    HISTORY BACKGROUND DOCUMENT IP 8-1-1

    Cooling Towers Page 1 of 1

    Rev. 0 June 1997

    THIS INFORMATION FORAUTHORIZED COMPANY USE ONLYEXXON RESEARCH AND ENGINEERING COMPANY FLORHAM PARK, N.J.

    INTERNATIONAL

    PRACTICE

    BACKGROUND HISTORY DOCUMENTATION

    FOR CORRESPONDING PARAGRAPHS OF IP 8-1-1 (REV. 0)

    R,E [H] 4.2 CTI STD WMS-112 procedures minimize the leaching of treatment chemicals.

    E [H] 5.10 Drift from cooling tower contains chemicals which can deposit locally causing corrosion. Otherspecialized concerns are fogging and freezing of water droplets escaping from tower. Lower levels can beobtained with attendant high costs.

    M,S [H] 5.14 Minimum fan stack height is to protect personnel on fan deck from reaching over top of fan.

    S,O [H] 5.18 Vent on return piping required to prevent surge due to heat exchanger tube failure of high pressurehydrocarbon causing return piping rupture. Two instances at Syncrude Refinery resulted in extensivedamage and fire.

    M,S [H] 5.21 Required egress from fan deck in emergency situations.

    R,S[H]

    5.25 Guards are needed to prevent the typically long driveshafts provided for cooling tower fans from flyingand to prevent against coupling failure.

    R,S [H] 5.28 Vibration monitor to avoid catastrophic damage caused by 20+ ft fan blades restrained only by fiberglassfan stack. Alternative for monitoring system in lieu of switch provided.

    R,S [H] 5.30 Note to highlight exposure requirements for electrical equipment.

    Notes:

    (1) Each paragraph to identify the Purpose Code(s) of the corresponding paragraph number of the applicable International Practice (IP).

    (2) The symbol [H] shall be used to denote all History Background Paragraphs which are for INFORMATION ONLY.

    http://../IP/08/080101.pdfhttp://../IP/08/080101.pdfhttp://../IP/08/080101.pdfhttp://../IP/08/080101.pdfhttp://../IP/08/080101.pdfhttp://../IP/08/080101.pdfhttp://../IP/08/080101.pdfhttp://../IP/08/080101.pdfhttp://../IP/08/080101.pdfhttp://../IP/08/080101.pdfhttp://../IP/08/080101.pdfhttp://../IP/08/080101.pdf