1. GENERAL CONTRACTOR SHALL VISIT THE SITE, REVIEW THE BUILDING SHELL DRAWINGS AS SUBMITTED BY THE LICENSEE'S ARCHITECT AND BECOME THOROUGHLY FAMILIAR WITH THE SITE CONDITIONS PRIOR TO BIDDING OR CONSTRUCTION. 2. GENERAL CONTRACTOR SHALL CONSULT WITH LICENSEE'S ARCHITECT AND STARBUCKS PROJECT DEVELOPMENT MANAGER TO RESOLVE ANY CHANGES, OMISSIONS OR PLAN DISCREPANCIES PRIOR TO BIDDING OR CONSTRUCTION. 3. ALL WORK SHALL BE PERFORMED IN STRICT COMPLIANCE WITH LOCAL, COUNTY, STATE AND FEDERAL CODES AND ORDINANCES. 4. GENERAL CONTRACTOR SHALL VERIFY THE LOCATION OF ALL UTILITIES. 5. GENERAL CONTRACTOR TO VERIFY ALL DIMENSIONS, INCLUDING CLEARANCES REQUIRED BY OTHER TRADES AND NOTIFY THE LICENSEE'S ARCHITECT AND STARBUCKS PROJECT DEVELOPMENT MANAGER OF ANY DISCREPANCIES PRIOR TOPROCEEDING WITH THE WORK. ALL DIMENSIONS ARE TO THE FACE OF THE FINISHED SURFACE UNLESS NOTED OTHERWISE. ALL DIMENSIONS TO BE TAKEN FROM DESIGNATED DATUM POINT. DO NOT SCALE DRAWINGS. 6. GENERAL CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS, FLOORS, CEILINGS, OR OTHER SURFACES IDENTIFIED TO REMAIN THAT MAY BECOME DAMAGED DURING THE COURSE OF THE WORK. 7. GENERAL CONTRACTOR IS RESPONSIBLE FOR OBTAINING PERMITS FOR FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL SYSTEMS PRIOR TO INSTALLATION OF SUCH SYSTEMS. 8. GENERAL CONTRACTOR SHALL RETAIN ONE SET OF THE PLANS TO NOTE AND DOCUMENT ALL CHANGES DURING CONSTRUCTION. THIS SET SHALL BE SUBMITTED TO THE STARBUCKS PROJECT DEVELOPMENT MANAGER FOR RECORD. 9. GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING DELIVERY OF MATERIALS FROM STARBUCKS CONTRACTED THIRD PARTY LOGISTICS DISTRIBUTION SERVICES AND VENDOR DIRECT SHIPMENTS. 10. RESPONSIBILITY FOR SUPPLY AND DELIVERY OF MATERIALS AND EQUIPMENT IS IDENTIFIED IN THE DRAWING SCHEDULE SHEETS UNDER THE COLUMN LABELED "RESPONSIBILITY". 11. FOR THE PURPOSE OF THESE DOCUMENTS, TO “INSTALL” SHALL MEAN TO PROVIDE ALL FASTENERS, MISCELLANEOUS HARDWARE, BLOCKING, ELECTRICAL CONNECTIONS, PLUMBING CONNECTIONS, AND OTHER ITEMS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION, UNLESS OTHERWISE NOTED. 12. ALL ITEM SUBSTITUTIONS MUST BE APPROVED BY THE STARBUCKS DESIGN MANAGER. 13. REFER TO ITEM CUTSHEETS FOR ADDITIONAL INFORMATION. GENERAL NOTES MAILING ADDRESS: DESIGN MANAGER: PROJECT DEVELOPMENT MANAGER: LICENSEE: ARCHITECT OF RECORD: STRUCTURAL /CIVIL ENGINEER MEP ENGINEER OF RECORD: STARBUCKS COFFEE COMPANY 2401 UTAH AVENUE SOUTH MS STOP: S-SD9 SEATTLE, WASHINGTON 98134 ANDREW HUMAYDAN STARBUCKS COFFEE COMPANY 60 SPEAR STREET, 7TH FLR SAN FRANCISCO, CA 94105 (415)537-7174 [email protected] JACQUIE HANNIBAL STARBUCKS COFFEE COMPANY (206)318.8867 [email protected] AURARIA HIGHER EDUCATION CENTER 1201 5th STREET, SUITE 370 DENVER, CO 80204 303.556.3349 KRISTINE ROUSE / BILL FURMAN SLATERPAULL | HORD COPLAN MACHT 1331 19th STREET DENVER, CO 80202 303.607.0977 [email protected] [email protected] STAN LEWIS PE ANDERSON & HASTINGS CONSULTANTS, INC. 12596 WEST BAYAUD AVENUE, SUITE 200 LAKEWOOD, CO 80228 720.452.0524 [email protected] RICHARD MATTHIES, PE BCER ENGINEERING 5420 WARD ROAD SUITE 200 ARVADA, CO 80002 303.405.2871 [email protected] PROJECT CONTACTS INDEX OF SHEETS SCOPE OF WORK TENANT IMPROVEMENT AND ALTERATION OF EXISTING SPACE TO CAFE VICINITY PLAN SB / GC SB / FC GC / GC LC / GC LC / LC FC / GC RESPONSIBILITY LEGEND - LICENSED STORES FURNISHED BY STARBUCKS / INSTALLED BY LICENSEE'S GENERAL CONTRACTOR FURNISHED BY STARBUCKS / INSTALLED BY STARBUCKS FIXTURE CONTRACTOR FURNISHED BY LICENSEE'S GENERAL CONTRACTOR / INSTALLED BY LICENSEE'S GENERAL CONTRACTOR FURNISHED BY LICENSEE / INSTALLED BY LICENSEE'S GENERAL CONTRACTOR FURNISHED BY LICENSEE / INSTALLED BY LICENSEE FURNISHED BY STARBUCKS FIXTURE CONTRACTOR / INSTALLED BY LICENSEE'S GENERAL CONTRACTOR CUSTOM DESIGN ID KEY SIGNAGE GRAPHICS AND ARTWORK SITE DOORS DATA DEVICE SPECIALITY EQUIPMENT CASEWORK FURNITURE LIGHTING FIXTURE PLUMBING / MECHANICAL FINISHES - PAINT FINISHES - FLOOR TREATMENT FINISHES - WALL TREATMENT FINISHES - CEILING TREATMENT "S" x0000 - x0999 "G" x1000 - x1099 "Y" x1100 - x1199 "D" x2000 - x2999 "A" x3000 - x3999 "E" x4000 - x4999 "C" x5000 - x5999 "F" x6000 - x6999 "L" x7000 - x7999 "P" / "M" x8000 - x8999 x9000 - x9199 "T" x9200 - x9399 "Q" / "R" x9400 - x9799 "U" x9800 - x9999 SCHEDULE PREFIX A - DATA DEVICE SCHEDULE B - WALL BASE SCHEDULE C - CASEWORK SCHEDULE D - DOOR SCHEDULE E - SPECIALTY EQUIPMENT SCHEDULE F - FURNITURE SCHEDULE G - GRAPHICS AND ARTWORK SCHEDULE L - LIGHTING FIXTURE SCHEDULE M - MECHANICAL EQUIPMENT SCHEDULE P - PLUMBING FIXTURE SCHEDULE Q - WALL TREATMENT (AREA) SCHEDULE R - WALL TREATMENT (LENGTH) SCHEDULE S - SIGNAGE SCHEDULE T - FLOOR TREATMENT SCHEDULE U - CEILING TREATMENT SCHEDULE W - WINDOW SCHEDULE Y - SITE SCHEDULE ABBREVIATIONS 3PL THIRD PARTY LOGISTICS AC AIR CONDITIONING ACC ACCESSIBLE ACT ACOUSTICAL CEILING TILE ADJ ADJUSTABLE AFF ABOVE FINISHED FLOOR AHJ AUTHORITIES HAVING JURISDICTION AMP AMPERE AOR ARCHITECT OF RECORD APPROX APPROXIMATE BOH BACK OF HOUSE BLDG BUILDING CAB CABINET CKT CIRCUIT CL CENTER LINE CLG CEILING CLR CLEAR OR CLEARANCE COL COLUMN COMP COMPARTMENT CONST CONSTRUCTION CONT CONTINUOUS CTR CENTER CW COLD WATER CWF COLD WATER FILTERED CX COMMISSIONING CXA COMMISSIONING AGENT DEG DEGREES DET DETAIL DIA DIAMETER DISP DISPENSER DIM DIMENSION DM STARBUCKS DESIGN MANAGER DN DOWN DWG(S) DRAWING(S) EA EACH EC ELECTRICAL CONTRACTOR EG EXHAUST GRILLE EL ELEVATION ELEC ELECTRICAL EM EMERGENCY EQ EQUAL EQUIP EQUIPMENT EXIST OR (E) EXISTING EXP EXPOSED EXT EXTERIOR FC STARBUCKS FIXTURE CONTRACTOR/INSTALLER FCO FLOOR CLEANOUT FD FLOOR DRAIN FF&E FURNITURE, FIXTURE AND EQUIPMENT F&I FURNISH AND INSTALL FIN FINISH FLR FLOOR FOH FRONT OF HOUSE FRP FIBERGLAS REINFORCED PANEL FS FLOOR SINK FT FOOT OR FEET GC GENERAL CONTRACTOR GFCI GROUND FAULT CIRCUIT INTERRUPTER GND GROUND HC HOLLOW CORE HDW HARDWARE HM HOLLOW METAL HORIZ HORIZONTAL HR HOUR HS HAND SINK HT HEIGHT HVAC HEATING, VENTILATING AND AIR CONDITIONING HW HOT WATER ID INSIDE DIAMETER LC LICENSEE LL LANDLORD LV LOW VOLTAGE MAX MAXIMUM MC MECHANICAL CONTRACTOR MECH MECHANICAL MEP MECHANICAL, ELECTRICAL AND PLUMBING MFR MANUFACTURER MIN MINIMUM MS MOP SINK NIC NOT IN CONTRACT NTS NOT TO SCALE OA OVER ALL OC ON CENTER OD OUTSIDE DIAMETER PC PLUMBING CONTRACTOR PD STARBUCKS PRODUCTION DESIGNER PDM STARBUCKS PROJECT DEVELOPMENT MANAGER PLAM PLASTIC LAMINATE POS POINT OF SALE R RADIUS REF REFERENCE REQ(‘D) REQUIRE(D) REV REVISION RG RETURN GRILLE RND ROUND RT ROOF TOP SB STARBUCKS SC SOLID CORE SF SQUARE FEET SHT SHEET SIM SIMILAR SPEC SPECIFICATION SQ SQUARE SST STAINLESS STEEL SUSP SUSPENDED TEL TELEPHONE TEMP TEMPORARY TW TEMPERED WATER TYP TYPICAL UC UNDERCOUNTER UON UNLESS OTHERWISE NOTED VD VENDOR DIRECT VERT VERTICAL VIF VERIFY IN FIELD W SANITARY WASTE WH WATER HEATER WP WEATHER PROOF WCO WALL CLEANOUT PXXX-ES X' XX" X N NORTH ARROW XXXX AFF ARCHITECTURAL SYMBOL LEGEND XXXXX W XX Scale: X =X 0 2 4 8 GRAPHIC SCALE DATUM POINT EXTERIOR ELEVATION CALL-OUT INTERIOR ELEVATION CALL-OUT SECTION CALL-OUT DETAIL CALL-OUT REVISION TAG PAINT TAG XXXXX X DESIGN ID TAG XXXXX D DOOR TAG WINDOW TAG SHEET NOTE CALLOUT ABOVE FINISH FLOOR HEIGHT TAG FINISH FACE TO FINISH FACE DIMENSION REVISION CLOUD CONSULTANT: ISSUE: OWNER: PROJECT: DRAWING INFORMATION: DRAWN BY: PROJECT NO: SHEET TITLE: APPROVED BY: CHECKED BY: SHEET OF 1 2 3 4 5 A B C D 1 2 3 4 5 THESE RECORD DRAWINGS HAVE BEEN PREPARED, IN PART, ON THE BASIS OF INFORMATION COMPILED AND FURNISHED BY OTHERS. THE ARCHITECT WILL NOT BE RESPONSIBLE FOR ANY ERRORS OR OMISSIONS WHICH HAVE BEEN INCORPORATED INTO THIS DOCUMENT AS A RESULT. P 303.607.0977 www.slaterpaull.com 1331 Nineteenth Street Denver, CO. 80202 5/26/2015 4:36:37 PM C:\Users\bfurman\Documents\11530 Tivoli Starbucks _A_2015_bfurman.rvt G-0001 G-0001 G-0001 G-0001 GENERAL INFORMATION AURARIA HIGHER EDUCATION CENTER AURARIA CAMPUS TIVOLI STARBUCKS Checker Author 11530.000 Approver 900 AURARIA PKWY DENVER, CO 80204 05/22/2015 CONSTRUCTION DOCUMENTS SHEET SHEET TITLE GENERAL G-0001 GENERAL INFORMATION G-0010 SPECIFICATIONS G-0011 SPECIFICATIONS G-0012 SPECIFICATIONS G-0013 SPECIFICATIONS G-0014 SPECIFICATIONS G-0015 SPECIFICATIONS G-0016 SPECIFICATIONS G-0017 SPECIFICATIONS G-0018 SPECIFICATIONS ARCHITECTURE A-0001 CODE PLAN INTERIORS I-1101 DEMOLITION FLOOR PLAN I-1102 DEMOLITION REFLECTED CEILING PLAN I-1103 FLOOR PLAN & DOOR SCHEDULE I-1104 PENETRATION PLAN I-1105 FF AND E PLAN I-1106 CASEWORK PLAN I-1107 CASEWORK UPPERS PLAN I-1108 REFLECTED CEILING PLAN I-1109 LIGHTING DIMENSION PLAN I-1110 FLOOR FINISH PLAN I-1111 WALL FINISH PLAN I-2101 INTERIOR ELEVATIONS I-2102 INTERIOR ELEVATIONS I-5001 DESIGN DETAILS I-5002 DESIGN DETAILS I-5004 CHILLED WALL CASE DETAILS I-6001 SCHEDULES STRUCTURAL S-1000 PARTIAL 1ST FLOOR STAIR FRAMING PLAN & SECTIONS MECHANICAL M-0001 MECHANICAL GENERAL INFORMATION M-0002 MECHANICAL SCHEDULES AND DETAILS M-0003 MECHANICAL SPECIFICATIONS M-1001 MECHANICAL DESIGN PLAN M-1011 MECHANICAL PIPING & FIRE PROTECTION DESIGN PLAN M-7001 MECHANICAL REMOVAL PLAN ELECTRICAL E-0001 ELECTRICAL GENERAL INFORMATION E-0002 ELECTRICAL SCHEDULES E-1001 ELECTRICAL LIGHTING DESIGN PLAN E-1011 ELECTRICAL POWER DESIGN PLAN E-1021 ELECTRICAL SYSTEMS DESIGN PLAN PLUMBING P-0001 PLUMBING GENERAL INFORMATION P-0002 PLUMBING SCHEDULES P-0003 PLUMBING SPECIFICATIONS P-1000 BELOW FLOOR PLUMBING PLAN P-1000C LEVEL 1 PLUMBING DESIGN PLAN - AREA C P-1000D LEVEL 1 PLUMBING DESIGN PLAN - AREA D P-1001 PLUMBING DESIGN PLAN P-5001 PLUMBING DETAILS P-7000 LEVEL 1 PLUMBING REMOVAL PLAN - AREA C P-7001 LEVEL 1 PLUMBING REMOVAL PLAN - AREA D

G-0001 - JEDI Balancing TIVOLI STARBUCKS...mep mechanical, ... m-1011 mechanical piping & fire protection design plan ... ps heat recovery return heat recovery supply hrr hrs

Embed Size (px)

Citation preview

Page 1: G-0001 - JEDI Balancing TIVOLI STARBUCKS...mep mechanical, ... m-1011 mechanical piping & fire protection design plan ... ps heat recovery return heat recovery supply hrr hrs

1. GENERAL CONTRACTOR SHALL VISIT THE SITE, REVIEW THEBUILDING SHELL DRAWINGS AS SUBMITTED BY THE LICENSEE'S ARCHITECTAND BECOME THOROUGHLY FAMILIAR WITH THE SITE CONDITIONS PRIORTO BIDDING OR CONSTRUCTION.

2. GENERAL CONTRACTOR SHALL CONSULT WITH LICENSEE'SARCHITECT AND STARBUCKS PROJECT DEVELOPMENT MANAGER TORESOLVE ANY CHANGES, OMISSIONS OR PLAN DISCREPANCIES PRIOR TOBIDDING OR CONSTRUCTION.

3. ALL WORK SHALL BE PERFORMED IN STRICT COMPLIANCE WITHLOCAL, COUNTY, STATE AND FEDERAL CODES AND ORDINANCES.

4. GENERAL CONTRACTOR SHALL VERIFY THE LOCATION OF ALLUTILITIES.

5. GENERAL CONTRACTOR TO VERIFY ALL DIMENSIONS, INCLUDINGCLEARANCES REQUIRED BY OTHER TRADES AND NOTIFY THE LICENSEE'SARCHITECT AND STARBUCKS PROJECT DEVELOPMENT MANAGER OF ANYDISCREPANCIES PRIOR TOPROCEEDING WITH THE WORK. ALL DIMENSIONSARE TO THE FACE OF THE FINISHED SURFACE UNLESS NOTED OTHERWISE.ALL DIMENSIONS TO BE TAKEN FROM DESIGNATED DATUM POINT. DO NOTSCALE DRAWINGS.

6. GENERAL CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTINGWALLS, FLOORS, CEILINGS, OR OTHER SURFACES IDENTIFIED TO REMAINTHAT MAY BECOME DAMAGED DURING THE COURSE OF THE WORK.

7. GENERAL CONTRACTOR IS RESPONSIBLE FOR OBTAINING PERMITSFOR FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICALSYSTEMS PRIOR TO INSTALLATION OF SUCH SYSTEMS.

8. GENERAL CONTRACTOR SHALL RETAIN ONE SET OF THE PLANS TONOTE AND DOCUMENT ALL CHANGES DURING CONSTRUCTION. THIS SETSHALL BE SUBMITTED TO THE STARBUCKS PROJECT DEVELOPMENTMANAGER FOR RECORD.

9. GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING DELIVERYOF MATERIALS FROM STARBUCKS CONTRACTED THIRD PARTY LOGISTICSDISTRIBUTION SERVICES AND VENDOR DIRECT SHIPMENTS.

10. RESPONSIBILITY FOR SUPPLY AND DELIVERY OF MATERIALS ANDEQUIPMENT IS IDENTIFIED IN THE DRAWING SCHEDULE SHEETS UNDER THECOLUMN LABELED "RESPONSIBILITY".

11. FOR THE PURPOSE OF THESE DOCUMENTS, TO “INSTALL” SHALLMEAN TO PROVIDE ALL FASTENERS, MISCELLANEOUS HARDWARE,BLOCKING, ELECTRICAL CONNECTIONS, PLUMBING CONNECTIONS, ANDOTHER ITEMS REQUIRED FOR A COMPLETE AND OPERATIONALINSTALLATION, UNLESS OTHERWISE NOTED.

12. ALL ITEM SUBSTITUTIONS MUST BE APPROVED BY THE STARBUCKSDESIGN MANAGER.

13. REFER TO ITEM CUTSHEETS FOR ADDITIONAL INFORMATION.

GENERAL NOTES

MAILINGADDRESS:

DESIGNMANAGER:

PROJECTDEVELOPMENTMANAGER:

LICENSEE:

ARCHITECTOF RECORD:

STRUCTURAL/CIVIL ENGINEER

MEP ENGINEEROF RECORD:

STARBUCKS COFFEE COMPANY2401 UTAH AVENUE SOUTHMS STOP: S-SD9SEATTLE, WASHINGTON 98134

ANDREW HUMAYDANSTARBUCKS COFFEE COMPANY60 SPEAR STREET, 7TH FLRSAN FRANCISCO, CA 94105(415)[email protected]

JACQUIE HANNIBALSTARBUCKS COFFEE COMPANY(206)[email protected]

AURARIA HIGHER EDUCATION CENTER1201 5th STREET, SUITE 370DENVER, CO 80204303.556.3349

KRISTINE ROUSE / BILL FURMANSLATERPAULL | HORD COPLAN MACHT1331 19th STREETDENVER, CO [email protected]@slaterpaull.com

STAN LEWIS PEANDERSON & HASTINGS CONSULTANTS, INC.12596 WEST BAYAUD AVENUE, SUITE 200LAKEWOOD, CO [email protected]

RICHARD MATTHIES, PEBCER ENGINEERING5420 WARD ROAD SUITE 200ARVADA, CO [email protected]

PROJECT CONTACTS INDEX OF SHEETS

SCOPE OF WORK

TENANT IMPROVEMENT AND ALTERATION OF EXISTING SPACE TO CAFE

VICINITY PLAN

SB / GCSB / FCGC / GCLC / GCLC / LCFC / GC

RESPONSIBILITY LEGEND - LICENSED STORES

FURNISHED BY STARBUCKS / INSTALLED BY LICENSEE'S GENERAL CONTRACTORFURNISHED BY STARBUCKS / INSTALLED BY STARBUCKS FIXTURE CONTRACTORFURNISHED BY LICENSEE'S GENERAL CONTRACTOR / INSTALLED BY LICENSEE'S GENERAL CONTRACTORFURNISHED BY LICENSEE / INSTALLED BY LICENSEE'S GENERAL CONTRACTORFURNISHED BY LICENSEE / INSTALLED BY LICENSEEFURNISHED BY STARBUCKS FIXTURE CONTRACTOR / INSTALLED BY LICENSEE'S GENERAL CONTRACTOR

CUSTOM DESIGN ID KEY

SIGNAGEGRAPHICS AND ARTWORK

SITEDOORS

DATA DEVICESPECIALITY EQUIPMENT

CASEWORKFURNITURE

LIGHTING FIXTUREPLUMBING / MECHANICAL

FINISHES - PAINTFINISHES - FLOOR TREATMENT

FINISHES - WALL TREATMENTFINISHES - CEILING TREATMENT

"S" x0000 - x0999 "G" x1000 - x1099 "Y" x1100 - x1199 "D" x2000 - x2999 "A" x3000 - x3999 "E" x4000 - x4999 "C" x5000 - x5999 "F" x6000 - x6999 "L" x7000 - x7999 "P" / "M" x8000 - x8999 x9000 - x9199 "T" x9200 - x9399 "Q" / "R" x9400 - x9799 "U" x9800 - x9999

SCHEDULE PREFIX

A - DATA DEVICE SCHEDULEB - WALL BASE SCHEDULEC - CASEWORK SCHEDULED - DOOR SCHEDULEE - SPECIALTY EQUIPMENT SCHEDULEF - FURNITURE SCHEDULEG - GRAPHICS AND ARTWORK SCHEDULEL - LIGHTING FIXTURE SCHEDULEM - MECHANICAL EQUIPMENT SCHEDULEP - PLUMBING FIXTURE SCHEDULEQ - WALL TREATMENT (AREA) SCHEDULER - WALL TREATMENT (LENGTH) SCHEDULES - SIGNAGE SCHEDULET - FLOOR TREATMENT SCHEDULEU - CEILING TREATMENT SCHEDULEW - WINDOW SCHEDULEY - SITE SCHEDULE

ABBREVIATIONS

3PL THIRD PARTY LOGISTICS

AC AIR CONDITIONINGACC ACCESSIBLEACT ACOUSTICAL CEILING TILEADJ ADJUSTABLEAFF ABOVE FINISHED FLOORAHJ AUTHORITIES HAVING JURISDICTIONAMP AMPEREAOR ARCHITECT OF RECORDAPPROX APPROXIMATE

BOH BACK OF HOUSEBLDG BUILDING

CAB CABINETCKT CIRCUITCL CENTER LINECLG CEILINGCLR CLEAR OR CLEARANCECOL COLUMNCOMP COMPARTMENTCONST CONSTRUCTIONCONT CONTINUOUSCTR CENTERCW COLD WATERCWF COLD WATER FILTEREDCX COMMISSIONINGCXA COMMISSIONING AGENT

DEG DEGREESDET DETAILDIA DIAMETERDISP DISPENSERDIM DIMENSIONDM STARBUCKS DESIGN MANAGERDN DOWNDWG(S) DRAWING(S)

EA EACHEC ELECTRICAL CONTRACTOREG EXHAUST GRILLEEL ELEVATIONELEC ELECTRICALEM EMERGENCYEQ EQUALEQUIP EQUIPMENTEXIST OR (E) EXISTINGEXP EXPOSEDEXT EXTERIOR

FC STARBUCKS FIXTURE CONTRACTOR/INSTALLERFCO FLOOR CLEANOUTFD FLOOR DRAINFF&E FURNITURE, FIXTURE AND EQUIPMENTF&I FURNISH AND INSTALLFIN FINISHFLR FLOORFOH FRONT OF HOUSEFRP FIBERGLAS REINFORCED PANELFS FLOOR SINKFT FOOT OR FEET

GC GENERAL CONTRACTORGFCI GROUND FAULT CIRCUIT INTERRUPTERGND GROUND

HC HOLLOW COREHDW HARDWAREHM HOLLOW METALHORIZ HORIZONTALHR HOURHS HAND SINKHT HEIGHTHVAC HEATING, VENTILATING AND AIR CONDITIONINGHW HOT WATER

ID INSIDE DIAMETER

LC LICENSEELL LANDLORDLV LOW VOLTAGE

MAX MAXIMUMMC MECHANICAL CONTRACTORMECH MECHANICALMEP MECHANICAL, ELECTRICAL AND PLUMBINGMFR MANUFACTURERMIN MINIMUMMS MOP SINK

NIC NOT IN CONTRACTNTS NOT TO SCALE

OA OVER ALLOC ON CENTEROD OUTSIDE DIAMETER

PC PLUMBING CONTRACTORPD STARBUCKS PRODUCTION DESIGNERPDM STARBUCKS PROJECT DEVELOPMENT MANAGERPLAM PLASTIC LAMINATEPOS POINT OF SALE

R RADIUSREF REFERENCEREQ(‘D) REQUIRE(D)REV REVISIONRG RETURN GRILLERND ROUNDRT ROOF TOP

SB STARBUCKSSC SOLID CORESF SQUARE FEETSHT SHEETSIM SIMILARSPEC SPECIFICATIONSQ SQUARESST STAINLESS STEELSUSP SUSPENDED

TEL TELEPHONETEMP TEMPORARYTW TEMPERED WATERTYP TYPICAL

UC UNDERCOUNTERUON UNLESS OTHERWISE NOTED

VD VENDOR DIRECTVERT VERTICALVIF VERIFY IN FIELD

W SANITARY WASTEWH WATER HEATERWP WEATHER PROOFWCO WALL CLEANOUT

PXXX-ES

X' XX"

X

N

NORTHARROW

XXXX AFF

ARCHITECTURAL SYMBOL LEGEND

XXXXXW

XX

Scale: X =X

0 2 4 8

GRAPHICSCALE

DATUMPOINT

EXTERIORELEVATIONCALL-OUT

INTERIORELEVATIONCALL-OUT

SECTIONCALL-OUT

DETAILCALL-OUT

REVISIONTAG

PAINTTAG

XXXXXX

DESIGN IDTAG

XXXXXD

DOORTAG

WINDOWTAG

SHEETNOTE

CALLOUT

ABOVE FINISHFLOOR

HEIGHT TAG

FINISH FACETO FINISH

FACEDIMENSION

REVISIONCLOUD

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5

A

B

C

D

1 2 3 4 5

THESE RECORD DRAWINGS HAVE BEENPREPARED, IN PART, ON THE BASIS OF

INFORMATION COMPILED ANDFURNISHED BY OTHERS. THE ARCHITECT

WILL NOT BE RESPONSIBLE FOR ANYERRORS OR OMISSIONS WHICH HAVE

BEEN INCORPORATED INTO THISDOCUMENT AS A RESULT.

P 303.607.0977www.slaterpaull.com

1331 Nineteenth StreetDenver, CO. 80202

5/26

/201

5 4:

36:3

7 PM

C:\U

sers

\bfu

rman

\Doc

umen

ts\1

1530

Tiv

oli S

tarb

ucks

_A_

2015

_bfu

rman

.rvt

G-0001G-0001G-0001G-0001

GENERALINFORMATION

AURARIA HIGHEREDUCATION CENTER

AURARIA CAMPUSTIVOLI STARBUCKS

CheckerAuthor

11530.000

Approver

900 AURARIA PKWYDENVER, CO 80204

05/22/2015 CONSTRUCTION DOCUMENTS

SHEET SHEET TITLE

GENERAL

G-0001 GENERAL INFORMATION

G-0010 SPECIFICATIONS

G-0011 SPECIFICATIONS

G-0012 SPECIFICATIONS

G-0013 SPECIFICATIONS

G-0014 SPECIFICATIONS

G-0015 SPECIFICATIONS

G-0016 SPECIFICATIONS

G-0017 SPECIFICATIONS

G-0018 SPECIFICATIONS

ARCHITECTURE

A-0001 CODE PLAN

INTERIORS

I-1101 DEMOLITION FLOOR PLAN

I-1102 DEMOLITION REFLECTED CEILING PLAN

I-1103 FLOOR PLAN & DOOR SCHEDULE

I-1104 PENETRATION PLAN

I-1105 FF AND E PLAN

I-1106 CASEWORK PLAN

I-1107 CASEWORK UPPERS PLAN

I-1108 REFLECTED CEILING PLAN

I-1109 LIGHTING DIMENSION PLAN

I-1110 FLOOR FINISH PLAN

I-1111 WALL FINISH PLAN

I-2101 INTERIOR ELEVATIONS

I-2102 INTERIOR ELEVATIONS

I-5001 DESIGN DETAILS

I-5002 DESIGN DETAILS

I-5004 CHILLED WALL CASE DETAILS

I-6001 SCHEDULES

STRUCTURAL

S-1000 PARTIAL 1ST FLOOR STAIR FRAMING PLAN & SECTIONS

MECHANICAL

M-0001 MECHANICAL GENERAL INFORMATION

M-0002 MECHANICAL SCHEDULES AND DETAILS

M-0003 MECHANICAL SPECIFICATIONS

M-1001 MECHANICAL DESIGN PLAN

M-1011 MECHANICAL PIPING & FIRE PROTECTION DESIGN PLAN

M-7001 MECHANICAL REMOVAL PLAN

ELECTRICAL

E-0001 ELECTRICAL GENERAL INFORMATION

E-0002 ELECTRICAL SCHEDULES

E-1001 ELECTRICAL LIGHTING DESIGN PLAN

E-1011 ELECTRICAL POWER DESIGN PLAN

E-1021 ELECTRICAL SYSTEMS DESIGN PLAN

PLUMBING

P-0001 PLUMBING GENERAL INFORMATION

P-0002 PLUMBING SCHEDULES

P-0003 PLUMBING SPECIFICATIONS

P-1000 BELOW FLOOR PLUMBING PLAN

P-1000C LEVEL 1 PLUMBING DESIGN PLAN - AREA C

P-1000D LEVEL 1 PLUMBING DESIGN PLAN - AREA D

P-1001 PLUMBING DESIGN PLAN

P-5001 PLUMBING DETAILS

P-7000 LEVEL 1 PLUMBING REMOVAL PLAN - AREA C

P-7001 LEVEL 1 PLUMBING REMOVAL PLAN - AREA D

Page 2: G-0001 - JEDI Balancing TIVOLI STARBUCKS...mep mechanical, ... m-1011 mechanical piping & fire protection design plan ... ps heat recovery return heat recovery supply hrr hrs

EXISTING

4"

ABBREVIATIONS AND DESCRIPTIONS

ALL SYMBOLS IN LEGEND MAY NOT NECESSARILY BE USED ON THIS PROJECT

MECHANICAL LEGEND

SHEET METAL FITTINGS AND EQUIPMENT

PIPING DESIGNATIONS, FITTINGS AND EQUIPMENT

CONTROLS DEVICES

BEVELED TAP OFF OF TOP

H

T

VCP

TYP

(E)

(R)

(N)

DIA, D

C

EL.

CI

CL

AFF

AP

FIRE DEPARTMENT CONNECTION

MANUAL VOLUME DAMPER

MOTORIZED DAMPER

MVD

MD

MIXED AIR

INVERT ELEVATION

MA

I.E.

FDC

EA OUTSIDE AIR

SUPPLY AIR

RETURN AIR

NIC

RA

SA

NORMALLY OPEN

NOT IN CONTRACT

NORMALLY CLOSED

OA

NC

NO

ROUND DUCT UP (1.5D ELBOW)

AIR FLOW - SUPPLY

AIR FLOW DIRECTION

RELOCATED

VITRIFIED CLAY PIPE

NEW

EXISTING

TYPICAL

UNIT MOUNTED THERMOSTAT

HUMIDISTAT

TRANSFER DUCT & GRILLES

M

BD

T

VANED ELBOW

LINEAR SLOT DIFFUSER

VANED ELBOW

RADIUS ELBOW; 1 DIAMETER

DOUBLE VANED ELBOW

CONDENSER WATER SUPPLY

CHILLED WATER RETURN

CHILLED WATER SUPPLY

HEATING WATER RETURN

HEATING WATER SUPPLY

LOW PRESSURE STEAM

CONDENSER WATER RETURNCR

LPR

LPS

HWR

CWR

CS

CWS

HWS

WALL MOUNTED THERMOSTATN - INDICATES NIGHTS - INDICATES SENSOR

FLEXIBLE DUCT CONNECTION

MOTORIZED DAMPER MOTOR

MANUAL VOLUME DAMPER

FLEXIBLE DUCT

DOOR UNDERCUT

ACCESS PANEL

BACK DRAFT DAMPER

REFRIGERANT HOT GAS

REFRIGERANT SUCTION

REFRIGERANT LIQUID

RHG

RS

RL

MEDIUM PRESSURE STEAM

HIGH PRESSURE STEAM

HPR

HPS

MPR

MPS

SUPPLY AIR DIFFUSER

RADIUS ELBOW

F

UC

TCOAD

TCEAD

VENT THROUGH ROOFVTR

S

FS

RETURN DUCT UP

SUPPLY DUCT UP

EXHAUST DUCT UP

F

INSTRUMENT AIR SIGNAL

INTERNAL SYSTEMSOFTWARE OR DATA LINK

AIR FLOW DIRECTION ARROW

FLOW SWITCH

FLOW TRANSMITTER

FS

FT

H HUMIDITY SENSOR

PDT

PI

PDS

PRESSURE DIFFERENTIALTRANSMITTER

POSITION INDICATOR

PRESSUREDIFFERENTIAL SWITCH

PSL PRESSURE SWITCH LOW

PSH PRESSURE SWITCH HIGH

TSH

TSL TEMPERATURE SWITCH LOW

TEMPERATURE SWITCH HIGH

T TEMPERATURE SENSOR

MANUAL SWITCH

P PRESSURE SENSOR

S

SP STATIC PRESSURE SENSOR

SENSOR

CO CARBON MONOXIDE

N

AQUASTATT

PRESSURE SWITCH

PRESSURE INDICATORPI

PS

HEAT RECOVERY RETURN

HEAT RECOVERY SUPPLY

HRR

HRS

INDICATOR LIGHT

CONDENSATE DRAINCD

(F) FUTURE

ROUND DUCT DOWN (1.5D ELBOW)

RETURN DUCT DOWN(MITERED ELBOW)

EXHAUST DUCT DOWN(MITERED ELBOW)

SUPPLY DUCT DOWN(MITERED ELBOW)

BOD

BOP

UNO UNLESS NOTED OTHERWISE

CONDENSER WATER (COMMON)

PRE-COOLING WATER RETURN

PRE-COOLING WATER SUPPLY

PWR

CDW

PWS

NON-POTABLE WATERNP

POTABLE (COLD) WATERCW

GASG

UNIT HEATER

EXHAUST FAN ON ROOF

BASEBOARD HEATER

SOUND ATTENUATOR

ABOVE FINISHED FLOOR

ACCESS PANEL

BOTTOM OF DUCT

BOTTOM OF PIPE

COMMON

CAST IRON

CENTER LINE ELEVATION

DIAMETER

EXHAUST AIR

ARROW PARALLEL TOLINE INDICATES PITCH

ARROW IN LINE INDICATESDIRECTION OF FLOW

LOW PRESSURE STEAM(CONDENSATE) RETURN

MEDIUM PRESSURE STEAM(CONDENSATE) RETURN

HIGH PRESSURE STEAM(CONDENSATE) RETURN

ROUND 90° CONICAL TAKE OFFFROM RECTANGLE TRUNK

RECTANGULAR 90° TAKEOFFFROM RECTANGULAR TRUNK

RECTANGULAR 90° TAKEOFFON END OF MAIN W/MIN. 12"AIR CUSHION DOWNSTREAM ROUND 90° CONICAL TAKEOFF

FROM RECTANGULAR TRUNK W/MANUAL VOLUME DAMPER

ROUND 90° SPIN-IN TAKEOFFFROM RECTANGULAR TRUNKW/MANUAL VOLUME DAMPER

DUCT TRANSITION CONCENTRIC

DUCT TRANSITION ECCENTRIC

SIDE TAKEOFF ATREGISTER OR GRILLE

BOTTOM TAKEOFF ATDIFFUSER. PROVIDE TYPICALPROJECT BALANCING

SIDE TAKEOFF AT DIFFUSER

RECTANGULAR 90° TAKEOFFWITH BEVELED TAP

ROUND DUCT DROP/RISE IN PLAN

RECTANGLE DUCTDROP/RISE IN PLAN

DIRECTION OF VIEW

M-?

1

DRAWN ON THIS SHEET

BOX ##__

A PICTURE DESIGNATION

NEW

LIGHT LINE WEIGHT FOREQUIPMENT, PIPING, SYMBOLS,TEXT, ETC. INDICATESEXISTING CONDITIONS WITHNEW WORK SHOWN AS DARK

HEATING COIL

CONTROL/COILACCESS

INDICATESSUPPLYAND RETURNPIPING TO UNIT

EQUIPMENTTERMINALOR VAV BOX

CFM

GPM

TB-103

650

1.2

POINT OFCONNECTION NEWTO EXISTING

STEAM TRAP

TEMPERATURE GAUGE

METERM

TEE DOWN

ELBOW DOWN

TEE UP

BRANCH-BOTTOM CONNECTION

BRANCH-TOP CONNECTION

RISE OR DROP

ELBOW UP

UNION

PIPE CAP OR PLUG

PIPE ALIGNMENT GUIDE

PIPE ANCHOR

STRAINER

FLEXIBLE CONNECTION

STRAINER W/BLOWOFF VALVE

EXPANSION JOINT

PIPE CONNECTION HOSE END BALL VALVE W/ CAP

VENTURI

VACUUM BREAKER

WELL

2-WAY CONTROL VALVE

3-WAY CONTROL VALVE

PRESSURE REDUCING VALVE

PRESSURE/TEMPERATURE TAP

AUTOMATIC AIR VENT

PRESSURE GAUGE W/ COCK

CIRCUIT SETTER

GLOBE VALVE

CHECK VALVE

TEMPERATURE/PRESSURE RELIEF VALVE

BUTTERFLY VALVE

BALANCING VALVE

BALL VALVE

PLUG VALVE

SOLENOID VALVE

CALIBRATED BALANCE VALVE

GAUGE W/ PIGTAIL

MANUAL AIR VENT

NEEDLE VALVE

PRESSURE INDEPENDENT VALVE

GAS COCK

GAS PRESSURE REGULATOR

BASE MOUNTED PUMP

IN-LINE PUMP

2-WAY VALVE

DUCT SMOKE DETECTORS

OPPOSED BLADE DAMPER

PARALLEL BLADE DAMPER

VFD

MS MOTOR STARTER

VARIABLE FREQUENCY DRIVE

DM DAMPER ACTUATOR

H HUMIDIFIER

CS CURRENT SENSOR

HORNH

FLOW SWITCHFS

DIRECTION OF CUT

SECTION DESIGNATION

TCRAD

RETURN OREXHAUSTREGISTER/GRILLE

UNSHADED AREAS INDICATEDIRECTION OF AIR FLOW (IF NOSHADING, 4-WAY ORADJUSTABLE)

ROUND DUCT TAKE OFFFROM TOP OF DUCT

BURIED,UNDERFLOOR ORUNDER DUCT

AIR FLOW -RETURNOR EXHAUST

4"

TEMPERATURE CONTROLEXHAUST AIR DAMPER

TEMPERATURE CONTROLOUTSIDE AIR DAMPER

TEMPERATURE CONTROLRETURN AIR DAMPER

EQUIPMENT TYPE

FLOOR #__IF MULTIPLE

TRANSITIONTOSIZE ON PLANS

CONTROLENCLOSURE

DASHED INDICATESEXISTING TO BE REMOVED

FIRE/SMOKE DAMPER (#REFERS TO SCHEDULE)

FIRE DAMPER

SMOKE DAMPER

CEILING AIR DEVICEWITH FIRE DAMPER

DASHED INDICATESEXISTING TO BE REMOVED

R

DR

D

SOFT COLD WATERSCW

CO CARBON DIOXIDE

RTS

FEK

FED

FECA

FECO2

FEABC

FEBC

WF

PS

AA

VS

R

P

CO

FA-?

1

A

RP

XX

SP

XX

F

ABBREVIATIONS and DESCRIPTIONS

ALL SYMBOLS IN LEGEND MAY NOT NECESSARILY BE USED ON THIS PROJECT

FIRE AND LIFE SAFETY LEGEND

4"

FIRE ALARM

FIRE EXTINGUISHERS

FIRE PROTECTION VALVES and FITTINGS

FIRE SPRINKLERS

V

A

H

J

LIFE SAFETY

FDC

PA

STANDPIPE

DAS

FIREMAIN

DRY/AUTOMATIC SPRINKLER

SP/AS

FM

SP

AUTOMATIC SPRINKLERAS

TEE DOWN

ELBOW DOWN

TEE UP

BRANCH-BOTTOM CONNECTION

BRANCH-TOP CONNECTION

RISE OR DROP

ELBOW UP

UNION

PIPE CAP OR PLUG

PIPE GUIDE

PIPE ANCHOR

STRAINER

FLEXIBLE CONNECTION

STRAINER W/BLOWOFF VALVE

EXPANSION JOINT

BACKFLOW PREVENTER

VENTURI

PRESSURE REDUCING VALVE

GLOBE VALVE

CHECK VALVE

BALL VALVE

SOLENOID VALVE

MANUAL AIR VENT

EXISTING TO BE REMOVED

DIRECTION OF VIEW

DRAWN ON THIS SHEET

SECTION DESIGNATION

PICTURE DESIGNATION

4"

EXIST.

NEW

DIA, D DIAMETER

EL.

C

LC

CI

AP

AFF

CENTER LINE ELEVATION

ABOVE FINISHED FLOOR

ACCESS PANEL

COMMON

CAST IRON

INVERT ELEVATIONI.E.

NC

NO

NIC

VITRIFIED CLAY PIPE

NORMALLY CLOSED

NOT IN CONTRACT

NORMALLY OPEN

TYPICAL

EXISTING

NEW

RELOCATED

(N)

(R)

(E)

TYP

VCP

VENT THROUGH ROOFVTR

FIRE DEPT. CONNECTION

DSP DRY/STANDPIPE

CLEAN AGENTCA

WATERMISTWM

CO

D

RM

FARP

FSCP

SPEAKER/HORN

FIRE ALARM PULL STATION

MINI HORN

CARBON MONOXIDE DETECTOR

SPEAKER

SPEAKER/HORN

FIRE ALARM PHONE

ABORT SWITCH

MAGNETIC DOOR HOLDER

FIRE SMOKE DAMPER

MONITOR MODULE

CONTROL MODULE

RELEASE MODULE

FIRE ALARM RELEASE PANEL

FIRE ALARM ANNUNCIATOR

FIRE ALARM PANEL

DUCT DETECTOR

FIRE ALARM CONTROL PANEL

R/F

R/C RATE COMPENSATION

F FIXED TEMPERATURE

-

-

-

C COMBINATION SMOKE/-

I IONIZED-

BT BEAM TRANSMITTER-

BR BEAM RECIEVER-

ASD AIR SAMPLING-

F FLAME-

UV ULTRA VIOLET-

IR INFRAED-

VR VISIBLE RADIATION-

HEAT DETECTOR

FLAME DETECTOR

SMOKE DETECTOR

FIRE FIGHTER CONTROL PANEL

TYPE 'ABC'

TYPE 'BC'

PREACTIONAUTOMATIC SPRINKLER

COMBINATION STANDPIPE/AUTOMATIC SPRINKLER

DELUGE AUTOMATICSPRINKLER

FIRESTANDPIPEDESIGNATION

FIRE SPRINKLERRISERDESIGNATION

LIGHT LINE WEIGHT FOREQUIPMENT, PIPING, SYMBOLS,TEXT, ETC. INDICATES EXISTINGCONDITIONS WITH NEW WORKSHOWN AS DARK

DASHED INDICATESEXISTING TO BEREMOVED

POINT OF CONNECTIONNEW TO EXISTING

TEMPERATURE/PRESSURE RELIEF VALVE

PRESSURE GAUGEWITH GUAGE COCK

HOSE END BALL VALVEWITH VACUUM BREAKER

FIRE HOSE VALVE CABINET(SURFACE MOUNTED)

BACKFLOW PREVENTER(REDUCED PRESSURE)

FIRE HOSE VALVECABINET (RECESSED)

BUTTERFLY VALVEW/TAMPER SWITCH

FREE STANDING FIREDEPARTMENT CONNECTION

CARBON MONOXIDE DETECTORWITH AUDIBLE ALARM

xxcd

15cd

F

COMBINATION: RATEOF RISE AND FIXEDTERMPERATURE

MAIN DRAIN ASSEMBLY

FIRE DEPARTMENTCONNECTION

WATER FLOW SWITCH

ANGLE VALVE

DRY PIPE VALVE

PRESSURE SWITCH

PREACTION VALVE

POST INDICATOR VALVE

FIRE HOSE RACK

FUTURE(F)

TRAVELDISTANCE

66.8 ft²

2 OCC.46.45

B

OCCUPANCY FLOOR AREA

OCCUPANT LOADFACTOR (OLF)

OCCUPANT LOAD

EXITING LOAD1 HR. FIRE PARTITION

2 HR. FIRE/SMOKE BARRIER

30 MIN. FIRE PARTITION

3 HR. FIRE RESISTANCE

WALL RATING LEGEND

STORAGE/PARKINGGROUP (S-1/S-2)

MEMORY CAREGROUP (I-2)

ASSISTED LIVINGGROUP (I-1)

INDEPENDENTLIVINGGROUP (R-2)

X

"DISTANCE IN FT"

30 MINUTE FIRE RATEDSMOKE PARTITION

P

WP

VALVE SUPERVISORYSWITCH

FIRE HYDRANT

xxcd

LHD

15cd

SS - SUPPLY

R - RETURN

REMOTE TEST SWITCH

FABP FIRE ALARM BOOSTER PANEL

ASFP

ACCESS CONTROL PANELACP

DACT

GRAPHIC MAPGMAP

ADDRESSABLE OUTPUT MODULEAOM

WITH GUARDWG

UNLESS OTHERWISE NOTEDUNO

WEATHER PROOFWP

DRY UPRIGHT SPRINKLER

UPRIGHT SPRINKLER

DRY PENDANT SPRINKLER

PENDANT SPRINKLER

SPRINKLER WITH GUARD

DRY SPRINKLER WITH GUARD

HORIZONTAL SIDEWALL SPRINKLER

OUTSIDE SPRINKLER

DRY OUTSIDE SPRINKLER

WATER SPRAY NOZZLE - DELUGE

WATER WASH WINDOW SPRINKLER

DRY SIDEWALL SPRINKLERC CONCEALED-R RECESSED-

TYPE 'CO2'TYPE 'CA'

TYPE 'D'

TYPE 'K'

V = BELLVS = BELL/STROBEC = CHIMECS = CHIME/STROBE

FIRE OR EMERGENCY PHONEFIRE OREMERGENCY PHONE- ACCESSIBLE

FIRE OR EMERGENCYPHONE - HANDSET

FIRE OR EMERGENCYPHONE - JACK

F

R RATE OF RISE ONLY-

P PHOTOELECTRIC-

HEAT DETECTOR

WATER FLOW SWITCH

PRESSURE SWITCH

VALVE SUPERVISORY SWITCH

LOW AIR PRESSURE ALARM

VS

WF

PS

AA

FIRE HOSE VALVE

SYMBOLS LEGEND

OCCUPANCY LEGEND

LIGHT HAZARD0.10GPM/1500 SQ. FT.

SPRINKLER DENSITY

ORDINARY HAZARDG1 0.15GPM/1500 SQ. FT.

EXTRA HAZARD G10.30 GPM/2500 SQ. FT.

ORDINARY HAZARDG2 0.20 GPM/1500SQ. FT.

NOTE: "EC" DENOTES EXTENDED COVERAGE SPRINKLER

DELUGE VALVE

NOTE: SIZES INDICATED IN SPECS / DRAWINGS

HEAT DETECTOR -LINE TYPE (CABLE)

STROBEWALL MOUNTED

STROBECEILING MOUNTED

SPEAKER/HORN/STROBE CEILING MOUNTED

SPEAKER/HORN/STROBEWALL MOUNTED WPDENOTES WEATHERPROOF

SMOKE DETECTORPHOTOELECTRIC WITH CARBONMONOXIDE DETECTION

FIRE FIGHTERS SMOKECONTROL PANEL

DIGITAL ALARMCOMMUNICATOR TERMINAL

AIR SAMPLING CONTROLDETECTION PANEL

LOW AIR SUPERVISORYSWITCH PRESSURE ALARM

GATE VALVE IN VERTICALWITH TAMPER SWITCH

NON-INDICATING VALVE(NON-RISING STEM)

T

T

T

T

T

T

T

FAA

FACP

FAP

FFCP

CM

MM

EXTRA HAZARD G20.40 GPM/2500 SQ. FT.

FACTORY (I-1)

CO

M

S

FS

OWNERSHIP OF DOCUMENTS:ALL DRAWINGS, SPECIFICATIONS AND OTHER WORK PRODUCT OF THE ENGINEER FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF THE ENGINEER WHETHER THEPROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE OF THE ENGINEER BY THE OWNER OF EXTENSIONS OF THIS PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER SHALL BE AT THEOWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE ENGINEER FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THEENGINEER'S INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER.

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.slaterpaull.com

1331 Nineteenth StreetDenver, CO. 80202

THESE RECORD DRAWINGS HAVE BEENPREPARED, IN PART, ON THE BASIS OF

INFORMATION COMPILED AND FURNISHEDBY OTHERS. THE ARCHITECT WILL NOT BE

RESPONSIBLE FOR ANY ERRORS OROMISSIONS WHICH HAVE BEEN

INCORPORATED INTO THIS DOCUMENT ASA RESULT.

5/2

6/2

015 2

:34:0

6 P

M

C:\

Users

\JP

EC

KO

VIT

CH

\Docum

ents

\Local R

evit F

iles\1

5915074 -

Tiv

oli

Sta

rbucks -

ME

P_R

15_jp

eckovitch.r

vt

M-0001

MECHANICALGENERALINFORMATION

Starbucks CoffeeCompany

AURARIA CAMPUSTIVOLI

RDM

JMP

65043-001

RDM

900 AURARIA PKWYDENVER, CO 80204

05/26/15 CONSTRUCTION DOCUMENTS

MECHANICAL SHEET LISTM-0001 MECHANICAL GENERAL INFORMATION

M-0002 MECHANICAL SCHEDULES AND DETAILS

M-0003 MECHANICAL SPECIFICATIONS

M-1001 MECHANICAL DESIGN PLAN

M-1011 MECHANICAL PIPING & FIRE PROTECTION DESIGN PLAN

M-7001 MECHANICAL REMOVAL PLAN

THE "ENGINE" SPACE OF STARBUCKS WILL REQUIRE THE INSTALLATION OF A NEW VAVTERMINAL WITH HEATING WATER HEAT COIL. DISTRIBUTED FROM THIS VAV WILL BE NEW.CONTROLS FOR THIS VAV WILL BE JOHNSON "METASYS" AND WILL BE CONNECTED TOBUILDING AND CAMPUS BAS SYSTEM.

THE PROJECT SCOPE FOR THE STARBUCKS OPEN SPACE WILL INCLUDE NEW SUPPLYDIFFUSER DISTRIBUTION FROM THE EXISTING VAV ZONE PRESENTLY INSTALLED ABOVE THECEILING.

MECHANICAL NARRATIVE

LOCATION:

OUTDOOR CONDITIONS:

INDOOR CONDITIONS:

ENVELOPECHARACTERISTICS:

INTERNAL LOADS:

OUTDOOR AIR VENTILATION RATE:

SPECIAL CONDITIONS:

SUMMERWINTER

COOLINGHEATING

(E) GLASS SHADING COEF.:(E) GLASS "U" FACTOR:(E) GLASS LOW-E:(E) GLASS INTERIOR SHADING:(E) WALL INSULATION "R":(E) ROOF INSULATION "R":

AVERAGE LIGHTING:AVERAGE MISC. ELECTRICAL:AVERAGE OCCUPANT LOAD:

LOAD CALCULATION DESIGN DATA

= 7.5 CFM/PERSON

= (1.0) WATTS/S.F.= (0.9) WATTS/S.F.= (150) S.F./PERSON

= (0.80)= (0.45)= (N)= (Y)= (14.0)= (NA)

= (93 DEGREES F/ 59 DEGREES (MEAN COINCIDENT W.B.)= (-10) DEGREES F

= (75) DEGREES F= (68) DEGREES F

Denver, Colorado; 5280 FT. ELEVATION,39° 5' DEGREES LATITUDE, 104° 5' DEGREESLONGITUDE

E. NATURAL GAS INPUTS ARE AT SEA LEVEL.

D. HORSEPOWERS ARE CORRECTED FOR ALTITUDE.

C. HEATING AND COOLING CAPACITIES ARE AT ALTITUDE OF PROJECT.

B. STATIC PRESSURES AND AIR PRESSURE DROPS ARE AT SEA LEVEL.

A. CFM IS AT ALTITUDE OF PROJECT.

23. CONVENTIONS USED IN THE PRESENTATION OF THE CONTRACT DOCUMENTS:

22. EXISTING EQUIPMENT AS NOTED ON THE DRAWINGS SHALL BE RETURNED TO THEOWNER AT THEIR DESIGNATED LOCATION.

21. EQUIPMENT E.E.R. AND/OR C.O.P. VALUES SHALL COMPLY WITH THE CURRENT EDITIONOF ASHRAE 90.1.

20. PROVIDE REDLINE MARK-UPS FOR ANY FIELD CHANGES OR MODIFICATIONS ON THECONSTRUCTION DOCUMENTS. REDLINE DRAWINGS SHALL BE PROVIDED WHETHERCOORDINATION DRAWINGS ARE REQUIRED OR NOT.

19. MOUNT THERMOSTAT AT 54" ON CENTER ABOVE FINISHED FLOOR UNLESSOTHERWISE NOTED. ADA REQUIREMENT.

18. RIGID INLET DUCTS TO VAV BOXES SHALL BE THE SAME SIZE AS THE VAV BOX INLETCONNECTION UNLESS NOTED OTHERWISE FOR A MINIMUM OF THREE DIAMETERS OFSTRAIGHT DUCT.

16. SPIN-IN FITTINGS TO VAV BOXES AND DIFFUSERS SHALL BE CONICAL TYPE (EXCEPTLOCATIONS WHERE LISTED DUCT HEIGHT DOES NOT ACCOMMODATE). SPIN-INFITTINGS TO DIFFUSERS SHALL INCLUDE AN INTEGRAL MANUAL VOLUME DAMPER.

15. ALL DUCT DIMENSIONS ARE OUTSIDE DIMENSIONS. WHERE DUCT LINER IS USED, THETHICKNESS OF THE LINER TO MAINTAIN THE CLEAR INSIDE DIMENSION HAS BEENINCLUDED. REFER TO DUCT INSULATION / LINER SCHEDULE AND/OR DIVISION 23 OFTHE SPECIFICATIONS.

14. CONTRACTOR SHALL CONSTRUCT AND INSTALL DUCTWORK ACCORDING TO SMACNASTANDARDS AS A MINIMUM REQUIREMENT. REFER TO SPECIFICATIONS FORADDITIONAL INFORMATION.

13. PROVIDE MANUAL AIR VENTS ON CLOSED SYSTEM WATER PIPING AT ALL CHANGES INELEVATION DOWNWARD IN DIRECTION OF WATER FLOW.

12. ALL EXISTING EQUIPMENT TO BE REMOVED SHALL HAVE ALL RELATEDHOUSEKEEPING PADS, PIPING, CONTROLS, GAUGES, ELECTRICAL SERVICE,HANGERS, SUPPORTS AND ANY MISCELLANEOUS RELATED SERVICE OR PARTS...

11. CONTRACTOR SHALL PROVIDE SUBMITTALS ON ITEMS LISTED IN THE MECHANICALSCHEDULES AND AS REQUIRED IN EACH SECTION OF SPECIFICATION TO THEENGINEER/OWNER FOR REVIEW PRIOR TO THE ORDER, PURCHASE OR INSTALLATIONOF THESE SAME ITEMS.

10. ALL MECHANICAL SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THECURRENT VERSION OF INTERNATIONAL BUILDING CODE, 2009 INTERNATIONAL FIRECODE OR NFPA 2012, 2012 INTERNATIONAL MECHANICAL CODE, AND 2009INTERNATIONAL PLUMBING CODE AND 2012 INTERNATIONAL ENERGY CONSERVATIONCODE. REFER TO ARCHITECTURAL CODE PLAN.

9. CONTRACTOR SHALL FIELD VERIFY ALL MECHANICAL ITEMS PRIOR TO COMMENCINGNEW WORK AND FOR SUBMITTING A BID. NO ADDITIONAL COST WILL BE ALLOWEDFOR CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS.

8. CONTRACTOR SHALL CLOSELY COORDINATE NEW MECHANICAL WITH ALL NEW ANDEXISTING MECHANICAL, PLUMBING, ELECTRICAL, FIRE PROTECTION, ARCHITECTURALAND STRUCTURAL MEMBERS.

7. CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATION AND INSTALLING SLEEVES,INSERTS AND SUPPORTS AS REQUIRED FOR THIS SCOPE OF WORK AND/OR COREDRILL REQUIREMENTS. COORDINATE WITH GENERAL CONTRACTOR ANDSTRUCTURAL ENGINEER AS REQUIRED.

6. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'SRECOMMENDATIONS UNLESS SPECIFICALLY DIRECTED OTHERWISE.

5. CONTRACTOR SHALL NOT SHUT-OFF/PUT OUT OF SERVICE ANY SYSTEMS/SERVICESWITHOUT FIRST COORDINATING ALL DOWNTIME WITH OWNER'S PERSONNEL.CONTRACTOR SHALL PROVIDE A DETAILED M.O.P. AS REQUIRED. DO NOT BEGINWORK WITHOUT WRITTEN APPROVAL.

4. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL DESIGN INTENT,ARRANGEMENT AND EXTENT OF SYSTEMS. DO NOT SCALE DRAWINGS NOR USE ASSHOP DRAWINGS. WHERE ALTERNATE ROUTING, OFFSETS AND TRANSITIONS AREREQUIRED FOR FIELD COORDINATION OF ALL TRADES, THIS CONTRACTOR SHALLMAKE CHANGES WITHOUT ADDITIONAL COSTS.

3. COORDINATE ALL DIFFUSER AND GRILLE LOCATIONS WITH ARCHITECTURALREFLECTED CEILING PLAN, FIRE PROTECTION, AND ELECTRICAL DRAWINGS.

2. THE EQUIPMENT SPECIFIED ON THE DRAWINGS HAVE BEEN SELECTED AS THE BASISOF DESIGN. THE USE OF REVIEWED OR SPECIFIED EQUALS SHALL BE COORDINATEDBY THE CONTRACTOR AS TO SPACE REQUIREMENTS, EQUIPMENT DIMENSIONS ANDPERFORMANCE. ANY ADDITIONAL COSTS EITHER DIRECTLY OR INDIRECTLY CAUSEDBY EQUALS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

1. DUCT AND PIPE SIZE DIMENSIONS ARE IN INCHES UNLESS NOTED OTHERWISE.

MECHANICAL GENERAL NOTES

DUCT LINER / INSULATION SCHEDULE

REMARKSPHYSICAL DUCT DIMENSIONSLISTED ON DRAWINGS

INSULATIONOR LINER

SYSTEM

NOTES:

1. REFER TO SPECIFICATIONS FOR THICKNESS OF DUCT LINER AND EXTERIOR INSULATION FOR EACH SYSTEM.

SUPPLY AIR FROM FANDISCHARGE TO TERMINAL BOX

SUPPLY AIR DOWNSTREAMOF TERMINAL BOX

RETURN AIR

EXHAUST AIR

TRANSFER AIR

OUTSIDE AIR INTAKEDUCTS AND PLENUMS

EXTERNALLYINSULATED

EXTERNALLYINSULATED

NO INSULATIONOR LINER

--

DUCT SIZES LISTED ARE ACTUAL SHEET METALSIZE AND INCLUDE THICKNESS OF LINER

--

DUCT SIZES LISTED ARE ACTUAL SHEET METALSIZE AND INCLUDE THICKNESS OF LINER

DUCT SIZES LISTED ARE ACTUAL SHEET METALSIZE AND INCLUDE THICKNESS OF LINER

-

-

-

-

-

-

--

INTERNALLYLINED

INTERNALLYLINED

INTERNALLYLINED

BCER CONTACT LIST

Arvada Office Colorado Springs Office

10807 New Allegiance Dr.Suite 400Colorado Springs, CO 80921P - 719.533.1112

5420 Ward Rd.Suite 200Arvada, CO 80002P - 303.422.7400

Project Engineer

Dick Matthies303.422.7400 [email protected]

Dick Matthies303.422.7400 [email protected]

Project Manager

17. PROVIDE DIMENSIONALLY LOCATED PIPE MAINS AND BRANCH LINES TO FACILITIESSTRUCTURE SUCH AS COLUMN LINES, WALLS, RECOGNIZED BENCH MARKS, ETC.

16. FIRE SPRINKLER SHOP DRAWINGS TO LOCATE AND DESCRIBE GUIDES, ANCHORS ANDHANGARS FOR ALL PIPING. FIRE SPRINKLER SHOP DRAWINGS TO PROVIDEPROTECTION FOR UNDERNEATH DUCTWORK AND OTHER OBSTRUCTIONS ASNEEDED.

15. PROVIDE SPRINKLER PROTECTION A BOTTOM OF ELEVATOR SHAFT PER NFPA 14 ANDXXX AMENDMENTS.

14. PROVIDE TAMPER VALVES AND FLOW SWITCHES FOR EACH FIRE ZONE. VERIFY WITHFIRE ALARM CONTRACTOR FOR WIRING.

13. INSTALL SPRINKLER IN THE CENTER OR QUARTER POINT OF CEILING TILES, WHEREAPPLICABLE.

12. THE FIRE PROTECTION CONTRACTOR/ENGINEER OF RECORD SHALL SECURE THESITE FLOW TEST INFORMATION AND DOCUMENTATION FROM THE LOCAL WATERDEPARTMENT PRIOR TO THE DESIGN OF THE FIRE PROTECTION SYSTEM.

11. THIS CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO PURCHASE OF ANY MATERIALS AND THE COMMENCEMENT OFANY WORK. CONTRACTOR SHALL NOTIFY THE ARCHITECT OF ANY DISCREPANCIESFOR RESOLUTION.

10. PROVIDE FIELD COORDINATION OF PIPING AND SPRINKLER HEAD INSTALLATIONSWITH EXISTING DUCTWORK, LIGHTS, SMOKE DETECTORS, DIFFUSERS, ETC..

9. FOR REMODEL AREAS NEW SPRINKLER HEADS SHALL MATCH EXISTING SPRINKLERS.EXISTING SPRINKLER HEADS SHALL NOT BE RELOCATED. INSTALL ALL NEW HEADS INREMODEL AREAS IF MATCHING HEADS CANNOT BE FOUND.

8. FIRE SUPPRESSION SYSTEM TO BE HYDRAULICALLY CALCULATED BASED ON NFPA 13AND 14 REQUIREMENTS. SPRINKLERS SHALL BE SPACED PER NFPA 13 REGARDINGOBSTRUCTIONS, BEAM POCKETS, HVAC DUCTWORK, PENETRATIONS AND ANY OTHERCLEARANCE RELATED ITEMS. CONTRACTOR SHALL VERIFY ALL SPACING ANDOBSTRUCTIONS BEFORE INSTALLATION.

7. PROVIDE ALL FITTINGS, RISER NIPPLES, ARM-OVERS, HANGERS, ETC. TO MAINTAINCONFORMANCE WITH APPLICABLE STANDARDS AND TO POSITION THE SPRINKLERHEADS IN THE PROPER LOCATIONS.

6. SEAL ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS AND FLOORS WITH ULLISTED FIRE PROOF MATERIALS AS REQUIRED TO MAINTAIN THE INTEGRITY OF THERATING.

5. FIRE PROTECTION CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL NEWFIRE PROTECTION EQUIPMENT AND PIPING WITH ALL OTHER TRADES PRIOR TOSUBMITTAL OF SHOP DRAWINGS AND SYSTEM INSTALLATION, SO AS NOT TOINTERFERE WITH THE ROUTING OF NEW DUCTWORK, PLUMBING, PIPING, ETC. REFERTO SPECIFICATION DIVISION 230000 FOR CEILING CAVITY SPACE ALLOCATIONPRIORITY.

4. ALL FIRE PROTECTION SYSTEMS INSTALLED SHALL BE IN ACCORDANCE WITH NFPA13, 14, 20 ETC. AND LOCAL BUILDING CODES AND ORDINANCES.

3. THE INFORMATION PRESENTED ON THESE DRAWINGS IS DIAGRAMMATIC. IT DOESNOT NECESSARILY REPRESENT ALL ELBOWS, OFFSETS, HANGERS, ETC. REQUIREDFOR A COMPLETE WORKING SYSTEM.

2. FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES NECESSARY FOR THEINSTALLATION OF A COMPLETE AND PROPERLY FUNCTIONING FIRE PROTECTIONSYSTEM.

1. THE SUCCESSFUL CONTRACTOR WILL BE THE ENGINEER OF RECORD FOR THEDESIGN ALTERATIONS OF THE FIRE PROTECTION SYSTEM. THE DESIGN ANDENGINEERING OF THE FIRE PROTECTION SYSTEM SHALL BE BY THE FIREPROTECTION CONTRACTOR. IT IS THE CONTRACTOR'S RESPONSIBILITY THAT THESYSTEM MEET ALL THE REQUIREMENTS OF NFPA AND THE AUTHORITY HAVINGJURISDICTION.

FIRE PROTECTION GENERAL NOTES

STARBUCKS

AURARIA HIGHEREDUCATION CENTER

Page 3: G-0001 - JEDI Balancing TIVOLI STARBUCKS...mep mechanical, ... m-1011 mechanical piping & fire protection design plan ... ps heat recovery return heat recovery supply hrr hrs

OBD WHERE SPECIFIEDREFER TO G.R.D.SCHEDULE FORREQUIREMENTS.

AIR DEVICE REFER TOG.R.D. SCHEDULE ANDPLANS FOR TYPE.

1" DUCT LINER

BRANCH DUCT

CEILING

SPIN-IN W/ MVD

FLEXIBLE DUCT (MAX.6'-0")SUPPORT AT 3'-0"O.C.

FLEXMASTER TYPE"6M" OR EQUAL ELBOWW/ 3/4" DIAMETERINNER RADIUSMINIMUM

CONNECT FLEX TO AIRDEVICE PER SPECS.

STAINLESS STEELCLAMPING BAND

RETURN GRILLE REFERTO G.R.D. SCHEDULEAND PLANS FOR TYPE.

2 TIMES NECK SIZENECK SIZE

FLOW

6"1" DUCT LINER

OPEN TO PLENUM

CEILING

1/2

NE

CK

SIZ

E(M

INIM

UM

12")

SUPPORT SOUND BOOTFROM STRUCTURE PERSMACNA.

STAINLESS STEELCLAMPING BAND

FLEX DUCT

SPIN-IN W/MVD

AIR FLOW

PROVIDE MINIMUM 3DIAMETERS OFSTRAIGHT DUCT ONINLET OF BOX

TRANSITION FROMDUCT SIZE SHOWNON DRAWINGS

1/2" DRAIN VALVEW/CAP AND CHAIN

ACCESS DOOR(FACTORY INSTALLED)

INSTALL HWS ON LOWERCOIL CONNECTION ANDLEAVING AIR SIDE OF COIL

SUPPORT TERMINAL BOXINDEPENDENTLY FROMSTRUCTURE WITH SHEET METALSTRAPS (MINIMUM OF 4)

UNION (TYP.)

HEATING COIL

TRANSITION TERMINALBOX DISCHARGE TODUCT SIZE SHOWNON DRAWINGS

6'-0"MINIMUM

1" MINIMUMACOUSTICAL LINER

P/T PORT (TYP.)

HWS MAIN

STRAINER

BALL VALVE (TYP.)

SWING JOINT

SWING JOINT

HWR MAIN

CALIBRATED BALANCINGVALVE ASSEMBLY

TWO-WAY MODULATINGCONTROL VALVE

MANUAL AIR VENT

TO FIRSTTAKE-OFF

NOTE:

1. HWS/HWR PIPING SHALL BE 3/4" UNLESS NOTED OTHERWISEON DRAWINGS.

2. INLET DUCT SIZE TO TERMINAL BOX SHALL BE THE SAME SIZEAS INLET OF TERMINAL BOX UNLESS NOTED OTHERWISE ONDRAWINGS.

3. PROVIDE PROPER RIGHT HAND/LEFT HAND COILCONNECTIONS TO PIPE AS SHOWN. DO NOT ROTATE COIL.

VAV TERMINAL BOX

PROVIDE DDC CONTROLS AS FOLLOWS. INCLUDE DAT SENSOR, H.C. TCV POSITION, AND AIRFLOW CFMSETPOINT AND ACTUAL.

OCCUPIED MODE:

1. HEATING: WHEN SPACE TEMPERATURE FALLS BELOW THE HEATING THERMOSTAT SETPOINTMODULATE THE HEATING COIL CONTROL VALVE TOWARD THE OPEN POSITION. AS HEATINGDEMAND INCREASES MODULATE THE VAV DAMPER WITH THE HEATING COIL CONTROL VALVETOWARD THE MAX HEATING CFM (ADJ).

a. OCCUPANCY SENSOR CONTROL: HEATING THERMOSTAT SETPOINT SHALL BE 70°F (ADJ). SETPOINT SHALL REDUCE TO 65°F (ADJ) WHEN ALL OCCUPANCY SENSORS WITHIN THE VAV ZONE INDICATE ROOMS ARE UNOCCUPIED FOR GREATER THAN 30 MIN.

2. COOLING: WHEN SPACE TEMPERATURE RISES ABOVE THE COOLING SETPOINT MODULATE THE VAVDAMPER FROM FROM MINIMUM TO MAXIMUM COOLING CFM (ADJ). HEATING COIL CONTROL VALVE ISCLOSED.

a. OCCUPANCY SENSOR CONTROL: COOLING THERMOSTAT SETPOINT SHALL BE 75°F (ADJ). SETPOINT SHALL INCREASE TO 80°F (ADJ) WHEN ALL OCCUPANCY SENSORS WITHIN THE VAV ZONE INDICATE ROOMS ARE UNOCCUPIED FOR GREATER THAN 30 MIN.

UNOCCUPIED MODE:

1. WHEN SPACE TEMPERATURE FALLS BELOW THE UNOCCUPIED HEATING THERMOSTAT SETPOINTMODULATE THE VAV DAMPER TOWARD THE MAX HEATING CFM (ADJ). HEATING COIL CONTROL VALVESHALL BE CLOSED.

SEQUENCE OF OPERATION:

MAX HEATING

ROOMTEMP.INCREASE

MINSETPOINT

MAX COOLING

CF

M

HEATING TSTAT SETPOINT COOLING TSTAT SETPOINT

HEATING WATERCONTROL VALVEPOSITION

VAV BOX

SPACETEMPERATURESENSOR

T

TS

4

3

12

5

OWNERSHIP OF DOCUMENTS:ALL DRAWINGS, SPECIFICATIONS AND OTHER WORK PRODUCT OF THE ENGINEER FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF THE ENGINEER WHETHER THEPROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE OF THE ENGINEER BY THE OWNER OF EXTENSIONS OF THIS PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER SHALL BE AT THEOWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE ENGINEER FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THEENGINEER'S INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER.

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.slaterpaull.com

1331 Nineteenth StreetDenver, CO. 80202

THESE RECORD DRAWINGS HAVE BEENPREPARED, IN PART, ON THE BASIS OF

INFORMATION COMPILED AND FURNISHEDBY OTHERS. THE ARCHITECT WILL NOT BE

RESPONSIBLE FOR ANY ERRORS OROMISSIONS WHICH HAVE BEEN

INCORPORATED INTO THIS DOCUMENT ASA RESULT.

5/2

6/2

015 2

:34:1

0 P

M

C:\

Users

\JP

EC

KO

VIT

CH

\Docum

ents

\Local R

evit F

iles\1

5915074 -

Tiv

oli

Sta

rbucks -

ME

P_R

15_jp

eckovitch.r

vt

M-0002

MECHANICALSCHEDULES ANDDETAILS

Starbucks CoffeeCompany

AURARIA CAMPUSTIVOLI

RDM

JMP

65043-001

RDM

900 AURARIA PKWYDENVER, CO 80204

05/26/15 CONSTRUCTION DOCUMENTS

TERMINAL BOX SCHEDULE

PLAN CODE

DESIGN INSTALLED INLET SIZE (IN.) AIRFLOW SETPOINTS MAXIMUM AIRPRESSURE DROP

(IN. W.C.)

MAXDISCHARGE

N.C.

HEATING COIL DATA

REMARKSMFR. MODEL MFR. MODEL DIA. W HCOOLING MAX

(CFM)AIRFLOW MIN

(CFM)HEATING MAX

(CFM) EAT (°F) LAT (°F) EWT (°F) LWT (°F)COILMBH GLYCOL % GPM

MAX WATERP.D. (FT. W.C.)

TB-15-201(3) TITUS DESV 12 1,500 800 800 0.5 25 55 85 180 150 21.6 0 1.4 0.00 psi

TB-15-201(4) TITUS DESV 14 2,250 1,200 1,200 0.5 25 55 85 180 150 32.4 0 2.2 0.00 psi

NOT TO SCALE

AIR DEVICE DETAIL

NOT TO SCALE

CEILING GRILLE RETURN AIR BOOT

NOT TO SCALE

ROUND DUCT TAKE-OFF DETAIL

NOT TO SCALE

AIR TERMINAL BOX DETAIL (2-WAY CONTROL VALVE)

GRILLES, REGISTERS AND DIFFUSERS SCHEDULE

PLAN CODE

DESIGN

TYPE

INSTALLED

FRAME MATERIAL FINISHDAMPER

TYPE LEGEND REMARKSMFR. MODEL MFR. MODEL

RG-1 TITUS PXP CEILING PERFORATED LAY-IN STEEL (1) - - 24x24 FACE

SD-3 TITUS TDC 12x12 - 10Ø NECK CEILING LOUVERED FACE LAY-IN STEEL (1) - 24x24 FACE

SD-4 TITUS TDC 12x12 - 10Ø NECK CEILING LOUVERED FACE GYP BOARD CLG STEEL (1) - 24x24 FACE

NOT TO SCALE

TYPICAL VAV BOX CONTROL DIAGRAM

VAV BOX POINTS LIST

TAG DESCRIPTION TYPE

1 ZONE DAMPER AO

2 SUPPLY AIR AIRFLOW AI

3 DISCHARGE AIR TEMPERATURE AI

4 REHEAT VALVE AO

5 ZONE TEMPERATURE AI

(2) BASED ON 0% PROPYLENE GLYCOL SOLUTION.

(1) PROVIDE EACH BOX WITH CONTROLS AND/OR COIL CONNECTIONS TO MATCH THE MAINTENANCE ACCESS LOCATION INDICATED ONTHE DRAWING.

(1) PAINT COLOR SELECTION BY ARCHITECT.

STARBUCKS

AURARIA HIGHEREDUCATION CENTER

Page 4: G-0001 - JEDI Balancing TIVOLI STARBUCKS...mep mechanical, ... m-1011 mechanical piping & fire protection design plan ... ps heat recovery return heat recovery supply hrr hrs

T

FS FS

T

T

T

WORKROOM

30

CAFE

32

BAR

33

RETAIL

34

M2

M2

(E)RG-1 (E)RG-1(E)SD-3

350(E)SD-3

350(E)SD-3

350

(E)SD-3

350

(E)SD-3

350

(E)SD-3

350

(E)SD-3

450

(E)RG-1

(E)SD-3

450

(E)SD-3

450

(E)RG-1

M1

M2

(E)32x16

(E)11x15 (E)17x15 (E)25x15

(E)2

4x12

(E)52x20

(E

)56

x2

4

(E)48x20

(E

)16

x1

4 (E

)14

x1

4

(E)22x18

(E)1

4x10

(E)52x20

M4

M2

M2

M2M2M1M2M1

(E)TB-201(1)

2,450

(E)TB-201(2)

2,700

M12

(E)64x44 RA UP

TO RTU-2

(E)64x44 SA MP

UP TO RTU-2

EXTENT OF HVACPROJECT SCOPE

TB-15-201(3)1,500

SD-3500

SD-3500

RG-1

SD-3500

20x16

(E

)16

x1

4

(E)24x10

SD-4450

SD-3450

SD-4450

SD-4450

SD-4450

SD-3450

SD-3450

SD-3350

M9

M6M6

M6

M7M8

M5

M5

M5

M5

RG-1

M9

M3

M3

M3M11

M11

M10M13

M2

24x14

SD-4450

TB-15-201(4)2,250

(E)32x16

M15

M17

M16

M14

OWNERSHIP OF DOCUMENTS:ALL DRAWINGS, SPECIFICATIONS AND OTHER WORK PRODUCT OF THE ENGINEER FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF THE ENGINEER WHETHER THEPROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE OF THE ENGINEER BY THE OWNER OF EXTENSIONS OF THIS PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER SHALL BE AT THEOWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE ENGINEER FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THEENGINEER'S INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER.

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.slaterpaull.com

1331 Nineteenth StreetDenver, CO. 80202

THESE RECORD DRAWINGS HAVE BEENPREPARED, IN PART, ON THE BASIS OF

INFORMATION COMPILED AND FURNISHEDBY OTHERS. THE ARCHITECT WILL NOT BE

RESPONSIBLE FOR ANY ERRORS OROMISSIONS WHICH HAVE BEEN

INCORPORATED INTO THIS DOCUMENT ASA RESULT.

5/2

6/2

015 2

:34:1

6 P

M

C:\

Users

\JP

EC

KO

VIT

CH

\Docum

ents

\Local R

evit F

iles\1

5915074 -

Tiv

oli

Sta

rbucks -

ME

P_R

15_jp

eckovitch.r

vt

M-1001

MECHANICAL DESIGNPLAN

Starbucks CoffeeCompany

AURARIA CAMPUSTIVOLI

RDM

JMP

65043-001

RDM

900 AURARIA PKWYDENVER, CO 80204

05/26/15 CONSTRUCTION DOCUMENTS

WORK NOTES

M1 EXISTING RG TO REMAIN.

M2 EXISTING SD-3; 255 CFM; TO REMAIN IN LAY-IN CEILING.

M3 EXISTING SD-3; 255 CFM; RELOCATE IN LAY-IN CEILING GRID.

M4 EXISTING SD-3 (255 CFM); TO REMAIN IN GYP. BRD. CEILING.

M5 PROVIDE NEW SD-4, BALANCE TO 255 CFM.

M6 REUSE EXISTING LAY-IN SD-3, 500 CFM EACH.

M7 NEW TB-15-201(3), 1500 CFM.

M8 CONNECT NEW 12Ø TO EXISTING 16X14 SUPPLY AIR.

M9 NEW RG-1.

M10 NEW THERMOSTAT TO NEW TERMINAL BOX.

M11 EXISTING TERMINAL BOX, REBALANCE TO CFM INDICATED.

M12 EXISTING SMOKE MANAGEMENT DUCT TO REMAIN.

M13 RELOCATED EXISTING THERMOSTAT SERVING EXISTING TB-15-201(2).

M14 PROVIDE NEW DUCT DIVIDER IN EXISTING 32X16 SA DUCT.

M15 NEW 24X14 REPLACING EXISTING 16X14.

M16 EXISTING THERMOSTAT TO REMAIN.

M17 NEW 14Ø SUPPLY AIR DUCT.

0'2' 1' 2' 4' 8'

1/4" = 1'-0"

HVAC DESIGN PLAN

2. REVIEW VAV AND THERMOSTAT CALIBRATION.

1. REBALANCE ALL DIFFUSERS AND VAV TERMINALS IN WORK AREA.

GENERAL NOTES

STARBUCKS

AURARIA HIGHEREDUCATION CENTER

RTU­02(NIC)

TB­201­01

TB­15­201­02

TB­201­02 TB­15­201­01

1

2

3

45

1

2

3

1

2 3

4

5

1 2

3

4

567

Page 5: G-0001 - JEDI Balancing TIVOLI STARBUCKS...mep mechanical, ... m-1011 mechanical piping & fire protection design plan ... ps heat recovery return heat recovery supply hrr hrs

T

T

T

T

WORKROOM

30

CAFE

32

BAR

33

RETAIL

34

H2

3/4" HWR

3/4" HWS

(E)1" HWS

(E)1" HWR

(E

)1"

HW

R

(E

)1"

HW

S

(E

)1"

HW

R

(E

)1"

HW

S

(E

)1"

HW

R

(E

)1"

HW

S

TB-15-201(3)1.4

(E)TB-201(2)

(E)TB-201(1)

(E)3/4" HWS

(E)3/4" HWR

(E)1" HWS

(E)1" HWR

(E

)CR

(E

)CS

H1

H3H3

H4

H4

FP1

H3

H3

H3

EXTENT OF HVACPROJECT SCOPE

TB-15-201(4)2.2

3/4" HWS

3/4" HWR

H1

OWNERSHIP OF DOCUMENTS:ALL DRAWINGS, SPECIFICATIONS AND OTHER WORK PRODUCT OF THE ENGINEER FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF THE ENGINEER WHETHER THEPROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE OF THE ENGINEER BY THE OWNER OF EXTENSIONS OF THIS PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER SHALL BE AT THEOWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE ENGINEER FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THEENGINEER'S INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER.

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.slaterpaull.com

1331 Nineteenth StreetDenver, CO. 80202

THESE RECORD DRAWINGS HAVE BEENPREPARED, IN PART, ON THE BASIS OF

INFORMATION COMPILED AND FURNISHEDBY OTHERS. THE ARCHITECT WILL NOT BE

RESPONSIBLE FOR ANY ERRORS OROMISSIONS WHICH HAVE BEEN

INCORPORATED INTO THIS DOCUMENT ASA RESULT.

5/2

6/2

015 2

:34:2

1 P

M

C:\

Users

\JP

EC

KO

VIT

CH

\Docum

ents

\Local R

evit F

iles\1

5915074 -

Tiv

oli

Sta

rbucks -

ME

P_R

15_jp

eckovitch.r

vt

M-1011

MECHANICAL PIPING& FIRE PROTECTIONDESIGN PLAN

Starbucks CoffeeCompany

AURARIA CAMPUSTIVOLI

RDM

JMP

65043-001

RDM

900 AURARIA PKWYDENVER, CO 80204

05/26/15 CONSTRUCTION DOCUMENTS

WORK NOTES

FP1 EXISTING FIRE SPRINKLER HEAD LOCATIONS ARE INDICATED. FIRE SPRINKLERCONTRACTOR SHALL REMOVE AND REPLACE WITH NEW HEADS OF SAME TYPETO PROVIDE COVERAGE THAT MEETS CURRENT IFC/NFPA CODES.

H1 PROVIDE NEW THERMOSTAT FOR NEW VAV TERMINAL.

H2 RELOCATED EXISTING THERMOSTAT SERVING EXISTING TB-201(2).

H3 EXISTING HEATING WATER PIPING.

H4 MEASURE EXISTING TERMINAL BOX GPM WITH TEMPERATURE CONTROL VALVEFULL OPEN; REBALANCE TO GPM AFTER NEW TERMINAL BOX IS INSTALLED.ADDITIONAL HEADS TO ALLOW FOR NEW WALLS AND COVERAGE IN ROOMSSHALL BE PROVIDED BY THE CONTRACTOR.

0'2' 1' 2' 4' 8'

1/4" = 1'-0"

MECHANICAL PIPING DESIGN PLAN/EXISTING FIRE PROECTION HEAD LAYOUT PLAN

STARBUCKS

AURARIA HIGHEREDUCATION CENTER