TABLEOFCONTENTSSl.No. Item Page
1 Preamble 1
2 Part1Scope(Sections1To27) 14
3
Part2
Consultancy
Services
Including
That
Of
Fire
Protection
Experts
/Specialists
And
Submittal Requirements For Obtaining Building Permit, Completion Certificate And
ApprovalsRelatedTheretoAndShopDrawingApprovals&FitOutWorksRequirements)
(Sections1To5)
4
5
4 Part3RiskAssessmentStudyandFireRiskAssessmentRequirements(Sections1To4) 57
5 Part4BuildingFireProtectionDesignfeatures&LifeSafetyRequirements(Sections1To
16)
716
6 Part 5 Miscellaneous (Sections 1 To 30) dealing with (1) Criteria for storage
configuration for JAFZAPBUs/LIUs,(2)HazardousAreaProtectionconcerningAssembly
Occupancies,Hotels andDormitories, (3) Building Rehabilitation, (4) SafeguardsDuring
Construction,(5)Temporarybuildings,facilitiesorstructuresatconstructionsitesforthe
useof
offices
and
labour
accommodation,
(6)
Covered
temporary
structures
Enclosed
tentsnormallyusedforevents/activitiessuchasstageshows,concerts,circus,exhibitions,
tradefairs,sportingevents&celebratoryfunctions,(7)Marinas&Boatyards,(8)Marine
Terminals, Piers and Wharves, (9) Quality Assurance During Construction, (10)
Performance BasedDesign (PBD), (11) Standby Power, (12) Basements, (13) Electrical
Services/Systems,(14)MechanicalSystems,(15)AirConditioning,VentilationandSmoke
Management Systems , (16) Transformers, (17) Stationery Combustion Engines, Gas
Turbines&Generators,(18)GasService,(19)InformationTechnologyFacilities,(20)Utility
Rooms,ShopAreas&IncidentalusePhases,(21)TrashDumpsters,(22)Laboratories,(23)
Flammable&Combustible liquids, (24)AnimalHousingFacilities, (25)CollectionStorage
Facilities, (26) Sign Boards and Name Plates for company premises, (27) Lightening
Protection, (28) Mission Critical Facilities, (29) Fitout works /TIE IN Connections of
Sprinklers,Standpipes,
Fire
Pumps
and
Fire
Alarm
Systems
in
Retails
&
Car
park
extensions
and(30)Approvaloflistedfireproducts,equipment&systems.
1622
7 Part6Plans/FireLayoutDrawingsSubmittalRequirements(Sections1To2) 2224
8 Part7 FirePreventionRequirements(Sections1To18) 2427
9 Part8Fire/EmergencyControlRequirements(Sections1To21) 2730
10 Part9CertificationAndApprovalrequirements (Sections1To2) 30
11 Part10Definitions 30
12 Appendix1ListOfActivitiesPermittedToBeCarriedOutInZoned/SectoredAreasOf
PCFC/JAFZ.
31 33
13
Appendix 2
Submittal
Requirements
For
Obtaining
Building
Permit,
Completion
CertificateAndApprovalsRelatedThereto.
34
37
14 Appendix3Fire&ExplosionIndexAndToxicityIndex 3839
15 Appendix4SubmissionofReportonFireProtection&LifeSafetyFeatures 4041
16 Appendix5FireProtection/FireSafetyGuidelinesforDesigningHighRiseBuildings 4243
17 Appendix6RequirementsConcerningFireDepartment VehicleAccess 4445
18 Appendix7DimensionalCriteriaConcerningFireEscapeStairs,ExitWidthsEtc. 4648
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
3/167
- 2 -
19 Appendix8OccupantLoadFactor 49
20 Appendix9CommonPath,DeadEndAndTravelDistanceLimits 50
21 Appendix10CriteriaForStorageConfigurationForJAFZPBUs/LIUs 51
22 Appendix11SafeguardsagainstFires&ExplosionsduringConstruction 5254
23 Appendix 12 Requirements For Temporary Buildings, Facilities Or Structures At
ConstructionSites
For
The
Use
Of
Offices
&
Labour
Accommodation
5556
24 Appendix13EHSFireDeptRequirementsForCoveredTemporaryStructuresEnclosed
Tents Normally Used For Events/Activities Such As Stage Shows,
Concerts,Circus,Exhibitions,TradeFairs,SportingEvents&Celebratory
Functions.
5758
25 Appendix14AirConditioning,Ventilation&SmokeManagementSystems 5961
26 Appendix15MechanicalSmokeControlSystemSubmittalRequirements 6263
27 Appendix16RequirementsForDesign,Installation,Testing,Certification&Maintenance
ofLPG/LNGInstallation.
6465
28 Appendix17 RequirementsForLightningProtectionSystem 6667
29 Appendix18 FireTrainingRequirements 68
30 Appendix19 AvoidanceOfFalseAlarmsFromAutomaticSmokeDetectors 69
31 Appendix20BuildingCompletionFireAlarmSystemTestCertificateFormat 7072
32 Appendix21BuildingCompletionFireProtectionSystemTestCertificateFormat 7376
33 Appendix22BuildingCompletionSmokeExhaustSystemTestCertificateFormat 7779
34 Appendix23BuildingCompletionStairwellPressurizationSystemTestCertificate
Format
8082
35 Appendix24BuildingCompletionFeaturesofConstructionTestCertificateFormat 83
36
Appendix25
Building
Completion
Installation
of
Fire
Rated
Doors
Test
Certificate
Format
84
37 Appendix26BuildingCompletionFireSeal/StopsFormat 85
38 Appendix27DocumentsSubmissionSchedule(MEPServices) 86
39 Appendix28RequirementsforDesignofFireWaterPumps 87
40 Appendix29RequirementsforDesignofWaterTankFireWaterPumpRoom 88
41 Appendix30RequirementsforDesignofPipes&ValvesFireWaterService 8990
42 Appendix31RequirementsforDesignofFire&SmokeControlDoors 9192
43 Appendix32RequirementsforDesignofElevatorsasperNFPA101 93
44
Appendix 33
Specification
for
Pillar
Hydrants
94
45 Appendix34SpecificationforUndergroundHydrants 95
46 Appendix35 RequirementsforPortableFireExtinguishers 96
47 Appendix36RequirementsforInstallationofFireAlarmSystems 9798
48 Appendix37RequirementsforApplication,Installation,Location,Performanceand
MaintenanceofFireAlarmSystem
99100
49 Appendix38 RequirementsforDesign,Installation&TestingofCleanAgent 101102
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
4/167
- 3 -
ExtinguishingSystem
50 Appendix39RequirementsforDesign,Installation&TestingofStandpipeAndHose
System
103104
51 Appendix40RequirementsforDesign,Installation&TestingofSprinklerSystem 105106
52 Appendix41RequirementsforDesign,Installation&TestingofHydrantSystem 107
53
Appendix42
Requirements
for
Design,
Installation
&
Testing
of
Water
Mist
System
108
54 Appendix43 Requirements forDesign,Installation&TestingofSmoke&Heat
VentilationSystem
109
55 Appendix 44 BasicGuidelines for Sequence ofOperations for Life Safety Systems in
HighRiseBuildings
110
56 Appendix45 ChecklistforFireProtectionPlanGeneralSubmittalRequirements 111113
57 Appendix46 ChecklistforBusinessOccupanciesNew&ExistingGeneralSubmittal
Requirements
114124
58 Appendix47 Checklist forApartmentBuildingsNew&ExistingGeneral Submittal
Requirements
125136
59 Appendix 48 Checklist for Warehouses New & Existing General SubmittalRequirements
137144
60 Appendix 49 Checklist for Fire Alarm NFPA 72 Systems General Submittal
Requirements
145146
61 Appendix50 ChecklistforFireSprinklersNFPA13SystemsGeneralSubmittal
Requirements
147148
62 Appendix 51 Checklist for Fire Pumps NFPA 20 Systems General Submittal
Requirements
149151
63 Appendix52RequirementsforTemporaryBuildings,Structures&Usesattheareassuch
asTheWorldIslands
152154
64 Appendix53RequirementsforCollectionStorageFacilities 155 157
65 Appendix54ListofOffences 158161
66 Appendix55 DefinitionsOfTerms,Acronyms&Abbreviations 162 163
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
5/167
- 1 - - 1 -
FIRE PROTECTION, FIRE PREVENTION & FIRE/EMERGENCY CONTROL
REGULATIONS(Preamble)
A)These regulations supersede and repeal the ones embodied in Planning &Construction Regulations for Control of Commercial Developments in Jebel
Ali Free Zone Building And General Civil Work Construction Regulations
Third Edition 2003 (Chapter 11). They are now published separately as
part of Health, Safety and Fire Regulations; and hence shall be read in
conjunction with all relevant provisions [concerning overall authority of
Trakhees/EHS Division, sanctions & penalties and enforcement etc] of the
latter.
B)These regulations provide fire protection planning, design, construction,sustainment, restoration and modernization criteria. They will be
periodically reviewed, updated and made available to users as part of EHS-
Fire Depts responsibility for providing fire protection criteria &
requirements to developers / lessees / licencees.
C)These regulations are distributed electronically through websites:www.trakhees.ae; www.ehss.ae
D)These regulations, having the force of law, are effective from the date ofissuance of their current (2010) electronic version / edition; and all
stakeholders are obligated to comply with them strictly.
E)Currency of hard/paper copies of these regulations shall be ensured by wayof doing minute checks against their current electronic version.
Part1
-Sections
1
to
27
(Scope)
1. Theprovisionsoftheseregulationsestablishminimum fireprotectionrequirements/prescriptivecriteria for
buildings,facilitiesorstructureswithinTrakhees/Ports,Customs&FreeZoneCorporation(PCFC)jurisdiction.
Therequirements/criteriareflecttheneedfortheprotectionoflifeandpropertywhiletakingintoaccountthe
assessed risksassociatedwith thebuildings, facilitiesor structures, theircontentsand*permittedactivities.
(*Refer to Appendix1) and quality assurance includingmanagement of changes (refer to guideline notes
followedbysection27)andsafeguardsbefore,duringandafterconstruction.
2. Theprovisionsshallbeapplicabletoallnewandalltypesofexistingbuildings,facilitiesorstructuresandtheircontents and permitted activities whether considered permanent or temporary, mobile & stationary
equipment,waterfrontfacilitiesandshoreprotectionforshipswithinTrakhees/PCFCjurisdiction.
3. The provisions shall also be applicable to construction, alteration, repair, equipment, use and occupancy,
maintenance,relocation&demolitionofanybuilding,facilityorstructureoranyappurtenancesconnectedor
attachedtosuchbuildings,facilitiesorstructureswithinTrakhees/PCFCjurisdiction.
4. Theprovisionsprimarilyaddressthoseconstruction,protectionandoccupancyfeaturesnecessarytominimize
dangertolife&property.
5. Allprovisionsarebasedalmoston functional requirementsanddonotencompassdetaileddimensionaland
technicalspecifications.
6. Theprovisionsaremandatory.Also,allrequirementsplacedhereunderateveryGuidelineNotesandtheones
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
6/167
- 2 - - 2 -
containedinAppendicestotheseregulationsaremandatorywithrelationtotheprincipalmattertowhichthey
standasrequirements.
7. Theprovisionsshallbeusedconsistentlyasamandatoryreferencedocumentforthedevelopmentofdetaileddocuments (including scope,basisofdesign, technical requirements,plans,designdrawings&specifications
etc.)bytheconsultingservices,includingthatoffireprotectionexperts/specialists,hiredbythestakeholders.
Theprovisionsshallnotbeusedinlieuofdetaileddocumentsthatarerequiredtobesodeveloped.
8. Trakhees/PCFChasadoptedbyreferenceNationalFireProtectionAssociation(NFPA)USAanditscompanion
Codes,standardsandpublicationsincludingtheirofficialdefinitions,forapplicationoftheirprescriptivedesign
criteria / requirementswithin Trakhees / PCFCjurisdiction. Accordingly, relevant provisions of themost
currentNFPAcodes&standardsshallapplynormallytotheextentasprescribed.
9. AHJ: (a) The term AuthorityHaving Jurisdiction (AHJ) as used inNFPA codes, standards and publications
referenced intheseregulations indicatestheofficeofresponsibility i.e.EHSFireDepartment,asrepresented
by itsofficers includingVicePresident/ChiefFireOfficerandhisdeputy forenforcing (i)therequirementsof
NFPAanditscompanioncodes,standardsandpublications(ii)provisionsoftheseregulations(iii)requirements
of EHSFireDepartment and (iv) applicable statutes and regulations ofUAE /DubaiGovernment; andVice
President / Chief Fire Officer of EHSFire Dept is the person who is ultimately responsible to Trakhees /
PCFC/EHSmanagementfortheenforcementoftheforegoingrequirements,statutes,rules®ulationsand
forthedeliveryof fire,nonfireandemergencymedicalservices(i.e.ambulanceservices inaccordancewith
DubaiGovernmentprotocol)withintheoptimumcapabilitiesofavailable resources. (b)VicePresident/Chief
FireOfficer,cantherefore,reverse,rescindormodifyanyapproval(s)/decision(s)takenandcommunicatedbyanyofficerbelowhisrankincasesuchapprovalordecisionissubsequentlyfoundtobeerroneousontheface
oftherecord. Nopartyshallbeentitledtothebenefitsofanysucherroneousapprovalordecision&(c)Inthe
event that a conflict arises on a code application, Vice President / Chief Fire Officer shall make the
determinationsonequivalencies,variancesandwaiversasapartofhiscodeinterpretation/administration/
enforcement responsibilities. All such decisionsmade by him shall be final and binding for the concerned
stakeholders.
10.Certainrequirementsandrecommendations[thatmaynotbecovered inNFPAcodes/publications/standards]
thatarenecessarilyrecommendedbytheEHS FireDepartmentonacasebycasebasisshallbecompliedwith
notwithstandingmerecompliancewithNFPAcodes/publications/standards.
11.Inthe
event
of
any
conflict
between
the
text
of
the
references
cited
herein
in
regard
to
NFPA
and
its
companion codes, standards andpublications, the textof the relevantandapplicable codes, standards and
publicationsshalltakeprecedence.
12.Omission of any specific references or cross references, in regard to any NFPA and its companion codes,
standardsandpublications,shallnotrelievethestakeholdersoftheirobligationtocomplyingwithsuchcodes,
standardsandpublicationshavingregulatoryjurisdictioneffectandforce.
13.Wherethesituationandthecontextwarrants,thestakeholders,includingtheconsultants,shallbeobligatedto
gathertheexplicitinterpretationofthewordsofanyprovisionsoftheseregulationsfromEHSFireDept/AHJ
andnot fromwhat theyprofess it tobewhen theyhave translated their selfassumptionor intention into
requirements.
14.Where appropriate relevant and current statutes and regulations of UAE/Dubai Governments shall be
applicable.
15.Equivalencies: (a) Equivalencies to any established prescriptive criteria of NFPA and its companion codes,
standardsandpublications,theprovisionsoftheseregulationsmaybeapprovedbytheEHSFireDept/AHJ,if
thealternativefireprotectionengineeringdesignprovidesanequivalentleveloffireprotectionandlifesafety.
Writtenrequestsforapprovalshallincludejustification,hazardanalysis,criteriausedandotherpertinentdata
(b)Lackof fundsand timedeadlinesofprojects shallnotbeconsidered sufficientjustification fordeviation
fromtheestablishedcriteriarequirementsandprovisions& (c)Approvedequivalenciesandalternativesshall
only apply to the specific building, facility or structure involved in extraordinary case where no technical
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
7/167
- 3 - - 3 -
alternativesexist;andshallnotconstituteblanketapprovalforsimilarcases.
16.AbsenceofCriteria: (a)Whena specificapplication isnotcoveredby thecriteriaor theprovisionsofNFPA
codes, standards & publications; other international building codes, recognized industry standards and
standardengineeringpracticesshallbefollowedwithpriorandexpressapprovalofEHSFireDepartment/AHJ.
(b)WhereappropriatetheprovisionofSection 15(Equivalencies)shallapply.
17.Waivers: (a)Written request forwaiver to any established prescriptive criteria ofNFPA and its companioncodes,standardsandpublicationsorprovisionsoftheseregulationsshallbesubmittedtoEHSFireDept/AHJ
fordeterminationprior to commencementofbuilding constructions. The same shalldemonstrate that the
provisions,criteriaorrequirementscannotbetechnicallyexecuted,ortheirexecutionwillincreaseahazardor
createanewhazardandnotechnicalalternativesexist. Writtenrequestforwaiversshallincludejustification,
hazard analysis, alternatives considered and other pertinent data (b) Lack of funds and time deadlines of
projectsshallnotbeconsideredsufficientjustificationfordeviationfromtheestablishedcriteria,requirements
orprovisions&(c)Waivers,ifgivenexpresslybyEHSFireDept/AHJ,shallonlyapplytothespecificbuilding,
structure,facilityorprojectinvolvedandshallnotconstituteblanketapprovalforsimilarcases.
18.Insurance:Thestakeholdersarerequiredtohavetheir landsandpremises insuredagainstFire,ExplosionandPerils.
19.Existing buildings, facilities or structures: (a) Existing buildings, facilities or structures that meet therequirementsofNFPA101 forexistingoccupanciesdonothavetobemodified tocomplywithprovisionsof
these regulations, (b) Buildings, facilitiesor structures thatdonotmeet the requirementsofNFPA 101 forexisting facilitiesshallbebroughtup to,at least, theminimumrequirements, includingsprinklerretrofit, for
existing occupancies, (c) If the facility cannot be brought up to the minimum requirements for existing
occupanciesandarenovation,modernizationorrehabilitationproject isrequired,thatprojectshallmeetthe
requirements fornew construction as stipulated in these regulations.& (d) any changes inoccupancy shall
requirethebuilding,facilityorstructuretomeettherequirementsfornewconstructionforthenewoccupancy
asstipulatedintheseregulations.
20.SustainmentandRestoration:(a)Newworkaccomplishedinexistingbuildings,facilitiesorstructuresaspartof
repair, restoration and sustainment actions /projects shallmeet the requirements fornew constructionas
stipulated intheseregulations. Sustainmentandrestorationeffortsshall lookbeyondthescopeofworkto
ensurethatthefireprotection,including lifesafety,featuresarenotbeingcompromisedordesignedonlyfor
theportion
of
the
building,
facilities
or
structure
that
is
being
repaired
&
(b)
The
repair
project,
ifpossible,
shall
include a basis to support the entire building, facility or structure i.e. if considering providing a fire alarm
extenderpanel to theexistingantiquated firealarmcontrolpanel,ensure thepanelbeingprovidedhas the
capabilitytosupporttheentirebuildingfacilityorstructuresothatanyadditionalprojectscanutilizethenew
panelwithouthavingtoremovewhatwasjustinstalled.
21.Conversionofuse/changeofoccupancy:(a)Whenanyportionofabuilding,facilityorstructure ismodifiedfrom its current use to thatof an inhabited building, facility, structure forone year ormore, the building,
facility or structure shall meet the requirements for new construction as stipulated in these regulations.
Exampleswould include a warehouse (uninhabited) being converted to administrative (inhabited) use; an
inhabitedadministrativebuildingbeingconvertedto uninhabitedbuilding, facilityorstructure;or inhabited
building,facilityorstructurebeingaltered,modernized,modified,rehabilitatedorrenovatedandconvertedto
uninhabitedbuilding,
facility
or
structure
or
vice
versa
&
(b)
When
any
portion
of
abuilding,
facility
or
structure
ismodified from its currentuse toanyotheroccupancyuse for two yearsormore, thebuilding, facilityor
structureshallmeettherequirementsofnewconstructionasstipulatedintheseregulations. Changinggroups
of occupantswithin the occupancy classification does not constitute an occupancy change. An example of
modifying from one occupancy to another would include an office building converted tomercantile. An
exampleofchanginggroupsofoccupantswouldincludeaninstallationpersonnelfunctionoccupyingtheoffice
spaceformallyusedbyaninstallationcontractingfunction.
22.DurationofvalidityofFireDeptNOCforbuildingpermit: Iftheconstructionworkdoesnotcommencewithinsixmonthsof issueofNOC forbuildingpermit,a freshNOC is required tobeobtained;and theconcerned
stakeholdersshallbeobligatedtocomplywithnewrequirements, ifany,asmayberequiredbythecurrent
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
8/167
- 4 - - 4 -
changesincodes/regulations.Suchnewrequirementsshallbeincorporated/stipulatedinthefreshNOC.
23.Offences: Appendix 53 contains the list of offences againstwhich appropriate financial penalties shall be
imposed.
24.Accreditation: Accreditationoftheconsultants,contractors,designteammembersand installersofactive&passivefireprotectionsystems,equipment,materialsorproductsthroughcompetentthirdpartyismandatory.
25.Fakeandcounterfeitmaterials/products/equipment
(a) Theconsultantsandcontractors shallbesubject to the lawsofUAE& relevantTrakhees regulations for
supplyandinstallation ofthematerials/products/equipmentandcomponentsorpartsthereofthatare
not genuine, original or not suitable for the intended purpose. This includes but not limited to the
materials/ products/equipment that are defective, suspect or fake/counterfeit,
materials/products/equipmentthathavebeenprovidedunderfalsepretensesandmaterials/products/
equipmentthataremateriallyaltered,damaged,deteriorated°raded.
(b) Fire Dept reserves the right to rejectmultiple /cross listed and private labeledmaterials / products /equipment.
26.Precedence:Theseregulationsshalltakeprecedenceoveranyconflictingsituation.
27.If any section, subsection, sentence, clause of phrase of these regulations is, for any reasons, held to beunenforceableforanyreasonwhatsoever,itshallnotaffecttheremainingportionsoftheseregulations.
GuidelineNotes:
ChangeManagement
Efficiency,effectivenessorsatisfactoryperformancesofanyfireprotectionsystemorequipmentondemand
primarilydependuponadherencetotheirdesigncriteriaandtimelymaintenancethroughoutthelifecycleof
building/facility. This life cyclemay involve changes in individual stakeholders including owners, tenants,
management, maintenance staff and designed facility configuration and occupancy. It is, therefore,
imperative that these changes bemanaged through recognition and adherence to (i) established change
managementpolicies&proceduresand(ii)buildingfacilitymaintenancemanualsandestablishedprocedures
fortheapprovalanddocumentationofbuilding/facilityusageandconfirmationattention.
Operation
&
Maintenance
manual
(O
&
M)
Thefireprotectionoperations&maintenancemanualclearlystatingtherequirementsofthebuilding/facility
operatortoensurethatall installedfireprotectionsystems&theircomponentsandfirefightingequipment
are inplaceandoperatingproperly /efficientlyatall times.TheO&M shallalsocontainappropriate fire
prevention checklist,method of implementing such fire preventionmeasures (Refer to Part 7 of these
regulations)andbuildingevacuationplan.
Part2Sections1to5
(ConsultancyServicesincludingthatofFireProtectionExperts/Specialistsand
SubmittalRequirementsForObtainingBuildingPermit,CompletionCertificateand
approvals
related
thereto
and
shop
drawing
approvals
&
fit
out
works
requirements)
1. Thequalified,competent&authorized/approvedconsultantsshallsubmitthedocumentsanddrawingsasperAppendix2. (RefertoCivilEngineeringDeptofTrakhees/PCFCforadditionalinformation/thecurrentlistof
suchconsultants).
2. TheConsultants(serviceproviders)executingprojectsinvolvingfireprotectiondesign,fireratedconstruction,
firedetection,firesuppressionor lifesafetysystemsincludingevacuationplansshallberequiredtoprovide/
hire the services and review of a qualified fire protection expert/specialist. Such fire protection
expert/specialist shall be an integral part of the design team and shall be involved in every aspect of fire
protectiondesign. Thisshallinclude,butnotlimitedto,buildingcodeanalysis,lifesafetycodeanalysis,design
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
9/167
- 5 - - 5 -
of automaticdetection and suppression systems,water supply analysis andamultidiscipline reviewof the
entireproject.
3. Aqualifiedfireprotectionexpert/specialistshallbefullyconversantwithallprovisionsoftheseregulationsandalsomeetoneofthefollowingconditions:
Fireprotectionexpert/specialistwithinthemeaning&contextoftheprovisionsoftheseregulationsshallbe
anengineerhavingaBachelorofScience,AdvancedDiplomaorMasterofScienceDegree inFireProtection
Engineering fromanaccrediteduniversityengineeringprogramor recognized FireEngineering Institutionof
repute plus aminimum of 15 years ofwork experience dedicated to fire protection engineering including
applicationofNFPAanditscompanioncodesandstandardsthatcanbeverifiedwithdocumentation.
OR
Aregisteredprofessionalengineer(P.E) inarelatedengineeringdisciplinewhohaspassedthe fireprotection
engineering written examination administered by an accredited university or recognized Fire Engineering
Institutionsofreputeplusminimumof10yearsofworkexperiencededicatedto fireprotectionengineering
includingapplicationofNFPAanditscompanioncodesandstandards thatcanbeverifiedwithdocumentation.
4. EHSFireDept/AHJreservestherighttoapprovefireprotectionexperts/specialists.
5. Aqualifiedfireprotectionexpert/specialistshallhaveanunderstandingoforanabilitytointerpretthelevelof
safetyintendedbythecodesorstandardsrelevanttotheprojectandtheabilitytodemonstrateanddocument
theachievement
of
acceptable
levels
of
protection.
He/she
shall
have
sufficient
relevant
knowledge
to
know
whichapproachescouldbeusedtoperformthetasksandtheapplicabilityand limitationsofthemethods(s)
thatcanbe selected. Examplesofareas that fireprotectiondesignprofessionalsoftenneed tounderstand
includethefollowing:
FireDynamics
FireModeling
ActiveandPassiveFireProtectionSystems
FireTesting
FireDeptoperations
HumanBehavior
GuidelineNotes:
i. The consultants shallbe solely subject to the lawsof theUAE for lossesordamages in termsof lifeandproperty stemming from design errors, implementation errors, deficiencies of inspections, failure to
construct in compliancewith the required standards, failure to complywith rules of Professional ethics,
failure touse knowledge and experience to the contracting entity, and similar reasons; and successively
(severally)liablewiththecontractorswheretheconsultantshaveundertakendesigncontrolandinspection
servicesonworks. The consultants shallbe caused to complete and compensate forany such lossesor
damagespursuanttothelawsoftheUAE.
ii. EHSFire
Dept/AHJ,
EHS
Dept
or
any
other
departments
of
Trakhees
/PCFC
and
their
directors,
officers
&
otherconcernedpersonnel shallnotbeheld responsibleor liable foranysuch lossesordamages,errors,
deficienciesandfailuresonthepartoftheconsultants.
Part3Sections1to4
(RiskAssessmentStudyandFireRiskAssessmentRequirements)
1. RiskAssessmentstudyshallbemandatorynormally formanufacturing&process industries,storeplaces for
flammable,combustibleandotherhazardousliquids,solids&gases,TankFarms,Spheres,Bullets,Liquid&gas
storagetanks,boilers&pressurevessels,gasdistributionsystems,Petrol,Oil&Chemicaldistributionsystems/
pipelinesandotherspecialstructures.
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
10/167
- 6 - - 6 -
2. RiskAssessmentstudyshallbecarriedoutandreporttothateffectshallbesubmittedtoEHSDeptandEHS
FireDeptbythequalified,competent&authorized/approvedconsultants(RefertoEHSDeptorEHSFireDept
forthecurrentlistofsuchconsultants).
3. EHSapprovedRiskAssessmentconsultantsshall include,butnot limitedto,the followingpoints intheirRiskAssessment/AnalysisReport:
a) Firehazardidentification.
b) Severityanalysis/Fire
&
Explosion
Index
(F
&
EI)
and
Toxicity
Index
(TI).
(RefertoAppendix3)
c) Mappingareasofrisk,riskcontoursandrisktransect
d) Directcomparisonwithactuarialdataandotherriskcriteria.
e) Criteriaforassessingmaximumreleasequantityandseparationdistances/quantifyingdispersion.
f) Scenariodevelopment.
g) Probabilityanalysis/thechancesoffireandexplosion.
h) Riskmonitoring(iftheriskisacceptable).
i) Identificationofenvironmentalproblemsthatarerelatedtofireprotection.
j) Riskreductionanalysis(iftheriskisnotacceptable)systems&methodsandrecommendationstopreventand/orreducethemtotheacceptablelevel(s).
k) Hazard
and
Operability
Study
(HAZOP)
l) Eventtrees
m) Casehistorieswhereappropriate
n) Compliancewithcodes,proceduresandregulations includingmanufacturingrequirement&management
underASMEcodeforboilers&pressurevessels.
o) Toxicityrelationships&densegasdispersionmodel
p) Damagefromfireandradiantheat
q) TheTNTequivalence
r) Primaryandsecondaryblastsrelationships
s) Topeventfrequencyestimation
t) Design
&
construction
procedures
u) MaintenanceOperations
v) Education&Trainingofstaff
w) Emergency/EvacuationPlans (onsite&offsiteplans includingemergencyactions,emergencyreportingprocedures, evacuation policy, exitmaps, procedure for sheltering in place, procedure for peoplewho
remain in place, procedure for accounting for all personnel, Rescue andmedical tasks and emergency
communicationplan.)
4. FireRiskAssessment(FRA):NFPA551shallbecompliedwithforevaluationofFireRiskAssessment. NFPA551
mainlyaddressesthefollowing:
a) Applyingriskinformeddecisionmakingforfiresafety
b) Selectingfire
scenarios,
identifying
representative
challenging
scenarios
and
grouping
such
scenarios
into
clustersforthepurposesofconductingmoreeffectiveconsequenceanalysis
c) Documentationthatshouldaccompanyafireriskassessment
d) Capabilitiesofthoseconductingafireriskassessment
Guidelinenotes:
i Thescalethatmeasuresseveritysuchasdeath,injuries,propertydamage,andareasreachedbyflamesshallbespecified.
ii Calculationsspecifyingtheseveritymeasureusedforaparticularfireshallbeincluded.
iii Activeandpassivefireprotectionmeasuresshallbeincluded.
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
11/167
- 7 - - 7 -
iv The consultants shallbe solely subject to the lawsof theUAE for lossesordamages in termsof life and
property stemming from design errors, implementation errors, deficiencies of inspections, failure to
construct in compliancewith the required standards, failure to complywith rules of Professional ethics,
failure to use knowledge and experience to the contracting entity, and similar reasons; and successively
(severally)liablewiththecontractorswheretheconsultantshaveundertakencontrolandinspectionservices
onworks. Theconsultants shallbecaused tocompleteand compensate forany such lossesordamages
pursuanttothelawsoftheUAE.
v EHSFireDept/AHJ,EHSDeptoranyotherdepartmentsofTrakhees/PCFCandtheirdirectors,officersand
otherconcernedpersonnel shallnotbeheld responsibleor liable forany such lossesordamages,errors,
deficienciesand
failures
on
the
part
of
the
consultants.
Part(4)Sections1to16)
(BuildingFireProtectionDesignFeaturesandLifeSafetyRequirements)
1. FireProtectionDesignAnalysis:
Afireprotectiondesignanalysisisrequiredforalldesignsandshalladdressthefireprotectionrequirementsof
theprojectasrequiredbytheseregulations. Thefireprotectiondesignanalysisshallbeseparatefromother
disciplinesandshallbesubmittedwithconceptsubmission. Thesameshallincludethefollowing:
a)Building code analysis i.e. type of construction, height and area limitations and building separation orexposureprotection.
b)Classificationof
occupancy.
c)Requirement for fire rated walls, fire rated doors, fire dampers with their fire resistive ratings, smokecompartmentation&smokebarriers.
d)MeansofegressinaccordancewithNFPA101(occupantloads,exitcapacitiesetc).
e)Analysis of automatic sprinkler systems and other suppression systems and protected areas, including
hydraulicanalysisofrequiredwaterdemand.
f)Watersupplies,waterdistribution,locationoffirehydrants.g)Smokecontrolmethodsandsmokecontrolsystems.
h)FireAlarmSystem(thetypeofalarmsystemandlocationofalarmequipment).
i) Firedetectionsystem(thetypeofdetectionsystemandlocationofdetectors).j) Standpipesystemsandfireextinguishers.
k)Interiorfinishratings.
l) Connectionto
and
description
of
fire
alarm
supervising
system.
m) Identifythevariousoccupanciesandhazardousareasassociatedwiththefacility.
n)FireDeptaccess.
o)Coordinationwithsecurityrequirements.
2. ClassificationofOccupancyandHazardsofContentsandSpecialOperation:
RelevantprovisionsofNFPA101andNFPA5000 shallapply. QualifiedFireProtectionexpert/specialistshall
submitareportonfireprotectionandlifesafetyfeatureswhenmakingbuildingpermitsubmissionforprojects.
(RefertoAppendix 4)
3. TypesofConstruction:
Newstructures
shall
be
constructed
from
non
combustible
or
the
resistive
construction
as
per
NFPA
5000.
4. Heightandarealimits:
Heightandarea limitationsofnewbuildingsshallbe inaccordancewithNFPA5000whereexistingbuildings
undergoadditions,thecombinedareaoftheexistingbuildingandthenewadditionshallcomplywiththelimits
establishedinNFPA5000wheretheareaoftheadditionwouldcausethebuildingtoexceedtheheightand/or
arealimitsofNFPA5000,firewallsand/orfirebarriersarerequiredasdeterminedbyNFPA5000.
5. SiteConsiderations:
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
12/167
- 8 - - 8 -
a) RefertoAppendix6FireDepartmentVehicleAccess. Atminimum,oneofthelongsidesofeverybuilding
shallbeaccessibletoFireDeptvehicles.
b) Buildingseparationandrequirementsforratedexteriorwallsandopeningsforprotectionfromexposures
byadjacentbuildingsorhazardsshallcomplywithNFPA5000.
6. SpecialStructures&HighRiseBuildings:
RelevantProvisionsofNFPA101andNFPA5000shallapply. Towers,highrisebuildings;watercoolingtowers;
television,microwaveandradiotransmittingtowers;windowlessandundergroundbuildings;tunnels;highway
andrailroadbridges; tents;grandstands;amusementparkstructures;membranestructures;piersandwater
surroundedstructures
used
for
purposes
other
than
vessel
mooring
or
cargo
handling;
air
right
structures;
coveredmallbuildingsandother special structures suchas signsandopenparkinggaragesareexamplesof
specialstructures.
Guidelinenotes:
Fordesigninghighrisebuildings,thefollowingmajorfireprotectionfactorsshallbeconsidered:
i. Accessibility
ii. Uniquepeoplemovement&egresssystems
iii. Increasedoccupant,equipment,materialandfuelload(s)
iv. Combinationofoccupanciesinasinglehighrisebuilding
v. Naturalforcesi.e.wind/stackeffectaffectingfireandsmokemovement.
RefertoAppendix5forFireProtection/FireSafetyGuidelinesforDesigningHighRiseBuildings
7. OccupanciesinSpecialStructures:
Relevant provisions of NFPA 5000 shall apply for all occupancies in special structure viz. underground
structures, limitedaccessstructures,vehiclesandvessels(mobileunits),openstructures (outdoorprocessing
facilities),towers,watersurroundedstructures,piers&helistops.
8. SpecialConstruction:
RelevantprovisionsofNFPA5000shallapplyforallspecialconstructionviz.bleachers,foldingandtelescopic
seating, grandstand, hot tub, membrane public pool, residential pool, swimming pool, spa, air inflated
structure,
air
supported
structure,
membrane
structure,
tensioned
membrane
structure,
permanent
&
temporarystructures,tent,privatepartytentandweatheredmembranematerial.
9. EncroachmentsintothePublicRightofway:
RelevantprovisionsofNFPA5000shallapply forprojection intoAlleys,spacebelow sidewalk,Balconiesand
Appendages,Doors,RoofDrainage,Airtightstructures&SkywalkBridges.
10.RoadTunnels,BridgesandotherLimitedAccessHighways:
RelevantprovisionsofNFPA5000shallapply.
11.PassiveFireProtection FeaturesofFireProtectionandFireResistiveMaterialsandConstruction:
a)Everybuilding,
facility
or
structure
shall
be
constructed,
arranged,
equipped,
maintained,
and
operated
to
avoidunduedangertotheoccupantsfromfire,smoke,fumes,unsafeconditionsorresultingpanics.
b)RelevantprovisionsofNFPA101,NFPA5000andNFPA220shallapply.
Guidelinenotes:
i Balancepassiveandactivefireprotectionmeasurestoreinforceandcomplimenteachother.
ii Implement key decisions related to passive fire protection made during design, construction andoccupancy.
iii Useoffireresistivebarrierstoslowspreadoffiretolargesecondaryitems.
iv Useconstructionbarriers toblock firespreadbetweenzones (wallassemblies,ceiling/floorassemblies,
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
13/167
- 9 - - 9 -
barriersbetweenoccupiedandconcealedplaces,firestopping inconcealedspacesandexteriorbarriers
toverticalspreadbetweenfloors).
v Design doors and windows to block fire spread between zones (Fire door assemblies and window
restrictionstoblockfirespreadbetweenbuildings/structures/plants).
vi Separatebuildings,facilitiesorstructuresenoughtopreventfirespreadbetweenthem.
vii Regulate design and operation of systems for heating, venting, and air conditioning to prevent theirservingasmechanismtotransfersmokeandgases intouncontaminatedoccupiedareas.(Thisshallalso
permitshutoffofairmovementinfires).
viii Plugverticalandhorizontalutilityopenings(pipes,cableducts,ACductsandcables)andpeepthrough(at
doors,columns&beams)bysuitablefireresistivesealant.
ix Considercompartmentationtocontainspreadoffire/smoke/heat.
x Fireretardanttreated(FRT)plywood: FRTplywoodshallnotbeused inanypartoftherooforroofing
systems. Existing FRT plywood installations shall be regularly inspected for structural integrity.
ReplacementofdamagedFRTplywoodmayrequireadditionalfireprotectionmeasuresifFRTplywoodis
tobereplacedwithmorecombustiblematerials.
xi Insulation: Thermal and acoustical insulationwith a flame spread (FS) ratingnothigher than75 and
smokedeveloped(SD)ratingnothigherthan150whentestedinaccordancewithASTME84(NFPA255)
shallbeused. Applicationofcellularplasticinsulationtobuildingexteriorsshallbeinaccordancewiththe
requirementsoftherelevantcode/standard. Cellularplasticshallnotbeusedforinteriorinsulation.
xii Roofcoveringsandroofdecks: Roofcoveringsapprovedand listedbyanNRTLshallbeused. TheUL
RoofingMaterials
and
Systems
Directory
lists
three
classes
(A,
B
and
C)
of
acceptable
roof
coverings
based
oncompliancewithUL790andNFPA256. RoofdeckassembliesshallbeUL listedasFireclassifiesor
equal listing or classification by an NRTL or FM approved except for fully sprinklered buildings and
buildingslessthan744m2.
xiii Wood: Woodusedforwalls,platforms,blocking,furringandsimilarapplicationsshallbefireretardant,
pressureimpregnated. Fireretardantcoatingsofintumescentpaintorotherfireretardantchemicalsare
notacceptableinlieuoffireretardanttreatment.
xiv Fire and Smoke Barriers: Fire and smoke barriers shall comply with the requirements of NFPA 101.RelevantprovisionsofNFPA90AshallapplyfortreatmentofHVACductpenetrations,locationsofsmoke
dampersand smokedetector requirements. Subject to theapprovalofEHSFireDept smokedampers
maybeomitted inHVACductsthatpenetratesmokebarrierswherethesystem isdesignedtoperform
any
of
the
following
functions:
Function as an engineered smokecontrol system, including the provision of continuous air
movementwithairhandlingsystem.
Provideairtootherareasofthebuildingduringafireemergency.
Providepressuredifferentialsduringafireemergency.
12. InteriorFinish,includingfloorfinish,Contents&Furnishings:
a) RelevantprovisionsofNFPA101andNFPA5000shallapply.
b) Restrictmaterialsused incontentsand furnishings to reduceheat release rateand smokegenerationrate&topreventunusualtoxichazardrelativetoquantityofsmokegenerated.
c) Addfireretardantstomaterialstoslowgrowthofheatreleaserate.
d) Restricttotal
fuel
load
to
limit
contents
based
in
total
fuel
potential.
e) Restrict liningsof rooms toprevent rapid flame spread (Restrictwallcoverings,ceilingcoverings,and
floorcoverings).
f) Restrictmaterialsinconcealedspaces(Restrictconcealedcombustiblesandconcealedspacelinings).
g) Dropoutceilings(foamgridpanels)shallnotbeused.
13. LiftsFireLifts/ElevatorsandConveyingSystems:
a) New lifts shall be designed in accordancewithASMEA 17.1which includesprovisions for a fire lift.RelevantprovisionsofNFPA101andNFPA5000shallapply.
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
14/167
- 10 - - 10 -
b) Allthefloorsshallbeaccessiblefor24hoursbythelifts.Theliftsprovided inthebuildingsshallnotbe
consideredasameansofescapeincaseofemergency.
c) Theliftmachineroomshallbeseparatedandnoothermachineryshallbeinstalledtherein.
d) Liftsdesigned in accordancewithDubaiMunicipality standards shall alsobeapproved subject to theconditionthatthefollowingrequirementsarestrictlymet:
i) Theelevatorshafttobeofthe2Hourfireresistantconstruction.ii) Elevatortobefittedwithprotectedandstandbypowersupplies.
iii) Smokeventingprovisionshallbeprovidedtotheseliftshafts.iv) Elevatorsshallreturntothelevelofexitdischargeincaseofemergency,andinthecaseofthe
emergencybeingontheLED,aalternativefloorshallbeusedasdefinedbytheFireSafetyStrategy
14. BuildingsServiceandFireProtectioninstallations/fireextinguishingSystemsandEquipment:
a) Design of new, andmodifications to existing buildings and facilities shall be in accordancewith the
requirementsof these regulationswhichdescribe specific fireprotectiondesign criteria. Design is to
incorporateredundantfireprotectionconcepts,employingactivefireprotectionthroughautomaticfire
suppression and detection systems, passive fire barrier features, and limiting combustible fuel load
withinthebuildingsinordertocontrolandminimizepotentiallosses.
Completeautomatic firesuppressionsystemsare tobeprovidedand installed inaccordancewiththe
applicable NFPAcodes/standards forallprojects (regardlessof fundingsources)where themaximum
credible fire loss (MCFL)withoutautomatic fire suppressionwould result in the lossofuseofa vital
structureor
equipment.
Inaddition to theabove requirement, fireextinguishingsystemsshallbeprovidedwhere requiredby
applicableNFPAcodes/standards.
When the criteria above does not apply, automatic fire suppression and/or detection may still be
warrantedbasedonanyofthefollowingfactors:
(i) Programmaticimportance(ii) Effectsonoperations(iii)Costvs.benefit
(iv)Exposure
(v) Futureconditions
b) FixedFireFighting Installations/FireExtinguishingSystems:Thefixedfirefighting installations/systems,sorequired,shallmostlyinclude[butnotlimitedto]thefollowing:
(i) HoseReel.
(ii) SprinklerincludingEarlySuppressionFastResponse(ESFR)sprinklerssystem
(iii) WaterSpraySystem
(iv) AutomaticSmoke/Heat/Flame/LowExplosiveLimit(LEL)Detectors.(v) Smokeandheatventilationsystem.(vi) Delugefoamorwatersprinkler&foamorwaterspraysystems.
(vii) ClosedHeadfoamwatersprinklersystem.
(viii)Totalfloodingsystems(ofappropriateextinguishingagent(s).)
(ix) FoamPourerSystem.
(x) Foam/Watermonitors.(xi) HydrantsandHoseBoxes.(xii) FirePumps&(xiii) FireWaterTanks.(xiv)PrivateFireServiceMains
(xv) CleanAgentFireExtinguishingSystems
c) FireDetection&FireAlarmSystems:Everybuilding,facilityorstructureshallbeprovidedwithsuitablefiredetection/alarmsystemscapableofenablingearlydetectionoffireandwarningoccupantsofthe
existenceoffire.
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
15/167
- 11 - - 11 -
When fire protection systems are installed in buildings/facilities they are to be compatiblewith and
connectedto(whereavailable),thesitewidefirealarmmonitoringsystem.
Firealarm installationsshallcomplywiththe requirementsandrecommendationsofNFPA72,project
specifications, and EHSFire Dept and Dubai Civil Defence requirements (24 X 7 CentralMonitoring
System).
AllnewfirealarmsystemsshallbeaddressableunlessotherwisepermittedbyEHSFireDept.
(i)Specialrequirements
Wheremultiple firealarm controlpanelsareprovided they shallbe interconnected inaClassA
(Style6or
7)
network
arrangement.
Allfirealarmsystemsshallbemonitoredbyasupervisingstation.
All firealarmcircuitsshallbe installed inconduit (EMT, IMT,or rigid). Theuseof firealarmMC
cablemaybepermitted,subjecttotheapprovalofEHSFireDept
SignalingLine,notificationappliance,andpowercircuitsshalleachbeinseparateconduit.(Referto
Appendices36&37andreferAppendix49forchecklists)
(ii) PublicAddress
Separate public address systems shall be provided for nonemergency communication where
desired/needed. Fire alarm systems shall not be used to address the public in nonemergency
situations.
d) Portable Fire Extinguishers: Every building, facility or structure shall be provided with portable fire
extinguishers
of
types,
capacities,
numbers,
and
locations
appropriate
to
the
individual
building
or
structurewithdueregardtothecharacterof itsoccupancy.Allthe fireextinguishersshallconformto
thestandardscurrentlyapprovedbyUAE/CivilDefenseauthorities.
e) SprinklerSystems
(i) FireSprinklerSystemdesigncriteriashallcomplywithNFPA13.
(ii) Thefollowingminimumdesigncriteriashallbemet:
Hydrauliccalculationsmustbeusedfordesign. Pipescheduledesignwillnotbeaccepted.
Reductions in thehydraulicallymost remoteareaallowed inNFPA13with theuseofquick
responsesprinklersarenotpermitted.
Variation indischarge from individual sprinklerheads in thehydraulicallymost remote area
shallbeaspertherespectivedensitycurves.
Thecalculatedpipevelocityshallnotexceed20ft/sec(6.1m/sec).
Safetymargin:Thetotaldemandwaterflowandpressuremustbeat least10% lessthanthe
availablewaterflowandpressure.
Pipeschedule:Schedule40orgreatershallbeused forallsprinklerpiping lessthan4 inches
(100mm). Schedule10,40,orgreatershallbeusedforsprinklerpiping4inches(100mm)and
larger.
Butterflyvalvesmaybeusedonlyonpiping4inches(100mm)andless.
GatevalvesshallbeOS&Ystyle.
Useofrestrictiveorifices,reducingflanges,unions,andplainendfittingswillnotbepermitted.
Branchoutletmechanicalfittingsandclamptypefittingsshallnotbepermitted.
Compact shelving shall be protected with automatic sprinkler system meeting the
requirementsofNFPA909
f) StandpipeSystems
i. When required, standpipe systems shall be installed in accordance with NFPA 14, Installation of
StandpipeandHoseSystems.
ii. Residualpressurerequirementsmaybeomittedforbuildingsunder150ft(45m)inheightwherefire
department apparatus are expected to boost pressure in standpipe systems. Piping for standpipe
systems shall be designed by hydraulic calculation to show that the fire department pumper,
connectedtoafiredepartmentconnection,candelivertheneededflowandpressureatthetopmost
hoseconnections.
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
16/167
- 12 - - 12 -
iii. ClassIstandpipesystemsshallbeprovidedinexitstairwaysofbuildingsfourstoriesormoreinheight.
Thesesystemsshallnot includehose.21/2by11/2(63.5by38mm)reducers,withcaps,shallbe
providedatallfiredepartmentvalves.
iv. ClassIstandpipesystemsshallalsobeprovided innonsprinkleredfacilitieswhereallportionsofthe
buildingcannotbereachedwith200feetoffirefightinghoselinesextendedfromtheexteriorofthebuilding, regardless of building height. Locate FD hose connections such that all portions of the
buildingcanbereachedwith100ft.(30.5m)ofhoseplus30ft.(9.14m)ofhosestream.
v. CombinedClassIIandClassIIIstandpipesarenotpermitted.
g) PrivateSystemsi. Privatewaterdistributionsystemsandwatersupplies shallbe installedinaccordancewithNFPA24
NFPA20,NFPA22andAWWAM31
ii. Supply Duration andMain Size Criteria: Thewater supply for fire protection shall haveminimum
supplydurationof2hours. Newprimarydistributionmainsshallinnocasebesmallerthan12inches
(300mm),building/facility loops shallbe8 inches (200mm)or larger,and fixed suppression feeds
shall,innocase,besmallerthan6inches(150mm).
iii. DistributionSystem:Fireprotectionwatersupplydistributionsystemsforallnewinstallationsshallbe
loopedtoprovidetwowayflow,withsectionalvalvesarrangedtoprovidealternatewaterflowpaths
toanypointinthesystem.
iv. IndependentSources:
Facilities
having
an
MPFL
in
excess
of
AED
200
million
shall
have
two
independentsourcesoffireprotectionwater.
v. Hydrants:FirehydrantsshallbeUL listed,FMapproved,or listedorclassifiedbyanNRTLand shallhave two 21/2inch (65mm) hose outlets and one 41/2inch (115mm) suction connectionwith
national standard fire hose threads in accordance with NFPA 24 and NFPA 1963, Fire Hose
Connections.
Hydrantsshallbeabovegroundtype.
Hydrantsshallbeinstalledadjacenttopavedareas,accessibletofiredepartmentapparatus/vehicles.
Hydrantsshallnotbecloserthan3feet(1m)norfartherthan7ft(2.1m)fromtheroadwayshoulder
orcurb line. Hydrantsshallbe installedwithnot lessthan6inch(65mm)connectiontothesupply
main,andvalvedattheconnection. Barrelsshallbelongenoughtopermitatleast18inch(450mm)
clearance
between
the
center
of
the
4
1/2
inch
(115
mm)
suction
connection
and
grade.
The
ground
shallbegradedsothatanysurfacedrainageisawayfromthehydrant.
InstallationshallbeinaccordancewithNFPA24. Suctionconnectionshouldbeperpendiculartothe
streettoallowstraightlinedconnectiontothepumper.
Asufficientnumberofhydrantsshallbeprovidedsothathosestreamdemandcanbemetwithout
takingmorethan1,250gpm(4,740L/min)fromanysinglehydrant. Hydrantsmustalsobespacedin
accordancewiththefollowingrequirements:
Allpartsofthebuildingexteriorshallbewithin350ft(106m)ofahydrantwithconsideration
given toaccessibility andobstructions. Hydrants shallbe locatedwith consideration given to
emergencyvehicleaccess.
Atleastonehydrantshallbelocatedwithin150ft(45m)ofthefiredepartmentconnection.
Hydrantsprotectingstoragefacilitiesaretobespacedamaximumof300ft(91m)apart.
Hydrantslocated
adjacent
to
parking
areas
or
other
vehicle
traffic
areas,
shall
be
protected
by
bollards. Thebollardsshallbelocatedsotheyarenotdirectlyinfrontofanoutlet.
(RefertoAppendix33)
Guidelinenotes:
i.SmokeControl&HeatVentilationSystem: Smoke&Heatventsshallbeconsidered inbuildingswhereahighrateofheatreleaseisanticipatedduringafire. RelevantprovisionsofNFPA92A,NFPA92BandBSEN
12101shallbeapplicablewhereappropriate.
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
17/167
- 13 - - 13 -
ii.Waterdemandsforsprinkleredbuildings,facilitiesorstructures:Thewaterdemandrequiredforsprinkler
protection shall take into considerationoccupancy,dischargedensity,design areaand typeof sprinkler
system(wetordry),typeofconstructionandotherbuildingfeatures.
iii.Waterdemands forhosestreams:Hosestreamsshallbeneededconcurrentlywithsprinklerdischarge in
ordertoeffectfinalextinguishmentortowetdownadjacentareas/structures.
iv.Totalwaterdemand forsprinkleredoccupancies:The totalwaterdemand forsprinkleredoccupancies isequaltothesumofthedomestic/industrialdemandplusthesprinklersystem(s)waterdemandandhose
stream(s) demand. The total demand shall be available at the sprinkler system connection to the
underground main and at the pressure necessary to produce the required sprinkler density over the
requiredhydraulicallymostremoteareaofsprinkleroperation.
Waterdemandforspecialfacilities,familyhousing,piledorrackstorage,rubbertirestorage,flammable&
combustibleliquidstorageshallbedeterminedonthebasisofrelevantNFPAcodes.
v.Water supplypressure requirements: Pressure required for sprinkleredbuildings, facilitiesor structuresshall be themost demanding pressure of the domestic / industrial demand, sprinkler demand or hose
streamdemandandshallbedeterminedbyhydrauliccalculations.
vi.Quantities of water required: Requirements for fire protection water storage shall be based on theassumptionthattherewillbeonlyonefireatatime. Thequantityofwaterrequiredshallbeequaltothe
product of the fire protectionwater demand and the required duration. This quantity represents fire
protectionrequirementsonlyandshallbeavailableatalltimes. Watersupplyfordomestic,industrialand
other
demands
shall
be
added
to
these
requirements
to
determine
the
total
amount
of
water
that
is
necessaryatthebuilding,facilityorstructure. Thewaterstorageshallbeselfreplenishing. Itshallreach
required volume during normal consumption within 48 hours and within 24 hours curtailing normal
consumption.
vii. Thepumps:Pumpsshallhaveadequatecapacitywithreliablepowerandwatersupply.Theyshallconform
totherequirementsofNFPA20.Firepumps,driversandotherequipmentincludingautomaticaccessories
shall be listed byUL, approved by FM or listed or classified byNRTL. Fire pumps shall be located in a
detached,noncombustiblepumphouseorlocatedina2hoursfireratedroomwithdirectaccessfromthe
exterior. A secondary fire pump shall be providedwhen thewater supply cannot support 25% of the
sprinklersinthehydraulicallymostremotedesignareawiththeprimaryfirepumpoutofservice.
viii.FireMains: Useof firemains for the services like irrigation,process&domesticpurposes shallnotbe
permitted.
PressureRegulating Valves (PRVs): PRVs are restricted in use on fire protectionwater systems.Where
essential,PRVsshallbeinstalledonindividualserviceratherthanonmainpiping.WherePRVsareprovided
in distributionmains supplying systems or portions of systems with fire hydrants, automatic sprinkler
systemsorother installed fireprotection, the following features shallbeprovided to safeguard against
failuresandtofacilitatemaintenance:
a) ControlvalvesoneachsideofthePRVs.
b) BypassaroundPRVs.
AlsorefertoAppendix31
ix.FoamSystems:FoaminstallationsshallbeinaccordancewithNFPA11,NFPA11AandNFPA16.FormoreinformationrefertotheNFPAFireProtectionHandbookandFMGlobalDataSheets.
x.DryChemical Extinguishing Systems:Dry chemical extinguishing systems shall conform toNFPA17.Dry
chemicalagentsshallnotbeusedprotectsensitiveelectronics.Drychemicalextinguishingsystemsareno
longerULlistedorFMapprovedfortheprotectionofcookingequipment.
xi.CarbonDioxideSystems:CarbondioxidesystemsshallconformtoNFPA12.
xii.WetChemicalsExtinguishingSystems:WetChemicalSystemsshallconformtoNPFA17A.
xiii.CleanAgentFireExtinguishingSystems:Cleanagentfireextinguishingsystemsaresuitableforprotectionof
certaintypesofspecialoccupancies,hazardsandfacilitiesandshallconformtoNFPA2001.Cleanagentfire
extinguishingsystemsshallnotbeinstalledasasubstituteforrequiredautomaticsprinklersystems. Stand
alonecontrolpanelsthatare listed forreleasingdeviceserviceandmonitoredby thebuilding firealarm
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
18/167
- 14 - - 14 -
systemshallbeprovided. Carefulconsiderationshallbegiventocompartmentunder/overpressurization
during the discharge of total flooding clean agent systems. Pressure relieving vents, located near the
finished ceiling,maybenecessary to regulate rapidpressure changesduringdischarge. Manufacturers
recommended procedures relative to enclosure venting shall be compliedwith. Amanually activated
exhaustsystemtofacilitatetheextractionofanyremainingcleanagentaftertherequiredholdtimeofthe
total flooding clean agent system shallbe provided. The exhaust system can be integrated intoHVAC
systemfortheenclosure.
xiv.CookingEquipmentSuppressionSystems:
a) AllcommercialgreasehoodandductsshallmeettherequirementsofNFPA96andNFPA17A.
b) Greaseductsshallbeprotectedbyapprovedproducts,designedwithclearancereductionmethodsandinstalledasfireratedenclosures.
xv.WaterMistFireProtectionSystems:WatermistfireprotectionsystemsshallconformtoNFPA750.Water
mistfireprotectionsystemsshallnotbeinstalledasasubstituteforrequiredautomaticsprinklersystems.
xvi.EmergencyWarningSystemshallincludeboth:audibleandvisualalarms.
xvii. SeismicCriteria:Fireprotection systems shallbedesignedand installed towithstand seismicevents in
accordance with the applicable NFPA standards except as required by other criteria for safety class
equipment.
15. MeansofAccess/Accessibility:
a) RelevantprovisionsofNFPA5000shallapply.
b) Nobuilding, facilityor structure shall be erected so as todeprive anyotherbuilding of themeansofaccess.
c) Theapproachroadtothebuildingandopenspacesonitsallsidesupto6mwidthandthelayoutforthe
sameshallbedoneinconsultationwithEHSFireDepartmentandthesameshallbeofallweatherground
accesshard surface capable of taking theweight of the heaviest fire vehicle availablewith FireDept.
/DubaiCivilDefence.
d) Mainentrancestothepremisesshallbeofadequatewidthtoalloweasyaccesstothefirevehiclesandin
nocaseitshallmeasurelessthan5meters.Theentrancegateshallfoldbackagainstthecompoundwall
ofthepremises,thusleavingtheexterioraccesswaywithintheplotfreeformovementoftheFire/Civil
DefenceVehicles.Ifarchwayisprovidedoverthemainentrance,theheightofthearchwayshallnotbeat
aheight
less
that
4m.
e) Anylockingdevicecontrollingvehicleaccessshallbeundercontrolof24hoursecuritypersonnellocatedatthespecificfacility.
f) Buildings,facilitiesorstructureswithfiredepartmentconnectionsforsprinklerorstandpipesystemsshallbeprovidedwithsuitableallweathergroundaccesssurfaceforpumperapparatuswithin45mofsuchfire
departmentconnections.
g) TheprovisionsofPart5Section5oftheseregulationsshallbecompliedwith.
h) RefertoAppendix6fortherequirementsconcerningFireDepartmentVehicleAccess.
16. MeansofEgress:
a) Everybuilding,
facility
or
structure
shall
be
provided
with
safest
means
of
egress
and
other
safeguards
of
kinds, numbers, locations and capacities appropriate to the individual building or structurewith due
regard to type of occupancy, the capabilities of the occupants, number of persons exposed, the fire
protectionavailable,thetypeofconstructionofthebuildingorstructureandotherfactorsnecessaryto
providealloccupantswithareasonabledegreeofsafety. Therequisitenumberandsizeofvariousexits
shall be providedbased on thepopulation in each room, area and floorbased on theoccupant load,
capacityofexits,traveldistanceandheightofbuildings. (RefertoAppendix7)
b) Adequatemeansofegressshallbeprovidedineverybuilding,facilityorstructure,wherethesize,areaofoccupancyandotherarrangements[thatarelikelytoendangertheoccupantsattemptingtouseasingle
meansofegress]areblockedbyfireorsmoke.Allsuchmeansofegressshallbesoarrangedtominimize
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
19/167
- 15 - - 15 -
thepossibilityoftheirsbeingrenderedimpassablebythesameemergencyconditions.
c) Everyexitstairwayandotherverticalopeningsbetweenfloorsofabuilding,facilityorstructureshallbesuitably enclosed or protected as necessary to afford reasonable safety to occupantswhile using the
meansofegressandtopreventthespreadof fire,smokeor fumesthroughtheverticalopenings from
floortofloorbeforetheoccupantshavereachedthenearestexit.
d) Exitsshallbesoarrangedthattheymaybereachedwithoutpassingthroughanotheroccupiedunitexceptincaseofresidentialbuildings.
e) MeansofegresscomponentshallcomplywithNFPA101andNFPA5000.
f) Thepopulation
in
rooms,
areas
of
floors
shall
be
calculated
based
on
the
occupant
load
factors
given
in
theAppendix8totheseregulations.
g) Common path, DeadEnd and Travel Distance limits etc. shall comply with Appendix9 to these
regulations.
h) IlluminationofmeansofEgress shallbeprovided inaccordancewithNFPA101 foreverybuildingand
structurewhererequired.
i) Emergency lighting facilities formeansofegressshallbeprovided inaccordancewithNFPA101forthebuildingsandstructureswhererequired.
j) WalkingsurfacesinmeansofegressshallcomplywithNFPA5000.
k) EveryrampusedasacomponentinmeansofegressshallconformtothegeneralrequirementsofNFPA
5000.
l) AreasofrefugeshallconformtoNFPA5000.
m) SlidEscapesshallbepermittedasacomponentinameansofegresswherepermittedinNFPA5000.
n) Locks, latches,alarmdevices,delayedegress locks,accesscontrolledegressdoors,Panichardware,Fire
exithardware,Selfclosingdevices,Powereddoors,revolvingdoors,turnstiles,doorsinfoldingpartitions,
balanced doors, horizontal sliding doors, stairs, curved stairs, spiral stairs, winders, landings, guards,
handrails,bridgesandbalconiesetcshallcomplywithrelevantsectionsofNFPA5000&NPFA101.
o) Corridors:Egresscorridorsshallnotbeusedasaportionofasupply,returnorexhaustairsystemserving
adjoining areas. Air transfer opening(s) shall not be permitted inwalls or in doors separating egress
corridors from adjoining areas. Exception: Toilet rooms, bath rooms, shower rooms, sink closets and
similarauxiliary
spaces
opening
directly
onto
the
egress
corridor.
p) Stairways:Stairsshallbeconstructedofconcrete,steeloracombinationoftwo. Woodconstructionshall
notbeused.Treadsshallbeprovidedwithnonskidnosingsoran integralabrasive ineh treadsurface.
Stairways that are part of the egress pattern shall havewidths, run lengths, landings, treads, risers,
handrails, guardrails, headroom, door sizes, door swings, door ratings, interior finishes,windows and
otheropeningsinaccordancewithNFPA101andNFPA80.
q) Scissorstaircasesarenotpermitted
Guidelinenotes:
i Exitshallbeeitherofhorizontalorverticaltype.Anexitmaybedoorway,corridorandpassagewaystoan
internalstaircaseorexternalstaircase,rampsortoverandahorterraceswhichhaveaccesstothestreetor
toroof
of
abuilding.
An
exit
leading
to
an
adjoining
building
at
the
same
level.
ii Doorsofsmallindividualroomssuchasofficesarenotconsideredasexitsunlesstheyactuallyleaddirectly
totheopenair.
iii Doorsoflargeroomsareconsideredtobeexits.
iv Aninteriorpassagewaydoesnotbecomepartofanexituntilitisenclosedasafirecompartmentwithatleasthalfanhourfireresistance.
v Whereanexternalstairwayexistsitshallbeensuredthattheuseofitatthetimeoffireisnotprejudiced
bysmokeandflameissuingfromopenings(e.g.Windows,doors)intheexternalfaceofthebuilding.
vi Internal stairways [asmeans of escape/egress] shall be suitably enclosed or protected as necessary to
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
20/167
- 16 - - 16 -
affordreasonablesafetytooccupantsandtopreventspreadoffire,smokeorfumesthroughthevertical
stairwayopening.
vii Lifts,escalators,andrevolvingdoorsnottobeconsideredasEXITS.
viii Adequatecapacityofallescapesroutepaths/passageways.
ix Protectionforescapepaths/passageways:a) Mark/signpost.
b) Markexitpaths/passagewaysclearlyandlightthem.
c) Restrictfuelloadsandfinishesinexitpaths/passageways.
d) Enclosestairways.
x Useconstructionbarrierstokeepfireout.
xi Usesmokecontrolmethodstoprotectatmosphereinexitpaths.
xii Escapetooutsideortoprotectedplaceoradequatedefenseofplaceswhereoccupantsshouldremain.
xiii Avoidanceofmakeshiftsecurityarrangements.
xiv Escaperoutesshallbelightedinsuchamannerthattheycanbeusedinafirewhenafailureofalocalelectricalcircuitisprobable.
xv EscapelightingshallbedistinguishedfromtheEmergencylightingwhichmightbeprovided,onfailureof
amainssupply,byastandbygenerator. Suchemergencylightingprobablywillnotfunctioninafiredue
tolocalcircuitfailureandescapelightingshallbeprovidedbyselfcontainedfittingswhicharecapableof
runningfor
aset
period
of
time.
The
provisions
of
NFPA
70
(Article
700)
shall
be
complied
with.
xvi Escapelightingsshallbeprovided/sitedatbutnotlimitedtothefollowing:
a)EachExitDoor.
b)NearEachStaircaseSoEachFlightReceivesDirectLight.
c)EachOtherChangeofFloor.
d)NearChangesofDirection.
e)NearEachIntersection.
f)NearEachFireAlarmCallPoint.
g)NearFireFightingEquipment.
h)OutsideEachFinalExitandClosetoit.
i)LiftCars.
j)
Plant
Rooms.
Escapelightingsshallalsobeprovidedtoilluminateexitsandsafetysigns.
xvii Egress lightsare fixturesconnectedtonormalpowersupplysystemsandare to functionsatall timeswhenthebuildingisoccupied.
xviii Emergencylightsorstandbylightsarenormallybatterytypeemergencyunitequipmentthatprovidenoilluminationuntilfailureoftheegresslightingcircuit. Theseunitsserveasabackupforegresslights.
xix Thecolouroftheexitsignsshallbegreen.
Part(5)Sections1to30
(Miscellaneous)
1. CriteriaforstorageconfigurationforJAFZAPBUs/LIUs.(RefertoAppendix 10)
2. HazardousAreaProtectionconcerningAssemblyOccupancies,HotelsandDormitories:
RelevantprovisionsofNFPA5000andNFPA101shallapply.
3) BuildingRehabilitation
RelevantprovisionofNFPA5000dealingwithrepair,renovation,modification,reconstruction,changeofuse
andchangeofoccupancyclassification,addition,damagedorunsafebuildings,historicbuildings&structures
etc.shallapply.
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
21/167
- 17 - - 17 -
4) SafeguardsDuringConstructiona) RelevantprovisionsofNFPA5000,NFPA241,NFPA70&NFPA1dealingwithsafeguardingconstruction,
alteration,demolitionoperations,protectionofutilities,temporarylight&poweranduseofexplosivesetc.
shallapply.(RefertoAppendix11)
b) Separatealloccupiedareas fromdemolition, renovation,orconstructionactivitiesby temporary smoke
tightconstructionpartitionsofgypsumboardorotherapprovednoncombustibleor limitedcombustible
material in accordancewith the requirements ofNFPA 241. Barrier design shall be detailed in project
documents.
Partitionsshallbefullheight,extendingthroughsuspendedceilingstothefloorslaborroofdeckaboveand
shallbe
one
hour
fire
rated,
unless
sprinklers
are
installed
and
are
operational
on
both
sides
of
the
temporarypartitionwhereuponthepartitionmaybepermittedtoterminateattheceiling inaccordance
withNFPA241.
Note: Thisrequirementisduetotheinherentlygreaterpotentialforfireorhazardousmaterialsincidents
associatedwiththecombustiblesandoperationsofdemolition/construction. Thisrisk ismadeworseby
thelikelihoodofcompromisedfireprotectionsystemsandfire/smokeresistantconstruction.Thisdoesnot
obviate the need to provide other protectivemeasures to contain dust and debris as required by EHS
regulations.
Sprinklersareconsideredtobeoperationalwhentheyare installed inaccordancewithNFPA13(spacing,
protection,distancefromtheceiling,etc.)andthereisasufficientautomaticwatersupply.
Phaseconstructionasnecessarytoensurethatexitsarenotobstructedorreduced inwidth.Ifexitsmust
beobstructed
during
construction,
provide
alternate
exit
routes
during
each
phase
of
construction
and
identifythealternateroutesontheconstructiondrawings.
Minimizeoravoiddisruptions to firealarmand sprinkler systems. Delineatephasingof construction to
ensurethat installationsofnewsystemsareexpedited,andwherepossible,maintainexistingsystems in
serviceuntilthereplacementsystemisoperational.
c) Stopwork:Theconsultantsandthemaincontractorsshallberesponsibleforensuringthattheconstruction
ofbuildings, facilitiesor structures is carriedout in compliancewith the required standards.They shall
immediately stop the work when contrary is observed in order to (i) correct any deviation from the
requirementsofEHSFireDept./AHJand(ii)correctorabateanunsafeconditionposingsignificantriskof
fire,explosionoraccident.
d) Theconstructionworkthat isnot inconformancewiththerequirementsofEHSFireDept./AHJshallbesubjecttorectificationwhichmayincludestoppageoftheworkanddemolition.
e) Removal of Construction Debris: The consultants, Contractors& Subcontractors shall ensure that all
hazardous,Combustibleand flammableconstructiondebrisare removedregularly fromconstructionsite
anddisposedofinaccordancewiththerequirementofEHSDept.
5) Temporary buildings, facilities or structures at construction sites for the use of offices and labour
accommodation:
a) Writtenrequestforapprovalofconstructionoftemporarybuildings,facilitiesorstructuresatconstructionsitesshallbesubmittedtoEHSFireDept.
b) EHSFireDeptreservestherighttoapprovesuchbuildings,facilitiesorstructures.
(Referto
Appendix
12).
6) Covered temporary structures Enclosed tents normally used for events/activities such as stage shows,
concerts,circus,exhibitions,tradefairs,sportingevents&celebratoryfunctions:
a) WrittenrequestforapprovalforconstructionoftemporarystructuresshallbesubmittedtoEHSFireDept.
b) EHSFireDeptreservestherighttoapprovesuchstructures.(RefertoAppendix13)
7) MarinasandBoatyards:
a) MarinecraftshallcomplywiththelawsoftheUAEandNFPA302FireProtectionStandardforPleasureandCommercialMotorCraft.
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
22/167
- 18 - - 18 -
b) Allboatsanddockingareasshallbeequippedwithportablefireextinguishers. Thenumberandtypeof
extinguishersshallbeasspecifiedinNFPA302.
c) Smokedetectorsshallbeprovidedonboatshavingsleepingquarters.
d) Allinboardpoweredboatswithanenclosedenginecompartmentshallhaveafiresuppressionsystemintheenginespace.
e) Watersupplyforfireprotectioninmarinas,piers,andboatyardsshallbeprovidedinaccordancewiththelatesteditionsofNFPA13StandardfortheInstallationofSprinklerSystems,NFPA14Standardforthe
InstallationofStandpipesandHoseSystems,andNFPA24StandardfortheInstallationofPrivateFire
ServiceMainsandTheirAppurtenances.
f) Standpipesshall
be
provided
for
piers
or
marine
docks
where
the
hose
lay
from
the
responding
fire
apparatusisinexcessof150feetlongperNFPA303FireProtectionStandardforMarinasandBoatyards,
orwheredeemednecessarybyEHSFireDept
RelevantprovisionsofNFPA303shallapply. Also,relevantEHSregulationsshallapply.
8) MarineTerminals,PiersandWharves:
RelevantprovisionsofNFPA307shallapply.Also,relevantEHSregulationsshallapply.
9) QualityAssuranceDuringConstruction
RelevantprovisionsofNFPA5000shallapply.
GuidelineNote:
Relevant
chapters
of
NFPA
5000
dealing
with
energy
efficiency,
Elevators
and
conveying
system,
Plumbing
system, Exterior wall construction, Interior Environment, High Hazard Contents, Structural Design; Soils,
FoundationsandRetainingWalls,RoofAssembliesandRoofStructures,FloorResistantDesign&construction,
Encroachments into thepublicRightofway, concrete,Aluminum,Masonry, Steel,WoodGlassandGlazing;
GypsumBoard,LathandPlasterandPlasticsshallapply.
10)PerformanceBasedDesign(PBD):
a) RelevantprovisionsofNFPA101andNFPA5000shallapply.
b) Performancebasedfiresafetydesignmethodsshallbeappliedtotherenovation,restoration,remodeling
ormodernization of existing facilities to address the evaluation of a sub system, system or complete
buildingwhenitisnotpossibletomeettheprovidedprescriptiverequirementsfornewconstruction.
c) Newbuildings,
facilities
or
structures
for
which
established
prescriptive
NFPA
code
criteria
exist
shall
not
be
permittedtouseperformancebasedfireandlifesafetydesignmethods.
d) Performancebased fire safety design methods may be permitted by EHSFire Dept / AHJ for uniquefacilitieswhere the usermandates requirements and objectives that are not addressed by established
prescriptiverequirementsofNFPAcodesortheseregulations.
e) PerformancebasedfiresafetydesignmethodsshallnotbeusedtoeliminaterequiredexitingrequirementsnorshallitbeusedtoeliminateautomaticsprinklersystemsrequiredbyrelevantNFPAcodes.
f) Performancebased fire safetydesign report shallbepreparedby theconcerned fireprotectionexpert /specialist indicating that thebuilding, facilityor structurewasdesignedusing a performancebased fire
safetydesignapproachasmaypermittedbyEHSFireDept/AHJ. Itshallconvey theexpectedhazards,
risksand systemperformanceover theentirebuilding lifecycle. It shallalso include theproject scope,
designgoals
and
objectives,
performance
criteria,
design
fire
scenarios,
critical
design
assumptions,
critical
design features, final design, design engineers qualifications & capabilities and data and evaluation
methodreferences.(RefertoFireDeptforrelevantproceduretobefollowed).
11)StandbyPower
a) A standby emergency / electric generator shall be installed to provide power to staircase, emergencylightingsystemsfirelifts,firepumps,pressurizationfanandblowers,smokeextractionanddampersystem
incaseoffailureofnormalelectricalsupply.Thegeneratorshallbecapableoftakingstartingcurrentofall
themachinesandcircuitsstatedabovesimultaneously.
b) RelevantprovisionsofNFPA101,110&NFPA111shallapply.
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
23/167
- 19 - - 19 -
12)Basements
a) RelevantprovisionsofNFPA5000includingthatofundergroundspacesshallapply.
b) Thebasementshallnotbenormallyusedforresidentialpurposes.
c) Theaccesstothebasementshallbeseparatefromthemainandalternatestaircaseprovidingaccessand
exitfromhigherfloors.Wherethestaircaseisincontinuousthesameshallbeofenclosedtypeservingasa
fire separation from the basement floor and higher floors. Open ramps shall be permitted if they are
constructedwithin the building line subject to the condition that adequate arrangements aremade to
prevententryofsurfacedrainageintothebasement.
d) Eachbasement
shall
be
separately
ventilated.
The
standard
of
ventilation
shall
be
the
same
as
required
by
the particular occupancy or relevant NFPA codes. Any deficiency shall bemet by providing adequate
mechanicalventilationintheformofblowers,exhaustfans,airconditioningsystemsetc.
e) Thebasementshallnotbepartitioned.
13)ElectricalServices/Systems:
a) RelevantprovisionsofNFPA5000shallapply.
b) Theelectricaldistributioncables/wiringshallbe laid inseparateduct.Theductshallbesealedatevery
floorwithnoncombustiblematerialshavingthesamefireresistanceasthatoftheduct.
c) Watermains,telephonelines,gaspipesoranyotherservice lineshallnotbelaidintheductforelectrical
cables.
d) Separate circuits for fire and other pumps, water pumps, lifts, staircases, and corridor lighting andpressurizingsystemshallbeprovideddirectlyfromthemainswitchgearpanel.
e) AllelectricalservicesshallbesubjecttoDEWAapproval.
14)MechanicalSystems:
RelevantprovisionsofNFPA5000shallapply.
15)AirConditioning,Ventilation&SmokeManagementSystems
a) WarmAirHeatingandAirConditioning systemsshallcomplywithNFPA90Bforfollowingoccupancies:
i) One ortwo familydwellingsorii) Serve
spaces
not
exceeding
708
Cu.
M.
b) Installationof AirConditioning systemsshallcomplywithNFPA90Afor followingoccupancies:
i) ServeBuildingsofTypesIII,IVandVconstructionof heightover3storiesii) Servespacesexceeding708Cu.M.
c) SmokeExtractSystemsshallcomplywithNFPA91.d) SmokeControlSystemsshallcomplywithNFPA92A.
e) SmokeManagementSystemsshallcomplywithNFPA92B.
(RefertoAppendices14&15)
f) Standard for ventilation Control and fire protection of commercial cooking operationNFPA 96 shall be
compliedwith.
16)Transformers:
Indoor and outdoor transformers shall be installed and located in accordance with the requirements /
standardsofDubaiElectricityandWaterAuthority(DEWA)
17)StationeryCombustionEngines,GasTurbinesandGenerators:
Engines,gasturbinesandgeneratorsshallbeinstalledinaccordancewiththerequirementofNFPA37.
18)GasService:
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
24/167
- 20 - - 20 -
GasservicemainsshallbeinstalledinaccordancewiththerequirementsofNFPA54andNFPA58GasService
mains shall not be permitted within the perimeter of foundation lines. Natural draft cross ventilation for
buildingcrawlspacescontaininggasservicepipingshallbeprovided.Supplyconnectionsfromthegasservice
mainsabovegradeoutsidethefoundationwallshallberaisedandpassedthroughafullswingjointorloopof
metallictubingbeforeenteringthebuilding.Thiswillavoidpiperuptureintheeventofdifferentialsettlement
or earthquake. Pressure regulators shall be located outside of buildings or vent to the outside. Refer to
Appendix 16.
19)InformationTechnologyFacilities:
a) Inaddition
to
compliance
with
NFPA
75,
mission
critical
IT
spaces,
research
laboratories,
and
other
operations vital to stakeholders/owner shall be protected by the following active and passive fire
protectionmeasures:
i. 2hourfireratedenclosures.
ii. Veryearlywarningsmokedetection.
iii. Cleanagentfiresuppressionsystemorotherapprovedactivesystem.
iv. Cleanagent,watermist,orCO2portablefireextinguisherandonewaterextinguisherforclassAfires.
v. Asignshallbelocatedadjacenttoeachfireextinguishertoplainlyindicatethetypeoffireforwhichitisintended.
vi. Drychemicalfireextinguishersshallnotbepermitted.
b) Combustiblestorage,suchaspaperstock, inks,andunusedrecordingmediawithinthecomputerroom
shallbe
restricted
to
the
minimum
necessary
for
efficient
operations,
and
shall
be
stored
in
closed
metal
cabinets.
c) LAN rooms and similar second tier IT spaces shallbeenclosedwith1hour fire rated construction,be
protectedwithsprinklersandsmokedetection,andkeptfreeofcombustiblestorage.
d) Where trash receptacles are specified as part of the design only noncombustible containers shall be
specified.
20) UtilityRooms,ShopAreasandIncidentalUseSpaces
a) Combustiblematerials(e.g.,lumber,plastic,mountingboards,etc.)shallnotbestockpiledinshopareas,
butshallbestored indesignatedstorageareas. Theseareasshallbeseparatedfromadjacentspacesby
1hour fireratedconstructionandprotectedwith firesuppressionsystemsdesignedspecifically forthe
fuelloadandstorage
b)
c) .econfiguration.
d) Unsprinkleredstorageroomsandsprinkleredstorageroomsover100sq.ft.(9.3sqm)shallbeenclosed
with1hourratedfirebarriers.
e) IncidentalUseareasshallbeenclosedwithratedbarriersasrequiredbyapplicablecodesandstandards.IneachcasethemostrestrictiverequirementofNFPAcodesandthese regulations shall be followed.
21.TrashDumpsters
Iflocatedinsideorwithin30feet(10m)ofabuilding,trashdumpstersshallbeplacedwithina2hourfire
ratedroomandprotectedwithautomaticsprinklers.
22.Laboratoriesa) Designoflaboratories shallbeinaccordancewiththerequirementsoftheIBC,NFPA45.
b) All designs for laboratory spaces shall follow the lab unit approach as defined in NFPA 45. Wherequantitiesofhazardousmaterialsstoredwithin labunitscanbeshowntoalsocomplywiththecontrol
arearequirementsofNFPA45shallapply.
c) Wherethequantitiesofhazardousmaterialsand/orthenumberoflabunitsonagivenlevelofabuildingexceedthelimitationsestablished,therequirementsofNFPA45shallgovernthedesign.
d) InallcasesthesprinklersystemrequirementsofNFPA45shallbefollowedforlaboratories.
e) Limitationson allowablequantitiesof corrosives, toxic chemicals, andotherhazardous materials,not
addressedbyNFPA45shallcomplywiththerequirementsoftheInternationalBuildingCode(IBC)
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
25/167
- 21 - - 21 -
23. FlammableandCombustibleLiquidsa) Thestorageandhandlingofflammableandcombustibleliquidsshallcomplywith NFPA30Flammableand
CombustibleLiquidsCode,andthefollowingrequirements:
i. Flammable liquid storageareas shallbe separated fromotherareasbybarriershavingaminimum2hourfirerating.
ii.Insprinklered flammable/combustible liquidsstorageareas,containmentmeasures fortheanticipated
sprinkler system discharge shall be considered, in addition to the requirements of diking, remote
impounding,andothercontainmentmeasures.
24. AnimalHousingFacilitiesa) AllAnimalHousingFacilities[ifandwherepermitted]shallcomplywithNFPA150,StandardonFireand
LifeSafetyinAnimalHousingFacilities.
b) AFireProtection/Life SafetyBasisofDesignnarrative shallbeprepared foreach renovationandnewconstructionprojectthataffectsanimalhousingfacilities. Thisnarrativeshalldescribehowthefireand
lifesafetysystemscomplywithNFPA150.
c) Means of egress shall be designed to meet the special requirements of animals and/or equipment
necessaryforegress.
d) All fire protection designs shall take into consideration the animals ability to reach the equipment,
potentiallyharmingtheanimalortheanimaldamagingtheequipment.
e) All fire alarm systems shall take into account theneed for apushbutton that silences the fire alarmnotificationappliancesintheanimalareasonly,butthatactivatesasilentredbeacontoindicatethatthe
system
is
still
in
alarm.
f) Smokeexhaustsystemsshallbeperformancebasedandshalltake intoconsiderationtoxicitylevels,thetemperature,thesmokelayerheightbasedontheanimalbreathingzone,and the risks of exposure to
the animals during a fire condition.
25. CollectionStorageFacilitiesRefertoAppendix53.
26. SignboardsandNameplatesforCompanyPremises:
a) Developers/lessees/licenseesarerequiredtoerectsuitablesignboardsontheirpremisesforwhichthey
areresponsible. Thedesign,size,colouringand locationofthesignboardshallbeapprovedbyPCFCCivil
Eng.department.
b) Selfilluminated
signs
(e.g.
Neon)
are
not
normally
permitted.
c) Written request for installationof selfilluminated signs,wherejustified, shallbe submitted to EHSFireDept.
d) EHSFireDeptreservesrighttoapproveselfilluminated/neonsigns.
e) SignboardsarenotrequiredforOfficeLessees. However,OfficeLesseesarerequiredtohaveaNameplateinstalled,manufactured from3mmthickBassandgradconformingtoAmericanstandardASTMB26.This
shallbelocatedexternally,adjacenttotheofficeentrance.
f) In the event of relocating / vacating premises, all sign boards and nameplates shall be transferred /removedbythedevelopers/lessees/licensees.
27. LighteningProtection:
Thebuildingsthatshallbeprotectedbylighteningprotectionsystem(s)inaccordancewithrelevantprovisions
ofNFPA780includebutnotlimitedtothefollowing:
(a) Ordinarystructures
(b) Miscellaneousstructures,specialoccupancies&highrisebuildings
(c) Heavydutystacks(d) Structurescontaining flammablevapours, flammablegasesor liquidsthatgivesoff flammablevapours
(RefertoAppendix 17)
28. MissionCriticalFacilities:
Allmissioncriticalareasshallbe identifiedandprovidedwithspecialprotection inaccordancewithrelevant
NFPAcodes.
7/27/2019 fireprotectionfirepreventionfirecontrolregulations2010edition
26/167
- 22 - - 22 -
29. Fitoutworks/TIEINCONNECTIONSofSprinklers,Standpipes,FirePumpsandFireAlarmsystemsinRetails&
Carparkextensions:
(a) Tenants / fit out works contractor shall be obligated to induce strict compliance with relevant
provisionsofPart 2(Appendix2,Subsection3,FitoutworksRequirements)ofDubaiWorld/EHS
FireProtection,FirePrevention&FireEmergencyControlRegulations.
(b) Alltenants fitoutworksconcerning fireprotection including firealarmsystem(floorand room layoutspecific)are subject toEHSFiredepartmentapprovalandshallconform toandbecompatible
withalldesigncriteriaanddescripti