20
February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection, Unimin Corporation Guion Facility AFIN: 33-00002 NPDES Permit No.: AR0001899, AR0001899C, ARR153588, and ARR00B148 Dear Mr. Maloney: On December 14, 2011 and December 15, 2011, ADEQ staff Steve Johnson, Brent Walker and I performed routine compliance, industrial stormwater, construction stormwater, and construction of wastewater treatment system inspections of the above referenced facility. These inspections were conducted in accordance with the provisions of the Federal Clean Water Act, the Arkansas Water and Air Pollution Control Act, and the regulations promulgated thereunder. The compliance evaluation inspection revealed the following permit (AR0001899) violations: 1. Non-standard devices were used to measure flow at all 3outfalls (001, 010, and 011). Additionally, there was no documentation to show that flow measurement methods were within +/- 10% of true discharge. This violates Part III, Section C. Item 2. of the permit which requires that appropriate flow measurement devices and methods consistent with accepted scientific practices shall be selected and used to insure the accuracy and reliability of measurements of the volume of monitored discharges. The devices shall be installed, calibrated, and maintained to insure the accuracy of the measurements are consistent with the accepted capability of that type of device. Devices selected shall be capable of measuring flows with a maximum deviation of less than +/- 10% from true discharge rates throughout the range of expected discharge volumes and shall be installed at the monitoring point of discharge. 2. Oil and Grease, COD, and TSS monthly averages were incorrectly reported as flow weighted values on DMR’s. This violates Part IV, Item 18. of the permit which requires the “Monthly average” to be calculated as the sum of all daily discharges measured during a calendar month divided by the number of daily discharges measured during that month.

February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

February 9, 2012

Mike Maloney

Unimin Corporation

P.O. Box 29

Guion, AR 72540-0029

RE: NPDES Compliance Inspection, Unimin Corporation – Guion Facility

AFIN: 33-00002 NPDES Permit No.: AR0001899, AR0001899C, ARR153588, and

ARR00B148

Dear Mr. Maloney:

On December 14, 2011 and December 15, 2011, ADEQ staff Steve Johnson, Brent Walker and I

performed routine compliance, industrial stormwater, construction stormwater, and construction of

wastewater treatment system inspections of the above referenced facility. These inspections were

conducted in accordance with the provisions of the Federal Clean Water Act, the Arkansas Water

and Air Pollution Control Act, and the regulations promulgated thereunder.

The compliance evaluation inspection revealed the following permit (AR0001899) violations:

1. Non-standard devices were used to measure flow at all 3outfalls (001, 010, and 011).

Additionally, there was no documentation to show that flow measurement methods were

within +/- 10% of true discharge. This violates Part III, Section C. Item 2. of the permit

which requires that appropriate flow measurement devices and methods consistent with

accepted scientific practices shall be selected and used to insure the accuracy and reliability

of measurements of the volume of monitored discharges. The devices shall be installed,

calibrated, and maintained to insure the accuracy of the measurements are consistent with

the accepted capability of that type of device. Devices selected shall be capable of

measuring flows with a maximum deviation of less than +/- 10% from true discharge rates

throughout the range of expected discharge volumes and shall be installed at the monitoring

point of discharge.

2. Oil and Grease, COD, and TSS monthly averages were incorrectly reported as flow

weighted values on DMR’s. This violates Part IV, Item 18. of the permit which requires the

“Monthly average” to be calculated as the sum of all daily discharges measured during a

calendar month divided by the number of daily discharges measured during that month.

Page 2: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

Mike Maloney, Unimin Corporation – Guion Facility

February 9, 2012

Page 2

NPDES Report Page 2

3. The time and individual performing measurement was not recorded for flow measurements.

This violates Part III, Section C. Item 8. of the permit which requires that records and

monitoring information shall include:

a) The date, exact place, time and methods of sampling or measurements, and

preservatives used, if any;

b) The individuals(s) who performed the sampling or measurements;

c) The date(s) analyses were performed;

d) The individual(s) who performed the analyses;

e) The analytical techniques or methods used; and

f) The measurements and results of such analyses.

The industrial stormwater inspection revealed the following permit (ARR00B148) violations:

1. The SWPPP was not updated as required. This violates Part 4.3 of the permit which requires

the permittee to modify the SWPPP whenever there is a change in design, construction,

operation, or maintenance of any BMP which cause(s) the SWPPP to be less effective in

controlling pollutants. The following items were noted;

a. The change in the number and location of outfalls was not updated in the SWPPP.

b. There was a process water outfall and a stormwater outfall in different locations with the

same ID (Outfalls 011).

c. The SWPPP did not include water sources for the listed outfalls.

d. The SWPPP did not address all areas that were disturbed by mining activity.

Specifically, there was a disturbed area east of the northern open mining area that was

not included in the SWPPP.

2. Each stormwater outfall was not sampled twice a year as required by the permit. This

violates Part 3.7 of the permit which requires each stormwater outfall to be sampled and

analyzed separately unless an outfall has been determined to be similar in accordance with

part 3.7.1 of the permit. Part 3.5 of the permit requires the facility to monitor at least twice

within a calendar year, within the time frames specified.

3. BMP’s were not adequately maintained to keep materials from washing offsite with

stormwater. It appeared that sand from the facility had washed into a tributary of Guion

Slough near the southern part of the facility. This violates Part 6.17(a) of the permit which

requires the operator to properly operate and maintain all control (and related

appurtenances)which are installed or used by the operator to achieve compliance with the

conditions of this permit at all times.

The construction stormwater inspection revealed the following permit (ARR153588) violations:

1. The slopes of the pond under construction (Pond T) were not adequately stabilized.

Page 3: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

Mike Maloney, Unimin Corporation – Guion Facility

February 9, 2012

Page 3

NPDES Report Page 3

No violations were observed during the wastewater treatment construction inspection

(Permit #AR001899C)

The above items require your immediate attention. Please submit a written response to these

findings to the Water Division Enforcement Branch of this Department. This response should be

mailed to the address below, or e-mailed to [email protected]. This

response should contain documentation describing the course of action taken to correct each item

noted. This corrective action should be completed as soon as possible, and the written response

with all necessary documentations (i.e. photos) is due by February 21, 2012.

For additional information you may contact the Enforcement Branch by telephone at 501-682-0639

or by fax at 501-682-0910.

If I can be of assistance, please contact me at [email protected] or 870-935-7221 ext.-15.

Sincerely,

Michael B. Greenway

District 3 Field Inspector

Water Division

cc: Water Division Enforcement Branch

Water Division Permits Branch

Page 4: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

ADEQ Water NPDES Inspection AFIN: 33-00002 Permit #: AR0001899

NPDES Report Page 4

UNITED STATES ENVIRONMENTAL PROTECTION AGENCY

Washington, D.C. 20460

NPDES Compliance Inspection Report

Form Approved

OMB No. 2040-0003

Section A: National Data System Coding

Transaction Code

NPDES

Yr/Mo/Day

Inspec. Type

Inspector

Fac. Type

1 N 2 5 3 A R 0 0 0 1 8 9 9 11 12 1 1 1 2 1 4 17 18 C 19 S 20 2

Remarks

3 3 - 0 0 0 0 2 I Z A R D

Inspection Work Days

Facility Evaluation Rating

BI

QA

-------------------------------Reserved------------------------------

67

69

70 1

71

N

72

N

73

74

75

80

Section B: Facility Data Name and Location of Facility Inspected (For industrial users discharging to POTW, also

include POTW name and NPDES permit number)

Unimin Corporation

South end of Main Street

Guion, AR

Izard County

Entry Time/Date

12-14-2011 / 10:15

12-15-2011 / 10:30

Permit Effective Date

April 1, 2011

Exit Time/Date

12-14-2011 / 16:45

12-15-2011 / 17:00

Permit Expiration Date

March 31, 2016

Name(s) of On-Site Representative(s)/Title(s)/Phone and Fax Number(s)

Gary Blankenship / QC-Safety Supervisor / 870-346-5301 / fax: 870-346-5707

Other Facility Data

35.924483

-90.94013

PDS # 063367

Name, Address of Responsible Official/Title/Phone and Fax Number

Mike Maloney / Plant Manager / 870-346-5301

Unimin Corporation – Guion Facility

P.O. Box 29

Guion, AR 72540-0029

Contacted

Yes No

Section C: Areas Evaluated During Inspection (S = Satisfactory, M = Marginal, U = Unsatisfactory, N = Not Evaluated)

S Permit U

Flow Measurement M

Operations & Maintenance S

Sampling

U Records/Reports U

Self-Monitoring Program N

Sludge Handling/Disposal N

Pollution Prevention

U Facility Site Review N

Compliance Schedules N

Pretreatment N

Multimedia

S Effluent/Receiving Waters S

Laboratory U

Storm Water N

Other:

Section D: Summary of Findings/Comments (Attach additional sheets if necessary)

On December 14, 2011 and December 15, 2011 a routine compliance inspection of the Unimin Corporation – Guion Facility was conducted by ADEQ staff Steve

Johnson, Brent Walker, and Michael Greenway. This inspection revealed the following violations:

1. No documentation that flow measurement methods are within +/- 10% of true discharge.

2. Oil and Grease, COD, and TSS were incorrectly reported as flow weighted values on DMR’s.

3. The time and individual was not recorded for flow measurements.

Refer to the attached letter and report for more information.

Name(s) and Signature(s) of Inspector(s)

Michael Greenway Brent Walker

Agency/Office/Telephone/Fax

AR Dept. of Environmental Quality-Jonesboro

(870) 935-7221 ext. 15 / (870) 935-4715 (Fax)

Date

December 21, 2011

Signature of Reviewer

Agency/Office/Phone and Fax Numbers

Date

Page 5: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

ADEQ Water NPDES Inspection AFIN: 33-00002 Permit #: AR0001899

NPDES Report Page 5

SECTION A: PERMIT VERIFICATION

PERMIT SATISFACTORILY ADDRESSES OBSERVATIONS S M U NA NE

DETAILS:

1. CORRECT NAME AND MAILING ADDRESS OF PERMITTEE: Y N NA NE

2. NOTIFICATION GIVEN TO EPA/STATE OF NEW DIFFERENT OR INCREASED DISCHARGES: Refer to permit # AR0001899C. Y N NA NE

3. NUMBER AND LOCATION OF DISCHARGE POINTS AS DESCRIBED IN PERMIT: Y N NA NE

4. ALL DISCHARGES ARE PERMITTED: Y N NA NE

SECTION B: RECORDKEEPING AND REPORTING EVALUATION

RECORDS AND REPORTS MAINTAINED AS REQUIRED BY PERMIT S M U NA NE

DETAILS: 1. ANALYTICAL RESULTS CONSISTENT WITH DATA REPORTED ON DMRS: Oil and Grease, COD, TSS parameters were incorrectly

reported as flow weighted monthly averages. The permit does not specify monthly averages to be flow weighted. Y N NA NE

2. SAMPLING AND ANALYSES DATA ADEQUATE AND INCLUDE: S M U NA NE

a. DATES AND TIME(S) OF SAMPLING: Time was not recorded for flow measurements. Y N NA NE

b. EXACT LOCATION(S) OF SAMPLING: Y N NA NE

c. NAME OF INDIVIDUAL PERFORMING SAMPLING: Not recorded for flow measurements. Y N NA NE

d. ANALYTICAL METHODS AND TECHNIQUES: Y N NA NE

e. RESULTS OF CALIBRATIONS: Y N NA NE

f. RESULTS OF ANALYSES: Y N NA NE

g. DATES AND TIMES OF ANALYSES: Y N NA NE

h. NAME OF PERSON(S) PERFORMING ANALYSES: Y N NA NE

3. LABORATORY EQUIPMENT CALIBRATION AND MAINTENANCE RECORDS ADEQUATE: S M U NA NE

4. PLANT RECORDS INCLUDE SCHEDULES, DATES OF EQUIPMENT MAINTENANCE AND REPAIR: S M U NA NE

5. EFFLUENT LOADINGS CALCULATED USING DAILY EFFLUENT FLOW AND DAILY ANALYTICAL DATA: Y N NA NE

SECTION C: OPERATIONS AND MAINTENANCE

TREATMENT FACILITY PROPERLY OPERATED AND MAINTAINED S M U NA NE

DETAILS: The depth and capacity of the settling ponds has been reduced by solids buildup.

1. TREATMENT UNITS PROPERLY OPERATED: S M U NA NE

2. TREATMENT UNITS PROPERLY MAINTAINED: Settling ponds were full of sand / solids. S M U NA NE

3. STANDBY POWER OR OTHER EQUIVALENT PROVIDED: S M U NA NE

4. ADEQUATE ALARM SYSTEM FOR POWER OR EQUIPMENT FAILURES AVAILABLE: S M U NA NE

5. ALL NEEDED TREATMENT UNITS IN SERVICE: S M U NA NE

6. ADEQUATE NUMBER OF QUALIFIED OPERATORS PROVIDED: S M U NA NE

7. SPARE PARTS AND SUPPLIES INVENTORY MAINTAINED: S M U NA NE

8. OPERATION AND MAINTENANCE MANUAL AVAILABLE: Y N NA NE

9. STANDARD OPERATING PROCEDURES AND SCHEDULES ESTABLISHED: Y N NA NE

10. PROCEDURES FOR EMERGENCY TREATMENT CONTROL ESTABLISHED: Y N NA NE

11. HAVE BYPASSES/OVERFLOWS OCCURRED AT THE PLANT OR IN THE COLLECTION SYSTEM IN THE LAST YEAR: Y N NA NE

12. IF SO, HAS THE REGULATORY AGENCY BEEN NOTIFIED: Y N NA NE

13. HAS CORRECTIVE ACTION BEEN TAKEN TO PREVENT ADDITIONAL BYPASSES/OVERFLOWS: Y N NA NE

14. HAVE ANY HYDRAULIC OVERLOADS OCCURRED AT THE TREATMENT PLANT: Y N NA NE

15. IF SO, DID PERMIT VIOLATIONS OCCUR AS A RESULT: Y N NA NE

Page 6: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

ADEQ Water NPDES Inspection AFIN: 33-00002 Permit #: AR0001899

NPDES Report Page 6

SECTION D: SAMPLING

PERMITTEE SAMPLING MEETS PERMIT REQUIREMENTS S M U NA NE

DETAILS:

1. SAMPLES TAKEN AT SITE(S) SPECIFIED IN PERMIT: Y N NA NE

2. LOCATIONS ADEQUATE FOR REPRESENTATIVE SAMPLES: Y N NA NE

3. FLOW PROPORTIONED SAMPLES OBTAINED WHEN REQUIRED BY PERMIT: Y N NA NE

4. SAMPLING AND ANALYSES COMPLETED ON PARAMETERS SPECIFIED IN PERMIT: Y N NA NE

5. SAMPLING AND ANALYSES PERFORMED AT FREQUENCY SPECIFIED IN PERMIT: Y N NA NE

6. SAMPLE COLLECTION PROCEDURES ADEQUATE: Y N NA NE

a. SAMPLES REFRIGERATED DURING COMPOSITING: Y N NA NE

b. PROPER PRESERVATION TECHNIQUES USED: Y N NA NE

c. CONTAINERS AND SAMPLE HOLDING TIMES CONFORM TO 40 CFR 136: Y N NA NE

7. IF MONITORING IS PERFORMED MORE OFTEN THAN REQUIRED ARE RESULTS REPORTED ON THE DMR: Y N NA NE

SECTION E: FLOW MEASUREMENT

PERMITTEE FLOW MEASUREMENT MEETS PERMIT REQUIREMENTS S M U NA NE

DETAILS: No documentation that flow measurement methods are accurate within +/- 10% of true discharge. 1. PRIMARY FLOW MEASUREMENT DEVICE PROPERLY INSTALLED AND MAINTAINED: TYPE OF DEVICE: Pipe and channels. Y N NA NE

2. FLOW MEASURED AT EACH OUTFALL AS REQUIRED: Y N NA NE

3. SECONDARY INSTRUMENTS (TOTALIZERS, RECORDERS, ETC.) PROPERLY OPERATED AND MAINTAINED: Y N NA NE

4. CALIBRATION FREQUENCY ADEQUATE: Y N NA NE

5. RECORDS MAINTAINED OF CALIBRATION PROCEDURES: Y N NA NE

6. CALIBRATION CHECKS DONE TO ASSURE CONTINUED COMPLIANCE: Y N NA NE

7. FLOW ENTERING DEVICE WELL DISTRIBUTED ACROSS THE CHANNEL AND FREE OF TURBULENCE: Y N NA NE

8. FLOW MEASUREMENT EQUIPMENT ADEQUATE TO HANDLE EXPECTED RANGE OF FLOW RATES: Y N NA NE

9. HEAD MEASURED AT PROPER LOCATION: Y N NA NE

SECTION F: LABORATORY

PERMITTEE LABORATORY PROCEDURES MEET PERMIT REQUIREMENTS S M U NA NE

DETAILS: 1. EPA APPROVED ANALYTICAL PROCEDURES USED (40 CFR 136.3 FOR LIQUIDS, 503.8(B) FOR SLUDGES) : Y N NA NE

2. IF ALTERNATIVE ANALYTICAL PROCEDURES ARE USED, PROPER APPROVAL HAS BEEN OBTAINED: Y N NA NE

3. SATISFACTORY CALIBRATION AND MAINTENANCE OF INSTRUMENTS AND EQUIPMENT: Y N NA NE

4. QUALITY CONTROL PROCEDURES ADEQUATE: Y N NA NE

5. DUPLICATE SAMPLES ARE ANALYZED >10% OF THE TIME: Y N NA NE

6. SPIKED SAMPLES ARE ANALYZED >10% OF THE TIME: Y N NA NE

7. COMMERCIAL LABORATORY USED: Y N NA NE

a. LAB NAME: Arkansas Testing Laboratories

b. LAB ADDRESS: 3301 Langley Dr., Searcy, AR, 72143

c. PARAMETERS PERFORMED: Oil and Grease, COD, TSS, and pH

8. BIOMONITORING PROCEDURES ADEQUATE: Y N NA NE

a. PROPER ORGANISMS USED: Y N NA NE

b. PROPER DILUTION SERIES FOLLOWED: Y N NA NE

c. PROPER TEST METHODS AND DURATION: Y N NA NE

d. RETESTS AND/OR TRE PERFORMED AS REQUIRED: Y N NA NE

Page 7: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

ADEQ Water NPDES Inspection AFIN: 33-00002 Permit #: AR0001899

NPDES Report Page 7

SECTION G: EFFLUENT/RECEIVING WATERS OBSERVATIONS

BASED ON VISUAL OBSERVATIONS ONLY S M U NA NE

DETAILS: Effluent appeared to be good.

OUTFALL #: OIL SHEEN GREASE TURBIDITY VISIBLE FOAM FLOATING SOLIDS COLOR OTHER

001 None None Low Low None Clear / Green --

010 None None Low None None Clear

011 None None Low None None Clear / Green

SECTION H: SLUDGE DISPOSAL

SLUDGE DISPOSAL MEETS PERMIT REQUIREMENTS S M U NA NE

DETAILS: No sludge in treatment process.

1. SLUDGE MANAGEMENT ADEQUATE TO MAINTAIN EFFLUENT QUALITY: S M U NA NE

2. SLUDGE RECORDS MAINTAINED AS REQUIRED BY 40 CFR 503: S M U NA NE

3. FOR LAND APPLIED SLUDGE, TYPE OF LAND APPLIED TO: (E.G., FOREST, AGRICULTURAL, PUBLIC CONTACT SITE):

SECTION I: SAMPLING INSPECTION PROCEDURES SAMPLE RESULTS WITHIN PERMIT REQUIREMENTS S M U NA NE

DETAILS: 1. SAMPLES OBTAINED THIS INSPECTION: Y N NA NE

2. TYPE OF SAMPLE: GRAB: COMPOSITE: METHOD: FREQUENCY:

3. SAMPLES PRESERVED: Y N NA NE

4. FLOW PROPORTIONED SAMPLES OBTAINED: Y N NA NE

5. SAMPLE OBTAINED FROM FACILITY'S SAMPLING DEVICE: Y N NA NE

6. SAMPLE REPRESENTATIVE OF VOLUME AND NATURE OF DISCHARGE: Y N NA NE

7. SAMPLE SPLIT WITH PERMITTEE: Y N NA NE

8. CHAIN-OF-CUSTODY PROCEDURES EMPLOYED: Y N NA NE

9. SAMPLES COLLECTED IN ACCORDANCE WITH PERMIT: Y N NA NE

SECTION J: STORM WATER POLLUTION PREVENTION PLAN STORM WATER MANAGEMENT MEETS PERMIT REQUIREMENTS S M U NA NE

DETAILS: A separate inspection report was included for the industrial stormwater permit ARR00B148.

1. SWPPP UPDATED AS NEEDED: DATE OF LAST UPDATE: 09/15/2009. - Site map did not reflect current conditions at the site. Y N NA NE

2. SITE MAP INCLUDING ALL DISCHARGES AND SURFACE WATERS: Y N NA NE

3. POLLUTION PREVENTION TEAM IDENTIFIED: Y N NA NE

4. POLLUTION PREVENTION TEAM PROPERLY TRAINED: Y N NA NE

5. LIST OF POTENTIAL POLLUTANT SOURCES: Y N NA NE

6. LIST OF POTENTIAL SOURCES AND PAST SPILLS AND LEAKS: Y N NA NE

7. ALL NON-STORM WATER DISCHARGES ARE AUTHORIZED: Y N NA NE

8. LIST OF STRUCTURAL BMPS: Y N NA NE

9. LIST OF NON-STRUCTURAL BMPS: Y N NA NE

10. BMPS PROPERLY OPERATED AND MAINTAINED: Not adequately maintained. It appeared that mined material had left the site. Y N NA NE

11. INSPECTIONS CONDUCTED AS REQUIRED: Y N NA NE

Page 8: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

ADEQ Water NPDES Inspection AFIN: 33-00002 Permit #: AR0001899

NPDES Report Page 8

DMR Calculation Check

Reporting Period: From

2011 01 01 To 2011 01 31

Year Month Day Year Month Day

Parameter Checked:

TSS -

Outfall 009A

Concentration

Monthly

Mo. Avg. - mg/L Daily Max - mg/L

Reported Value: 14.90 45.0

Calculated Value: 21.75 45.0

Permit Value: 20 30

If calculated value does not equal reported value, explain:

Not Equal. The facility is reporting a monthly flow weighted average for COD, TSS, and Oil

and Grease parameters. A non-compliance report (NCR) was submitted for exceeding the

TSS daily maximum, however the TSS monthly average was calculated incorrectly was not

reported on the NCR for exceeding the permit value. The data used for these calculations is

shown in photo #1 at the end of this report.

Page 9: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

ADEQ Water NPDES Inspection AFIN: 33-00002 Permit #: AR0001899

NPDES Report Page 9

DMR Calculation Check

Reporting Period: From 2011 09 01 To 2011 09 30

Year Month Day Year Month Day

Parameter Checked:

COD –

Outfall 010A

Concentration

Monthly

Mo. Avg. - mg/l Daily Max - mg/L

Reported Value: 2.0 2.0

Calculated Value: 2.0 2.0

Permit Value: 50 75

If calculated value does not equal reported value, explain: Equal

Page 10: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

ADEQ Water NPDES Inspection AFIN: 33-00002 Permit #: AR0001899

NPDES Report Page 10

Water Division NPDES Photographic Evidence Sheet

Location: Unimin Corporation – Guion Facility

Photographer: Michael Greenway Witness: Brent Walker

Photo # 1 Of 5 Date: 12/15/2011 Time: 12:03

Description: A monthly summary (January 2011) showing how oil and grease, TSS, and COD, are flow

weighted.

Photographer: Michael Greenway Witness: Brent Walker

Photo # 2 Of 5 Date: 12/15/2011 Time: 12:03

Description: Flow measurement records did not include a time or the individual who took the measurements.

Page 11: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

ADEQ Water NPDES Inspection AFIN: 33-00002 Permit #: AR0001899

NPDES Report Page 11

Water Division NPDES Photographic Evidence Sheet

Location: Unimin Corporation – Guion Facility

Photographer: Michael Greenway Witness: Brent Walker

Photo # 3 Of 5 Date: 12/15/2011 Time: 15:32

Description: Treated wastewater leaving the facility through outfall 001. The height of the water entering the

metal channel is used to measure flow.

Photographer: Michael Greenway Witness: Brent Walker

Photo # 4 Of 5 Date: 12/15/2011 Time: 15:38

Description: Outfall 001 is shown in the top right of photo. Treated wastewater flows into Rocky Bayou and

then into White River. No evidence of sand from the facility was observed past the outfall.

Page 12: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

ADEQ Water NPDES Inspection AFIN: 33-00002 Permit #: AR0001899

NPDES Report Page 12

Water Division NPDES Photographic Evidence Sheet

Location: Unimin Corporation – Guion Facility

Photographer: Michael Greenway Witness: Brent Walker

Photo # 5 Of 5 Date: 12/15/2011 Time: 15:37

Description: Downstream of outfall 001 where treated wastewater enters Rocky Bayou and White River. No

evidence of sand from the facility was observed in the receiving streams.

Page 13: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

C:\Documents and Settings\allen-daniel\Local Settings\Temporary Internet Files\Content.Outlook\PMWGGM81\GU_SW Compliance Response 2-21-12.DOC

4000 Baker Road · Ottawa, IL 61350 (Phone) 815/434-4178 · (Fax) 815/434-3828 February 21, 2012 Water Division Enforcement Branch Arkansas Department of Environmental Quality 5301 Northshore Drive North Little Rock, AR 72118-5317 RE: Compliance Inspection December 14-15, 2011 – Unimin Corporation Guion Plant NPDES Permit No. AR0001899, AR0001899C, ARR153588, and ARR00B148

AFIN: 33-00002 Dear Mr. Greenway: In response to the Compliance Inspection on December 14-15, 2011 please note the following. The areas of concern are listed with Unimin’s response in italics. Permit AR0001899 1. Non-standard devices were used to measure flow at a1l 3 0utfalls (001, 010, and 011).

Additionally, there was no documentation to show that flow measurement methods were within +/- 10% of true discharge. This violates Part III, Section C. Item 2. of the permit which requires that appropriate flow measurement devices and methods consistent with accepted scientific practices shall be selected and used to insure the accuracy and reliability of measurements of the volume of monitored discharges. The devices shall be installed, calibrated, and maintained to insure the accuracy of the measurements are consistent with the accepted capability of that type of device. Devices selected shall be capable of measuring flows with a maximum deviation of less than +/- 10% from true discharge rates throughout the range of expected discharge volumes and shall be installed at the monitoring point of discharge. Unimin operated the Outfalls OO1 and O11 believing that they were Parshall flumes which can be measured with an accuracy of +/-10%. Following a discussion with ADEQ, ADEQ has advised that the discharge structures are not Parshall flumes. Unimin believes that the structures are a standard open channel and by using the correct calculation, the accuracy of +/- 10% will be met to be in compliance with the regulations. For Outfall 010, the California pipe method has been used for some time, but this will be replaced with either a Parshall flume or an open channel which can be measured with the required accuracy. This replacement will take place by May 1, 2012.

2. Oil and Grease, COD, and TSS monthly averages were incorrectly reported as flow weighted values on

DMR's. This violates Part IV, Item 18 of the permit which requires the "Monthly average" to be calculated as the sum of all daily discharges measured during a calendar month divided by the number of daily discharges measured during that month.

Environmental Affairs

Page 14: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

C:\Documents and Settings\allen-daniel\Local Settings\Temporary Internet Files\Content.Outlook\PMWGGM81\GU_SW Compliance Response 2-21-12.DOC

Unimin has corrected the methodology of reporting the “Monthly Average” starting in December 2011 and will continue to report these values correctly in the future.

3. The time and individual performing measurement was not recorded for flow measurements. This violates

Part III, Section C. Item 8 of the permit which requires that records and monitoring information shall include: a) The date, exact place, time and methods of sampling or measurements, and preservatives used, if any; b) The individual(s) who performed the sampling or measurements: c) The date(s) analyses were performed; d) The individual(s) who performed the analyses; e) The analytical techniques or methods used; and f) The measurements and results of such analyses. The log book used to record information on the samples taken has been modified to include the items in a) and b) in the above section of the permit. All required information will be recorded for all future samples.

Permit ARR00B148 1. The SWPPP was not updated as required. This violates Part 4.3 of the permit which requires the

permittee to modify the SWPPP whenever there is a change in design, construction, operation, or maintenance of any BMP which cause(s) the SWPPP to be less effective in controlling pollutants. The following items were noted; a) The change in the number and location of outfalls was not updated in the SWPPP. b) There was a process water outfall and a stormwater outfall in different locations with the same ID

(Outfalls 011). c) The SWPPP did not include water sources for the listed outfalls. d) The SWPPP did not address all areas that were disturbed by mining activity. Specifically, there was a

disturbed area east of the northern open mining area that was not included in the SWPPP. Unimin has scheduled a site inspection in March 2012 to review the items listed above and will then modify the SWPPP by April 15, 2012 to meet the requirements in the permit.

2. Each stormwater outfall was not sampled twice a year as required by the permit. This violates Part 3.7 of

the permit which requires each stormwater outfall to be sampled and analyzed separately unless an outfall has been determined to be similar in accordance with part 3.7.1 of the permit. Part 3.5 of the permit requires the facility to monitor at least twice within a calendar year, within the time frames specified.

Unimin will sample all outfalls twice per year as required in the permit. This will be reflected in the next annual report to be submitted in January of 2013.

3. BMP's were not adequately maintained to keep materials from washing offsite with stormwater. It

appeared that sand from the facility had washed into a tributary of Guion Slough near the southern part of the facility. This violates Part 6.17(a) of the permit which requires the operator to properly operate and maintain all control (and related appurtenances) which are installed or used by the operator to achieve compliance with the conditions of this permit at all times.

Page 15: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

C:\Documents and Settings\allen-daniel\Local Settings\Temporary Internet Files\Content.Outlook\PMWGGM81\GU_SW Compliance Response 2-21-12.DOC

Unimin will maintain and operate this BMP and others as required in the permit, and will perform any necessary upgrades and maintenance. These modifications will be completed by April 15, 2012. However, Unimin feels that at least some, if not all, of the material seen in the tributary of Guion Slough near the southern part of the facility was deposited there by backwater coming up from the White River during one of the recent large floods.

Permit ARR153588 1. The slopes of the pond under construction (Pond T) were not adequately stabilized.

Unimin understands that stabilization of the side slopes needed to occur as soon as practicable and since the stabilization method was to seed the slopes this was scheduled to occur within two weeks of the project being completed. Unimin did not view the project as being completed in sections and therefore did not feel that stabilization of a section was necessary. After discussing this with ADEQ following receipt of this compliance letter, Unimin understands that applying a cooler weather cover crop as an intermediate stabilization step would have aided in complying with the intent of the permit.

Unimin strives to comply with environmental regulations and is very proactive in maintaining compliance at its facilities. If you have any questions, or require any additional information, please contact me at [email protected], by phone: 815/431-2205, or at the above address. Respectfully, Unimin Corporation Steve Froisland Environmental Engineer CC: M. Maloney

B. Shalter

Page 16: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

March 5, 2012 Steve Froisland Unimin Corporation 4000 Baker Road Ottawa, IL 61350 RE: NPDES Permit No.: AR001899, AR0001899C, ARR53588, and AR00B148 AFIN: 33-00002: Response to Inspection Dear Mr. Froisland: The Department has received your response to the December 14 and December 15, 2011 compliance inspections by our District Field Inspectors, Steven Johnson, Brent Walker and Michael Greenway. Your letter appears to adequately address the discrepancies identified during the inspection. The Department assumes the corrective actions taken will be maintained to ensure consistent compliance with the requirements of the permit. Acceptance of this response by the Department does not preclude any future enforcement action deemed necessary at this site or any other site. The Department will keep the inspection and response on file. If future violations occur that require enforcement action, the Department will consider the inspection and response as required by the Pollution Control and Ecology Commission Regulation No. 7, Civil Penalties. This regulation requires the Department to consider the past history of your site and how expeditiously the violations were addressed in determining any civil penalty that may be necessary for any future violations. If we need further information concerning this matter, we will contact you. Thank you for your attention to this matter. Should you have any questions, feel free to contact me at 501-682-0823 or you may e-mail me at [email protected]. Sincerely,

Kevin Suel Enforcement Analyst Water Division Enforcement Branch

Page 17: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,
Page 18: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,
Page 19: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

From: Stout, MarilynTo: Allen-Daniel, LeslieSubject: FW: Unimin AR001899, AR0001899C, ARR53588, and AR00B148Date: Thursday, April 19, 2012 9:29:42 AM

Leslie –Can you save this to: PDS 063618, 063368, 063369, and 063367 for me? Thanks! Marilyn From: Walker, Brent Sent: Thursday, April 19, 2012 8:37 AMTo: Stout, MarilynSubject: FW: Unimin AR001899, AR0001899C, ARR53588, and AR00B148 Brent L. Walker

District 3 Field Inspector

Water Division - Jonesboro Field Office

Arkansas Department of Environmental Quality

870-935-7221 ext.-12

[email protected]

From: Johnson, Steven Sent: Tuesday, April 03, 2012 14:59To: Uyeda, CraigCc: Walker, Brent; Fleming, Eric; Greenway, Michael; Saunders, SeanSubject: RE: Unimin AR001899, AR0001899C, ARR53588, and AR00B148 Hello Craig, Unimin has hired new Environmental Compliance personnel and we have been asked to perform acompliance assistance visit at this site. It appears this facility is moving in a good directionconcerning environmental protection matters. I support the extension proposed in the email belowthat may be needed for “fine tuning” of the draft revised SWPPP. Thanks, Steve From: Walker, Brent Sent: Monday, April 02, 2012 12:19 PMTo: Johnson, StevenCc: Fleming, Eric; Greenway, Michael; Saunders, SeanSubject: Unimin AR001899, AR0001899C, ARR53588, and AR00B148 Steve I just spoke with Phil Wilkes at Unimin regarding corrective action from our December 2011inspection. In their response to the inspection, they self-imposed an April 15, 2012 deadline for a

Page 20: February 9, 2012 - Arkansas Department of Environmental ...€¦ · February 9, 2012 Mike Maloney Unimin Corporation P.O. Box 29 Guion, AR 72540-0029 RE: NPDES Compliance Inspection,

new SWPPP. They currently have a new draft SWPPP and would like to take us up on my offer for acompliance assistance visit. Currently it looks like my first opening that matches their schedule islate April or early May – in my opinion, Sean’s attendance is mandatory, so we’ll have to work withhis schedule too. Michael actually wrote the letter and inspection report, so he gets a say also, ifhe desires.

I advised them to send a letter to enforcement asking for a one month extension of the April 15th

deadline for a final revised SWPPP. If you agree with the extension, will you please pass this alongwith your recommendation to Enforcement? Thanks,Brent Brent L. Walker

District 3 Field Inspector

Water Division - Jonesboro Field Office

Arkansas Department of Environmental Quality

870-935-7221 ext.-12

[email protected]