AEH561
FUJI Low Voltage Distributionand Control Equipment
Fuji Electric FA meets customer needs with a wide range of products and
Page number
2P 2P 6P
14P
10P 10P
13P
6P
10P
Combinationstarters
Power receiving
Motor load 1 Motor load 2 Motor load 3 Heaters
Vacuum circuitbreakers
Voltage transformers
Multi display lights
Voltmeters
Current transformers
Cast-resintransformers
Power monitoringequipment
10P
Semiconductorfuses
InvertersServo system
Solid statecontactors
Pushbuttons Selectors
Pilot lights
Air circuitbreakers
MCCBsELCBs
MCCBsELCBs
MCCBsELCBs
MCCBsELCBs
Manual motorstarters
Magnetic contactorsand starters
Magnetic contactorsand starters
Magneticcontactors
VCB
CT
T
VT
solid reliability
CONTENTS
17P 18P
20P
Fuji Electric FA Components & Systems Co., Ltd. provides a wide range of component equipment and system products, such as power distribution, control, and drive control equipment, to support the operation and safety of factory FA lines, intelligent buildings, and other applications.
Capacitors
Surge protectivedevices
Panel switches
Protective relaysAmmeters
Terminal blocks
Current-limitingfuses
10P
Voltagetransformers
Magneticcontactors
for capacitorbank
Currenttransformers
2Magnetic Contactors and Starters
6Manual Motor Starters and Contactors
10Molded Case Circuit Breakers
13Air Circuit Breakers
Pushbuttons, Selectors, Pilot Lights14
Command Switches
17Time Delay Relays
18Industrial Control Relays
20Power Monitoring Unit
Industrialcontrol relays
Time delayrelays
MCCBsELCBs
Powermonitoring
unit
2
Type ContactorStarter
Max. motor 200-240Vcapacity (kW) 380-440VAC-3 500-550VIEC 60947-4-1 600-660VOperational 200-240Vcurrent (A) 380-440V
500-550V600-660V
Thermal current (A)Auxiliary contact arrangement
Durability Electrical 200V( x 106 operations) 400V MechanicalSwitching cycle per hourThermal overload Standard typerelay
Phase-loss protectionSetting range (A)
Dimensions (mm) ContactorsW x H x D Starters Standard
SC-03SW-03/3H 2.5 4 4 411 9 7 5201NO1NC21.75101800TR-0N/3
TK-0N0.1-0.150.13-0.20.15-0.240.2-0.30.24-0.360.3-0.450.36-0.540.48-0.720.64-0.960.8-1.20.95-1.451.4-2.21.7-2.62.2-3.42.8-4.24-65-86-97-11
43 x 81 x 8044 x 122 x 80IEC 60947-4-1, EN60947-4-1, VDE0660, TÜV, CE mark, CSA C22.2, UL508, CCC, NK, LR, BV, KR
SC-0SW-0/3H 3.5 5.5 5.5 5.51312 9 7201NO1NC21.5101800TR-0N/3
TK-0N0.1-0.150.13-0.20.15-0.240.2-0.30.24-0.360.3-0.450.36-0.540.48-0.720.64-0.960.8-1.20.95-1.451.4-2.21.7-2.62.2-3.42.8-4.24-65-86-97-119-13
43 x 81 x 8044 x 122 x 80
SC-05SW-05/3H 3.5 5.5 5.5 5.51312 9 7201NO+1NC2NO, 2NC21.5101800TR-0N/3
TK-0N0.1-0.150.13-0.20.15-0.240.2-0.30.24-0.360.3-0.450.36-0.540.48-0.720.64-0.960.8-1.20.95-1.451.4-2.21.7-2.62.2-3.42.8-4.24-65-86-97-119-13
53 x 81 x 8053 x 122 x 80
SC-4-0SW-4-0/3H 4.5 7.5 7.5 7.5181613 9251NO1NC1.51101800TR-5-1N/3
TK-5-1N0.1-0.150.13-0.20.15-0.240.2-0.30.24-0.360.3-0.450.36-0.540.48-0.720.64-0.960.8-1.20.95-1.451.4-2.21.7-2.62.2-3.42.8-4.24-65-86-97-119-1312-18
53 x 81 x 8153 x 127 x 81
SC-4-1SW-4-1/3H 5.51111 7.5222217 9321NO1NC1.51101800TR-5-1N/3
TK-5-1N0.1-0.150.13-0.20.15-0.240.2-0.30.24-0.360.3-0.450.36-0.540.48-0.720.64-0.960.8-1.20.95-1.451.4-2.21.7-2.62.2-3.42.8-4.24-65-86-97-119-1312-1816-2253 x 81 x 8153 x 127 x 81
SC-5-1SW-5-1/3H 5.51111 7.5222217 9321NO+1NC, 2NO2NC, 2NO+2NC1.51101800TR-5-1N/3
TK-5-1N0.1-0.150.13-0.20.15-0.240.2-0.30.24-0.360.3-0.450.36-0.540.48-0.720.64-0.960.8-1.20.95-1.451.4-2.21.7-2.62.2-3.42.8-4.24-65-86-97-119-1312-1816-2264 x 81 x 8164 x 127 x 81
SC-N1SW-N1/3H 7.515151132322415502NO+2NC4NO+4NC1.51101200TR-N2/3
TK-N24-65-86-97-119-1312-1818-2624-36
74 x 87 x 9674 x 146 x 96
Standard type non-reversing, open 03 to N1
Controlling energy to manage motorsand machinery
SW-0SW-N5
3
Type ContactorStarter
Max. motor 200-240Vcapacity (kW) 380-440VAC-3 500-550VIEC 60947-4-1 600-660VOperational 200-240Vcurrent (A) 380-440V
500-550V600-660V
Thermal current (A)Auxiliary contact arrangement
Durability Electrical 200V( x 106 operations) 400V MechanicalSwitching cycle per hourThermal overload Standard typerelay
Phase-loss protectionSetting range (A)
Dimensions (mm) ContactorsW x H x D Starters Standard
SC-N2SW-N2/3H1118.518.51540402919602NO+2NC4NO+4NC1.51101200TR-N2/3
TK-N24-65-86-97-119-1312-1818-2624-3632-42
74 x 87 x 9674 x 146 x 96IEC 60947-4-1, EN60947-4-1, VDE0660, TÜV, CE mark, CSA C22.2, UL508, CCC, NK, LR, BV, KR
SC-N2SSW-N2S/3H1522252250503826802NO+2NC4NO+4NC21.551200TR-N3/3
TK-N37-119-1312-1818-2624-3628-4034-5045-65
88 x 110 x 11188 x 177 x 111
SC-N3SW-N3/3H18.5303730656560381002NO+2NC4NO+4NC21.551200TR-N3/3
TK-N37-11 9-1312-1818-2624-3628-4034-5045-6548-6853-80 *65-95 *85-105 *88 x 110 x 11188 x 177 x 111
SC-N4SW-N4/3H22403737808060441352NO+2NC4NO+4NC10.851200TR-N5/3
TK-N518-2624-3628-4034-5045-6553-80
88 x 127 x 11788 x 189 x 117
SC-N5SW-N5/3H 30 55 55 55105105 85 641502NO+2NC4NO+4NC0.80.751200TR-N5/3
TK-N518-2624-3628-4034-5045-6553-8065-9585-105
88 x 127 x 13288 x 189 x 132
SC-N6SW-N6/3H 37 60 60 60125125 90 721502NO+2NC4NO+4NC0.60.551200TR-N6/3
TK-N645-6553-8065-9585-125110-160 *
100 x 144 x 138100 x 225 x 138
SC-N7SW-N7/3H 45 75 75 901501501201032002NO+2NC4NO+4NC10.851200TR-N7/3
TK-N745-6553-8065-9585-125110-160
115 x 156 x 140155 x 237 x 140
Note: * Separate mounting only
Type ContactorStarter
Max. motor 200-240Vcapacity (kW) 380-440VAC-3 500-550VIEC 60947-4-1 600-660VOperational 200-240Vcurrent (A) 380-440V
500-550V600-660V
Thermal current (A)Auxiliary contact arrangement
Durability Electrical 200V( x 106 operations) 400V MechanicalSwitching cycle per hourThermal overload Standard typerelay
Phase-loss protectionSetting range (A)
Dimensions (mm) ContactorsW x H x D Starters Standard
SC-N8SW-N8/3H 55 901301321801801801502602NO+2NC4NO+4NC10.851200TR-N8/3
TK-N865-9585-125110-160125-185
138 x 209 x 174138 x 305 x 174IEC 60947-4-1, EN60947-4-1, VDE0660, TÜV, CE mark, CSA C22.2, UL508, CCC, NK, LR, BV, KR
SC-N10SW-N10/3H 651101321322202202001502602NO+2NC4NO+4NC10.851200TR-N10/3
TK-N1085-125110-160125-185160-240
138 x 209 x 174138 x 287 x 174
SC-N11SW-N11/3H 901601602003003002302303502NO+2NC4NO+4NC10.851200TR-N12/3
TK-N12110-160125-185160-240200-300
148 x 240 x 195148 x 360 x 195
SC-N12SW-N12/3H1202202503004004003603604502NO+2NC4NO+4NC0.70.651200TR-N12/3
TK-N12110-160125-185160-240200-300240-360300-450148 x 240 x 195148 x 360 x 195
SC-N14SW-N14/3H1803154004806006006006006602NO+2NC4NO+4NC0.60.551200TR-N14/3
TK-N14240-360300-450400-600
290 x 332 x 327290 x 463 x 327
SC-N16–2204405005008008007206308002NO+2NC4NO+4NC0.30.252.51200–
––
290 x 332 x 327–
Standard type non-reversing, open N2 to N7
Standard type non-reversing, open N8 to N16
4
Optional unit
Type
Used with
Auxiliary contact block
All contacts are bifurcated contacts so that the minimum voltage current is 5V DC, 3mA.
4-poleSZ-AFront mounting
SC-03 to N3
Operation counter
This unit indicates the number of contactor on-off operations to ensure easy maintenance and inspection.
Coil surge suppression unitThis unit absorbs coil surge voltage due to contactor on-off operation.
Main circuit surge suppression unitThis unit prevents misoperation of electronic equipment due to surge voltage generated from motor when contactor is open or closed.
SZ-J
SC-03 to N3
SZ-Z
SC-03 to N4SC-03/G to SC-N3/G
SZ-ZMFront mounting
SC-03 to N3SC-03 to N3
2-poleSZ-A
Single-poleSZ-ASSide mounting
Side mounting
SC-03 to N16
Optional unit
Type
Used with
Mechanical interlock unit and power connection kit for reversing
This unit is used to interlock two contactors for reversing.
SZ-RM
SC-03 to N3
Coil drive unit for IC output
This unit controls on-off operation for contactor by the DC output of electronic equipment.
3-pole parallel connection kit
This kit modifies a 3-pole contactors to a single-pole contactor for resistive load.
SZ-CDTop mounting
SC-03 to N3
SZ-CDSide mounting
SC-N1 to N12
SZ-SP
SC-03 to N16
Base unit for separate mounting
This unit is used when thermal relay is required to mount independently.
SZ-H
TR-0N to N3
Dial cover
For protection against the current setting being changed in error.SZ-DA
TR-0N to N14
SZ-RW
SC-03 to N3
Optional unit
Type
Used with
Trip indicator
This unit indicates thermal relay tripping status.
SZ-L
TR-0N to N14
Terminal cover
This covers conform to DIN 57106 and VDE 0106 Teil 100.
Insulation barrier
This unit prevents accidental short-circuits caused by metallic objects falling onto the terminals.
SZ-T , T,SZ-W T
SC-03 to N12SW-03 to N12
TR-0N to N3TR-N2H, N3H, N6H
SZ-B
SC-N4 to N12SW-N4 to N12TR-N6H, N10H, N12H
Live-section cover
This cover prevents exposure of the live section for increasing safety.
SZ- J, W J SZ-J , JW
SC-03 to N12SW-03 to N12
Off-delay release unit
This unit prevents circuit opening due to instantaneous voltage drop.
SZ-DE SZ- DE
SC-03/G to N14
Optional accessories
5
Max. motor capacity (kW)Single-phase110V0.40.50.50.60.80.8
1.21.7–––––––Coil voltage *• SW-03P to 5-1P, N1PB to N4PB24V 50Hz / 24-26V 60Hz48V 50Hz / 48-52V 60Hz100V 50Hz / 100-110V 60Hz100-110V 50Hz / 110-120V 60Hz110-120V 50Hz / 120-130V 60Hz200V 50Hz / 200-220V 60Hz200-220V 50Hz / 220-240V 60Hz220-240V 50Hz / 240-260V 60Hz346-380V 50Hz / 380-420V 60Hz380-400V 50Hz / 400-440V 60Hz415-440V 50Hz / 440-480V 60Hz480-500V 50Hz / 500-550V 60Hz
Auxiliary contact
Standard1NO1NO1NO+1NC1NO1NO1NO+1NC
2NO+2NC2NO+2NC2NO+2NC2NO+2NC2NO+2NC2NO+2NC2NO+2NC2NO+2NC2NO+2NC
• SW-N5PB to N10PBAC24-25V 50/60Hz48-50V 50/60Hz100-127V 50/60Hz200-250V 50/60Hz265-347V 50/60Hz380-450V 50/60Hz460-575V 50/60Hz
With on-off/reset pushbuttonTypeSW-03P/3HSW-0P/3HSW-05P/3HSW-4-0P/3HSW-4-1P/3HSW-5-1P/3H
SW-N1PB/3HSW-N2PB/3HSW-N2SPB/3HSW-N3PB/3HSW-N4PB/3HSW-N5PB/3HSW-N6PB/3HSW-N8PB/3HSW-N10PB/3H
3-phase200/240V
2.53.53.54.55.55.5
7.5111518.52230375565
380/440V45.55.57.5
1111
1518.5223040556090
110
• Compact and simple operation – Provided with ON-OFF and reset pushbuttons, hence best suited for direct-on-line starting.
• Superior motor protection – Built-in highly reliable thermal overload relay is designed to give motor complete protection against overcurrent.
• Long service life – Hyperfine silver alloy contacts performance and a long electrical life.
Starters with on-off and RESET pushbuttons
* Other coil voltages between 24V and 600V AC are available.
DC24V48V100-120V200-240V
Motor capacity (kW)AC-3 3-phase200/240V
33.55.57.5
111518.51.53.03.53.03.53.03.51.5
Coil voltage *• FC-0/UL to 4UL24V 50Hz / 24-26V 60Hz48V 50Hz / 48-52V 60Hz100V 50Hz / 100-110V 60Hz100-110V 50Hz / 110-120V 60Hz110-120V 50Hz / 120-130V 60Hz200V 50Hz / 200-220V 60Hz200-220V 50Hz / 220-240V 60Hz220-240V 50Hz / 240-260V 60Hz346-380V 50Hz / 380-420V 60Hz380-400V 50Hz / 400-440V 60Hz415-440V 50Hz / 440-480V 60Hz
Operationalcurrent (A)AC-1202030304060808
2020202020208
Auxiliary contact
Standard1NO, 1NC1NO, 1NC1NO+1NC *1
1NO+1NC *1
1NO+1NC *1
1NO+1NC *1
1NO+1NC *1
1NO, 1NC1NO, 1NC1NO, 1NC1NO, 1NC1NO, 1NC1NO, 1NC1NO, 1NC1NO, 1NC
• FC-0/GUL to 0A/G24V DC48V DC60V DC100V DC110V DC200V DC220V DC
Non-reversing Open TypeFC-0ULFC-0SULFC-1ULFC-1SULFC-2SULFC-3ULFC-4ULFC-0AFC-0TULFC-0STULFC-0/GULFC-0S/GULFC-0/TGULFC-0S/TGULFC-0A/G
380/440V2.54.55.57.5
1118.530
–2.54.52.54.52.54.5
–
• Small size, light weight • Budget priced• Long service life – The contacts are self-cleaning by
a scrubbing section during operation and are made of silver alloy.
• Highly reliable operating coil – Pick up voltage 75% of rated voltage • Self-lifting terminals make it easy to wire.
Definite purpose contactors and starters
*1 : Auxiliary contact arrangement 2NO or 2NC is available.* Other coil voltages between 24V and 440V AC are available.
Type
ContactRated thermal current (A)
Make and break 110V ACcapacity (A) 220V AC
440V AC550V AC
Rated operationalcurrent (A) 110V AC
220V AC440V AC550V AC 24V DC 48V DC110V DC220V DC
Coil voltage *
Contact arrangement
SH-44-pole, 8-poleBifurcated10
60301512Ind.631.51.231.50.550.2724V 50Hz / 24-26V / 60Hz,48V 50Hz / 48-52V / 60Hz,100V 50Hz / 100-110V / 60Hz,110-120V 50Hz / 120-130V / 60Hz,200V 50Hz / 200-220V / 60Hz4-pole : 4NO, 3NO+1NC, 2NO+2NC8-pole : 8NO, 7NO+1NC, 6NO+2NC, 5NO+3NC, 4NO+4NC5-pole : 5NO, 4NO+1NC, 3NO+2NC, 2NO+3NC, 1NO+4NC, 5NC
SH-55-pole
Res.10 8 5 5 5 3 2.5 1
SH-5H5-pole
Res.1010101010 5 4 1
SH-4H4-pole, 8-poleSingle10
60604040Ind.664451.50.70.27220-240V 50Hz / 240-260V / 60Hz,346-380V 50Hz / 380-420V / 60Hz,380-400V 50Hz / 400-440V / 60Hz,415-440V 50Hz / 440-480V / 60Hz,480-500V 50Hz / 500-550V / 60Hz
• Employing of bifurcated contact assures an increase of high contact reliability in low-level circuit use (5V, 3mA)
• Variety of optional function units: Auxiliary contact block, off-delay release unit, coil surge suppression unit and operation counter
• Snap-on 35mm rail mounting available • UL, CSA, TÜV, BV and Lloyd approved
Standard type industrial relay
* Other coil voltages between 24V and 600V AC are available.
Versions
See page 01/1 of D & C catalog 19th Edition.Further Information
6
Standard breaking capacityBM3RSB- BM3RSBK-
P16P25P40P630011P62P50046P3010013016020025032040050063
0.1-0.160.16-0.250.25-0.4 0.4-0.630.63-1 1-1.61.6-2.52.5-4 4-6.3 6.3-10 9-1311-1614-2019-2524-3228-4035-5045-63
3Rocker0.16 to 32200 to 69050/606906Category AAC-31013 x le maximum7W: In=0.16 to 25A 8.5W: In=32AMechanical 100,000: In=0.16 to 25A 70,000: In=32A Electrical 100,000: In=0.16 to 25A 70,000: In=32A25ProvidedProvided
45 x 90 x 66 45 x 90 x 79IEC 60947-1, 60947-2, 60947-4-1, UL 508, CSA C22.2 No.14, TÜV, CCC
Dimensions (mm) W x H x DStandard
Number of polesHandle typeRated current Ie (A)Rated operational voltage Ue (V)Rated frequency (Hz)Rated insulation voltage Ui (V)Rated impulse withstand voltage Uimp (kV)Utilization IEC 60947-2 Circuit breakercategory IEC 60947-4-1 Motor starterTrip class IEC 60947-4-1 *Instantaneous trip characteristicPower loss (total of 3-pole)Durability (operations)Max. operations per hour (motor start-up)Phase-loss protectionTrip indicator / Test trip functionRated breakingcapacity (kA)
IEC 60947-2
Replace the mark in the type number by current range codes.
Adjustable thermal-magnetic trip type Instantaneous trip type
3Rotary
High breaking capacityBM3RHB- BM3RHBK-
240V/230VIcu Ics100 100100 100100 100100 100100 100100 100100 100100 100100 100100 100100 100100 100 50 38 50 38 50 38–––
415V/400VIcu Ics100 100100 100100 100100 100100 100100 100100 100100 100100 100100 100 50 38 25 19 25 19 25 19 25 19–––
460V/440VIcu Ics100 100100 100100 100100 100100 100100 100100 100100 100 50 38 15 11 10 8 10 8 10 8 10 8 10 8–––
500V
Icu Ics100 100100 100100 100100 100100 100100 100100 100100 100 50 38 10 8 6 5 6 5 6 5 6 5 6 5–––
690V/600VIcu Ics100 100100 100100 100100 100100 100100 100 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2–––
240V/230VIcu Ics100 100100 100100 100100 100100 100100 100100 100100 100100 100100 100100 100100 100100 100100 100100 100–––
415V/400VIcu Ics100 100100 100100 100100 100100 100100 100100 100100 100100 100100 100100 100 50 38 50 38 50 38 50 38–––
460V/440VIcu Ics100 100100 100100 100100 100100 100100 100100 100100 100100 100 50 38 50 37 35 27 35 27 35 27 35 27–––
500V
Icu Ics100 100100 100100 100100 100100 100100 100100 100100 100100 100 50 38 42 32 10 8 10 8 10 8 10 8–––
690V/600VIcu Ics100 100100 100100 100100 100100 100100 100 8 6 8 6 6 5 6 5 6 5 4 3 4 3 4 3 4 3–––
Note: * Adjustable thermal-magnetic tirp type only
Adjustable current rangeCode Ie: Min.–Max. (A)
MMSs / 32AF
Molded case circuit breaker and thermaloverload relay functions integrated intohighly compact unit
DUO series
7
MMSs / 63AF
Standard breaking capacityBM3VSB- BM3VSBK-
P16P25P40P630011P62P50046P3010013016020025032040050063
0.1-0.160.16-0.250.25-0.4 0.4-0.630.63-1 1-1.61.6-2.52.5-4 4-6.3 6.3-10 9-1311-1614-2019-2524-3228-4035-5045-63
3Rotary10 to 63200 to 69050/6010008Category AAC-31013 x le maximum11W: In=10 to 32A 15W: In=40 to 50A 17W: In=63AMechanical 50,000 Electrical 25,00025ProvidedProvided
55 x 110 x 96IEC 60947-1, 60947-2, 60947-4-1, UL 508, CSA C22.2 No.14, TÜV, CCC
Dimensions (mm) W x H x DStandard
Number of polesHandle typeRated current Ie (A)Rated operational voltage Ue (V)Rated frequency (Hz)Rated insulation voltage Ui (V)Rated impulse withstand voltage Uimp (kV)Utilization IEC 60947-2 Circuit breakercategory IEC 60947-4-1 Motor starterTrip class IEC 60947-4-1 *Instantaneous trip characteristicPower loss (total of 3-pole)Durability (operations)Max. operations per hour (motor start-up)Phase-loss protectionTrip indicator / Test trip functionRated breakingcapacity (kA)
IEC 60947-2
Replace the mark in the type number by current range codes.
Adjustable thermal-magnetic trip type Instantaneous trip type
3Rotary
High breaking capacityBM3VHB- BM3VHBK-
240V/230VIcu Ics– – – – – – – – – 100 100100 100100 100 50 38 50 38 50 38 50 38 50 38 50 38
415V/400VIcu Ics– – – – – – – – – 100 100 50 38 25 19 25 19 25 19 25 19 25 19 25 19 25 19
460V/440VIcu Ics– – – – – – – – – 15 1210 810 810 810 810 810 810 810 8
500V
Icu–––––––––10 6 6 6 6 6 6 6 6
690V/600VIcu–––––––––444444444
240V/230VIcu–––––––––100100100100100100100100100
415V/400VIcu–––––––––100100 50 50 50 50 50 50 50
460V/440VIcu–––––––––505050503535353535
500V
Icu–––––––––504212121210101010
690V/600VIcu–––––––––665555555
Note: * Adjustable thermal-magnetic tirp type only
Adjustable current rangeCode Ie: Min.–Max. (A)
Ics
855555555
Ics
333333333
Ics
100100100100100100100100100
Ics
100100 38 38 38 38 38 38 38
Ics
383838382727272727
Ics
3832 9 9 9 8 8 8 8
Ics
554444444
8
Contactor Non-reversingReversing
Motor capacity 3-phase AC-3 (kW) 200-240V380-440V
Rated operational current AC-3 (A)200-240V380-440V
Rated thermal current AC-1 (A)Auxiliary contact Non-reversingDimensions (mm) W x H x D AC operatedNon-reversing DC operatedStandardThermal overload relay(standard type) Ampere setting range (A)
Dimensions W x H x D (mm)Standard
Contactor Non-reversing ReversingMotor capacity 3-phase AC-3 (kW)
200-240V380-440V
Rated operational current AC-3 (A)200-240V380-440V
Rated thermal current AC-1 (A)Auxiliary contact Non-reversingDimensions (mm) W x H x D AC operatedNon-reversing DC operatedStandardThermal overload relay(standard type) Ampere setting range (A)
Dimensions W x H x D (mm)Standard
SC-M01SC-M01RM
1.52.2
66
201NO, 1NC45 x 48 x 5645 x 48 x 68IEC 60947-4-1, EN 60947-4-1, VDE 0660, UL 508, CSA C22.2TK-M0
0.11-0.170.17-0.260.26-0.430.43-0.650.65-1.00.85-1.31.1-1.61.35-2.01.7-2.42.2-3.22.5-4.03.0-4.74.0-6.3
45 x 68.5 x 53IEC 60947-1, EN 60947-4-1, VDE 0660, UL 508, CSA C22.2
SC-E2SC-E2RM
1118.5
404060–54 x 90 x 9654 x 90 x 121.5IEC 60947-4-1, EN 60947-4-1, VDE 0660, UL 508, CSA C22.2TK-E2
4-65-86-97-119-1312-1818-2624-3632-42
54 x 78.5 x 97IEC 60947-1, EN 60947-4-1, VDE 0660, UL 508, CSA C22.2
SC-E2SSC-E2SRM
1522
505065–
TK-E2
4-65-86-97-119-1312-1818-2624-3632-4240-5044-54
SC-E3SC-E3RM
18.530
6865100–67 x 112 x 11167 x 112 x 130
TK-E3
7-119-1312-1818-2624-3628-4034-5045-6548-68
68 x 89.5 x 107.5
SC-E4SC-E4RM
2240
8080105–
TK-E3
7-119-1312-1818-2624-3628-4034-5045-6548-6864-80
76.5 x 105 x 106
SC-E5SC-E5RM
3055
1051051502NO+2NC88 x 155 x 132
TK-E5
18-2624-3628-4034-5045-6565-9585-105
100 x 122 x 123
SC-E6SC-E6RM
3760
1251251502NO+2NC100 x 169 x 138
TK-E6
45-6553-8065-9585-125
SC-E7SC-E7RM
4575
1501502002NO+2NC115 x 175 x 140
TK-E6
45-6553-8065-9585-125110-160
SC-E02SC-E02RM
2.24
99
20–43 x 81 x 8143 x 81 x 108
TK-E02
0.1-0.150.13-0.20.15-0.240.2-0.30.24-0.360.3-0.450.36-0.540.48-0.720.64-0.960.8-1.20.95-1.451.4-2.21.7-2.62.2-3.42.8-4.24-65-86-97-11
53 x 60.5 x 80.5
SC-E03SC-E03RM
35.5
121220–
TK-E02
0.1-0.150.13-0.20.15-0.240.2-0.30.24-0.360.3-0.450.36-0.540.48-0.720.64-0.960.8-1.20.95-1.451.4-2.21.7-2.62.2-3.42.8-4.24-65-86-97-119-13
SC-E04SC-E04RM
47.5
181825–
TK-E02
0.1-0.150.13-0.20.15-0.240.2-0.30.24-0.360.3-0.450.36-0.540.48-0.720.64-0.960.8-1.20.95-1.451.4-2.21.7-2.62.2-3.42.8-4.24-65-86-97-119-1312-18
SC-E05SC-E05RM
5.511
252532–
TK-E02
0.1-0.150.13-0.20.15-0.240.2-0.30.24-0.360.3-0.450.36-0.540.48-0.720.64-0.960.8-1.20.95-1.451.4-2.21.7-2.62.2-3.42.8-4.24-65-86-97-119-1312-1816-2220-25
SC-E1SC-E1RM
7.515
323250–54 x 90 x 9654 x 90 x 121.5
TK-E2
4-65-86-97-119-1312-1818-2624-36
54 x 78.5 x 97
SC-M02SC-M02RM
34
99
201NO, 1NC
TK-M0
0.11-0.170.17-0.260.26-0.430.43-0.650.65-1.00.85-1.31.1-1.61.35-2.01.7-2.42.2-3.22.5-4.03.0-4.74.0-6.35.5-8.07.5-10.5
Contactors / SC-M, SC-E
9
Protective coordination between MMSs and contactors (Individuation)IEC 60947-4-1 Type 1 The rated conditional short-circuit current Iq=50kA/240V AC, 415V AC
Note: • The full-load current of each three-phase motor is a reference value. Check the actual full-load current of the motor before use.
Motor capacity and full load current3-phase200-240V ACCapacity(kW)0.030.06–0.12–0.25–0.37–0.75–1.52.2345.57.5
1115
Manual motor starterType
BM3RSB-P25BM3RSB-P40BM3RSB-P63BM3RSB-001BM3RSB-001BM3RSB-1P6BM3RSB-1P6BM3RSB-2P5BM3RSB-004BM3RSB-004BM3RSB-6P3BM3RSB-010BM3RSB-010BM3RSB-013BM3RHB-020BM3RHB-025BM3RHB-032BM3VHB-032BM3VHB-040BM3VHB-050
Magnetic contactorType
M seriesSC-M01SC-M01SC-M01SC-M01SC-M01SC-M01SC-M01SC-M01SC-M01SC-M01SC-M01SC-M02SC-M02
M series6666666666699
E series 9 9 9 9 9 9 9 9 9 9 9 9 912182532
4050
E seriesSC-E02SC-E02SC-E02SC-E02SC-E02SC-E02SC-E02SC-E02SC-E02SC-E02SC-E02SC-E02SC-E02SC-E03SC-E04SC-E05SC-E1
SC-E2SC-E2S
SC seriesSC-03SC-03SC-03SC-03SC-03SC-03SC-03SC-03SC-03SC-03SC-03SC-03SC-03SC-0 or SC-05SC-4-0SC-4-1 or SC-5-1SC-N1
SC-N2SC-N2S
SC series 9 9 9 9 9 9 9 9 9 9 9 9 912162232
4050
Rated operational currentAC-3 (A)
Adjustablecurrent range (A)
0.16 to 0.250.25 to 0.40.4 to 0.630.63 to 1.00.63 to 1.01.0 to 1.61.0 to 1.61.6 to 2.52.5 to 4.02.5 to 4.04.0 to 6.36.3 to 106.3 to 109 to 1314 to 2019 to 2524 to 32
28 to 4035 to 50
Current(A)0.240.37–0.72–1.4–2–3.6–6.19.212162229
3850
380-415V ACCapacity(kW)0.060.090.180.180.250.370.550.751.11.52.2345.57.51115
18.522
Current(A)0.210.310.630.630.81.11.51.92.53.44.56.5811142128
3545
Protective coordination between MMSs and contactors (Combination starters)IEC 60947-4-1 Type 1 The rated conditional short-circuit current Iq=50kA/240V AC, 415V AC
Notes: • The full-load current of each three-phase motor is a reference value. Check the actual full-load current of the motor before use.• The above table shows combinations with AC operated type magnetic contactors. The link module will differ if the magnetic contactor is a DC operated type.*1 Use the base plate type in ( ) when you use the base plate.
Motor capacity and full load current3-phase200-240V ACCapacity(kW)0.03
0.06
–
0.12
–
0.25
–
0.37
–
0.75
–
1.5
2.2
345.57.5
1115
Manual motor starterType
BM3RSB-P25
BM3RSB-P40
BM3RSB-P63
BM3RSB-001
BM3RSB-001
BM3RSB-1P6
BM3RSB-1P6
BM3RSB-2P5
BM3RSB-004
BM3RSB-004
BM3RSB-6P3
BM3RSB-010
BM3RSB-010
BM3RSB-013BM3RHB-020BM3RHB-025BM3RHB-032BM3VHB-032BM3VHB-040BM3VHB-050
Magnetic contactor Type
SC-M01SC-E02SC-M01SC-E02 SC-M01SC-E02 SC-M01SC-E02 SC-M01SC-E02 SC-M01SC-E02 SC-M01SC-E02 SC-M01SC-E02 SC-M01SC-E02 SC-M01SC-E02 SC-M01SC-E02 SC-M02SC-E02 SC-M02SC-E02 SC-E03SC-E04SC-E05SC-E1
SC-E2SC-E2S
Link module
BZ0LRC09AA BZ0LRE22AA BZ0LRC09AA BZ0LRE22AA BZ0LRC09AA BZ0LRE22AA BZ0LRC09AA BZ0LRE22AA BZ0LRC09AA BZ0LRE22AA BZ0LRC09AA BZ0LRE22AA BZ0LRC09AA BZ0LRE22AA BZ0LRC09AA BZ0LRE22AA BZ0LRC09AA BZ0LRE22AA BZ0LRC09AA BZ0LRE22AA BZ0LRC09AA BZ0LRE22AA BZ0LRC09AA BZ0LRE22AA BZ0LRC09AA BZ0LRE22AA BZ0LRE22AA BZ0LRE22AA BZ0LRE22AA BZ0LRE32AA BZ0LVE51AA BZ0LVE51AA BZ0LVE51AA
Base plate
*1
(BZ0BPRE22A) BZ0BPRE22A (BZ0BPRE22A) BZ0BPRE22A (BZ0BPRE22A) BZ0BPRE22A (BZ0BPRE22A) BZ0BPRE22A (BZ0BPRE22A) BZ0BPRE22A (BZ0BPRE22A) BZ0BPRE22A (BZ0BPRE22A) BZ0BPRE22A (BZ0BPRE22A) BZ0BPRE22A (BZ0BPRE22A) BZ0BPRE22A (BZ0BPRE22A) BZ0BPRE22A (BZ0BPRE22A) BZ0BPRE22A (BZ0BPRE22A) BZ0BPRE22A (BZ0BPRE22A) BZ0BPRE22A BZ0BPRE22A BZ0BPRE22A BZ0BPRE22A BZ0BPRE32A BZ0BPV51A BZ0BPV51A BZ0BPV51A
Rated operational current (AC-3) (A)
6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 9 9 9 912182532
4050
Adjustablecurrent range(A)
0.16 to 0.25
0.25 to 0.4
0.4 to 0.63
0.63 to 1.0
0.63 to 1.0
1.0 to 1.6
1.0 to 1.6
1.6 to 2.5
2.5 to 4.0
2.5 to 4.0
4.0 to 6.3
6.3 to 10
6.3 to 10
9 to 1314 to 2019 to 2524 to 32
28 to 4035 to 50
Current(A)0.24
0.37
–
0.72
–
1.4
–
2
–
3.6
–
6.1
9.2
12162229
3850
380-415V ACCapacity(kW)0.06
0.09
0.18
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.57.51115
18.522
Current(A)0.21
0.31
0.63
0.63
0.8
1.1
1.5
1.9
2.5
3.4
4.5
6.5
8
11142128
3545
See page 02/1 of D & C catalog 19th Edition.Further Information
10
BW series/2, 3-pole
E series/2, 3-pole
FramePoleTypeRated current (A)
Rated interrupting 415V ACcapacity (kA) 380V ACIEC 60947-2 (Icu/Ics) 230V AC
100A3BW103E015, 20, 25, 30 40, 50, 60, 75 80,10015/818/925/13
160A2BW162E0100, 125, 150, 160
18/918/925/13
3BW163E0
250A2BW252E0175, 200, 225, 250
18/918/925/13
3BW253E0
100A2BW102S015, 20, 25, 30, 40, 50, 60, 75 80, 100
30/830/1550/25
3BW103S0
30/830/15100/50
FramePoleTypeRated current (A)Rated interrupting 415V ACcapacity (kA) 380V ACIEC 60947-2 (Icu/Ics) 230V AC
160A2BW162J0100, 125, 150, 16025/1325/1350/25
3BW163J0
2BW162S0100, 125, 150, 16036/1836/1885/43
3BW163S0
3BW253J0
2BW252S0175, 200, 225, 25036/1836/1885/43
3BW253S0
250A2BW252J0175, 200, 225, 25025/1325/1350/25
FramePoleTypeRated current (A)Rated interrupting 415V ACcapacity (kA) 380V ACIEC 60947-2 (Icu/Ics) 230V AC
30A2EA32AC -CE3, 5, 10, 15, 20, 301.5/11.5/12.5/2
3EA33AC -CE
50A2EA52C -CE5, 10, 15, 20, 30, 40, 502.5/22.5/25/3
3EA53C -CE
60A2EA62C -CE602.5/22.5/25/3
3EA63C -CE
FramePoleTypeRated current (A)Rated interrupting 415V ACcapacity (kA) 380V ACIEC 60947-2 (Icu/Ics) 230V AC
100A2EA102C -CE50, 60, 75, 10010/510/525/13
225A2EA202C -CE125, 150, 175, 200, 22518/518/535/18
3EA203C -CE
400A2EA402C -CE250, 300, 350, 40025/1325/1335/18
3EA403C -CE
3EA103C -CE3EA103C -CE
Compact, modular units help to reduce paneldesign and manufacturing costs
EA103C-CE SA203C-CEBW253S0
11
FramePoleTypeRated current (A)Rated interrupting 415V ACcapacity (kA) 380V ACIEC 60947-2 (Icu/Ics) 230V AC
600A3EA603C -CE500, 60035/1835/1850/25
800A3EA803 -CE700, 80035/1835/1850/25
FramePoleTypeRated current (A)Rated interrupting 415V ACcapacity (kA) 380V ACIEC 60947-2 (Icu/Ics) 230V AC
30A2SA32C -CE3, 5, 10, 15, 20, 302.5/22.5/25/3
3SA33C -CE
50A2SA52C -CE5, 10, 15, 20, 30, 40, 507.5/47.5/410/5
3SA53C -CE
2SA52RC -CE10, 15, 20, 30, 40, 5010/510/525/13
3SA53RC -CE
FramePoleTypeRated current (A)Rated interrupting 415V ACcapacity (kA) 380V ACIEC 60947-2 (Icu/Ics) 230V AC
100A2SA102C -CE15, 20, 30, 40, 50, 60, 75, 10030/830/850/25
3SA103C -CE
2SA102RC -CE15, 20, 30, 40, 50, 60, 75, 10050/1350/13100/50
3SA103RC -CE
FramePoleTypeRated current (A)Rated interrupting 415V ACcapacity (kA) 380V ACIEC 60947-2 (Icu/Ics) 230V AC
2SA202RC -CE125, 150, 175, 200, 22550/1350/13100/50
3SA203RC -CE
225A2SA202C -CE125, 150, 175, 200, 22530/830/850/25
3SA203C -CE
FramePoleTypeRated current (A)Rated interrupting 415V ACcapacity (kA) 380V ACIEC 60947-2 (Icu/Ics) 230V AC
800A3SA803RC -CE700, 80050/2550/2585/43
1000A3SA1003E -CE500-100065/4985/64100/75
1250A3SA1253E -CE500-1000, 630-125065/4985/64100/75
1600A3SA1603E -CE800-160085/64100/75125/94
FramePoleTypeRated current (A)Rated interrupting 415V ACcapacity (kA) 380V ACIEC 60947-2 (Icu/Ics) 230V AC
2SA402RC -CE250, 300, 350, 40050/2550/2585/43
3SA403RC -CE
600A3SA603RC -CE500, 60050/2550/2585/43
400A2SA402C -CE250, 300, 350, 40035/1835/1850/25
3SA403C -CE
FramePoleTypeRated current (A)Rated interrupting 415V ACcapacity (kA) 380V ACIEC 60947-2 (Icu/Ics) 230V AC
60A2SA62C -CE607.5/47.5/410/5
3SA63C -CE
2SA62RC -CE6010/510/525/13
3SA63RC -CE
S series/2, 3-pole
12
H and L series/2, 3-pole
S and E series/4-pole
FramePoleTypeRated current (A)
Rated interrupting 440V ACcapacity (kA) 400V ACIEC 60947-2 (Icu/Ics) 230V AC
50A2H52BA15, 20, 30, 40, 50
65/1765/17125/32
50A3LA53B5, 10
50/2560/30100/50
100A2H102BA15, 20, 30, 40, 50, 60, 75, 100
65/1765/17125/32
3H103R40, 50, 60, 7510085 (*415V AC)100 (*380V AC)125 (*240V AC)
3H103BA
3H53BA
FramePoleTypeRated current (A)
Rated interrupting 440V ACcapacity (kA) 400V ACIEC 60947-2 (Icu/Ics) 230V AC
400A2H402B250, 300, 350, 400
65/3365/33125/63
3H403R250, 300, 350400125/63125/63125/63
3H403B
600A3H603B500, 600
65/3365/33125/63
3H603R500, 600
125/63125/63125/63
800A3H803B700, 800
65/3365/33125/63
3H803R700, 800
125/63125/63125/63
FramePoleTypeRated current (A)
Rated interrupting 440V ACcapacity (kA) 400V ACIEC 60947-2 (Icu/Ics) 230V AC
225A2H202BA125, 150, 175, 200, 225
65/1765/17125/32
3H203R125, 150, 175200, 22585 (*415V AC)100 (*380V AC)125 (*240V AC)
3H203BA
FramePoleTypeRated current (A)
Rated interrupting 415V ACcapacity (kA) 380V ACIEC 157-1 240V AC
50A4SA54B5, 10, 15, 20, 30, 40507.5 7.5 10
100A4EA104B50, 60, 75, 100
10 15 25
100A4SA104R15, 20, 30, 40, 5060, 75, 10045 50 80
225A4SA204R125, 150, 175, 20022550 50 85
400A4SA404HA250, 300, 350, 400
45 45 85
FramePoleTypeRated current (A)
Rated interrupting 415V ACcapacity (kA) 380V ACIEC 157-1 240V AC
600A4SA604H500, 600
45 4585
800A4SA804H700, 800
45 4585
1000A4SA1004E -CE500-1000
65/49*85/64*100/75 (* 230V AC)
1250A4SA1254E -CE500-1000, 630-1250
65/49*85/64*100/75 (* 230V AC)
1600A4SA1604E -CE800-1600
85/64*100/75*125/94 (* 230V AC)
Note: * Interrupting capacity are conforming to IEC 60947-2 (Icu/Ics)
Note: * Interrupting capacity are conforming to IEC 157-1
See page 06/1 of D & C catalog 19th Edition.Further Information
13
SeriesFramePoleInstallation
Closing mechanismTripping mechanismOvercurrentprotectiondevice
FixedDraw-out
Characteristic
Protection function
L-characteristicsR-characteristicsS-characteristicsLong time delayShort time delayInstantaneousPre-alarmGround faultEarth leakagePreverse powerN-phase protectionContact temp.monitoring
DH series800, 1250, 1600, 2000, 2500, 3200, 4000A3, 4Available (except 4000AF)AvailableManual spring, motor springShunt trip, undervoltage tripAvailableAvailableAvailableAvailable
AvailableAvailableAvailableAvailableAvailableAvailable
DA series5000, 6000A2, 3, 4Not availableAvailable
AvailableNot availableAvailableAvailable
AvailableAvailableNot availableNot availableAvailableNot available
Selection guide
Comparison of interrupting capacity
Rated current (A)Rated interruptingcapacity (kA sym.)/Rated making current(kA peak)
800A 1250A 1600A 2000A 2500A 3200A 4000A 5000A 6000ARated voltage690V AC
Rated voltage440V AC
DHDH HDH PDADHDH HDH PDA
50/105 65/143 75/16555/121
85/18785/187
65/143 85/187 100/22080/176
100/220120/264
StandardsIEC60947-2EN60947-2AS3947-2NEMA PUB No. SG3ANSI C37.13BS EN60947-2VDE 0660 part 101JIS C 8372 (JIS C8201-2)JEC 160
Provides positive protection for electricpower systems
Further Information See page 08/47 of D & C catalog 19th Edition.
DH series
ASTALRABGLBVNK
14
Illuminated pushbutton switchesOperator
Momentary typeAlternate typeContact arrangementLamp voltage
LampColor of lens
Flush round head
AR22F0LAR22F5L1NO, 1NC, 1NO+1NC, 2NO, 2NC, 2NO+2NC, 3NO, 3NC, 4NO, 4NC, 5NO, 5NC5.5V AC/DC, 6V AC, 6V DC, 12V AC/DC, 15V AC/DC, 20V AC/DC, 24V AC/DC100-110V AC, 115-127V AC, 200-220V AC, 230-254V AC, 350-380V AC, 400-440V AC, 480V AC, 500-550V ACLED lamp, Incandescent lamp Green, Red, White, Yellow, Orange, Blue
Extended round head
AR22E0LAR22E5L
Extended with transparent full guard
AR22G4LAR22G9L
Flush square head
AR22F0MAR22F5M
Extended square head
AR22E0MAR22E5M
Operator
Momentary typeAlternate typeContact arrangementColor of button
Flush round head
AR22F0RAR22F5R1NO, 1NC, 1NO+1NC, 2NO, 2NC, 2NO+2NC, 3NO, 3NC, 3NO+3NC, 4NO, 4NC, 5NO, 5NC Green, Red, Black White, Yellow, Orange, Blue
Extended round head
AR22E0RAR22E5R
Mushroom head
AR22M0RAR22M5R
Flush round head with square bezel
AR22F0YAR22F5Y
Flush square head
AR22F0SAR22F5S
Operator
TypeContact arrangementColor of button
Push-lock, turn-reset(40mm dia.)
AR22V0R1NC, 1NO+1NC, 2NC, 2NO+2NC, 3NC, 4NC Red
Push-lock, turn-reset(29mm dia.)
AR22V4R
Key release push-lock,turn-reset
AR22V7R
Push-lock, pull-reset
AR22Q2R
Unibody push-lock, turn-reset
AR22VGE
Pushbutton switches
Emergency stop pushbutton switches
Ergonomically designed andperfectly suited for control panels
Command SwitchesAR22, DR22 series (22mm dia.)
The manufacturing range varies depending on the model.
AR22, DR22 series
AR30, DR30 series
15
Lens
TypeLamp voltage
LampColor of lens
Dome
DR22D0L5.5V AC/DC, 6V AC, 6V DC, 12V AC/DC, 15V AC/DC, 20V AC/DC, 24V AC/DC, 110V DC100-110V AC, 115-127V AC, 200-220V AC, 230-254V AC, 350-380V AC, 400-440V AC, 480V AC, 500-550V ACLED lamp, incandescent lamp Green, Red, White, Yellow, Orange, Blue
Extended round
DR22E3L
Flush square(transparent lens)
DR22F4M
Flush square
DR22F3M
Extended square
DR22E3M
Pilot lights
Operator
Type Konb/key operated controlContact arrangementColor of knob
Knob
AR22PRAR22PCR1NO, 1NC, 1NO+1NC, 2NO, 2NC, 2NO+2NC, 3NO, 3NC, 3NO+3NC, 4NO, 4NC, 5NO, 5NC Black, Green, Red
Lever
AR22WRAR22WCR
Key
AR22JRAR22JCR
Key (Long durability)
AR22JAR–
Selector switches
AR30, DR30 series (30mm dia.)
Illuminated pushbutton switchesOperator
Momentary typeAlternate typeContact arrangementLamp voltage
LampColor of lens
Extended round head
AR30E0LAR30E5L1NO, 1NC, 1NO+1NC, 2NO, 2NC, 2NO+2NC, 3NO, 3NC, 4NO, 4NC, 5NO, 5NC5.5V AC/DC, 6V DC, 6V AC, 12V AC/DC, 15V AC/DC, 20V AC/DC, 24V AC/DC100-110V AC, 115-127V AC, 200-220V AC, 230-254V AC, 350-380V AC, 400-440V AC, 480V AC, 500-550V ACLED lamp, incandescent lamp Green, Red, White, Yellow, Orange, Blue
Extended with transparent full guard
AR30G4LAR30G9L
Extended with full guard
AR30G3LAR30G8L
Extended with full guard(with openings)
AR30G2LAR30G7L
Push-lock, turn-reset
–AR30V5L
Operator
Momentary typeAlternate typeContact arrangementColor of button
Flush round head
AR30F0RAR30F5R1NO, 1NC, 1NO+1NC, 2NO, 2NC, 2NO+2NC, 3NO, 3NC, 3NO+3NC, 4NO, 4NC, 4NO+4NC, 5NO, 5NC Green, Red, Black White, Yellow, Orange, Blue
Extended round head
AR30E0RAR30E5R
Mushroom head
AR30M0RAR30M5R
Extended with full guard
AR30G1RAR30G6R
Giant head with full guard
AR30B2R–
Pushbutton switches
The manufacturing range varies depending on the model.
16
Further Information
See page 04/2 of D & C catalog 19th Edition.
Lens
TypeLamp voltage
LampColor of lens
Dome
DR30D0L5.5V AC/DC, 6V AC, 6V DC, 12V AC/DC, 15V AC/DC, 20V AC/DC, 24V AC/DC, 50V DC, 110V DC, 100-110V AC 115-127V AC, 220V DC, 200-220V AC, 230-254V AC, 350-380V AC, 400-440V AC, 480V AC, 500-550V ACLED lamp, incandescent lamp Green, Red, White, Yellow, Orange, Blue
Extended round
DR30E3L
Faceted
DR30K0L
Flush square
DR30F4M
Pilot lights
Operator
Type Knob/key operated controlContact arrangementColor of knob
Knob
AR30PRAR30PCR1NO, 1NC, 1NO+1NC, 2NO, 2NC, 2NO+2NC, 3NO, 3NC, 3NO+3NC, 4NO, 4NC, 4NO+4NC, 5NO, 5NC Black, Green, Red
Lever
AR30WRAR30WCR
Key
AR30JRAR30JCR
Key (Long durability)
AR30JAR–
Selector switches
Operator
TypeContact arrangementColor of button
Push-lock, turn-reset(40mm dia. with white arrow)
AR30V0R1NC, 1NO+1NC, 2NC, 2NO+2NC, 3NC, 4NC Red
Push-lock, turn-reset(65mm dia. )
AR30V1R
Push-lock, turn-reset(40mm dia. )
AR30V2R
Push-lock, pull-reset
AR30Q2R
Emergency stop pushbutton switches
The manufacturing range varies depending on the model.
17
Super timersDescription Operation Contact arrangement Timer Required socket
Surface mounting Flush mounting Rail mountingTimed Instant. Type Type Type Type
Super Timer Multi-mode 2PDT – MS4SM TP411X TP411SBA+TX4 TP411XMulti-range, • On-delay 11GB (Adaptor)compact body • Flicker + ATX2NS+TX4
• One-shot FX3 (Adaptor)• Signal off-delay (Hold-down spring)
On-delay 2PDT – MS4SA TP48X TP48SB+TX4 TP48XSPDT SPDT MS4SC 8GB (Adaptor)
Off-delay 2PDT – MS4SF + ATX1NS+TX4SPDT MS4SF-R FX3 (Adaptor)
Star-delta 2NO 1NO MS4SY
On-delay 2PDT – MS4SEwith electrical resetOn-off repetitive 2PDT – MS4SRoperationOn-off SPDT – MS4SB
Description Contact arrangement Input voltage (V) Timer Required socketTimed Instant. Surface mounting Surface mounting Flush mounting
Type Type Type
Digital timer SPDT – 100–110V AC SD4 TP28X-ULSPDT – 200–220V AC SD4D
24V DC
SPDT – 100–240V AC MD4E-AP TP48X24V AC/DC MD4E-CE 8GB
TP48SBATX1NS
TP48SBATX1NS
On-delay 2PDT – ST7P-2 TP88 – TP88X2Off-delay SPDT – ST7PF TP88R2 TP88X1
TP88B
On-delay 4PDT – ST7P-4 TP814 – TP814X2TP814R2 TP814X1TP814B
Super TimerMiniaturesize
(Hold-down spring)
Direct reading time-scaleand compact body
See page 03/49 of D & C catalog 19th Edition.
MS4S
Digital timers
Further Information
18
Miniature control relays HH52, 53, 54
TypeContact arrangementContact formRated thermal currentResistive load
Inductive loadL/R=15ms (DC)Cosø=0.3 to 0.4 (AC)Contact resistanceCoil Rated voltage
Power consumption
HH522PDTSingle5A5A5A5A0.3A1.5A2A0.2A50mΩ max. 6 to 240V AC, 6 to 110V DC (50/60Hz)AC: 1.0/1.2VA max. (60Hz), 1.2/1.4VA max. (50Hz) DC: 0.9W
HH533PDTSingle5A5A5A5A0.3A1.5A2A0.2A
HH544PDTSingle3A3A3A3A0.3A1A2A0.2A
HH52 U2PDTSingle7A7A7A7A0.3A1.5A2A0.2A
HH54 U4PDTSingle5A5A5A5A0.3A1A2A0.2A
HH52 W2PDTBifurcated5A5A5A5A0.3A1.5A2A0.2A
HH54 W2PDTBifurcated3A3A3A3A0.3A1A 2A0.2A
• SocketsDescriptionSoldering
PC board
Wire wrap
Rail mounting Screw terminal M3.5
Rail mounting Screw terminal M3.0
TypeTP58TP511TP514TP58BTP511BTP514BTP58R2TP511R2TP514R2TP58X2TP511X2TP514X2TP58X1–TP514X1
Used withHH52PHH53PHH54PHH52PHH53PHH54PHH52PHH53PHH54PHH52PHH53PHH54PHH52P–HH54P
120V AC240V AC 30V DC120V DC
120V AC 30V DC120V DC
Solder PC board
Rail mounting
Wire wrap
Reliable operation and long life
HH54
StandardsUL, CSA, TÜV
19
Miniature power relays HH62, 63, 64
TypeContact arrangementContact formRated thermal currentResistive load
Inductive loadL/R=15ms (DC)Cosø=0.3 to 0.4 (AC)Contact resistanceCoil Rated voltage
Power consumption
HH622PDTSingle10A10A10A8A0.3A1.5A2A0.2A50mΩ max. 6 to 240V AC, 6 to 110V DC (50/60Hz)AC: 2VA max. (60Hz), 2.5VA max. (50Hz) DC: 1.5W max.
HH633PDTSingle10A10A10A8A0.3A1.5A2A0.2A
HH644PDTSingle10A10A10A8A0.3A1.5A2A0.2A
HH62 W2PDTBifurcated7A5A5A5A0.3A1.5A2A0.2A
• SocketsDescription
SolderingPC boardWire wrapRail mounting screw terminal
Finger protection cover
Type
TP68TP68BTP68RTP68X2TP611X2TP614X2RZ62X2RZ64X2
Used with
HH62
HH62HH63HH64TP68X2TP614X2
120V AC240V AC 30V DC120V DC120V AC 30V DC120V DC
Further Information
See page 03/25 of D & C catalog 19th Edition.
StandardsUL, CSA, TÜV
20
UM02
UM03
Performs precise energy control at low cost
F-MPC04UM01-A A4EIntegrated power monitoring unit
F-MPC04PUM02-AR2Multi-circuit power monitoring unit
UM02-AR3 UM02-AR4F-MPC04UM03-ARA3GSingle-circuit power monitoring unit
UM03-ARA3
Measuring function
Protection
Communications interfaceDisplay and settingDevices to be connected
Type
No. of phases and wires
No. of voltage circuitsMeasuring item
Maintenance item
Harmonic currentCurrent prealarm (OCA)Leakage current prealarm (OCGA)Leakage current trip (OCG)
Current sensor (Current Transformer:CT)
Single-phase 2-wireSingle-phase 3-wire 3-phase 3-wire3-phase 4-wire
VoltageCurrentPowerActive powerReactive powerReactive energyPower-factorLeakage currentBasic component of leakage currentDemand
Max. voltage valueMin. voltage value
[V][A][W][Wh][var][varh]
[Io]
[Iob]CurrentPowerMax. currentMax. power
10 circuits10 circuits
6 circuits2
–
RS-485, T-link
*
12 circuits—
—1
–
––
–––
––––RS-485Display and setting unit UM02SCT: 5, 50, 200, 400A
—8 circuits
—
——
4 circuits
1 circuit
—1
–– (Demand only)
RS-485
1 circuit
—1
––
––
––RS-485
ZCT (separately installed)MCCB with ZCT
––
––
Note: * F-MPC 04 (UM01) is connected to CT via CT-BOX. Available
F-MPC04
UM01
Further Information See page 09/119 of D & C catalog 19th Edition.
Sales area: China
Fuji Electric (Shanghai) Co., Ltd.Suite A.B.C, 17 FI., East Bldg.Shanghai New Hualian MansionNo. 755 Huai Hai Rd. (Middle)200020 ShanghaiTHE PEOPLE’S REPUBLIC OF CHINATel: +86-21-6466-2810Fax: +86-21-6473-3292URL http://www.fesh.com.cn
Sales area: Hong Kong
Fuji Electric (ASIA) Co., Ltd.Rm. 1001,10 FI., West Wing, TsimshatsuiCenter, 66 Mody Rd., Tsimshatsui East KowloonHONG KONGTel: +852-2311-8282Fax: +852-2312-0566
Sales area: Taiwan
Fuji Electric FA Taiwan Co., Ltd.12 Fl., No. 70, Cheng Teh Rd., Sec. 1Taipei 103, TAIWAN ROCTel: +886-2-2556-0716Fax: +886-2-2556-0717URL http://www.fcs.fujielectric.com.tw
Sales area: Korea
Fuji Electric FA KOREA Co., Ltd.16 Fl, Shinsong Bldg. 25-4Youido-dong, Youngdungpo-guSeoul, 150-010, KOREATel: +82-2-780-5011Fax: +82-2-783-1707
Sales area: South East Asia, Oceania
Fuji Electric FA Singapore Private Ltd.171, Chin Swee Rd.12-01/04 San CentreSingapore 169877, SINGAPORETel: +65-6533-0010Fax: +65-6533-0021URL http://www.fujielectric.com.sg
Sales area: Thailand
Fuji Electric Technology Co., Ltd.889 Thai CC Tower, 12th Fl., Rm. 124South Sathorn Rd., Yannawa, SathornBangkok 10120, THAILANDTel: +66-2-210-0615Fax: +66-2-675-6641
Sales area: North America
Fuji Electric Corp. of AmericaPark 80 West Plaza II, Saddle BrookNJ 07663, U.S.A.Tel: +1-201-712-0555Fax: +1-201-368-8258URL http://www.fujielectric.com
Sales area: Europe
Fuji Electric GmbHGoethering 5863067 Offenbach am MainF.R. GERMANYTel: +49-69-6690290Fax: +49-69-6661020URL http://www.fujielectric.de
Distribution and Control ProductsSales Centers
Printed in Japan 2005-2 sh100 FISInformation in this catalog is subject to change without notice.
5-7, Nihonbashi Odemma-cho, Chuo-ku, Tokyo, 103-0011, Japan
URL http://www.fujielectric.co.jp/fcs/eng
Safety Considerations• For safe operation, before using the product read the instruction manual or user manual that comes with the product carefully or consult the
Fuji sales representative from which you purchased the product.• Products introduced in this catalog have not been designed or manufactured for such applications in a system or equipment that will affect
human bodies or lives.• Customers, who want to use the products introduced in this catalog for special systems or devices such as for atomic-energy control,
aerospace use, medical use, passenger vehicle, and traffic control, are requested to consult the Fuji sales division.• Customers are requested to prepare safety measures when they apply the products introduced in this catalog to such systems or facilities
that will affect human lives or cause severe damage to property if the products become faulty.• For safe operation, wiring should be conducted only by qualified engineers who have sufficient technical knowledge about electrical work or
wiring.