20
Fire Protection by Water Mist Systems The view of VdS VdS 3188 Guideline for Planning and Installation Stefan Kratzmeir Head of Product Management, VdS Schadenverhuetung (Germany)

Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

  • Upload
    buicong

  • View
    243

  • Download
    4

Embed Size (px)

Citation preview

Page 1: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Fire Protection by Water Mist

Systems The view of VdS

VdS 3188 Guideline for Planning and Installation

Stefan Kratzmeir

Head of Product Management, VdS Schadenverhuetung (Germany)

Page 2: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 2

Planning & Installation (Status of Today)

Risk:

Application Rate

(Pressure / Flow):

Nozzle Spacing:

Special Restrictions:

Hydraulic Area:

Other Requirements:

Wirkfläche m²Brand-gefahren-

klasse

Mindestwasser-beaufschlagung

mm/minNaß- oder vor-

gesteuerte AnlageTrocken- oder Naß-

Trockenanlage

LH 2,25 84 Auslegung nach OH1

OH1 5,0 72 90

OH2 5,0 144 180

OH3 5,0 216 270

OH4 5,0 360 Auslegung nach HHP1

HHP1 7,5 260 325

HHP2 10,0 260 325

HHP3 12,5 260 325

HHP4 nicht zulässig nicht zulässig

Maximale Abstände in Bild 11.01

Normal-Sprinkler- anordnung

Versetzte Sprinkler- anordnung

S D S D

Brandgefahren- klasse

Maximale Schutzfläche je

Sprinkler

m2

m m m m

LH 21,0 4,6 4,6 4,6 4,6

OH 12,0 4,0 4,0 4,6 4,0

HHP und HHS 9,0 3,7 3,7 3,7 3,7

Tabelle 11.01: Maximale Schutzfläche und Abstände für Sprinkler außer Seitenwandsprinklern

Sprinkler Systems Water Mist Systems

Product Specific Planning &

Installation Guideline

VdS CEA 4001 VdS 2109

Page 3: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 3

Approved Systems - Details

All approved systems and approved

installers can be found at:

www.vds.de Certfications

General requirements and restrictions

can be seen in Annex 3 of the VdS

certificate

Page 4: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 4

Guidelines for Water Mist at VdS

Water Mist Sprinkler or Water Mist

Extinguishing System

Water Mist Extinguishing

System Water Mist Sprinkler

VdS 2109

+

Planning + Installation

Handbook of the Nozzle

VdS 3188

+

Planning + Installation

Handbook of System and

Nozzle

VdS 3188

+

Planning + Installation

Handbook of System and

Nozzle

VdS CEA 4001

+

Planning + Installation

Handbook of the Nozzle

pOperation> 16 bar pOperation > 16 bar pOperation ≤ 16 bar pOperation ≤ 16 bar

Page 5: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 5

VdS Quality System applied to Water Mist

Planning and

Installation Guidelines

Approved Installers

First and Periodic

Inspections

Approved Components and Systems

p > 16 bars: VdS 3188 p < 16 bars: VdS 4001 (Sprinkler) or VdS 2109 (Deluge)

VdS 2100-X + VdS 2562 + Individual Laboratory Test Plan

Technical Inspection Service

VdS 2132

Page 6: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 6

„New“ Fire Fighting Systems (Water Mist Systems)

Proof of Effectivness (Fire Tests)

Tests of Components and Systems in the VdS

Laboratories

Manufacturer- and System related Planning

and Installation Guidelines

Evaluation of new

technologies according

effectivness, safety and

reliability

Proofen VdS procedures

and test methods are

adapted to new

technologies

Page 7: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 7

Types of Approvals

Cable Tunnels

Machinery Spaces / Engine Test Rooms

Paint Cabins / Paint Storage / Storage of burnable

Liquids

Office and Accomodation Areas / Selected Storage

Areas

Parking Garages

Local Protection

Special Case approvals….

For latest version of fire test Procedures just contact VdS (contact details on last page)

Page 8: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 8

Drei horizontal

gestapelte Ordner

1,52 m

1,84 m

0,76 m

3,04 m

Plastikordner

Papierordner, 3 kg (vertikal)

Bücher

Papierordner, 3 kg (horizontal)

Papierordner, 2 kg (vertikal)

Zeitungen

Computer

Approval for Office Areas

Comparison with Sprinkler System

Fixed to maximum ceiling height

Standardized fire load

Applicable for:

Office Areas

Etc..

Page 9: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 9

3m ceiling height, ignition

between 4 Nozzels

Pendent spray sprinkler, 3m

ceiling height, ignition under

1 sprinkler

Approval for Office Areas: Comparison (1)

Page 10: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 10

Water Mist

Activation: 4:52 min

max. Gastemp.: 79 °C

Sprinkler

Activation: 6:27min,

max. Gastemp.: 159 °C

Approval for Office Areas: Comparison (2)

Page 11: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 11

Example for Layout for Office Areas

Sprinkler (VdS 4001) Water Mist System

Water Application Rate

5 mm/min 2 mm/min

Protection Area 72 m² 72 m²

Water Flow 5 l/min * 72 m² 2 l/min * 72 m²

Operation Time 40 min 40 min

Total Water Amount

= 5 l/min x 72 m2 x 40 min x 1,4 = 20169l für 40 min

= 2 l/min x 72 m2 x 40 min x 1,4 = 8064l für 40 min

Page 12: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 12

Extension for Office Approval

„Extenstion Accomodation“ can be

used for:

Hotel and Accomodation Areas

Hospitals,

Conference Areas

Extension Suspended Ceiling /

Floor

Page 13: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 13

Office and Storage Areas

Selected Storage Areas

(Racks and Block Storage):

Page 14: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 14

Machinery / Generator Spaces (no storage)

Engine and Machinery

Spaces

Transformers (housed)

Engine Test Cells

Turbines

Page 15: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 15

Cable Tunnels

Cable Tunnels

Page 16: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 16

Painting & Adjacent Areas

Painting Booths

Paint Mixing Areas

Paint Storage Areas

Page 17: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 17

VdS 3188

VdS 3188 – VdS Guidelines for Planning and

Installation:

Water Mist-Sprinkler and Water Mist Fire

Extinguishing Systems

Same systematic as VdS CEA 4001

For specific applications: Water Mist is regarded equal to

Sprinkler, Deluge or Gas Exinguishing Systems

VdS 3188 will include CEN TS 14972

Page 18: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 18

VdS Outlook – The new VdS 3188

VdS Planning & Installation will be published in End of 2014!

VdS 3188: Planning & Installation for Water Mist

Systems

Product related Planning & Installation (System + Nozzle)

Principle system layout (minimum requirements)

Principle design & installation for certain applications

Principles and minumum requirements for approvals and proof of effectiveness

Detail nozzle layout System pressure Detail design

Page 19: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Folie 19

Major Changes

System approvals are based on applications

OH 1

OH 2

OH 3

System approvals are based on type of pressuring method

Office, Public Space and Accomodation Areas

Parking Garages

Selected Storage and Shopping Areas

Change of standard approval description:

Hydraulic demanding area will be same systematic as in VdS CEA 4001

Page 20: Fire Protection by Water Mist Systems - IWMA ·  · 2014-10-22Fire Protection by Water Mist Systems The view of VdS ... For latest version of fire test Procedures just contact VdS

Thank you very much for your

attention!

Questions, Comments, Further assistance:

Stefan Kratzmeir: [email protected]

Christian Kopp: [email protected]