7
64 ASHRAE Journal October 1998 ASHRAE JOURNAL ntroducing fresh air into air- conditioned buildings in hot and humid climates requires careful analysis. Bringing in fresh air can constitute a substantial portion of the total energy consumed by the building. For ex- ample, if this makeup air is improperly treated and controlled, it can cause el- evated humidity levels. A primary/secondary system design wherein fresh air is introduced and treated via a dedicated fresh air-handling unit (AHU) and then delivered to a second- ary system offers system flexibility and improved humidity control. This type of system can also help save energy. In this article, the application of runaround coils configured in this type of a system is de- scribed. This arrangement can save en- ergy while improving humidity control. The dominant application of runaround coils is to exchange heat between fresh air and exhaust air. In hot and humid climates more than 50% of the load is latent. There- fore, cooling coils have to over-cool the air to achieve a sufficiently low sensible heat factor. This usually forces the use of re- heat to avoid high indoor humidity levels. For many of the buildings for which analy- ses were conducted, the primary cause of high indoor relative humidity was oversizing. A secondary, but still important factor, was improper treatment of introduced outside air. Figure 1 illustrates an application of the runaround coil, wherein one of the coils is placed before the cooling coil and the second after the cooling coil. The re- covery of energy from the hot outdoor air is used in reheating the overcooled air, which achieves dual energy savings. This scheme simultaneously reduces the required cooling and reheat energy as shown in Figure 2. Runaround Coil Energy Savings A simplified analysis is used to illus- trate the possible energy savings. The analysis is based on the following as- sumptions: Constant volume of AHU operating at 10,000 cfm (4719 L/s). Supply fresh air properties at stan- dard conditions (70°F [21°C] and 50% RH are used). An equation is used to express the runaround coil’s capacity Q at various conditions for the previously specified AHU: Q = F (T al T wi ) (1) Where Q is in Btu/h, F is the coil pro- Fresh Air Treatment In Hot and Humid Climates I About the Author George J. Berbari is the manager of the design department of Tabreed, a district cooling service provider in the United Arab Emirates. By George J. Berbari Member ASHRAE Saving Energy Using Runaround Recovery Coils Figure 1: A schematic of the fresh air AHU with runaround recovery coils. portionality factor, T al is the temperature of the air entering the coil, and T wi is the temperature of the water entering the coil. A manufacturer product selection pro- gram was used to evaluate the coils at three different ambient conditions: DB/WB temp. = 115/85°F (46/29°C) DB/WB temp. = 95/80°F (35/27°C) DB/WB temp. = 75/70°F (24/21°C) A polynomial was then utilized to in- terpolate the equation variables F and T wi . The basic solution is to equalize the log mean temperature differential (LMTD) of the two runaround coils: 1- Pre-cooling Runaround Coil 3- Re-heat Runaround Coil 2- Cooling Coil 4- Supplementary Heating Coil (Optional) Circulating Pump Fresh Air Treated Fresh Air Expansion Tank Pre-filter & Bag Filter 2 3 4 1 The following article was published in ASHRAE Journal, October 1998. © Copyright 1998 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE.

FreshAir_1

Embed Size (px)

DESCRIPTION

fresh air

Citation preview

6 4 ASHRAEJournal October 1998A SHRAEJ OURNALntroducingfreshairintoair-conditionedbuildingsinhotandhumidclimatesrequirescarefulanalysis. Bringing in fresh air canconstitute a substantial portion of the totalenergy consumed by the building. For ex-ample, if this makeup air is improperlytreatedandcontrolled,itcancauseel-evated humidity levels.Aprimary/secondarysystemdesignwherein fresh air is introduced and treatedviaadedicatedfreshair-handlingunit(AHU) and then delivered to a second-ary system offers system flexibility andimproved humidity control. This type ofsystem can also help save energy. In thisarticle, the application of runaround coilsconfigured in this type of a system is de-scribed.Thisarrangementcansaveen-ergy while improving humidity control.The dominant application of runaroundcoils is to exchange heat between fresh airand exhaust air. In hot and humid climatesmore than 50% of the load is latent. There-fore, cooling coils have to over-cool the airto achieve a sufficiently low sensible heatfactor. Thisusuallyforcestheuseofre-heat to avoid high indoor humidity levels.For many of the buildings for which analy-ses were conducted, the primary cause ofhighindoorrelativehumiditywasoversizing. A secondary, but still importantfactor, was improper treatment of introducedoutside air.Figure 1 illustrates an application oftherunaroundcoil,whereinoneofthecoils is placed before the cooling coil andthe second after the cooling coil. The re-coveryofenergyfromthehotoutdoorairisusedinreheatingtheovercooledair, which achieves dual energy savings.This scheme simultaneously reduces therequiredcoolingandreheatenergyasshown in Figure 2.Runaround Coil Energy SavingsA simplified analysis is used to illus-tratethepossibleenergysavings.Theanalysisisbasedonthefollowingas-sumptions: Constant volume of AHU operatingat 10,000 cfm (4719 L/s). Supply fresh air properties at stan-dard conditions (70F [21C] and 50% RHare used).AnequationisusedtoexpresstherunaroundcoilscapacityQatvariousconditionsforthepreviouslyspecifiedAHU:Q = F (Tal Twi)(1)Where Q is in Btu/h, F is the coil pro-Fresh Air TreatmentIn Hot and Humid ClimatesIAbout the AuthorGeorge J. Berbari is the manager of thedesign department of Tabreed, a districtcoolingserviceproviderintheUnitedArab Emirates.By George J. BerbariMember ASHRAESaving EnergyUsing Runaround Recovery CoilsFigure 1: A schematic of the fresh air AHU with runaround recovery coils.portionality factor, Tal is the temperatureof the air entering the coil, and Twi is thetemperature of the water entering the coil.A manufacturer product selection pro-gramwasusedtoevaluatethecoilsatthree different ambient conditions:DB/WB temp. = 115/85F (46/29C)DB/WB temp. = 95/80F (35/27C)DB/WB temp. = 75/70F (24/21C)A polynomial was then utilized to in-terpolate the equation variables F and Twi.The basic solution is to equalize the logmean temperature differential (LMTD) ofthe two runaround coils:1- Pre-cooling Runaround Coil3- Re-heat Runaround Coil2- Cooling Coil 4- Supplementary Heating Coil (Optional)Circulating PumpFreshAirTreatedFreshAirExpansionTankPre-filter& Bag Filter2 3 4 1The following article was published in ASHRAE Journal, October 1998. Copyright 1998 American Society of Heating, Refrigerating and Air-Conditioning Engineers,Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE.Advertisement in the print edition formerly in this space.Advertisement in the print edition formerly in this space.Advertisement in the print edition formerly in this space.6 8 ASHRAEJournal October 1 9 9 8) d e u n i t n o c ( l i o C g n i l o o C ) d e u n i t n o c ( l i o C g n i l o o C ) d e u n i t n o c ( l i o C g n i l o o C ) d e u n i t n o c ( l i o C g n i l o o C ) d e u n i t n o c ( l i o C g n i l o o C l i o C A . R t a e H - e R l i o C A . R t a e H - e R l i o C A . R t a e H - e R l i o C A . R t a e H - e R l i o C A . R t a e H - e R l i o C t a e H - e R l i o C t a e H - e R l i o C t a e H - e R l i o C t a e H - e R l i o C t a e H - e Rl i o C f f O l i o C f f O l i o C f f O l i o C f f O l i o C f f O t a e H e l b i s n e S t a e H e l b i s n e S t a e H e l b i s n e S t a e H e l b i s n e S t a e H e l b i s n e S t a e H l a t o T t a e H l a t o T t a e H l a t o T t a e H l a t o T t a e H l a t o T . p m e T B D . p m e T B D . p m e T B D . p m e T B D . p m e T B D t a e H l a t o T t a e H l a t o T t a e H l a t o T t a e H l a t o T t a e H l a t o T . p m e T B D . p m e T B D . p m e T B D . p m e T B D . p m e T B D t a e H l a t o T t a e H l a t o T t a e H l a t o T t a e H l a t o T t a e H l a t o TW WWWWb l / b l b l / b l b l / b l b l / b l b l / b l h / u t B h / u t B h / u t B h / u t B h / u t B h / u t B h / u t B h / u t B h / u t B h / u t B F F F F F h / u t B h / u t B h / u t B h / u t B h / u t B F F F F F h / u t B h / u t B h / u t B h / u t B h / u t B5 9 0 0 . 0 7 6 7 , 1 0 3 7 8 4 , 5 2 5 1 . 4 7 3 9 7 , 1 9 1 1 . 4 7 05 9 0 0 . 0 0 0 7 , 9 6 2 0 8 3 , 3 9 5 0 . 2 7 0 6 8 , 9 6 1 2 7 05 9 0 0 . 0 5 0 6 , 7 3 2 5 6 9 , 7 2 5 0 . 0 7 5 5 9 , 7 4 1 0 7 55 9 0 0 . 0 2 0 4 , 5 0 2 2 6 9 , 1 7 4 0 . 8 6 8 5 1 , 6 2 1 0 7 2 0 8 , 1 25 9 0 0 . 0 0 1 0 , 3 7 1 0 7 7 , 5 1 4 0 . 6 6 0 5 5 , 4 0 1 0 7 0 1 4 , 3 45 9 0 0 . 0 7 4 3 , 0 4 1 7 0 3 , 9 5 3 0 . 4 6 3 1 2 , 3 8 0 7 7 4 7 , 4 65 9 0 0 . 0 1 3 3 , 7 0 1 1 3 3 , 5 4 3 1 . 2 6 9 2 2 , 2 6 0 7 1 3 7 , 5 85 9 0 0 . 0 9 7 8 , 3 7 9 9 1 , 6 2 2 2 . 0 6 1 8 6 , 1 4 0 7 9 7 2 , 6 0 13 9 0 0 . 0 8 0 9 , 9 3 8 0 9 , 9 3 3 . 8 5 2 5 6 , 1 2 0 7 8 0 3 , 6 2 16 8 4 , 9 5 4 , 5 5 6 6 8 4 , 9 5 4 , 5 5 6 6 8 4 , 9 5 4 , 5 5 6 6 8 4 , 9 5 4 , 5 5 6 6 8 4 , 9 5 4 , 5 5 6 6 0 6 , 8 7 7 , 6 6 6 , 1 6 0 6 , 8 7 7 , 6 6 6 , 1 6 0 6 , 8 7 7 , 6 6 6 , 1 6 0 6 , 8 7 7 , 6 6 6 , 1 6 0 6 , 8 7 7 , 6 6 6 , 1 4 3 2 , 3 9 6 , 9 8 3 4 3 2 , 3 9 6 , 9 8 3 4 3 2 , 3 9 6 , 9 8 3 4 3 2 , 3 9 6 , 9 8 3 4 3 2 , 3 9 6 , 9 8 3 1 2 9 , 3 5 1 , 8 9 3 1 2 9 , 3 5 1 , 8 9 3 1 2 9 , 3 5 1 , 8 9 3 1 2 9 , 3 5 1 , 8 9 3 1 2 9 , 3 5 1 , 8 9 3Table 1: Energy analysis of a 10,000 cfm fresh air AHU with runaround heat recovery coils in Augusta, Ga.Table 1 continued.e d i s t u O e d i s t u O e d i s t u O e d i s t u O e d i s t u O e d i s t u O e d i s t u O e d i s t u O e d i s t u O e d i s t u O l a u n n A l a u n n A l a u n n A l a u n n A l a u n n A e r u t s i o M e r u t s i o M e r u t s i o M e r u t s i o M e r u t s i o M l i o C . A . R g n i l o o C - e r P l i o C . A . R g n i l o o C - e r P l i o C . A . R g n i l o o C - e r P l i o C . A . R g n i l o o C - e r P l i o C . A . R g n i l o o C - e r P l i o C g n i l o o C l i o C g n i l o o C l i o C g n i l o o C l i o C g n i l o o C l i o C g n i l o o Cb l u B y r D b l u B y r D b l u B y r D b l u B y r D b l u B y r D b l u B t e W b l u B t e W b l u B t e W b l u B t e W b l u B t e W n i B n i B n i B n i B n i B t n e t n o C t n e t n o C t n e t n o C t n e t n o C t n e t n o C W TW TW TW TW T1 1111t a e H l a t o T t a e H l a t o T t a e H l a t o T t a e H l a t o T t a e H l a t o T l i o C n O l i o C n O l i o C n O l i o C n O l i o C n O l i o C f f O l i o C f f O l i o C f f O l i o C f f O l i o C f f O. p m e T b l u B y r D . p m e T b l u B y r D . p m e T b l u B y r D . p m e T b l u B y r D . p m e T b l u B y r D . p m e T b l u B y r D . p m e T b l u B y r D . p m e T b l u B y r D . p m e T b l u B y r D . p m e T b l u B y r DF F F F F F F F F F s r u o H s r u o H s r u o H s r u o H s r u o H b l / b l b l / b l b l / b l b l / b l b l / b l F F F F F h / u t B h / u t B h / u t B h / u t B h / u t B F F F F F F F F F F 2 0 1 7 7 6 2 4 1 0 . 0 3 . 8 7 3 9 7 , 1 9 1 2 . 4 8 3 . 6 57 9 8 7 4 7 3 6 1 0 . 0 9 . 5 7 0 6 8 , 9 6 1 3 . 1 8 3 . 6 52 9 6 7 3 9 2 6 5 1 0 . 0 5 . 3 7 5 5 9 , 7 4 1 3 . 8 7 3 . 6 57 8 4 7 6 9 4 1 5 1 0 . 0 1 . 1 7 8 5 1 , 6 2 1 3 . 5 7 3 . 6 52 8 2 7 7 3 6 6 4 1 0 . 0 7 . 8 6 0 5 5 , 4 0 1 3 . 2 7 3 . 6 57 7 0 7 3 0 9 1 4 1 0 . 0 3 . 6 6 3 1 2 , 3 8 3 . 9 6 3 . 6 52 7 9 6 3 5 1 , 1 5 4 1 0 . 0 9 . 3 6 9 2 2 , 2 6 2 . 6 6 3 . 6 57 6 5 6 2 3 9 7 2 1 0 . 0 5 . 1 6 1 8 6 , 1 4 1 . 3 6 3 . 6 52 6 8 5 8 1 8 3 9 0 0 . 0 1 . 9 5 2 5 6 , 1 2 0 . 0 6 3 . 6 5L A T O T L A T O T L A T O T L A T O T L A T O T 2 1 3 , 5 2 1 3 , 5 2 1 3 , 5 2 1 3 , 5 2 1 3 , 5 4 3 2 , 3 9 6 , 9 8 3 4 3 2 , 3 9 6 , 9 8 3 4 3 2 , 3 9 6 , 9 8 3 4 3 2 , 3 9 6 , 9 8 3 4 3 2 , 3 9 6 , 9 8 3s r H 2 1 3 , 5 : s i y g r e n e c i r t c e l e p m u p g n i t a l u c r i c d e t a m i t s E 6 4 7 . 0 : s i r e w o p p m u p g n i t a l u c r i c d e t a m i t s E . r a e y / r H - W k 1 7 4 , 5 = w K 3 0 . 1W k / p H m p g 7 2 1 ( 0 6 9 , 3 ( / ) t f 7 + t f 5 . 1 1 . W k 3 0 . 1 = ) . f f e % 0 7October 1 9 9 8 ASHRAEJournal 6 9H U M I D I T YTwi = (Tal + Ta3) / 2 + 1.5303 Tal 0.029625Tal + 0.0000625Tal 2 F = 7277 + 52.78( Tal Twi)( Tal Twi)2(2)WhereTa3 istheleavingairconditionofthecoolingcoilcontrolled at 56F (13C).A simplified control system is assumed. The main coolingcoil should dehumidify the air to a level of 66.5 grains (.0095 Kg/Kg of dry air), which corresponds to that of the comfort condi-tions of 76F (24C) and 50% RH. This can be attained via a dewpoint temperature controller or a simpler DB temperature con-troller set at 56F (13C).In this system the runaround coil is operated all summer withan on-off control. A diverting valve can be used to control theleaving air temperature of the second downstream runaroundcoil, which should not exceed 70F (21C). An optional supple-mentary reheat coil, if used, can control the final leaving airtemperature which should not drop below 70F (21C).Two hot and humid climates were chosen for the analysis:Augusta, Ga. in the United States and Abu Dhabi in the UnitedArab Emirates. The Bin Hour method was used to estimate theannual energy required.Heat pipes are widely used now in place of runaround watercoils.Heatpipesareslightlymoreeffectiveastheydonotrequire circulating pumps. They use refrigerant phase changeas a heat transfer media between hotter and colder deck. Run-around coils use recirculating water for the same purpose.Heat pipe manufacturers software was used to evaluate theheat pipes performance using the same weather data for Au-gusta, Ga. The heat transfer results and annual recovered en-ergyforheatpipeswereincloseaccordancewiththoseofrunaround coils.Benefits of Runaround CoilsThe runaround coils reduced the cooling coils total annualcooling energy by 19% for Augusta (from 2056.4 106 Btu to1666.8 106 Btu [2170 GJ to 1758 GJ]) and by 21% for AbuDhabi (from 4137 106 Btu to 3280 106 Btu [4364 GJ to 3461GJ]). The supplementary reheat coil total annual energy wasreduced by 49% for Augusta (from 786 106 Btu to 398.1 106Btu [829 GJ to 420 GJ]) and by 62% for Abu Dhabi (from 1303.9 106 Btu to 495.7 106 Btu [1375.6 GJ to 523 GJ]). The Augustaresults are displayed in Tables 1 and 2.A three-way diverting valve and a third recovery coil can beused for winter heat recovery between exhaust air and fresh air.Because water piping is much easier to install than air ducts,exhaust and fresh air duct distance is not an issue. Supplemen-tary reheat is generally not required if indoor relative humidityis in the range of 60% to 65% at off-peak conditions. At relatively low ambient conditions (below 70F or 21C)the coils can be switched off and the system will operate in theeconomizer cycle mode, further reducing the cooling energyand eliminating supplementary reheat. In milder climates, thesystem can be used with reduced effectiveness. In this applica-tion, a lower supply air duct relative humidity is achieved, thusreducing the possibility of mold or mildew build-up inside theduct.The system has proven its reliability with hundreds of in-stallations in the UAE. As an example, one 5200 cfm unit (with-out supplementary reheat) was delivering a leaving air tempera-ture of DB/WB = 71.5/64F (21.9/17.8C) when ambient tem-perature was 93F (34C) and 46% RH. After the runaround coilcirculating pump was switched off and the system was left tostabilize, the leaving air condition was determined to be 60.5/60F (15.8/15.6C).e d i s t u O e d i s t u O e d i s t u O e d i s t u O e d i s t u O e d i s t u O e d i s t u O e d i s t u O e d i s t u O e d i s t u O l a u n n A l a u n n A l a u n n A l a u n n A l a u n n A e r u t s i o M e r u t s i o M e r u t s i o M e r u t s i o M e r u t s i o M l i o C g n i l o o C l i o C g n i l o o C l i o C g n i l o o C l i o C g n i l o o C l i o C g n i l o o C l i o C t a e H - e R l i o C t a e H - e R l i o C t a e H - e R l i o C t a e H - e R l i o C t a e H - e Rb l u B y r D b l u B y r D b l u B y r D b l u B y r D b l u B y r D b l u B t e W b l u B t e W b l u B t e W b l u B t e W b l u B t e W n i B n i B n i B n i B n i B t n e t n o C t n e t n o C t n e t n o C t n e t n o C t n e t n o C l i o C f f O l i o C f f O l i o C f f O l i o C f f O l i o C f f O l i o C f f O l i o C f f O l i o C f f O l i o C f f O l i o C f f O t a e H e l b i s n e S t a e H e l b i s n e S t a e H e l b i s n e S t a e H e l b i s n e S t a e H e l b i s n e S t a e H l a t o T t a e H l a t o T t a e H l a t o T t a e H l a t o T t a e H l a t o T . p m e T B D . p m e T B D . p m e T B D . p m e T B D . p m e T B D t a e H l a t o T t a e H l a t o T t a e H l a t o T t a e H l a t o T t a e H l a t o T. p m e T b l u B y r D . p m e T b l u B y r D . p m e T b l u B y r D . p m e T b l u B y r D . p m e T b l u B y r D W WWWWF F F F F F F F F F s r u o H s r u o H s r u o H s r u o H s r u o H b l / b l b l / b l b l / b l b l / b l b l / b l F F F F F b l / b l b l / b l b l / b l b l / b l b l / b l h / u t B h / u t B h / u t B h / u t B h / u t B h / u t B h / u t B h / u t B h / u t B h / u t B F F F F F h / u t B h / u t B h / u t B h / u t B h / u t B2 0 1 7 7 6 2 4 1 0 . 0 3 . 6 5 5 9 0 0 . 0 0 6 5 , 3 9 4 0 8 2 , 7 1 7 0 7 0 6 9 , 7 4 17 9 8 7 4 7 3 6 1 0 . 0 3 . 6 5 5 9 0 0 . 0 0 6 5 , 9 3 4 0 4 2 , 3 6 7 0 7 0 6 9 , 7 4 12 9 6 7 3 9 2 6 5 1 0 . 0 3 . 6 5 5 9 0 0 . 0 0 6 5 , 5 8 3 0 2 9 , 5 7 6 0 7 0 6 9 , 7 4 17 8 4 7 6 9 4 1 5 1 0 . 0 3 . 6 5 5 9 0 0 . 0 0 6 5 , 1 3 3 0 2 1 , 8 9 5 0 7 0 6 9 , 7 4 12 8 2 7 7 3 6 6 4 1 0 . 0 3 . 6 5 5 9 0 0 . 0 0 6 5 , 7 7 2 0 2 3 , 0 2 5 0 7 0 6 9 , 7 4 17 7 0 7 3 0 9 1 4 1 0 . 0 3 . 6 5 5 9 0 0 . 0 0 6 5 , 3 2 2 0 2 5 , 2 4 4 0 7 0 6 9 , 7 4 12 7 9 6 3 5 1 , 1 5 4 1 0 . 0 3 . 6 5 5 9 0 0 . 0 0 6 5 , 9 6 1 0 6 5 , 7 0 4 0 7 0 6 9 , 7 4 17 6 5 6 2 3 9 7 2 1 0 . 0 3 . 6 5 5 9 0 0 . 0 0 6 5 , 5 1 1 0 8 8 , 7 6 2 0 7 0 6 9 , 7 4 12 6 8 5 8 1 8 3 9 0 0 . 0 3 . 6 5 3 9 0 0 . 0 0 6 5 , 1 6 0 6 5 , 1 6 0 7 0 6 9 , 7 4 1L A T O T L A T O T L A T O T L A T O T L A T O T 2 1 3 , 5 2 1 3 , 5 2 1 3 , 5 2 1 3 , 5 2 1 3 , 5 0 2 7 , 2 5 1 , 5 4 0 , 1 0 2 7 , 2 5 1 , 5 4 0 , 1 0 2 7 , 2 5 1 , 5 4 0 , 1 0 2 7 , 2 5 1 , 5 4 0 , 1 0 2 7 , 2 5 1 , 5 4 0 , 1 0 4 8 , 1 7 4 , 6 5 0 , 2 0 4 8 , 1 7 4 , 6 5 0 , 2 0 4 8 , 1 7 4 , 6 5 0 , 2 0 4 8 , 1 7 4 , 6 5 0 , 2 0 4 8 , 1 7 4 , 6 5 0 , 2 0 2 5 , 3 6 9 , 5 8 7 0 2 5 , 3 6 9 , 5 8 7 0 2 5 , 3 6 9 , 5 8 7 0 2 5 , 3 6 9 , 5 8 7 0 2 5 , 3 6 9 , 5 8 7Table 2: Energy analysis of a 10,000 cfm fresh air AHU summer cooling requirement in Augusta, Ga.7 0 ASHRAEJournal October 1 9 9 8Cost Effectiveness of CoilsRunaround coils can achieve substantial energy savings inhot and humid climates. The hotter and more humid the climate,themoreeffectivethesystem.Thesystemsdesigncanbeflexible. The runaround coils recovery system is relatively inex-pensive. The added cost for installing a 10,000-cfm (4719 L/s)AHU is estimated at approximately US$8,000. This is offset bythe reduction of cooling plant capacity by about 15 tons (53kW) for Augusta and 20 tons (70kW) for Abu Dhabi, with anFigure2:ThepsychometricprocessofthefreshairAHUwith runaround recovery coils.Please circle the appropriate number on the Reader ServiceCard at the back of the publication.Extremely Helpful ..................................................... 466Helpful ................................................................... 467Somewhat Helpful ................................................... 468Not Helpful ............................................................. 469installedcostofaroundUS$800perton.Substantialenergysavings are gained mostly during peak summer demand.The runaround recovery system described in this article pro-vides a real opportunity for capital cost savings, as well as oper-ating cost savings. It is a reliable and flexible system that can beused with other system components to further save on energy.Bibliography1982. Stoecker, W. F. and J. W. Jones. Refrigeration& Air Condition-ing, Second Edition. New York: McGraw-Hill.ASHRAE Standard 90.1-1989, Energy Efficient Design of New Build-ings Except Low-Rise Residential Buildings.1992 ASHRAE Handbook, HVAC Systems & Equipment.1995. Desiccant Technology Transfer Workshop Manual, TechnologyTransfer Workshop: Desiccant Cooling Systems. Advertisement in the print edition formerly in this space.