Upload
dinhtuong
View
224
Download
0
Embed Size (px)
Citation preview
Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik [email protected]
2 © 2007 Electric Power Research Institute, Inc. All rights reserved.
BACKGROUND
• APS and SCE have had slow voltage recovery events • This was attributed to a/c motor stalling • EPRI Performed work for both utilities to model the
phenomenon • The objectives were to:
– Test actual air-conditioning (a/c) units – Identify the physical behavior of these units – Use this information to develop a model – Test/Validate the approach against measured system
events (simulate in GE PSLFTM)
3 © 2007 Electric Power Research Institute, Inc. All rights reserved.
TESTING A/C UNITS IN THE LAB
• A survey was conducted of the typical types and sizes of a/c units in the South West
• 12 units were purchased from manufacturers • A test plan was developed in collaboration with SCE • SCE and BPA separately performed similar tests on
multiple other units – the results from test by all three entities were quite similar
4 © 2007 Electric Power Research Institute, Inc. All rights reserved.
KEY FINDINGS OF LAB TESTS
• Main load (> 80%) is the a/c compressor motor • Motor has a very light inertia (~0.03 kWs/kVA) • Unit stalls in 3 cycles or less • Stall voltage = 55 to 66%, depends on unit and outdoor
temperature • Motor contactor opens at = 40 to 55% voltage –
independent of temperature, dependent on unit • Single-Phase Motors • Once voltage recovers, the contactor closes back in and
the unit may then stall
5 © 2007 Electric Power Research Institute, Inc. All rights reserved.
KEY FINDINGS OF LAB TESTS
• All units have Thermal Overload (TOL) protection • TOL operated between 2 to 20 seconds, depending on
system voltage • This is an I2t phenomenon so the higher the voltage, the
higher the current draw and the quicker the TOL operates • When the unit stalls it draws as much as five times its
steady-state current (real and reactive) • Reciprocating compressors, once stalled they trip on TOL • Scroll compressors can recover from stalling, without
tripping on TOL, if the voltage recovers fast enough
6 © 2007 Electric Power Research Institute, Inc. All rights reserved.
Current Characteristics of a Typical A/C Unit
Unit #4 Current Characteristics
0
10
20
30
40
50
60
70
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Voltage (%)
Cur
rent
(A)
Stall
Normal100F
115F
80F
100F 115F80FConstant Impedance
7 © 2007 Electric Power Research Institute, Inc. All rights reserved.
Behavior of a Reciprocating Compressor Unit
• Example response of a reciprocating unit to delayed voltage recovery – stalled; TOL protection operated and tripped the unit
0 5 10 15 20 250
10
20
30
40
50
60
70
80
90
time(sec)
I1(A
)TOL operated and tripped the unit
Constant Impedance
8 © 2007 Electric Power Research Institute, Inc. All rights reserved.
Behavior of a Scroll Compressor Unit
• Example response of a scroll unit to delayed voltage recovery – stalled but recovered once voltage recovered.
0 5 10 15 20 25 30 35 40 45 500
10
20
30
40
50
60
time(sec)
I1(A
)
Constant Impedance
9 © 2007 Electric Power Research Institute, Inc. All rights reserved.
MODELING THE A/C UNIT (NORMAL CONDITION)
• Under normal (not stalled) operation a/c compressor may be reasonably represented as a standard 3-phase positive sequence induction motor model
• Graph shows the fit for various mechanical torque models for a normal circuit breaker clearing transient (measured is black curve – real power is shown)
Variations in Overall Response due to Different Motor Mechanical Torque ModelSCE Unit #7(CB Transient Data: Voltage Sag 60% 9cycles 100F) - Scroll Unit
0.2
0.4
0.6
0.8
1
1.2
1.4
0 0.1 0.2 0.3 0.4 0.5 0.6
Time
Pmea
sure
d vs
Pev
alua
ted
(pu)
Pm Pc (Tm-TYPE1)
Pc (Tm-TYPE2) Pc (Tm-TYPE3)
Pc (Tm-TYPE4)
10 © 2007 Electric Power Research Institute, Inc. All rights reserved.
MODELING THE A/C UNIT (NORMAL CONDITION) – REACTIVE POWER
Variations in Overall Response due to Different Motor Mechanical Torque ModelSCE Unit #7 (CB Transient Data: Voltage Sag 60% 9cycles 100F) - Scroll Unit
-0.4
-0.2
0
0.2
0.4
0.6
0.8
1
1.2
0 0.1 0.2 0.3 0.4 0.5 0.6
Time
Qm
easu
red
vs
Qev
alu
ated
(pu
)
Qm Qc(Tm-TYPE1)
Qc(Tm-TYPE2) Qc(Tm-TYPE3)
Qc(Tm-TYPE4)
11 © 2007 Electric Power Research Institute, Inc. All rights reserved.
MODELING THE A/C UNIT - INERTIA
Full-Load Running Speed (RPM)
Motor Rotor
Mass (kg) WattsWidth
(inches)Weight
(lb)Height
(inches)
Rotor Radius
(cm) H (Ws/VA)3500 3.67 1780 9.567 66 15.6 3.20 0.083500 3.67 2230 9.567 67 15.6 3.20 0.063500 3.67 2520 9.567 48.6 15.6 3.20 0.053500 3.80 3620 9.567 69 16.14 3.20 0.043500 4.30 5050 9.71 90 17.75 3.25 0.033500 8.66 9750 11.69 200 24.65 3.91 0.053500 8.97 8300 11.69 200 24.65 3.91 0.063500 3.67 1130 9.567 66 15.6 3.20 0.123500 3.67 1410 9.567 67 15.6 3.20 0.093500 3.67 1670 9.567 48.6 15.6 3.20 0.083500 3.80 2410 9.567 69 16.14 3.20 0.063500 4.30 3520 9.71 90 17.75 3.25 0.053500 8.66 6800 11.69 200 24.65 3.91 0.073500 8.66 5850 11.69 200 24.65 3.91 0.083500 3.59 1100 9.565 66 15.275 3.20 0.123500 3.59 1660 9.565 66 15.275 3.20 0.083500 3.98 2250 9.565 66 16.93 3.20 0.063500 3.29 800 9.3 43.6 14.82 3.11 0.14
Rough estimates:
Manufacturers
Could Really
Help Us to Better
Understand Inertia
12 © 2007 Electric Power Research Institute, Inc. All rights reserved.
HYBRID MODEL FOR POWER SYSTEM SIMULATIONS
• The modeling approach is based on a hybrid approach (similar to [1] but fully automated) – Assume that the positive sequence 3-phase IM model
is adequate for capturing the single-phase compressor IM for normal operation (i.e. not stalled)
– Use a constant impedance model to represent the stall condition
[1] G. L. Chinn, “Modeling Stalled Induction Motors”, IEEE T&D Conference,
May 2006.
13 © 2007 Electric Power Research Institute, Inc. All rights reserved.
HYBRID-MODEL
SmallMotor
all other model (large motor etc. also connected to this bus)
Stallm.p
Bus
vol
tage
Sta
ll cu
rren
t
14 © 2007 Electric Power Research Institute, Inc. All rights reserved.
COMPOSITE MODEL STRUCTURE
• Convert all loads through an automated user-written EPCL
DistributionCaps.
OLTC
Transmission Bus
End of Feeder (Load Bus)
LargeMotor
SmallMotor
Discharge Lighting
Electronics (constant
P, Q)
Constant Impedance
Load
feeder
Distribution BusBus 2
Bus 1
Bus 3
Transmission Bus
Lumped LoadModel in Powerflow
ConstantP,Q Load
Bus 1
Hybrid a/c motor model
15 © 2007 Electric Power Research Institute, Inc. All rights reserved.
STATE TRANSITION DIAGRAM FOR HYBRID MODEL
- Motor
- Stalling
- Contactor
- TOL (I-squared t)
State 1Motor running
(motor model status =1stall shunt status = 0)
State 4TOL Operates
(motor model status = 0stall shunt status = 0)
State 3Motor Stalled
(motor model status =0stall shunt status = 1)
State 2Contactor Open(motor model status = 0Stall shunt status = 0)
V < Vcontactor (for 10 ms)
V < Vcontactor
V > Vcontactor (for 10 ms/V2)
V < V
stall (for 50 ms)
and V > V
contactor
V > V
re-start and TOL does not
operate within Trs = 10
seconds (for scroll units)
I2t < TOL time
I2t > TOL time
16 © 2007 Electric Power Research Institute, Inc. All rights reserved.
APS EVENT – Hassayampa, 28th July, 2003
17 © 2007 Electric Power Research Institute, Inc. All rights reserved.
APS EVENT – Feeder Voltages
0 0.5 1 1.5 20
0.5
1
V (p
u)Baseline 12.5 kV
0 0.5 1 1.5 20
0.5
1
Gila 12.5 kV
0 0.5 1 1.5 20
0.5
1
V (p
u)
Cashion 12.5 kV
0 0.5 1 1.5 20
0.5
1
Griswald 12.5 kV
0 0.5 1 1.5 20
0.5
1
V (p
u)
Time (seconds)
Valencia 12.5 kV
0 0.5 1 1.5 20
0.5
1
Time (seconds)
Pima 12.5 kV
MeasuredSimulated
18 © 2007 Electric Power Research Institute, Inc. All rights reserved.
APS EVENT – System Response
• Over a 20 second period roughly 400 to 600 MW of air-conditioning loads tripped.
• The I2t TOL results in this behavior • They started tripping at around 2.6 seconds and stopped
tripping at around 29 seconds. • This is quite indicative of actual system behavior. • The trace of recorded APS load shows a dip of roughly
500 MW in the first minute following the disturbance.
19 © 2007 Electric Power Research Institute, Inc. All rights reserved.
APS EVENT – Sensitivity Analysis
• A large number of sensitivity runs were performed • The intent was to show the relative sensitivity of results to
load model parameters • In order of most sensitive to least sensitive:
– Load composition (% motor, % of static loads) – V-stall of stalling motor – H of stalling motor – Load torque of motors – All others (feeder impedance, machine electrical
parameters etc.) – much less sensitive • Most of the stalling happened after the fault cleared
20 © 2007 Electric Power Research Institute, Inc. All rights reserved.
SCE EVENT – Valley, July 2006
0 5 10 15 20 25 300
0.2
0.4
0.6
0.8
1
Time (seconds)
Vol
tage
(pu)
MeasuredPresent WECC Model
21 © 2007 Electric Power Research Institute, Inc. All rights reserved.
SCE EVENT – The Challenge With Modeling
• Large, radial fed, load with no source near the load
22 © 2007 Electric Power Research Institute, Inc. All rights reserved.
SCE EVENT – Modeling
• In original model – single lumped load • Split it into tens of smaller portions • Vary feeder impedance between maximum to minimum
value • Details of distribution network not readily available – to
emulate variations in TOL pickup and voltage recovery, set TOL time based on normal random distribution with 4 second standard deviation
23 © 2007 Electric Power Research Institute, Inc. All rights reserved.
SCE EVENT – Valley, July 2006
0 5 10 15 20 25 300
0.2
0.4
0.6
0.8
1
Time (seconds)
Vol
tage
(pu)
MeasuredNew Load Model - With Motor Stalling
24 © 2007 Electric Power Research Institute, Inc. All rights reserved.
SCE EVENT - Sensitivity
• Load composition - % motor load • Variations in inertia of the a/c load not as important
– Units light enough that they stall quickly • Because the load is served radially and there are no short
circuit sources (generation) below the 115 kV level, thus when we have a fault, if the voltage falls low enough, all a/c units stall.
• The response is really governed by: – the nature of the remaining connected load, – the effective impedance from the source to the load, – the thermal overload tripping time, and – the effective stall impedance (motor current draw).
• MOTORS STALL DURING THE FAULT - The stall voltage is a key factor
25 © 2007 Electric Power Research Institute, Inc. All rights reserved.
CURSORY LOOK AT TRANSMISSION SOLUTIONS
0 5 10 15 20 25 300
0.2
0.4
0.6
0.8
1
Time (seconds)
Vol
tage
(pu)
Simulated EventWith +300/-150 MVAr SVC at Valley 115 kVWith 300 MVA Synchronous Condensor at Valley 115 kV
26 © 2007 Electric Power Research Institute, Inc. All rights reserved.
THE ISSUES
• What can you do about it now? • What should we be doing?
– Minimize risk of cascading – This requires boosting voltage on transmission as quickly
and as much as possible • Cannot stop all the stalling – it happens too fast • Can reduce stalling:
– Faster clearing of faults (where practical) – Increasing system short circuit (where practical)
• Fixes at the a/c units themselves may take years to impact a critical mass → Transmission solutions are needed
27 © 2007 Electric Power Research Institute, Inc. All rights reserved.
SOLUTIONS MOVING FORWARD
• Put sources closer to the load • Put protection on the a/c units – might lead to overvoltage due to
large blocks tripping • Internationals (e.g. Japan) have full-converter drives on a/c units →
shutdown at low voltage and smooth start; much more expensive. • Put smoothly controlled reactive compensation at the transmission
bus: – Reduces risk of cascading – Controls under- and over-voltage
• Reduce impedance between source and load (build more lines or series compensation)
• Really need combination transmission and load side solutions
28 © 2007 Electric Power Research Institute, Inc. All rights reserved.
CONCLUSIONS
• We can reasonably replicate the system behavior with new models • The results are highly sensitive to:
– The amount of motor load and other static load components – The stall voltage of motors (voltage below which air-conditioner
motors stall) – The effective inertia of motors – The characteristics of the mechanical load on the motors – The stall impedance
• One focus from this point on should be on Sensitivity Analysis with credible bounds
• Solutions likely need to be pursued both at the system and component level