50
Figure 1. Kyle ® Type ME electronic recloser control These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide direction for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user’s purpose, please contact your Cooper Power Systems sales engineer. April 2002 Supersedes 12/88 Reclosers Type ME Electronic Recloser Control, Form 3 and 3A Maintenance Instructions - Basic 1 CONTENTS Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Periodic Field Inspection and Maintenance . . . . . . . 6 Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Circuit Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Plug-In Circuit Boards Function . . . . . . . . . . . . . . . .10 Battery Charging Board . . . . . . . . . . . . . . . . . . . .10 Phase Trip No. 1 Board . . . . . . . . . . . . . . . . . . . .11 Phase Trip No. 2 Board . . . . . . . . . . . . . . . . . . . .11 Ground Trip No. 1 and No. 2 Boards . . . . . . . . . .11 Output Board . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Diode Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Recloser-Reset Board . . . . . . . . . . . . . . . . . . . . .12 Closing Coil Control Fuse . . . . . . . . . . . . . . . . . . . . .12 Interchangeability of Boards Between Form 2, Form 3 and Form 3A Electronic Controls . . . . . . . . .12 Troubleshooting and Testing . . . . . . . . . . . . . . . . . . .13 Detailed Circuit Checks . . . . . . . . . . . . . . . . . . . . . . .14 Input Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 Internal dc Load Current Signal . . . . . . . . . . . . . .18 Internal Minimum Trip Signal .....................................19 Time-Current Characteristic Curves (TCC) ................20 Control-Recloser operation ........................................22 Major Control Damage ...............................................29 Battery Charging ........................................................31 Mechanical and Electrical Hardware ..........................35 Battery Maintenance ...........................................................35 Battery Specifications ......................................................35 Maintaining Battery Charge .............................................35 Field Testing a Battery .....................................................35 Shop Testing a Battery .....................................................36 Appendix I ...........................................................................37 Test Sheet ........................................................................37 Appendix II ..........................................................................38 List of Electronic Recloser Maintenance Manuals ...........38 Appendix III .........................................................................38 List of Electronic Control Accessory Manuals ..................38 Appendix IV .........................................................................38 Service Parts List .............................................................38 Appendix V ..........................................................................41 Form 2 Connection Diagram ............................................42 Form 3 Connection Diagram ............................................44 Form 3A Connection Diagram .........................................48 88936KMA S280-75-2 Service Information

Form 3-3A ME Control Basic Maintenance Information

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Form 3-3A ME Control Basic Maintenance Information

Figure 1.Kyle® Type ME electronic recloser control

These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide direction formeeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem notcovered sufficiently for the user’s purpose, please contact your Cooper Power Systems sales engineer.

April 2002 ● Supersedes 12/88

ReclosersType ME Electronic Recloser Control,Form 3 and 3AMaintenance Instructions - Basic

1

CONTENTSSafety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Periodic Field Inspection and Maintenance . . . . . . . 6Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Circuit Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Plug-In Circuit Boards Function . . . . . . . . . . . . . . . .10

Battery Charging Board . . . . . . . . . . . . . . . . . . . .10Phase Trip No. 1 Board . . . . . . . . . . . . . . . . . . . .11Phase Trip No. 2 Board . . . . . . . . . . . . . . . . . . . .11Ground Trip No. 1 and No. 2 Boards . . . . . . . . . .11Output Board . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Diode Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Recloser-Reset Board . . . . . . . . . . . . . . . . . . . . .12

Closing Coil Control Fuse . . . . . . . . . . . . . . . . . . . . .12Interchangeability of Boards Between Form 2,Form 3 and Form 3A Electronic Controls . . . . . . . . .12Troubleshooting and Testing . . . . . . . . . . . . . . . . . . .13

Detailed Circuit Checks . . . . . . . . . . . . . . . . . . . . . . .14Input Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . .17Internal dc Load Current Signal . . . . . . . . . . . . . .18

Internal Minimum Trip Signal .....................................19Time-Current Characteristic Curves (TCC) ................20Control-Recloser operation ........................................22Major Control Damage ...............................................29Battery Charging ........................................................31Mechanical and Electrical Hardware ..........................35

Battery Maintenance ...........................................................35Battery Specifications ......................................................35Maintaining Battery Charge .............................................35Field Testing a Battery .....................................................35Shop Testing a Battery .....................................................36

Appendix I ...........................................................................37Test Sheet ........................................................................37

Appendix II ..........................................................................38List of Electronic Recloser Maintenance Manuals ...........38

Appendix III .........................................................................38List of Electronic Control Accessory Manuals ..................38

Appendix IV .........................................................................38Service Parts List .............................................................38

Appendix V ..........................................................................41Form 2 Connection Diagram ............................................42Form 3 Connection Diagram ............................................44Form 3A Connection Diagram .........................................48

88936KMA

S280-75-2Service Information

Page 2: Form 3-3A ME Control Basic Maintenance Information

2

TYPE ME ELECTRONIC RECLOSER CONTROL

The instructions in this manual are not intended as asubstitute for proper training or adequate experience inthe safe operation of the equipment described. Onlycompetent technicians who are familiar with this equip-ment should install, operate, and service it.

A competent technician has these qualifications:

• Is thoroughly familiar with these instructions.

• Is trained in industry-accepted high- and low-voltagesafe operating practices and procedures.

• Is trained and authorized to energize, de-energize,clear, and ground power distribution equipment.

• Is trained in the care and use of protective equipmentsuch as flash clothing, safety glasses, face shield,hard hat, rubber gloves, hotstick, etc.

Following is important safety information. For safe instal-lation and operation of this equipment, be sure to readand understand all cautions and warnings.

Safety InstructionsFollowing are general caution and warning statementsthat apply to this equipment. Additional statements, relat-ed to specific tasks and procedures, are located through-out the manual.

SAFETY INFORMATION

SAFETY FOR LIFECooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We activelypromote safe practices in the use and maintenance of our products through our service literature, instructional trainingprograms, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture,marketing, and service.

We strongly urge that you always follow all locally approved safety procedures and safety instructions when workingaround high voltage lines and equipment and support our “Safety For Life” mission.

!SAFETYFOR LIFE

!SAFETYFOR LIFE

This manual may contain four types of hazardstatements:

DANGER: Indicates an imminently haz-ardous situation which, if not avoided, will

result in death or serious injury.

WARNING: Indicates a potentially haz-ardous situation which, if not avoided, could

result in death or serious injury.

CAUTION: Indicates a potentially hazardoussituation which, if not avoided, may result in

minor or moderate injury.

CAUTION: Indicates a potentially hazardous situ-ation which, if not avoided, may result in equip-ment damage only.

!

!

Hazard Statement Definitions

!

WARNING: This equipment is not intended toprotect human life. Follow all locally approved

procedures and safety practices when installing or oper-ating this equipment. Failure to comply can result indeath, severe personal injury and equipment damage.

G102.1

!

DANGER: Hazardous voltage. Contact withhazardous voltage will cause death or severe

personal injury. Follow all locally approved safety pro-cedures when working around high and low voltagelines and equipment. G103.3

!

WARNING: Before installing, operating, main-taining, or testing this equipment, carefully read

and understand the contents of this manual. Improperoperation, handling or maintenance can result in death,severe personal injury, and equipment damage. G101.0

!

WARNING: Power distribution equipment mustbe selected for the intended application. It must

be installed and serviced by competent personnel whohave been trained and understand proper safety proce-dures. These instructions are written for such personneland are not a substitute for adequate training and expe-rience in safety procedures. Failure to properly select,install, or maintain this equipment can result in death,severe personal injury, and equipment damage. G122.2

!

Page 3: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

3

Figure 2.Electronic control panel.

88937KMA

INTRODUCTIONService Information S28O-75-2 covers basic maintenanceinstructions for the Type ME electronic control. The manualincludes a general description of the control, its operatingprinciples and instructions for periodic inspection and testing.Service parts lists along with ordering information are includ-ed in Appendix IV.

An introduction to the Form 3A, Type ME, electronic controlis available on video cassette (KSPV3); in this program thefunction of all standard operating and programming featuresis explained.

The factory service department offers maintenance trainingcourses for Type ME controls. These classes, taught by ex-

perienced service technicians, are held at the factory’s in-housetraining facility. For additional information, contact your sales engi-neer.

DESCRIPTIONThe Kyle Type ME electronic recloser control (Figure 1 ) is com-prised of a number of programmable, solid-state electronic circuitsthat perform the command functions involved in automatic recloseroperation. It is used to operate all Kyle electronically controlledreclosers.

A swing-out front panel contains the programming and operatingelements of the control (Figure 2). The upper, black portion

Page 4: Form 3-3A ME Control Basic Maintenance Information

4

Figure 3.Tie board on back of front panel mounts the individual printed circuit boards.

Type ME Electronic Recloser Control

88938KMA

of the front panel contains the plug-in components and settingknobs for programming automatic recloser operation. Theswitches and indicators used for manual operation and serviceare grouped on the bottom, light portion of the panel.

The front panel is backed by a printed-circuit tie board whichsupports and interfaces the plug-in circuit boards with otherrelated circuit components (Figure 3). Program-altering,remote control, indicating, and general convenience acces-sories can be added to further expand and enhance the appli-cation capabilities of the control.

Line current flowing through the recloser is sensed by threeinternally mounted bushing-current transformers, one on eachphase. When the phase current, or the zero-sequence (ground)

current, exceeds its programmed minimum-trip value, theelectronic control initiates the programmed sequence ofrecloser tripping and reclosing operations. If the fault is tempo-rary, the control ceases to command recloser operations aftersuccessful reclose, and the control resets to the start of itsoperating sequence after a preset time delay. If the fault ispermanent, the control performs its complete programmedsequence of recloser commands and locks out with the reclos-er open. Once locked out, the control must be manually resetto the start of its operating sequence which simultaneouslycloses the recloser.

Factory-calibrated timing plugs establish the time-currentcharacteristics for both phase and ground tripping. Two sets ofindividual timing curves provide dual timing for both phase andground.

Page 5: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

5

Figure 4.Typical operating sequence of an electronically controlled recloser under permanent fault conditions.

Figure 5.Typical operating sequence of an electronically controlled recloser under temporary fault conditions.

OPERATIONSince the understanding of the terminology and the operat-ing sequences of an electronically controlled recloser isimportant to the rest of this maintenance manual, examplesof typical operating sequences of an electronically controlledrecloser under permanent fault (Figure 4) and temporaryfault (Figure 5) conditions are given. The definition of theterms and callouts used in Figures 4 and 5 are:• Minimum Trip—Minimum trip is usually set at greater

than 2 times (200%) the maximum expected load currentto help prevent nuisance tripping on inrush currents, whilestill being sensitive to low level faults.

• Over-Current—Any current that exceeds the minimum-trip level of the control.

• Permanent Fault—Any over-current condition that per-sists through the operating sequence of the control.

• Temporary Fault—Any over-current condition that doesnot persist through the operating sequence of the control.

• Home Position—Position of sequence relay immediately after areset operation of the control. Reset operation can be eithermanual, by moving the Manual Control Switch to “CLOSE”, or automatic, after a temporary fault.

• Lockout—Sequence-relay position when over-current is not cleared before the operating sequences of the control are exceeded; control and recloser are tripped and held open until manually reset with the Manual Control Switch, or remotely with one of the remote close accessories.

• TCC—Time-Current-Characteristic-Curve.• Reclose Interval—Time-delay interval for each reclosing opera-

tion within the operating sequence of the control.• Fault Level Current—Any current that exceeds the minimum-

trip level of the control.• Normal Load—Any current below the minimum-trip level of the

control.

Page 6: Form 3-3A ME Control Basic Maintenance Information

6

Figure 6.Functional block diagram of Type ME control.

Type ME Electronic Recloser Control

A functional block diagram of the control operation is shownin Figure 6. Line current conditions are continuously monitoredby the three bushing-type current transformers in the recloser.output from these transformers is fed to the trip network in thecontrol, which includes: the minimum-trip resistors, isolationtransformers, and rectifier circuits.

If current remains above the minimum-trip level, the tripping—reclosing sequence of fast and delayed operations is repeat-ed as programmed to lockout.

When current above the selected minimum-trip level isdetected in one or more phases, the following chain of eventswill occur for an operating sequence of two-fast and two-delayed operations:

The overcurrent signal is integrated with time on the charac-teristic curve of the timing plug in Socket 1 to produce the sig-nal which energizes the trip circuit. Energizing the trip circuitconnects the battery to the trip solenoid, tripping the recloser.Simultaneously, the sequence relay advances to energize thefirst reclosing interval-delay plug. Upon expiration of thisreclosing interval delay, a closing signal, from the control, clos-es the recloser, and the sequence relay sets up the circuitry forthe second fast trip operation.

If the overcurrent is cleared before the operating sequencereaches lockout, the reset-delay circuit starts timing when therecloser closes into the unfaulted line. When the reset-delayplug times out, the sequence relay is reset to the start or“HOME” position and the control is ready for another two-fast,two-delayed trip-operating sequence. However, should thefault restart before the reset plug times out, the control willcontinue its operating sequence, where it left off last, and thereset-delay timing will be erased.

Ground-fault sensing and tripping operations occur exactlythe same as phase-fault sensing and tripping, except thatzero-sequence (ground) current is sensed instead of phasecurrent. The ground-fault circuitry includes its own minimum-trip resistor, fast and delayed trip-timing plugs, and number offast operations setting. Reclose and reset intervals and opera-tions to lockout are common for both phase-trip and ground-trip modes of operation.

PERlODIC FIELD INSPECTlON AND MAINTENANCEPeriodic inspection of the ME control should include these proce-dures:

1. Remove control from service (if connected to an in servicerecloser):A. Switch Ground Trip Block switch to “BLOCK”. B. Disconnect control cable from control.

2. Check the outer surface of the control cabinet for paintscratches. Touch up any paint scratches to maintain the cabi-net condition.

3. If the second entrance hole in the bottom of the cabinet is notused, be sure that the hole plug is secure in the bottom of thehousing to maintain its weatherproof design.

4. Inspect the gasketing. Check the control interior for any mois-ture or foreign matter. Repair or correct if necessary.

5. Check that the timing plugs, reset and reclosing intervaldelays, and minimum-trip resistors are firmly in their sockets(Figure 2).

6. Swing open the front panel. Check to see that all leads to tie-board terminals are secure (Figure 7).

CAUTION: Shorting battery positive to batterynegative at the battery test terminals will cause per-

manent damage to the control. The control will be inoper-ative and possible misoperation (unintentional operation)of the recloser may result.

!

CAUTION: In order to prevent possible, misoper-ation (unintentional operation) of the recloser, the

control must be removed from service prior to performingany maintenance, testing or programming changes.

!

WARNING: High voltage. Contact with high volt-age will cause serious personal injury or death.

Follow all locally approved safety procedures when work-ing around high voltage lines and equipment.

!

Page 7: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

7

Figure 7.View of a Form 3A tie board (back if front panel. Notations in parenthesis after callout refer to the circuit points on the tie board dia-gram illustrated in Figure 57.

88939KMA

7. Check battery voltage. Three battery test terminals in thelower right corner of the panel (Figure 2) are used to checkbattery voltage, quiescent drain, and charging rate. Referto the “Battery Maintenance” instructions in this manual.

The left-hand pair of terminals (V) are connected directlyacross the battery output to check battery voltage. The redterminal (far left) is positive (+). The output voltage of a fullycharged battery will normally be 26-28-volts. If lower, refer

to the “Detailed Circuit check—Battery Charging” and/or“Battery Maintenance” section of this manual.

If necessary, recharge the battery, as detailed in the“Battery Maintenance” section.

8. Make sure circuit boards are secure in their receptacles.Examine wiring between transformers and tie boards to see ifconnections are in order. Close front panel and secure firmlywith fasteners.

Page 8: Form 3-3A ME Control Basic Maintenance Information

8

Figure 8.Detailed block diagram of Type ME control in lockout position. Letters in circles (A,B, etc.) refer to control cable receptacle connec-tion pins and to test points referred to in the "Troubleshooting and Testing" section.

Type ME Electronic Recloser Control

9. Check control battery charging rate before returning thecontrol/recloser to service; see the “Battery Maintenance”section for details on charging rate testing.

NOTE: The servicing procedures outlined in this manual are for astandard Type ME Form 3 and Form 3A control and do not includethe operational checks of any of the accessories that may beattached. In some cases the accessories may modify the standardoperating characteristics of the Type ME control. Refer to catalogbulletin 280-75 for accessories furnished and/or Accessory opera-tion, Testing, and Installation manuals listed in Appendix lll of thismanual.

10. Return control to service:A. Check battery to ensure that it is properly connected.B. Move Manual Control Switch to match position of reclos-

er (open or closed).C. Reconnect control cable to control.D. Switch Ground Trip Block switch to “NORMAL”.

SERVICINGCircuit LogicLine current conditions are monitored continuously by threebushing-current transformers in the recloser, one on eachphase. The current transformers are connected to the control-phase matching transformers in a typical “WYE” to “WYE” con-figuration. Zero-sequence current is derived from the vector sumof the phase currents and fed to a fourth ground matching trans-former.

The minimum-trip resistors calibrate the overall recloser tripcurrent by diverting a portion of the recloser current from thecontrol matching transformers.

The four matching transformers isolate the various signalsfrom each other and deliver an ac voltage proportional to therecloser-line current to the phase-trip No.1 end ground-trip No.1 boards.

Page 9: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

9

Figure 9.Diagram of Form 3A tie board showing plug-in circuit board location. Form 3 tie boards are similar (see Figure 18), except some ofthe terminals are missing or in a slightly different location.

From this point, phase- and ground-trip signals are verysimilar, and only phase signals will be described.

The phase-trip No. 1 board circuitry, consisting of a three-phase full-wave rectifier, which converts the ac input signalfrom three phase to a single do signal. The do signal isapplied to the phase-trip No. 2 board which measures the dolevel, and determines whether a fault current exists at therecloser.

If the load current conditions are in the fault region, the mini-mum-trip portion of the phase-trip No. 2 board switches on, allow-ing the time-current curve circuits to start their programmed timedelay. The time-current curves are driven by the same do voltageoutput of the phase-trip No. 1 board, and as a result higher fault-current levels will result in a shorter time delay before tripping.

Page 10: Form 3-3A ME Control Basic Maintenance Information

10

Figure 10.Battery-charging board,

Type ME Electronic Recloser Control

82027aKMA 88940KMA

After the timing plugs have completed their cycle, the outputboard is triggered. The output board applies a 24-Vdc signal tothe recloser trip coil, the control counter, and the controlsequence relay. The output board is switched off when therecloser “a” contact de-energize the circuitry, including thesequence relay. The sequence-relay rotary contacts thenadvance to the next position in the tripping and reclosing cycle.

The recloser “b” contacts then close, connecting batterypower to the reclose intervals of the control which provides atime delay for reclosing the recloser. The rotary close solenoidis then energized through the recloser “b” contacts, the controlfuse, and the reclose portion of the control circuitry. Thismechanically closes the closing contactor in the recloser—allowing the closing solenoid to be energized.

After closing the recloser “b” contact opens, this removes dopower from the entire closing circuit.

The automatic reset portion of the Form 3A control is ener-gized by the sequence relay and the recloser “a” contact; if afault does not exist on either phase or ground trip, reset timingis initiated (unless connected to time after first trip). If a faultexists on either phase or ground, the reset timing is erasedand is blocked for the duration of the fault. For Form 3, resettiming begins after the first tripping operation. Should the resettime-delay operate before the recloser has locked open, thesequence relay will return to the starting position and a newsequence of operations will begin.

NOTE: F3 controls can be updated, with the addition of the KA304ME,to duplicate the automatic reset mode of a F3A control.

The Form 3A control battery is charged by the ac input(120-or 240-Vac) to the control. The ac input is applied througha current limiting resistor and isolating transformer to the bat-tery charging board. The battery charging board converts theinput to dc and supplies charging current to the control battery.on Form 3 controls, the battery is charged by bushing currenttransformers on the recloser unless equipped with an accharging accessory. on motor operated reclosers, the ac sup-ply to the motor also supplies power to the Form 3 batterycharger.

Plug-in Circuit Boards - FunctionThe ME control contains a total of eight plug-in circuit boards onwhich are assembled the bulk of its operating circuits. Theboards and their function will be discussed individually in theorder they appear on the tie board, starting with the bottomboard.

BATTERY-CHARGING BOARDThe lowest board in the rack is the battery-charging board(Figure 10). Prior to serial number 50070 controls were equippedwith a fixed rate potential charging board (MEA 388-1 ) as stan-dard equipment. After serial number 50070 a temperature regu-lated battery-charging board (MEA 1172) has been supplied asstandard. !

The fixed rate charging board consists of a full-wave bridgerectifier, a capacitor, a reference zener diode and some resis-tors. The resistors control the charging rate into the battery, fromthe zener supply voltage.

The temperature regulated battery-charging board also makesuse of a full-wave bridge rectifier, a capacitor, and a zener diode(used to regulate voltage). In addition a temperature sensitivethermistor is added to regulate the bias over a pair of transistors.These transistors are used in the circuit output to regulate thecharging rate, in response to temperature. Several resistors areused in the transistor bias circuit; and one resistor is used to limitthe maximum charging rate. A diode is placed in the output toprotect the circuit from reverse bias. ‘

Energy for either battery-charging board comes from the 120-or 240-Vac source,through current limiting resistance and apotential transformer.

CAUTION: Do not replace a MEA 388-1 boardwith a MEA 1172, or vice-versa. A MEA 388-1

board will be damaged if replaced ffor a MEA 1172. AMEA 1172 will not provide adequate charging current ifreplaced for a MEA 388-1

!

Page 11: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

11

Figure 14.Ground-trip No. 2 board.

Figure 20.Capacitor for CT-type battery charger.

86773KMA

Figure 13.Ground-trip No. 1 board.

88943KMA

Figure 11.Phase-trip No. 1 board.

88941KMA88944KMA

PHASE-TRIP NO. 1 BOARD The second board from the bottom is the phase-trip No. 1board (Figure 11). It has three full-wave diode sets, one foreach phase, along with a loading resistor for each phase.This board also has the beginning circuits for the minimumtrip function.

PHASE-TRIP NO. 2 BOARDThe phase-trip No. 2 board (Figure 12) carries the remaining cir-cuits for minimum-trip and the wave-shaping circuits for the timingplugs. There are two tabs on the phase-trip No. 2 board for theForm 3 and 3A control. one tab is labeled minimum-trip (MIN.TRIP)* and is battery plus for normal line currents and switches tobattery minus for fault currents; the second tab marked (DIR.BLOCK)* is an inactive tab at this time.

* In early Form 3 boards, these tabs may not be labeled.

GROUND-TRIP NO. 1 AND NO. 2 BOARDSThe next two boards up, ground-trip No. 1 and No. 2 (Figures 13and 14), are like the corresponding phase-trip boards, except thatthe ground-trip No. 1 board has only a single input diode bridge forground current. These boards carry almost the same parts andsame configurations as the corresponding phase boards.

Page 12: Form 3-3A ME Control Basic Maintenance Information

12

Figure 15.Output Board.

Type ME Electronic Recloser Control

88945KMA

Figure 17.Reclose-reset board.

88947KMA

Figure 16.Diode Board.

88946KMA

OUTPUT BOARDThe output board (Figure 15) of the control has another doamplifier which senses the charge on the timing plugs and atthe proper time gates the tripping SCR. This board also carriesthe diodes and resistors which make up the various referencevoltages for the control. Other circuits on this board are usedto inter-tie the tripping circuits and the reclose and reset cir-cuits.

DlODE BOARD The diode board (Figure16)consists of a group of diodes whichare connected to circuits on the other printed circuit boards.These diodes connect to the timing plugs, the reset circuit, thetrip circuit, and the reclose circuit. The board also contains thecircuit related to the closing circuit fuse.

RECLOSE-RESET BOARD The reclose-reset board ( Figure 17) carries all circuits neces-sary for reclosing and resetting. The various large capacitorson this board are the C parts of an R-C circuit operating alongwith unijunctions and SCR’s. The large SCR on this board isthe reclose SCR.

Closing Coil Control FuseOn solenoid-operated reclosers, the fuse will open the closing cir-cuit to protect the potential closing coil in the recloser if closingcannot be accomplished due to low closing voltage. On motor-operated reclosers, the fuse is connected in series with the clos-ing circuit contactor in the recloser.

A Buss Type MDQ-3/8 amp, 250-volt fuse, manufactured byBussman Manufacturing is used and a box of five spare fuses issupplied with each control. Fuses of similar ratings by other man-ufacturers have slightly different characteristics and should not beused for replacement.

CAUTION: Use only Buss Type MDQ-3/8 ampfuses. Previously, all Form 3A and most earlier con-

trols were supplied with Buss Type MDL-3/8 amp fuses.Buss has redesigned and changed the characteristics ofthat fuse and it is no longer suitable for use on any Form3 or Form 3A control. Failure to use proper closing coilcontrol fuse will result in unnecessary fuse operation andprevent the recloser from closing.

!

NOTE: Buss has redesigned the MDL-2.5 amp fuse that is used on con-trols shipped with reciosers having “quick-close” mechanisms such asType VSO and VSMT reclosers. The characteristics of the new single ele-ment MDL-2.5 fuse do not affect the application in the control. Buss willalso continue to manufacture the original dual element version of the fuseunder the new designation of MDQ-2.5. The MDQ-2.5 amp fuse will besupplied with controls for this application. Both the MDL-2.S amp fuseand the MDQ-2.S amp fuse are acceptable for this application.

INTERCHANGEABILITY OF BOARDSBETWEEN FORM 2, FORM 3 AND FORM 3AELECTRONIC CONTROLS.The battery-charger, phase-trip #1, phase-trip #2, ground-trip#1 and ground-trip #2 circuit boards can electrically be inter-changed between Form 2, Form 3 and Form 3A controls.However, the Form 2 circuit boards have an offset connectorwhich can result in clearance problems when Form 2 and Form3/3A boards are mixed in the same control. This procedure istherefore not recommended except in an emergency.

The fixed rate battery charging board (MEA 388-1 ) is electri-cally interchangeable between Form 2, Form 3 and Form 3Acontrols, when replacing another fixed rate board. The temper-ature regulated charging board (MEA 1172) should only beused to replace another charging board of the same type.

The upper three circuit boards (output, diode, and reclose-reset boards) are not interchangeable between Form 2 andForm 3/3A controls. Interchanging them will cause controlmisoperation, and may cause circuit board damage.

Page 13: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

13

Figure 18.Form 3 electronic control tie board.The test points listed above will be covered in detail in the "Detailed Circuit Check" section ofthis manual.

TROUBLESHOOTING AND TESTINGA number of relatively simple circuit tests can be made onthe ME electronic control. These tests will indicate whethermajor circuits are operating properly or not, but they will notnecessarily isolate the faulty component within the circuit.For easy reference to testing points, refer to Figures 18 and19 for Form 3 controls and Figures 20 and 21 for Form 3Acontrols. When appropriate, isolated test points will beshown for individual circuit tests with reference to the prop-ertie board (Figures 18 to 21).

Trouble Check

1. Completely Are boards plugged in correctly? inoperative Is battery connected and fully charged (23-Vdc

minimum)?Is control cable connected?Is control programming correct?

2. Won’t close Is the control fuse good?RE and WE series reclosers—Is the yellow oper-

ating handle up?CE, ME and VS series reclosers—Is the manual-

trip/reset knob in the proper position?RE and WE series reclosers—Can the rotary close

solenoid be heard to operate? If so, test for highvoltage to recloser closing coil (refer to specificrecloser maintenance manual— Appendix II).

Is there 120- or 240-Vac power to the control?

3. Won’t trip Is battery connected and fully charged (23-Vdcminimum)?Is control cable properly connected?

TABLE 1Pre-Check

82040KMA

Page 14: Form 3-3A ME Control Basic Maintenance Information

Figure 19.Form 3 electronic control tie board and control back panel.The test points listed above will be covered in detail in the "DetailedCircuit Check" section of this manual.

Type ME Electronic Recloser Control

14

CAUTION: Be sure that test equipment leadshave insulated clips to prevent short circuiting adja-

cent ME control terminals during testing. Shorting termi-nals may cause permanent damage to circuit compo-nents. The control may be inoperative and possiblemisoperation (unintentional operation) of the reclosermay result.

!

82047KMA

Pre-Check When troubleshooting a control reported to have failed or tohave not worked properly, always check for simple problemsfirst.

Detailed Circuit Checks The following test procedures require only the following twotest devices.

A volt-ohm meter will be required (minimum meter inputimpedance 20,000 ohms per volt) to perform tests. The Kyle Type MET test set, or an actual recloser with a

source of primary or secondary test currents can also be used toperform tests.

Page 15: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

15

Figure 20.Form 3A electronic control tie board.The test points listed above will be covered in detail in the "Detailed Circuit Check" section ofthis manual.

88948KMA

If a circuit board failure is suspected, always check orchange the diode board first because:• The diode board circuits operate in conjunction with the tim-

ing plugs, the output circuit, reset circuit, and reclosing cir-cuit.

• A primary diode failure on the diode board can cause sec-ondary failures on the output board or reclose set board.

NOTE Diode board short circuits are very rare in controls manufacturedafter 1970.

If this does not isolate the problem, continue with the circuittest.

Page 16: Form 3-3A ME Control Basic Maintenance Information

Figure 21.Form 3A electronic control back panel.The test points listed above will be covered in detail in the "Detailed Circuit Check" section ofthis manual.

Type ME Electronic Recloser Control

16

88939KMA

Page 17: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

17

INPUT CIRCUITS

WARNING: High voltage. Contact with high volt-age will cause serious personal injury or death.

Follow all locally approved safety procedures whenworking around high voltage lines and equipment.

!

CAUTION: When measuring voltage betweenthe violet and gray leads be careful not to short

between the gray wire and the B+ terminal. If the graywire is shorted to the B+ terminal the Phase Trip #1board will be permanently damaged.

!

Figure 22.Measured voltage across minimum-trip resistors.

TABLE 2Terminal Strip T1 Test Points for Matching Transformers(100% Minimum-Trip) (Figures 23 and 24)

82040KMA

Figure 23.Block diagram of matching transformers (Table 2). See Figure 8for complete block diagram.

To check input signals to the control, measure the voltageacross the minimum-trip resistors and matching transformersecondaries as follows:1. Measure voltage across minimum-trip resistors (Figure 22)

with 100% of minimum-trip current applied to control. Thevoltage should be approximately:

• Phase Resistors—0.17-Vac (170 millivolts)• Ground Resistors—0.26-Vac (260 millivolts)

NOTE: The above voltages are proportional to the recloser line currentand can be used to calculate the actual load current on the differentphases, using a digital AC voltmeter such as a Fluke 77 series. The fol-lowing formula can be used.

(Volts on (ResistorLine Amps = resistor x value amp)

0.17Example: 0.023-volts (23-millivolts) measured across a 560-amp phaseresistor is equivalent to 75.7-amps recloser-load current.Total accuracyis approximately +5%.

2. Measure voltage across matching transformer secondaries(Figures 23 and 24) with 100% of minimum-trip current ap-plied to control. The test terminals on “T1 “ are shown inTable2. The voltages should be:• Phase Transformers—6.5-Vac• Ground Transformers—1.2-Vac

Failure to get these voltage readings can be a result of:A. Opens in current source, control cable, matching trans-

former windings, or wiring to the transformers and asso-ciated components.

B. Shorts in the control’s male input-cable receptacle.

NOTE: Matching transformers are interchangeable between Form2, 3, and 3A controls.

Transformer Terminal Position Voltage Reading (Vac)

GND BRO—RED 1.2Aφ ORG—YEL 6.5Bφ GRN—BLU 6.5Cφ VI—GRY 6.5

Page 18: Form 3-3A ME Control Basic Maintenance Information

Type ME Electronic Recloser Control

18

Figure 24.Measuring voltage across matching transformers (Table 2) (control panel open, middle left hand side of control).

Figure 25.Block diagram of secondary side of matching transformers andinput bridge (Table 3).See Figure 8 for complete block diagram.

Figure 26.Form 3 tie board test points for internal dc-load-current signal (Table3.For relationship of terminal location on the tie board,see figures 18and 19.

88950KMA

82040KMA

INTERNAL dc-LOAD-CURRENT SIGNALTo check the dc-load-current output signal, measure the volt-age at tie board test points listed in Table 3 at 100% minimum-trip current.

Failure to get these signals can be due to trouble in thematching transformers, or open/or shorted diodes in phase-tripNo. 1 or ground-trip No. 1 circuit boards.

TABLE 3Tie Board Test Points for dc-Load-Current Signal(100% Minimum-Trip) (Figures 25,26 and 27)

Terminal Position VoltageLoad Current Form 3 Form 3A Readings

+Lead -Lead +Lead -Lead Vdc*

Seq. Seq.Phase Relay M-ph Relay Phase Minus 6.1

7A 7A

Seq. Seq.Ground Relay M-gnd Relay Gnd Minus 0.78

7A 7A

*These are full-wave rectified signals.

Page 19: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

19

Figure 28.Form 3 tie board test points for internal minimum-trip signal (Table 4). For relationship of terminal location on the tie board, seeFigures 18 and 19.

Figure 27.Form 3A tie board test points for internal dc-load-current signal(Table 3).For relationship of terminal location on the tie board,seefigures 20 and 21.

88948KMA

TABLE 4Tie Board Test Points for Minimum-Trip Signal Figures 28,29,and 30)

INTERNAL MINIMUM TRIP SIGNALTo check the minimum-trip signal, measure the voltage at tieboard test points listed in Table 4.

Failures to get these signals are most likely due to troubles onthe phase-trip No. 2 or ground-trip No. 2 circuit boards or possi-bly with the phase-trip No.1 or ground-trip No.1 boards. Batteryvoltage below 21-Vdc will cause control misoperation of the min-imum-trip, timing and trip signals of the control. Battery voltageabove 23 volts will operate the circuits correctly. Refer to“Battery Maintenance,” page 35, for battery charging and testinginformation.

Minimum Terminal Position Voltage Reading VdcTrip Form 3 Form 3A 120%

Signal Minimum-+Lead -Lead +Lead -Lead No Fault Trip*

Ph Seq. Ph Seq.Phase Min. Relay Min. Relay 25 or 0.30 Max.

Trip 7A Trip 7A Battery

Gnd. Seq. Gnd. Seq.Ground Min. Relay Min. Relay 25 or 0.30 Max.

Trip 7A Trip 7A Battery

*Voltage reading will last only for the duration of the clearing time of the controland recloser/simulator.

Page 20: Form 3-3A ME Control Basic Maintenance Information

Figure 29.Form 3A tie board test points for internal minimum-trip signal(Table 4). For relationship of terminal location on the tie board,see Figures 20 and 21.

Figure 30.Block diagram of internal minimum-trip signal circuit (Table4). See Figure 8 for complete block diagram.

Figure 31.Block diagram of time-current circuit (Table 5). See Figure 8 forcomplete block diagram.

Type ME Electronic Recloser Control

20

88948KMA

TIME CURRENT CHARACTERISTIC CURVES (TCC)NOTE: Since some volt meter burdens will change control calibration, thistest will only verify TCC plug operation.

To check the charging of the phase-or-ground-TCC plug, measurethe voltage drop at the tie board and the TCC socket pin testpoints listed in Table 5. Make connections and raise currentto120% minimum-trip level.

Failure to get a sudden voltage change for a fast TCC plug or agradual change for a slow TCC plug can be caused by trouble onthe phase-trip No. 2 or ground-trip No. 2 board, trouble on the var-ious timing plugs, open diodes on the diode board, or open con-tacts on the phase- or ground-trip socket No. 1 selector switches.*

* Problems on selector switches are rare on ME controls above S/N 6000.

TABLE 5Tie Board/TCC Socket Pin Test Points for TCC Charging(120% Minimum-Trip) (Figures 31,32 and 33)

* On a fast TCC curve the voltage will drop from 24-Vdc to less than 7-Vdc theinstant the fault current increases above minimum-trip.

* * On a delayed TCC plug an obvious time delay can be observed as the meter volt-age slowly drops from 24-Vdc to 7-Vdc at which time the unit trips

Test PointsTCC Form 3 and 3A VoltageCurve +Lead (Phase or -Lead Drop Vdc

Ground TCC Plug)

Fast No. 1 pin, No. 2 TCC Sequence Relay 7A 24 - 7*

Slow No. 1 pin, No. 2 TCC Sequence Relay 7A 24 - 7*

Page 21: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

21

Figure 32.Form 3 test points for TCC operation (Table 5). For relationships of terminal/pin location on the tie board and rear of front panel, seeFigures 18 and 19.

82040KMA

Figure 33.Form 3 test points for TCC operation (Table 5). For relationships of terminal/pin location on the tie board and rear of front panel, seeFigures 20 and 21.

88948KMA

Page 22: Form 3-3A ME Control Basic Maintenance Information

Figure 35.Typical motor operated recloser (VSAT shown) and electronic control connection.

Figure 34.Typical RXE and WE series reclosers with electronic control cable connection.

Type ME Electronic Recloser Control

22

CONTROL-RECLOSER OPERATIONTo provide a better understanding of the control operational cir-cuit checks and the relationship between the recloser circuitsand the control output, typical recloser connections to the ME

electronic control are shown in Figures 34 and 35. For detailedinformation on electronic recloser/control operational circuits, con-sult the maintenance manual for your recloser (see Appendix 11).

Page 23: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

23

To check voltage changes during typical recloser-tripoperations, measure voltage at test points listed in Table 6.

Failure to get voltage readings indicated usually indicatesproblems in the recloser. Consult the recloser maintenancemanual for testing and service information (see Appendix 11).

Figure 36.Block diagram of trip-operating (Table 6). See Figure 8 for com-plete block diagram. Letters in circles (A,B, etc.) are test pointsand correspond to control cable receptacle pin connectionpoints.

Figure 37.Form 3 test points of recloser-trip operations (Table 6). For rela-tionship of terminal test points, see Figures 2, 18 and 19.

82040KMA

TABLE 6Test Points for Trip Operating Circuit(Figures 36,37,and 38)

* Trip signals have a time duration of only 0.04- to 0.5-seconds, depending on recloser type. If voltage on tie board B drops to 2.2-volts for longer than 5-seconds, the recloser failed to trip. Unplug the controlbattery.

Test PointsVoltage Vdc

Voltage Vdc Control Recloser Closed Voltage Vdc Voltage Vdc Recloser open,+Lead -Lead Control in Lockout No Fault Trip Signal* But Not Locked out

Form 3 and 3A Form 3 and 3A

Tie Board A Middle Battery Test Terminal 24 24 24 24

Seq. Relay 7A Middle Battery Test Terminal 24 0 0 0

Tie Board B Middle Battery Test Terminal 24 24 2.2 24

Page 24: Form 3-3A ME Control Basic Maintenance Information

Figure 38.Form 3A test points for recloser-trip operation (Table 6). Forrelationship of terminal tet points, see Figures 2, 20, and 21.

Figure 39.Block diagram of closing, tripping and reclosing circuit (Table 7).See Figure 8 for complete block diagram. Letters in circles (A, B,etc.) are test points and correspond to control cable receptaclepin connection points.

Type ME Electronic Recloser Control

24

88948KMA

To check voltage changes during closing from lockout,tripping and reclosing, measure voltages at test points listed inTable 7.

Failure to get voltage readings indicated usually indicates prob-lems in the recloser. Consult the recloser maintenance manual fortesting and service information (see Appendix 11).

TABLE7Test Points for Closing,Tripping and Reclosing Circuit(Figures 39,40,41)

* Closing signal is about 0.5-seconds, depending on recloser type.* * Value may vary depending on recloser type

***Recloser will close when approximately 15-Vdc is reached and will drop to zero after reclose operation. This voltage measurement tests the circuitry of the Recloser-Reset board (MEA381)

Test Points+Lead -Lead Voltage Vdc Voltage Vdc Voltage Vdc Voltage Vdc Voltage Vdc

Form 3 and 3A Form 3 and 3A Control in Lockout Control Reset Closing* Coil Energized Control Closed Reclosed Timing

Seq. Relay Middle BatteryTest Terminal 25 0 0 0 0

F-1 Middle BatteryTest Terminal 25 25 1 0 25

F-2 Middle BatteryTest Terminal 25 25 1.5** 0 25

E Middle BatteryTest Terminal 25 25 1.5** 0 25

F Middle BatteryTest Terminal 25 25 25 0 25

A Middle BatteryTest Terminal 25 25 25 25 25

8 Middle BatteryTest Terminal 1 0 0 0 0 to15***

Page 25: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

25

Figure 40.Form 3 test points for closing, tripping and reclosing operation (Table 7). For relationship of terminal test points, see Figures 2, 18and 19.

82040KMA

Figure 41.Form 3 test points for closing, tripping and reclosing opeation (Table 7). For relationship of terminal test points, see Figures 2, 18and 19.

88948KMA

Page 26: Form 3-3A ME Control Basic Maintenance Information

Figure 42.Block diagram of trip-reset circuit (Table 8). See figure 8 for complete block diagram. Letters in circle (A,B, etc.) are test points andcorrespond to control cable receptacle pin connection points.

Type ME Electronic Recloser Control

26

To check voltage changes during trip and reset opera-tions, measure voltage at test points listed in Table 8.

Failure to get voltage readings indicated usually indicatesproblems in the reset-reclose circuit board. Repair involvesreplacement of the circuit board. Unstable minimum-trip volt-age levels will upset or prevent automatic reset operation.

TABLE 8Test Points for Trip and Reset Circuit(Figures 42,43 and 44).

* At 15-Vdc automatic reset occurs returning voltage levels to "control in home" condition. Voltage returns to zero after rest operation.

Test Points Voltage VdcVoltage Reclose Into Voltage Vdc

+Lead -Lead Vdc Low Level Reclose IntoForm 3 Form 3 Tripped Fault (120% No Faultand 3A and 3A Minimum-Trip)

MiddleBattery

Reset #2 Test 0 0.7 0.7 to 15*Terminal

MiddlePhase Trip Battery#2 Board, Test 25/0 0 25Minimum-Trip Terminal

Page 27: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

27

Figure 43.Form 3 test points for trip-reset operation (Table 8). For relationship of terminal test points, see Figures 2, 18 and 19.

Page 28: Form 3-3A ME Control Basic Maintenance Information

Figure 44.Form 3A test points for trip-reset operation (Table 8). For relationship of terminal test points, see Figures 2, 20, and 21.

Type ME Electronic Recloser Control

28

Page 29: Form 3-3A ME Control Basic Maintenance Information

Figure 45.Form 3 continuity checks (Table 9). For relationship of terminal test points, see Figures 2, 18, and 19.

82040KMA

S280-75-2

29

MAJOR CONTROL DAMAGE To verify the condition of the Form 3 and 3A tie board in theevent of major control damage, check the continuity of commontie board terminals listed in Table 9 (Form 3) and Table 10(Form 3A).

Failure to get continuity for any of the test points indicates tieboard failure. Failure in other circuitry is extremely rare.

TABLE 9Form 3 Tie Board Continuity Checks (Figure 45)

Continuity fromTerminals "B+" To

LampLA5A

Counter C-1

Continuity fromTerminals "B-" To

N4B

Page 30: Form 3-3A ME Control Basic Maintenance Information

Figure 46.Form 3A continuity checks (Table 10). For relationship of terminal test points, see Figures 20 and 21.

Type ME Electronic Recloser Control

30

88948KMA

TABLE 10Form 3A Tie Board Continuity Checks (Figure 46)

Continuity fromTerminals "A+" To

Lamp5A

Counter 1

Continuity fromTerminals "N-1" To*

L-24B

* For controls with capacitor backup trip accessory (KA1119ME or KA1122ME,check continuity from diode point shown on Figure 47.

Page 31: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

31

Figure 47.Battery test terminals.

Figure 48.Comparison of charging rates.

BATTERY CHARGINGTo check the battery charging operation:1. Make sure control is in home (reset) position by moving

manual operator to “CLOSE.”2. Connect a dc milliammeter into right hand pair of battery-test

terminals(←l→ ),see Figure 47. Loosen both terminalsslightly and disconnect shorting link from between terminals.

3. With battery charger deenergized, current will flow oppositeto the direction shown by CHG. Under normal conditions,quiescent drain will be 1-1/2-to 2-mA. However, shorter timereset plugs and certain accessories can, as shown in Table11, increase quiescent drain above nominal value.

NOTE: To verify the charge/discharge polarity of the test meter,momentarily actuate the LAMP/LOCKOUT TEST toggle switch to"LAMP TEST." The current measured is a discharge current.

TABLE 11Quiescent-Battery Drain Above Normal*

Description Drain (mA)

3-second reset plug 2.310-second reset plug 0.8Sequence coordination accessory (if blocked in

home) 0.8Remote minimum-trip double-supervisory contacts

closed) 6Targets 1.9

* For complete list of accessory quiescent drain, see the Service Informationmanual on the MET Tester, S28O-76-1.

4. With the battery charger energized, current will flow in thedirection shown by CHG. The charging rate should beapproximately 17-mA minus the discharge rate measured inStep 3, if the control is equipped with the fixed rate batterycharging board ( MEA 388-1). The charging rate wilI varywith internal control cabinet temperature if equipped with the

temperature regulated charging board (MEA 1172), See Figure48). A typical charging rate will be about 27 mA, at normal roomtemperature.

NOTE: The 17-mA charging rate is a nominal value based on a 27-voltbattery and rated input parameters (e.g. 120-Vac). Even under thesestandard conditions. a variation of +2-mA may be observed in thecharging rate.

Prior to 1978 many recloser-control combinations (controlserial numbers below 26000) had the battery-charging circuitryin the recloser. Refer to ME control installation manual S280-75-1 for exact Control-Recloser interchangeability.• In the RE & WE family (Form 3 ME Control era), where the

charging supply is taken from the line on B phase, at least40-amps must flow in B phase for a minimum of 12 hours per24-hour day to maintain an adequate battery charge.

• In the motor operated equipment (VS, ME and CE family)manufactured between 1969 and 1978 the charging supply istaken from the 240-Vac motor supply that is required to oper-ate the recloser. To maintain battery charge on these units,the 240-Vac supply must be connected to the recloser, andthe recloser and control must be connected via the controlcable. After 1978 (above serial number 26000) most controlswere provided with battery-charging circuitry within the con-trol itself. These require 120-Vac (or 240-Vac) to be connect-ed to the control’s power-supply-input terminals.Failure to get the proper charging rate can be caused by

either a high control quiescent-battery discharge rate or by amalfunction in the battery-charger circuitry. To help isolate prob-lems in the battery-charging circuitry, see Figures 49, 50 and 51and Table 12.

NOTE: A totally discharged battery may indicate an excessive quies-cent-battery discharge rate due to a problem in the ME control. Testquiescent-battery discharge rate with a fully charged battery.

Page 32: Form 3-3A ME Control Basic Maintenance Information

Figure 49.Block diagram of test points for battery-charging circuitry. See Figures 50 and 51 and Tale 12 for specific testing points and values.

Type ME Electronic Recloser Control

32

Page 33: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

33

Figure 50.Form 3 test points for battery-charging acessory circuitry (Table 12).

TABLE 12Battery-Charging Circuitry Checks (Figures 49,50 and 51)

* The actual voltage reading will depend on the type of voltmeter used. This voltage will be lower if the control battery is totally discharged. Repeat testwith a fully charged battery.

Voltage Reading (Vac)Test Points Location Form 3 Form 3A Form 3A If Voltage Reading Is

Fixed Rate Temperature Not Obtained, Check:Charger Regulated Charger

A Incoming - Fused switch 120/240 - - • Low voltage supply

A Incoming - Potential battery charging - 120/240 120/240 • Connections and wire from terminal strip

board • Fused switch

B Outgoing - Fused switch 120/240 - - • Fuses

B1 & B2 Outgoing - Potential battery charging - 35-38* 52-55* • Shorted battery

board • Defective ballast board

• Open circuit

C Outgoing - Surge protection module 120/240 • Defective surge module

• Input receptacle connections

C1 & C2 Tie board terminals (L&K) and (3 & 4) - 35-38* 52-55* • Wiring

• Open transformer

D Outgoing - Battery charging acessory • Accessory board connections

35-38* - - • Wiring

• Defective potential battery charger accessory

• Open transformer

• Battery transformer connections

D Tie board terminals 1 and 2 - 32-35* 34-36* • Wiring

• Open transformer winding

• Battery transformer connections

E Tie board terminals BRD and RED 32-35* - - • Wiring

• Open transformer winding

Page 34: Form 3-3A ME Control Basic Maintenance Information

Figure 51.Form 3A test points for battery-charging circuitry (Table 12).

Type ME Electronic Recloser Control

34

Page 35: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

35

Figure 52.Field testing a battery.

MECHANICAL AND ELECTRICAL HARDWAREAll mechanical and electrical hardware components (selectorswitches, toggle switches, manual switch, operations counter,trip sockets, phase sockets, resistor brackets, fuse receptacle,etc.) can be visually or electrically checked. If replacement isneeded, remove wires, noting their exact placement, remove allconnecting hardware and then remove the existing component.Install the new component by reversing procedure. SeeAppendix V for connection diagrams for ME controls Form 2, 3,and 3A.

BATTERY MAINTENANCEBattery Specifications• Nickel-cadmium. • 24-volts (20 cells in series). • 1.0 Ampere hour capacity (10 hour rate).• Charging rate: 50-mA maximum.• Weight: 41.5 oz. • Length: 10”. • Width: 2”. • Height: 2”.

Maintaining Battery ChargeThe battery is fully charged and ready to use just prior to ship-ment. For storage at temperatures under 70-degrees, the bat-tery will maintain adequate charge for operation up to 1-monthwithout trickle charging. However, extremely high ambient stor-age temperatures can result in a battery shelf-life of as little asone month. Thus we recommend that a control battery in stor-age not be left off charge for a period of more than 1-month.

Two convenient methods exist for applying a trickle chargeto the control battery.1. Connect the battery to the ME control and energize the

potential charger.

CAUTION: Shorting battery positive to batterynegative at the battery test terminals will cause

permanent damage to the control. The control will beinoperative and possible misoperation (unintentionaloperation) of the recloser may result.

!

CAUTION: Shorting the battery positive toground will damage a resistor on the control input

board, this will result in the battery negative floating,with respect to ground.

!

CAUTION: Do not short battery positive to thecontrol cabinet (or other ground). If shorted on a

Form 3 control the control will be permanently damaged,the control will be left inoperative and possible misoper-ation (unintentional operation) of the recloser mayresult. If shorted on a Form 3A control a resistor on theinput board will be destroyed; however, the control willremain operative.

!

WARNING: High voltage. The COMMON ACGND terminal is connected to the control cabinet.

If the incoming 120-Vac supply is inadvertently connect-ed to the common terminal the control cabinet will be at120-Vac potential. Contact with high voltage will causesevere personal injury or death.

!

2. A KA1142ME3 120-Vac battery charger is available for main-taining one ME control battery.

The KA1142ME3 battery charger provides two chargingrates, 15-mA and 50-mA. The 15-mA charging rate is used tomaintain a battery at full charge. The 50-mA rate is used tocharge a discharged battery. A battery must be charged atthe 50-mA rate for 48 hours.

NOTE: A fully discharged battery can be brought to full charge inabout 7-days with the control’s potential charger, if the battery isgood. The KA1142ME3 battery charger, at the 50-mA charge level,will recharge battery in about 48 hours.

Field Testing a BatteryNOTE: The battery in the Form 3 and 3A control has a steady drain ofapproximately 1.5- to 2.5-milliamperes (may be as high as 4.5-mil-liamperes with certain accessories).

To check the condition of a battery, a field test can easily bemade. To positively insure proper control operation, this test isconservative; failure to pass does not necessarily mean the bat-tery needs replacement. But a more thorough test can then beperformed—normally in a repair or maintenance shop.

To field test:

1. From the battery test terminals on the control front panelmeasure the battery voltage (see Figure 52). If battery volt-age is below 24-volts, the battery is either low on charge oris faulty. The battery should be removed for recharging andretested before returning to service.

2. If battery voltage is above 24-volts, a power delivery checkshould be made. To load the battery, a 10-ohm resistor (mini-mum of 10-watt size) is required. To test the battery—whilemeasuring battery voltage connect a 10-ohm resistor acrossthe battery test terminals, for approximately 2-3 seconds.The battery voltage should drop by no more than 3-voltsfrom the open circuit voltage, for ambient temperaturesabove 20 degrees F.

NOTE: Either a KA638ME voltmeter accessory or a KMET test setcan be used for the load test. Both devices have an internal 10-ohmload resistor.

3. If the temperature is below 20-degrees F. the voltage shouldbe approximately that shown by the lower curve in Figure53. If the voltage is lower than this, the battery should beremoved for shop testing.

Page 36: Form 3-3A ME Control Basic Maintenance Information

Figure 53.Typical voltage versus temperature characteristics of nickel-cadmium battery.

Type ME Electronic Recloser Control

36

Shop Testing a BatteryBefore testing, the top and bottom covers of the battery shouldbe removed. Then the following tests can be made.1. Check for leaking cells. These are detectable by the pres-

ence of a white powdery deposit of electrolyte.2. Measure voltage across each cell. Any cell measuring 0.0

volts is cause for immediate rejection of the entire battery.3. If all cells have at least 0.1-volts or more, charge the battery

using the KA1142ME battery charger. All cells should haveet least 1.0-Vdc within 5 minutes. Any battery failing thistest should be rejected.

4. Charge the battery for 48 hours with the KA1142ME batterycharger.

5. Place a 10-ohm load (a KA638ME voltmeter or MET Tester

has this built in) across the battery for approximately 2-3 sec-onds. The voltage must not drop more than 3-volts below theopen circuit voltage for temperatures above 20-degrees F.

6. Make a capacity check. Discharge the battery through a 100-ohm, 12-watt resistor for 3-hours. At the end of this period andwhile under load, check the individual cell voltages. No cellshould read less than 1.1-volts.

7. Remove the 100-ohm resistor. Recheck the open-circuit volt-age on each cell after 7-days. All cells should measure veryclose to the same voltage level. Do not recharge the batteryprior to this test.

If the battery passes the above test, it is in satisfactory condi-tion; replace the battery covers, recharge (48-hours using theKA1142ME battery charger) and return to service.

Page 37: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

37

APPENDIX ITest SheetNOTE: The following sample test sheet is a convenient method to systematically test the ME electronic control and then return it to its original pro-gramming condition

TEST RECORD SHEET FOR TYPE ME ELECTRONIC CONTROL

DATE CIRCUIT NO.

LOCATION

TESTER CONTROL S/N

RECLOSER S/N

CONTROL PROGRAMMING AS FOUND

MINIMUM TRIP GND Aφ Bφ Cφ

DIAL SETTING GND: LOCKOUT PHASE:

TOGGLE SWITCH POSITION:

TCC PLUGS GND 1st 2nd GND SWITCH BLOCK ( )

PHASE 1st 2nd GND SWITCH NORMAL ( )

COUNTER READING AS FOUND NORMAL RECLOSE ( )

BATTERY VOLTAGE AS FOUND NON-RECLOSE ( )

RECLOSING PLUGS 1st 2nd 3rd RESET

TESTS

MINIMUM TRIP GND Aφ Bφ Cφ

DIAL SETTING GND: FAST DELAY LOCKOUT SHOTS

PHASE: FAST DELAY

TIMING % AMP FIRST SHOT SECOND SHOT THIRD SHOT FOURTH SHOT

GND

PHASE A

PHASE B

PHASE C

RECLOSING 1st 2nd 3rd RESET

NON-RECLOSE TEST ( ) BATTERY DISCHARGE RATE

GND BLOCK TEST ( ) BATTERY CHARGE RATE

BATTERY VOLTAGE AS LEFT

COUNTER READING AS LEFT

Page 38: Form 3-3A ME Control Basic Maintenance Information

Type ME Electronic Recloser Control

38

TABLE 13Electronic Recloser Maintenance Manuals

APPENDIX IIMaintenance Manuals

TABLE 14Form 3 and 3A Type ME Electronic Control AcessoryOperation,Circuitry,Testing and Field Installation Manuals

APPENDIX IIIAccessory Manuals

TABLE 15Type ME Control Plug-In Panel Components Form 2 (AboveS/N 1900),Form 3 (Above S/N 4000),Form 3A (Above S/N26000)

APPENDIX IVME Contol PartsNOTE: For reference to Control parts and components, refer to Figures 2,7, 55, 56 and 57. For current prices, see the latest edition of the PartsPrice List.

Service Information Number Product Type

S280-40-4 WES280-40-6 VWE and VWVES280-40-7 RXE (S/N 517 and above)

WE (S/N 6316 and above)S280-40-8 RVE (S/N 2200 and above)

WVE (S/N 1000 and above)S280-45-3 VSML

ServiceInformation Form Accessory Accessory

Number 2,3,3A Catalog No. Description

S280-75-4 3, 3A KA316ME4 Remote-CloseS280-75-5 2, 3 KA304M E Reset-After-RecloseS280-75-14 2, 3, 3A KA333ME Reclose-BlockingS280-75-15 2, 3 KA1009, Low Ground Fault Tripping

KA1010KA1011,KA1012

S280-75-17 2 KA418ME Sequence CoordinationS280-75-19 2, 3, 3A KA287ME Surge ProtectionS280-75-20 2 3 KA542ME ThermostaticalIy Controlled,

HeaterS280-75-21 3, 3A KA1002ME Minimum-Trip DoublerS280-75-22 2, 3 KA531ME Fuse-EliminationS280-75-23 2, 3 KA472ME Lockout IndicatingS280-75-25 3, 3A KA1037ME Instantaneous TripS280-75-26 2, 3 KA458M E Battery-ChargingS280-75-31 3, 3A KA1004ME Remote TripS280-75-32 2, 3 KA880ME DC Voltage SupplyS280-75-33 3, 3A KA1036ME Instantaneous LockoutS280-75-34 3 KA418ME3 Sequence CoordinationS280-75-36 3, 3A KA333M E Reclose-BlockingS280-75-37 3A KA418ME7 Sequence CoordinationS280-75-38 3, 3A KA639ME3 Remote LockoutS280-75-39 3A KA542ME ThermostaticalIy Controlled

HeaterS280-75-40 3A KA880ME DC Voltage SupplyS280-75-41 3, 3A KA1137ME Target AnnunciatorS280-75-42 3, 3A KA1163ME Minimum Response TimeS280-75-43 3, 3A KA1009ME, Low Ground Fault Tripping

KA1010ME,KA1011 ME,KA1012ME

S280-75-44 3, 3A KA531ME Fuse EliminationS280-75-45 3A KA1174ME Temperature Regulated Battery

ChargerS280-75-47 3A KA1021ME Phase and Ground Protective

AccessoryS280-75-48 3A KA1119ME, Capacitor Backup Trip

KA1122MES280-75-49 3, 3A KA2003ME Remote Close With Cold Load

PickupS280-75-50 3, 3A KA545ME3 Load Current IndicatorS280-75-51 3, 3A KA2039ME Recloser StatusS280-75-52 3, 3A KA2035ME2 Remote Non-Reclose and

Remote Ground Trip Block,Maintained Contact

S280-75-53 3 3A KA2071 ME1 Remote Non-Reclose and, Remote Ground Trip Block,Pulsed Contact

S280-75-55 3, 3A KA2070ME Remote Close With Cold LoadPick Up, Remote Lockoutand Recloser Status

S280-75-56 3 3A KA2072ME Remote Battery Test and, Battery Voltage MonitorAnalog output

S280-75-57 3, 3A KA2047ME Remote Battery Test andVoltage Monitor

S280-75-61 2, 3, 3A KA1142ME3 Portable Dual Rate BatteryCharger

Catalog No. DescriptionKA216ME1S Ground Trip Timing Plug Curve 1KA216ME2S Ground Trip Timing Plug Curve 2KA216ME3S Ground Trip Timing Plug Curve 3KA216ME4S Ground Trip Timing Plug Curve 4KA216MESS Ground Trip Timing Plug Curve 5KA216ME6S Ground Trip Timing Plug Curve 6KA216ME7S Ground Trip Timing Plug Curve 7KA216ME8S Ground Trip Timing Plug Curve 8KA216ME9S Ground Trip Timing Plug Curve 9KA216M E11S Ground Trip Timing Plug Curve 11KA216ME13S Ground Trip Timing Plug Curve 13KA216ME14S Ground Trip Timing Plug Curve 14KA216ME15S Ground Trip Timing Plug Curve 1SKA216ME16S Ground Trip Timing Plug Curve 16KA216ME17S Ground Trip Timing Plug Curve 17KA216ME18S Ground Trip Timing Plug Curve 18KA216MEKS Ground Trip Timing Plug Curve KKA217MEAS Phase Trip Timing Plug Curve AKA217MEBS Phase Trip Timing Plug Curve BKA217MECS Phase Trip Timing Plug Curve CKA217MEDS Phase Trip Timing Plug Curve DKA217MEES Phase Trip Timing Plug Curve EKA217MEFS Phase Trip Timing Plug Curve FKA217MEGS Phase Trip Timing Plug Curve GKA217MEHS Phase Trip Timing Plug Curve HKA217MEJS Phase Trip Timing Plug Curve JKA217MEKS Phase Trip Timing Plug Curve KKA217MELS Phase Trip Timing Plug Curve LKA217MEMS Phase Trip Timing Plug Curve MKA217MENS Phase Trip Timing Plug Curve NKA217MEPS Phase Trip Timing Plug Curve PKA217MERS Phase Trip Timing Plug Curve RKA217METS Phase Trip Timing Plug Curve TKA217MEVS Phase Trip Timing Plug Curve VKA217MEWS Phase Trip Timing Plug Curve WKA217MEXS Phase Trip Timing Plug Curve XKA217MEZS Phase Trip Timing Plug Curve ZKA243MEXXXS Phase Min Trip Resistor 100,120,140,170,

200, 240, 280, 300, 340, 400, 480, 560, 600,680, 800, 960, or 1120 Amp Yellow Label forall Reclosers Except ME and VSMT.Change XXX in Catalog No. to Amps.Ex: KA243ME280S

KA244ME10SS Low Ground Min Trip Resistor 10 Amp YellowLabel for all Reclosers Except ME andVSMT

KA244MEXXXS Ground Min Trip Resistor 25, 35, 50, 70,100,120,140,170, 200, 240, 280, 340, 400, 480,or 560 Amp Yellow Label for all ReclosersExcept ME and VSMT. Change XXX inCatalog No. to Amps. Ex: KA244ME140S

KA244ME5.8S Low Ground Min Trip Resistor 5.8 AmpYellow Label for all Reclosers Except MEand VSMT

KA275MEXXS Reclosing Delay Single Value, INST. or 60Sec. Change XX in Catalog No. to INST.Ex: KA275MEINST

KKA301MEXXXS Phase Min Trip Resistor 200, 240, 280, 340,400, 480, 560, 600, 680, 800, 960,11201200,1360 1600 1920 or 2240 Amp BlueLabel for ME and VSMT Reclosers only.Change XXX in Catalog No. to Amps.Ex: KA301ME800S

KA302MEXXXS Ground Min Trip Resistor 100,140, 200, 240,280, 340, 400, 480, 560, 680, 800, 960, or1120 Amp Blue Label for ME and VSMTReclosers only. Change XXX in CatalogNo. to Amps. Ex: KA3O2MES60S

KA101SMES Reset Delay Multiple Value Plug IncludingSettings for 1015, 30, 45, 60, 90,120 and180 Seconds

KA1016MES Reclosing Delay Multiple Value Plug IncludingSettings for 1,2,5,7,10,15,30 and 45 Seconds

Page 39: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

39

TABLE 16Type ME Control Circuit Boards and Control CablesForm 2 (Above S/N 1900),Form 3 (Above S/N 4000,Form 3A (Above S/N 26000)

TABLE 17Type ME Control Replacement Parts and AccessoriesForm 2 (Above S/N 1900),Form 3 (Above S/N 4000),Form 3A (Above S/N 26000)

Catalog No. Description

KA1ME7 Control Cable, 7 Ft. All ReclosersKA1MEXX Longer Control Cable: 8 Thru 80 Ft. for RVE RXE

VWE, VWVE, WE, WVE Reclosers. 8 Thru 19 Ft.for CXE, ME, VSA, VSAT, VSML, VSMTReclosers. Replace XX With Length.

KA18ME20 Control Cable, 20 Ft. for CXE, ME, VSA, VSAT,VSML, VSMT Reclosers

KA18MEXX Extra Long Control Cable: 81 Thru 125 Ft. forRVE, RXE, VWE, VWVE, WE, WVE Reclosers.20 Thru 35 Ft. for CXE, ME, VSA, VSAT, VSML,VSMT Reclosers. Replace XX With Length.

KA251 ME Phase Trip No. 1 Circuit Board for Form 2KA252ME Phase Trip No. 2 Circuit Board for Form 2KA253ME Ground Trip No. 1 Circuit Board for Form 2KA254ME Ground Trip No. 2 Circuit Board for Form 2KA255ME Output Circuit BoardKA256ME Diode Circuit Board for Form 2KA257ME Battery Charging Circuit Board for Form 2KA267ME Reclose and Reset Circuit Board for Form 2

Catalog No. Description

KA381MES Reclose and Reset Circuit Board for Form 3and 3A

KA382MES Diode Circuit Board for Form 3 and 3AKA383MES Output Circuit Board for Form 3 and 3AKA384MES Ground Trip No. 2 Circuit Board for Form 3 and 3AKA385MES Ground Trip No. 1 Circuit Board for Form 3 and 3AKA386MES Phase Trip No. 2 Circuit Board for Form 3 and 3AKA387MES Phase Trip No. 1 Circuit Board for Form 3 and 3AKA388ME1S Battery Charging Circuit Board for Standard

Charger on Form 3 and 3A Below 53381KA388ME2S Battery Charging Circuit Board for Dual Rate

Charger on Form 3 Above 5500 and Form 3AKA1103ME Tie Board for Form 3AKA1109ME8 120-Vac Ballast and Surge Card for Fixed or

Temperature Regulated Battery ChargerKA1L00ME9 240-Vac Ballast and Surge Card for Fixed or

Temperature Regulated Battery ChargerKA1172ME Temperature Regulated Battery Charging Board

for Form 3A

Catalog No. Description

KA107LS1 Relay AssemblyKA107LS2 Relay AssemblyKA234ME1 Ground Matching Transformer (1 Per Control)KA250ME Tie Board for Form 2KA279ME Phase Matching Transformer (3 Per Control)

Form 2 and 3KA287ME5S 24-Vdc Supply Adapter Accessory for Form 3,

from 5501 Thru 25999KA287ME6S 24-Vdc Supply Adapter Accessory for Form 3A

Above 26000KA290ME1 Selector Switch and Wire Pistol Grip Form

2 and 3KA293ME2 Load Current Indicator Accessory Form 3,

Above 5500KA304ME1 Reset After Successful Reclose Accessory for

Form 2, Below 1900KA304ME4 Reset After Successful Reclose Accessory for All

Form 3 ControlsKA316ME2S Remote Closing Accessory for Form 2, 1900

and AboveKA316ME4S Remote Closing Accessory for Form 3,

Above 5500KA325ME2 Adapter Accessory for Form 3 Control to Form 1

RecloserKA333ME7 Blocking of Reclosing Accy. When Deenergized

for 120-Vac for Form 3 Above 5500 to 26000KA333ME8 Blocking of Reclosing Accessory When

Energized for 12O-Vac for Form 3, Above 5500to 26000

KA333ME9 Blocking of Reclosing Accessory WhenDeenergized for 240-Vac for Form 3, Above5500 to 26000

KA333ME10 Blocking of Reclosing Accessory WhenEnergized for 240-Vac for Form 3, Above 5500to 26000

KA333ME11 Block of Reclosing Accy.—120-Vac WhileDeenergized, for F3A 26000 and Above

KA333ME12 Block of Reclosing Accy.—120-Vac WhileEnergized, for F3A 26000 and Above

KA406ME Input Plug and Wire Harness for Form 2KA410ME Tie Board for Form 3KA418ME3 Sequence Coordination Accessory for Form 3,

Below 5500KA418ME7S Sequence Coordination Accessory—for Form 3

5501-25999 and Form 3A, Above 26000KA423MES Circuit Board—for Remote Closing AccessoryKA450ME2S Battery—24V, for Form 3 and 3AKA452ME Control Counter Assembly Form 1 2, 3 and 3AKA458ME3 Battery Charging Accessory 115-Vac for Form 3,

from 5501 Thru 25999KA458ME4 Battery Charging Accessory 230-Vac for Form 3

from 5501 Thru 25999

Catalog No. Description

KA472ME3S Lockout Indicating Contact Accy.—for Form 3Above 5500 and Form 3A

KA514ME1 Phase Trip Protection Accessory—1 RequiredPer Control for Form 2, 1615 and Above; forForm 3 Below 4100; Obsolete

KA531ME3S Fuse Elimination Accessory for Form 2, 1900 andAbove, Form 3 and Form 3A

KA544ME1S Heater Element Oniy 120-Vac 100-85FKA544ME2S Heater Element Only 240-Vac 100-85FKA544ME3S Heater Element only 120-Vac 60-15FKA544ME4S Heater Element Only 240-Vac 60-15FKA578MES Potential Battery Charger—for Form 3 onlyKA609ME1 Target Accessory—With Indicating Buttons,

Phase Trip only for Double Size Cabinet, forForm 3 Below 5500; obsolete

KA614ME1 Control Cable Locking SleeveKA638ME1S Battery Test Voltmeter Portable TypeKA639ME3S Remote Lockout Accessory for Form 3 Above

5500 and Form 3AKA641 ME500 Single CabinetKA642ME500 Double CabinetKA682ME1 Standard Input Plug Board and Harness Form 3KA684ME Battery ConnectorKA689ME920 Ground Trip Sequence Selector Switch Form 2

and 3KA703ME Battery (Gould) for Form 1—ObsoleteKA710ME2 Battery Adapter Kit for Connection of Form 2

Battery to Form 3 Control, Male ReceptacleKA710ME3 Battery Adapter Kit for Connection of Form 3

Battery to Form 2 Control, Female ReceptacleKA712ME3 24-Vdc Supply Adapter Accy. for Field

Installation for Form 3, Below 5500KA712ME4 24-Vdc Supply Adapter Accessory for Field

Installation for Form 3, 5500 and AboveKA713ME1 Field Kit for Thermostatic Heater With Surge

Protection 115-Vac, for 1900 to 12250KA713ME2 Field Kit for Thermostatic Heater with Surge

Protection 23O-Vac, for 1900 to 12250KA713ME3 Field Kit for Thermostatic Heater with Surge

Protection and Fuse Disconnect 115-Vac, fromS/N 12250 to 26000

KA713ME4 Field Kit for Thermostatic Heater With SurgeProtection and Fuse Disconnect 230-Vac, fromS/N 12250 to 26000

KA713ME5 Field Kit for Thermostatic Heater 120-Vac, 85/100Degree F. Above 26000

KA713ME6 Field Kit for Thermostatic Heater 120-Vac,15/60 Degree F; Above 26000

KA713ME7 Field Kit for Thermostatic Heater 240-Vac,85/100 Degree F; Above 26000

KA713ME8 Field Kit for Thermostatic Heater 240-Vac,15/60 Degree F; Above 26000

Page 40: Form 3-3A ME Control Basic Maintenance Information

Catalog No. Description

KA1037ME6S Instantaneous Trip—Phase and Ground. PhaseMultiple of 1.4, 2.0, 2.8, 4.0 or 5.6; GroundMultiple of S.6, 8.0, 11.2, 16.0, or 22.4

KA1037ME7S Instantaneous Trip—Phase and Ground, PhaseMultiple of 5.6, 8.0, 11.2, 16.0, or 22.4: GroundMultiple of 1.4, 2.0, 2.8, 4.0, or 5.6

KA1037ME8S Instantaneous Trip—Phase and Ground, BothWith Multiples of 5.6, 8.0, 11.2, 16.0, or 22.4

KA1102ME1 Standard Input Plug Board and Harness forForm 3A

KA1103ME Tie Board, Form 3AKA1109ME8 Standard Charger Board—120-Vac, F3A OnlyKA1109ME9 Standard Charger Board—240-Vac, F3A OnlyKA1134ME1S Automatic Resetting Fault Indicator Circuit BoardKA1137ME1S Annunciator—Type Target Accessory—Auto

Reset, Phase only; Above 14450KA1137ME2S Annunciator—Type Target Accessory—Auto

Reset, Phase and Ground; Above 14450KA1141ME1 Selector Switch and Wire Pistol Grip, Form 3A

onlyKA1142ME3 Shelf Battery Charger, PortableKA1159ME Ground Trip Sequence Selector Switch—Form

3A onlyKA1160ME Operations to Lockout Sequence Switch—Al1

ControlsKA1163MES Minimum Response TimeKA1174ME1S Temperature Regulated Battery Charger Accy.—

120-Vac, for F3A 26000 and AboveKA1174ME2S Temperature Regulated Battery Charger Accy.—

240-Vac, for F3A 26000 and AboveKA1193ME Harness only for Standard Input Plug Board

for F3AKA1194ME1 Standard Input Plug Board only for Form 3AKA2003MES Remote Close With Cold-Load PickupKA2035ME2S Remote Non-Reclose and Ground Trip Block—

Maintained Contact, 24VKA2039ME1S Recloser Status—Without Indicator LampsKA2039ME2S Recloser Status—With Indicator LampsKA2047MES Battery Monitor—over 30-Vdc/Under 22-Vdc

IndicationKA2070ME1S Remote Close With Cold Load Pickup Remote

Lockout and Status—Without Indicator LampsKA2070ME2S Remote Close With Cold Load Pickup Remote

Lockout and Status—With Indicator LampsKA2071ME1S Remote Non-Reclose and Ground Trip Block—

Pulse Contact, 24VKA2072MES Battery Monitor—AnalogKA2189MES Remote Indication of Fault Target AccessoryKP457ME Mounting Strip (Conducting)KP483ME1 Trip Resistor ClampsKP509ME Mounting Strip InsulatingKP674ME1 Sequence Relay—for Form 3 and 3AKP884ME Circuit Board ShieldKP894ME1 Battery Mounting Bracket, Form 3 and 3AKP953ME Panel Locking SpringKP1077ME1S CoverKP1100ME Fuse Block Single SectionKP1110ME Fuse Block End Closure UnitKP1139ME1 Flip Disc Target—CompleteKP2069A4 Knob for Number of operations Selector

Switches (Ground, Phase or Lockout)KP2069A8 Manual Control Switch HandleKP2075A2 2 Amp Fuse—Type AGC, Glass Tube; Min.

Qty. 5KP2075A4 3/4 Amp Fuse, Type AGXKP2075A13 15 Amp Fuse—Type BAN, Fibre Tube; Min.

Qty. 5KP2075A18 3/8 Amp Fuse, Slow Blow Type MDQ, Min. Qty. 5KP2075A19 6 Amp Fuse, Type BANKP2080A1S Plastic Battery Connector—Male, Battery

ConnechonKP2080A2S Plastic Battery Connector—Female, Control

ConnectionKP4060A12 120 Volt Relay, 2 to 60 Sec.KP4060A22 28 Volt Relay, 2 to 60 Sec.KP4061A3 28 Volt Relay, 0.15 to 1.0 Sec.K721525105018A Screw—for Trip Resistors ClampsK999904310283A Bulb—24V, for Lockout Indicator

Type ME Electronic Recloser Control

40

TABLE 17Type ME Control Replacement Parts AcessoriesForm 2 (Above S/N 1900),Form 3 (Above S/N 4000),Form 3A (Above S/N 26000) (continued)

Catalog No. Description

KA716ME Reclosing Fuse Replacement KitKA719ME 120-Vac Surge Protection Field KitKA720ME 240-Vac Surge Protection Field KitKA721ME Battery Post Installation Kit, 4000 and AboveKA734ME1 48-Vdc Supply Adapter (AEP only 15 Amp)KA734ME2 125-Vdc Supply Adapter (AEP only 5 Amp)KA734ME3 125-Vdc Supply Adapter (AEP only 5 Amp)KA734ME4 48-Vdc Supply Adapter (15 Amp) from 5501 Thru

25999KA734ME5 125-Vdc Supply Adapter (15 Amp) from 5501

Thru 25999KA734ME6 125-Vdc Supply Adapter (15 Amp) from 5501

Thru 25999KA734ME10 48-Vdc Supply Adapter (15 Amp) 26000 and

AboveKA734ME11 125-Vdc Supply Adapter (5 Amp) 26000 and

AboveKA734ME12 125-Vdc Supply Adapter (15 Amp) 26000 and

AboveKA734ME13 48-Vdc Field Kit for DC Supply—15A 240-Vac

F3AKA734ME14 125-Vdc Field Kit for DC Supply—5A 240-Vac

F3AKA734ME15 125-Vdc Field Kit for DC Supply—15A 240-Vac

F3AKA735ME Battery Bracket Mounting Kit for GE Batteries in

Controls Below 15000KA736ME Conversion Kit to Cold Load Pickup from Form 3

to Form 3AKA741 ME4 Retrofit Kit for Replacing Demand Meters—With

Instantaneous Indicating Elements Below35909

KA741 ME5 Retrofit Kit for Replacing Demand Meters—Without Instantaneous Indicating Elements,Below 35909

KA746ME Battery—24V, for Form 2KA835ME901 Phase Trip Sequence Selector SwitchKA835ME902 Phase Trip Sequence Selector Switch—for Use

With Sequence Coodination AccessoryKA852ME2S Standard Heater—240VKA871ME2 Battery Charging Isolation TransformerKA1000ME1S Minimum Trip Doubler—Local Operation—

Phase onlyKA1000ME2S Minimum Trip Doubler—Local Operation—

Phase and GroundKA1002ME4S Minimum Trip Doubler—Remotely operatedKA1002ME5S Minimum Trip Doubler—Three Wire Control to

Double ReturnKA1004MES Remote Trip Accessory KitKA1021 ME4 Protective Accessory Field Kit for Ground Trip—

4000 to 50071, Supersedes KA921 ME4KA1021 ME5 Protective Accessory Field Kit for Phase Trip—

4000 to 50071, Supersedes KA921 ME5KA1021 ME6 Protective Accessory Field Kit for Phase and

Ground Trip—4000 to 50071, SupersedesKA921 ME6

KA1030ME2S Fault Indicator—Counter Type Phase andGround, Above 14450

KA1036ME1S Instantaneous Lockout—Phase only, Multipleof 1.4, 2.0, 2.8, 4.0, or 5.6

KA1036ME2S Instantaneous Lockout—Phase Only, Multipleof 5.6, 8.0 11.2 16.0 or 22.4

KA1036ME5S Instantaneous Lockout—Phase and Ground,Both With Multiples of 1.4, 2.0, 2.8, 4.0, or 5.6

KA1036ME6S Instantaneous Lockout—Phase and Ground,Phase Multiple of 1.4, 2.0, 2.8, 4.0 or 5.6;Ground Multiple of 5.6, 8.0, 11.2, 16.0, or 22.4

KA1036ME7S Instantaneous Lockout—Phase and GroundPhase Multiple of 5.6, 8.0, 11.2 1 6.0 or 22.4Ground Multiple of 1.4, 2 0, 2.8, 4.0 or 5.6

KA1036ME8S Instantaneous Lockout—Phase and Ground,Both With Multiples of 5.6, 8.0, 11.2, 16.0, or22.4

KA1037ME1S Instantaneous Trip—Phase only, Multiplesof 1.4, 2.0, 2.8, 4.0 or 5.6

KA1037ME2S Instantaneous Trip—Phase only, Multiplesof 5.6, 8.0, 11.2 16.0, or 22.4

KA1037ME5S Instantaneous Tr;p—Phase and Ground, BothWith Multiples of 1.4, 2.0, 2.8, 4.0 or 5.6

Page 41: Form 3-3A ME Control Basic Maintenance Information

S280-75-2

41

APPENDIX V

Schematic diagramsForm 2 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pages 42-43Form 3 Connections (below S/N 5500) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pages 44-45Form 3 Connections (S/N 5500-25999) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pages 46-47Form 3A Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pages 48-49

Page 42: Form 3-3A ME Control Basic Maintenance Information

Figure 54.Form 2 connection diagram (below S/N 1900). Since late Form 2 and early Form 3 controls share common circuits and design,this connection diagram is given for reference.

Form 2 Connections

42

Type ME Electronic Recloser Control

Page 43: Form 3-3A ME Control Basic Maintenance Information

Figure 54 - continued.

Form 2 Connections - continued

43

S280-75-2

Page 44: Form 3-3A ME Control Basic Maintenance Information

Figure 55.Form 3 connection diagram (below S/N 5500).

Form 3 Connections

44

Type ME Electronic Recloser Control

Page 45: Form 3-3A ME Control Basic Maintenance Information

Figure 55 - continued.

Form 3 Connections - continued

45

S280-75-2

Page 46: Form 3-3A ME Control Basic Maintenance Information

Figure 56.Form 3 connection diagram (S/N 5500 to 25999).

46

Type ME Electronic Recloser Control

Form 3 Connections

Page 47: Form 3-3A ME Control Basic Maintenance Information

Figure 56 - continued.

47

S280-75-2

Form 3 Connections - continued

Page 48: Form 3-3A ME Control Basic Maintenance Information

Figure 57.Form 3A connection diagram.

48

Type ME Electronic Recloser Control

Form 3A Connections

Page 49: Form 3-3A ME Control Basic Maintenance Information

Figure 57 - continued.

Form 3A Connections - continued

S280-75-2

49

Page 50: Form 3-3A ME Control Basic Maintenance Information

KRP1/01

P.O. Box 1640Waukesha, WI 53187www.cooperpower.com

©2002 Cooper Power Systems, Inc.Kyle® is a registered trademark of Cooper Industries, Inc.

Printed on Recycled Paper

Type ME Electronic Recloser Control