    Intelligent Vortex Flowmeter Model 83S-TInstallation, Configuration, Troubleshooting, and Maintenance

    REMOTE MOUNTEDELECTRONICS HOUSINGSHOWN WITH DIGITALDISPLAY/CONFIGURATOR

    BRACKET MOUNTS TOSURFACE OR PIPE

    FLOWTUBEASSEMBLY(INCLUDESCABLE)

    HART COMMUNICATOR

  • 8/13/2019 Foxboro 83ST

    2/72

    MI 019-174 May 2007

  • 8/13/2019 Foxboro 83ST

    3/72

    MI 019-174 May 2007

    iii

    Contents

    Figures................................................................................................................................... vii

    Tables................................................................................................................................... viii

    1. Introduction...................................................................................................................... 1

    Overview .............................................................................................................................. 1

    Reference Documents ............................................................................................................... 1Standard Specifications ......................................................................................................... 2

    Electrical Safety Specifications ................................................................................................... 3

    2. Installation ........................................................................................................................ 5

    Fundamental Installation Requirements ............................................................................... 5Unpacking ............................................................................................................................ 5Flowmeter Identification ...................................................................................................... 5

    Mechanical Installation ............................................................................................................. 6Dimensions .......................................................................................................................... 6Piping Considerations .......................................................................................................... 6Installing the Flowmeter Body .............................................................................................. 8Mounting the Electronics Housing .................................................................................... 11

    Field Termination Wiring ....................................................................................................... 12Two-Wire Hook-up ........................................................................................................... 13Three-Wire Hook-up ......................................................................................................... 15Four-Wire Hook-up ........................................................................................................... 17

    3. Operating the Flowmeter ................................................................................................ 19

    Introduction ............................................................................................................................ 19

    Passwords ................................................................................................................................ 19

    Configuration Database .......................................................................................................... 19

    Changing the Configuration (Configuration Menu) ............................................................... 22Identification Parameters .................................................................................................... 22Electronics Options ............................................................................................................ 23Process Fluid Parameters .................................................................................................... 24Application Parameters ....................................................................................................... 24Output Options ................................................................................................................. 25

    Preconfiguring the Meter ........................................................................................................ 25

    Displaying the Configuration Database ................................................................................... 25

    Adjusting the Meter ................................................................................................................ 25mA Calibration (D/A Trim) ............................................................................................... 25Total Reset ......................................................................................................................... 26Low Flow Cut-In ............................................................................................................... 26

    http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/
  • 8/13/2019 Foxboro 83ST

    4/72

    MI 019-174 May 2007

    iv

    Upper Range Value ............................................................................................................ 26

    Reading the Measurements ..................................................................................................... 26

    Testing the Meter and Loop (Test Menu) ............................................................................... 27Self-Test ............................................................................................................................. 27Loop Test or Loop Calibration ........................................................................................... 27

    Electronic Module Replacement ............................................................................................. 27

    4. Troubleshooting.............................................................................................................. 29

    General Troubleshooting ........................................................................................................ 29Flowmeter Has Incorrect Output ....................................................................................... 29Flowmeter Output Indicates Flow When There Is No Flow ............................................... 29Flowmeter Output Indicates Higher Flow Rate with Decreasing Flow ............................... 30Fluctuating Output ............................................................................................................ 30

    No Output Troubleshooting ................................................................................................... 30

    Module Test Procedure ........................................................................................................... 31

    Sensor Test Procedure ............................................................................................................. 31

    Appendix A. Determining Special Measuring Units............................................................. 33

    Appendix B. HART Configuration Instructions................................................................. 35

    Introduction ............................................................................................................................ 35

    HART Menu Structure ........................................................................................................... 35

    Appendix C. Local Configuration Instructions................................................................... 41

    Introduction ............................................................................................................................ 41

    Using the Local Configurator .................................................................................................. 42Measurements (MEASURE) .............................................................................................. 42Display Bar Indicator ......................................................................................................... 42Moving inside the Menu System ........................................................................................ 42Viewing Data (DISPLAY) .................................................................................................. 43Answering a Question ........................................................................................................ 43Entering the Password ........................................................................................................ 43Activating an Edit, Pick-List or User Function Menu Block ............................................... 43Editing Numbers and Strings ............................................................................................. 44Picking from a List ............................................................................................................. 44mA Calibration (TEST/CAL 4 mA or CAL 20 mA) .......................................................... 44Transmitter Status .............................................................................................................. 44Changing the Password ...................................................................................................... 44

    Local Configurator Menu Tree ............................................................................................... 45

    Local Configurator Menu (1 through 8) ................................................................................. 46

    Appendix D. Configuration Database.................................................................................. 55

    Flowtube Parameters ............................................................................................................... 55

    Identification Parameters ......................................................................................................... 56

    http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/
  • 8/13/2019 Foxboro 83ST

    5/72

    MI 019-174 May 2007

    v

    Elecrtonics Options ................................................................................................................. 56

    Process Fluid Parameters ......................................................................................................... 57

    Application Parameters ........................................................................................................... 59

    Output Options ...................................................................................................................... 60

    Index .................................................................................................................................... 61

    http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/
  • 8/13/2019 Foxboro 83ST

    6/72

    MI 019-174 May 2007

    vi

  • 8/13/2019 Foxboro 83ST

    7/72

    Figures MI 019-174 May 2007

    vii

    Figures

    1 83S Sanitary Vortex Flowmeter .................................................................................... 5

    2 Flowmeter Identification .............................................................................................. 63 Flowmeter Body Cable Support ................................................................................... 74 Bypass Piping ............................................................................................................... 75 3A I-Line Fitting .......................................................................................................... 96 NSI Class 150 RF Flange ............................................................................................. 97 SI Coupling ................................................................................................................. 108 RJT Coupling .............................................................................................................. 109 3A Tri-Clamp .............................................................................................................. 11

    10 ISS Coupling ................................................................................................................ 1111 Pipe-Mounted Electronics Housing ............................................................................. 1212 Electronics Housing ..................................................................................................... 13

    13 Installation Wiring - 4 to 20 mA Output (Two-wire) .................................................. 1414 Load Requirements ...................................................................................................... 1515 Installation Wiring - Pulse Output (Three-wire) .......................................................... 1616 Installation Wiring (Four-wire) .................................................................................... 1717 Normal Vortex Frequency Waveform .......................................................................... 3218 HART On-Line Menu Structure Part 1 of 2 ........................................................... 3719 HART On-Line Menu Structure Part 2 of 2 ........................................................... 3920 Fast-Key Function/Variable Chart ............................................................................... 40

    http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/
  • 8/13/2019 Foxboro 83ST

    8/72

    Tables MI 019-174 May 2007

    viii

    Tables

    1 Reference Documents .................................................................................................. 1

    2 Standard Specifications ................................................................................................ 23 Electrical Safety Stpecifications .................................................................................... 44 Typical Piping Configurations ..................................................................................... 86 User Information ......................................................................................................... 205 Configuration Database ............................................................................................... 207 Menu Tree Functional Overview ................................................................................. 418 Configuration Database ............................................................................................... 55

    http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/
  • 8/13/2019 Foxboro 83ST

    9/72

    1

    1. Introduction

    Overview

    The 83S-T Sanitary Vortex Flowmeter measures fluid flow rates using the principle of vortexshedding. The flowmeter produces a digital signal (HART protocol), a 4 to 20 mA analog signal,and a scaled pulse signal proportional to the volumetric flow rate.

    Fluid flowing through the flowmeter body passes a specially shaped vortex shedder that causesvortices to form and shed alternately from sides of the shedder at a rate proportional to the flowrate of the fluid. These shedding vortices create an alternating differential pressure that is sensedby a detector located within the shedder. A pulsed voltage is generated by the detector with afrequency that is synchronous with the vortex shedding frequency. This voltage is thenconditioned by an electronic module and processed by the microcontroller to produce a digitalsignal, an analog (4 to 20 mA dc) signal, and a scaled pulse signal.

    The flowtube body is connected to the electronic housing by a 4.5 m (15 ft) flexible cable. Theelectronics housing is mounted to a bracket, which must be mounted to a vibration-free wall orpipe.

    Reference DocumentsIn addition to this instruction, there are other user documents that support the 83S-T SanitaryVortex Flowmeter. These documents are shown in Table 1.

    Table 1. Reference Documents

    Document Number Document Description

    Dimensional Print

    DP 019-154 83S, Style A Sanitary Vortex Flowmeter

    Parts List

    PL 008-713 83S, Style A Sanitary Vortex Flowmeter

    Instructions

    MI 019-196

    MI 019-198

    MI 020-495MI 020-501MI 020-505MAN 4250

    E83, E83, and E83 Vortex Flowmeters, Conversion to I/A SeriesIntelligent Vortex FlowmetersVortex Meter Digital Display/Configurator Kit

    PC20/IFDC Intedlligent Field Device ConfiguratorPC50 Intelligent Field Device Tool (installation and parts list)PC50 Intelligent Field Device Tool (operation using HART protocol)HART Communicator Product Manual

  • 8/13/2019 Foxboro 83ST

    10/72

    MI 019-174 May 2007 1. Introduction

    2

    Standard SpecificationsTable 2. Standard Specifications

    Item Specification

    Process Temperature Limits 20 and +200C (0 and 400F)

    Ambient Temperature Limits 40 and +85C (40 and +185

    F)

    Flowmeter OutputAnalog

    Digital (HART)

    Scaled Pulse

    4 to 20 mA dc into a maximum of 1450 ohms depending onpower supply (refer to graph in Figure 14).

    Digital signal conveyed at a 1200 baud transmission rate viaFSK tones superimposed on power supply leads. HARTprotocol.

    Isolated 2-wire contact closure. Pulse rate (0 to 100 Hz)proportional to volumetric flow rate.

    Product Safety Specification Refer to instrument data plate for type of certification andobserve applicable wiring requirements. Electricalcertifications and conditions of certification are listed inTable 3 on page 4.

    Flow Rate Requirements Refer to FlowExpertProsizing program.

    Static Pressure Limits

    With Flanged Connection

    All Other Connections

    Full vacuum to the pressure rating of the mating connections,as follows:All sizes: 1035 kPa (150 psi)

    50 mm (2 in) size: 1725 kPa (250 psi)

    80 mm (3 in) size: 1035 kPa (150 psi)Flowmeter Output:

    Analog 4 to 20 mA dc into a maximum of 1450 depending onpower supply (refer to graph in Figure 14).

    Pulse Square wave voltage equals supply voltage minus two volts.Maximum current is 10 mA (sink or source). Shielded andtwisted cable is recommended.

    http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/
  • 8/13/2019 Foxboro 83ST

    11/72

    1. Introduction MI 019-174 May 2007

    3

    Electrical Safety SpecificationsNOTE

    The 83S-T Flowmeter has been designed to meet the electrical classifications listedin Table 3. For detailed information on status of the agency approvals/certifications,contact Invensys Foxboro.

    Scaled Pulse OutputSpecifications

    Isolated 2-wire contact-closure Applied voltage limits:

    12.5 V dc minimum

    42.0 V dc maximum Maximum ON state voltage drop: 0.5 V dc Maximum ON state current: 250 mA Update rate: 4 Hz Maximum OFF state leakage current:

    0.10 mA @ 12.5 V dc0.25 mA @ 24.0 V dc0.42 mA @ 42.0 V dc

    250 mA short circuit protected Reverse polarity protected

    Signal Output Combinations 2-Wire Hook-Up

    4 to 20 mA and HART (1200 baud)3-Wire Hook-Up 4 to 20 mA, HART (1200 baud), and Scaled Pulse4-Wire Hook-Up 4 to 20 mA, HART (1200 baud), and Scaled Pulse

    (a) Maximum temperature limit is a function of sensor type.

    Table 2. Standard Specifications (Continued)

    Item Specification

  • 8/13/2019 Foxboro 83ST

    12/72

    MI 019-174 May 2007 1. Introduction

    4

    Table 3. Electrical Safety Stpecifications

    Agency Certification,Types of Protection, and

    Area Classification Conditions of Certification

    ElectricalSafety Design

    Code

    CSAintrinsically safe for Class I, Division 1,Groups A, B, C, and D; Class II, Division 1,Groups E, F, and G; Class III, Division 1.

    Temperature Class T3C at 85C,and T4A at 40C.Connect per TI 005-105.

    A

    CSAsuitable for Class I, Division 2, GroupsA, B, C, and D; Class II, Division 2, Groups Fand G; Class III, Division 2.

    Maximum ambient 85C.

    FMintrinsically safe for Class I, Division 1,Groups A, B, C, and D; Class II, Division 1,Groups E, F, and G; Class III, Division 1.

    Temperature Class T3C, Ta = 85Cand T4A, Ta = 40C.Connect per TI 005-101.

    FMnonincendive for Class I, Division 2,

    Groups A, B, C, and D; Class II, Division 2,Groups F and G; Class III, Division 2.

    Temperature Class T5. Ta = 85C.

  • 8/13/2019 Foxboro 83ST

    13/72

    5

    2. Installation

    Fundamental Installation Requirements

    Foxboro vortex flowmeters shall be installed to meet all applicable local installation regulations,such as hazardous location requirements, electrical wiring codes, and mechanical piping codes.Persons involved in the installation should be trained in these code requirements to ensure thatthe installation takes maximum advantage of the safety features designed into the flowmeters.

    Figure 1. 83S Sanitary Vortex Flowmeter

    UnpackingThe 83S Series Vortex Flowmeter is built to be durable, but it is part of a calibrated precisionsystem and should be handled as such.

    Use care when unpacking. The flowmeter is a rugged two-piece unit. The flowmeter is shippedwith the flowtube body connected to the electronics housing by a flexible cable. Do notcut or

    disconnect the cable.Packing material should be disposed of in accordance with local regulations. All packing materialis nonhazardous and is generally acceptable to landfills.

    Flowmeter IdentificationTo determine the model configuration of your flowmeter, refer to Figure 2. For interpretation ofthe Model Code, refer to PL 008-713.

    ELECTRONICSHOUSING

    MOUNTING BRACKETFOR PIPE OR SURFACEMOUNTING

    U-CLAMPAND NUTS

    CABLE STRAPCABLE STRAP

    SUPPORT FORCABLE STRAP

    PIPELINE

    FLOWMETERBODY

    END CONNECTION

    CLAMP

    FLEXIBLE CABLE

    DN 50 OR2 IN PIPE

  • 8/13/2019 Foxboro 83ST

    14/72

    MI 019-174 May 2007 2. Installation

    6

    Figure 2. Flowmeter Identification

    Mechanical Installation

    DimensionsFor overall dimensions of the flowmeter and end connections, see DP 019-154.

    Piping Considerations

    CAUTION!

    1. Prior to installation, spring back the piping on either end of the flowmeter to allowas much space as is required to install the flowmeter without damaging the flowtubeends.2. Mating end connection parts (clamps, connections, and gaskets) are required andare supplied by the user. Select a gasket or seal material which is suitable for the

    process liquid.3. Support the cable that connects the flowmeter body to the electrical housing. Thesupports must be approximately 30 cm (12 in) from the flowmeter body.4. Temperature limit of cable is 105C (220F). Do not support cable on surfaceexceeding this temperature. See Figure 3.

    VORTEX FLOWMETER

    MODEL 83S-TREF.NO. ORIGINSUPPLY 12.5-42 Vdc MWP @ 100FMETER BODY MATLMAX. AMB. TEMP. 85CTEMP. LIMITREF K-FACT. PULSES/

    CUST. DATA

    3

    CONFORMS

    SANITARY

    TO3-A

    28 - 02

    STANDARD

    DATA/AGENCY LABEL SERIAL NO.

    MODEL CODE

    STYLE LETTER

    PLANT OF MFG. AND DATE

    TEMP. LIMIT

    CUSTOMERTAGGING INFO.

    MATERIAL MAXIMUM PRESSURE

    AMPLIFIER CALIBRATIONAT UPPER RANGE VALUE

    REFERENCE K-FACTOR

    FLEXIBLE CABLE

    THE FOXBORO COMPANY, FOXBORO, MA, U.S.A.

  • 8/13/2019 Foxboro 83ST

    15/72

    2. Installation MI 019-174 May 2007

    7

    Figure 3. Flowmeter Body Cable Support

    Effects of Piping on Flowmeter Performance

    The vortex shedder axis may be oriented to reduce, or in some cases eliminate, vibrationinfluence. Positioning the flowmeter body so that vibrations are parallel to the sensor diaphragms

    minimizes the effect of vibrations.

    The flowmeter body should be mounted in a straight, unobstructed pipe to ensure that it willperform to its fullest capabilities. The recommended minimum amount of minimum pipeupstream is shown in Table 4. There should be a minimum of eight diameters of straight pipedownstream. See Figure 4.

    It is recommended that control valves, when required, be mounted downstream from theflowmeter body to ensure that back pressure is sufficient to maintain a full pipe, and to preventpressure loss sufficient to cause flashing or cavitation. Ensure that gaskets do not protrude intopipe line.

    CAUTION!The piping which attaches to the flowmeter body end connections must be rigidlysupported. This minimizes the effects of piping vibration on flowmeter performance.

    Figure 4. Bypass Piping

    APPROXIMATELY30 CM (12 IN)

    8 PIPEDIAMETERS

    SHUTOFF VALVES

    SEE TABLE 4

  • 8/13/2019 Foxboro 83ST

    16/72

    MI 019-174 May 2007 2. Installation

    8

    NOTE

    1. The flowmeter should not be located near pump discharge line or suction lines.Pumps often produce oscillatory flow which may affect vortex shedding orproduce pipe vibration.

    2. Flowmeters mounted near the discharge of liquid positive displacement pumpsmay experience severe flow fluctuations and cause damage to the sensor.

    3. Good piping practice is to assume that for four pipe diameters upstream and twopipe diameters downstream, the internal surface of the pipe shall be free frommill scale, pits, holes, reaming scores, rifling, bumps, or other irregularities.

    Bypass Piping

    It is sometimes desirable to provide bypass piping if the flow cannot be interrupted for servicing

    the flowmeter. See Figure 4.

    WARNING!

    If a bypass is used, it must also incorporate some means to relieve the pressure fromthe main line before the vortex flange bolts or clamps are loosened.

    Installing the Flowmeter BodyThe 83S Sanitary Vortex Flowmeter has six different end connection possibilities. The endconnections that you have were determined from the selections made in the original specificationof your flowmeter configuration.

    All end connections are welded to the flowtube body.

    The mating end connections, gaskets, and clamps are supplied by you, the user.

    3A I-Line Fitting (Code C)

    The 3A I-Line fitting mates with Cherry Burrell 15 WI or equivalent. See Figure 5.

    1. Insert seals into flowtube ends.

    Table 4. Typical Piping Configurations

    Upstream ConfigurationRecommended Upstream

    Pipe Diameters

    90Elbow 30

    Two elbows in different planes with closest elbow insame plane as shedder element(a). 45

    Two elbows in different planes with closest elbowperpendicular to plane of shedder(a).

    35

    1.5:1 reduction in piping diameter. 35

    Butterfly valve (wide open) 30(a)Shedder is located in bore of flowmeter.

  • 8/13/2019 Foxboro 83ST

    17/72

    2. Installation MI 019-174 May 2007

    9

    2. Insert mating pipe end and tighten clamp securely.

    Figure 5. 3A I-Line Fitting

    ANSI Class 150 RF Flange (Code F)

    The ANSI Class 150 RF flange is a crevice-free design for general sanitary service. SeeFigure 6.

    Figure 6. NSI Class 150 RF Flange

    1. Gaskets are normally required and are supplied by the user. Select a gasket materialthat is suitable for the process fluid.

    2. Insert gaskets between body of flowmeter and adjacent flanges. Position gaskets sothat ID of each gasket is centered on ID of flowmeter and adjacent piping.

    CAUTION!

    1. Verify that the ID of the gaskets is larger than that of the flowmeter bore and pipe

    and that they do not protrude into the flowmeter entrance or exit. Protrusion into theflowstream has an adverse affect on performance.2. Gaskets do not prevent flanges from being wetted by process fluids.

    NOTE

    If welding of flanges to the process piping is required, protect the inside diameter ofthe flowmeter from weld splatter. Failure to do this may adversely affect flowmeteraccuracy.

  • 8/13/2019 Foxboro 83ST

    18/72

    MI 019-174 May 2007 2. Installation

    10

    3. Visually inspect for concentricity of mating flanges.

    4. Tighten bolts in accordance with conventional flange bolt tightening practice (i.e.,incremental and alternate tightening of bolts).

    SI Coupling (Code M)

    Code M is an SI (DIN 11851) coupling with an external thread. See Figure 7.

    Figure 7. SI Coupling

    1. Insert seals into grooves in flowtube ends.

    2. Tighten nuts securely.

    RJT Coupling (Code R)

    Code R is an RJT coupling (ring-type joint coupling) per BS 1864 with an external thread. SeeFigure 8.

    Figure 8. RJT Coupling

    1. Insert seals into cavity in flowtube ends.2. Tighten nuts securely.

  • 8/13/2019 Foxboro 83ST

    19/72

    2. Installation MI 019-174 May 2007

    11

    3A Tri-Clamp (Code T)

    Code T is a 3A Tri-Clamp Type Quick-Disconnect Ferrule. It mates with Tri-Clover 14 WMPor equivalent. See Figure 9.

    Figure 9. 3A Tri-Clamp

    1. Insert seal into flowtube ends.2. Full face contact should be made between the ends prior to installing and tightening

    the clamps.

    ISS Coupling (Code U)

    Code U is an ISS (ISO 2853) coupling with an external thread. See Figure 10.

    Figure 10. ISS Coupling

    1. Insert seals onto flowtube ends.

    2. Tighten nuts securely.

    Mounting the Electronics HousingThe electrical housing can be either pipe or wall mounted. Do notmount the electronics housingon process piping. Excess vibration may damage the amplifier and amplifier housing. Support thecable that connects the flowmeter body to the electronics housing. The supports must beapproximately 30 cm (12 in) from the flowtube body and the electronics housing. A loose cablemay cause wear at the cable connections (see Figure 11).

  • 8/13/2019 Foxboro 83ST

    20/72

    MI 019-174 May 2007 2. Installation

    12

    .

    Figure 11. Pipe-Mounted Electronics Housing

    CAUTION!

    Temperature limit of cable is 105C (220F). Do not support cable on any surfacethat exceeds this temperature.

    Field Termination Wiring

    NOTE

    The wiring installation shall be in accordance with the local or national regulationsapplicable to the specific site and classification of the area.

    The electronics housing has an electronic module compartment and a field terminalcompartment. It also provides 1/2 NPT conduit openings for access from either side of theflowmeter and for ease in wiring to the field terminals. See Figure 12.

    NOTE

    One conduit opening contains a threaded plug. Do not discard this plug.

    Remove the field terminal compartment cover (shown in Figure 12) to make electricalconnections. Keep the electronic module compartment cover closed to ensure protection for theelectronic module and to prevent moisture and atmospheric contaminants from entering thecompartment.

    ELECTRICALHOUSING

    MOUNTINGBRACKET

    CABLE STRAPWITHIN30 CM (12 IN)

    APPROXIMATELY30 CM (12 IN)

    ELECTRICAL CONDUIT OPENING

    (PLUGGED IF UNUSED)

  • 8/13/2019 Foxboro 83ST

    21/72

    2. Installation MI 019-174 May 2007

    13

    Figure 12. Electronics Housing

    There are three wiring combinations that depend on how the flowmeter is to be used.

    2-Wire Hook-up4 to 20 mA and HART (1200 baud)

    3-Wire Hook-up

    4 to 20 mA, HART (1200 baud), and Scaled Pulse 4-Wire Hook-up

    4 to 20 mA, HART (1200 baud), and Scaled Pulse

    Two-Wire Hook-up

    4 to 20 mA Output Mode

    A dc power supply must be used with each flowmeter and receiver wiring loop to supply powerfor the mA signal. The dc power supply may be either a separate signal unit, a multiple unit

    supplying power to several flowmeters, or built into the receiver.Connect the supply and receiver loop wiring (0.50 mm2or 20 AWG typical) to the terminals inthe field-terminal compartment of the flowmeter, as shown in Figure 13.

    ELECTRONICMODULECOMPARTMENT

    ELECTRICAL CONDUIT OPENING

    FIELD TERMINAL COMPARTMENT

  • 8/13/2019 Foxboro 83ST

    22/72

    MI 019-174 May 2007 2. Installation

    14

    Figure 13. Installation Wiring - 4 to 20 mA Output (Two-wire)

    Twisted pair wiring should be used to prevent electrical noise from interfering with the dc currentoutput signal. In some instances, shielded cable may be necessary. Grounding of the shield shouldbe installed at one point only (at the power supply). Do not ground the shield at the flowmeter.

    Flowmeter connection polarities are indicated on the terminal block. If the loop is to containadditional instruments, install them between the negative terminal of the flowmeter and thepositive terminal of the receiver, as shown in Figure 13.

    Power Supply and External Load

    The required loop power supply voltage is based on the total loop resistance. To determine thetotal loop resistance, add the series resistance of each component in the loop (do not includeflowmeter). The required power supply voltage can be determined from Figure 14.

    +

    A B

    --

    +

    POWER RECEIVER

    ADDITIONALRECEIVERS

    IN LOOP

    CASE GROUND TERMINAL

    TWO 1/2 NPT CONDUIT CONNECTIONS AREPROVIDED (ON OPPOSITE SIDES). INSERTPLUG IN CONNECTION NOT USED.

    TERMINAL BLOCK

    SUPPLY

    250 OHM MIN LOAD

    REQUIRED FOR

    HART COMMUNICATOR.CONNECT TO LOOP TO

    CONFIGURE FLOWMETER

    ++COMMUNICATION

  • 8/13/2019 Foxboro 83ST

    23/72

    2. Installation MI 019-174 May 2007

    15

    Figure 14. Load Requirements

    The flowmeter will function with an output load less than 250 ohms, provided that a configuratoris not connected to it. Connecting a configurator to a loop with less than 250 ohms may causecommunication problems.

    As an example, for a flowmeter with a loop resistance of 500 ohms, referring to Figure 14, theminimum power supply voltage is 22 V dc, while the maximum power supply voltage is 42 V dc.

    Conversely, given a power supply voltage of 24 V dc, the allowable loop resistance is from 200 to565 ohms.

    NOTE

    1. The power supply must be capable of supplying 22 mA.2. Power supply ripple must not allow the instantaneous voltage to drop below12.5 V dc at the flowmeter.3. The recommended minimum load is 250 ohms.

    Three-Wire Hook-up

    Scaled Pulse Output

    This wiring is primarily used to retrofit E83SA flowmeters that were wired as pulse onlyflowmeters for totalization. This wiring is typically for retrofitting existing installations.Configure the flowmeter for pulse output. Refer to Changing the Configuration (ConfigurationMenu) on page 22.

    For new installations, a four-wire hook-up is recommended for scaled pulse operation to improvecommunication integrity.

    14501400

    1300

    1200

    1100

    1000 900

    800

    700

    600

    500

    400

    300

    200

    100

    0

    12.520 30 40

    42

    OPERATING AREA

    SEE NOTE BELOW

    RECOMMENDED SUPPLY VOLTAGEAND LOAD LIMITS

    VDC243032

    LOAD (OHMS)250 AND 565250 AND 860250 AND 960

    LOADMIN.

    SUPPLY VOLTAGE, V DC

    OUTPUTLOAD,

    0

    http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/
  • 8/13/2019 Foxboro 83ST

    24/72

    MI 019-174 May 2007 2. Installation

    16

    A dc power supply must be used with each flowmeter and counter wiring loop to supply powerfor the flowmeter and for generation of pulses for the counter.

    The dc power supply can be either a separate signal unit, a multiple unit supplying power toseveral flowmeters, or built into the receiver.

    Connect the supply and counter loop wiring for pulse out (0.50 mm2or 20 AWG typical) to the

    terminals in the field-terminal compartment of the flowmeter, as shown in Figure 15. To use thistype of 3-wire hookup, the blue and green terminals on the back of the module must be shorted.Refer to MI 019-196.

    Figure 15. Installation Wiring - Pulse Output (Three-wire)

    A resistor is required to produce a voltage drop for proper operation of the counter. A 680 , 2 Wresistor is recommended for most counters. This resistor from the counter must be connecteddirectly to the positive terminal of the power supply.

    The pulse signal can cause interference to signals in adjacent signal cables. In some instances,shielded cable may be necessary. Grounding of the shield should be at one point only (at thepower supply). Do notground the shield at the flowmeter. Flowmeter connection polarities areindicated on the terminal block.

    COUNTERPOWERSUPPLY

    +

    +

    A

    TERMINAL BLOCK

    250 OHM MIN. LOADREQUIRED FOR

    HART COMMUNICATOR.CONNECT TO LOOP

    TO CONFIGUREFLOWMETER

    CASEGROUNDTERMINAL

    YELLOW (P)

    SHORTING WIREACROSS B AND G

    OUTPUT SIGNAL WIRESRED (+)

    BLUE (-)

    BACK OF MODULEELECTRONICS SIDE

    B

    680 OHM

    COMMUNICATION

    +_

    SENSOR/PREAMPLIFIER WIRES

  • 8/13/2019 Foxboro 83ST

    25/72

    2. Installation MI 019-174 May 2007

    17

    Power Supply and Load

    The power supply voltage must be between 12.5 and 42 V dc. The pulse OFF state current is amaximum of 0.42 mA at 42 V dc. In the ON state, the pulse output is short circuit protectedfor 250 mA.

    Four-Wire Hook-upTwo separate loops are required when using the scaled pulse output in the four-wire hook-uparrangement. Each loop requires its own power supply. Refer to Figure 16. Select the resistor sothat the current through the contact closure does not exceed 250 mA.

    Figure 16. Installation Wiring (Four-wire)

    Wiring may be run in conduit or in wireways. The wiring must meet all applicable local standardssuch as hazardous location requirements and electrical wiring codes. Signal wires should not berun in the same conduit as power wires. Shielded twisted pair wiring is recommended.

    POWERSUPPLY

    +

    A B

    4 TO 20 MA LOOP

    COUNTER

    SCALED PULSE LOOP

    TERMINAL BLOCK

    + +

    680

    CASEGROUNDTERMINAL

  • 8/13/2019 Foxboro 83ST

    26/72

    MI 019-174 May 2007 2. Installation

    18

  • 8/13/2019 Foxboro 83ST

    27/72

    19

    3. Operating the Flowmeter

    Introduction

    You can communicate with your 83S-T Vortex Flowmeter via the HART Communicator or theoptional local digital display/configurator. General instructions for using the HARTCommunicator can be found in MAN 4250, HART Communicator Product Manual. Vortex-specific instructions for using the HART Communicator are found in HART ConfigurationInstructions on page 35of this document. Complete instructions for using the LocalConfigurator are in Local Configuration Instructions on page 41.

    NOTE

    For proper communication with 83S-T Flowmeters, the HART Communicatormust contain the DD for the 83 Series Invensys Foxboro Flowmeter. This DD isavailable from Invensys Foxboro, or any other authorized HART Foundationsource.

    PasswordsThe flowmeter itself has no password. Rather, security measures, i.e., the ability to accessfunctions such as calibration, configuration, and testing, are associated with the configuratorsused to communicate with the flowmeter. The HART Communicator has no security measureother than access to the device itself. The Local Digital Display/Configurator requires a passwordthat is user definable. See Local Configuration Instructions on page 41.

    Configuration DatabaseIn order to function, the flowmeter requires specific embedded information, termed theconfiguration database. The parameters in this database are listed in Table 5, and defined inConfiguration Database on page 55.

    http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/
  • 8/13/2019 Foxboro 83ST

    28/72

    MI 019-174 May 2007 3. Operating the Flowmeter

    20

    Each flowmeter is shipped from the factory with an operating configuration database; however,the meter will not provide an accurate measurement if the configuration does not fit theapplication. Be sure to check the configuration of each meter prior to start-up!

    In all cases, the factory configuration includes the flowmeter Model Code, Meter Body SerialNumber, and Reference K-Factor. It also includes the User Information in Table 6, if supplied

    with the purchase order. If not supplied with the purchase order, it comes with ReferenceK-Factor only..

    If the User Information in Table 6is not supplied with the purchase order, the flowmeter isshipped with the following default set:

    Table 5. Configuration Database

    Flowtube Parameters

    Model Code

    Meter Body Serial Number

    Reference K-Factor

    Process Fluid Parameters

    Fluid Type

    Process Temperature

    Process Density

    Base Density Process Viscosity

    Identification Parameters

    Tag

    Descriptor

    Date

    Message

    Polling Address

    Application Parameters

    Mating Pipe

    Piping Configuration

    Upstream Distance

    Custom K-factor Bias

    Upper Range Value

    Transmitter Options

    Flow Units

    Total Units Noise Rejection

    Signal Conditioning

    Low Flow Correction

    Low Flow Cut-In

    Output Options

    Damping Value

    Pulse Output AO/PO Alarm Type

    Table 6. User Information

    Tag

    Fluid Type

    Flow Units

    Total Units

    Process Temperature (value and units)

    Process Density (value and units)

    Base Density (if applicable; value) Process Viscosity (if applicable; value and units)

    Upper Range Value

    Item Metric U.S.

    Tag Number blank blank

  • 8/13/2019 Foxboro 83ST

    29/72

    3. Operating the Flowmeter MI 019-174 May 2007

    21

    NOTE

    These defaults are not recommended for general operation. If no other processinformation is available, entering Liquid, Gas, or Steam as fluid type willestablish default data bases as listed in Electronics Options on page 23. Be sure toread the explanation of each parameter in Configuration Database on page 55prior to changing the configuration.

    The remaining items in the database have the following default values:

    NOTE

    These default values should be changed to match the specific application. Beforemaking any changes, be sure to read the explanation of each parameter inConfiguration Database on page 55.

    Flow Units l/min USgpm

    Total Units l USgal

    Fluid Type Liquid (water) Liquid (water)

    Process Temperature 20C 70F

    Process Density 998.2 kg/m3 62.301 lb/ft3

    Flowing Viscosity 1.002 cP 0.9753 cP

    Upper Range Value Upper Range Limit for Meter Size

    The units of this default configuration database, i.e., Metric or U.S., are established by theunits of the Reference K-Factor.

    Descriptor blank

    Date blank

    Message blank

    Polling Address 0

    Noise Rejection On

    Signal Conditioning On

    Low Flow Correction*

    OffLow Flow Cut-In (3rd level above minimum)

    Mating Pipe Schedule 40

    Piping Configuration Straight

    Upstream Distance 30 Pipe Diameters

    Custom K-factor Bias 0.0%

    Damping Value 2.0 sec

    Pulse Output Off

    AO/PO Alarm Type Upscale

    * If the process density and viscosity are provided, the Low Flow Correction is set

    to ON.

    Item Metric U.S.

    http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/
  • 8/13/2019 Foxboro 83ST

    30/72

    MI 019-174 May 2007 3. Operating the Flowmeter

    22

    Changing the Configuration (Configuration Menu)Using the HART Communicator or the Local Digital Display/Configurator, any parameter in theconfiguration database can be changed to fit the application by entering the Device Setup orConfiguration Menu. The specific details for doing this depend on the configurator, and aredescribed in the relevant appendix (B or C). Some general information is presented below.

    Identification Parameters

    NOTE

    The HART protocol allows the connection of up to 15 HART devices on a single

    twisted pair of wires, or over leased telephone lines, a concept known asmultidropping. In a multidrop installation, each flowmeter is identified by aunique address (1-15) referred to as the polling address. In the multidrop mode,that is, if the polling address is non-zero, the analog output is set to a fixed value of4 mA. For a nonmultidrop installation, that is, a single flowmeter loop, the pollingaddress of the flowmeter should be left in its default value (0) if the analog output isintended to indicate flow (4 to 20 mA). In a multidrop installation the pollingaddress of each flowmeter must be set to a unique integral value of 1 through 15.This can be done before or after installation with the local configurator. If using theHART Communicator, the polling address of each flowmeter must be setindividually prior to installing in a multidrop environment.

    Tag Default tag may be changed as desired.

    Descriptor Default descriptor may be changed as desired.

    Date Default date may be changed as desired.

    Message Default message may be changed as desired.

    Polling Address Default address may be changed as desired. (See note below).

  • 8/13/2019 Foxboro 83ST

    31/72

    3. Operating the Flowmeter MI 019-174 May 2007

    23

    Electronics Options

    If the User Information is not supplied with the purchase order, the following default data for aLIQUIDwill reside in the database.

    If the process fluid is not a liquid, changing the fluid type to GASautomatically brings up thedefault set shown below.

    If the process fluid is not a liquid, changing the fluid type to STEAMautomatically brings up thedefault set shown below.

    Flow Units Default units may be changed as desired.

    Total Units Default units may be changed as desired.

    Noise Rejection Keep default value On.

    Signal Conditioning Keep default value On.

    Low Flow Correction Should be changed to On if the low end of the operatingrange is below a Reynolds Number of 20,000.NOTE: If On is selected, actual values of the process densityand process viscosity must be entered into the database!

    Low Flow Cut-In The default value for the Low Flow Cut-In is the third

    level above the minimum. After installing the flowmeter,

    this level can be changed such that under no-flow

    conditions the flow output is zero. (See the following

    section Adjusting the Meter on page 25.

    Parameter Metric U.S.

    Tag blank blank

    Flow Units l/min USgpm

    Total Units l USgal

    Fluid Type Liquid(water) Liquid(water)

    Process Temperature 20C 70F

    Process Density 998.2 kg/m3 62.301 lb/ft3

    Process Viscosity 1.002 cP 0.9753 cP

    Upper Range Value Upper Range Limit for Meter Size

    Parameter Metric U.S.

    Tag blank blank

    Flow Units Nm3/hr SCF/hr

    Total Units Nm3 SCF

    Fluid Type Gas(Air) Gas(Air)

    Process Temperature 20C 70F

    Process Density 9.546 kg/m3 0.5858 lb/ft3

    Base Density 1.293 kg/m3 0.07634 lb/ft3

    Process Viscosity 0.0185 cP 0.0186 cP

    Upper Range Value Upper Range Limit for Meter Size

  • 8/13/2019 Foxboro 83ST

    32/72

    MI 019-174 May 2007 3. Operating the Flowmeter

    24

    As mentioned previously, the units of the default configuration database, i.e., US or Metric, areestablished by the units of the Reference K-Factor.These defaults are not recommended for general operation and should be used only when noother information is known about the process other than the fluid type. Be sure to read theexplanation of each parameter in Configuration Database on page 55prior to changing the

    configuration.

    Process Fluid Parameters

    Application Parameters

    NOTE

    The meter uses the above three parameters to correct internally for the effects ofupstream piping and disturbances on the Flowing K-Factor. Other known biascorrections can be entered under Custom K-Factor Bias.

    Parameter Metric U.S.

    Tag blank blank

    Flow Units kg/hr lb/hr

    Total Units kg/hr lb/hr

    Fluid Type Steam(saturated) Steam(saturated)Process Temperature: 175C 350F

    Process Density 4.618 kg/m3 0.2992 lb/ft3

    Process Viscosity 0.0149cP 0.0150 cP

    Upper Range Value Upper Range Limit for Meter Size

    Fluid Type Selecting the fluid type establishes an appropriate default database

    which can be modified to fit the application.

    Process Temperature For accurate flow measurement, the actual value in the selected

    units must be entered.

    Process Density For optimal performance and accurate mass flow measurement, the

    actual value in the selected units must be entered.

    Base Density For accurate standard volume flow measurement, the proper valuemust be entered in the same units as Process Density.

    Process Viscosity For accurate flow measurement at low flow, the actual value in the

    selected units must be entered. It is essential that the process

    viscosity be entered if the Low Flow Correction option is On.

    Mating Pipe Select upstream mating pipe schedule.

    Piping Configuration Select upstream piping configuration.

    Upstream Distance Enter distance to first upstream flow disturbance in pipe diameters.

    http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/
  • 8/13/2019 Foxboro 83ST

    33/72

    3. Operating the Flowmeter MI 019-174 May 2007

    25

    Output Options

    Preconfiguring the MeterWith the HART Communicator, the database can be generated offline and then downloaded tothe flowmeter. The procedure for building the database consists of entering the appropriate

    information as it is requested.

    NOTE

    The password for the local display configurator cannot be configured from theHART Communicator.

    Displaying the Configuration DatabaseHART Communicator (Review Menu)

    The parameters in the configuration database can be viewed without entering the Setup Menu.

    This is done via the Review Menu.Local Configurator (Display Menu)

    The parameters in the configuration database can be viewed without entering the ConfigurationMenu. This is done via the Display Menu.

    Adjusting the MeterThe following four adjustments can be made to the meter:

    These appear in various places in the structures (refer to Appendixes Band C).

    mA Calibration (D/A Trim)This function allows the 4 to 20 mA output of the flowmeter to be calibrated or matched to thecalibration of the receiving device.

    Custom K-factor Bias To compensate for additional known biases in the flow

    measurement system, enter the value, with sign, in percent.

    Upper Range Value Enter desired maximum flowrate.

    Damping Value Enter desired time in seconds.

    Pulse Output Select desired output.

    AO/PO Alarm Type Select desired fail condition. Applies only to 4 to 20 mA and Pulseoutputs.

    mA Calibration (D/A Trim)

    Total Reset Low Flow Cut-In

    Upper Range Value

  • 8/13/2019 Foxboro 83ST

    34/72

    MI 019-174 May 2007 3. Operating the Flowmeter

    26

    NOTE

    The flowmeter has been accurately calibrated at the factory. Recalibration of theoutput is normally notrequired unless it is being adjusted to match the calibrationof the receiving device.

    Total ResetThis function allows the flow total to be reset to zero.

    Low Flow Cut-InThe low flow cut-in parameter allows you to set the level above which the flowmeter begins tomeasure flow, that is, the lower range limit of the meter. This process can be carried outautomatically if the flow is turned off. Otherwise, manual selection from the following pick-list ofeight levels can be made:

    For convenience, these levels are displayed as estimated flow rates in the selected flow units. Thevalue of these flow rates depend on the specific application parameters.

    With the HART Comunicator, the current value is displayed and you can elect to decrease orincrease the level by one. If the level does not change when this is done, the minimum ormaximum level has been reached. In the case of the local configurator, you can select the desiredlevel from the displayed pick-list.

    If Automatic mode is selected, the meter chooses the lowest level at which no signal is detectedover a 20 second time interval. You may wish to increase or decrease this setting. For instance,noise signals could be occurring at an interval greater than 20 seconds and possibly not be

    detected during the automatic selection process. Repeating the auto-selection process helps toavoid this possibility.

    Upper Range ValueThis parameter sets the desired maximum flowrate of the flowmeter.

    Reading the MeasurementsThe Process Variables Menu (HART) or the Measurement Menu (Local) provides periodicallyupdated values of the flow rate, vortex frequency (frequency in), scaled pulse frequency (frequency

    out), and flow total. The flow rate and total are presented in units of volume or mass asconfigured, the frequencies in Hz. Due to the limited size of the local display only one parameteris displayed at a time. It is possible to configure the device to display in succession two, three, orfour of the variables, as selected from a pick-list.

    AUTO, (L0), (L1), (L2), (L3), (L4), (L5), (L6), (L7)

  • 8/13/2019 Foxboro 83ST

    35/72

    3. Operating the Flowmeter MI 019-174 May 2007

    27

    Testing the Meter and Loop (Test Menu)Entering the Diag/Service Menu for the HART Communicator or Test Menu for the LocalConfigurator allows the following two test procedures to be activated:

    Self-Test

    Loop Test or Loop Calibration

    Self-TestThis selection checks flowmeter operation by injecting, near the front end of the electronics, aninternally generated periodic signal of known frequency. The frequency of this signal is in turnmeasured and checked against the injected signal.

    Loop Test or Loop CalibrationThis selection allows the flowmeter to be used as a signal source to check and/or calibrate otherinstruments in the control loop, such as indicators, controllers, and recorders. The mA, scaled

    pulse, and digital output signals can be adjusted to any value within the range limits of the meter.

    Electronic Module ReplacementIf an Electronic Module is shipped as a replacement, the correct flowtube parameters will notreside in its configuration database. For proper operation of the flowmeter, the correct values mustbe entered. If the configuration database from the original meter was saved to a file, this file,containing the correct flowtube parameters, can be downloaded to the new flowmeter. If this isnot the case, they must be entered manually from the flowmeter tag.

    In the latter case, enter the following data first when configuring the meter!

    Model Code: Enter alphanumeric Model Code from flowmeter body tag (first 14characters).

    Meter Body Serial Number: Enter alphanumeric Serial Number from flowmeter tag.

    NOTE

    Although the meter will operate properly without this information, it is convenientto enter it at this point.

    Reference K-Factor: Enter numeric value from flowmeter body tag.

    NOTE

    It is not necessary to enter the units of the Reference K-Factor. The units, that is,

    US (pulses/ft3) or Metric (pulses/liter), are determined internally by the meter,based on the nominal size of the meter (contained in the Model Code) and theentered numeric value of the Reference K-Factor.

  • 8/13/2019 Foxboro 83ST

    36/72

    MI 019-174 May 2007 3. Operating the Flowmeter

    28

  • 8/13/2019 Foxboro 83ST

    37/72

    29

    4. Troubleshooting

    General Troubleshooting

    To maximize the usefulness of this chapter, read this General Troubleshooting section first. Then,follow the applicable procedural steps in the order presented. Persons performing troubleshootingprocedures should be suitably trained and qualified for those procedures.

    NOTE

    If applicable, remove flowmeter under test from multidrop environment.

    Flowmeter Has Incorrect OutputCheck the configuration. Be sure the meter has been configured correctly.

    Incorrect 4 to 20 mA Output

    1. Be sure the upper range value is correct.

    2. Check that the correct flow units are specified.

    3. Check that the meter is not in the multidrop mode by verifying that the pollingaddress is zero. In the multidrop mode the mA output is fixed at a constant 4 mA.

    4. Check that the meter is not in one of the application default modes.

    a. For liquid the default mode is water. For many situations this may be adequate.

    b. For steam the default is 125 psig saturated steam. There may be significant errorat other pressures.

    c. For gas the default mode is 100 psig air. Other gases and other conditions requirethe correct configuration for density and base density.

    Incorrect Digital Output

    1. Check that the correct flow units are specified.

    2. For custom flow units check that the conversion factor is correct. Refer toDetermining Special Measuring Units on page 33to calculate the conversion factor.

    3. Check to be sure that the meter is not in one of the application default modes. Referto Item 4 above.

    Incorrect Pulse Output

    1. Verify that correct flow units are used. Check the pulse resolution factor.2. The scaled pulse output can only be used with a receiver that does not calculate

    period, such as a counter.

    Flowmeter Output Indicates Flow When There Is No FlowIn some installations, the flowmeter can indicate flow when the line is shut down. This could bethe effect of a leaking valve, sloshing fluid, or noise sources such as pump-induced pipe vibration.To eliminate these false signals, try the following:

    http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/
  • 8/13/2019 Foxboro 83ST

    38/72

    MI 019-174 May 2007 4. Troubleshooting

    30

    1. Be sure there is no flow.

    2. Be sure the noise rejection feature is set to ON.

    3. If damping is ONand set to greater than zero, the noise spikes that exceed the lowflow cut-in appear as decaying signals less than the low flow cut-in.

    4. Adjust the low flow cut-in level to produce zero output. This level can be

    automatically set or manually adjusted via the configurator.5. Check that flowmeter and power supply are properly grounded. This is particularly

    important for remote installations. Refer to Field Termination Wiring on page 12.

    6. For remote meters, verify that signal cable has been properly terminated.

    Flowmeter Output Indicates Higher Flow Rate withDecreasing Flow

    1. Be sure the noise rejection feature is set to ON.

    2. Adjust the low flow cut-in level to produce zero output. This can be done with

    automatic or manual adjustment.

    Fluctuating Output1. Verify that the signal conditioning feature is ON.

    2. Fluctuations may be a true picture of the actual flow.

    3. A small offset of 1 to 2% with rapid fluctuations may be caused by gaskets protrudinginto the flow stream.

    No Output Troubleshooting1. Be sure there is flow.2. Check the power supply. The voltage across the + and - terminals must be between

    12.5 and 42 V dc.

    a. If voltage is zero, check for blown fuse in power supply.

    b. If voltage is low, but not zero, the flowmeter may be loading the power supply.Remove the field terminal cover. Disconnect the + and - leads and measure thevoltage from the power supply. If the voltage returns to normal, the circuit is goodto this point. Reconnect power to the + and - terminals.

    c. Remove the electronic module compartment cover. Loosen the mounting screwsand remove the electronic module from the housing. Disconnect the blue-red-yellow-green ribbon cable from the terminal blocks on the electronic module.Measure the voltage across the red and blue wires. If the voltage is normal, theelectronic module is bad. Replace the electronic module.

    d. If the voltage remains low, the housing/field terminal wiring is bad. Replace thehousing or return the meter to Invensys Foxboro for repair.

    http://mi_019-174_b.pdf/http://mi_019-174_b.pdf/
  • 8/13/2019 Foxboro 83ST

    39/72

    4. Troubleshooting MI 019-174 May 2007

    31

    3. Checking the 4 to 20 mA output loop.

    a. The 4 to 20 mA loop may be monitored via the test jacks in the field outputterminal board. The signal produced will be 0.1 to 0.5 volts, corresponding to4 to 20 mA. Be sure the meter is not configured for the multidrop mode byverifying that the polling address is zero. The output is fixed at a constant 4 mA inthe multidrop mode.

    b. Increase the flow to be sure that the lack of response is not caused by operationbelow the Low Flow Cut-in.

    c. If there is no response to increasing flow, perform one of the following tests:

    Module Test Procedure on page 31.

    Sensor Test Procedure on page 31.

    Module Test ProcedureThe module may be tested for input frequency with a frequency generator. Connect the

    frequency generator to the outside terminals of the four-position terminal block. Connectthe positive to the brown terminal and the negative to the yellow terminal. Be sure thatloop power is connected. Increase the frequency until a flow rate is read. Do not exceed3000 Hz. If no flow measurement is indicated, check that the module is configuredcorrectly.

    Sensor Test Procedure1. Remove electronic module from housing.

    2. Disconnect the yellow and brown sensor leads from back of electronic module.

    3. Connect sensor lead to an oscilloscope.

    4. With fluid flow in the pipe, observe signal waveform on oscilloscope. Waveformshould be similar to that shown in Figure 17.

    a. If waveform is similar to Figure 17, the sensor is good. If there is no output fromthe electronic module, the electronic module input stage has failed. The entireelectronic module should be replaced.

    b. If there is no sensor output signal, the sensor has failed and the meter should bereplaced.

    NOTE

    For the sensor, be sure the signal being read is not the local power line frequency,that is, 50 or 60 Hz.

  • 8/13/2019 Foxboro 83ST

    40/72

    MI 019-174 May 2007 4. Troubleshooting

    32

    Figure 17. Normal Vortex Frequency Waveform

  • 8/13/2019 Foxboro 83ST

    41/72

    33

    Appendix A. Determining SpecialMeasuring Units

    There may be a need to use flow units that are not listed in the units menu. To enter customunits, select special from the flow and/or total units menu.

    The following four entries are required to configure the flowmeter for special flow and total units.

    1. Total name, maximum six characters, is required for displaying total.

    2. Flow name, maximum six characters, is required for displaying the flow rate.

    3. Total conversion factor for computing total.

    4. Flow conversion factor for computing flow.

    The conversion factors must be related to the internal software and the manner in which the

    meter computes flow. The conversion factor for total is a direct conversion from ft3

    to the desiredunits. The conversion factor for flow is a direct conversion from ft3/s to the desired flow units.Any table of conversion factors may be used.

    Example: Barrels per hour

    To measure total in barrels and flow in barrels per hour.

    Total Name: bbl

    Flow Name: bbl/h

    Total Conversion Factor: 0.1781 bbl/ft3

    Flow Conversion Factor: 0.1781 x 3600 = 641.2 bbl/h

    where: 3600 = seconds/hour

    Example: BTU per minute

    The conversion factor for total must be in BTU/ft3. If the BTU factor is known in mass units,then it must be converted to volume units by multiplying by density. The flow factor is a directconversion from ft3/s to the desired units.

    Total Name: BTU

    Flow Name: BTU/m

    Total Conversion Factor: (BTU/lb) x density

    Flow Conversion Factor: (BTU/lb) x density x 60where: 60 = seconds/minute

    Example: Calories per hour

    The conversion factor for total must be in calories/ft3. If the calories factor is known in cal/kg, itmust be converted to cal/ft3 by multiplying by the density and volume conversion factors (m3to ft3). The flow factor must be related to ft3/s.

    Total Name: cal

  • 8/13/2019 Foxboro 83ST

    42/72

    MI 019-174 May 2007

    34

    Flow Name: cal/h

    Total Conversion Factor: (cal/kg) x density x 0.028317

    where: 0.028317 = m3/ft3

    Flow Conversion Factor: (cal/kg) x density x 0.028317 x 3600

  • 8/13/2019 Foxboro 83ST

    43/72

    35

    Appendix B. HART ConfigurationInstructions

    IntroductionGeneric instructions regarding the installation and operation of the HART Communicator can befound in MAN 4250, HART Communicator Product Manual.

    Specific 83 Series Vortex Flowmeter instructions are described in this appendix.

    HART Menu StructureThe on-line menu structure for the HART Communicator is shown in Figure 18. Key sequencesfor rapidly accessing given functions or parameters are shown in Table 20.

  • 8/13/2019 Foxboro 83ST

    44/72

    MI 019-174 May 2007

    36

    .

    1 DEVICE SETUP

    2 FLOW RATE

    3 ANALOG OUT

    4 URV

    5 LOW FLOW CUT IN

    1 PROCESS VARIABLES

    2 DIAG/SERVICE

    3 BASIC SETUP

    4. DETAILED SETUP

    5. REVIEW

    1 PROCESSVARIABLES

    2 METER CONFIG

    3 FLOW UNITS CONFIG

    4 PROCESS PARAM.

    5 PIPING

    6. CALIBRATION

    7 TEST DEVICE

    UPPER RANGE VALUE (URV)UPPER SENSOR LIMIT (USL)

    PROCESS DENSITYBASE DENSITY

    PROCESS VISCOSITYMATING PIPEPIPING CONFIGURATIONUPSTREAM DISTANCECUSTOM K BIASAO/PO ALARM TYPEMANUFACTURER

    DEVICE IDTAGDESCRIPTORMESSAGEDATEFLUID TYPEUNIVERSAL REVISIONFIELD DEVICE REVISIONSOFTWARE REVISIONSOFTWARE RELEASEHARDWARE REVISIONPOLL ADDRESSNO. OF REQUEST

    PREAMBLES

    1 FLOW RATE

    2 % RANGE

    3 ANALOG OUT

    4 VORTEX FREQ

    5 PULSE OUT

    FREQ6 TOTAL

    1 TEST DEVICE

    2 LOOP TEST

    3 CALIBRATION

    1 MEASURINGELEMENTS

    2 SIGNALCONDITIONING

    3 OUTPUTCONDITIONING

    4 DEVICE INFO

    1 PROCESS VARIABLES

    2 RANGE VALUES

    3 FLOW UNITS CONFIG

    4 CALIBRATION

    5 SIGNAL PROCESSING

    1 FLOW UNITS

    2 TAG

    3 RANGE VALUES

    4 DEVICE INFO

    1 URV

    2 USL

    3 MIN SPAN

    4 LOW FLOW

    CUT IN

    1 MFR.

    2 TAG

    3 DESCRIPTOR

    4 MESSAGE

    5 DATE

    6 DEVICEDESCRIPTION

    7 REVISIONS

    1 D/A TRIM2 SCALED

    D/A TRIM

    1 SET DIGITAL OUT2 SET ANALOG OUT

    3 SET PULSE OUT

    1 SELF TEST

    2 STATUS

    1 MFR.2 TAG3 DESCRIPTOR

    4 MESSAGE5 DATE6 DEVICE DESCRIPTION7 REVISIONS

    1

    2

    3

    4

    5

    6

    7

    8

    9

    A

    B

    C

    D

    E

    F

    G

    H

    3 DATE

    MINIMUM SPANDAMPING VALUELOW FLOW CUT INMODEL CODEMETER BODY SERIAL NO.REFERENCE K FACTORPULSE OUTPUT MODEFLOW UNITSSPECIAL FLOW UNITS

    CONVERSION FACTORSPECIAL FLOW UNITSTOTAL UNITSSPECIAL TOTAL UNITS

    CONVERSION FACTORSPECIAL TOTAL UNITSNOISE REJECTIONSIGNAL CONDITIONINGLOW FLOW CORRECTIONPROCESS TEMPERATURE

  • 8/13/2019 Foxboro 83ST

    45/72

    MI 019-174 May 2007

    37

    Figure 18. HART On-Line Menu Structure Part 1 of 2

  • 8/13/2019 Foxboro 83ST

    46/72

    MI 019-174 May 2007

    38

    .

    1 MODEL CODE2 METER BODY SERIAL NO.3 REFERENCE K FACTOR

    1 UNIVERSAL REVISION2 FIELD DEVICE REV.3 SOFTWARE REVISION4 SOFTWARE RELEASE5 HARDWARE REVISION

    1 MODEL CODE2 METER BODY SERIAL NO.3 REFERENCE K FACTOR

    1 UNIVERSAL REVISION

    2 FIELD DEVICE REVISION3 SOFTWARE REVISION4 SOFTWARE RELEASE5 HARDWARE REVISION

    1 FLOW RATE

    2 % RANGE

    3 ANALOG OUT

    4 VORTEX FREQ

    5 PULSE OUT FREQ

    6 TOTAL

    2 SPECIAL FLOWFACTOR1 SPECIAL FLOW UNITS

    1 D/A TRIM2 SCALED D/A TRIM

    1 MODEL CODE2 K-FACTOR

    3 METER BODY S/N

    1 REFERENCE K FACTOR2 FLOWING K FACTOR

    1 FLUID TYPE2 PROCESS TEMP3 PROCESS TEMP UNITS4 PROCESS DENSITY5 PROCESS DENSITY UNITS6 BASE DENSITY7 PROCESS VISCOSITY8 PROCESS VISCOSITY UNITS

    1 FLOW RATE

    2 % RANGE

    3 ANALOG OUT

    4 VORTEX FREQ

    5 PULSE OUTFREQ

    6 TOTAL

    1 FLOW RATE2 TOTAL3 TOTAL RESET4 SET DIGITAL OUT

    1 D/A TRIM2 SCALED D/A TRIM

    1 ANALOG OUTPUT2 AO/PO ALARM TYPE3 SET ANALOG OUT4 CALIBRATION

    1 PULSE OUTPUT FREQ2 PULSE OUTPUT MODE3 AO/PO ALARM TYPE4 SET PULSE OUTPUT

    1 POLL ADDRESS2 NO. OF REQUEST

    1 TOTAL UNITS2 SPECIAL TOTAL UNITS

    1 SPECIAL TOTAL UNITS2 SPECIAL TOTAL FACTOR

    1 SET DIGITAL OUTPUT2 SET ANALOG OUTPUT3 SET PULSE OUTPUT

    1 PROCESS VARIABLES

    2 DAMPING VALUE

    3 DIGITAL OUTPUT

    4 ANALOG OUTPUT

    5 PULSE OUTPUT

    6 TOTALIZER

    7 HART OUTPUT

    8 LOCAL DISPLAY

    9 LOOP TEST

    1 NOISE REJECTION2 SIGNAL CONDITIONING3 LOW FLOW CORRECTION4 LOW FLOW CUT IN

    1 TOTAL2 TOTAL RESET3 TOTAL UNITS

    CONFIG.

    1 FLOW UNITS2 SPECIAL UNITS

    1 MATING PIPE2 PIPING CONFIG.3 UPSTREAM DISTANCE4CUSTOM K BIAS

    1 SELF TEST2 STATUS

    1 FLOW RATE

    2 % RANGE

    3 ANALOG OUT

    4 VORTEX FREQ

    5 PULSE OUTFREQ

    6 TOTAL

    1 FLOW UNITS2 SPEC. UNITS

    2 SPEC. FLOW FACTOR1 SPEC. FLOW UNITS

    1 URV2 USL3 MIN SPAN

    4 LFCI

    1 D/A TRIM2 SCALED D/A TRIM

    PREAMBLES

    1

    2

    3

    4

    5

    6

    8

    9

    A

    B

    C

    D

    E

    F

    G

    H

    7

    3 DATE

    3 DATE

    3 DATE

  • 8/13/2019 Foxboro 83ST

    47/72

    MI 019-174 May 2007

    39

    Figure 19. HART On-Line Menu Structure Part 2 of 2

  • 8/13/2019 Foxboro 83ST

    48/72

    MI 019-174 May 2007

    40

    Figure 20. Fast-Key Function/Variable Chart

    Function/Variable Key Sequence

    Analog OutputAO/PO Alarm TypeAuto Low Flow Cut-InD/A TrimDamping ValueDateDensity, BaseDensity, ProcessDescriptorFluid TypeFlow RateFlow Rate (% of range)K-Factor, ReferenceK-Factor, FlowingK-Factor Bias, CustomLocal DisplayLoop Test

    Low Flow CorrectionLow Flow Cut-InManufacturerMessageMeter Body Serial NumberMinimum SpanModel CodeNoise RejectionNumber of Req. PreamblesPipingPoll AddressProcess ParametersProcess Variables

    Pulse Output FrequencyPulse Output ModeRanges ValuesReviewRevisionsScaled D/A TrimSelf TestSignal ConditioningSpecial Units, FlowSpecial Units, TotalStatusTagTemperature, Process

    TotalTotal ResetUnits, FlowUnits, TotalUpper Range Value (URV)Upper Sensor Limit (USL)Viscosity, ProcessVortex Frequency

    31, 4, 3, 4, 21,3,3,41,2,3,11,4,3,21,2, 3, 31,4,1,4,61,4,1,4,41,3,4,31,4,1,4,121,1,21,3,4,6,31,4,1,2,2,21,4,1,5,41,4,3,81,2,2

    1,4,2,5,31, 3, 3, 41,3,4,11,3,4,41,3,4,6,21,3,3,31,3,4,6,11,4,2,5,11,4,3,7,21,4,1,51,4,3,7,11,4,1,41,1

    1,1,51,4,3,5,21,3,31,51,3,4,71,2,3,21,2,1,11,4,2,5,21,4,1,3,21,4,3,6,3, 21,2,1,21,3,21,4,1,4,2

    1,1,61,4,3,6,21,3,11,4,3,6,3,11, 3, 3, 11,3,3,21,4,1,4,71,1,4

  • 8/13/2019 Foxboro 83ST

    49/72

    41

    Appendix C. Local ConfigurationInstructions

    IntroductionLocal configuration of your flowmeter is accomplished via four multi-function pushbuttons onthe local keypad/display shown below. A functional overview of the Menu Tree is presented inTable 7.

    Table 7. Menu Tree Functional Overview

    Level 1 Level 2 Function

    MEASURE Display Flowrate and TotalDISPLAY OPTIONSPARAMSTAGS

    Display Transmitter and Output OptionsDisplay Fluid and Application ParametersDisplay Flowtube and ID Parameters

    CALIB SHOW LFCIRESET TOTALCAL 4 mACAL 20 mA

    Set Measurement Display ModeSet Low Flow Cut-InSet Total to ZeromA Calibration @ 4 mAmA calibration @ 20 mA

    TEST DIAGSET DIG

    SET MASET HZSELFTSTXMTTEMP

    Display StatusSet Digital Output for Loop Calibration

    Set 4-20 mA Output for Loop CalibrationSet Scaled Pulse Output for Loop CalibrationActivate Transmitter Self-TestDisplay Transmitter Temperature

    ESC ENTER

    BACKNEXT

  • 8/13/2019 Foxboro 83ST

    50/72

    MI 019-174 May 2007

    42

    Using the Local Configurator

    Measurements (MEASURE)

    The system starts up displaying the measured Flowrate (FLOW

    ), the Total (TOTAL

    ), or the Flowand Total (BOTH), in an alternating fashion, depending on the selection made in theCalibrate/Show menu.

    Display Bar IndicatorThe analog bar indicator at the top of the display indicates the flow measurement, as a percentageof the upper range value.

    NOTE

    If the flow measurement is out-of-range, the bar indicator blinks.If the flowmeter is off-line, the middle four bars of the bar indicator blink.

    In TEST/SET DIG, the bar indicator continues to display the flow measurement. However, inTEST/SET MA, it displays the percentage of span set.

    Moving inside the Menu SystemPressing ESCstops displaying measurements, and shows the first menu item, DISPLAY. Fromhere, the four buttons allow the user to move around the menu tree, as indicated by the arrows.Press the down arrow repeatedly; the menu display cycles through each of the top level (Level 1)menu items. Refer to the menu structure diagram on the following pages as you move around.

    NOTE

    Each menu item has its level (1 - 4) displayed at the beginning of the top line.

    The four buttons also allow the user to move up and down the picklists, as indicated by thearrows. Also, pressing ESCmoves one from the current level to the next higher level. PressingESCwithin the top level menu returns the user to the MEASUREblock.

    CONFIG OPTIONSOUTPUTFLUID

    UNITSBIASTAGSNEWTUBEPASSWD

    Select Transmitter OptionsSelect Output OptionsEnter Fluid Parameters

    Enter Units, URV, and DampingEnter Application ParametersEnter Identification ParametersEnter Flowtube ParametersChange Passwords

    Table 7. Menu Tree Functional Overview (Continued)

    Level 1 Level 2 Function

  • 8/13/2019 Foxboro 83ST

    51/72

    MI 019-174 May 2007

    43

    Viewing Data (DISPLAY)The OPTIONS, PARAMS, and TAGSsub menus are all read only. You may move around inthem, but not alter any data.

    In the PARAMSmenu, the display alternates for all menu items between the parameter name andvalue/units (This is also the case when viewing the Transmitter Temperature in

    TEST/XMTTEMP). Go to PARAMS/URV; note that the URV and value/units alternate.In the TAGSmenu, the alphanumeric strings may be longer than the number of displayedcharacters. To shift the hidden characters into view, press the right or left arrow buttons. Go toTAGS/MODEL, and press the right arrow key several times. The MODELstring scrolls to the left,allowing you to view the hidden characters. To exit this menu item, either press the up or downarrows, or press ESCrepeatedly until the string scrolls back to its original position.

    Answering a QuestionThere are several places in the menu tree where a question is displayed, such as LOOP INMANUAL?, mentioned below in Entering the Password. To answer Yes, press Enter, if No,

    press ESC.

    Entering the PasswordThe CALIB, TESTand CONFIGsub menus require a password (a 4-character alphanumericstring). Changing the password is addressed later. Select the CALIB, TESTor CONFIGmenufrom the top level, and press Enter at the PASSWDprompt. Two brackets surrounding 4 spaces([____]) appears on the second line of the display. The cursor, a flashing icon, appears at the firstcharacter.

    To enter the password, use the up and down arrows to scroll through the list of acceptablecharacters. After selecting the desired character, press the right arrow to move to the next

    character. Continue this process until the password is complete. Pressing the right arrow oncemore moves the flashing cursor to the right bracket. Pressing Enternow completes the process.Prior to pressing Enter, the left and right arrows can be used to move back and forth to modify anincorrect selection.

    If you enter an incorrect password, the display indicates SORRY for 1 second, then return tothe PASSWDprompt.

    After entering the correct password, the following message appears, LOOP IN MANUAL?.Press Enterif Yes, ESCif No. Yes moves the user into the calibration, test, or configurationsub-menus. No returns you to CALIBor CONFIGin the main menu.

    The default password from the factory for TEST, CALIB, and CONFIGis [____], (four spaces).To enter it quickly, press the right arrow 5 times.

    Activating an Edit, Pick-List or User Function Menu BlockTo open a menu block that allows the user to edit or select data or to perform a function, such asRESET TOTAL, move to the menu block and press the Right arrow.

  • 8/13/2019 Foxboro 83ST

    52/72

    MI 019-174 May 2007

    44

    Editing Numbers and StringsEditing any number or string in the menu system is done in the same way as entering thepassword above. The up and down arrows scroll through a list of acceptable characters for thecurrent position. The right arrow moves the cursor to the right; Enteraccepts the change at theend. The left arrow moves the cursor to the left; ESCcancels the change at the beginning.

    There are three kinds of edit items: signed numbers, unsigned numbers, and strings.Unsigned numbers cycle through the digits 0-9, and the decimal point, with the up and downarrows. For example, try changing the CONFIG/FLUID/DENSITYitem to 8.200.

    When you enter a decimal point in any position, and there is already a decimal point to the left ofthe cursor, the new decimal point overrides the old one. Change the DENSITYfrom 8.200 to82.00 by first selecting the decimal point to the right of the 2. Notice what happens when youenter the second decimal point (that is, press the Right arrow).

    Signed numbers always have a + or - sign at the beginning. The + can only be changed to , andvice versa.

    Finally, characters in strings may be changed to any valid character. The sequence of charactersyou can get for strings by pressing the up and down arrows is: space, A-Z, a-z, 0-9, period, dash,slash. Go to CONFIG/TAGS/MESSAGEand change it. Note that the entire data field is notvisible at once. To enter the change you must still press Enterfrom the right side of the data field,after scrolling to the right side with the right arrow.

    Picking from a ListPick-List items allow the user to choose a value from a flowmeter supplied list of alternatives. Goto CONFIG/FLOW/UNITS, and press Enter. The entire bottom line of the display flashes. If youpress the up or down arrows, the display shows the next or previous choice from its list. PressingEnteraccepts the change; pressing ESCreturns the previous value.

    mA Calibration (TEST/CAL 4 mA or CAL 20 mA)When opening the CAL 4 mAor CAL 20 mAmenu block, 0.5+/is displayed. To enter thisvalue, that is, to change the mA output of the flowmeter, press the up arrow to add 0.5 mA, ordown arrow to subtract 0.5 mA. By pressing the right arrow values of 0.05 and 0.005 can beselected, and entered by the up and down arrows. The display does not change when entering theselected value. To have the new calibration accepted by the flowmeter, move with the right arrowto the end of the data field. To restore the original calibration, move with the left arrow to thebeginning.

    Transmitter StatusIf there is a flowmeter failure, an error message appears when entering the TESTmenu.

    Changing the PasswordChanging the password is done in CONFIG/PASSWD. Before changing the password, a promptappears requesting the old password to be entered. CALIBand TESTshare the same password. Adifferent password can be used for CALIB.

  • 8/13/2019 Foxboro 83ST

    53/72

    MI 019-174 May 2007

    45

    Local Configurator Menu Tree

    The menu tree used to carry out local configuration is shown on the following pages. Each blockon the menu diagram signifies a menu item. The text in the block indicates the title of the item,and any data displayed. The text under each block indicates the type of menu item. There are fiveitem types: Branch, Edit----, PickList, Group, and UserFunc.

    Branch items do not display or edit data, but simply move you to another menu itemdepending on which key is pressed.

    Edit ---- items* display a numeric (real or integer) or string value, which may beedited.

    PickList items* display one of several alternatives, which may be selected. PickListitems have the choices to pick from enclosed in a dashed box to the right of the item.

    Group items display, alternately, a parameter name and its value/units. You are notallowed to change them at this point in the menu tree.

    UserFunc items do not display or edit data, rather they allow a built-in function to be

    activated.

    * Edit---- and PickList items marked R/O (read only) displays the associated data, butyou will be unable to change them at this point in the menu tree.

  • 8/13/2019 Foxboro 83ST

    54/72

    MI 019-174 May 2007

    46

    Local Configurator Menu (1 through 8)

    MEASURE

    DISPLAY OPTIONSPULSE

    OUT OFF

    NOISEFILT OFF

    SIGNAL

    COND OFF

    LF CORR

    OFF

    RATEOFF

    OFFON

    OFFON

    OFFON

    1 of 8

    BRANCH BRANCHPICK LISTR/O

    PICK LISTR/O

    PICK LISTR/O

    PICK LISTR/O

  • 8/13/2019 Foxboro 83ST

    55/72

    MI 019-174 May 2007

    47

    PARAMS URV

    LFCI

    K REF

    K FLOW

    DAMPING

    0 SEC

    FLTEMP

    FLDENS

    FLVISC

    XXX.X

    USGPM

    X.XXX

    USGPM

    XXX.X

    PUL/FT3

    XX.XX

    P/USGAL

    XXX.

    F

    XX.XX

    LB/FT3

    X.XXX

    CPOISE

    BRANCH GROUP

    GROUP

    GROUP

    GROUP

    EDIT REALR/O

    GROUP

    GROUP

    GROUP

    2 of 8

  • 8/13/2019 Foxboro 83ST

    56/72

  • 8/13/2019 Foxboro 83ST

    57/72

    MI 019-174 May 2007

    49

    ONLINE LOCAL

    TEST

    BRANCH

    PASSWD

    XXXX

    BRANCH, STRINGCHK

    LOOP IN

    MANUAL?

    BRANCH

    SET DIG

    XX.X

    EDITREAL

    SET MA

    XX.X

    EDITREAL

    SELFTST

    BRANCH

    XMTTEMP

    GROUP

    SET DIG

    XX.X

    EDITREALR/O

    SET MA

    XX.X

    EDITREALR/O

    TEST

    PASSED

    USERFUNC

    XXX.

    C

    ONLINE CONFIGCNFPWD

    CONFIG

    BRANCH

    PASSWD

    XXXX

    BRANCH, STRINGCHK

    LOOP IN

    MANUAL?