Fire Alarm Systems | FP Conventional Fire Panels The FP Conventional Fire Panel, using trusted DC line techniques, is the ideal solution for small and medium- sized objects when modern bus technology can be done without. System Overview M1 M2 M4 M5 M6 M7 M8 M9 M10 BZ1 Fuse 1/ F/ 1A Fuse 2/ F/ 2A 33VCA 33VCA ALARM AV=FAULT ZONE6 ZONE5 ZONE4 ZONE3 ZONE1 L6 / EX ZONE5 ZONE4 ZONE3 ZONE1 24 V VALV SIR INI ZONE2 ZONE2 PREAL + - + - + - + - + - + - + - + - + - + - AV AL AV AL AV AL AV AL AV AL AVAL NANC C NA NC C NA NCC B+ B- B/2 Anlage Summer Revision Alarm Voralarm Störung abgeschaltet Revision Codebetrieb Betrieb Störung Netz/Batterie Systemstörung Alarm Störung Abgeschaltet Revision Revision -1 Abschalten 1 2 3 4 5 6 Betriebsart Signalgeber Melder- gruppe N PH Fuse 0.315 3 4 1 2 5 7 8 6 Meldergruppe Melder- gruppe Melder- gruppe Melder- gruppe Melder- gruppe Melder- gruppe Anlage rücksetzen abschalten abschalten Ein / Aus Alarm Störung Abgeschaltet Revision Revision -2 Abschalten Alarm Störung Abgeschaltet Revision Revision -3 Abschalten Alarm Störung Abgeschaltet Revision Revision -4 Abschalten Alarm Störung Abgeschaltet Revision Revision Abschalten Alarm Störung Abgeschaltet Revision Revision Abschalten Pos. Designation 1 Fuses F1 and F2 2 Terminal blocks M9 and M10 for mains and battery power. 3 Mains connection clamp block 4 Fuse F3 5 Operating panel (in corresponding national language) 6 Control panel housing FP Conventional Fire Panels Simple operation with clearly-structured operating panel and membrane keypad For two, four or six detector groups, each connecting up to 30 detectors. Alarm and fault display by multicolour LEDs, customized for each detector group Internal buzzer for acoustic alarm and fault display Separate function control for fire panel and for each individual detector zone Robust sheet steel housing www.boschsecurity.com

FP Conventional Fire Panels - Bosch Security Systemsresource.boschsecurity.com/documents/Data_sheet_enUS_1318572171.pdf · FP Conventional Fire Panels | 3 Fuses • Power supply T

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: FP Conventional Fire Panels - Bosch Security Systemsresource.boschsecurity.com/documents/Data_sheet_enUS_1318572171.pdf · FP Conventional Fire Panels | 3 Fuses • Power supply T

Fire Alarm Systems | FP Conventional Fire Panels

The FP Conventional Fire Panel, using trusted DC linetechniques, is the ideal solution for small and medium-sized objects when modern bus technology can be donewithout.

System Overview

M1 M2 M4 M5 M6 M7 M8

M9 M10

BZ1Fuse 1/ F/ 1A

Fuse 2/ F/ 2A

33V

CA

33V

CA

ALARMAV=FAULTZONE6ZONE5ZONE4ZONE3ZONE1L6 / EXZONE5ZONE4ZONE3ZONE124 VVALV SIR INIZONE2 ZONE2 PREAL

+ - + -+ -+ - + -+ -+ - + -+ - + - AV AL AV AL AV AL AV AL AV AL AVAL NANC C NA NC C NA NCC

B+ B-B/2

Anlage Summer Revision

Alarm

Voralarm

Störung

abgeschaltet

Revision

Codebetrieb

Betrieb

StörungNetz/Batterie

Systemstörung

AlarmStörungAbgeschaltetRevision

Revision -1Abschalten

1 2 3 4 5 6

BetriebsartSignalgeber

Melder-gruppe

N PH

Fuse 0.3153 4

1

2

5

7

8

6

Meldergruppe

Melder-gruppe

Melder-gruppe

Melder-gruppe

Melder-gruppe

Melder-gruppe

Anlagerücksetzen abschaltenabschalten Ein / Aus

Alarm

StörungAbgeschaltetRevision

Revision -2Abschalten

Alarm

StörungAbgeschaltetRevision

Revision -3Abschalten

Alarm

StörungAbgeschaltetRevision

Revision -4Abschalten

AlarmStörungAbgeschaltetRevision

RevisionAbschalten

Alarm

StörungAbgeschaltetRevision

RevisionAbschalten

Pos. Designation

1 Fuses F1 and F2

2 Terminal blocks M9 and M10 for mains and battery power.

3 Mains connection clamp block

4 Fuse F3

5 Operating panel (in corresponding national language)

6 Control panel housing

FP Conventional Fire Panels▶ Simple operation with clearly-structured operating

panel and membrane keypad

▶ For two, four or six detector groups, each connectingup to 30 detectors.

▶ Alarm and fault display by multicolour LEDs,customized for each detector group

▶ Internal buzzer for acoustic alarm and fault display

▶ Separate function control for fire panel and for eachindividual detector zone

▶ Robust sheet steel housing

www.boschsecurity.com

Page 2: FP Conventional Fire Panels - Bosch Security Systemsresource.boschsecurity.com/documents/Data_sheet_enUS_1318572171.pdf · FP Conventional Fire Panels | 3 Fuses • Power supply T

2 | FP Conventional Fire Panels

Pos. Designation

7 Internal buzzer

8 Clamp blocks M1 - 8 for detector and sensor lines

Functions

The fire panels FP 102/104/106‑PA have a pre alarmfunction, and can be made dependent on the activation oftwo detectors.

The fire panels FP 102/104/106‑2SO have an Englishoperating panel (country-specific customization possible),a second sensor lead, although no pre alarm.

In the case of versions with pre alarms (PA controlpanels), three delay times can be selected: 30, 60 or120 s.

In the event of an alarm being triggered, a controllablesignaling device (siren) can be switched on or off at anytime. The sounder can also be activated if the fire panel isnot in alarm status.

Reset of the fire panel after a fault is automatically carriedout once the reason for the fault has been dealt with.

Operating levelsThe fire panels have three different operating levels:

Access to level 0 is possible without code entry. Four-digitaccess codes are required to access operating level 1and 2. The access codes are set at the works and cannotbe amended.

A test of various functions can be carried out at eachoperating level.

• The level 0 test checks the functioning of the LEDsand the buzzer.

• The test at level 1 puts all detector zonessimultaneously into revision operation, whereby thefire panel must be reset following the triggering of adetector.

• The level 2 test allows certain detector groups to beselected for testing, the other groups remaining innormal mode.

ProgrammingThe PA fire panels can be used to program each individualdetector zone either for one-detector or for two-detectordependency. Independent of the programming of theindividual detector zones, all detector zones can beswitched simultaneously to single detector dependency.The switching does not affect the respective programmingof the individual detector zones.

Certifications and Approvals

Region Certification

Europe CE FP 102-PA

FP 104-PA

FP 106-PA

FP 102-2SO

FP 104-2SO

FP 106-2SO

Installation/Configuration Notes

• The fire panel must be mounted in a dry, maintainedinterior room, environmental conditions (seeTechnical Data) being taken into account.

• Attach the fire panels to the wall in such a way thatthe operating panel is at eye level.

• To enable the front door to be removed, at least50 mm of free space must be left on the left-hand sideof the control panel.

• For optimum battery life, the fire panel should only beoperated in locations having normal roomtemperatures.

• The appropriate requirements stipulated by the localauthorities (e. g. fire service) are to be conformed to.

Technical Specifications

Special features

Number of detector zones

• FP 102-PA / FP 102-2SO 2

• FP 104-PA / FP 104-2SO 4

• FP 106-PA / FP 106-2SO 6

Connectable detectors Max. 30 per detector zone

Electrical

Power supply voltage 230 V AC +/- 10%

Power supply current 300 mA

Frequency 50/60 Hz

Power supply output voltage 28V DC

Power supply output current Max. 1,800 mA

Current consumption in stand-by mode

• FP 102-PA / FP 102-2SO 100 mA

• FP 104-PA / FP 104-2SO 120 mA

• FP 106-PA / FP 106-2SO 140 mA

Current consumption in alarm mode

• FP 102-PA / FP 102-2SO 1,400 mA

• FP 104-PA / FP 104-2SO 1,600 mA

• FP 106-PA / FP 106-2SO 1,800 mA

Page 3: FP Conventional Fire Panels - Bosch Security Systemsresource.boschsecurity.com/documents/Data_sheet_enUS_1318572171.pdf · FP Conventional Fire Panels | 3 Fuses • Power supply T

FP Conventional Fire Panels | 3

Fuses

• Power supply T – 315 mA

• Battery power supply F – 2 A

• Primary line output F – 1 A

Battery power supply

Battery type and amount Gel-accumulator, 2 units (con-nected in series)

Battery capacity 12 V / 7.2 Ah

Battery charge voltage 27.4 V DC

Battery charge current 500 mA

Back-up time

• FP 102-PA / FP 102-2SO Max. 70 h in stand-by modeMax. 4 h in event of alarm

• FP 104-PA / FP 104-2SO Max. 59 h in stand-by modeMax. 4 h in event of alarm

• FP 106-PA / FP 106-2SO Max. 45 h in stand-by modeMax. 4 h in event of alarm

Primary line features

Stand-by voltage

• Zones 20 V DC (+5% / -10%)

• Signaling device lines 24 V DC (±5%)

Current consumption

• In standby mode Approx. 5 mA (±1%)

• In alarm mode Approx. 102 mA (±1%)

Terminator resistance RE (when con-nected to Bosch detectors)

3.92 kΩ ¼ W

Maximum line resistance 100 Ω (per primary line)

Mechanics

Dimensions (W x H x D) 350 x 340 x 90 mm

Weight

• Without batteries 3.5 kg

• With 2 batteries (12V/7.2Ah) 7.9 kg

Housing color Light-gray, RAL 9002

Environmental Considerations

Protection class as per EN 60529 IP 30

Classes of equipment as per EN 60950 Class II equipment

Permissible operating temperature 0 °C . . . +40 °C

Permissible storage temperature -40 °C . . . +70 °C

Ordering Information

FP 102‑PA Conventional Fire PanelFor two detector zones, up to 60 detectors,with pre-alarm, two-detector dependencypossible

FP-102-PA

FP 104‑PA Conventional Fire PanelFor four detector zones, up to 120 detectors,with pre-alarm, two detector dependencypossible

FP 104-PA

FP 106‑PA Conventional Fire Panelfor six detector zones, up to 180 detectors,with pre-alarm, two detector dependencypossible

FP 106-PA

FP 102‑2SO Conventional Fire Panelfor two detector zones, up to 60 detectors,without pre-alarm, two signaling device out-puts

FP 102-2SO

FP 104‑2SO Conventional Fire Panelfor four detector zones, up to 120 detectors,without pre-alarm, two signaling device out-puts

FP 104-2SO

FP 106‑2SO Conventional Fire Panelfor six detector zones, up to 180 detectors,without pre-alarm, two signaling device out-puts

FP 106-2SO

Accessories

Gel Battery 12 V / 7.2 Ah(DU = 1 unit)

IPP-12V-7.2Ah

www.boschsecurity.com

Page 4: FP Conventional Fire Panels - Bosch Security Systemsresource.boschsecurity.com/documents/Data_sheet_enUS_1318572171.pdf · FP Conventional Fire Panels | 3 Fuses • Power supply T

4 | FP Conventional Fire Panels

Americas:Bosch Security Systems, Inc.130 Perinton ParkwayFairport, New York, 14450, USAPhone: +1 800 289 0096Fax: +1 585 223 [email protected]

Europe, Middle East, Africa:Bosch Security Systems B.V.P.O. Box 800025600 JB Eindhoven, The NetherlandsPhone: + 31 40 2577 284Fax: +31 40 2577 [email protected]

Asia-Pacific:Robert Bosch (SEA) Pte Ltd, Security Systems11 Bishan Street 21Singapore 573943Phone: +65 6258 5511Fax: +65 6571 [email protected]

Represented by

© Bosch Security Systems Inc. 2010 | Data subject to change without noticeT274947211 | Cur: en-US, V15, 27 Jul 2010