Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
EXAMPLE 1: Balanced Y-Y Connection
Calculate the line currents in the three-wire Y-Y system as
shown below
0
pca
0
pbc
0
pab
210V3V
90V3V
30V3V
Line to line voltages or line voltages:
Magnitude of line voltages:
pL V3V
cabcabL VVVV cnbnanp VVVV
SOLUTION
• Due to the three-phase circuit is balanced; we may replace it
with its single-phase equivalent circuit
• Phase “a” equivalent circuit:
21.86.8121.816.155
0110I
8.21155.16)810()25(Z
;Z
VI
Aa
T
T
ANAa
jj
• Since the source voltage are in positive (ABC) phase
sequence, the line currents are also in positive sequence:
A2.986.811.8266.81
024II
A141.86.81
120II
AaCc
AaBb
EXAMPLE 2: Balanced Y-Delta Connection
A balanced Y-connected source with
is connected to a Δ-connected balanced load (8+j4)Ω per phase. Calculate the phase and line currents.
V10100V 0
an
CA
0
pca
BC
0
pbc
AB
0
pab
V210V3V
V90V3V
V30V3V
Line voltages:
903
1503
303
ABBCCAc
ABABBCb
ABCAABa
IIII
IIII
IIII
Line currents:
Z
VI
Z
VI
Z
VI
CACA
BC
BC
ABAB
Phase currents:
**NOTES:
SOLUTION
• Line Voltage:
• Phase Current
• Line Current
EXAMPLE 3: Balanced Delta-Delta
Connection
A balanced Δ connected load having an impedance
20-j15 Ω is connected to a Δ connected, positive sequence
generator having
Calculate the phase currents of the load and the line
currents.
V0330V 0
ab
Z
VI
Z
VI
Z
VI
CACA
BC
BC
ABAB
CAca
BCbc
ABab
VV
VV
VV
Line voltages: Line currents:
3II pL
Magnitude line currents:
3
ZZY
Total impedance:
Phase currents:
903
1503
303
ABBCCAc
ABABBCb
ABCAABa
IIII
IIII
IIII
SOLUTION
• Line Voltage= phase voltage
• Phase current
• Line Current
EXAMPLE 4: Balanced Delta-Y Connection
A balanced Y connected load with a phase resistance
of 40 Ω and a reactance of 25 Ω is supplies by a
balanced, positive sequence Δ connected source with
a line voltage of 210 V. Calculate the phase currents.
Use Vab as reference.
A single phase equivalent circuit
Y
p
Y
an
aZ
V
Z
VI
0303
SOLUTION
• Phase voltage = Line voltage (generator side)
• Phase Voltage (load side)
• Phase Current
EXERCISE 1
A Y-connected balanced three-phase generator with an impedance
of 0.4+j0.3 Ω per phase is connected to a Y-connected balanced load
with an impedance of 24 + j19 Ω per phase. The line joining the
generator and the load has an impedance of 0.6 + j0.7 Ω per phase.
Assuming a positive sequence for the source voltages and that
Find: (a) the line voltages
(b) the line currents
VVan
030120
EXERCISE 2
One line voltage of a balanced Y-connected
source is If the source is connected
to a Δ -connected load of
Find: (a) the phase currents
(b) the line currents
EXERCISE 3
A positive-sequence, balanced -connected source
supplies a balanced Δ-connected load. If the
impedance per phase of the load is 18+j12 Ω
and , find IAB and VAB
In a balanced -Y circuit,
and ZY = (12 + j15) Ω.
Calculate the line currents.
EXERCISE 4
VVab
015240
EXAMPLE 5: Unbalanced Y Connected
load
The unbalanced Y-load has balanced voltages of 100 V.
Calculate the line currents. Take
SOLUTION:
EXAMPLE 6: Unbalanced delta
Connected load
The unbalanced -load is supplied by balanced line-to-line voltages
of 240 V in the positive sequence. Find the line currents. Take VAB as
reference.
Active Power in Single Phase
• Active Power (P) delivered to or absorb by
resistive component to each phase, Pᶲ:
where
is the phase angle between and
or
(W)IVPV
I cos
(W)RIP 2
(W)R
VP R
2
V
I V I
Reactive Power in Single Phase
• Reactive Power (Q) delivered to or absorb by
reactive component to each phase, Qᶲ:
where
is the phase angle between and
or
(VAR)IVQV
I sin
(VAR)XIQ 2
(VAR)X
XQ
x
2
V
I V I
• Apparent Power (S) - is the product of voltage and current that deliver to each phase.
or
Apparent Power in Single Phase
(VA)IVS
(VA)ZIS 2
Power in Y-Connection
3
sin 3
co 3
cos3
3
cos3
cos
3
LLT
LLT
LL
LLT
T
VIS
VIQ
sVI
VIP
VIPP
VIP
The angle θ is angle between the voltage and current in any phase of
the load ( it is the same in all phases), and the power factor of the load is the cosine of the impedance
angle θ
Power in Δ-Connection
3
sin 3
co 3
cos3
3
cos3
cos
3
LLT
LLT
LL
LL
T
T
VIS
VIQ
sVI
VI
P
VIPP
VIP
The angle θ is angle between the voltage and current in any phase of
the load ( it is the same in all phases), and the power factor of the load is the cosine of the impedance
angle θ
V
I
T
T
S
Pcospf,FactorPower
Displacement angle between V and I
Power Factor, pf
Defined as the ratio of the real power flowing to
the load over the apparent power in the circuit.
Active Power, P (kW) Rea
ctiv
e Po
wer
, Q
(kV
AR
)
• Defined as 'the cosine of the angle between the voltage and
current'.
• In AC circuit, the voltage and current are ideally in phase.
• But practically, there exists a phase difference between them.
• The cosine of this phase difference is termed as power factor.
• It can be defined and mathematically represented as follows:
• Power factors are usually stated as "leading" or "lagging" to show the sign of the phase angle. Capacitive loads are leading (current leads voltage), and inductive loads are lagging (current lags voltage).
Phase Voltage Phase Current
Phase Current Phase Voltage
•Lagging power factor ( inductive loads)
•leading power factor • (capacitive loads)
EXAMPLE 7
A 208-V three-phase power system is shown in above figure. It consists of an
ideal 208-V Y-connected three-phase generator connected through a three-
phase transmission line to a Y-connected load. The transmission line has an impedance of 0.06+ j 0.12Ω per phase, and the load has an impedance of 12 + j9Ω per phase. Find
(a) the active, reactive and apparent powers consumed by the load
(b) the power factor of the load
SOLUTION
(a) The active power consumed by the load is
The reactive power consumed by the load is
The apparent power consumed by the load is
(b) The load power factor is
3 cos
3(120 )(7.94 )cos37.1
2280
load L LP V I
V A
W
3 sin
3(120 )(7.94 )sin 37.1
1724 var
load L LQ V I
V A
3
3(120 )(7.94 )
2858
load L LS V I
V A
VA
cos
cos37.1
0.8
loadPF
lagging
TWO-WATTMETER METHOD
To measure the power delivered by a three-phase, 4-wire system,
three single-phase wattmeter could be connected to measure
power in each of the phases and the readings added to obtain the total power.
However is not necessary because two single-phase wattmeter
connected as shown in Figure 1 will gave the same result.
The total power is the algebraic sum of the two wattmeter readings
and this method of power measurement is known as the two-
wattmeter method.
Figure 1: The Two-Wattmeter Method of Measuring Three-Phase Power
Figure 2 shows a wattmeter connected to measure the power delivered to a load and the equivalent circuit connections of the DAI
to obtain the same result with the Metering system.
Figure 2: Measuring Power with a Wattmeter
Two Wattmeter Method Alternative hookup for the Two
Wattmeter Method
EXAMPLE 8
An unbalanced Δ load is connected to a three-phase, Y-connected generator having a line voltage of EAB, EBC and ECA. Calculate the readings of the wattmeters W1 and W2. Find PTotal
SOLUTION