2
Lighthouse Worldwide Solutions Benelux BV Van Heemstraweg 19a NL-6657 KD Boven Leeuwen [email protected] www.golighthouse.com Specialist in Cleanroom monitoring Tel: +31-487-560811 Fax: +31-487-560013 Laminar Air Flow Box Aerosol Photometer Upstream Concentration Downstream Concentration Generator Data Acquisition Software Lighthouse Benelux mission is to provide a complete solution to all clean air industry sectors for their filter and cleanroom testing requirements. We do this by the timely supply of high quality instruments, fast and reliable repair and calibration services, supply of consumable and spare items, unrivalled training programmes, professional consultancy and technical support. The product line of DOP Solutions perfectly fits into our mission. DOP Solutions provides instrumentation for cleanroom, HEPA filter and safety cabinet testing and qualification. Aerosol photometers, aerosol generators and various auxiliaries for professional HEPA/ULPA filter testing. HEPA/UPLA test Standards and Guides: BS 3928: 1969 Sodium flame testing of HEPA filters (Eurovent 4/4) BS 5295: 1989 Environmental cleanliness in enclosed spaces BS EN1822: 2000 High Efficiency Particulate Air Filters BS EN ISO 14644-3: 2005 Test methods PD6609: 2007 Guide to in situ high efficiency filter leak testing Test Set Up Contains: Aerosol Photometer SP200-DAS-P with scanning probe Thermal Aerosol Generator DOP1100 Data Acquisition Software for test reporting Report example Sample,-injection ports Filter Test Equipment Acc. ISO 14644-3 Model 1100 Aerosol Generator Model SP200-DAS Aerosol Photometer Features Aerosol Photometer System: Aerosol Photometer SP200-DAS: 100 to 0.01 range - sensitivity is 0.00001 μg/l Zero stability better than 0.00003 μg/l suitable for DESH, Emery 3004, DOP, Ondina EL Sample 28LPM; highly reliable 24VDC pump DNS Digital Noise Suppression selectable Length 417 mm Depth 290 mm Height 143 mm DAS data logging included Adjustable audio alarm 100..240VAC Power Weight is only 9 Kg Aerosol Generator DOP1100: Concentration up to 54.000m³/hr Volume Max aerosol concentration 18gr/ltr Operates with any inert gas Precision vernier dial Dim. 435 x 195 x 346 mm Weight is 12 Kg 100..240VAC Power Laskin Nozzle Aerosol Generator SPG300: Cold Pneumatically generated aerosol Concentration up to 1350m³/hr Volume Operates with compressed air One or two Nozzles Unit with Pump available: DOP600C15 Features Data Acquisition Software: Automatic filter performance reports Data logging start/stop from Scanning Probe buttons Data exported to excel; Min, Max, average penetration Storing 25 readings per second! Software supplied as standard Auxiliaries available:

Filter Test Equipment Acc. ISO 14644-3 - Lighthouse

  • Upload
    ngominh

  • View
    408

  • Download
    14

Embed Size (px)

Citation preview

Page 1: Filter Test Equipment Acc. ISO 14644-3 - Lighthouse

Lighthouse Worldwide Solutions Benelux BV

Van Heemstraweg 19a

NL-6657 KD Boven Leeuwen

[email protected]

www.golighthouse.com

Specialist in Cleanroom monitoring

Tel: +31-487-560811

Fax: +31-487-560013

Laminar Air Flow Box

Aerosol Photometer

Upstream Concentration Downstream

Concentration Generator

Data Acquisition Software

Lighthouse Benelux mission is to provide a complete solution to all clean air industry sectors for their filter and cleanroom testing requirements. We do this by the timely supply of high quality instruments, fast and reliable repair and calibration services, supply of consumable and spare items, unrivalled training programmes, professional consultancy and technical support. The product line of DOP Solutions perfectly fits into our mission. DOP Solutions provides instrumentation for cleanroom, HEPA filter and safety cabinet testing and qualification. Aerosol photometers, aerosol generators and various auxiliaries for professional HEPA/ULPA filter testing.

HEPA/UPLA test Standards and Guides: ★ BS 3928: 1969 Sodium flame testing of HEPA filters (Eurovent 4/4) ★ BS 5295: 1989 Environmental cleanliness in enclosed spaces ★ BS EN1822: 2000 High Efficiency Particulate Air Filters ★ BS EN ISO 14644-3: 2005 Test methods ★ PD6609: 2007 Guide to in situ high efficiency filter leak testing

Test Set Up Contains: ★ Aerosol Photometer SP200-DAS-P with scanning probe ★ Thermal Aerosol Generator DOP1100 ★ Data Acquisition Software for test reporting

Report example Sample,-injection ports

Filter Test Equipment Acc. ISO 14644-3

Model 1100 Aerosol Generator Model SP200-DAS Aerosol Photometer

Features Aerosol Photometer System: Aerosol Photometer SP200-DAS: ★ 100 to 0.01 range - sensitivity is 0.00001 µg/l ★ Zero stability better than 0.00003 µg/l ★ suitable for DESH, Emery 3004, DOP, Ondina EL ★ Sample 28LPM; highly reliable 24VDC pump ★ DNS Digital Noise Suppression selectable ★ Length 417 mm Depth 290 mm Height 143 mm ★ DAS data logging included ★ Adjustable audio alarm ★ 100..240VAC Power ★ Weight is only 9 Kg

Aerosol Generator DOP1100: ★ Concentration up to 54.000m³/hr Volume ★ Max aerosol concentration 18gr/ltr ★ Operates with any inert gas ★ Precision vernier dial ★ Dim. 435 x 195 x 346 mm ★ Weight is 12 Kg ★ 100..240VAC Power

Laskin Nozzle Aerosol Generator SPG300: ★ Cold Pneumatically generated aerosol ★ Concentration up to 1350m³/hr Volume ★ Operates with compressed air ★ One or two Nozzles ★ Unit with Pump available: DOP600C15

Features Data Acquisition Software: ★ Automatic filter performance reports ★ Data logging start/stop from

Scanning Probe buttons ★ Data exported to excel; Min, Max,

average penetration ★ Storing 25 readings per second! ★ Software supplied as standard

Auxiliaries available:

Page 2: Filter Test Equipment Acc. ISO 14644-3 - Lighthouse

Lighthouse Worldwide Solutions Benelux BV

Van Heemstraweg 19a

NL-6657 KD Boven Leeuwen

[email protected]

www.golighthouse.com

Specialist in Cleanroom monitoring

Tel: +31-487-560811

Fax: +31-487-560013

Lighthouse can offer Various sets of Filter Efficiently Test equipment. HEPA & ULPA filters are installed in many Clean environments and process applications, and the method for testing them is well recognised in the ISO14644-3 standard and followed across the world. An aerosol generator is used to produce an oil aerosol that is introduced into the airstream that is going to pass through the HEPA/ULPA filter media to be tested, and a Particle Counter or Aerosol Photometer is used to measure the amount of aerosol upstream and downstream of the filter. The result gives the performance of the HEPA/ULPA filter reported and identifies if any leaks are present in the frame, seals or media. Generation of a PSL aerosol at the MPPS of the filter media is required for testing according to EN1822.

Test setup with Particle Counters contains: ★ Aerosol Generator; Model ATM226 ★ Aerosol Dilutor 1:100; Model DIL554 ★ Particle Counter; Model Solair 3100 or Solair 1100 ★ Filter scanning Probe ★ CRQWin Datalogging Software

Cleanroom Qualification Expertise

Features Aerosol and Dilution System: Aerosol Generator ATM226: ★ Generates Aerosol with patented injector nozzle ★ Uses DESH, Emery 3004, DOP, paraffin oils salt solutions

or PSL ★ No gas-source required, uses built-in pump ★ Operating time 25 hour without refill ★ 2.5gr/hour mass flow output ★ Weight is only 4.2 Kg ★ 100..240VAC Power ★ Dimensions. 200 x 280 x 175mm

Aerosol Dilutor DIL554: ★ Flow rate; 1cfm, 2cfm or 50ltr ★ Dilution factor; 1:10 of 1:100 ★ 9V Battery Power ★ Dimensions. 160 x 300 x 110mm ★ Weight is only 3.2 Kg ★ Very low pressure drop

Features Particle Counting System: Lighthouse Solair Series: ★ Sensitivity 0.1µm or 0,3µm ★ Flow rate; 1cfm, 2cfm, 50ltr or 100ltr/min ★ Up to 8 channels ★ Battery powered or mains supply ★ Printer included ★ Calibrated acc. to ISO21501-4

Features CRQWin software: ★ Automatic filter performance reports ★ ISO14644-1 reports ★ Cleanroom Recovery tests ★ Environmental conditions ★ GMP/FDA compliance ★ Wireless or Bluetooth communication option available ★ CRQWin STRUCTURED data logging of particle counter

data ★ CQRWin SUPPORT for calculations with respect to clean

room classification ★ CQRWin has a PROTOCOLL Maker to report complete

test parameters and measurements

Aerosol Generator ATM226

Dilutor DIL554

CRQWin datalogging software

Lighthouse Particle Counter

Solair Series

Laminar Air Flow Box

Dilutor

Particle

Counter

Upstream Concentration

Downstream Concentration

Generator

CRQWin Software

Particle Size Distribution DESH

Solair Series Particle

Counters

Generator ATM226 and Dilutor DIL554