Upload
christian-fruto
View
881
Download
4
Embed Size (px)
DESCRIPTION
seminar presentation
Citation preview
FAMILIARIZATION OF FAMILIARIZATION OF ELECTRICAL DISTRIBUTION ELECTRICAL DISTRIBUTION
LINE EQUIPMENTLINE EQUIPMENT
ENGR. ROMEO F. CEDIENGR. ROMEO F. CEDIÑÑO, JR.O, JR.
Manager ForManager For
Technical Services DepartmentTechnical Services Department
SORECO II SORECO II
GENERAL DEFINITION:GENERAL DEFINITION:
TRANSFORMER IS A DEVICE THAT TRANSFERS ELECTRICAL TRANSFORMER IS A DEVICE THAT TRANSFERS ELECTRICAL
ENERGY FROM ONE ELECTRIC CIRCUIT TO ANOTHER ENERGY FROM ONE ELECTRIC CIRCUIT TO ANOTHER
WITHOUT A CHANGE IN FREQUENCY, DOES SO BY THEWITHOUT A CHANGE IN FREQUENCY, DOES SO BY THE
PRINCIPLE OF ELECTROMAGNETIC INDUCTION AND HASPRINCIPLE OF ELECTROMAGNETIC INDUCTION AND HAS
ELECTRIC CIRCUITS THAT ARE LINKED BY A COMMONELECTRIC CIRCUITS THAT ARE LINKED BY A COMMON
MAGNETIC CIRCUIT.MAGNETIC CIRCUIT.
POWER TRANSFORMERPOWER TRANSFORMER
••
BY TYPE (SUBSTATION POWER TRANSFORMER):BY TYPE (SUBSTATION POWER TRANSFORMER):
––
STEP UPSTEP UP
––
STEP DOWNSTEP DOWN
* THE POWER TRANSFORMER IS * THE POWER TRANSFORMER IS CONSIDERED AS THE CONSIDERED AS THE ““HEARTHEART””
OF THE OF THE
TRANSMISSION AND DISTRIBUTION TRANSMISSION AND DISTRIBUTION SYSTEMSYSTEM
POWER CIRCUIT BREAKERSPOWER CIRCUIT BREAKERS
POWER CIRCUIT BREAKERPOWER CIRCUIT BREAKER
DEFINITION:
AN ELECTRICAL DEVICE CAPABLE OF:
1. CARRYING NORMAL LOAD CURRENT TO WHICH IT IS DESIGNED
2. MAKING AND BREAKING NORMAL LOAD CURRENT
(CAPABLE OF MULTIPLE INTERRUPTION OF NORMAL LOAD CURRENT)
3. INTERRUPTING RATED FAULT CURRENT TO WHICH IT IS DESIGNED
(CAPABLE OF MULTIPLE INTERRUPTION OF RATED FAULT CURRENT)
4. WITHSTANDING MOMENTARY FAULT CURRENT
MAIN FUNCTIONS/PURPOSES OF POWER MAIN FUNCTIONS/PURPOSES OF POWER CIRCUIT BREAKERSCIRCUIT BREAKERS
1. INTERRUPT FAULT CURRENT AS QUICKLY AS POSSIBLE
2. ISOLATE AFFECTED CIRCUITS TO MINIMIZE DAMAGE TO OTHER EQUIPMENT
3. ENSURES CONTINUITY OF SERVICE
TYPES OF CIRCUIT BREAKERTYPES OF CIRCUIT BREAKER
CLASSIFICATION ACCORDING TO ARC QUENCHING MEDIUM
1. OIL CIRCUIT BREAKER (OCB)
2. AIR CIRCUIT BREAKER (ACB)
3. GAS CIRCUIT BREAKER (GCB)
4. VACUUM CIRCUIT BREAKER (VCB)
TYPES OF CIRCUIT BREAKERTYPES OF CIRCUIT BREAKER
CLASSIFICATION ACCORDING TO OPERATING MECHANISM
1. MAGNETIC OR MAGNEBLAST
2. PNEUMATIC
3. SPRING OPERATED
4. HYDRAULIC
METHODS OF ARC DISTINGUISHINGMETHODS OF ARC DISTINGUISHING1. OIL CIRCUIT BREAKER
A. COOLING THE ARC BY PUMPING OIL INSIDE THE INTERRUPTERB. ABSORBS HEAT BROUGHT ABOUT BY THE ARCC. GOOD INSULATING MEDIUM WHICH PREVENTS RESTRIKING
OF INTERRUPTED CURRENT
2. AIR CIRCUIT BREAKERA. BLOWING OF AIR TO THE ARC TOWARDS THE ARC CHUTES
3. GAS CIRCUIT BREAKER
A. PUFFING SF6 GAS TO THE INTERRUPTER AND ABSORBING HEAT BROUGHT ABOUT BY THE ARC.
B. HIGH DIELECTRIC STRENGTH OF SULFUR HEXAFLOURIDE (SF6)PREVENTS RESTRIKING OF INTERRUPTED CURRENT.
4. VACUUM CIRCUIT BREAKER
A. AIR WHICH CONTRIBUTES TO ARC PRODUCTION IS ABSENT, THUS NO ARC IS PRODUCED DURING CURRENT INTERRUPTION.
SAMPLE OF A TYPICAL WITHDRAWABLE TYPESAMPLE OF A TYPICAL WITHDRAWABLE TYPEAIR CIRCUIT BREAKERAIR CIRCUIT BREAKER
TYPICAL TYPICAL COMPONENTS COMPONENTS
OF AN OIL OF AN OIL CIRCUIT CIRCUIT BREAKERBREAKER
SAMPLE OUTLINE OF A PNEUMATIC GAS CIRCUIT BREAKER SAMPLE OUTLINE OF A PNEUMATIC GAS CIRCUIT BREAKER
VACUUM CIRCUIT BREAKER (WITHDRAWABLE TYPE) VACUUM CIRCUIT BREAKER (WITHDRAWABLE TYPE)
CUTAWAY CUTAWAY VIEW OF A VIEW OF A VACUUM VACUUM CIRCUIT CIRCUIT BREAKERBREAKER
SWITCHGEARSSWITCHGEARS
CONVENTIONAL SUBSTATIONCONVENTIONAL SUBSTATION
GAS INSULATED SWITCHGEAR CROSS SECTIONAL VIEWGAS INSULATED SWITCHGEAR CROSS SECTIONAL VIEW
DISTRIBUTION TRANSFORMERSDISTRIBUTION TRANSFORMERS
Typical Distribution TransformerTypical Distribution Transformer
Company Number
Primary H1 Bushing
KVA Rating
Nameplate(Hidden)
Secondary(X1, X2, X3)Bushings
Primary H2 Bushing
(At the Back)
Tap Changer(External/Internal)
Symbols Used in Transformer Voltage RatingsSymbols Used in Transformer Voltage Ratings
NAME SYMBOL APPLICATION EXAMPLES
Cross X
To designate separate voltages which can be obtained by reconnecting the coils of a winding in series or multiple combinations
13200 GRDY / 7620 V -120/240 X 139/277 V
7620 V - 240/120 V
13200 GRDY / 7620 V -120/240 V
Slant or Slash
To separate the voltage rating or ratings of separate windings.
Dash -To separate voltage to be applied or to be obtained from the same winding.
/
Primary Voltage Rating
Secondary Voltage Rating
KVA Rating
VoltageRatingper tapposition
Schematic Diagrams
Polarity(Additive)
DT Nameplate SampleDT Nameplate Sample
A Transformer Rated 13200 Grd.Y/7620 VA Transformer Rated 13200 Grd.Y/7620 V
Operation1. De-energize the DT2. Loosen lock screw3. Rotate switch to
desired position4. Tighten lock screw5. Energize the DT
External TapExternal Tap--ChangersChangers
Lock Screw
Other Types of External TapOther Types of External Tap--ChangersChangers
Internal View of a DT With an Internal View of a DT With an External TapExternal Tap--ChangerChanger
TapTap-- ChangerChanger
Internal TapInternal Tap--ChangersChangers
Rotary TapRotary Tap--ChangersChangers
Internal Tap changer
Dual Voltage Taps
Samples of DTs With Dual Voltage TapSamples of DTs With Dual Voltage Tap
Always refer to nameplate for actual ratings.
Tap changer Dual Voltage Taps
Changing the DUAL VOLTAGE TAP is done by transferring the connection of the primary lead
Samples of DTs With Dual Voltage TapSamples of DTs With Dual Voltage Tap
Dual Voltage
Taps
Changing the DUAL VOLTAGE TAP is done by transferring the connection of the outer end of the curved copper strip
Samples of DTs With Dual Voltage TapSamples of DTs With Dual Voltage Tap
SECTIONALIZINGSECTIONALIZING EQUIPMENTEQUIPMENT
SECTIONALIZINGSECTIONALIZINGSectionalizing is the proper application of isolating and overcurrent protective devices to:
1. Facilitate manual and automatic line switching
2. Limit power interruption to the smallest practical segment of the line
RATIONALERATIONALEThe primary objective of sectionalizing is to minimize the extent and effect of power interruption in a circuit through the proper application of isolating and protective line equipment.
EQUIPMENT USED FOR EQUIPMENT USED FOR SECTIONALIZINGSECTIONALIZING
• Switch• Fuse• Recloser• Sectionalizer• Fault Indicator
SWITCHSWITCH• A device for making, breaking
or changing the connection in an electric circuit
• It should be able to carry the normal load current continuously
• It should also be able to handle abnormal or short circuit currents for short periods
TYPES OF SWITCHESTYPES OF SWITCHES
• Disconnect Switch (DS)• Air Break Switch (ABS)• Load Break Switch (LBS)• Remote-Controlled Line
Switch (RCLS)
TYPES OF DISCONNECT SWITCHES TYPES OF DISCONNECT SWITCHES
1. HORIZONTAL MOUNTING1. HORIZONTAL MOUNTING
2. VERTICAL MOUNTING2. VERTICAL MOUNTING
3. UNIVERSAL MOUNTING3. UNIVERSAL MOUNTING
4. CENTER BREAK4. CENTER BREAK
Disconnect SwitchDisconnect Switch
• Plain knife-blade switch
• Has no interrupter and is intended to be operated only when the circuit has been de-energized by some other means
• Applications: primary line switch (PLS), disconnect switch
Air Break SwitchAir Break Switch
• A disconnecting switch equipped with an arcing horn
• Can be operated with the circuit energized but carrying only charging or magnetizing current
• The arcing horn helps extinguish the opening arc by extending it as the switch contacts open
Load Break SwitchLoad Break Switch
• A disconnecting switch equipped with an interrupter
• Can be operated when the circuit is energized and carrying normal load current
• Can also be closed against a fault
RemoteRemote--Controlled Line SwitchControlled Line Switch
• An LBS that can be operated remotely through SCADA
• It has the capability to measure voltage, current and other circuit parameters
• If provided with the more advanced type of electronic control, an RCLS can function like a sectionalizer
FUSEFUSE• An overcurrent
protective device which is placed in series in a circuit and has an element that melts during the passage of an overcurrent through it and thus interrupts the circuit
• A fuse must be replaced after its operation
TYPES OF FUSESTYPES OF FUSES• Fuselinks• Power Fuses
– Type SMD-5– Type SMD-20– Type SMD-50– Type SMD-100
• Current Limiting Fuses (CLF)
Fuse LinkFuse Link• Used in protecting
distribution transformers, line capacitor banks, and lateral taps
• Can be applied for fault currents up to 5,000 amperes and load below 4 MVA
• Easily opened and closed using a telescopic hot stick
Power FusePower Fuse• Used in protecting transformer vaults
and primary-metered services in high fault areas
• Can be applied for fault currents up to 28,000 amperes and loads up to 12 MVA
Type SMType SM--5 Power Fuse5 Power Fuse
• Can be applied for fault currents up to 28,000 amperes and loads up to 12 MVA
• Uses a porcelain fuse holder
• Can be opened with a telescopic hot stick but must be closed using a hook stick from a basket truck
Type SMDType SMD--20 Power Fuse20 Power Fuse
• Can be applied for fault currents up to 10,000 amperes and loads up to 8 MVA
• Uses a fiber fuse holder
• Can be opened and closed using a telescopic hot stick
Current Limiting Fuse (CLF)Current Limiting Fuse (CLF)
• Used in conjunction with a fuse link to protect distribution transformers in high fault areas as well as station service transformers
• Has no time-current characteristic (TCC) and operates only at high fault current magnitudes
• Has no external moving parts that could indicate its operation
An Automatic Circuit Recloser is a self- contained device with the necessary intelligence to sense an overcurrent condition, interrupt the current flow, and then after a predetermined time delay, recloses automatically to re- energize the line. If the fault is permanent, it locks open after a pre-set number of operations thus isolating the faulted portion from the main part of the system.
DESCRIPTIONDESCRIPTION
RECLOSERRECLOSER• A self-contained device with the
necessary intelligence to sense an overcurrent condition, interrupt the current flow, & then after a predetermined time delay, recloses automatically to re- energize the line.
• If the fault is permanent, it locks open after a pre-set number of operations thus isolating the faulted portion from the main part of the system.
RECLOSER CLASSIFICATIONSRECLOSER CLASSIFICATIONS
1. PhaseSingle-phase or three-phase
2. ControlHydraulic or electronic
3. InterruptersOil or Vacuum
4. InsulationOil , Air or Epoxy
SINGLESINGLE--PHASE RECLOSERS PHASE RECLOSERS
• Used to protect single-phase lines such as single-phase laterals
• Can also be used on three- phase circuits where the load is predominantly single-phase
• Examples are the Type D (15.5 kV) and DV (38 kV) Kyle Reclosers from Cooper Power Systems
THREETHREE--PHASE RECLOSERSPHASE RECLOSERS
1. Triple-Single tripping(Ex. NOVA Type TS reclosers)
2. Three-phase tripping(Ex. Type KFME, WE, WVE, VWVE reclosers)
TYPES OF CONTROLTYPES OF CONTROL1. Hydraulic Control• Built as an integral part of the recloser• Overcurrent is sensed by a trip coil that is
connected in series with the line. When the overcurrent flows through the coil, a plunger is drawn into the coil to trip open the recloser contacts.
• Timing and sequencing are accomplished by pumping oil through separate hydraulic chambers or ducts.
TYPES OF CONTROLTYPES OF CONTROL2. Electronic Control• More flexible, more easily
customized and programmed, and many have advanced protection, metering, and automation functionality.
• Line current is sensed by special sensing current transformers in the recloser
• The electronic control is housed in a cabinet separate from the recloser and conveniently permits changes to operational settings.
TYPES OF INTERRUPTING MEDIUMTYPES OF INTERRUPTING MEDIUM
1. Oil Interrupters• Reclosers using
oil for current interruption use the same oil for basic insulation.
• Some reclosers with hydraulic control also use the same oil for timing and counting functions.
TYPES OF INTERRUPTING MEDIUMTYPES OF INTERRUPTING MEDIUM
2. Vacuum Interrupters• Vacuum interrupters provide
fast, low-energy arc interruption with long contact and interrupter life, low mechanical stress, and maximum operating safety.
• With arc interruption taking place in a vacuum, contact and interrupter life far exceeds other interrupting media.
OPERATING LEVERS & INDICATORSOPERATING LEVERS & INDICATORS1. Manual Operating Handle• A yellow lever that is used to
manually trip the recloser• For the Type DV recloser, this
is also used to close the recloser.
• For the Type KFME, WE, WVE & VWVE reclosers, this is used for manual tripping & to override the controls to keep the recloser open. This cannot be used to manually close the recloser but must be in the closed position (up) before the recloser contacts can be closed.
• A red flag that is also linked to the interrupter mechanism but independent of the yellow handle
• It drops down from under the sleethood when the interrupter contacts are open.
2. Contact Position Indicator
OPERATING LEVERS & INDICATORSOPERATING LEVERS & INDICATORS
4. Non-reclosing Lever• Found on Type DV
reclosers, this sets the unit to one shot to lockout after fault interruption
OPERATING LEVERS & INDICATORSOPERATING LEVERS & INDICATORS
3. Operations Counter• Cumulatively records
each time the recloser opens.
THE KYLE TYPE DV THE KYLE TYPE DV HYDRAULICALLYHYDRAULICALLY--
CONTROLLED CONTROLLED RECLOSERRECLOSER
Nominal System Voltage (kV) 24.9 - 34.5
Maximum Rated Voltage (kV) 38
BIL (kV) 150
Max Continuou Current 560
Max Interrupting Rating (Sym.) 8000
Interrupting Medium Oil
Control Type Hydraulic
Specifications Summary
Construction features, operating levers, and indicators for the Type DV Recloser
THE KYLE TYPE DV RECLOSERTHE KYLE TYPE DV RECLOSER
Operating Levers and Indicators
The DV Reclosers’ sleet hood, showing the manual operating handle, non- reclosing lever and contact position indicator. Also found under the sleet hood is the operations counter.
THE KYLE TYPE DV RECLOSERTHE KYLE TYPE DV RECLOSER
Major ComponentsMajor Components
1. Arc interrupting assembly1. Arc interrupting assembly2. Closing solenoid2. Closing solenoid3. Closing solenoid contactor3. Closing solenoid contactor4. Hydraulic integrator assembly4. Hydraulic integrator assembly5. Series trip solenoid5. Series trip solenoid6. Time6. Time--delay unitdelay unit7. Head mechanism7. Head mechanism
THE KYLE TYPE DV RECLOSERTHE KYLE TYPE DV RECLOSER
Manual Closing Manual Closing of a of a DeDe--energizedenergized Type DV Type DV RecloserRecloser
THE KYLE TYPE DV RECLOSERTHE KYLE TYPE DV RECLOSER
THE KYLE TYPE KFMETHE KYLE TYPE KFMEELECTRONICALLYELECTRONICALLY--
CONTROLLEDCONTROLLEDRECLOSERRECLOSER
Phase 3
Nominal System Voltage (kV) 2.4 - 14.4
Maximum Rated Voltage (kV) 15.5
BIL (kV) 110
Max Continuou Current 400
Max Interrupting Rating (Sym.) 6000
Interrupting Medium Vacuum
Control Type Electronic
OperationOperation•• Tripping & closing are initiated by signals from Tripping & closing are initiated by signals from
the electronic controlthe electronic control
•• When currents in excess of the programmed When currents in excess of the programmed minimumminimum--trip value are detected in one or more trip value are detected in one or more phases, a signal from the control actuates a phases, a signal from the control actuates a solenoid in the operating mechanism to trip the solenoid in the operating mechanism to trip the opening springs & open the interrupter contactsopening springs & open the interrupter contacts
THE KYLE TYPE KFME RECLOSERTHE KYLE TYPE KFME RECLOSER
Form 4C ControlForm 3A Control
OperationOperation
• Closing energy and the force to charge the opening springs is supplied by a closing solenoid energized from the source side of the recloser
THE KYLE TYPE KFME RECLOSERTHE KYLE TYPE KFME RECLOSER
• Arc interruption takes place within the 3 sealed vacuum interrupters.
• Oil is used for electrical insulation, but is not involved in arc interruption.
OperationOperationTHE KYLE TYPE KFME RECLOSERTHE KYLE TYPE KFME RECLOSER
Operating Levers and Indicators
Manual operating handle (yellow)
Non-reclosinglever
Contact position indicator
Operationscounter
THE KYLE TYPE KFME RECLOSERTHE KYLE TYPE KFME RECLOSER
Electronic Control
• All operating parameters, like phase- and ground- fault minimum trip levels, TCC selection & sequence of recloser operation are done via the electronic control
• The Form 3A control is a solid-state electronic type while the Form 4C is a microprocessor- based control type
Form 4C Control
THE KYLE TYPE KFME RECLOSERTHE KYLE TYPE KFME RECLOSER
Form 3A Control
Typical Pole InstallationsTypical Pole Installations
THE KYLE TYPE KFME RECLOSERTHE KYLE TYPE KFME RECLOSER
THE TYPE WE, WVE & VWVE RECLOSERSTHE TYPE WE, WVE & VWVE RECLOSERSOperationOperation
• Closing energy & the force to required to charge the opening springs is supplied by a closing solenoid
• Oil interrupters are used in WE & WVE. Vacuum interrupters are used in VWVE.
• All are oil-insulated.
WE Recloser VWVE Recloser
THE TYPE WE, WVE & VWVE RECLOSERSTHE TYPE WE, WVE & VWVE RECLOSERS
Untanked view of Type WE recloser. Construction of WVE is similar.
Untanked Type VWVE vacuum recloser
THE TYPE WE, WVE & VWVE RECLOSERSTHE TYPE WE, WVE & VWVE RECLOSERS
THE TYPE WE, WVE & VWVE RECLOSERSTHE TYPE WE, WVE & VWVE RECLOSERSManual Operating Lever & Indicator
Yellow manual operating(trip-and-reset) handle• Used to manually trip
the recloser & override the control to keep the recloser open
Contact position Indicator• A red flag labeled OPEN independent of the yellow handle• Drops down from under the sleethood when the
interrupter contacts open
Form 4C Control Form 5 Control
Electronic Control Electronic Control • As with the Type KFME recloser, all operating
parameters for the Type WE, WVE & VWVE reclosers are provided by the electronic control
• The controls used by MERALCO are the Form 3A solid-state electronic control & the Form 4C & Form 5 microprocessor-based controls
THE TYPE WE, WVE & VWVE RECLOSERSTHE TYPE WE, WVE & VWVE RECLOSERS
Form 3A Control
Type WE & WVE Reclosers in
service
A device that indicates fault current flow
Senses the magnetic field caused by the current flowing through the conductor
Classified either as manual reset or automatic reset
FAULT INDICATORFAULT INDICATOR
SECTIONALIZERSSECTIONALIZERS
A SECTIONALIZER is a self-contained electrical device that interrupts its load side after sensing the passage of a predetermined number of successive fault currents and the corresponding trippings of the back- up device at its source side.
DESCRIPTIONDESCRIPTION
SECTIONALIZERSECTIONALIZER• A self-contained electrical
device that interrupts its load side after sensing the passage of a pre- determined number of successive fault currents & the corresponding trippings of the back-up device at its source side
• It opens during the open interval of the backup device
OPERATIONOPERATION• It opens during the open interval of
the backup device
• It does not interrupt fault current but can be closed into a faulted line
• It can be used to interrupt normal load current
• Once open, the sectionalizer will remain open until manually closed
The Type GW The Type GW SectionalizerSectionalizer
Nominal Voltage 34.5 kVRated Maximum Voltage 38 kVBIL 150 kVContinuous Current Rating 400 ARated Symmetrical Interrupting Current 880 A rmsRated Making Current, Asymmetrical 15000 AMomentary Maximum, Asymmetrical 15000 A
BASIC SECTIONALIZER RATINGS
Phase-Minimum-Actuating Current (Amps)
16, 24, 40, 56, 80, 112, 160, 224, 256, 296, 320, 448, 640,
768, 896Ground-Minimum-Actuating Current (Amps)
3.5, 7, 16, 20, 28, 40, 56, 80, 112,
160, 224, 320, 384, 448, BLOCK
Number of Counts to Open 1, 2, 3Count Resest (Seconds) 15, 30, 60, 120, 180Phase Actuating Level Multiplier (Inrush Restraint)
X1, X2, X4, X6, X8, BLOCK
Phase Inrush Reset (Cycles)
5, 10, 15, 20
Ground Inrush Reset (Seconds)
0.3, 0.7, 1.5, 3, 5
OPERATING DATA
A PoleA Pole--mounted Type GW mounted Type GW SectionalizerSectionalizer
A PoleA Pole--mounted Type GW mounted Type GW SectionalizerSectionalizer
This sectionalizer is installed on an open- wye primary lateral
External Features of Kyle Electronically External Features of Kyle Electronically Controlled Controlled SectionalizerSectionalizer
Internal Details of the Type GW Internal Details of the Type GW SectionalizerSectionalizer
Operating Mechanism and Electronic ControlOperating Mechanism and Electronic Control
MANUAL OPERATING CONTROLSMANUAL OPERATING CONTROLS
The sectionalizer’s manual operating controls are located on the underside of the operator mechanism housing placed on one side of the sectionalizer’s tank.
AUTOMATICAUTOMATICVOLTAGEVOLTAGE
REGULATORSREGULATORS
• A tap-changing autotransformer with the ability to continuously monitor its output voltage and automatically adjust itself by changing taps until the desired voltage is obtained.
• It regulates line voltage from 10% raise (boost) to 10% lower (buck) in 32, approximately 5/8 steps.
Automatic Voltage Automatic Voltage RegulatorRegulator
• To improve system voltage
• To improve quality of service
• To meet regulatory standards
Reasons for Installing Reasons for Installing AVRsAVRs
• Undervoltage• Overvoltage• Unbalanced voltage
Effects of Effects of AVRsAVRs on Voltage Problemson Voltage Problems
Problems Solved by AVRs
• Voltage sags• Voltage swells• Voltage flickers/fluctuations
Problems Not Solved by AVRs
Sample AVR InstallationSample AVR Installation(Pole Mounted) (Pole Mounted)
Sample AVR InstallationsSample AVR Installations(Platform Mounted)(Platform Mounted)
MAJOR COMPONENTS MAJOR COMPONENTS OF AN AVROF AN AVR
1. S (Source) Bushing
2. L (Load) Bushing
3. SL (Neutral) Bushing
4. Series Arrester
5. Position Indicator
6. Electronic Control
1 324
5
6
MAJOR COMPONENTS OF AN AVRMAJOR COMPONENTS OF AN AVR
Position Indicator
• Has a pointer mechanically connected to the tap- changing switch
• Indicates the actual position of the tap-changer through the yellow pointer
• Indicates the maximum & minimum positions attained during raise & lower operations through its drag hands.
• Allows load bonus setting of the regulator
MAJOR COMPONENTS OF AN AVRMAJOR COMPONENTS OF AN AVR
Series Arrester
• A bypass arrester connected across the series winding between the S & L bushings.
• Limits the voltage developed across the series winding during lightning strikes, switching surges & line faults.
Typical Features of an Electronic Typical Features of an Electronic ControlControl
1. Voltage Level Selector
2. Bandwidth Selector
3. Time Delay Selector
4. Band-edge Indicator
5. Line Drop Compensation Selectors
6. Neutral Indicating Light
7. Drag hand Reset/Neutral Light Test Button
8. Internal/External Power Switch
Typical Features of an Electronic Typical Features of an Electronic ControlControl
9. Control Switch
10. External Power Terminals
11. Voltmeter Terminal
12. Motor & Panel Fuses
13. Operations Counter
14. Data Port
15. LCD Display
16. Keypads
The Cooper/McGraw Edison VRThe Cooper/McGraw Edison VR--32 32 StepStep--Voltage RegulatorVoltage Regulator
1. CL-2 / CL-2A
2. CL-4C
3. CL-5A
CONTROL TYPES
Cooper AVR with a CLCooper AVR with a CL--2A Control2A Control
1 LCD Display 2 Keypad 3 Data Port 4 Power Switch 5 Voltmeter Terminals 6 External Power
Terminals 7 Panel Fuse 8 Differential Voltage
Fuse 9 Motor Fuse 10 Manual RAISE-
LOWER Switch 11 AUTO/REMOTE- OFF-
MANUAL Switch 12 Neutral Lamp Test-
Drag Hand Reset Switch
13 Neutral Indicating Light
Cooper AVR with a CLCooper AVR with a CL--4C Control4C Control
Input Voltage:Input Voltage:
80 80 --
170 V170 V
45 45 --
65 Hz65 Hz
Cooper AVR with a CLCooper AVR with a CL--5A Control5A Control
Input Voltage:Input Voltage:
80 80 --
137 V137 V
45 45 --
65 Hz65 Hz
Cooper AVR Bank with a CLCooper AVR Bank with a CL--5E Control5E Control
Nameplate of a Cooper VRNameplate of a Cooper VR--32 AVR32 AVR
The GE Type VRThe GE Type VR--1 Step1 Step--Voltage Voltage RegulatorRegulator
CONTROL TYPES
1. VR-1
2. SM-3
The Siemens Type JFR The Siemens Type JFR StepStep--Voltage RegulatorVoltage Regulator
A 250 kVA, 7.62 kV Type JFR AVR with an MJ-3A control
The Siemens Type JFR The Siemens Type JFR StepStep--Voltage RegulatorVoltage Regulator
A 400 kVA, 19.92 kV Type JFR AVR with an MJ-XL control
Nameplate of a Siemens Type JFR AVRNameplate of a Siemens Type JFR AVR
Line CapacitorsLine Capacitors
CAPACITORCAPACITOR•• A device for introducing a capacitive A device for introducing a capacitive
reactance in a circuit to counteract the reactance in a circuit to counteract the effects of inductive reactanceeffects of inductive reactance
•• It reduces the impedance of a circuit with It reduces the impedance of a circuit with a consequent reduction in the voltage a consequent reduction in the voltage drop and an improvement in the PFdrop and an improvement in the PF
•• By reducing the current required to supply By reducing the current required to supply a load, it decreases losses in a circuita load, it decreases losses in a circuit
SAMPLE 200 KVAR, 13200 V, CAPACITOR UNITSAMPLE 200 KVAR, 13200 V, CAPACITOR UNIT
CAPACITOR BANKSCAPACITOR BANKS
FACTORYFACTORY--ASSEMBLED BLOCK WITH HORIZINTALLY ASSEMBLED BLOCK WITH HORIZINTALLY MOUNTED CAPACITOR UNITSMOUNTED CAPACITOR UNITS
ADVANTAGES OF HAVING A CAPACITOR ADVANTAGES OF HAVING A CAPACITOR BANK INSTALLATIONBANK INSTALLATION
1. RAISE AND LOWER VOLTAGE WHEN NEEDED
2. RAISE VOLTAGE ON SOURCE SIDE
3. REDUCES LOSSES IN THE SYSTEM
4. REDUCES THERMAL LOADING
5. RAISES SYSTEM LOADING CAPABILITY
TYPES OF CAPACITOR BANKSTYPES OF CAPACITOR BANKS
Series Capacitor BankSeries Capacitor Bank•• Connected in series with the lineConnected in series with the line•• Used to compensate for the reactive Used to compensate for the reactive
voltage drop in the circuitvoltage drop in the circuit•• Typically used in lowTypically used in low--voltage, heavyvoltage, heavy--
current applications such as furnaces & current applications such as furnaces & welders, to compensate for the voltage welders, to compensate for the voltage drop in the conductorsdrop in the conductors
Shunt Capacitor BankShunt Capacitor Bank•• Connected in parallel with the loadConnected in parallel with the load•• Used to correct the component of current Used to correct the component of current
caused by inductive loads caused by inductive loads •• Typically used for PF correctionTypically used for PF correction
BENEFITS DERIVED FROM SHUNT BENEFITS DERIVED FROM SHUNT CAPACITOR BANKSCAPACITOR BANKS
1. Released Capacity- due to PF improvement
2. Voltage Rise- due to reduction in line impedance
3. Loss Reduction- due to reduction in line impedance
kVAR2
CkVAR
kVAR1
kW
kVA2
kVA1
TYPES OF CAPACITOR CONTROLTYPES OF CAPACITOR CONTROL
1. Fixed
2. Time
3. Voltage
4. Current
5. Power Factor
6. KVAR
7. Temperature
GUIDELINES IN HANDLING GUIDELINES IN HANDLING CAPACITOR BANKSCAPACITOR BANKS
1.1. Before placing a capacitor bank in service, Before placing a capacitor bank in service, inspect individual units for bulged or cracked inspect individual units for bulged or cracked tanks. Proper care should be exercised in tanks. Proper care should be exercised in handling capacitor units to prevent damage handling capacitor units to prevent damage to or denting of capacitor case.to or denting of capacitor case.
2.2. Before working upon capacitor units, the Before working upon capacitor units, the capacitor bank must be allowed to stand at capacitor bank must be allowed to stand at least five (5) minutes after disconnecting least five (5) minutes after disconnecting from source of power, after which it shall be from source of power, after which it shall be shortshort--circuited and grounded before work is circuited and grounded before work is started.started.
Always use the capacitor oil switch when energizing Always use the capacitor oil switch when energizing & de& de--energizing a capacitor bank. When the oil energizing a capacitor bank. When the oil switch is inoperable, the following shall be switch is inoperable, the following shall be observed:observed:
ENERGIZING & DEENERGIZING & DE--ENERGIZING ENERGIZING LINE CAPACITOR BANKSLINE CAPACITOR BANKS
1.1. Closing of Closing of FCOsFCOs shall be done only while the shall be done only while the line is deline is de--energizedenergized
2.2. For line capacitor banks installed on 13.8kV For line capacitor banks installed on 13.8kV circuits & below, opening of circuits & below, opening of FCOsFCOs shall be done shall be done with the use of load busterwith the use of load buster
3.3. For line capacitors installed on 34.5kV circuits, For line capacitors installed on 34.5kV circuits, opening of opening of FCOsFCOs shall be done only when the shall be done only when the line is deline is de--energizedenergized
CooperCooper’’s Type TSC Threes Type TSC Three--Phase Oil SwitchPhase Oil Switch
Nominal System Voltage 34.5 kVRated Maximum Voltage 38 kV
Rated Momentary Current 12000 ARated Making Current 12000 A
Capacitive Continuous Current 135 A
Type TSC Oil Switch OperationType TSC Oil Switch Operation
1. The oil switch is manually operated by means of the red handle under the sleet hood. Pulling down the handle will either open or close the switch depending upon its previous position.
2. A disc-type contact-position indicator shows the switch position.
Type TSC Oil Switch OperationType TSC Oil Switch Operation
4. When the operating handle is released, it automatically returns to its up position under the sleet hood.
5. The manual reset lever, however, must be returned to its up position before the motor circuit is armed & the switch is returned to remote electrical control.
3. When the operating handle is pulled down, the manual reset lever is also pulled down.
CooperCooper’’s Type NR Singles Type NR Single--Phase Oil SwitchPhase Oil Switch
Nominal System Voltage 14.4 kVRated Maximum Voltage 15 kVRated Momentary Current 9000 ARated Making Current 9000 ACapacitive Continuous Current 200 A
Manual Operation of the Type NR Oil SwitchManual Operation of the Type NR Oil Switch
The oil is manually opened & closed by operating the yellow handle under the sleet hood.
End of PresentationEnd of Presentation
Thank You!Thank You!