Upload
shirley-wang
View
216
Download
0
Tags:
Embed Size (px)
DESCRIPTION
http://www.ijnese.org/paperInfo.aspx?ID=16247 Experiments are performed in a scaled 1x3 rod bundle adiabatic air-water test facility to investigate the effects of a spacer grid on single- and two-phase flows. A four-sensor conductivity probe is used to obtain detailed measurements of local time-averaged two-phase flow parameters, including the void fraction and interfacial area concentration, throughout the flow cross-section at four axial locations. The local two-phase flow data indicates that the spacer grid causes redistribution of the bubbles. In the transition from bubbly to slug flows, the spacer grid is found to promote bubble coalescence. In the slug to churn-turbulent transition, however, the grid breaks up the larger bubbles,
Citation preview
www.ijnese.org International Journal of Nuclear Energy Science and Engineering Volume 4 Issue 2, June 2014
doi: 10.14355/ijnese.2014.0402.02
50
Experimental Investigation on the Effects of a
Spacer Grid on Single- and Two-Phase Flows Joshua Wheeler1, Adam Rau2, Ted Worosz3, Seungjin Kim4
Department of Mechanical and Nuclear Engineering, The Pennsylvania State University
230 Reber Building, University Park, Pennsylvania 16802, USA
[email protected]; [email protected]; [email protected]; [email protected]
Received 15 April, 2014; Revised 20 May, 2014; Accepted 29 May, 2014; Published 23 June, 2014
© 2014 Science and Engineering Publishing Company
Abstract
Experiments are performed in a scaled 1x3 rod bundle
adiabatic air-water test facility to investigate the effects of a
spacer grid on single- and two-phase flows. A four-sensor
conductivity probe is used to obtain detailed measurements
of local time-averaged two-phase flow parameters, including
the void fraction and interfacial area concentration,
throughout the flow cross-section at four axial locations. The
local two-phase flow data indicates that the spacer grid
causes redistribution of the bubbles. In the transition from
bubbly to slug flows, the spacer grid is found to promote
bubble coalescence. In the slug to churn-turbulent transition,
however, the grid breaks up the larger bubbles, causing an
increase in the interfacial area concentration across the
spacer grid. Additionally, local velocity measurements in
single-phase liquid flow are performed with a laser Doppler
anemometer to investigate the change in the turbulence
structure across the grid. The axial turbulence intensity
measurements show the influence of the spacer grid
dimples, indicating an increased mixing effect from these
structures.
Keywords
Spacer Grid; Two-Phase Flow; Air-Water; Conductivity Probe;
Interfacial Area Concentration; Turbulence Intensity
Introduction
In a light water nuclear reactor core, the nuclear fuel
rods are supported by spacer grids. As such, spacer
grids are one of the major flow restrictions in the core
that affect the hydrodynamic and heat transfer
characteristics of the coolant flow. Understanding
these effects is required for best-estimate design and
analysis of the plant. In view of this, experimental
studies on the effects of spacer grids are indispensable
for improving the capability to predict the coolant
flow through the reactor.
Single-phase flows through rod bundles and spacer
grids have been investigated by many past researchers
(Rehme and Trippe, 1980; Neti et al., 1983; Yang and
Chung, 1998; Holloway et al., 2008; Caraghiaur et al.,
2009, Chang et al., 2008; Dominguez-Ontiveros et al.,
2012). Yang and Chung (1998) used a laser Doppler
anemometer (LDA) to investigate the effects of spacer
grids and mixing vanes on the turbulence structure in
a 5-by-5 spacer grid. Measurements were taken in the
center of the rod gap and in the center of the
subchannel. They concluded that the decay of the
turbulence intensity after the spacer grid is similar to
that downstream of mesh grids or screens. Similarly,
Caraghiaur et al. (2009) performed a study of multiple
flow parameters inside of a 24-rod fuel bundle with
spacer grids. Among the parameters studied was the
decay of axial turbulence intensity after the spacer
grid. The data showed that the turbulence intensity in
the side-wall subchannel increased sharply after the
spacer grid and then decayed monotonically, in
accordance with the correlations used by Yang and
Chung (1998). However, different behavior was
observed for the interior subchannel, implying that
turbulence intensity distribution is not exclusively
dependent on local channel geometry features. While
this study compared turbulence decay in the interior
and side-wall subchannels, the axial turbulence
intensity throughout the flow cross-section was not
collected in detail.
Comparatively few studies of two-phase flows
through rod bundles and spacer grids are available
that provide measurements of local two-phase flow
parameters, such as the void fraction, α, and interfacial
area concentration, ai. These parameters are of
particular importance since they are fundamental
International Journal of Nuclear Energy Science and Engineering Volume 4 Issue 2, June 2014 www.ijnese.org
51
geometric two-phase flow parameters that describe the
interfacial structure and, consequently, the interfacial
transfers of mass, momentum, and energy between the
phases. Of the available studies, Yun et al. (2008)
performed experiments in a large range of subcooled
boiling flow conditions. Measurements of local two-
phase flow parameters were acquired using a double-
sensor conductivity probe at multiple points within
the cross-section of an eighth-section of the central
subchannel of a 3x3 rod bundle. While this database
allows for study of the two-phase flow structure
around the rod, measurements were only performed
at one axial elevation, precluding study of the flow
development. Paranjape (2009) measured local two-
phase flow parameters using a four-sensor
conductivity probe at various elevations throughout
an eighth section of a 8x8 rod bundle with spacer
grids. However, owing to the near prototypic bundle
geometry, measurement locations in the subchannels
were limited to points along the rod-gap centerlines.
The present work experimentally investigates the
effects of a spacer grid on single- and two-phase flows
in a scaled adiabatic air-water test facility. A flow
visualization study is performed over a wide range of
two-phase flow conditions to study the effects of the
grid on flow regime transition and to identify flow
conditions for further investigation. Measurements of
local two-phase flow parameters are performed with a
four-sensor conductivity probe (Kim et al., 2000) to
study the effect of the grid on their development.
Additionally, single-phase liquid velocity
measurements are performed with a laser Doppler
anemometer (LDA) to investigate the change in
turbulence structure across the grid. Before discussing
the experimental results, an overview of the
experimental facility is provided.
Experimental Facility
Scaling Considerations
The present experimental facility was designed to
study the effects of a spacer grid on adiabatic air-water
flows through a rod bundle at near ambient
conditions. Owing to the differences between the
experimental conditions and prototypic reactor
conditions, scaling considerations were made in the
designing the facility (Nedwidek, 2011; Green, 2012).
A conventional pressurized water reactor (PWR)
(Westinghouse, 2006) was chosen as the reference
system for the scaling. Although the reactor coolant
primarily remains single-phase liquid during normal
PWR operation, two-phase flows are possible during
accident scenarios. To compare the reference and
experimental systems, scaling ratios were calculated
as:
exp
]ref
R
(1)
Where ψ represents a generic parameter of interest.
The subscripts ref and exp indicate that the parameters
are evaluated based on the reference and experimental
systems, respectively.
The scaling methodology was to maintain the scaling
ratios of key hydrodynamic and geometric parameters
near unity to preserve similarity to single- and two-
phase flows in the reference system. The
hydrodynamic parameters that were considered
included the channel liquid Reynolds number (Ref),
the bubble Reynolds number (Reb), and the bubble
Weber number (Web). Since the bubble size under
prototypic reactor conditions is smaller than that in
air-water flows at near ambient conditions, it was
important to maintain the relative size of the channel
structures with respect to the bubble size in the facility
design. Therefore, nineteen geometric scaling ratios
were considered that compared various bubble and
system length scales for the reference and
experimental systems. The geometric scaling ratios
were optimized to be near unity through design
iterations of the experimental spacer grid and rod
bundle dimensions. This scaling approach preserved
the scale of the channel structures with respect to each
other and to the bubble size. Table 1 shows several of
the important geometric parameters and the
associated scaling ratios that were used in the facility
design. Details of the scaling study are given by
Nedwidek (2011) and Green (2012).
Facility Description
Fig. 1 shows images of the Spacer Grid Separate-
Effects Test Facility. The test section is constructed
from clear cast acrylic to form a rectangular channel
(13.65cm x 4.45cm). Within the channel, there is a 1x3
array of 3.18cm diameter clear acrylic rods separated
by a pitch of 4.45cm. The resulting overall channel
hydraulic diameter (Dh) is 2.23cm. The entrance of the
spacer grid section, which is 10Dh long, is located 27Dh
downstream of the air-water injector. The total
development length after the spacer grid is 109Dh.
Seven axial measurement ports are available along the
length of the test section to provide access to the flow
for instrumentation. One port is located 7Dh upstream
www.ijnese.org International Journal of Nuclear Energy Science and Engineering Volume 4 Issue 2, June 2014
52
of the entrance of the spacer grid, and the remaining
six ports are located 7, 16, 30, 45, 69, and 98Dh
downstream of the exit of the spacer grid.
FIG. 1 SCHEMATIC AND PHOTOGRAPH OF THE SPACER GRID
SEPARATE EFFECTS TEST FACILITY
The spacer grid section is designed to be
interchangeable with removable grid inserts so that
different grid designs can be investigated. In view of
the complicated geometry and proprietary designs of
prototypic spacer grids, a simplified spacer grid
design based on a reference PWR spacer grid is
implemented in the present study. The simplified grid
does not include swirl vanes, and the dimples and
springs that holds the rods in place are simulated as
circular arcs. Fig. 2 shows images of the experimental
spacer grid section and a diagram of a representative
subchannel showing the arrangement of the dimples
and springs. Note that the springs are located at the
mid-height of the grid, and the dimples are located
both at the bottom and top of the grid.
FIG. 2 IMAGES OF THE EXPERIMENTAL SPACER GRID
Although the channel walls influence the flow around
the 1x3 array of rods unlike in a prototypic system,
this initial configuration was selected to allow for
unobstructed access to the flow area around the
simulant fuel rods. As such, this configuration
provides the ideal condition for applying optical
instrumentation, including a high speed video camera
for flow visualization and a laser Doppler anemometer
for local liquid velocity measurements, around the
rods and within the spacer grid section. Furthermore,
a traversing unit, shown in Fig. 3, was designed to fit
in the measurement ports to precisely position a four-
sensor conductivity probe (Kim et al., 2000)
throughout the channel cross-section. This capability
enables detailed measurements of local time-averaged
two-phase parameters to be acquired around the
simulant fuel rods.
TABLE 1 EXAMPLE GEOMETRIC SCALING PARAMETERS
Parameter (ψ) Description Reference (ψref) Experimental (ψexp) Scaling Ratio (ψ]R)
P/Drod Fuel Rod Pitch to Diameter Ratio 1.378 1.4 0.98
LSG/Dh,ch Spacer Grid Length to
Subchannel Hydraulic Diameter Ratio 6.539 6.539 1.00
Dh,ch/Db,sph Subchannel Hydraulic Diameter to
Maximum Spherical Bubble Diameter Ratio 14.067 14.726 0.96
Dh,SG/Db,sph Spacer Grid Hydraulic Diameter to
Maximum Spherical Bubble Diameter Ratio 6.479 6.783 0.96
Spring
Grid Strap
Dimple
Representative Subchannel
Top View from Back Front View
International Journal of Nuclear Energy Science and Engineering Volume 4 Issue 2, June 2014 www.ijnese.org
53
FIG. 3 LOCAL CONDUCTIVITY PROBE TRAVERSING UNIT
The facility is an adiabatic air-water test facility
capable of generating single- and two-phase flows.
Experiments are performed at 20°C and near
atmospheric pressure conditions. Filtered water is
supplied to the test section from a 2270L accumulator
tank by a 10HP centrifugal pump. A variable
frequency controller is used to set the pump speed
and, consequently, adjust the liquid flow rate. An air
compressor supplies dry air to the facility that is
regulated to a gauge pressure of 414kPa. The air is fed
to three sintered stainless steel spargers in the dual-
stage air-water injector to generate bubbles for two-
phase flow conditions. The spargers have an average
pore size of 10μm, and they are the same diameter as
the acrylic rods. Each of the three rods sits flush on
top of a sparger such that the bubbles are injected
around the circumference of the rods without
obstruction. The water supply is split into main and
auxiliary liquid flows. The main liquid flow is
distributed amongst twelve lines to provide uniform
liquid injection and is varied to set the desired flow
condition. The auxiliary liquid flow is fed at a constant
rate into annular regions around the air spargers in the
injector to shear off bubbles. This provides a controlled
method of injecting a uniform bubble size at the inlet
of the test section independent of the main liquid flow
rate. After passing through the test section, the flow
enters a two-phase separator, where the air is allowed
to exhaust to the room and the water returns to the
accumulator tank.
Instrumentation
The air flow rate is controlled by set of rotameters with
accuracies of ±3% of their full scale readings. The
liquid flow rate is measured by an electromagnetic
flow meter with an accuracy of ±0.5% of the flow rate.
At each measurement port, pressure taps are available
to acquire pressure measurements with a differential
pressure transducer with an accuracy of ±0.04% of the
measurement. In two-phase flow experiments, a four-
sensor conductivity probe is used to measure local
time-averaged two-phase flow parameters including
the void fraction (α), interfacial area concentration (ai),
bubble velocity (vg), and bubble Sauter-mean diameter
(DSm) (Kim et al., 2000).
An integrated backscatter LDA system capable of one-
dimensional velocity measurements is used to
measure the local axial velocity in single-phase liquid
flow. The light beam is generated by a 600nm
wavelength 35mW laser; other characteristics of the
LDA are listed in Table 2. The LDA is mounted on a
two-dimensional traversing system. The traversing
system has a resolution of 1µm. In positioning the
LDA measurement volume within the channel, the
differences in the refractive indices of air, acrylic, and
water are accounted for by employing Snell’s law. To
perform the single-phase liquid velocity
measurements, the flow is seeded with polyamide
seeding particles that have a mean diameter of 20µm
and specific gravity of 1.04.
TABLE 2 LDA CHARACTERISTICS
Measurement Length 300 mm
Beam Width 2.0 mm
Measurement Volume 0.1mm x 0.1mm x1.0mm
Maximum Measureable Velocity 27 m/s
Measurable Velocity Fluctuation 0.7µm/s-4.6mm/s
Experimental Results and Discussion
Two-Phase Flow Visualization Study
Flow visualizations are performed with a high-speed
video camera to visually observe the effect of the
spacer grid on flow regime transition and to identify
conditions of interest for local conductivity probe
measurements. Videos are captured in flow conditions
in the superficial liquid velocity (jf) range of 0.25 m/s to
2 m/s and superficial gas velocity (jg) range of 0.1 m/s
to 6 m/s, at locations 7Dh upstream and downstream of
the entrance and exit to the spacer grid section,
respectively. These positions are selected so that the
visualizations correspond to the available conductivity
probe measurement locations. The videos were
independently viewed and classified by the
researchers into bubbly, cap-turbulent, slug, and
churn-turbulent flow regimes. Example images of
these flow regimes are shown in Fig. 4.
The flow conditions were then plotted on the jf-jg plane
to identify transition boundaries for the flow regimes
observed both before and after the grid. Fig. 5 shows
the resulting flow regime map for the facility. The
solid and dashed lines indicate the transition
boundaries identified before and after the grid
Four-Sensor
Conductivity Probe
www.ijnese.org International Journal of Nuclear Energy Science and Engineering Volume 4 Issue 2, June 2014
54
respectively. The numbered dots indicate the flow
conditions that were selected for further investigation
with the local conductivity probe, which are discussed
in the next section.
0.1
1
0.1 1
j f[m
/s]
jg [m/s]
1 2 3 4
5 6 7 8
5
5
FIG. 5 FLOW REGIMES BEFORE AND AFTER THE SPACER GRID.
An impact on the flow regime transition is apparent in
Fig. 5. The transition boundaries between bubbly to
turbulent-cap and turbulent-cap to slug are observed
to shift to lower jg after the spacer grid. This indicates
that the grid is promoting increased bubble
coalescence near the transition boundaries. High speed
images demonstrating this effect for the turbulent-cap-
to-slug transition boundary are shown in Fig. 6.
In the transition between the slug and churn-turbulent
flow regimes, the grid is found to induce a breakup
effect on the flow structure, causing the flow to
resemble a slug regime immediately after the spacer
grid. The grid breaks up the larger gas voids as they
travel through the spacer grid, generating increased
amount of larger bubbles observed after the grid.
Smaller bubbles are generated when the larger bubbles
are forced to breakup upon entering the spacer grid.
Fig. 7 shows example images of this phenomenon.
(A) (B)
FIG. 6 IMAGES OF TWO-PHASE FLOW (A) BEFORE AND (B)
AFTER THE SPACER GRID INDICATING ENHANCED BUBBLE
COALESCENCE AT THE TURBULENT-CAP TO SLUG
BOUNDARY (jf = 1.00 m/s and jg,1= 0.87 m/s).
(A) (B)
FIG. 7 IMAGES OF TWO-PHASE FLOW (A) BEFORE AND (B)
AFTER THE SPACER GRID INDICATING BUBBLE BREAKUP AT
THE SLUG TO CHURN-TURBULENT BOUNDARY (jf = 1.00 m/s
and jg,1= 1.6 m/s).
Two-Phase Flow Experimental Conditions and
Measurement Locations
Table 3 shows the ‹jg1›1 and ‹jf› values for the two-
phase flow conditions considered in the present study.
The subscript 1 indicates that the jg values shown
correspond to the first measurement location 7Dh
upstream of the spacer grid. To study the effect of
increasing gas flow rate through different flow
regimes, gas flow rates were selected in each of the
identified flow regimes from Fig. 5.
(A) (B) (C) (D)
FIG. 4 IMAGES OF (A) BUBBLY, (B) TURBULENT-CAP, (C) SLUG, AND (D) CHURN-TURBULENT TWO-PHASE FLOW REGIMES.
International Journal of Nuclear Energy Science and Engineering Volume 4 Issue 2, June 2014 www.ijnese.org
55
TABLE 3 TWO-PHASE FLOW CONDITIONS INVESTIGATED
Run ‹jf› [m/s] ‹jg1›1 [m/s] Run ‹jf› [m/s] ‹jg›1 [m/s]
1 3.00 0.10 5 1.00 0.40
2 3.00 0.23 6 1.00 0.87
3 3.00 0.34 7 1.00 1.1
4 3.00 0.51 8 1.00 1.6
Fig. 8 shows the cross-sectional measurement mesh
that was used for conductivity probe measurements.
For a given axial location, local measurements were
performed at 64 locations throughout the cross-section
around the center rod. The measurement points were
selected to capture the variation of two-phase flow
parameters near the surface of the rod. Measurements
were performed at four axial locations: 7Dh upstream
and 7, 16, and 45Dh downstream of the spacer grid.
The last measurement location corresponds to the
location of the next spacer grid in a prototypic system.
(Hochreiter et al., 2010).
FIG. 8 LOCAL CONDUCTIVITY PROBE MEASUREMENT POINTS
IN THE CHANNEL CROSS-SECTION
Repeatability and Benchmarking of Local Two-Phase
Flow Measurements
To confirm the repeatability of the experimental data,
measurements along the centerlines between the rods
were repeated throughout the study. Fig. 9 compares
void fraction measurements collected along the left
rod-gap centerline 7Dh before the spacer grid for two
different trials of Run 8. The trials were separate flow
start-ups using different conductivity probes. The
solid red line on the inset view of the channel cross-
section indicates the line along which the local
measurements were acquired. Referring to Fig. 8, the
void fraction data is plotted against the y-coordinate
nondimensionalized by the half-pitch (Phalf). The
negative and positive y/Phalf values refer to the front
and back of the channel, respectively. In each trial, the
flow condition was set up using the same start-up
procedure beginning with an empty test section. From
the repeatability tests, it is found that the
measurements are generally repeatable within
approximately ±10%. This provides confidence in the
ability to consistently replicate the experimental data.
0
0.2
0.4
0.6
0.8
1
-1 -0.5 0 0.5 1
α [
-]
y/Phalf [-]
Trial 1Trial 2
10% error bars on
FIG. 9 REPEATABILITY OF VOID FRACTION MEASUREMENTS
ALONG THE LEFT ROD-GAP CENTERLINE at L/Dh=-7 FOR RUN
8 (jf =1.00 m/s & jg,1= 1.6 m/s).
To benchmark the conductivity probe measurements,
two measures of the volumetric gas flux (i.e.
superficial gas velocity, ‹jg›z) at each axial location are
compared. One measure of ‹jg›z can be obtained by
area-averaging the product of the local void fraction
and bubble velocity measurements obtained with the
conductivity probe as:
‹jg›z = ‹αvg›z (2)
where the brackets ‹-› denote the area-average
operator. The second measure of ‹jg›z is obtained from
the inlet gas flow rate, Qg, and the pressure pz at a
given axial location. Qg and pz are measured by the
rotameters and the pressure transducer, respectively,
so they provide a global measurement, ‹jg›z,global. Thus,
comparing ‹αvg›z and ‹jg›z,global compares local and
global measurement techniques for obtaining ‹jg›z.
Based on the accuracies of the conductivity probe
(Kim et al., 2000; Wu and Ishii, 1999), pressure
transducer, and flow meters, measurements that
benchmark within approximately ±10% are considered
reliable for bubbly flows.
Fig. 10 compares the ‹αvg›z obtained from the
conductivity probe data to the value obtained from the
gas flow rate and pressure measurements, ‹jg›z,global.
Ideally, the values should be equal and fall on a 45°
line extending from the origin; ±10% deviation from
the ideal case is indicated by the dashed lines. The
majority of the measurements agree well within ±10%,
for the bubbly conditions. For non-bubbly flow
conditions, such as Runs 6-8, there are four data points
showing probe measurements that underestimate
those estimated by the pressure transducer and
volumetric gas flux. Considering that these points
www.ijnese.org International Journal of Nuclear Energy Science and Engineering Volume 4 Issue 2, June 2014
56
represent data acquired near the inlet, the difference
may stem from inlet effects.
0.0
0.5
1.0
1.5
2.0
0.0 0.5 1.0 1.5 2.0
<αv
g>z
[m/s
]
<jg>z,global [m/s]
Run 1 Run 5
Run 2 Run 6
Run 3 Run 7
Run 4 Run 8
±10% lines
FIG. 10 VOLUMETRIC GAS FLUX BENCHMARK
Local Two-Phase Flow Parameters
A state-of-the-art four-sensor conductivity probe was
used to acquire measurements of local time-averaged
two-phase flow parameters in the test section.
Experimental data from Runs 2, 6, and 8 are presented
to discuss characteristic effects of the spacer grid on
the development of two-phase flow parameters.
Run 2 is representative of the bubbly conditions
considered at jf=3.0 m/s and 1.0 m/s. Fig. 11 presents
conductivity probe measurements for Run 2 of local
void fraction, interfacial area concentration, bubble
velocity, and Sauter-mean diameter along the left rod-
gap centerline at each axial location. ±10% error bars
are included on the measurements at -7Dh for
reference. A slightly skewed void fraction profile, Fig.
11(A), towards the front of the channel (-y/Phalf) is
observed at the measurement location upstream of the
spacer grid (-7Dh). This is attributed to inlet effects
characteristic of the present test facility. The void
fraction profile becomes more symmetric after the
spacer grid (7Dh), indicating that the grid induces a
redistribution of the bubbles within the channel,
reducing the inlet effect. Downstream of the grid
(45Dh), a wall-peaked void fraction profile is observed.
Peaking observed at the channel wall would not occur
in a rod bundle of infinite extent. However, a peak is
also observed in the center of the channel, indicating
peaking near the surface of the rods. Similar trends are
observed in the interfacial area concentration profiles,
Fig. 11(B), since the interfacial area concentration is
proportional to the void fraction in bubbly flows.
FIG. 11 CONDUCTIVITY PROBE MEASUREMENTS OF LOCAL
(A) α, (B) ai, (C) vg, AND (D) DSm ALONG THE LEFT ROD-GAP
CENTERLINE FOR RUN 2 (jf=3.00 m/s & jg,1 =0.23 m/s). ±10%
ERROR BARS SHOWN.
International Journal of Nuclear Energy Science and Engineering Volume 4 Issue 2, June 2014 www.ijnese.org
57
The bubble velocity, Fig. 11(C), and Sauter-mean
diameter, Fig. 11(D), centerline profiles do not vary
significantly between the measurement locations
immediately upstream and downstream of the spacer
grid. Considering that the spacer grid induces
additional pressure loss, this observation is
counterintuitive. At the measurement locations further
downstream, there is a noticeable increase in both vg
and DSm. The trend across the grid for vg and DSm may
be indicative of bubble disintegration due to the
spacer grid. The vg measurements closest to the
channel wall remain relatively similar at each axial
location with significant change towards the center,
and the DSm profile is relatively flat along the entire
centerline. The increased velocity gradient near the
channel wall further downstream may be responsible
for the wall-peaking phenomenon in the void fraction
and interfacial area concentration profiles.
The observed phenomena indicate two-characteristic
effects of the spacer grid in the bubbly flow conditions
investigated. The redistribution of the void fraction
after the spacer grid indicates increased mixing and
lateral motion of the bubbles. Also, spacer grid
induced bubble disintegration is indicated by the near
constant DSm across the grid.
The relatively dense measurement mesh allows for the
experimental data to be plotted as a surface
throughout the cross-section of the subchannel to help
better visualize the distribution of the parameters.
Three-dimensional surface plots using cubic
interpolation of the experimental data, assuming all
parameters go to zero at the surface of the rod and
channel walls, are generated in MATLAB. Figs. 12(A)
and (B) are plots of the measured local void fraction
and interfacial area concentration for Run 2. The black
region on the surface plots represents the rod location.
In Figs. 12(A) and (B), the redistribution effect of the
grid is readily observed, as the skewed void fraction
and interfacial area concentration profiles before the
grid are redistributed throughout the subchannel by
7Dh after the grid. 16Dh downstream of the grid,
additional redistribution is observed, leading to more
uniform profiles. Slight wall-peaking is beginning to
develop, as well; this is particularly clear near the
surface of the rod in the interfacial area concentration
profile. By 45Dh downstream of the grid, a distinct
wall-peaked profile at the channel walls and around
the surface of the rod is observed. A similar pattern of
the gas phase being redistributed and developing a
wall peak by 45Dh after the grid is observed for Runs
1,3, and 4. The turbulent-cap condition of Run 5 at the
lower superficial liquid flow rate is also redistributed
after the grid. However, it is wall-peaked before the
grid (-7Dh) and remains so up to 45Dh after the grid.
(A) (B)
FIG. 12 SURFACE PLOTS OF CONDUCTIVITY PROBE
MEASUREMENTS OF LOCAL (A) VOID FRACTION AND (B)
INTERFACIAL AREA CONCENTRATION ALONG THE TEST
SECTION FOR RUN 2 (jf=3.00 m/s & jg,1 =0.23 m/s).
With increasing gas flow rate, the flow transitions
away from bubbly and turbulent-cap flows to become
a slug flow. Slug flows contain intermittent slug
bubbles, large bullet-nosed bubbles that span across
subchannels. The slug bubbles are followed by a wake
region containing bubbly-like flow called liquid slugs.
Since different size bubbles have different transport
characteristics, the bubbles are categorized into two
groups in the conductivity probe signal processing
scheme. Group-I consists of smaller spherical and
distorted bubbles, and group-II consists of cap, slug,
and churn-turbulent bubbles (Kim et al., 2000).
Run 6 is located in the transition region between
turbulent-cap and slug flows. Fig. 13 shows the local
total, group-I, and group-II void fraction
measurements for Run 6 along the left rod-gap
centerline at each axial location. The total void fraction
is equal to the sum of the group void fractions. The
total void fraction profile, Fig. 13(A), is initially
www.ijnese.org International Journal of Nuclear Energy Science and Engineering Volume 4 Issue 2, June 2014
58
skewed at -7Dh and becomes more uniform
downstream of the spacer grid, indicating a
redistribution effect of the grid similar to the bubbly
flows. Figs. 13(B) and (C) show the group-I and group-
II void fractions, respectively. The group-I void
fraction is distributed relatively uniformly throughout
the channel, peaking near the walls. The group-II void
profile is highly skewed at -7Dh, which is attributed to
inlet effects, but becomes more symmetric as the flow
develops along the test section. Thus, the group-II
bubbles are the primary source of the asymmetry
observed in the total void fraction profile before the
spacer grid and the continuation downstream. It is
also observed that immediately downstream of the
grid (7Dh) there is a significant decrease in the group-I
void fraction with an increase in group-II void
fraction. The flow visualizations shown in Fig. 6 for
this condition support this result with the increased
number of slug bubbles downstream of the grid. Such
a dramatic exchange between the group void fractions
is one indication that bubble coalescence is enhanced
by the spacer grid in the transition from turbulent-cap
to slug flows.
Fig. 14 shows the local total, group-I, and group-II
interfacial area concentration measurements for Run 6
along the left rod-gap centerline. In contrast the total
void fraction for this condition, the total interfacial
area concentration, Fig. 14(A), has a more uniform
profile across the cross-section, with slight wall
peaking. Unlike bubbly flows where bubbles are
dispersed and approximately spherical, the total
interfacial area concentration is not directly
proportional to the void fraction in higher gas flow
rate conditions owing to the wider range of bubble
sizes and shapes. Noting the different scales in Figs.
14(B) and (C) that show the group-I and group-II
interfacial area concentrations, respectively, it is
apparent that the group-I interfacial area
concentration contributes to the majority of the total
interfacial area concentration in this condition. In view
of the more uniform group-I void fraction and
interfacial area concentration profiles, this explains
why the total interfacial area concentration is more
uniform in comparison to the total void fraction. The
group-I interfacial area concentration decreases
dramatically across the spacer grid, similar to the
group-I void fraction. A decrease in the interfacial area
concentration also indicates bubble coalescence. The
trends in the local void fraction and interfacial area
concentration profiles are also supported by the
development of the area-averaged parameters along
the test section (Wheeler et al., 2014).
FIG. 13 CONDUCTIVITY PROBE MEASUREMENTS OF (A) TOTAL, (B) GROUP-I, AND (C) GROUP-II VOID FRACTION FOR RUN 6 (jf=1.00
m/s & jg,1 =0.87 m/s). ±10% ERROR BARS SHOWN.
FIG. 14 CONDUCTIVITY PROBE MEASUREMENTS OF (A) TOTAL, (B), GROUP-I, AND (C) GROUP-II INTERFACIAL AREA
CONCENTRATION FOR RUN 6 (jf=1.00 m/s & jg,1 =0.87 m/s). ±10% ERROR BARS SHOWN.
International Journal of Nuclear Energy Science and Engineering Volume 4 Issue 2, June 2014 www.ijnese.org
59
The next flow condition considered, Run 8, is located
in the transition from the slug flow regime into the
churn-turbulent regime. Fig. 15 shows local total,
group-I, and group-II void fraction measurements for
Run 8 along the left rod-gap centerline at each axial
location. The corresponding interfacial area
concentration measurements for are shown in Fig 16.
The total void fraction, Fig. 15(A), shows an increasing
trend along the test section. The total interfacial area
concentration, Fig 16(A), increases across the grid, but
it then decreases as the flow continues downstream.
The group void fractions are not observed to change
significantly across the grid. However, the group-I
interfacial area concentration, Fig. 16(B) is observed to
increase across the grid, while the group-II interfacial
area concentration, Fig. 16(C), remains relatively
unchanged. The decreasing group interfacial area
concentrations farther downstream (16Dh and 45Dh) is
an indicator of this flow condition’s natural tendency
to coalescence in the absence of flow obstructions. The
increasing trend of interfacial area concentration
across the grid is indicative of the grid breaking up the
bubbles, offsetting the natural tendency of the flow.
FIG. 15 CONDUCTIVITY PROBE MEASUREMENTS OF (A) TOTAL, (B) GROUP-I, AND (C) GROUP-II VOID FRACTION FOR RUN 8 (jf=1.00
m/s & jg,atm =1.6 m/s). ±10% ERROR BARS SHOWN ON.
FIG. 16 CONDUCTIVITY PROBE MEASUREMENTS OF (A) TOTAL, (B), GROUP-I, AND (C) GROUP-II INTERFACIAL AREA
CONCENTRATION FOR RUN 8 (jf=1.00 m/s & jg,1 =1.6 m/s). ±10% ERROR BARS SHOWN.
FIG. 17 (A) GROUP-I AND (B) GROUP-II SAUTER-MEAN DIAMETERS FOR RUN 8 (jf=1.00 m/s & jg,1 =1.6 m/s). ±10% ERROR BARS SHOWN.
www.ijnese.org International Journal of Nuclear Energy Science and Engineering Volume 4 Issue 2, June 2014
60
The group DSm provide additional insight to what is
occurring in this flow condition. The group-I DSm, Fig.
17(A), decreases across the grid and stays relativity
constant downstream. Group-II maintains relativity
constant across the grid even though there is an
additional pressure drop, which should lead to an
increase. These trends collectively are indicative a
breakup effect that results in the generation of group-I
bubbles and smaller group-II bubbles from group-II
bubbles as they travel through the spacer grid. This is
supported by the flow visualizations for this
condition, Fig. 7, where the wake regions following
the large bubbles were observed to become denser
after the grid, indicating the generation of numerous
smaller bubbles. These observations are also
supported in the trends of the area-averaged
experimental data discussed by Wheeler et al. (2014).
Single-Phase Liquid Velocity Measurements
Single-phase axial liquid velocity measurements were
performed using an LDA to study the development of
the turbulence structure across the grid. Mean local
axial velocities and axial turbulence intensities were
investigated. At a given axial elevation, local
measurements were performed at 89 positions within
the cross-section around the center rod on a mesh
similar to that used for the conductivity probe
measurements. The measurements were performed at
three axial locations along the test section: -3Dh before
the spacer grid and 3Dh and 40Dh after the spacer grid.
To ensure statistical reliability of measurements, a
minimum of 5000 samples are measured at each local
point, and the burst signal validation was maintained
above 93%.
Two single-phase liquid flow conditions were chosen
such that the bulk liquid velocities, Ubulk, corresponded
to the superficial liquid velocities used during the two-
phase experiments. The flow conditions and
corresponding channel Reynolds numbers are
provided in Table 4.
TABLE 4 SINGLE-PHASE LIQUID FLOW CONDITIONS FOR LDA
Run Ubulk [m/s] Ref [-]
i 3.00 6.68x104
ii 1.00 2.23x104
In view of presenting the experimental results, the
local mean axial velocity (U) is normalized by the bulk
velocity Ubulk. Fig. 18 shows the contour plots for
normalized liquid velocity measurements taken in the
test section. The black semicircle region represents the
location of the rod. The dashed semicircles at 3Dh after
the spacer grid show the location and approximate
geometry of the two most downstream features of the
spacer grid, the dimples. The dots note the locations of
the actual measurements of the flow. The gray section
represents the area near the channel wall that was not
measured in the current experiments focusing on the
distribution of the flow around the center rod. The
axial velocity in the test section is decreased in the
areas directly above the spacer grid features and
increases in the azimuthal gap between them. Far
downstream of the spacer grid, the velocity contours
return to a similar flow structure found before the
spacer grid.
FIG. 18 CONTOURS OF MEAN AXIAL LIQUID VELOCITY
MEASUREMENTS AT THREE AXIAL LOCATIONS FOR RUN I
(Ubulk=3.00 m/s).
The LDA system used can also obtain the turbulence
intensity. The turbulence intensity (I) is defined as the
root-mean-square velocity variation divided by the
mean axial liquid velocity:
'RMS
uI
U (3)
Figure 19 shows contour plots of the turbulence
intensity at axial locations 3Dh before the spacer grid,
3Dh and 40Dh after the spacer grid. In general, the
International Journal of Nuclear Energy Science and Engineering Volume 4 Issue 2, June 2014 www.ijnese.org
61
spacer grid creates a rise in turbulence intensity
despite the absence of swirl vanes. The two most
downstream dimples appear to have the most
significant impact on axial turbulence intensity; these
are located in the front of the channel and in the left
rod gap. The most prominent turbulence intensity
peak is found at the azimuthal midpoint between
these two spacer grid features. Another region of high
turbulence intensity appears to the right of the front
dimple. Axial turbulence intensity is not found to
increase directly above the grid features, and is in fact
lower above the left dimple than on the right side of
the channel at this axial location. Far downstream of
the spacer grid the turbulence intensity returns to a
similar flow structure found before the spacer grid.
Understanding how the individual structures impact
the turbulence intensity will enable methods to be
developed that increase the mixing in the flow
through the spacer grid.
FIG. 19 CONTOURS OF AXIAL TURBULENCE INTENSITY
MEASUREMENTS AT THREE AXIAL LOCATIONS FOR RUN I
(Ubulk=3.00 m/s).
Conclusions
The current study performed separate-effects
experiments on the effects of a spacer grid on the
hydrodynamics of single- and two-phase flows. The
investigation was conducted through the use of a
scaled 1x3 rod bundle, designed to allow for detailed
local measurements around the simulant fuel rods. As
a first step, a flow visualization study was performed
over a wide range of two-phase flow conditions to
study the effects of the grid on flow regime transition.
Although the transition boundaries developed from
the visualizations in the present study are specific to
the current facility and likely cannot be used in
general, they do provide insight into the possible
effects of spacer grids on flow regime transition. These
include enhanced bubble coalescence in the transition
from bubbly to slug flows, as well as bubble breakup
in the transition from slug to churn-turbulent flows.
Based on the flow visualization study, eight two-phase
flow conditions were chosen to investigate the effects
of the spacer grid on local two-phase flow parameters
in regions of flow regime transition using a four-
sensor conductivity probe. Detailed local
measurements of two-phase flow parameters
including the void fraction, interfacial area
concentration, bubble velocity, and bubble Sauter-
mean diameter were performed with the conductivity
probe throughout the cross-section of a representative
subchannel at four axial locations, yielding a database
of over 2000 local measurement points. The local
conductivity probe data demonstrates the increased
mixing effect induced by the spacer grid. The local
void fraction in bubbly flows demonstrated the effect
of the mixing creating a redistribution effect following
the grid. For the conditions on the transition boundary
of turbulent-cap to slug flow, the decrease in group-I
void fraction and increase in group-II void fraction
indicates a coalescence effect. This coalesce effect is
also observed globally in the shift in the flow regimes.
The experimental data on transition boundary of slug
to churn-turbulent flows, shows smaller group-I DSm,
and nearly constant group-II DSm across the grid. This
occurrence indicates that the group-II bubbles are
breaking up into smaller group-I and group-II upon
exiting the spacer grid, thus increasing the interfacial
area concentration.
In addition to the investigations in two-phase flow
conditions, single-phase liquid axial velocity
measurements were performed using a 1-D LDA to
investigate the change of the turbulence structure
induced by the spacer grid. The individual structures
of the grid are found to influence the axial turbulence,
downstream of the grid. Specifically, the turbulence
intensity is observed to increase immediately
downstream of the dimple structures in the spacer
www.ijnese.org International Journal of Nuclear Energy Science and Engineering Volume 4 Issue 2, June 2014
62
grid. Understanding how these characteristic features
of the spacer grid impact the distribution of flow is
critical in understanding and improving the mixing
effects.
Nomenclature
Latin
ai Interfacial area concentration [1/m]
Dh Hydraulic diameter [cm]
Drod Rod diameter [cm]
DSm Bubble Sauter-mean diameter [mm]
I Axial turbulence intensity [-]
jk kth-phase superficial velocity [m/s]
L/Dh Non-dimensional axial distance [-]
P Rod pitch [cm]
Phalf Half rod pitch, P/2, [cm]
pz Gauge pressure [kPa]
Qg Inlet gas flow rate [scfh]
Reb Bubble Reynolds number [-]
Ref Channel liquid Reynolds number [-]
U Local mean axial liquid velocity [m/s]
Ubulk Bulk single-phase liquid velocity [m/s]
'RMSu Local root-mean square liquid velocity [m/s]
vg Bubble velocity [m/s]
Web Bubble Weber number [-]
Greek
α Void fraction [-] Generic parameter
]R Scaling ratio [-]
Subscripts and Superscripts
atm Atmospheric pressure condition
b Bubble
ch Subchannel
exp Experimental system
f Liquid phase
g Gas phase
I Group-I quantity
II Group-II quantity
ref Reference system
SG Spacer Grid
sph Spherical
total Total quantity
Mathematical Operators
Area-average, 1
AdA
A
Void-weighted area-average,
REFERENCES
“The Westinghouse Pressurized Water Reactor Nuclear
Power Plant.” Westinghouse Electric Company LLC,
2006.
Caraghiaur, Diana, Henryk Anglart and Wiktor Frid.
“Experimental Investigation of Turbulent Flow through
Spacer Grids in Fuel Rod Bundles.” Nucl. Eng. and
Design 239 (2009): 2013-2021.
Chang, Seok Kyu, Sang Ki Moon, Won Pil Baek, and Yong
Don Choi. “Phenomenological investigations on the
turbulent flow structures in a rod bundle array with
mixing devices.”Nucl. Eng. and Design 238 (2008):600-
609.
Dominguez-Ontiveros et al. “Experimental benchmark data
for PWR rod bundle with spacer grids.” Nucl. Eng. and
Design 253 (2012): 396-405.
Green, Chad R. “Experimental Study on the Effect of a
Spacer Grid in Two-Phase Flow Through a 1x3 Rod
Bundle.” Master’s thesis, The Pennsylvania State
University, 2012.
Hochreiter, L.E et al., “Rod Bundle Heat Transfer Test
Facility Test Plan and Design.” NUREG CR-6975.
U.S.Nuclear Regulatory Commission, 2010.
Holloway, Mary V., Donald E. Beasley, and Michael E.
Conner. “Single-Phase Convective Heat Transfer in Rod
Bundles.” Nucl. Eng. and Design 238 (2008): 848-858.
Kim, S., X.Y. Fu, X. Wang, and M. Ishii. “Development of the
Miniaturized Four-Sensor Conductivity Probe and the
Signal Processing Scheme.” International Journal of Heat
and Mass Transfer 43 (2000): 4101-4118.
Nedwidek, Frank. “Experimental Studies for the Effects of
the Spacer Grid on Two-Phase Flow Regime Transition.”
Master’s thesis, The Pennsylvania State University, 2011.
Neti, S., R. Eichhorn, and O.J. Hahn. ”Laser Doppler
Measurements of flow in a Rod Bundle.” Nucl. Eng. and
Design 74 (1983): 105-116.
Paranjape, Sidharth S. “Two-Phase Flow Interfacial
Structures in a Rod Bundle Geometry.” Ph.D. Thesis,
Purdue University, 2009.
Rehme, K. and G. Trippe. “Pressure Drop and Velocity
Distribution in Rod Bundles with Spacer Grids.” Nucl.
Eng. and Design 62 (1980): 349-359.
Wheeler, J., T. Worosz, and S. Kim. “Experiments on the
International Journal of Nuclear Energy Science and Engineering Volume 4 Issue 2, June 2014 www.ijnese.org
63
Effects of a Spacer Grid in Air-Water Two-phase Flow.”
To be presented at Proceeding of 2014 ANS Annual
Meeting, Embedded Topical Meeting on Advances in
Thermal Hydraulics (ATH 14), Reno, NV, USA, June 15-
19, 2014.
Wu, Q. and M. Ishii. “Sensitivity Study on Double-Sensor
Conductivity Probe for the Measurement of Interfacial
Area Concentration in Bubbly Flow.” International
Journal of Multiphase Flow 25 (1999): 155-173.
Yang, Sun Kyu and Moon Ki Chung. “Spacer Grid Effects on
Turbulent Flow in Rod Bundles.” Journal of Korean
Nucl. Society 28 (1998): 56-71.
Yun, Byong-Jo, Goon-Cherl Park, J. Enrique Julia, and
Takashi Hibiki. “Flow Structure of Subcooled Boiling
Water Flow in a Subchannel of 3x3 Rod Bundles.”
Journal of Nucl. Science and Technology, 45, (2008): 402-
422.
Zuber, N. and J. A. Findlay. “Average Volumetric
Concentration in Two-Phase Flow Systems.” Journal of
Heat Transfer 87 (1965): 453-468.)