FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 1/44
FIRELEC
FIRELEC Migration Solution
EMERSON Provox™ > DeltaV™
CL Series - Using IOPs
Discrete Inputs
FMS-PVXCL-DV-1
Rev Date Subject
01 12/04/2013 First revision
02 18/07/2013 Update of cable references
03 07/03/2014 Document update
04 07/12/2016 Update of cable references
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 2/44
FIRELEC
Summary
INTRODUCTION ................................................................................................................. 3
1.1. KEY ADVANTAGES OF THE FMS-PVXCL-DV-1 SOLUTION...................................................... 4
1.2. DESCRIPTION OF THE FMS-PVXCL-DV-1 SOLUTION ............................................................ 5
1.2.1. Existing Provox architecture ........................................................................................ 5
1.2.2. Existing Provox Hardware to be removed.................................................................... 5
1.2.3. Process I/Os kept in place ........................................................................................... 6
1.2.4. New DeltaV architecture .............................................................................................. 6
DISCRETE INPUTS ............................................................................................................ 7
2.1. CL6781 / CL6783 / CL6787(CE) (SIMPLEX) CL6784 / CL6788(CE) (REDUNDANT) ............ 8
2.1.1. Description and connection .......................................................................................... 8
2.1.2. Solution : FMS-PVXCL-DV-1-DI1-A ............................................................................. 9
2.1.3. Solution : FMS-PVXCL-DV-1-DI1-B ........................................................................... 12
2.1.4. Solution : FMS-PVXCL-DV-1-DI1-C .......................................................................... 15
2.2. CL6761 / (SIMP.) / CL6762 (RED.) CL6763(CE) (SIMP.) /CL6764(CE) (RED.)................... 17
2.2.1. Description and connection ........................................................................................ 17
2.2.2. Solution : FMS-PVXCL-DV-1-DI2-A ........................................................................... 18
2.2.3. Solution : FMS-PVXCL-DV-1-DI2-B ........................................................................... 20
2.2.4. Solution : FMS-PVXCL-DV-1-DI2-C .......................................................................... 23
2.3. CL6343(CE) (SIMPLEX / REDUNDANT) - IS (EX) .............................................................. 26
2.3.1. Description and connection ........................................................................................ 26
2.3.2. Solution : FMS-PVXCL-DV-1-DI3-A ........................................................................... 27
2.3.3. Solution : FMS-PVXCL-DV-1-DI3-B ........................................................................... 31
2.4. CL6344(CE) (SIMPLEX / REDUNDANT) - IS (EX) .............................................................. 35
2.4.1. Description and connection ........................................................................................ 35
2.4.2. Solution : FMS-PVXCL-DV-1-DI4-A ........................................................................... 36
2.5. CL6301-3(CE) (SIMPLEX / REDUNDANT) - IS (EX) ........................................................... 38
2.5.1. Description and connection ........................................................................................ 38
2.5.2. Solution : FMS-PVXCL-DV-1-DI5-A ........................................................................... 39
2.6. CL6301-4(CE) (SIMPLEX / REDUNDANT) - IS (EX) - PULSE INPUTS ................................... 42
2.6.1. Description and connection ........................................................................................ 42
2.6.2. Solution : FMS-PVXCL-DV-1-DI6-A ........................................................................... 43
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 3/44
FIRELEC
INTRODUCTION
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 4/44
FIRELEC
The purpose of this document is to guide the user of a 20 series I/Os PROVOXTM system with the safe, efficient and easy way to migrate toward a DeltaVTM system. FIRELEC has developed a migration solution (FMS-PVXCL-DV-1) allowing to protect the existing wiring investment as the user convert from an existing PROVOX system toward the DeltaVTM system. The FMS-PVXCL-DV-1 solution is a set of new I/O panels installed in place of the existing 20 series ProvoxTM I/O panels, allowing to migrate easily the existing ProvoxTM I/Os toward a new DeltaVTM system, keeping the I/O wiring in place. The ProvoxTM I/Os connected on the existing I/O panels are kept in place and connected on a new IOPs electrically and mechanically fully compatible with existing I/Os and the new DeltaVTM I/O cards linked using suitable cables provided with each type of new IOP.
1.1. KEY ADVANTAGES OF THE FMS-PVXCL-DV-1 SOLUTION
FMS-PVXCL-DV-1 solution protects the wiring investment as the user converts from the PROVOXTM 20series system toward the DeltaVTM system of Emerson Process Management with following advantages :
1. FMS-PVXCL-DV-1 is a pre-engineered solution, ready to work without any technical rework or limitation regarding the existing capabilities of the Provox system to be migrated.
2. As the instrument wiring is not disturbed, the instrument checkout during startup is reduced to the
minimum
3. The DeltaVTM system's configuration allows for the engineering conversion to be done efficiently. The speed at which FMS-PVXCL-DV-1 solution can be implemented ensures to reduce the process downtime to the minimum.
4. All existing documentations (electrical and loop drawings, maintenance procedures, .....) remain
unchanged as the I/O labelling is strictly the same on new IOPs than on previous ProvoxTM I/O panels removed
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 5/44
FIRELEC
1.2. DESCRIPTION OF THE FMS-PVXCL-DV-1 SOLUTION
1.2.1. Existing Provox architecture
1.2.2. Existing Provox Hardware to be removed
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 6/44
FIRELEC
1.2.3. Process I/Os kept in place
1.2.4. New DeltaV architecture
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 7/44
FIRELEC
DISCRETE INPUTS
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 8/44
FIRELEC
2.1. CL6781 / CL6783 / CL6787(CE) (SIMPLEX) CL6784 / CL6788(CE) (REDUNDANT)
2.1.1. Description and connection 16 channel - Discrete input
Existing Provox architecture Panel Cable Provox card
CL6781 / CL6783 / CL6787(CE) CBL-SUBD37/SUBD37 CL6721
Existing Provox architecture
Panel Cable Provox card CL6784 / CL6788(CE) 2 x CBL-SUBD37/SUBD37 2 x CL6721
CL6784 : 4U
CL6788 : 3U
Redundancy 1:1 or 1:N
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 9/44
FIRELEC
2.1.2. Solution : FMS-PVXCL-DV-1-DI1-A
Existing Provox Panel : CL6781(Simplex) / CL6783 (S implex) / CL6784 (Redundant)
Module Description
CL6751X1-A7 Discrete input module - Dry contact connected to the signal common
CL6751X1-A8 Discrete input module - Dry contact with current limiter
Existing Provox Panel : CL6787(CE) (Simplex) / CL67 88(CE) (Redundant)
Module Description
CL6753X1-A12 Discrete input module - Dry contact with current limiter (CE version)
CL6753X1-A13 Discrete input module - Dry contact connected to the signal common (CE version)
New FIRELEC IOP : IOP-DI-01-1 (16 channels)
Description
16 channels - Discrete input termination panel with fuse for dry contact
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 10/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI1-A1 Interface unit Cable DeltaV card
IOP-DI-01-1
CBL-1097 (Shielded Round Cable)
SUB25F > HE1020 CH 1 to 16 : Cable option A
CH 17 to 32 : Cable option B
½ VE4001S2T2B5 / ½ SE4001S2T2B5 Discrete Input card, 32
channels, 24 Vdc, Dry contact,
40 pin Mass Termination block
New DeltaV architecture - FMS-PVXCL-DV-1-DI1-A2 Interface unit Cable DeltaV card
IOP-DI-01-1 CBL-PVXCL-DV-DI1-A2
CH 1 to 16 : Cable option A CH 17 to 32 : Cable option B
½ VE4001S2T2B4 / ½ SE4001S2T2B4 Discrete Input card, 32
channels, 24 Vdc, Dry contact,
Terminal block
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 11/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI1-A3 Interface unit Cable DeltaV card
IOP-DI-01-1 2 x CBL-PVXCL-DV-DI1-A3
2 x VE4031S2T2B1 / 2 x SE4031S2T2B1
Discrete Input card, 8 channels,
24 Vdc, Dry contact, Redundant, Terminal block
New DeltaV architecture - FMS-PVXCL-DV-1-DI1-A4
Interface unit Cable DeltaV card
IOP-DI-01-1 2 x CBL-1281
(Shielded Round Cable) SUB25F > HE1016
2 x VE4001S2T2B3 / 2 x SE4001S2T2B3
Discrete Input card, 8 channels,
24 Vdc, Dry contact, 16 pin Mass Termination
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 12/44
FIRELEC
2.1.3. Solution : FMS-PVXCL-DV-1-DI1-B
Existing Provox Panel : CL6781(Simplex) / CL6783 (S implex) / CL6784 (Redundant)
Module Description
CL6751X1-A1 Discrete isolated input module - 3-32Vdc debounce (25Hz max) with external power (not powered by the panel)
CL6751X1-A2 Discrete isolated input module - 3-32Vdc Fast (10KHz) with external power (not powered by the panel)
2H10882-Y012 Discrete isolated input module - 20-65Vdc Fast (10KHz) with external power (not powered by the panel)
CL6751X1-A7 Discrete input module - Dry contact with current limiter (when mixed with some other pulse input modules on same panel)
CL6751X1-A8 Discrete input module - Dry contact (when mixed with some other pulse input modules on same panel)
Existing Provox Panel : CL6787(CE) (Simplex) / CL67 88(CE) (Redundant)
Module Description
CL6753X1-A10 Discrete isolated input module - 3-32Vdc debounce (25Hz max) ) with external power (not powered by the panel)
CL6753X1-A2 Discrete isolated input module - 3-32Vdc Fast (10KHz) ) with external power (not powered by the panel)
CL6753X1-A14 Discrete isolated input module - 20-65Vdc Fast (10KHz) ) with external power (not powered by the panel)
CL6751X1-A13 Discrete input module - Dry contact with current limiter.
CL6751X1-A12 Discrete input module - Dry contact with current limiter.
New FIRELEC IOP : IOP-DI-02-1 (16 channels)
Description
16 channels - isolated discrete input termination panel powered by 15 to 60Vdc voltage
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 13/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI1-B1 Input frequency limited at 75Hz due to the DeltaV c ard frequency limitation
Interface unit Cable DeltaV card IOP-DI-02-1
(15Vdc to 60Vdc)
Input frequency limited to 75Hz due to the DeltaV card frequency limitation.
For frequency greater than 75Hz see FMS-PVXCL-
DV-1-DI-C1
CBL-1097 (Shielded Round Cable)
SUB25F > HE1020 CH 1 to 16 : Cable option A
CH 17 to 32 : Cable option B
½ VE4001S2T2B5 / ½ SE4001S2T2B5 Discrete Input card, 32
channels, 24 Vdc, Dry contact,
40 pin Mass Termination block
New DeltaV architecture - FMS-PVXCL-DV-1-DI1-B2 Input frequency limited at 75Hz due to the DeltaV c ard frequency limitation
Interface unit Cable DeltaV card IOP-DI-02-1
(15Vdc to 60Vdc)
Input frequency limited to 75Hz due to the DeltaV card frequency limitation.
For frequency greater than 75Hz see FMS-PVXCL-
DV-1-DI-C1
CBL-PVXCL-DV-DI1-B2 CH 1 to 16 : Cable option A
CH 17 to 32 : Cable option B
½ VE4001S2T2B4 / ½ SE4001S2T2B4 Discrete Input card, 32
channels, 24 Vdc, Dry contact, Terminal block
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 14/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI1-B3 Input frequency limited at 75Hz due to the DeltaV c ard frequency limitation
Interface unit Cable DeltaV card IOP-DI-02-1
(15Vdc to 60Vdc) Input frequency limited to 75Hz due to the DeltaV
card frequency limitation. For frequency greater than 75Hz see FMS-PVXCL-
DV-1-DI-C1
2 x CBL-PVXCL-DV-DI1-B3
2 x VE4031S2T2B1 / 2 x SE4031S2T2B1
Discrete Input card, 8 channels, 24 Vdc, Dry contact, Redundant,
Terminal block
New DeltaV architecture - FMS-PVXCL-DV-1-DI1-B4 Input frequency limited at 75Hz due to the DeltaV c ard frequency limitation
Interface unit Cable DeltaV card
IOP-DI-02-1 (15Vdc to 60Vdc)
Input frequency limited to 75Hz due to the DeltaV card frequency limitation.
For frequency greater than 75Hz see FMS-PVXCL-DV-1-DI-C1
2 x CBL-1281 (Shielded Round Cable)
SUB25F > HE1016
2 x VE4001S2T2B3 / 2 x SE4001S2T2B3
Discrete Input card, 8 channels, 24 Vdc, Dry contact, 16 pin
Mass Termination
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 15/44
FIRELEC
2.1.4. Solution : FMS-PVXCL-DV-1-DI1-C
Existing Provox Panel : CL6781(Simplex) / CL6783 (S implex) / CL6784 (Redundant)
Module Description
CL6751X1-A1 Discrete isolated input module - 3-32Vdc debounce (25Hz max) with external power (not powered by the panel)
CL6751X1-A2 Discrete isolated input module - 3-32Vdc Fast (10KHz) with external power (not powered by the panel)
2H10882-Y012 Discrete isolated input module - 20-65Vdc Fast (10KHz) with external power (not powered by the panel)
CL6751X1-A7 Discrete input module - Dry contact with current limiter (when mixed with some other pulse input modules on same panel)
CL6751X1-A8 Discrete input module - Dry contact (when mixed with some other pulse input modules on same panel)
Existing Provox Panel : CL6787(CE) (Simplex) / CL67 88(CE) (Redundant)
Module Description
CL6753X1-A10 Discrete isolated input module - 3-32Vdc debounce (25Hz max) ) with external power (not powered by the panel)
CL6753X1-A2 Discrete isolated input module - 3-32Vdc Fast (10KHz) ) with external power (not powered by the panel)
CL6753X1-A14 Discrete isolated input module - 20-65Vdc Fast (10KHz) ) with external power (not powered by the panel)
CL6751X1-A13 Discrete input module - Dry contact with current limiter.
CL6751X1-A12 Discrete input module - Dry contact with current limiter.
New FIRELEC IOP : IOP-DIP-01-1 (16 channels)
Description
16 channels - pulse input termination panel
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 16/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI1-C1 Input frequency up to 10KHz for pulse inputs
Interface unit Cable DeltaV card
IOP-DIP-01-1 (15Vdc to 60Vdc)
Input frequency up to 10KHz.
4 x CBL-PVXCL-DV-DI1-C1 CH 1 to 4 : Cable option A CH 5 to 8 : Cable option B
CH 9 to 12 : Cable option C CH 13 to 16 : Cable option D
4 X VE4015 / 4 X SE4015
Pulse Input card, 4 channels,
Terminal block
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 17/44
FIRELEC
2.2. CL6761 / (SIMP.) / CL6762 (RED.) CL6763(CE) (S IMP.) /CL6764(CE) (RED.)
2.2.1. Description and connection 8 channels - Pulse inputs
Existing Provox architecture Panel Cable Provox card
CL6761 / CL6763(CE) CBL-SUBD37/SUBD37 CL6721
Existing Provox architecture
Panel Cable Provox card CL6762 / CL6764(CE) 2 x CBL-SUBD37/SUBD37 2 x CL6721
CL6762 : 4U
CL6764 : 3U
Redundancy 1:1 or 1:N
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 18/44
FIRELEC
2.2.2. Solution : FMS-PVXCL-DV-1-DI2-A
Existing Provox Panel : CL6761 / (Simplex) / CL6762 (Redundant)
Module Description
CL6751X1-A1 Pulse isolated input module - 3-32Vdc debounce (25Hz max) with external power (not powered by the panel)
CL6751X1-A2 Pulse isolated input module - 3-32Vdc Fast (10KHz) with external power (not powered by the panel)
CL6751X1-A3 Pulse isolated input module - Vortex Powered in 24Vdc by the panel
2H10882-Y012 Pulse isolated input module - 20-65Vdc Fast (10KHz) with external power (not powered by the panel)
CL6751X1-A7 Discrete input module - Dry contact with current limiter (when mixed with some other pulse input modules on same panel)
CL6751X1-A8 Discrete input module - Dry contact (when mixed with some other pulse input modules on same panel)
Existing Provox Panel : CL6763 (CE) (Simplex) / CL6 764 (CE) (Redundant)
Module Description
CL6753X1-A2 Pulse isolated input module - 3-32Vdc debounce (25Hz max) with external power (not powered by the panel)
CL6753X1-A10 Pulse isolated input module - 3-32Vdc Fast (10KHz) with external power (not powered by the panel)
CL6753X1-A11 Pulse isolated input module - Vortex Powered in 24Vdc by the panel
CL6753X1-A14 Pulse isolated input module - 20-65Vdc Fast (10KHz) with external power (not powered by the panel)
CL6753X1-A12 Discrete input module - Dry contact with current limiter (when mixed with some other pulse input modules on same panel)
CL6753X1-A13 Discrete input module - Dry contact (when mixed with some other pulse input modules on same panel)
New FIRELEC IOP : IOP-DIP-02-1 (8 channels)
Description
8 channels - pulse input termination panel
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 19/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI2-A1 Interface unit Cable DeltaV card
IOP-DIP-02-1 (For existing I/O modules
CL6751X1-A1 (1) - CL6753X1-A10 (1) CL6751X1-A2 - CL6753X1-A2 CL6751X1-A3 - CL6753X1-A11
CL6751X1-A7 (1) - CL6753X1-A13 (1) CL6751X1-A8 (1) - CL6753X1-A12 (1)
2H10882-Y012 CL6753X1-A14
(1) : With RC filter to be selected if input is dry contact
2 x CBL-PVXCL-DV-DI2-A1
2 X VE4015 / 2 X SE4015
Pulse Input card, 4 channels,
Terminal block
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 20/44
FIRELEC
2.2.3. Solution : FMS-PVXCL-DV-1-DI2-B
Existing Provox Panel : CL6781 / CL6783 (Simplex) / CL6784 (Redundant)
Module Description
CL6751X1-A5 Discrete isolated input module - 90-140Vac
Existing Provox Panel : CL6787(CE) (Simplex) / CL67 88(CE) (Redundant)
Module Description
CL6753X1-A5 Discrete isolated input module - 90-140Vac
New FIRELEC IOP : IOP-DI-03-1 (16 channels)
Description
16 channels - isolated discrete input termination panel powered by AC voltage
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 21/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI2-B1 Interface unit Cable DeltaV card
IOP-DI-03-1
CBL-1097 (Shielded Round Cable)
SUB25F > HE1020 CH 1 to 16 : Cable option A
CH 17 to 32 : Cable option B
½ VE4001S2T2B5 / ½ SE4001S2T2B5 Discrete Input card, 32
channels, 24 Vdc, Dry contact,
40 pin Mass Termination block
New DeltaV architecture - FMS-PVXCL-DV-1-DI2-B2 Interface unit Cable DeltaV card
IOP-DI-03-1 CBL-PVXCL-DV-DI2-B2
CH 1 to 16 : Cable option A CH 17 to 32 : Cable option B
½ VE4001S2T2B4 / ½ SE4001S2T2B4 Discrete Input card, 32
channels, 24 Vdc, Dry contact,
Terminal block
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 22/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI2-B3
Interface unit Cable DeltaV card
IOP-DI-03-1 2 x CBL-PVXCL-DV-DI2-B3
2 x VE4031S2T2B1 / 2 x SE4031S2T2B1
Discrete Input card, 8 channels, 24 Vdc, Dry contact, Redundant,
Terminal block
New DeltaV architecture - FMS-PVXCL-DV-1-DI2-B4
Interface unit Cable DeltaV card
IOP-DI-03-1 2 x CBL-1281
(Shielded Round Cable) SUB25F > HE1016
2 x VE4001S2T2B3 / 2 x SE4001S2T2B3
Discrete Input card, 8 channels, 24 Vdc, Dry contact, 16 pin
Mass Termination
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 23/44
FIRELEC
2.2.4. Solution : FMS-PVXCL-DV-1-DI2-C
Existing Provox Panel : CL6781 / CL6783 (Simplex) / CL6784 (Redundant)
Module Description
CL6751X1-A6 Discrete isolated input module - 180-280Vac
Existing Provox Panel : CL6787(CE) (Simplex) / CL67 88(CE) (Redundant)
Module Description
CL6753X1-A6 Discrete isolated input module - 180-280Vac
New FIRELEC IOP : IOP-DI-03-2 (16 channels)
Description
16 channels - isolated discrete input termination panel powered by AC voltage
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 24/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI2-C1 Interface unit Cable DeltaV card
IOP-DI-03-2
CBL-1097 (Shielded Round Cable)
SUB25F > HE1020 CH 1 to 16 : Cable option A
CH 17 to 32 : Cable option B
½ VE4001S2T2B5 / ½ SE4001S2T2B5 Discrete Input card, 32
channels, 24 Vdc, Dry contact, 40 pin Mass Termination block
New DeltaV architecture - FMS-PVXCL-DV-1-DI2-C2
Interface unit Cable DeltaV card
IOP-DI-03-2 CBL-PVXCL-DV-DI2-C2
CH 1 to 16 : Cable option A CH 17 to 32 : Cable option B
½ VE4001S2T2B4 / ½ SE4001S2T2B4 Discrete Input card, 32
channels, 24 Vdc, Dry contact, Terminal block
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 25/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI2-C3
Interface unit Cable DeltaV card
IOP-DI-03-2 2 x CBL-PVXCL-DV-DI2-C3
2 x VE4031S2T2B1 / 2 x SE4031S2T2B1
Discrete Input card, 8 channels, 24 Vdc, Dry contact, Redundant,
Terminal block
New DeltaV architecture - FMS-PVXCL-DV-1-DI2-C4
Interface unit Cable DeltaV card
IOP-DI-03-2 2 x CBL-1281
(Shielded Round Cable) SUB25F > HE1016
2 x VE4001S2T2B3 / 2 x SE4001S2T2B3
Discrete Input card, 8 channels,
24 Vdc, Dry contact, 16 pin Mass Termination
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 26/44
FIRELEC
2.3. CL6343(CE) (SIMPLEX / REDUNDANT) - IS (EX)
2.3.1. Description and connection 32 channels - IS (Ex) Discrete inputs
Existing Provox architecture
Panel Cable Provox card IS (Ex) CL6343(CE) (SIMPLEX) 2 x CBL-SUBD37/SUBD37 2 x CL6721
Redundancy 1:1 or 1:N
Existing Provox architecture
Panel Cable Provox card IS (Ex) CL6343(CE) (REDUNDANT) 4 x CBL-SUBD37/SUBD37 4 x CL6721
Redundancy 1:1 or 1:N
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 27/44
FIRELEC
2.3.2. Solution : FMS-PVXCL-DV-1-DI3-A
Existing Provox Panel : CL6343 / (Simplex) and (Red undant)
Module Description
CL6356 2 channels - IS (Ex) Discrete input isolated barrier - Dry contact or proximity detector (7,7 - 9,0 Vdc)
New FIRELEC IOP : FC5301-1 or FC5301-4 / (Simplex) and (Redundant) (16 slots)
Module Description
CL6356 2 channels - IS (Ex) Discrete input isolated barrier - Dry contact or proximity detector (7,7 - 9,0 Vdc)
Keeping the existing CL6356 modules installed on the new panel FC5301-1 or -4 FC5301-1 + 16 x CL6356 or FC5301-4 + 16 x CL6356 Loop agreement remains unchanged and still in use
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 28/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI3-A1 Interface unit Cable DeltaV card
FC5301-1 (1 x SUBD37)+ 16 modules CL6356 CBL-PVXCL-DV-DI3-A1
VE4001S2T2B5 / SE4001S2T2B5
Discrete Input card, 32 channels, 24 Vdc, Dry contact,
40 pin Mass Termination block
Equiped with 16 conversion modules CL6356
New DeltaV architecture - FMS-PVXCL-DV-1-DI3-A2 Interface unit Cable DeltaV card
FC5301-1 (1 x SUBD37)+ 16 modules CL6356 CBL-PVXCL-DV-DI3-A2
VE4001S2T2B4 SE4001S2T2B4
Discrete Input card, 32 channels, 24 Vdc, Dry contact,
Terminal block
Equiped with 16 conversion modules CL6356
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 29/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI3-A3 Interface unit Cable DeltaV card
FC5301-4 (4 x SUBD15) + 16 modules CL6356 CBL-PVXCL-DV-DI3-A3
4 x VE4001S2T2B3 / 4 x SE4001S2T2B3
Discrete Input card, 8 channels, 24 Vdc, Dry contact, 16 pin
Mass Termination Block
Equiped with 16 conversion modules CL6356
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 30/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI3-A4 Interface unit Cable DeltaV card
FC5301-4 (4 x SUBD15) + 16 modules CL6356 CBL-PVXCL-DV-DI3-A4
4 x VE4031S2T2B1 / 4 x SE4031S2T2B1
Discrete Input card, 8 channels, 24 Vdc, Dry contact, Redundant,
Terminal block
Equiped with 16 conversion modules CL6356
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 31/44
FIRELEC
2.3.3. Solution : FMS-PVXCL-DV-1-DI3-B
Existing Provox Panel : CL6343 / (Simplex) and (Red undant)
Module Description
CL6356 2 channels - IS (Ex) Discrete input isolated barrier - Dry contact or proximity detector (7,7 - 9,0 Vdc)
New FIRELEC IOP : FC5301-1 or -4 / (Simplex) and (R edundant) (16 slots)
Module Description
FC302 2 channels – I.S. discrete input for switch or proximity detector. Solid state output
New modules type FC302 installed on the new panel FC5301-1 or -4 FC5301-1 + 16 x FC302 or FC5301-4 + 16 x FC302 Input IS parameters have to be checked for compatibility with new FC302 barriers.
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 32/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI3-B1 Interface unit Cable DeltaV card
FC5301-1 (1 x SUBD37) + 16 modules FC302 CBL-PVXCL-DV-DI3-B1
VE4001S2T2B5 / SE4001S2T2B5
Discrete Input card, 32 channels, 24 Vdc, Dry contact,
40 pin Mass Termination block
Equiped with 16 conversion modules FC302
New DeltaV architecture - FMS-PVXCL-DV-1-DI3-B2 Interface unit Cable DeltaV card
FC5301-1 (1 x SUBD37) + 16 modules FC302 CBL-PVXCL-DV-DI3-B2
VE4001S2T2B4 / SE4001S2T2B4
Discrete Input card, 32 channels, 24 Vdc, Dry contact,
Terminal block
Equiped with 16 conversion modules FC302
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 33/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI3-B3 Interface unit Cable DeltaV card
FC5301-4 (4 x SUBD15) + 16 modules FC302 CBL-PVXCL-DV-DI3-A3
4 x VE4001S2T2B3 / 4 x SE4001S2T2B3
Discrete Input card, 8 channels, 24 Vdc, Dry contact, 16 pin
Mass Termination Block
Equiped with 16 conversion modules FC302
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 34/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI3-B4 Interface unit Cable DeltaV card
FC5301-4 (4 x SUBD15) + 16 modules FC302 CBL-PVXCL-DV-DI3-B4
4 x VE4031S2T2B1 / 4 x SE4031S2T2B1
Discrete Input card, 8 channels, 24 Vdc, Dry contact, Redundant,
Terminal block
Equiped with 16 conversion modules FC302
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 35/44
FIRELEC
2.4. CL6344(CE) (SIMPLEX / REDUNDANT) - IS (EX)
2.4.1. Description and connection 16 channels - IS (Ex) Pulse inputs
Existing Provox architecture
Panel Cable Provox card IS (Ex) CL6344(CE) (SIMPLEX) CBL-SUBD37/SUBD37 CL6721
Existing Provox architecture Panel Cable Provox card
IS (Ex) CL6344(CE) (REDUNDANT) 2 x CBL-SUBD37/SUBD37 2 x CL6721
Redundancy 1:1 or 1:N
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 36/44
FIRELEC
2.4.2. Solution : FMS-PVXCL-DV-1-DI4-A
Existing Provox Panel : CL6343 / (Simplex) and (Red undant)
Module Description
CL6358 1 channel - IS (Ex) Pulse input isolated barrier - (3,6 - 12,0 Vdc) (50KHz max)
New FIRELEC IOP : FC5301-4 / (Simplex) (16 slots)
Module Description
CL6358 1 channel - IS (Ex) Pulse input isolated barrier - (3,6 - 12,0 Vdc) (50KHz max)
Keeping the existing CL6358 installed on the new panel FC5301-4 FC5301-4 + 16 x CL6358 Loop agreement remains unchanged and still in use
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 37/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI4-A1 Input frequency up to 10KHz for pulse inputs
Interface unit Cable DeltaV card
FC5301-4 (4 x SUBD15) + 16 modules CL6358
Input frequency up to 10KHz. CBL-PVXCL-DV-DI4-A1
4 X VE4015 / 4 X SE4015
Pulse Input card, 4 channels, Terminal block
Equiped with 16 conversion modules CL6358
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 38/44
FIRELEC
2.5. CL6301-3(CE) (SIMPLEX / REDUNDANT) - IS (EX)
2.5.1. Description and connection 16 channels - IS (Ex) Discrete inputs – Dry contact and proximity switch NAMUR)
Existing Provox architecture
Panel Cable Provox card
IS (Ex) CL6301-3(CE) (SIMPLEX) CBL-SUBD37/SUBD37 CL6721
Existing Provox architecture
Panel Cable Provox card
IS (Ex) CL6301-3(CE) (REDUNDANT) 2 x CBL-SUBD37/SUBD37 2 x CL6721
Redundancy 1:1 or 1:N
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 39/44
FIRELEC
2.5.2. Solution : FMS-PVXCL-DV-1-DI5-A
Existing Provox Panel : CL6301-3 / (Simplex) and (R edundant)
Module Description
CL6302-1 1 channel - IS (Ex) Discrete input isolated barrier - Dry contact or proximity detector (NAMUR) (Power supply : 8vdc – 4mA)
CL6302-2 1 channel - IS (Ex) Discrete input isolated barrier - Proximity switch input PP 3 wires (Power supply : 18vdc – 25mA)
New FIRELEC IOP : FC5301-1 / (Simplex) and (Redunda nt) (16 slots)
Module Description
FC302 2 channels – I.S. discrete input for switch or proximity detector. Solid state output
New modules type FC302 installed on the new panel FC5301-1 FC5301-1 + 8 x FC302 Input IS parameters have to be checked for compatibility with new FC302 barriers.
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 40/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI5-A1 Interface unit Cable DeltaV card
FC5301-1 (1 x SUBD37) + 8 modules FC302 CBL-PVXCL-DV-DI5-A1
CH 1 to 16 : Cable option A CH 17 to 32 : Cable option B
½ VE4001S2T2B5 / ½ SE4001S2T2B5 Discrete Input card, 32
channels, 24 Vdc, Dry contact, 40 pin Mass Termination block
Equiped with 8 conversion modules FC302
New DeltaV architecture - FMS-PVXCL-DV-1-DI5-A2 Interface unit Cable DeltaV card
FC5301-1 (1 x SUBD37) + 8 modules FC302 CBL-PVXCL-DV-DI5-A2
CH 1 to 16 : Cable option A CH 17 to 32 : Cable option B
½ VE4001S2T2B4 / ½ SE4001S2T2B4 Discrete Input card, 32
channels, 24 Vdc, Dry contact, Terminal block
Equiped with 8 conversion modules FC302
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 41/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI5-A3 Interface unit Cable DeltaV card
FC5301-4 (4 x SUBD15) + 8 modules FC302 CBL-PVXCL-DV-DI5-A3
2 x VE4031S2T2B1 / 2 x SE4031S2T2B1
Discrete Input card, 8 channels,
24 Vdc, Dry contact, Redundant, Terminal block
Equiped with 8 conversion modules FC302
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 42/44
FIRELEC
2.6. CL6301-4(CE) (SIMPLEX / REDUNDANT) - IS (EX) - PULSE INPUTS
2.6.1. Description and connection 16 channels - IS (Ex) Pulse inputs (Fast 10KHz)
Existing Provox architecture Panel Cable Provox card
IS (Ex) CL6301-4(CE) (SIMPLEX) CBL-SUBD37/SUBD37 CL6721
Existing Provox architecture Panel Cable Provox card
IS (Ex) CL6301-4(CE) (REDUNDANT) 2 x CBL-SUBD37/SUBD37 2 x CL6721
Redundancy 1:1 or 1:N
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 43/44
FIRELEC
2.6.2. Solution : FMS-PVXCL-DV-1-DI6-A
Existing Provox Panel : CL6301-4 / (Simplex) and (R edundant)
Module Description
CL6302-3 1 channel - IS (Ex) Discrete input isolated barrier – Pulse input 10KHz (Power supply : 5 – 32Vdc ; 3 – 15mA)
New FIRELEC IOP : FC5301-4 / (Simplex) (16 slots)
Module Description
FC302 2 channels – I.S. discrete input for switch or proximity detector only . Solid state output
New modules type FC302 installed on the new panel FC5301-4 FC5301-4 + 16 x FC302 Input IS parameters have to be checked for compatibility with new FC302 barriers.
FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.
Migration_Provox_DeltaV_FMS-
PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs
Non contractual documentation – Firelec can improve the design or the specifications of the product described herein
without prior notification
FMS-PVXCL-DV-1-DI
Page 44/44
FIRELEC
New DeltaV architecture - FMS-PVXCL-DV-1-DI6-A1 Input frequency up to 3KHz for pulse inputs
Interface unit Cable DeltaV card
FC5301-4 (4 x SUBD9) + 16 modules FC302
Max Frequency up to 3KHz 4 x CBL-PVXCL-DV-DI6-A1
4 X VE4015 / 4 X SE4015
Pulse Input card, 4 channels, Terminal block
Equiped with 16 conversion modules FC302