External Alarm Box n Installtion

  • Upload
    kienna

  • View
    225

  • Download
    1

Embed Size (px)

Citation preview

  • 8/11/2019 External Alarm Box n Installtion

    1/34

    Alcatel-Lucent GSM

    External Alarm Box Installation

    and Commissioning Manual

    BSC & TC Document

    Installation & Dismantling Manual

    3BK 17422 3101 RJZZA Ed.08

  • 8/11/2019 External Alarm Box n Installtion

    2/34

    Status RELEASED

    Short title INS

    All rights reserved. Passing on and copying of this document, useand communication of its contents not permitted without writtenauthorization from Alcatel.

    BLANK PAGE BREAK

    2 / 34 3BK 17422 3101 RJZZA Ed.08

  • 8/11/2019 External Alarm Box n Installtion

    3/34

    Contents

    Contents

    Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    1.1 Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81.1.1 Hardware Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81.1.2 Cases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.1.3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.1.4 Initial State. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.1.5 Final State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.1.6 Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.1.7 Grouped Task Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    1.2 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111.2.1 Prerequisites. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111.2.2 Site-Specific Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    1.3 Scheduling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121.4 Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    1.4.1 Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121.4.2 Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121.4.3 Applicable Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    2 External Alarm Box Installation and Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    2.1 Before Going on Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162.2 Before You Start (On Arrival at the Site) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    2.2.1 Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162.2.2 Required Knowledge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    2.3 EAB Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172.3.1 Wall Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172.3.2 Fix the EAB to the Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172.3.3 Connect Cables to EAB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    2.4 EAB Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212.4.1 Check the Power Supply and Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212.4.2 Set EAB Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222.4.3 Declare the EAB at OMC-R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

    2.5 Finish Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

    3BK 17422 3101 RJZZA Ed.08 3 / 34

  • 8/11/2019 External Alarm Box n Installtion

    4/34

    Contents

    4 / 34 3BK 17422 3101 RJZZA Ed.08

  • 8/11/2019 External Alarm Box n Installtion

    5/34

    Preface

    Preface

    Purpose This document describes how to install on site an External Alarm Box for A9130BSC/MFS Evolution of ALCATEL-LUCENT BSS.

    Whats New In Edition 08Description improvement in the following sections:

    Configure OMC-R IP Address on EAB(Section 2.4.2.10)

    Connect the EAB to the A9130 BSC/MFS Evolution(Section 2.4.2.12)

    Test the Connectivity(Section 2.4.2.14).

    In Edition 07Description improvement in:

    Prerequisites (Section 1.2.1)

    Connect the EAB to the A9130 BSC/MFS Evolution(Section 2.4.2.12).

    In Edition 06Description improvement in:

    Installation Kits(Section 1.4.1.1)

    Configure IP Addresses on EAB(Section 2.4.2.5).

    In Edition 05Description update in:

    Configure IP Addresses on EAB(Section 2.4.2.5)

    Finish Installation (Section 2.5).The following sections were added:

    Check if Wago BootP Software is Installed(Section 2.4.2.1)

    Download Wago BootP Software(Section 2.4.2.2)

    Modify EAB IP Address(Section 2.4.2.11).

    3BK 17422 3101 RJZZA Ed.08 5 / 34

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 8/11/2019 External Alarm Box n Installtion

    6/34

    Preface

    In Edition 04Description update in:

    Connect the External Alarm Cables(Section 2.3.3.3)

    Site-Specific Information (Section 1.2.2)

    Configure Gateway Address on EAB(Section 2.4.2.8)

    Restriction removal inDeclare the EAB at OMC-R (Section 2.4.3).

    In Edition 03

    Restriction introduction inDeclare the EAB at OMC-R (Section 2.4.3).

    In Edition 02Description update in:

    Configure OMC-R IP Address on EAB(Section 2.4.2.10)

    Connect the EAB to the A9130 BSC/MFS Evolution(Section 2.4.2.12)

    Test the Connectivity(Section 2.4.2.14).

    SectionDeclare the EAB at OMC-R (Section 2.4.3) was added.

    In Edition 01

    First official release of document.

    Audience This document is intended for:

    Installers

    Site administrators

    Supervisors

    Project managers

    Field service technicians

    Occasional users.

    Assumed Knowledge You must have a basic understanding of the following:

    Basic knowledge of Alcatel-Lucent BSS equipment

    Experience of electrical mounting and cabling.

    6 / 34 3BK 17422 3101 RJZZA Ed.08

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 8/11/2019 External Alarm Box n Installtion

    7/34

    1 Overview

    1 Overview

    This Overview gives information needed by project managers and foremen, forpresentation to the customer and for site planning.

    3BK 17422 3101 RJZZA Ed.08 7 / 34

  • 8/11/2019 External Alarm Box n Installtion

    8/34

    1 Overview

    1.1 Presentation

    1.1.1 Hardware Description

    The External Alarm Box provides external alarm inputs adaptable to the

    individual requirements. Typically can be used for main power supply, rectifiers,batteries, air conditioning, intrusion.

    1.1.1.1 Module Configuration

    The External Alarm Box includes:

    A Programmable Field Bus controller Ethernet TCP/IP 10/100 Mbits/s

    for Input/Output modules.

    Six input modules with four channels for signal control from digital field

    devices numbered from left to right side.

    One module for bus termination of internal data circuit and correct data flow.

    One power supply adaptor

    Fused disconnect terminal block with LED.

    C

    D

    A

    B

    2 4 V 0 V

    + +

    ETHERNET

    LINK

    MS

    NS

    I/ O

    USR

    TxD/RxD

    C

    D

    A

    B

    13 14

    + +

    15 16

    WAGO

    750 432

    + +

    01

    C

    D

    A

    B

    13 14

    + +

    15 16

    WAGO

    750 432

    + +

    02

    C

    D

    A

    B

    13 14

    + +

    15 16

    WAGO

    750 432

    + +

    03

    C

    D

    A

    B

    13 14

    + +

    15 16

    WAGO

    750 432

    + +

    04

    C

    D

    A

    B

    13 14

    + +

    15 16

    WAGO

    750 432

    + +

    05

    C

    D

    A

    B

    13 14

    + +

    15 16

    WAGO

    750 432

    + +

    06

    C

    D

    A

    B

    WAGO

    750 600

    EntreSortie

    + 0

    + + +

    +

    2

    Figure 1: External Alarm Box (Front View)

    8 / 34 3BK 17422 3101 RJZZA Ed.08

  • 8/11/2019 External Alarm Box n Installtion

    9/34

    1 Overview

    1.1.1.2 Weight and Dimensions

    The following tables gives the dimensions and weight of the EAB.

    Width

    Depth

    Height

    280 mm

    180 mm

    380 mm

    Weight 2.5 kg

    1.1.2 Cases

    None.

    1.1.3 Options

    None.

    1.1.4 Initial State

    The External Alarm Box and installation kit are packed and delivered on site.

    1.1.5 Final State

    After finishing the installation and commissioning the EAB is ready to bedeclared ant the OMC-R.

    The EAB will be ready for use after:

    Declaration at OMC-R side

    Assignment of an OMC-R device type.

    1.1.6 Restrictions

    None.

    3BK 17422 3101 RJZZA Ed.08 9 / 34

  • 8/11/2019 External Alarm Box n Installtion

    10/34

    1 Overview

    1.1.7 Grouped Task Sequence

    EAB Installation

    Before You Start

    Before Going On Site

    EAB Commissioning

    Finish Installation

    10/ 34 3BK 17422 3101 RJZZA Ed.08

  • 8/11/2019 External Alarm Box n Installtion

    11/34

    1 Overview

    1.2 Preparation

    1.2.1 Prerequisites

    The following prerequisites apply:

    The site conforms to the "Safety rules" of General Wiring Handbook

    The site is ready to receive the EAB, according to SPP 59

    The A9130 BSC/MFS Evolution is already operational and able to route the

    EAB messages towards the OMC-R.

    1.2.2 Site-Specific Information

    Site: The following specific information (input) is needed to complete thescenario:

    Grounding plate location

    Power supply cabinet location

    Fuse breakers location into power box

    2 wires or 3 wire power system (if applicable)

    EAB precise location

    Number of alarms to be connected

    Wago Protocol Type

    Wago Reverse

    Alarm is active when the electrical status is open loop.Wago DirectAlarm is active when the electrical status is close loop.

    Alarm cabling diagram

    EAB IP Address, Subnet Mask and Gateway IP Address

    OMC-R IP Address

    OMC-R username and password for secure connection.

    3BK 17422 3101 RJZZA Ed.08 11/ 34

  • 8/11/2019 External Alarm Box n Installtion

    12/34

    1 Overview

    1.3 Scheduling

    Task Duration (mn)

    1st person

    Preliminary checks 30

    EAB installation 30

    EAB commissioning 20

    Finishing installation 10

    Total Time: 1h 30min

    1.4 Resources

    1.4.1 Tools

    1.4.1.1 Installation Kits

    The following table describe the necessary installation kits.

    Installation kits Mnemo Reference Qty

    External Alarm Box equipped JBXEAB 1AB 24048 0001 1

    Ethernet cable ALETHC 3BW01805JA 1

    1.4.1.2 Software Tools

    None.

    1.4.1.3 Hardware Tools

    The following table is used to check, on base, the availability of the necessarytools.

    See Tools catalogue for content checking.

    Kit name Reference Calibration

    Basic kit tools OUT 001 no

    1.4.2 Supplies

    None.

    12/ 34 3BK 17422 3101 RJZZA Ed.08

  • 8/11/2019 External Alarm Box n Installtion

    13/34

    1 Overview

    1.4.3 Applicable Documents

    The following table is used to check, at base, the availability of the necessarydocuments.

    Document tittle Reference

    Applicable Notification List(ITL-PRO) 3DF 00462 0004 AAAGA

    Applicable Operation Instructions(IO) 3DF 00300 0004 UAZZA

    General Wiring Handbook 3BK 17160 0001 RJZZA

    Tools catalogue for Field Activity 3BK 20458 0001 RJZZA

    Site premises inspection form (CEL) 8BL 00704 0015 DRBRA

    Installation Manual Generic CCL 3BK 17200 0002 QZZZA

    Specification for site preparation (SPP 59) 8BL 00704 0076 DRZZA

    BSS Site Premises Inspection, Post Handover 8BL 00704 0016 DRBRA

    BSS Configuration HandbookB9 Release 3BK 20901 AAAA PCZZA

    BSS Configuration HandbookB10 Release 3BK 21201 AAAA PCZZA

    3BK 17422 3101 RJZZA Ed.08 13/ 34

  • 8/11/2019 External Alarm Box n Installtion

    14/34

    1 Overview

    14/ 34 3BK 17422 3101 RJZZA Ed.08

  • 8/11/2019 External Alarm Box n Installtion

    15/34

    2 External Alarm Box Installation and Commissioning

    2 External Alarm Box Installation and Commissioning

    This Scenario presents all checks needed before beginning the scenario, andall detailed tasks to be performed on site.

    3BK 17422 3101 RJZZA Ed.08 15/ 34

  • 8/11/2019 External Alarm Box n Installtion

    16/34

    2 External Alarm Box Installation and Commissioning

    2.1 Before Going on Site

    Before going on site you must check that the following information and toolsare available:

    AllPrerequisites (Section 1.2.1) are fulfilled

    The customer has been informed of the:

    Date and time

    Site name and address

    Purpose of the operation.

    Personnel are available and ready for operation (refer to Scheduling

    (Section 1.3)

    Site-Specific Information (Section 1.2.2) is available and ready for operation

    Hardware Tools(Section 1.4.1.3)are available and ready for operation

    Installation Kits(Section 1.4.1.1)are available and ready for operation

    Applicable Documents (Section 1.4.3)are available and ready for operation.

    2.2 Before You Start (On Arrival at the Site)

    2.2.1 Checks

    Before you start, perform the following operations:

    Check that all Prerequisites (Section 1.2.1)are fulfilled

    Check applicable notifications and operating instructions (refer to the

    Applicable Notifications Listand Applicable Operation Instructions List)

    Check the availability of all necessary tools and supplies.

    Refer to BSS Site Premises Inspection, Post Hand over and complete the

    Premises Inspection form (CEL).

    Check that the safety precautions have been taken in accordance with the

    safety instructions described in theBSS Methods Handbook.

    Check whichCases (Section 1.1.2) or Options (Section 1.1.3) apply

    Complete the header field of the CCL. The CCL is completed as each

    instruction is carried out.

    2.2.2 Required Knowledge

    You must be familiar with the following:

    The safety rules and precautions given in the BSS Methods Handbook.

    How to document faults and anomalies as described in the BSS Methods

    Handbook.

    16/ 34 3BK 17422 3101 RJZZA Ed.08

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 8/11/2019 External Alarm Box n Installtion

    17/34

    2 External Alarm Box Installation and Commissioning

    2.3 EAB Installation

    2.3.1 Wall Preparation

    To prepare the wall:

    1. Mount four mural foot pieces on the back side of EAB box.

    2. Mark the drilling positions on the wall.

    Note: Depending on site configuration following position can be used

    20

    20

    254

    20

    20

    20

    20

    3. Drill the holes.

    2.3.2 Fix the EAB to the Wall

    To fix the EAB:

    1. Insert the expanding plugs in the holes.

    2. Place the EAB box in position and fix it to the wall with provided screws.

    3BK 17422 3101 RJZZA Ed.08 17/ 34

  • 8/11/2019 External Alarm Box n Installtion

    18/34

    2 External Alarm Box Installation and Commissioning

    2.3.3 Connect Cables to EAB

    2.3.3.1 Connect the Ground and Power Cables

    To connect the ground and power cables:

    1. Connect the ground cable to the site grounding plate

    2. Connect the ground cable to the ground terminal block

    3. At site power distribution panel switch OFF the EAB power breaker

    4. Connect the power cables to the power supply module as follows:

    Connect the 0V DC to the left position on the EAB power supply

    Connect the -48V DC to the right position on the EAB power supply as

    shown in the figure below.

    + 0

    + + +

    48 VDC0 VDC GND

    Figure 2: GND and Power Cables Connection

    5. Connect the power cables to the site distribution panel.

    18/ 34 3BK 17422 3101 RJZZA Ed.08

  • 8/11/2019 External Alarm Box n Installtion

    19/34

    2 External Alarm Box Installation and Commissioning

    2.3.3.2 Connect the Ethernet Cable

    Connect the Ethernet cable between the PC and the EAB controller module:

    1. Identify the Ethernet cable connecting position

    Figure 3: Ethernet Connector Location

    2. Connect the Ethernet cable to the controller module.

    3. Connect the Ethernet cable to the PC.

    3BK 17422 3101 RJZZA Ed.08 19/ 34

  • 8/11/2019 External Alarm Box n Installtion

    20/34

    2 External Alarm Box Installation and Commissioning

    2.3.3.3 Connect the External Alarm Cables

    If WAGO REVERSE protocol (normal close loop) is used you mustconnect provided straps for all unused alarm ports.

    To connect the external alarm cables to the alarm input modules:

    1. Insert the screwdriver into the opening above the connection

    2. Insert the wire into the opening

    Figure 4: Wire Connection Principle

    3. Remove the screwdriver.

    After removing the operating tool, the conductor is safely clamped.

    4. Perform the above steps for all alarms to be connected.

    5. If WAGO REVERSE protocol (normal close loop) is used, connect providedstraps for all unused alarm ports.

    The following table gives the alarm number allocation for all input modulesand for all ports on each module.

    Input Module Input Number Alarm Number

    13 & + 1

    14 & + 2

    15 & + 3

    1

    16 & + 4

    13 & + 5

    14 & + 6

    15 & + 7

    2

    16 & + 8

    20/ 34 3BK 17422 3101 RJZZA Ed.08

  • 8/11/2019 External Alarm Box n Installtion

    21/34

    2 External Alarm Box Installation and Commissioning

    Input Module Input Number Alarm Number

    13 & + 9

    14 & + 10

    15 & + 11

    3

    16 & + 12

    13 & + 13

    14 & + 14

    15 & + 15

    4

    16 & + 16

    13 & + 17

    14 & + 18

    15 & + 19

    5

    16 & + 20

    13 & + 21

    14 & + 22

    15 & + 23

    6

    16 & + 24

    2.4 EAB Commissioning

    2.4.1 Check the Power Supply and Power Up

    To check the power supply and powering up:

    1. Using a multimeter check at site power supply the voltage and polarity.

    2. Switch ON the power breaker for the EAB.

    LED on power supply module is switched ON.

    3BK 17422 3101 RJZZA Ed.08 21/ 34

  • 8/11/2019 External Alarm Box n Installtion

    22/34

    2 External Alarm Box Installation and Commissioning

    2.4.2 Set EAB Parameters

    If on the EAB Programmable Field Controller you find a label with the defaultgeneric IP Address of the device continue with section Configure Local PC(Section 2.4.2.6).

    The default generic IP address of EAB is 192.192.4.1 and the SubnetMask is 255.255.255.248.If on the EAB you do not find the label with default generic IP address continuewith next sectionCheck if Wago BootP Software is Installed(Section 2.4.2.1)

    2.4.2.1 Check if Wago BootP Software is Installed

    To check if Wago BootP Software is installed:

    1. From the Windows desktop click on [ Start ] then click [ Control Panel ] .

    The "Control Panel" window opens.

    2. Double-click on the Add or Remove Programs.

    The "Add or Remove Programs" window opens.

    3. If the WAGO BootP Server software is on the "Currently installed programs:"list continue with sectionDisable Windows XP Firewall(Section 2.4.2.4).

    4. If the WAGO BootP Server software is not on the "Currently installedprograms:" list continue with sectionDownload Wago BootP Software(Section 2.4.2.2).

    2.4.2.2 Download Wago BootP Software

    To download Wago BootP Software:

    1. Launch Mozilla Internet Browser. In the address field typehttp://www.wago.comthen press [ Enter ].

    The "Wago Innovative Connections " window opens.

    2. Click on [ WAGO Global Site ] link then select from menu Service ->Downloadsin the"WAGO Kontakttechnik GmbH & Co. KG" window.

    3. Click on ELECTRONICC

    The new frame opens when you are asked to agree with Terms andConditions.

    4. Click on [ I agree ] to accept the Terms and Conditions agreement.

    5. In the "ELECTRONICC Downloads" table chosse WAGO BootPServersoftware to download.

    6. Save to disk BootPSer.zipin thedirectory.7. Unzip BootPSer.zip. in the :\WagoSoftwarefolder.

    22/ 34 3BK 17422 3101 RJZZA Ed.08

    Edited by Foxit ReaderCopyright(C) by Foxit Software Company,2005-2008For Evaluation Only.

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 8/11/2019 External Alarm Box n Installtion

    23/34

    2 External Alarm Box Installation and Commissioning

    2.4.2.3 Install the Wago BootP Software

    You must be logged on the PC as an administrator or a member of theAdministrators group in order to install the software.

    To install Wago BootP Software:

    1. Navigate in\WagoSoftwaredirectory.

    2. Launch Setup.exe.

    3. In the "Welcome" ("Willkommen") window click on [ Next ] ([ Weiter ]).

    4. Enter the folder where WAGO BootP Server software will be installedc:\Program Files\WAGO Software\WAGO BootP Server\then click on[ Next ] ([ Weiter ]).

    5. Choose Start Menu FolderWAGO Software\WAGO BootP Server thenclick on [ Next ] ([ Weiter ]).

    6. Click on [ Finish ] ([ Beenden ]).

    2.4.2.4 Disable Windows XP Firewall

    During EAB installation the Windows XP firewall must be disable.If the firewall was enabled when you started the operation, be careful to set thefirewall back to enable at the end of the operation.You must to be logged on PC as an administrator or a member of Administratorsgroup in order to modify the firewall status.The following procedure must be performed only if the PC used for localterminal, is running Windows XP as operating system.

    To disable XP Firewall

    1. From the Windows desktop click on [ Start ] then click [ Run ]cmd

    A DOS window opens.

    2. In the DOS window enter the following commandnet stop SharedAccess

    If the Firewall was started the following message is displayedThe Windows Firewall/Internet Connection Sharing

    service was stopped successfully.

    If the Firewall was not started the following message is displayed

    The Windows Firewall/Internet Connection Sharing

    service is not started

    3. Close DOS window.

    If on the PC there are other applications used for port scanning, virus protectionor spam blocking, disable these applications during the EAB installation.

    3BK 17422 3101 RJZZA Ed.08 23/ 34

  • 8/11/2019 External Alarm Box n Installtion

    24/34

    2 External Alarm Box Installation and Commissioning

    2.4.2.5 Configure IP Addresses on EAB

    1. From the Windows desktop, follow the menu path:

    Start -> Programs -> Wago Software -> Wago BootP Server-> WagoBootP Server

    2. In "Wago BootP Server" window click on [ Edit Bootptab ] to configure

    BootP server.

    Any line that begins with a # symbol is a comment, and will not be processed.

    3. Edit the configuration parameters:

    To configure BootP changes only the line in bold

    The contents of this file looks like this:# bootptab.txt: database for bootp server#

    # Blank lines and lines beginning with # are ignored.#.................................................................................................# Example of entry with no gatewayKeinProxy:ht=1:ha=0030DE000002:ip=10.1.254.202:# Example of entry with gateway# The gateway address must be inserted in hexadecimal# after the T3 parameterhamburg:ht=1:ha=0030DE000003:ip=10.1.254.203:T3=0A.01.FE.01:

    In the line KeinProxy (Node Name) you need to modify:

    On the left side of EAB Programmable Field Controller you find theunique MAC ID of the device.

    Hardware address ha=0030DE000003 with the provided MAC

    Address

    Host IP address ip=10.1.254.202 with the default generic IP

    Address: ip=192.192.4.1

    At the end of line KeinProxy (Node Name) you need to add:

    Default generic Subnet Mask IP Address: sm=255.255.255.248

    : at the end of the line.

    At the beginning of the line:

    hamburg:ht=1:ha=0030DE000003:ip=10.1.254.203:T3=0A.01.FE.01:

    type #

    4. Click on File -> Saveand then close the file.

    5. Switch OFF the power breaker for the EAB and wait for a couple of seconds.

    6. Switch ON the power breaker for the EAB.

    24/ 34 3BK 17422 3101 RJZZA Ed.08

  • 8/11/2019 External Alarm Box n Installtion

    25/34

    2 External Alarm Box Installation and Commissioning

    To assign EAB IP address:

    7. In "Wago BootP Server" window click on [ Start ] to configure BootP server.

    If a messages sequence appears as shown in the figure below it means thatthe EAB Programmable Field Controller is configured with the provided IPaddress.

    8. Click on [ Stop ] then click on [ Exit ]

    If the firewall was enabled when you started the operation, be careful toset the firewall back to enable.

    3BK 17422 3101 RJZZA Ed.08 25/ 34

  • 8/11/2019 External Alarm Box n Installtion

    26/34

    2 External Alarm Box Installation and Commissioning

    2.4.2.6 Configure Local PC

    On the local PC you must set the network interface IP address to be in thesame network address range as the default generic IP address for EAB.Be careful to set the PC IP Address and subnetmask back at the end ofthe commissioning.

    To set the network interface IP address:

    1. If not already done, connect the PC to the EAB Ethernet Interface usingthe Ethernet cable.

    The Ethernet Interface is located on EAB Programmable Field Bus controller.

    2. Start the PC and login as local Administrator.

    3. Select the following menu path:

    Start -> Setting -> Network Connections

    The "Network Connections" window is displayed.

    4. Select Local Area Connection.

    The "Local Area Connection" window is displayed.

    5. Right-click on [ Properties ] and select Internet Protocol (TCP/IP) in the list.

    The "Properties" window is open.

    6. Click on [ Properties ].

    The "Properties" window is displayed.

    7. Select Use the following IP address frame.

    8. Type the PC IP address in the IP address field.

    The PC IP Address is 192.192.4.2

    9. Type the mask in the Subnetmask fieldThe Subnetmask is 255.255.255.248

    10. Click on [ OK ] in the "Internet Protocol (TCP/IP)" window.

    11. Click on [ OK ] in the "Local Area Connection" window.

    2.4.2.7 Set Date and Time on EAB

    To set date and time on EAB:

    1. Launch Mozilla Internet Browser. In the address field type the default genericEAB IP address then press [ Enter ].

    A "Status information" window is displayed.

    2. In the left frame of this window click on Clock

    3. A "Prompt" window is opened. Type:

    User name

    admin

    and Passwordwago

    Click on [ OK ]

    4. The new frame Configuration of the internal clock is displayed

    5. To set time on EAB:

    In the field Time on device type current time inhh:mm:ssformat.

    6. Click on [ SUBMIT ] to save new time on EAB.

    26/ 34 3BK 17422 3101 RJZZA Ed.08

  • 8/11/2019 External Alarm Box n Installtion

    27/34

    2 External Alarm Box Installation and Commissioning

    7. To set date on EAB:

    In the field Date on device type date in dd.mm.yyyyformat

    8. Click on [ SUBMIT ] to save new date on EAB.

    2.4.2.8 Configure Gateway Address on EAB

    To configure gateway address on EAB:

    1. Launch Mozilla Internet Browser. In the address field type the default genericEAB IP address then press [ Enter ].

    A "Status information" window is displayed.

    2. In the left frame of this window click on TCP/IP

    If a password dialog box is open, you must enter the user name and thepassword.

    3. The new frame TCP/IP configuration is displayed.

    4. In the field Gateway type the provided gateway.

    In case of BSC, active OMCP IP address

    In case of MFS, Router Interface IP address.

    5. Click on [ SUBMIT ] to save new gateway on EAB.

    2.4.2.9 Check EAB Port Configuration

    To check port configuration on EAB:

    1. Launch Mozilla Internet Browser. In the address field type the default genericEAB IP address then press [ Enter ].

    A Status information is displayed2. In the left frame of this window click on Port

    If a password dialog box is open, you must enter the user name and thepassword.

    3. The new frame Port configuration is displayed.

    4. Enable SNMP protocol corresponding to ports 161 and 162, if the case.

    5. Disable BootP protocol corresponding to port 68, if the case.

    6. Click on [ SUBMIT ] to save changes on EAB.

    3BK 17422 3101 RJZZA Ed.08 27/ 34

  • 8/11/2019 External Alarm Box n Installtion

    28/34

    2 External Alarm Box Installation and Commissioning

    2.4.2.10 Configure OMC-R IP Address on EAB

    To configure the OMC-R IP address on EAB:

    1. Launch Mozilla Internet Browser. In the address field type the default genericEAB IP address then press [ Enter ].

    The "Status information" window is displayed as below

    2. In the left frame of this window click on Snmp . A "Prompt" window isopened. Type:

    User name

    admin

    and Passwordwago

    Click on [ OK ]

    28/ 34 3BK 17422 3101 RJZZA Ed.08

  • 8/11/2019 External Alarm Box n Installtion

    29/34

    2 External Alarm Box Installation and Commissioning

    3. The new frame SNMP Configuration is displayed.

    The displayed frame: Current SNMP Configuration is similar with thefigure below.

    4. To assign OMC-R IP address where EAB is sending SNMP traps:

    In the field First SNMP Agent type the first OMC-R IP address.

    If is the case, in the field Second SNMP Agent type the second OMC-R

    IP address, otherwise leave it empty.

    In case of OMC-R X Large or XX Large configuration, enter the IP address ofthe Master Station.

    5. Click on [ SUBMIT ] and then click on [ RESET ] to save the currentsettings to the EAB.

    2.4.2.11 Modify EAB IP Address

    To modify IP address on EAB:

    1. Launch Mozilla Internet Browser. In the address field type the default genericEAB IP address then press [ Enter ].

    A "Status information" window is displayed.

    2. In the left frame of this window click on TCP/IP

    If a password dialog box is open, you must enter the user name and the

    password.

    3. The new frame TCP/IP configuration is displayed.

    4. In the field IP-Address type the provided EAB IP address.

    5. In the fieldSubnet Mask type the provided subnet mask address.

    6. In the field Gateway type the provided gateway.

    In case of BSC, active OMCP IP address

    In case of MFS, Router Interface IP address.

    7. Click on [ SUBMIT ] to save new values on EAB.

    3BK 17422 3101 RJZZA Ed.08 29/ 34

  • 8/11/2019 External Alarm Box n Installtion

    30/34

    2 External Alarm Box Installation and Commissioning

    8. Switch OFF the power breaker for the EAB and wait for a couple of seconds.

    9. Switch ON the power breaker for the EAB.

    The EAB Programmable Field Controller is configured with the provided IPaddress.

    2.4.2.12 Connect the EAB to the A9130 BSC/MFS Evolution

    To connect the EAB to the A9130 BSC/MFS Evolution:

    1. Identify the Ethernet cable used for EAB connection

    2. Connect the Ethernet cable:

    In case of BSC, from the EAB to the JAXSSW1 port ETH 5 in

    corresponding ATCA shelf as shown in the Figure 5

    OMCR

    BSC

    Evolution

    EAB

    IP

    Network

    IP

    Cisco

    Router*

    ETH 5SSW1

    BSC Site

    Figure 5: EAB Connection at BSC Site

    * The Cisco Router is localized at BSC site or in case of MLPPPconnection at TC/MSC site.

    In case of MFS, from the EAB to the Router/Switchs corresponding

    ETH port as shown in the Figure 6

    OMCRMFS

    Evolution

    EAB

    IP

    Network

    IP

    Cisco

    Router

    MFS Site

    Figure 6: EAB Connection at MFS Site

    30/ 34 3BK 17422 3101 RJZZA Ed.08

  • 8/11/2019 External Alarm Box n Installtion

    31/34

    2 External Alarm Box Installation and Commissioning

    2.4.2.13 Check EAB LED Status

    The following table describes the status of the LEDs, when EAB is operatingcorrectly.

    LED Status

    Link Green

    MS (Module Status) Green

    NS (Node Status) Green or flashing green

    TxD/RxD Flashing green

    I/O Green

    Table 1: Normal Operation Status

    2.4.2.14 Test the Connectivity

    To test the connectivity between BSC/MFS Evolution and EAB:

    1. Connect the Ethernet cable from the Local PC to the JAXSSW1 port ETH 8in corresponding ATCA shelf.

    2. Open a Telnet session on the active OMCP boardtelnet 172.17.y.x

    where:

    In case of MFS:

    x is 3 for OMCP1

    x is 4 for OMCP2

    In case of BSC:

    x is 30 for OMCP1

    x is 40 for OMCP2

    y is 3 for Shelf 3

    y is 4 for Shelf 4

    telnet 172.17.y.x

    3. Type:

    Username:root

    Password:

    alcatel

    3BK 17422 3101 RJZZA Ed.08 31/ 34

  • 8/11/2019 External Alarm Box n Installtion

    32/34

  • 8/11/2019 External Alarm Box n Installtion

    33/34

    2 External Alarm Box Installation and Commissioning

    2.5 Finish Installation

    To finish the installation:

    1. Fit the labels to the EAB.

    2. Write on the reserved area of the label the new IP address, if is the case.

    3. Fix the cover.

    4. Clear away packaging.

    5. Clean the site. Do not put packages into the customer bin.

    Figure 7: Clean the Site

    3BK 17422 3101 RJZZA Ed.08 33/ 34

  • 8/11/2019 External Alarm Box n Installtion

    34/34

    2 External Alarm Box Installation and Commissioning

    BLANK PAGE BREAK