50 R Communication Error with G50
0-OK, 1-Comm.Error active
1 Drive RW Start/Stop
0-OFF, 1-ON
2 Mode RW Operation Mode 0-COOL, 1-DRY, 2-FAN, 3-HEAT, 4-AUTO, 5-HEATRECOVERY, 6-LC_AUTO, 7-BYPASS, 8-AUTOHEAT, 9-AUTOCOOL PWFY units have special working modes: 0-COOLING, 1-ANTIFREEZE, 2-HEATINGECO, 3-HEATING, 4-HOTWATER
3 SetTemp RW Temperature Set Point (in steps of 0.5°C)
In COOL or DRY:19..30.0 ºC, in HEAT: 17..28.0 ºC, in
AUTO:19..28.0 ºC
PWFY units have special setpoint limits:
All modes: 10 … 70.0 ºC
4 AirDirection RW Vane Position
0-HORIZONTAL, 1-MID1, 2-MID2, 3-VERTICAL, 4-SWING
5 FanSpeed RW Fan speed of the AC or LOSSNAY
0-LOW, 1-MIDL , 2-MIDH, 3-HIGH
6 RemoCon RW Prohibition for General control from the local panel
0-Deactivate Prohibitions, 1-Activate Prohibitions
7 DriveItem RW Prohibition for ON/OFF control from the local panel
0-Allowed , 1-Prohibited
8 ModeItem RW Prohibition for Mode control from the local panel
0-Allowed , 1-Prohibited
9 SetTempItem RW Prohibition for Set Point control from the local panel
0-Allowed , 1-Prohibited
10 FilterItem RW Prohibition for Filter Reset control from the local
panel
0-Allowed , 1-Prohibited
11 Ventilation RW Operational status for LOSSNAY or OA
0-OFF, 1-LOW, 2-HIGH
12 FilterSign R Status for Filter Dirty
0-OK, 1-Filter dirty
13 ErrorSign R Error status
0-OK, 1-Error
14 InletTemp R Ambient Temperature
Read: 0.0 to 99.9 multiplied by 10
15 FilterSign
Reset
WR Filter dirty status
Read: Allowed but it is nonsense
Write: RESET
16 ErrorSign
Reset
WR Error status
Read: Allowed but it is nonsense
Write: RESET
17 CommErrorGro
up
R Group Communication Error
0-OK, 1-Communication Error
18 Polling Active RW Polling active
Read:0-Deactivated, 1-Activated
Write: 0-Deactivate, 1-Activate
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
11 / 33
19 SetTemp1 RW Setpoint1 /COOL-DRY (when Dual Setpoint Cfg)
19..30.0 °C / 19..35.0 °C
20 SetTemp2 RW Setpoint2 /HEAT (when Dual Setpoint Cfg)
17..28.0 °C / 4.5..28.0 °C
21 SetTemp3 RW Setpoint3 /AUTO (when Dual Setpoint Cfg and separate
Auto setpoint)
°C
22 AutoModeSWE
x
R Auto Mode Setpoint Cgf
0-Disabled, 1-Auto with own setpoint (Setpoint3)
2-Auto uses HEAT/COOL Setpoints (Setpoint1/Setpoint2)
23 AlarmCode R M-Net device’s AlarmCode
0..9999 (0 no Alarm)
RW indicates Read, Write, or both.
3. LinkBoxMB. Configuration & monitoring tool for IntesisBox Modbus Server series
3.1 Introduction
LinkBoxMB is a Windows 98/NT/2000/XP compatible software developed specifically to
monitor and configure IntesisBox Modbus Server series. It is possible to configure all
external protocols available for IntesisBox Modbus Server and to maintain different
customer’s configurations based on a LinkBoxMB project for every different installation.
Maintaining always on hard disk a copy of the last configuration files for every external
protocol and customer, that is to say for every project.
From LinkBoxMB, as well as configure the integration signals list and connection parameters
for every external protocol, it is permitted to select the serial port to use to connect to
IntesisBox Modbus Server and the use of some tools for monitoring and debugging de
device. Some of these tools will be explained in this document but only some of them, the
rest of available debugging tools and commands will not be explained here because they are
for exclusive use under the recommendations of Intesis Software technical support.
LinkBoxMB allows configuring all IntesisBox Modbus Server series independently of the
external system used. For every external system, LinkBoxMB has a specific configuration
window. Periodically, new free versions of LinkBoxMB are released incorporating the latest
developed integrations for external systems.
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
12 / 33
3.2 Project definition
The first step to do in LinkBoxMB for a new installation is to create the installation’s project
giving a descriptive name to it. When you create a project, a new folder is created with the
name of the project containing the configuration files needed depending on the external
protocol selected for the project. It is strongly recommended that you create a new project
for every installation, if not, overwriting of configuration files of previous installations using
the same external protocol may occur, loosing the configuration data for those previous
installations. The projects folder is located in AppFolder\ProjectsMB, where AppFolder is the
installation folder of LinkBoxMB (by default C:\Program Files\Intesis\LinkBoxMB). Inside the
projects folder, a new folder will be created for every project defined in LinkBoxMB with the
files needed for the project.
When you open LinkBoxMB, the project selection window will appear inviting you to select a
project or create a new one. A demo project for every external protocol supported is
provided with the standard installation of LinkBoxMB. You can create a new project or select
a demo project based on the external protocol desired, and create a new one from the
demo one selected.
Project selection window
To create a new project, select a project using the same external protocol you want to use
in the new project and click on New button. You will be prompted to create a copy of the
selected project (useful for similar installations) or create a new one.
If you select Yes you will be prompted to specify a name and a description for the new
project that will be based on the same external protocol than the selected one. If you select
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
13 / 33
No you can specify a name, a description and an external protocol to use from the list of
available external protocols.
On Accept, a new folder will be created inside the projects folder with the name given to the
project, this folder will contain the template configuration files if the project is a brand new
one, or a copy of the configuration files if it is a copy of a selected one.
A description of the files created for a Mitsubishi Electric G50 protocol based project can be
found in section Files in this document.
From all the possibilities of LinkBoxMB, only changes in configuration for the integration and
configuration file generation can be performed while disconnected from IntesisBox (working
off-line), allowing you to do these tasks in the office more comfortably. Before any
monitoring or downloading action to IntesisBox can be performed, the connection between
IntesisBox and the PC running LinkBoxMB must be established (working on-line). To do so
follow these steps:
1. Make sure IntesisBox is powered-up a correctly connected to the Modbus system via the
Ethernet connection (Modbus TCP) or serial connection (Modbus RTU) and to Mitsubishi
Electric G50 devices via the Ethernet network (consult details for connection and pin
assignments in section Connections of this document).
2. Connect a free PC serial port to the IntesisBox serial port marked as PC Console. (Use
the standard serial cable supplied with the device or a customer’s cable following the pin
assignments specified in section Connections in this document).
3. Select in LinkBoxMB the PC serial port used for the connection to IntesisBox. Use menu
Configuration -> Connection.
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
14 / 33
4. Check the checkbox off-line under the menu bar (it will change automatically to on-line)
and LinkBoxMB will ask for INFO about the IntesisBox connected to it via the serial
connection, if the connection is ok then IntesisBox will respond with its identification
(this can be monitored in the IntesisBox Communication Console window, as showed
below).
Once connected to IntesisBox, all the options of LinkBoxMB are fully operative.
To monitor the communication between IntesisBox and the Modbus master device, select
the menu View -> Bus -> Modbus. The Modbus communication Viewer window will be
opened. This window show in real time all the communication frames between IntesisBox
and the Modbus master device as well as debugging messages referent to internal protocol
(Modbus) sent by IntesisBox.
To monitor the communication between IntesisBox and the external system (Mitsubishi
Electric G50 in this case), select the menu View -> Bus -> MitsubishiG50. The External
protocol communication viewer window will be opened. This window show in real time all
the communication frames between IntesisBox and G50 devices as well as debugging
messages referent to external protocol (Mitsubishi Electric G50) sent by IntesisBox.
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
15 / 33
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
16 / 33
3.3 Connections configuration
To configure the IntesisBox's connection parameters and to see the signals list, select menu
Configuration -> IntesisBox. The Mitsubishi Electric G50 Configuration window will be
opened.
Select the Connection tab to configure the connection parameters.
Two kinds of information are configured using this window, the referent to the Modbus
interface and the referent to the Mitsubishi Electric G50 interface.
Modbus interface configuration parameters:
Modbus Interface Configuration
1. Enter the IP address for IntesisBox.
2. Enter the IP netmask for IntesisBox.
3. Enter the default router address for IntesisBox, leave blank is there is no need of router.
4. Select the type of Modbus communication to use (TCP or RTU).
If Modbus TCP is selected, then:
5. Enter the TCP port to use, by default 502.
If Modbus RTU is selected, then:
6. Select the connection used (RS232 or RS485).
7. Select the baud rate.
8. Enter the Modbus slave number for IntesisBox.
4
1
2
2 3
2
5
2
6
7
2 8
2
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
17 / 33
Mitsubishi Electric G50 interface configuration parameters:
ME G50 Interface Configuration
1. List of configured G50 devices, only those checked will be active in the configuration.
Note that you should not activate more G50s than the maximum supported by the
IntesisBox model used, there are different models of IntesisBox supporting different number
of G50s. You can identify the model of IntesisBox by the order code printed in the front
label:
• ME-AC-MBS-50. Model supporting up to 1 G50 and 50 City Multi groups.
• ME-AC-MBS-100. Model supporting up to 2 G50 and 100 City Multi groups.
You can identify also the model of your IntesisBox through the identification given by it
in response to an INFO command, it is something like this:
IntesisBox_MODBUS_SVR_MITSUG50-1… -> this is the ME-AC-MBS-50 model
supporting up to one G50, up to 50 City Multi groups.
IntesisBox_MODBUS_SVR_MITSUG50-2… -> this is the ME-AC-MBS-100 model
supporting up to two G50, up to 100 City Multi groups.
Select a G50 to configure its properties:
2. IP address of the G50/AG150. When using Expansion Controllers with an AG150 the IP
to be set is the one of the AG150, not the EC ones. The selection of the EC explained in
point 5.
3. TCP port used (by default 80).
3
1
6
2
4
8
7
9
10
5
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
18 / 33
4. Descriptive name (optional, for user informative purposes).
5. Type: It needs to be selected what the IntesisBox is connected to. If EC are used which
one is going to be used (1,2 or 3) needs to be selected here.
Common parameters for all the G50s configured.
6. Polling interval (in seconds): Waiting time between a reception of an answer and
sending the following read command
7. Polling cycles to validate the return of status for any command sent to Mitsubishi.
8. Answer timeout: Time that the IntesisBox waits for an answer. After it expires it
continues with the following polling
9. Number of polling cycles to check the alarms in the G50
10. Select this if you want IntesisBox to deactivate automatically the polling for those
groups that are not configured into the G50 (automatically detected).
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
19 / 33
3.4 Signals list
Select the Points tab to see the signals list.
In this case (integration of Mitsubishi Electric G50), there is no need of configuring the
signals list because the IntesisBox has a fixed Modbus address map for the signals of the
G50s configured. The signals list in this particular integration is just to consult and for user
informative purposes.
Signals list
1. Address Formula. Formula used by IntesisBox to define the Modbus address for the
point. Use this address (obtained with this formula) to access the point from your
Modbus master device. See section 2.4 Address Map.
2. Property. Property number of the G50 signal. See section 2.4 Address Map.
3. R/W. Indicates if the signal is Read only, Write only, or Read and Write (always from the
Modbus system point of view). See section 2.4 Address Map.
4. Signal. Signal description. See section 2.4 Address Map.
5. Values. Possible values for the signal. See section 2.4 Address Map. When connecting to
PWFY units the values differ from the standard ones. In this column both of them are
specified
1 2 3 4 5
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
20 / 33
3.5 Sending the configuration to IntesisBox
When the configuration has been saved (button Accept) and the IntesisBox configuration
binary file has been generated (remember to select yes when asked if you want to generate
the IntesisBox file), to send the configuration file to IntesisBox click on the button Send
File. The process of file transmission can be monitored in the IntesisBox Communication
Console window. If the file transmission is ok, IntesisBox will reboot automatically with the
new configuration loaded.
Remember that saving the configuration and generating the IntesisBox file only saves to the
hard disk on the PC the configuration files. Do not forget to send the configuration file
to the IntesisBox using button Send File.
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
21 / 33
3.6 Signals viewer
Once IntesisBox is running with the correct configuration, to supervise the status of the
configured signals, select menu View -> Signals. The Signals Viewer window will be opened.
This window shows all the active IntesisBox's signals with its main configuration parameters
and its real time value in the column Value. After a reset of IntesisBox or after sending a
configuration file to the IntesisBox, all the signal's values will be updated automatically in
the signals viewer, in case you connect to the IntesisBox when it is already running, you
should press the Update button to get updated values, press just once the button to update
all the signals values, since that moment the signal values will be maintained updated until
the connection is closed.
The signals viewer can be used although only one system is connected to the IntesisBox,
Modbus or Mitsubishi Electric G50, and is very useful for supervision and test.
It is possible to force a specific value to any signal for test purposes, to do so just double
click on the row and select the desired value and Accept in the Data Test window. If the
signal is of type R or RW, then the value entered will be available to be read from Modbus
master device, if the signal is of type W or RW, then the value entered will be sent to the
corresponding Mitsubishi Electric G50.
This tool is very useful to test any of the systems connected to IntesisBox, Modbus and
Mitsubishi Electric G50 without the need to actuate on the real signals.
The signals viewer window has a button to copy to the Windows Clipboard all the contents
of the window (in tab separated text format).
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
22 / 33
3.7 System commands
LinkBoxMB includes an option to send to IntesisBox a set of system commands for
debugging and control purposes; this list is available in the commands list as shown in the
figure below. To send a command to IntesisBox just select it from the list, or type it with
the correct format, and press Enter or click on button Send. IntesisBox will act accordingly
with the command received; the process can be monitored in the IntesisBox Communication
Console window. The use of some of these commands can be critical for IntesisBox normal
functioning, having this in mind use only these commands following the recommendations
of Intesis Software technical support. A list of the more commonly used commands and the
way to use them will be returned by IntesisBox after sending the command HELP.
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
23 / 33
3.8 Files
LinkBoxMB saves the integration configuration in the following files inside the project folder:
PROJECT.INI
.ini file containing general information referent to the project
MITSUBISHIG50.INI .ini file containing the information referent to the connection
window and other special adjustments
MITSUBISHIG50.DAT
Text file (tab separated values) with the contents of the signals list.
MITSUBISHIG50.LBOX Binary file created from the information in the files described
above. This is the file downloaded to the IntesisBox.
It is strongly recommended to back up the project folder containing these files in external
media, once the installation process is finished. This way you will be able to do future
configuration changes in case of reinstallation of LinkBoxMB due, for example, to a failure of
the hard disk in the PC where LinkBoxMB was installed.
The configuration cannot be uploaded from IntesisBox to LinkBoxMB, only can be
downloaded; the download file MITSUBISHIG50.LBOX does not contain all the
integration information, as for example the signals description.
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
24 / 33
4. Setup process and troubleshooting
4.1 Pre-requisites
It is necessary to have the Modbus master device operative and well connected to the
Modbus port of IntesisBox, remember to respect the maximum of 15 meters cable distance
if using RS232 communication.
It is necessary to have an Ethernet 10BT network connection near IntesisBox (network hub
or switch port) with all Mitsubishi Electric G50 devices connected to this Ethernet network.
Connectors, connection cables, PC for LinkBoxMB, and other auxiliary material, if needed,
are not supplied by Intesis Software for this standard integration. The items supplied by
Intesis Software for this integration are:
• IntesisBox Modbus Server device with Mitsubishi Electric G50 external protocol
firmware loaded.
• LinkBoxMB software to configure IntesisBox.
• Console cable needed to download the configuration to IntesisBox.
• Product documentation.
If requested, Intesis Software also can supply:
• Standard plug-in power supply 220Vac 50Hz to power IntesisBox (European plug
type).
4.2 Setup procedure
1. Install LinkBoxMB on your laptop, use the setup program supplied for this and follow the
instructions given by the Installation wizard.
2. Install IntesisBox in the desired installation site. The mounting can be on DIN rail or on
a stable not vibrating surface (DIN rail mounted inside a metallic industrial cabinet
connected to ground is recommended).
3. Connect the communication cable coming from the Modbus master device to the port
marked as Modbus of IntesisBox (used either RS232, RS485 or Ethernet port
depending on the type of Modbus communication to use). (See details for this
communication cable in section Connections of this document).
4. Connect the communication cable coming from the network hub or switch to the port
marked as ETH of IntesisBox. (See details for this communication cable in section
Connections of this document).
5. Power up IntesisBox. The supply voltage can be 9 to 30 Vdc or just 24 Vac. You can use
also the standard plug-in power supply 220/125VAC-12VDC/300mA supplied with the
device (if requested). Take care of the polarity of the supply voltage applied.
WARNING! In order to avoid earth loops that can damage IntesisBox and/or any
other equipment connected to it, we strongly recommend:
• The use of DC power supplies, floating or with the negative terminal connected to
earth. Never use a DC power supply with the positive terminal connected
to earth.
• The use of AC power supplies only if they are floating and not powering any other
device.
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
25 / 33
6. Connect the communication cable coming from the serial port of your laptop PC to the
port marked as PC Console of IntesisBox. (See details for this communication cable in
section Connections of this document).
7. Open LinkBoxMB, create a new project selecting a copy of the one named DEMO
MitsuG50 and give it the name desired, select the serial port used to connect to
IntesisBox (menu Configuration -> Connection) and switch working mode to on-line
(checkbox off-line/on-line). The IntesisBox identification must appear in the IntesisBox
communication console window as showed below.
8. Modify the configuration as desired, save it and download the configuration file to
IntesisBox as explained before.
9. Open the Modbus Communication Viewer window (menu View -> Bus -> Modbus) and
check that there is communication activity, some TX frames and some other rx frames.
This means that the communication with the Modbus master device is ok. In case there
is no communication activity between IntesisBox and the Modbus master device check
that it is operative, check the baud rate, and check also the communication cable used
to connect both devices. (See details for this communication cable in section
Connections of this document).
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
26 / 33
10. Open the External Protocol Communication Viewer window (menu View -> Bus ->
MitsubishiG50) and check that there is communication activity, some TX frames and
some other rx frames as showed in the figure below. This means that the
communication with the Mitsubishi Electric system is ok.
In case there is no response from the Mitsubishi Electric G50 devices to the frames sent
by IntesisBox, check that they are operative and reachable from the network connection
used by IntesisBox, check the IntesisBox's Ethernet interface making pings to its IP
address using a PC connected to the same Ethernet network. See details for the
communication cable between IntesisBox and Mitsubishi Electric in section Connections
of this document.
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
27 / 33
5. Connections
IntesisBox
(RJ45 F)
C1 G50s & Modbus TCP Connection Master TCP
(RJ45 F)
Cable
(RJ45 M)
Ethernet Cable
(RJ45 M)
Cable UTP/FTP Cat5 Crossed 1 device
G50
Cable UTP/FTP Cat5 Straight Hub N devices
G50
IntesisBox
(DB9 M)
C2 Modbus RTU Connection Master RTU
(DB9 M)
Cable
(DB9 F)
RS-232
(Crossed)
Cable
(DB9 F)
RX 2 2 RX
TX 3 3 TX
GND 5 5 GND
Cable
(DB9 F)
or RS-485
TX/RX+ TX/RX+
TX/RX- TX/RX-
IntesisBox
(DB9 F)
C3 PC Connection (LinkBoxMB) PC
(DB9 M)
Cable
(DB9 M)
RS-232
(Straight)
Cable
(DB9 F)
TX 2 2 RX
RX 3 3 TX
GND 5 5 GND
C2
C1
C3
Ethernet RJ45
PC Console
ETH
PC (LinkBoxMB)
- +
Modbus RTU
RS485 RS232
Mitsu.Elec. G50
+
Modbus TCP
- + CMN 24Vac
Power
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
28 / 33
6. Functional characteristics
Modbus
interface
Device type Slave.
Modbus modes
supported
TCP, RTU RS232 or RS485.
Modbus TCP
configuration
parameters
• IP address.
• Subnet mask.
• Default gateway address.
• TCP port.
Modbus RTU
configuration
parameters
• RS232/RS485.
• Baud rate.
• Slave number.
Points
Configuration No point configuration needs to be done, all the Mitsubishi
Electric G50 signals are automatically associated to predefined
fixed Modbus Addresses.
Modbus function
codes supported
Read functions:
• 3- Read holding registers.
• 4- Read input registers.
Write functions:
• 6- Write single register.
• 16- Write multiple registers.
If poll records are used to read/write multiple records, the range of addresses requested must contain valid addresses, if not the corresponding Modbus error code will be returned.
Modbus data
coding
All the point's values are coded in 2 bytes registers (even if their possible
values are 0 and 1) and expressed in MSB..LSB.
General
Max. Number of
Mitsubishi
Elec.G50s
Up to 2 G50s can be supported. There are two different models for this
gateway, supporting: 1 or 2 G50s respectively.
Virtual signals • One communication error virtual signal per every G50 device defined.
• One communication error virtual signal per every group into the G50
device.
• One virtual signal per every group into the G50 device to
enable/disable this group in the polling process.
All these virtual signals can be read/written from Modbus.
Mitsubishi
Electric G50
interface
Device type Client.
Configuration
Parameters
Polling interval (1..600 seconds).
Per every G50 defined:
• Descriptive name.
• IP address.
• TCP port.
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
29 / 33
7. Mechanical & Electrical characteristics
Enclosure Plastic type PC (UL 94 V-0). Size: 107mm x 105mm x 58mm.
Colour Grey. RAL 7035.
Power 9 to 30VDC +/-10% 1.4W.
24VAC +/-10% 1.4VA.
Power connector is a 2 pole plug-in screw terminal bloc.
Mounting options Desktop
Wall
DIN rail EN60715 TH35.
Modbus RTU ports 1 x Serial RS232 (DB9 male DTE).
1 x Serial RS485 (Plug-in screw terminal block 2 poles).
Modbus TCP &
Mitsubishi
Elec.G50 port
1 x Ethernet 10BT RJ45 connector.
LED indicators 1 x Power.
2 x Ethernet port activity (LNK, ACT).
2 x Modbus RTU port activity (Tx, Rx).
Console port RS232. DB9 female connector (DCE).
Configuration Via console port.1
Firmware Allows upgrades via console port.
Operational
temperature range
-40°C to +70°C
Operational
humidity range
5% to 95%, non condensing
Protection IP20 (IEC60529).
RoHS conformity Compliant with RoHS directive (2002/95/CE).
Certifications CE 1 Along with the device it is also supplied a standard DB9 male - DB9 female 1.8 m. cable for configuring and monitoring the
device using a PC via serial COM port. The configuration software LinkBoxMB, compatible with MS Windows® operating systems, is also supplied with the device.
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
30 / 33
8. Dimensions
Recommended available space for its installation into a cabinet (wall or DIN rail mounting),
with space enough for external connections:
115 mm
130 mm
100 mm
Power
+
Ethernet port
107 mm 105
mm
58 mm
Modbus RTU
RS232/485
Console
port
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
31 / 33
9. Annexes
9.1 Gateways Mitsubishi Electric G-50A and GB-50A
G-50A
GB-50A
For more information about these devices contact Mitsubishi Electric.
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
32 / 33
9.2 Examples of Modbus addresses
Address G50 Group Property Address G50 Group Property
1 1 0 Error Com. G50 2 2 0 Error Com. G50
101 1 1 1 Drive 5101 2 1 1 Drive
102 1 1 2 Mode 5102 2 1 2 Mode
103 1 1 3 SetTemp 5103 2 1 3 SetTemp
104 1 1 4 AirDirection 5104 2 1 4 AirDirection
105 1 1 5 FanSpeed 5105 2 1 5 FanSpeed
106 1 1 6 RemoCon 5106 2 1 6 RemoCon
107 1 1 7 DriveItem 5107 2 1 7 DriveItem
108 1 1 8 ModeItem 5108 2 1 8 ModeItem
109 1 1 9 SetTempItem 5109 2 1 9 SetTempItem
110 1 1 10 FilterItem 5110 2 1 10 FilterItem
111 1 1 11 Ventilation 5111 2 1 11 Ventilation
112 1 1 12 FilterSign 5112 2 1 12 FilterSign
113 1 1 13 ErrorSign 5113 2 1 13 ErrorSign
114 1 1 14 InletTemp 5114 2 1 14 InletTemp
115 1 1 15 FilterSignReset 5115 2 1 15 FilterSignReset
116 1 1 16 ErrorSignReset 5116 2 1 16 ErrorSignReset
117 1 1 17 Error Com. Group 5117 2 1 17 Error Com. Group
118 1 1 18 Polling Active 5118 2 1 18 Polling Active
5001 1 50 1 Drive 10001 2 50 1 Drive
5002 1 50 2 Mode 10002 2 50 2 Mode
5003 1 50 3 SetTemp 10003 2 50 3 SetTemp
5004 1 50 4 AirDirection 10004 2 50 4 AirDirection
5005 1 50 5 FanSpeed 10005 2 50 5 FanSpeed
5006 1 50 6 RemoCon 10006 2 50 6 RemoCon
5007 1 50 7 DriveItem 10007 2 50 7 DriveItem
5008 1 50 8 ModeItem 10008 2 50 8 ModeItem
5009 1 50 9 SetTempItem 10009 2 50 9 SetTempItem
5010 1 50 10 FilterItem 10010 2 50 10 FilterItem
5011 1 50 11 Ventilation 10011 2 50 11 Ventilation
5012 1 50 12 FilterSign 10012 2 50 12 FilterSign
5013 1 50 13 ErrorSign 10013 2 50 13 ErrorSign
5014 1 50 14 InletTemp 10014 2 50 14 InletTemp
5015 1 50 15 FilterSignReset 10015 2 50 15 FilterSignReset
5016 1 50 16 ErrorSignReset 10016 2 50 16 ErrorSignReset
5017 1 50 17 Error Com. Group 10017 2 50 17 Error Com. Group
5018 1 50 18 Polling Active 10018 2 50 18 Polling Active
IntesisBox® Modbus Server - Mitsubishi Electric G50 User’s manual r19 eng
© Intesis Software S.L.U. - All rights reserved This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SLU
URL Email tel
http://www.intesisbox.com [email protected] +34 938047134
33 / 33
Address G50 Group Property Address G50 Group Property
3 3 0 Error Com. G50 4 4 0 Error Com. G50
10101 3 1 1 Drive 15101 4 1 1 Drive
10102 3 1 2 Mode 15102 4 1 2 Mode
10103 3 1 3 SetTemp 15103 4 1 3 SetTemp
10104 3 1 4 AirDirection 15104 4 1 4 AirDirection
10105 3 1 5 FanSpeed 15105 4 1 5 FanSpeed
10106 3 1 6 RemoCon 15106 4 1 6 RemoCon
10107 3 1 7 DriveItem 15107 4 1 7 DriveItem
10108 3 1 8 ModeItem 15108 4 1 8 ModeItem
10109 3 1 9 SetTempItem 15109 4 1 9 SetTempItem
10110 3 1 10 FilterItem 15110 4 1 10 FilterItem
10111 3 1 11 Ventilation 15111 4 1 11 Ventilation
10112 3 1 12 FilterSign 15112 4 1 12 FilterSign
10113 3 1 13 ErrorSign 15113 4 1 13 ErrorSign
10114 3 1 14 InletTemp 15114 4 1 14 InletTemp
10115 3 1 15 FilterSignReset 15115 4 1 15 FilterSignReset
10116 3 1 16 ErrorSignReset 15116 4 1 16 ErrorSignReset
10117 3 1 17 Error Com. Group 15117 4 1 17 Error Com. Group
10118 3 1 18 Polling Active 15118 4 1 18 Polling Active
15001 3 50 1 Drive 20001 4 50 1 Drive
15002 3 50 2 Mode 20002 4 50 2 Mode
15003 3 50 3 SetTemp 20003 4 50 3 SetTemp
15004 3 50 4 AirDirection 20004 4 50 4 AirDirection
15005 3 50 5 FanSpeed 20005 4 50 5 FanSpeed
15006 3 50 6 RemoCon 20006 4 50 6 RemoCon
15007 3 50 7 DriveItem 20007 4 50 7 DriveItem
15008 3 50 8 ModeItem 20008 4 50 8 ModeItem
15009 3 50 9 SetTempItem 20009 4 50 9 SetTempItem
15010 3 50 10 FilterItem 20010 4 50 10 FilterItem
15011 3 50 11 Ventilation 20011 4 50 11 Ventilation
15012 3 50 12 FilterSign 20012 4 50 12 FilterSign
15013 3 50 13 ErrorSign 20013 4 50 13 ErrorSign
15014 3 50 14 InletTemp 20014 4 50 14 InletTemp
15015 3 50 15 FilterSignReset 20015 4 50 15 FilterSignReset
15016 3 50 16 ErrorSignReset 20016 4 50 16 ErrorSignReset
15017 3 50 17 Error Com. Group 20017 4 50 17 Error Com. Group
15018 3 50 18 Polling Active 20018 4 50 18 Polling Active