The following table shows the connections between DDF sockets and SWIN pins. Alarm ID Connecto r Pin Core Colo r Connecto r Pin Core Color Alarm Name DDF PIN NO. 6438 X1.2 Whit e X1.36 Blue Telecom shelter air condition #1 fault X1-0 6440 X1.3 Whit e X1.37 Orang e Telecom shelter air condition #2 fault X1-1 6442 X1.4 Whit e X1.38 Green Telecom/General shelter fire alarm X1-2 6444 X1.5 Whit e X1.39 Brown Telecom/General shelter door alarm X1-3 6446 X1.6 Whit e X1.40 Grey Telecom shelter high temperature alarm X1-4 6448 X1.7 Red X1.41 Blue Telecom shelter minor power fail(minor) X1-5 6450 X1.8 Red X1.42 Orang e Telecom shelter tower light alarm X1-6 6452 X1.9 Red X1.43 Green Telecom shelter battery discharge/ commercial power X1-7 6454 X1.10 Red X1.44 Brown Generator #1 fault X2-0 6456 X1.11 Red X1.45 Grey Telecom shelter power fail major X2-1 6458 X1.12 Blac k X1.46 Blue Generator #1 running(indication) X2-2 6460 X1.13 Blac k X1.47 Orang e Generator low fuel – day tank (no wiring) X2-3 6462 X1.14 Blac k X1.48 Green Generator low fuel – storage tank X2-4 6464 X1.15 Blac k X1.49 Brown Telecom shelter commercial power fail X2-5 6466 X1.16 Blac k X1.50 Grey Generator #2 fault (faulty) X2-6 6422 X1.17 Blac k X1.51 Blue Generator #2 running(indication) (faulty) X2-7 6424 X1.18 Whit e X1.52 Blue Telecom/ Generator shelter FM200 released/ FA fault X3-0 6426 X1.19 Whit e X1.53 Orang e Telecom shelter high humidity alarm X3-1 6428 X1.20 Whit e X1.54 Green Telecom shelter battery/ AC fail- access control X3-2

External Alarm Schematic

Embed Size (px)

DESCRIPTION

Alarms

Citation preview

The following table shows the connections between DDF sockets and SWIN pins.Alarm IDConnector PinCore ColorConnector PinCore ColorAlarm NameDDF

PIN NO.

6438X1.2WhiteX1.36BlueTelecom shelter air condition #1 faultX1-0

6440X1.3WhiteX1.37Orange Telecom shelter air condition #2 faultX1-1

6442X1.4WhiteX1.38GreenTelecom/General shelter fire alarmX1-2

6444X1.5WhiteX1.39BrownTelecom/General shelter door alarmX1-3

6446X1.6WhiteX1.40GreyTelecom shelter high temperature alarmX1-4

6448X1.7RedX1.41BlueTelecom shelter minor power fail(minor)X1-5

6450X1.8RedX1.42Orange Telecom shelter tower light alarmX1-6

6452X1.9RedX1.43GreenTelecom shelter battery discharge/ commercial powerX1-7

6454X1.10RedX1.44BrownGenerator #1 faultX2-0

6456X1.11RedX1.45GreyTelecom shelter power fail majorX2-1

6458X1.12BlackX1.46BlueGenerator #1 running(indication)X2-2

6460X1.13BlackX1.47Orange Generator low fuel day tank(no wiring)X2-3

6462X1.14BlackX1.48GreenGenerator low fuel storage tankX2-4

6464X1.15BlackX1.49BrownTelecom shelter commercial power failX2-5

6466X1.16BlackX1.50GreyGenerator #2 fault(faulty)X2-6

6422X1.17BlackX1.51BlueGenerator #2 running(indication)(faulty)X2-7

6424X1.18WhiteX1.52BlueTelecom/ Generator shelter FM200 released/ FA faultX3-0

6426X1.19WhiteX1.53Orange Telecom shelter high humidity alarmX3-1

6428X1.20WhiteX1.54GreenTelecom shelter battery/ AC fail-access controlX3-2

6430X1.21WhiteX1.55BrownTelecom shelter OPP alarmX3-3

6432X1.22WhiteX1.56GreyDSX FuseX3-4

6434X1.23RedX1.57BlueMicro Wave MajorX3-5

6436X1.24RedX1.58Orange Micro Wave MinorX3-6

6468X1.25RedX1.59GreenMicro Wave RemoteX3-7

6470X1.26RedX1.60BrownTTA AlarmX4-1

6472X1.27RedX1.61GreyBoolean Value Alarm on Path 26Future

6474X1.28BlackX1.62BlueBoolean Value Alarm on Path 27Future

6476X1.29BlackX1.63Orange Boolean Value Alarm on Path 28Future

6478X1.30BlackX1.64GreenBoolean Value Alarm on Path 29Future

6480X1.31Black X1.65BrownBoolean Value Alarm on Path 30Future

6482X1.32BlackX1.66GreyBoolean Value Alarm on Path 31Future

6484X1.33BlackX1.67BlueBoolean Value Alarm on Path 32Future

Table 11-3 connections between DDF sockets and DDFpins