Casing Dimension Wiring Diagram Bracket Parameter Modes True RMS measurement Low set & High set Operation hour recording Fault & Trip LED indication Trip value recording (3 memory) Neutral current display THD-I display Last 30 mins. ampere demand Maximum ampere demand Selectable 6 IDMT graphs 2 output relays Auto shorting of CTs (when unplugged) Programmable software lock Selectable frequency (50 / 60 Hz) Flush mount features Current Setting ( I>) 20 ~ 200% (1% step) DTL 10 ~ 200% (1% step) IDMT High-set ( I ) OFF or 20 ~ 2000% (10% step) DTL/IDMT Time setting ( TMI or TI ) 0.05 ~ 20.0 sec. (0.1 sec. step) DTL 0.05 ~ 1.00 sec. (0.01 time multiplier step) IDMT High-set time ( TI ) 0.03 ~ 20.0 sec. (0.1 sec. step) DTL/IDMT Measurement True RMS Ampere Power supply AC 85 ~ 270 V / DC 100 ~340 V DC 16 ~ 36 V (model : D24n) Rated current ../5A (../1A upon request) Rated frequency 50 / 60 Hz (selectable) Relay operation level 1.10 x (IDMT), 1.0 x (DTL) Power Consumption 2 VA C.T. burden@5A 0.5 VA Tripping contact SPDT 5A / 240 VAC Weight ~ 520 g Operating temp. 0 o C ~ +55 o C Standard IEC : 61000-4-2/4-4/4-5/255-5:1 Enclosure Protection IP50 (dust protected) Case Material ABS resin complying with UL-94 VO (flame retardant) version 9.23 version 9.33 User Guide for model : TM-9200s-U240n-5A (DTL) TM-9300s-U240n-5A (IDMT) numerical based Over Current Relay All measurement in millimeters SIDE VIEW 98 98 92 92 Panel Cut-out 92 x 92 mm FRONT VIEW PANEL CUT-OUT Plug-in screw terminal 95 DELAB Wiring connection 35 mm wide DIN Rail mount TECHNICAL DATA SETTING RANGE Modes definition Technical Specification Technical data / Setting range Panel Description Overview / Button Functions SETTING mode description INFO SPECIAL SETTING MODE I > To set over current Characteristic I > Selectable IDMT curves TM I > or T I > To set trip time ( Time Multiplier ) I >> To set high set fault T I >> (sec) To set high set trip time Operation hr. Device operated in hours ( x 1000 hr. ) Trip mem.1 Most recent trip value Trip mem.2 Trip value before ( Trip mem.1 ) Trip mem.3 Trip value before ( Trip mem.2 ) Software lock Keypad lock : ON or OFF TripRelay K1 response type Latching or Non-latching Output relay K2 function Programmable relay output TripRelay K2 response type Latching or Non-latching Network frequency Selectable as : 50 Hz or 60 Hz Standby mode Running LED bar : ON or OFF mode (L1,L2,L3) LED ( Phase Indicator ) 3-digit display Display current measurement & informations (X 10) LED ( Lit when display value x 10 ) Fault LED Lit when fault is detected I trip LED Lit when fault is detected (low-set) I trip LED Lit when fault is detected (high-set) Cancel / Reset / Test button To undo parameter setting Reset device after trip Test trip (hold 5 secs.) Select, Set Auto, Manual, Cancel Single digit mode display Display mode selection, In default mode, the mode display is blank Down(-) button Set value decrement Select / Set button To display info or value To select mode To set or confirm parameter setting Up Down Up (+) button Set value increment Flashing decimal Indicate standby mode is active Also indicates seconds count (5 secs.= 5 flashes) on depress & hold button when access to special setting mode or test trip function 9 x 10 11 12 13 14 15 16 K1 K2 SUPPLY POWER Trip contact 1 3 5 7 8 L O A D N L3 L2 L1

for model : TM-9200s-U240n-5A TM-9300s-U240n-5A DELAB ... 2013.pdf · (refer to IDMT Graph) Select the desired IDMT curve using the [ Up / (+) ] or [ Down / (-) ] button. Newly selected

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

  • Casing Dimension

    Wiring Diagram

    Bracket

    Parameter Modes

    True RMS measurementLow set & High setOperation hour recordingFault & Trip LED indicationTrip value recording (3 memory)Neutral current displayTHD-I displayLast 30 mins. ampere demandMaximum ampere demandSelectable 6 IDMT graphs2 output relaysAuto shorting of CTs (when unplugged)Programmable software lockSelectable frequency (50 / 60 Hz)Flush mount

    features

    Current Setting ( I>) 20 ~ 200% (1% step) DTL

    10 ~ 200% (1% step) IDMT

    High-set ( I ) OFF or 20 ~ 2000% (10% step) DTL/IDMT

    Time setting ( TMI or TI ) 0.05 ~ 20.0 sec. (0.1 sec. step) DTL

    0.05 ~ 1.00 sec. (0.01 time multiplier step) IDMT

    High-set time ( TI ) 0.03 ~ 20.0 sec. (0.1 sec. step) DTL/IDMT

    Measurement True RMS Ampere

    Power supply AC 85 ~ 270 V / DC 100 ~340 V

    DC 16 ~ 36 V (model : D24n)

    Rated current ../5A (../1A upon request)

    Rated frequency 50 / 60 Hz (selectable)

    Relay operation level 1.10 x (IDMT), 1.0 x (DTL)

    Power Consumption 2 VA

    C.T. burden@5A 0.5 VA

    Tripping contact SPDT 5A / 240 VAC

    Weight ~ 520 g

    Operating temp. 0o C ~ +55o C

    Standard IEC : 61000-4-2/4-4/4-5/255-5:1

    Enclosure Protection IP50 (dust protected)

    Case Material ABS resin complying with UL-94 VO (flame retardant)

    version 9.23 version 9.33User Guide for model : TM-9200s-U240n-5A (DTL) TM-9300s-U240n-5A (IDMT)numerical based Over Current Relay

    All measurement in millimeters

    SIDE VIEW

    98

    98

    92

    92

    Panel Cut-out92 x 92 mm

    FRONT VIEW

    PANEL CUT-OUT

    Plug-inscrewterminal

    95

    DELAB

    Wiring connection

    35 mm wide DIN Rail mount

    TE

    CH

    NIC

    AL

    DA

    TA

    SE

    TT

    ING

    RA

    NG

    E

    Modes definition

    Technical Specification Technical data / Setting range

    Panel Description Overview / Button Functions

    SE

    TTIN

    G

    mode description

    INF

    OS

    PE

    CIA

    L S

    ETT

    ING

    MO

    DE

    I > To set over current

    Characteristic I > Selectable IDMT curves

    TMI > or TI > To set trip time ( Time Multiplier )

    I >> To set high set fault

    TI >> (sec) To set high set trip time

    Operation hr. Device operated in hours ( x 1000 hr. )

    Trip mem.1 Most recent trip value

    Trip mem.2 Trip value before ( Trip mem.1 )

    Trip mem.3 Trip value before ( Trip mem.2 )

    Software lock Keypad lock : ON or OFF

    TripRelay K1 response type Latching or Non-latching

    Output relay K2 function Programmable relay output

    TripRelay K2 response type Latching or Non-latching

    Network frequency Selectable as : 50 Hz or 60 Hz

    Standby mode Running LED bar : ON or OFF

    mode

    (L1,L2,L3) LED( Phase Indicator )

    3-digit displayDisplay currentmeasurement &informations

    (X 10) LED( Lit when display value x 10 )

    Fault LEDLit when fault is

    detected

    I trip LEDLit when fault is

    detected(low-set)

    I trip LEDLit when fault is

    detected(high-set)

    Cancel / Reset / TestbuttonTo undo parameter settingReset device after tripTest trip (hold 5 secs.)

    Select,Set

    Auto,Manual,Cancel

    Single digitmode display

    Display mode selection,In default mode,

    the mode display is blank

    Down(-) buttonSet value decrement

    Select / Setbutton

    To display info or valueTo select mode

    To set or confirmparameter setting

    Up

    Down

    Up (+) buttonSet value increment

    Flashingdecimal

    Indicate standbymode is active

    Also indicatesseconds count

    (5 secs.= 5 flashes)on depress & hold

    button when accessto special setting

    mode ortest trip function

    9 x 10 11 12 13 14 15 16

    K1 K2SUPPLYPOWER

    Trip

    con

    tact

    1 3 5 7 8

    LOAD

    NL3L2L1

  • How to do setting

    step

    step

    step

    Set over current IDMT curves Set time multiplier

    Setting Parameters

    Special Setting Modes

    IDMT Graph

    mode

    Mode displayIn default mode, themode display is blank

    Viewing Info

    Press [ Set ] to store new value and proceed to the next mode.

    Press [ Cancel ] button toexit mode or undo changes.

    All modes exit automatically if leftuntouched for more than 20 secs.

    Press [ Select ] button whilein default mode to access toparameter setting mode:

    To scroll thru modes, just press &release the [Select] button

    1

    2

    3

    User Guide for model : TM-9200s-U240n-5A / 9300s-U240n-5Aversion 9.32 version 9.33

    Press [ Up ] or [ Down ] buttonto adjust desire value

    For fast increment or decrement,press and hold the UP or Down button

    Manual ‘ test trip ’

    Manual test trip allows the user to test the device for any fault in tripping.To do a manual test trip, follow the instruction below:When NO mode is selected (mode display is blank),

    i) Press & hold [ Test ] button for 5 seconds.The mode display decimal will flash 5 times to indicate 5 seconds count.

    ii) Release the button when the display show :

    iii) Mode starts to count down from 5 and trips at zero. The display will show :

    To abort test when mode has not counted down to zero, press the [ Cancel ] button.

    Test device for fault in tripping

    0.1

    1.0

    10.0

    100.0

    1000.0

    1 10Overload Ratio (In/Is)

    Tim

    e (

    Se

    c)

    IDMTDTL

    Step by step instruction

    When mode display is blank, press[Select] button to acess toparameter setting mode.

    mode mode mode

    Modes

    Modes

    Time graph based onTime Multiplier 1.0

    Press [ Select ] until mode is displayed.Display will show the existing set value. (Range : OFF or 20 ~ 2000 %)Select the desired value using the [ Up / (+) ] or [ Down / (-) ] button.Newly selected value will flash. Press [ Select ] to store / confirm new value and advanceto mode or press [ Cancel ] to undo changes.

    Press [ Select ] until mode is displayed.Display show : (Disabled -> Mode 4 is set to OFF)When mode 4 is not set to OFF :-Display will show the existing set value (Range : 0.03 ~ 20.0 sec.)Select the desired value using the [ Up / (+) ] or [ Down / (-) ] button.Newly selected value will flash. Press [ Select ] to store / confirm new value and advanceto mode or press [ Cancel ] to undo changes.

    Press [ Select ] once to enter mode .Display will show the existing set value (%). (Range : 20~200 DTL / 10~200 IDMT)Select the desired over current value using the [ Up / (+) ] or [ Down / (-) ] button.Newly selected value will flash. Press [ Select ] to store / confirm new value and advanceto mode or press [ Cancel ] to undo changes.

    Press [ Select ] until mode is displayed.Display will show the existing set value. (refer to IDMT Graph)Select the desired IDMT curve using the [ Up / (+) ] or [ Down / (-) ] button.Newly selected value will flash. Press [ Select ] to store / confirm new value and advanceto mode or press [Cancel] to undo changes.

    Press [ Select ] until mode is displayed.Display will show the existing set value. (0.05~20.0 / 0.05~1.0 time-multiplier)Select the desired value using the [ Up / (+) ] or [ Down / (-) ] button.Newly selected value will flash. Press [ Select ] to store / confirm new value and advanceto mode or press [ Cancel ] to undo changes.

    No Flash > phase did not cause tripping Flash Once > phase cause a low-set trip Flash Twice > phase cause a high-set trip

    Modes

    Press [ Select ] until mode is displayed.Press [ Select ] button again each time to view individual tripped memory for: mode > phase L1, L2, L3 (most recent tripped value) mode > phase L1, L2, L3 (tripped value before mode A) mode > phase L1, L2, L3 (tripped value before mode b)To exit, press [ Cancel ].

    Reset Trip Memory

    Press [ Select ] button until mode [A] is displayed.

    If the display show ( NO tripping has occurred ), no resetting is required.If the display show a certain value ( tripping has occurred ), then follow the steps below:-

    Press [ Cancel ] button and hold for 3 seconds in current mode -> mode (The mode display decimal will flash 3 times to indicate 3 seconds count)

    The display will reset to show . To exit, press the [ Cancel ] button.

    Reset recorded trip memories ortotal trip count

    Up / Downbutton

    To adjust value

    Select / Setbutton

    To select mode& to set

    parameter

    Up

    Down

    CancelbuttonTo exit mode orundo changes

    Select,Set

    Auto,Manual,Cancel

    Characteristics ( IE )Normal Inverse 3.0 /10Normal Inverse 1.3 /10Very Inverse

    Extremely InverseExtremely Inverse (0.64 sec)

    Long Time Inverse Definite Time

    User can lock the keypad on the device to avoid unauthorized or accidentaladjustment to the settings and to do special settings.When NO mode is selected (mode display is blank),

    i) Press [ Select ] and [ Cancel ] button simultaneously and hold for 5 seconds.ii)Press [ Up / (+) ] or [ Down / (-) ] button to select or modifyiii) Press [ Set ] button to confirm and proceed to next mode

    Software keypad lock: Parameters modification : Allowed: Parameters modification : Not Allowed

    Trip relay K1 response type: Latching trip signal: Non-Latching trip signal

    Output relay K2 function: Tripping output (Lc or nLc ): Low-set fault start signal output (nLc): High-set fault start signal output (nLc): Any fault start signal output (nLc)

    : Device failure output: Circuit breaker failure output (Lc or nLc): Alarm output (nLc)

    K2 response type: Latching trip signal: Non-Latching trip signal: Not Available

    Standby option

    : De-activate : ActivateA flashing decimal on the mode display indicate standbymode is enable. After about 3 minutes of idle and noleakage is detected, running LED bar will be displayedinstead of the real time leakage current. Stanby modeautomatically exits on leakage detection or when anybutton is depressed. When device trips, standby mode istemporary de-activated until device is reset.Alternatively, simply press [Cancel] button when poweringup the device to activate or de-activate standby function.

    After Stanby mode, the display will show : .Press [Set] to confirm all of the above settings or press[Cancel] to go back one previous mode.Press & hold [Cancel] for 3 seconds to exit and abort themodification without saving (previous setting unchanged).New setting only takes effect when [Set] button is pressedduring is displayed.

    Electrical network system frequencyElectrical network frequency setting: = 50 Hz = 60 Hz

    Press [ Select ] until mode to view the total operation hours.To view : THD & Amp Demand, press & hold [ Select ] for 2 secs.Press [select] again each time to view THD for individual phase ( L1 , L2 , L3 ).After phase L3 is viewed, pressing [Select] will display the Amp Demand,

    (last 30 mins demand) for phase L1. Press [Select] again to view phase L2 & L3.After phase L3 is viewed, pressing [Select] will display the

    (maximum demand) for phase L1. Press [Select] again to view phase L2 & L3.After phase L3 is viewed, pressing [Select] will go to mode or press [Cancel] to exit.

    I (%) CharIE TMI or TI

    I > : To set over current (%)

    Char IE : To select IDMT curves

    TMI or TI : To set Trip Time

    I : To set High-set over current (%)

    TI : To set High-set trip time (sec.)

    View operation hour x 1000 / THD / Amp Demand

    View trip memory : 3 tripping memories