608 State St. South Kirkland, WA 98033 www.faira.com [email protected] +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, WA 98102 September 22, 2017 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property. You may view more detailed information for this home and can make an offer at http://www.faira.com/listings/11522 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team

FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

608 State St. South

Kirkland, WA 98033

www.faira.com

[email protected]

+1.800.571.FAIR

FAIRA TRANSPARENCY REPORTS

2424 Federal Ave E, Seattle, WA 98102

September 22, 2017

Thank you for your interest in this Faira Certified home.

We have coordinated the efforts of certified and licensed inspection and title professionals to

create the Faira Transparency Reports for this home. The Faira Transparency Reports are a

detailed portfolio of information that is prepared on behalf of buyers in preparation for making

an informed offer on the property.

You may view more detailed information for this home and can make an offer at

http://www.faira.com/listings/11522

All of the information in the Faira Transparency Reports was gathered and compiled without any

bias or influence from the seller(s). In fact, these reports are materially identical had you as the

buyer(s) ordered the same professionals to perform the evaluations on the same date.

Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are

recommended to conduct their own due-diligence to their satisfaction.

Please contact us if you have any questions or would like more information.

We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of

working with you!

The Faira Team

Page 2: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

RW West Consultants, Inc.Property Inspection Report

Cover Page

2424 Federal Ave E, Seattle, WA 98102Inspection prepared for: Faira .com

Real Estate Agent: Faira .com -

Date of Inspection: 9/27/2017 Time: 9:00 AMOrder ID: 2704

Inspector: Clifton MoodyLicense # 957

Phone: 425.885.0722Email: [email protected]

Page 3: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

RW West Consultants, Inc. 2424 Federal Ave E, Seattle, WA

Page 1 of 14

Inspection Details We appreciate the opportunity to conduct this inspection for you! Please carefully read your entireInspection Report. Call us after you have reviewed your report, so we can go over any questions you mayhave. Remember, when the inspection is completed and the report is delivered, we are still available to youfor any questions you may have, throughout the entire closing process.Properties being inspected do not "Pass" or "Fail.” - The following report is based on an inspection of thevisible portion of the structure; inspection may be limited by vegetation and possessions. Depending uponthe age of the property, some items like GFI outlets may not be installed;For your safety and liability purposes, we recommend that licensed contractors evaluate and repair anycritical concerns and defects. Note that this report is a snapshot in time. We recommend that you or yourrepresentative carry out a final walk-through inspection immediately before closing to check the conditionof the property, using this report as a guide. Items denote serious, safety or items that required further investigationItems denote minor or maintenance itemsGreen notes denote locations and shutoff valves

Page 4: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

RW West Consultants, Inc. 2424 Federal Ave E, Seattle, WA

Page 2 of 14

General Exterior Note 1. Exterior NoteObservations:• East Elevation• West Elevation

||2||West Elevation ||2||East Elevation

Page 5: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

RW West Consultants, Inc. 2424 Federal Ave E, Seattle, WA

Page 3 of 14

Exterior Areas 1. GuttersObservations:• Missing sections of downspouts; recommend missing sections are installed for proper function.

2. Driveway and Walkway ConditionConcrete sidewalks appeared in good condition overall. • Gravel driveway appeared in goodcondition.Observations:• Cracking at the driveway/sidewalk does not appear unusual.

Page 6: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

RW West Consultants, Inc. 2424 Federal Ave E, Seattle, WA

Page 4 of 14

3. GradingCollection drains present to help control runoff.Observations:• Grade Slopes towards the house from South to north.

4. ElectricalObservations:• Exterior covers missing/damaged, recommend conditions are repaired as a safety precaution. SE

Page 7: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

RW West Consultants, Inc. 2424 Federal Ave E, Seattle, WA

Page 5 of 14

5. Gate ConditionMaterials: Chain linkObservations:• Fences are NOT INCLUDED as part of a home inspection.

6. Retaining WallConcrete block retaining wall. • Rockery retaining wall.Observations:• Indications of failure occurring at retaining wall, recommend conditions are investigated furtherand corrected.

Page 8: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

RW West Consultants, Inc. 2424 Federal Ave E, Seattle, WA

Page 6 of 14

Page 9: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

RW West Consultants, Inc. 2424 Federal Ave E, Seattle, WA

Page 7 of 14

Exterior Stairs 1. StairSteps appeared uniform.Observations:• Handrail does not extend full length of stairs, recommend installing handrail when there are 4 ormore steps as a safety precaution.

Page 10: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

RW West Consultants, Inc. 2424 Federal Ave E, Seattle, WA

Page 8 of 14

Roof 1. Roof ConditionEPDM rubberized roofing material, average life span of this surface is 15 to 40 years dependant onmil thickness.Observations:• Recommend following conditions are investigated further by licensed roofing contractor andconditions corrected as required.• Cracking to membrane surface.

Page 11: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

RW West Consultants, Inc. 2424 Federal Ave E, Seattle, WA

Page 9 of 14

Garage 1. ConditionObservations:• Wood rot and decay to framing mostly at west side. Recommend conditions are investigatedfurther and corrected by licensed contractor.

Page 12: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

RW West Consultants, Inc. 2424 Federal Ave E, Seattle, WA

Page 10 of 14

2. Floor ConditionObservations:• Cracking to the floor. Recommend conditions are investigated further and corrected by licensedcontractor.

3. ElectricalObservations:• Outlets are not GFCI protected, recommend GFCI protecting outlets as a safety precaution• Ungrounded outlets, recommend a licensed electrical contractor investigate conditions further andcorrect as required.

4. Garage DoorsObservations:• No test to automatic garage door. Wires disconnected. Recommend further investigation.

Page 13: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

RW West Consultants, Inc. 2424 Federal Ave E, Seattle, WA

Page 11 of 14

5. Window DeficienciesObservations:• Cracked or broken window glass was observed. Injury could occur. Recommend repair orreplacement of the damaged glass.

Page 14: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

RW West Consultants, Inc. 2424 Federal Ave E, Seattle, WA

Page 12 of 14

GlossaryGlossary

Term DefinitionGFCI A special device that is intended for the protection of personnel

by de-energizing a circuit, capable of opening the circuit wheneven a small amount of current is flowing through the groundingsystem.

Page 15: FAIRA TRANSPARENCY REPORTS 2424 Federal Ave E, Seattle, … · 2017-09-28 · Garage Doors Observations: • No ... Estimates for repairs are approximations and we do not guarantee

RW West Consultants, Inc. 2424 Federal Ave E, Seattle, WA

Page 13 of 14

Report SummaryReport Summary

This is a visual inspection. No destructive testing is performed. This is not a soil inspection nor do weinspect for formaldehyde, radon, asbestos, Chinese drywall, lead paint, mold, hazardousmaterials/substances, landscape lighting, sprinkler systems, septic systems/drain fields, smoke alarmsor recreational equipment such as Jacuzzis etc.. It is recommended that noted deficiencies beinvestigated further by licensed companies specializing in those disciplines. Inspection is subject toconditions at the time of inspection. Appliances are checked to see if they're in operable condition. Thisis not a code inspection as codes change frequently and vary between municipalities. We make noguarantees for expected life. It is impossible to verify conditions of places inaccessible in walls under andin between floors, behind furniture appliances etc., and we assume no responsibility for those items assuch. Estimates for repairs are approximations and we do not guarantee their accuracy. Possiblesolutions for problems are solely opinions based on conditions at the time of the inspection and are notto be assumed as being totally conclusiveThe summary below consists of potentially significant findings. These findings can be a safety hazard, adeficiency requiring a major expenses or further investigation to correct or items I would like to drawextra attention to. The summary is not a complete listing of all the findings in the report, and reflects theopinion of the inspector. Please review all of the pages of the report as the summary alone does notexplain all the issues. We recommend repairs should be done by licensed &bonded contractors. We alsorecommend obtaining a copy of all receipts, warranties and permits for the work done. Exterior AreasPage 4 Item: 4 Electrical • Exterior covers missing/damaged, recommend conditions

are repaired as a safety precaution. SEPage 5 Item: 6 Retaining Wall • Indications of failure occurring at retaining wall, recommend

conditions are investigated further and corrected.Exterior StairsPage 7 Item: 1 Stair • Handrail does not extend full length of stairs, recommend

installing handrail when there are 4 or more steps as a safetyprecaution.

RoofPage 8 Item: 1 Roof Condition • Recommend following conditions are investigated further by

licensed roofing contractor and conditions corrected asrequired.• Cracking to membrane surface.

GaragePage 9 Item: 1 Condition • Wood rot and decay to framing mostly at west side.

Recommend conditions are investigated further and correctedby licensed contractor.

Page 10 Item: 2 Floor Condition • Cracking to the floor. Recommend conditions areinvestigated further and corrected by licensed contractor.

Page 10 Item: 3 Electrical • Outlets are not GFCI protected, recommend GFCI protectingoutlets as a safety precaution• Ungrounded outlets, recommend a licensed electricalcontractor investigate conditions further and correct asrequired.

Page 11 Item: 5 WindowDeficiencies

• Cracked or broken window glass was observed. Injury couldoccur. Recommend repair or replacement of the damagedglass.