28
Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik [email protected]

Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

Embed Size (px)

Citation preview

Page 1: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik [email protected]

Page 2: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

2 © 2007 Electric Power Research Institute, Inc. All rights reserved.

BACKGROUND

• APS and SCE have had slow voltage recovery events • This was attributed to a/c motor stalling • EPRI Performed work for both utilities to model the

phenomenon • The objectives were to:

– Test actual air-conditioning (a/c) units – Identify the physical behavior of these units – Use this information to develop a model – Test/Validate the approach against measured system

events (simulate in GE PSLFTM)

Page 3: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

3 © 2007 Electric Power Research Institute, Inc. All rights reserved.

TESTING A/C UNITS IN THE LAB

• A survey was conducted of the typical types and sizes of a/c units in the South West

• 12 units were purchased from manufacturers • A test plan was developed in collaboration with SCE • SCE and BPA separately performed similar tests on

multiple other units – the results from test by all three entities were quite similar

Page 4: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

4 © 2007 Electric Power Research Institute, Inc. All rights reserved.

KEY FINDINGS OF LAB TESTS

• Main load (> 80%) is the a/c compressor motor • Motor has a very light inertia (~0.03 kWs/kVA) • Unit stalls in 3 cycles or less • Stall voltage = 55 to 66%, depends on unit and outdoor

temperature • Motor contactor opens at = 40 to 55% voltage –

independent of temperature, dependent on unit • Single-Phase Motors • Once voltage recovers, the contactor closes back in and

the unit may then stall

Page 5: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

5 © 2007 Electric Power Research Institute, Inc. All rights reserved.

KEY FINDINGS OF LAB TESTS

• All units have Thermal Overload (TOL) protection • TOL operated between 2 to 20 seconds, depending on

system voltage • This is an I2t phenomenon so the higher the voltage, the

higher the current draw and the quicker the TOL operates • When the unit stalls it draws as much as five times its

steady-state current (real and reactive) • Reciprocating compressors, once stalled they trip on TOL • Scroll compressors can recover from stalling, without

tripping on TOL, if the voltage recovers fast enough

Page 6: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

6 © 2007 Electric Power Research Institute, Inc. All rights reserved.

Current Characteristics of a Typical A/C Unit

Unit #4 Current Characteristics

0

10

20

30

40

50

60

70

0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Voltage (%)

Cur

rent

(A)

Stall

Normal100F

115F

80F

100F 115F80FConstant Impedance

Page 7: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

7 © 2007 Electric Power Research Institute, Inc. All rights reserved.

Behavior of a Reciprocating Compressor Unit

• Example response of a reciprocating unit to delayed voltage recovery – stalled; TOL protection operated and tripped the unit

0 5 10 15 20 250

10

20

30

40

50

60

70

80

90

time(sec)

I1(A

)TOL operated and tripped the unit

Constant Impedance

Page 8: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

8 © 2007 Electric Power Research Institute, Inc. All rights reserved.

Behavior of a Scroll Compressor Unit

• Example response of a scroll unit to delayed voltage recovery – stalled but recovered once voltage recovered.

0 5 10 15 20 25 30 35 40 45 500

10

20

30

40

50

60

time(sec)

I1(A

)

Constant Impedance

Page 9: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

9 © 2007 Electric Power Research Institute, Inc. All rights reserved.

MODELING THE A/C UNIT (NORMAL CONDITION)

• Under normal (not stalled) operation a/c compressor may be reasonably represented as a standard 3-phase positive sequence induction motor model

• Graph shows the fit for various mechanical torque models for a normal circuit breaker clearing transient (measured is black curve – real power is shown)

Variations in Overall Response due to Different Motor Mechanical Torque ModelSCE Unit #7(CB Transient Data: Voltage Sag 60% 9cycles 100F) - Scroll Unit

0.2

0.4

0.6

0.8

1

1.2

1.4

0 0.1 0.2 0.3 0.4 0.5 0.6

Time

Pmea

sure

d vs

Pev

alua

ted

(pu)

Pm Pc (Tm-TYPE1)

Pc (Tm-TYPE2) Pc (Tm-TYPE3)

Pc (Tm-TYPE4)

Page 10: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

10 © 2007 Electric Power Research Institute, Inc. All rights reserved.

MODELING THE A/C UNIT (NORMAL CONDITION) – REACTIVE POWER

Variations in Overall Response due to Different Motor Mechanical Torque ModelSCE Unit #7 (CB Transient Data: Voltage Sag 60% 9cycles 100F) - Scroll Unit

-0.4

-0.2

0

0.2

0.4

0.6

0.8

1

1.2

0 0.1 0.2 0.3 0.4 0.5 0.6

Time

Qm

easu

red

vs

Qev

alu

ated

(pu

)

Qm Qc(Tm-TYPE1)

Qc(Tm-TYPE2) Qc(Tm-TYPE3)

Qc(Tm-TYPE4)

Page 11: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

11 © 2007 Electric Power Research Institute, Inc. All rights reserved.

MODELING THE A/C UNIT - INERTIA

Full-Load Running Speed (RPM)

Motor Rotor

Mass (kg) WattsWidth

(inches)Weight

(lb)Height

(inches)

Rotor Radius

(cm) H (Ws/VA)3500 3.67 1780 9.567 66 15.6 3.20 0.083500 3.67 2230 9.567 67 15.6 3.20 0.063500 3.67 2520 9.567 48.6 15.6 3.20 0.053500 3.80 3620 9.567 69 16.14 3.20 0.043500 4.30 5050 9.71 90 17.75 3.25 0.033500 8.66 9750 11.69 200 24.65 3.91 0.053500 8.97 8300 11.69 200 24.65 3.91 0.063500 3.67 1130 9.567 66 15.6 3.20 0.123500 3.67 1410 9.567 67 15.6 3.20 0.093500 3.67 1670 9.567 48.6 15.6 3.20 0.083500 3.80 2410 9.567 69 16.14 3.20 0.063500 4.30 3520 9.71 90 17.75 3.25 0.053500 8.66 6800 11.69 200 24.65 3.91 0.073500 8.66 5850 11.69 200 24.65 3.91 0.083500 3.59 1100 9.565 66 15.275 3.20 0.123500 3.59 1660 9.565 66 15.275 3.20 0.083500 3.98 2250 9.565 66 16.93 3.20 0.063500 3.29 800 9.3 43.6 14.82 3.11 0.14

Rough estimates:

Manufacturers

Could Really

Help Us to Better

Understand Inertia

Page 12: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

12 © 2007 Electric Power Research Institute, Inc. All rights reserved.

HYBRID MODEL FOR POWER SYSTEM SIMULATIONS

• The modeling approach is based on a hybrid approach (similar to [1] but fully automated) – Assume that the positive sequence 3-phase IM model

is adequate for capturing the single-phase compressor IM for normal operation (i.e. not stalled)

– Use a constant impedance model to represent the stall condition

[1] G. L. Chinn, “Modeling Stalled Induction Motors”, IEEE T&D Conference,

May 2006.

Page 13: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

13 © 2007 Electric Power Research Institute, Inc. All rights reserved.

HYBRID-MODEL

SmallMotor

all other model (large motor etc. also connected to this bus)

Stallm.p

Bus

vol

tage

Sta

ll cu

rren

t

Page 14: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

14 © 2007 Electric Power Research Institute, Inc. All rights reserved.

COMPOSITE MODEL STRUCTURE

• Convert all loads through an automated user-written EPCL

DistributionCaps.

OLTC

Transmission Bus

End of Feeder (Load Bus)

LargeMotor

SmallMotor

Discharge Lighting

Electronics (constant

P, Q)

Constant Impedance

Load

feeder

Distribution BusBus 2

Bus 1

Bus 3

Transmission Bus

Lumped LoadModel in Powerflow

ConstantP,Q Load

Bus 1

Hybrid a/c motor model

Page 15: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

15 © 2007 Electric Power Research Institute, Inc. All rights reserved.

STATE TRANSITION DIAGRAM FOR HYBRID MODEL

- Motor

- Stalling

- Contactor

- TOL (I-squared t)

State 1Motor running

(motor model status =1stall shunt status = 0)

State 4TOL Operates

(motor model status = 0stall shunt status = 0)

State 3Motor Stalled

(motor model status =0stall shunt status = 1)

State 2Contactor Open(motor model status = 0Stall shunt status = 0)

V < Vcontactor (for 10 ms)

V < Vcontactor

V > Vcontactor (for 10 ms/V2)

V < V

stall (for 50 ms)

and V > V

contactor

V > V

re-start and TOL does not

operate within Trs = 10

seconds (for scroll units)

I2t < TOL time

I2t > TOL time

Page 16: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

16 © 2007 Electric Power Research Institute, Inc. All rights reserved.

APS EVENT – Hassayampa, 28th July, 2003

Page 17: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

17 © 2007 Electric Power Research Institute, Inc. All rights reserved.

APS EVENT – Feeder Voltages

0 0.5 1 1.5 20

0.5

1

V (p

u)Baseline 12.5 kV

0 0.5 1 1.5 20

0.5

1

Gila 12.5 kV

0 0.5 1 1.5 20

0.5

1

V (p

u)

Cashion 12.5 kV

0 0.5 1 1.5 20

0.5

1

Griswald 12.5 kV

0 0.5 1 1.5 20

0.5

1

V (p

u)

Time (seconds)

Valencia 12.5 kV

0 0.5 1 1.5 20

0.5

1

Time (seconds)

Pima 12.5 kV

MeasuredSimulated

Page 18: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

18 © 2007 Electric Power Research Institute, Inc. All rights reserved.

APS EVENT – System Response

• Over a 20 second period roughly 400 to 600 MW of air-conditioning loads tripped.

• The I2t TOL results in this behavior • They started tripping at around 2.6 seconds and stopped

tripping at around 29 seconds. • This is quite indicative of actual system behavior. • The trace of recorded APS load shows a dip of roughly

500 MW in the first minute following the disturbance.

Page 19: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

19 © 2007 Electric Power Research Institute, Inc. All rights reserved.

APS EVENT – Sensitivity Analysis

• A large number of sensitivity runs were performed • The intent was to show the relative sensitivity of results to

load model parameters • In order of most sensitive to least sensitive:

– Load composition (% motor, % of static loads) – V-stall of stalling motor – H of stalling motor – Load torque of motors – All others (feeder impedance, machine electrical

parameters etc.) – much less sensitive • Most of the stalling happened after the fault cleared

Page 20: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

20 © 2007 Electric Power Research Institute, Inc. All rights reserved.

SCE EVENT – Valley, July 2006

0 5 10 15 20 25 300

0.2

0.4

0.6

0.8

1

Time (seconds)

Vol

tage

(pu)

MeasuredPresent WECC Model

Page 21: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

21 © 2007 Electric Power Research Institute, Inc. All rights reserved.

SCE EVENT – The Challenge With Modeling

• Large, radial fed, load with no source near the load

Page 22: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

22 © 2007 Electric Power Research Institute, Inc. All rights reserved.

SCE EVENT – Modeling

• In original model – single lumped load • Split it into tens of smaller portions • Vary feeder impedance between maximum to minimum

value • Details of distribution network not readily available – to

emulate variations in TOL pickup and voltage recovery, set TOL time based on normal random distribution with 4 second standard deviation

Page 23: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

23 © 2007 Electric Power Research Institute, Inc. All rights reserved.

SCE EVENT – Valley, July 2006

0 5 10 15 20 25 300

0.2

0.4

0.6

0.8

1

Time (seconds)

Vol

tage

(pu)

MeasuredNew Load Model - With Motor Stalling

Page 24: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

24 © 2007 Electric Power Research Institute, Inc. All rights reserved.

SCE EVENT - Sensitivity

• Load composition - % motor load • Variations in inertia of the a/c load not as important

– Units light enough that they stall quickly • Because the load is served radially and there are no short

circuit sources (generation) below the 115 kV level, thus when we have a fault, if the voltage falls low enough, all a/c units stall.

• The response is really governed by: – the nature of the remaining connected load, – the effective impedance from the source to the load, – the thermal overload tripping time, and – the effective stall impedance (motor current draw).

• MOTORS STALL DURING THE FAULT - The stall voltage is a key factor

Page 25: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

25 © 2007 Electric Power Research Institute, Inc. All rights reserved.

CURSORY LOOK AT TRANSMISSION SOLUTIONS

0 5 10 15 20 25 300

0.2

0.4

0.6

0.8

1

Time (seconds)

Vol

tage

(pu)

Simulated EventWith +300/-150 MVAr SVC at Valley 115 kVWith 300 MVA Synchronous Condensor at Valley 115 kV

Page 26: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

26 © 2007 Electric Power Research Institute, Inc. All rights reserved.

THE ISSUES

• What can you do about it now? • What should we be doing?

– Minimize risk of cascading – This requires boosting voltage on transmission as quickly

and as much as possible • Cannot stop all the stalling – it happens too fast • Can reduce stalling:

– Faster clearing of faults (where practical) – Increasing system short circuit (where practical)

• Fixes at the a/c units themselves may take years to impact a critical mass → Transmission solutions are needed

Page 27: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

27 © 2007 Electric Power Research Institute, Inc. All rights reserved.

SOLUTIONS MOVING FORWARD

• Put sources closer to the load • Put protection on the a/c units – might lead to overvoltage due to

large blocks tripping • Internationals (e.g. Japan) have full-converter drives on a/c units →

shutdown at low voltage and smooth start; much more expensive. • Put smoothly controlled reactive compensation at the transmission

bus: – Reduces risk of cascading – Controls under- and over-voltage

• Reduce impedance between source and load (build more lines or series compensation)

• Really need combination transmission and load side solutions

Page 28: Experience With A/C Stalling Behavior and Modeling it for Power System … · Experience With A/C Stalling Behavior and Modeling it for Power System Studies 4/22/08 P. Pourbeik

28 © 2007 Electric Power Research Institute, Inc. All rights reserved.

CONCLUSIONS

• We can reasonably replicate the system behavior with new models • The results are highly sensitive to:

– The amount of motor load and other static load components – The stall voltage of motors (voltage below which air-conditioner

motors stall) – The effective inertia of motors – The characteristics of the mechanical load on the motors – The stall impedance

• One focus from this point on should be on Sensitivity Analysis with credible bounds

• Solutions likely need to be pursued both at the system and component level