Upload
apcin8746
View
85
Download
0
Embed Size (px)
Citation preview
Electro-Magnetic Field Analysis Electro-Magnetic Field Analysis andand
Faraday Cage DesignFaraday Cage Design
Faraday cage design process
Identifying and characterizing the magnetic and electric field sources through measurements
Calculating the cage aperture based on frequency composition of the EMI and shield thickness based on field strength
Simulating the test setup (source, measuring equipment and faraday cage) and evaluating shielding effectiveness
Selection of the most cost effective and least disruptive field reduction method
Magnetic Field Magnetic Field AnalysisAnalysis
Faraday Cage Model Enclosing PD Measuring Equipment
Current Cycling Test Equipment (1200A)
Faraday Cage
PD Measuring Equipment
B-Field In Actual Lab Conditions
The B-Field is very low and any thin cage can give the required shielding. Considering the worst scenario, wherein the current cycling loop is in proximity (10 cm) of PD equipment further evaluation is carried out
The current cycling loop is about 6m away from PD measuring equipment
Flux density on PD measuring equipment
Case A: Without faraday cage Case B: With faraday cage
Case A Case B[Cage shown for reference]
Flux density on the impinging phase of measuring equipment
Case A
Case B
[Cage shown for reference]
Flux density along the cross -section of faraday cage enclosing PD measuring equipment
Case A
Case B
Case A
Case BOuter Surface
Flux density on the nearest face of faraday cage
Case BInner Surface
Flux density (Tesla)
Case A Case B
On Measuring Equipment
0.5 0.003
On Faraday cage (Outer face)
0.12 0.48
Magnetic Field Analysis
Inferences
Considering maximum radio or PD discharge interference frequency of 3 GHz the mesh size shall be smaller than 5cm
Considering the worst scenario the flux density on faraday cage for Case1 is 0.5 Tesla. The use of steel mesh (µr-1000 and thickness 2mm) as in Case2 brought down the B-value from 0.5 Tesla to less than 3mTesla (required limit 7-50 mTesla)
The skin depth evaluation is not considered as the field is static and hence flux distribution is based on ratio of air to mesh permeability alone
Theoretical calculations are in agreement with simulation results
Ref. Std: IEEE Std C95.6™-2002
Electric Field AnalysisElectric Field Analysis
Faraday Cage Model Enclosing PD Measuring Equipment
Current Cycling Test Equipment 1 kV
Faraday Cage
PD Measuring Equipment
Case A Case B
Electric stress on PD measuring equipment
Case A: Without faraday cage Case B: With faraday cage
Emax- 0.15 kV/m Emax- 0.00004 kV/m
Case A
Case B
Electric field distribution
Electric Stress (kV/m)
Case A Case B
On measuring Equipment
0.15 0.00004
On Faraday cage 0.02 0.08
Electric Field Analysis
Inferences
The maximum electric field is 0.08 kV/m on faraday cage (worst scenario case) which is well with in the required limit (5 kV/m)
The electric and magnetic fields in the laboratory are low. The effect of electric field is much lower than magnetic field. Hence, the proposed shield design is based on minimum requirements and magnetic field.
The steel mesh of µr-1000 and thickness 2mm shall provide the required shielding
Ref. Std: IEEE Std C95.6™
Thank youThank you