Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ESEA committee

Page 2: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Electricity is an essential part of

our development

No nation can survive the

present developmental challenges

without POWER

Backgrounder

Page 3: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Electric power should not only

be available, realiable and

affordable, but above all SAFE.

One of the primary advocacies of

IIEE is ELECTRICAL SAFETY!

Backgrounder

Page 4: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Engineering is all about safety. One of

IIEE Safety Program is the signing of a

MOA with our industry partners. e.g.

The International Copper Industry

Association of Southeast Asia (ICIASEA)

Backgrounder

Page 5: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

This brought about the creation of

ESEA (Electrical Safety Enforcement and

Awareness)

Presidential Executive Order # 193

declares that every month of every year

is ELECTRICAL SAFETY MONTH.

Backgrounder

Page 6: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

On May 28, 2015, a joint project of IIEE and

MERALCO will conduct the 2nd Electrical Safety

Summit

The event will highlight the concerted effort

of IIEE and MERALCO of the importance of

electrical safety to our citizen.

2nd Electrical Safety Summit

Page 7: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Statistic from the Bureau of

Fire of the Philippines (BFP)

shows that 35% of the cause

of fire is electrical related.

FIRE CAUSES

Page 8: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Though their reason is “FAULTY

ELECTRICAL WIRING”

Need regular electrical

inspection of work places and

residences.

FIRE CAUSES

Page 9: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Electrical safety should a

primary concern of all electrical

engineers and practitioners and

manufacturers.

ELECTRICAL SAFETY

Page 10: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Philippine Electrical Code (PEC)

should at all time be followed

and impose!

PEC

Page 11: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

“ELECTRICAL SAFETY

STARTS WITH ME”

Page 12: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

ELECTRICAL INSPECTION STRATEGY AND GUIDE

• Republic Act 7920

An act providing for a more responsive and comprehensive regulation for the practice, licensing, and regulation of electrical engineers and electricians

Page 13: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

STRATEGIC SOLUTIONS The Philippine Electrical code

is used nationally as the

basis for safeguarding

persons, buildings and its

contents from hazards that

may arise from the use of

electricity.

This code contains provisions

which is considered

necessary for safety and thus

is used as basis for the legal

enforcement agency in the

government regarding

electrical installation

Page 14: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Electrical

Safety

Enforcement and

Awareness

Page 15: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

ESEA Profile June 27, 2011 – President Aquino signed

Proclamation No. 193 declaring the Month of

May of every year thereof as the Electrical

Safety Month.

Page 16: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

• DECLARING THE MONTH OF MAY

OF EVERY YEAR AS THE

ELECTRICAL SAFETY MONTH

WHEREAS, many lives and

properties are lost due to fires

and electrocution

PRESIDENTIAL PROCLAMATION NO. 193

Page 17: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

• WHEREAS, most of these fires and incidents of electrocution are attributed to “faulty electrical wiring”

PRESIDENTIAL PROCLAMATION NO. 193

Page 18: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

• WHEREAS, economic

losses brought about by

fires contribute to

reduced productivity and

therefore affect the

economy of the country

PRESIDENTIAL PROCLAMATION NO. 193

Page 19: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

PRESIDENTIAL PROCLAMATION NO. 193

• WHEREAS, there is a real need

to increase public awareness on

electrical safety and educate our

people in the safe use of

electricity.

Page 20: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

MISSION - To ensure ESEA is

properly enforced through improving

local inspectors’ capacity and to

increase the public’s awareness on

electrical safety.

ESEA Profile

Page 21: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

• VISION - To be a major campaign that leads the public towards an electrically safe environment.

ESEA Profile

Page 22: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Objectives

•designed to enhance the enforcement

of the Philippine Electrical Code

(PEC);

•provide capacity building to improve

the skills of local inspectors

• increase the awareness of and

educate the public on the importance

of electrical safety

ESEA Profile

Page 23: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

•and strengthen the institutional cooperation between government and industry such as the local government units, developers, and contractors association, among others.

“Electrical Safety Starts With Me!” – ESEA Slogan

ESEA Profile

Page 24: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Electrical Safety Flyer

Page 25: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

ELECTRICAL SAFETY ENFORCEMENT AND AWARENESS

This manual is intended to inform the general public about the importance of Electrical Safety in our daily lives.

Page 26: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Electrical Safety

Key Result Areas • Compliance with

National/International Standards

– Safety

– Workmanship

• Improve Power Quality

– Voltage Stability

– Arrest Surges

– Harmonics

• Attain Flexibility – Reduce/Add Loads

• Maintain Reliability – Interruption Frequency

– Interruption Duration

• Ensure Cost Effectiveness – Effective Budget Cost

– Efficient Maintenance Program/Enercon/man

– Energy Savings

Page 27: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Electricity- The Dangers • 12,301 Fires recorded nationwide- source BFP as of

2013

Page 28: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

WHAT IS AN ELECTRICAL INSPECTION & AUDIT?

• An electrical audit is a thorough survey/ inspection, review and evaluation of an electrical system which is already in operation for several years.

Page 29: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

WHAT IS THE PURPOSE OF AN ELECTRICAL INSPECTION &

AUDIT? • The purpose of an electrical safety inspection or audit is to identify potentially hazardous electrical situations and provide corrective actions for these situation.

Page 30: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

OBJECTIVES of ELECTRICAL

INSPECTION & AUDIT - 1

• # 1. Determine compliance of the electrical system to electrical safety, viz-a-viz:

- Philippine Electrical Code (Part I & II)

- National Electrical Code - NFPA 70E - NFPA 70B - OSHA 1910.331-335

- Other Electrical Codes (IEC)

Page 31: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

OBJECTIVES OF AN ELECTRICAL

INSPECTION & AUDIT – 2,3,4

• #2. Review and provide corrective actions for

safe electrical work processes.

• # 3. Review and provide corrective measures for electrical maintenance tools.

• # 4. Identify efficient measures and potential cost savings through modifications/ improvements in the electrical system.

Page 32: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

• So what would be the samples of electrical violations or errors that you should be mindful of when you do your electrical audit/ inspections?

Page 33: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

1. THE USE OF HIGHER RATED CIRCUIT PROTECTION . . . THIS IS A RAMPANT VIOLATION!

Page 34: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

1-A. ANOTHER CASE OF USING VERY HIGH RATING OF PROTECTION..

AS INSPECTED IN 2011, THE SIZE OF THIS SERVICE ENTRANCE FEEDER IS 2 – 14 SQUARE MM IN A PVC CONDUIT, SO THAT THE ALLOWABLE AMPACITY IS

70 AMPERES BUT THE PROTECTION IS 200-AMPERE FUSES!

THE IIEE ESC/ESEA VOLUNTEER TEAM IN 2012 REPLACED IT WITH 100-AMPERE FUSES.

Page 35: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

2. INADEQUATE EQUIPMENT GROUNDING . .

WHAT WOULD BE THE MAXIMUM GROUNDING RESISTANCE? IS IT 25 OHMS?5 OHMS?1 OHM? THE LOWER THE VALUE, THE SAFER! WHY? GROUND FAULT CURRENT SEEKS THE PATH OF LOWER RESISTANCE.

Page 36: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

3. NOT USING GROUNDING TYPE CONVENIENCE OUTLETS . . .

Page 37: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

4. NOT USING GFCI DEVICE FOR CIRCUITS IN

DAMP LOCATIONS OR EXTERIOR AREAS . .

Page 38: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

5. NOT CHECKING THE BUS BAR CAPACITY OF THE PANEL BOARDS/ BUS BAR GUTTERS . .

Page 39: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

6. FAILURE TO TEST COMPLETELY BEFORE ENERGIZATION

• AFTER A PROLONGED SHUTDOWN OF A SWITCHGEAR, A DANGEROUS ARC FLASH FAULT BETWEEN PHASES MAY RESULT AFTER ENERGIZATION OF THE BUS BARS!

• THIS MAY HAPPEN WHEN THERE IS A FAILURE TO

DETERMINE THE INSULATION RESISTANCE OF THE ENCLOSED

BUS BARS.

• AFTER A PROLONGED SHUTDOWN ON A HUMID DAY, MOISTURE MAY OCCUR DUE TO CONDENSATION INSIDE THE SWITCHGEAR.

• WARNING: ALWAYS MEGGER TEST CIRCUIT BREAKERS, BUS

BARS, CABLE FEEDERS BEFORE ENERGIZATION!

• THE HIGHER THE MEGGER READING, THE SAFER!

Page 40: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

7. USING IMPROPER SPLICES

Page 41: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

8. NOT USING SEAL FITTINGS IN HAZARDOUS LOCATIONS…

NOTE THAT THERE ARE NO TYPE “EYS” CONDULET SEAL FITTINGS ON THE CONDUITS WITHIN 150MM FROM THE

SWITCH BOXES.

IN CLASSIFIED LOCATIONS, THE CONDUIT SEAL WOULD

PREVENT THE ENTRY OF FLAMABLE GASES OR VAPORS TO THE SWITCHES WHICH ARE

POSSIBLE SOURCES OF A SPARK.

Page 42: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

9. LACK OF SUPERVISION DURING CONSTRUCTION…

THESE INAPPROPRIATELY/POORLY SPLICED WIRES INSIDE A BADLY BURNT FLEXIBLE PVC CONDUIT. THE ELECTRICAL SUPERVISOR/FOREMAN MISSED THIS.

Page 43: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

10. TEMPORARY WIRING ALLOWED TO BECOME TEMPORARY-PERMANENT

THE FLYING WIRES/CABLES WHICH INCLUDE POWER & COMMUNICA-TION LINES ARE INSTALLED TEMPORARILY.. UNTIL AN UNTOWARD INCIDENT HAPPEN AGGRAVATING MATTERS – ACCIDENTS.

Page 44: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

11. NOT USING SEAL FITTINGS IN HAZARDOUS LOCATIONS…

NOTE THAT THERE ARE NO TYPE “EYS” CONDULET SEAL

FITTINGS ON THE CONDUITS WITHIN 150MM FROM THE

SWITCH BOXES.

IN CLASSIFIED LOCATIONS, THE CONDUIT SEAL WOULD

PREVENT THE ENTRY OF FLAMABLE GASES OR VAPORS TO THE SWITCHES WHICH ARE

POSSIBLE SOURCES OF A SPARK.

Page 45: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

12.LACK OF SAFETY SENSE…

NOTICE THE SERVICE ENTRANCE WIRES, NO ENTRANCE CAP OR DRIP LOOP – THIS ALLOWS WATER TO ENTER CONDUIT AND MAY EVEN REACH PANELBOARD INSIDE, CAUSE DAMAGE, OR GROUND FAULT. THERE IS ALSO NO GROUND WIRE.

Page 46: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

13.NOT USING BOLT-ON TYPE MAINS THE 60A PANEL MAIN CBs ARE PLUG-IN TYPE, SHOULD BE BOLT-ON TYPE..

THE PLUG-IN MAINS WILL RESULT TO LOOSE CONNECTION, LOCALIZE HEATING..

Page 47: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

14. LACK OF MAINTENANCE

REGULAR CLEANING

REQUIRED.

CABLE

TERMINATIONS

ARE VIOLATIONS.

COLOR CODING OF

WIRES MUST BE

FOLLOWED.

Page 48: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

15. JUNCTION BOX COVER MISSING ..

THE ABSENCE OF THE COVER FOR THE JUNCTION BOX EXPOSES THE CONDUCTORS NOT ONLY TO WATER BUT ALSO TO THE ULTRA-VIOLET (UV) RAYS OF THE SUN, CAUSING THE DETERIORATION OF THE INSULATION OF

THE CONDUCTORS FASTER.

Page 49: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

16. Panel Cover & Power CBs Not Fitted Properly…

In a big manufacturing plant, during the retrofitting or replacement of the main circuit breaker of the Low Voltage Switchgear, the panel opening is so big where in there is a large clearance between the front face of new power breaker and the panel opening. This may allow foreign bodies such as dust, and even live creatures to possibly enter inside the switchgear and cause a shutdown. A control wire is even left not tied properly.

Page 50: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

17. Old Fused Disconnects Still in Use?

The use of old fused disconnect switches where in the load side feeder wires are

too small in their ampacities as matched to the rating of the fuses. The fuses may protect

the small wires from high magnitude short circuit current but not on an overload current

or during a low magnitude line-to-ground fault. These

installations must be replaced with bus bar type panel board

of power distribution to various load circuits.

Page 51: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

18. Cables Not Provided w/ Raceways..

Would you believe that this kind of cable installation still exists? If you are the electrical practitioner assigned to supervise the electrical works, how would you have provided for a better job?By providing flexible metallic conduits?By a cable duct?Or by extending the cable trench?

Page 52: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

19. POOR VENTILATION FOR HEAT GENERATING EQUIPMENT

THE TRANSFORMER BELOW WHICH WAS INSTALLED INSIDE A CABINET THAT IS NOT ADEQUATELY VENTILATED OR NOT PROVIDED WITH LOUVERS SHOWS SIGNS OF EXCESSIVE HEAT BEING DISSIPATED. IT WAS SOON DAMAGED

Page 53: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

AS-BUILT PLANS • After your thorough electrical inspection & audit,

you will now prepare/ update your electrical drawings:

* Lighting Layouts * Power Layouts * Panel Arrangements * Single Line Diagram/ Riser Diagram * Load Schedules and Computations * Service Entrance

* Substation * Meter Center * Grounding system * Lightning Protection system * Other electrical details of

the electrical system

Note down all observations of non-compliance/ Code violations, unsafe situations, inefficient

system/ equipment, etc…

Page 54: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

When Would We Learn

FIRE TRAGEDIES

Page 55: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Electrical

Unknown/Others

Open Flames/Cooking

Combustion/Bonfire

Cigarette Butts/

Smoking

Origin/Causes 2006 2007 2008 2009 2010 TOTAL

FIRE OCCURRENCE NATIONWIDE (2005-2010)

2249 2087 2300 2532 2333 2616 14,117

2334 1871 2485 3395 1966 2324 14,375

1598 1144 1726 2285 997 1280 9,030

710 538 1094 1592 392 540 4,866

324 257 349 355 132 199 1,616

Electrical 2249 2087 2300 2532 2333 2616 14,117

TOTAL 7215 5897 7954 10159 5820 6959

2005

Page 56: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

2,861; 33%

396; 4%

71; 1%

5,470; 62%

2012 Total Fire Incidents in the Philippines – 8,798

Electrical Connections

Electrical Appliances

Electrical Machiniries

Others

Page 57: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Damage to Properties –

Php 3,373,240,786.16

• 37.8% causes of fire – due to electrical in nature such as:

Defective Electrical Device, Sub-standard electrical appliances and wires, circuit overloading, short circuits, arcing, overheating and malpractice of electricity.

• ‘Working together towards an electrical safety conscious nation’ – 2013 Theme of Electrical Safety Month

Page 58: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

250 Civilians died

645 were injured

2 Firefighters died

and 100 were injured

Total of 252 fatalities

and 745 were injured

Page 59: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

3,532; 28.7%

408; 3.3% 74;

0.6%

8,287; 67.3%

2013 Total Fire Incidents in the Philippines – 12,301

Electrical Connections

Electrical Appliances

Electrical Machineries

Others

Page 60: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Damage to Properties –

Php 5,465,832,497.74

• 32.6% causes of fire – due to electrical in nature such as:

Defective Electrical Device, Sub-standard electrical appliances and wires, circuit overloading, short circuits, arcing, overheating and malpractice of electricity.

• ‘Electrical Safety starts with me ’ – 2014 Theme of Electrical Safety Month

Page 61: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

244 Civilians died

697 were injured

No Firefighters died

but 77 were injured

Total of 244 fatalities

and 774 were injured

Page 62: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Big Fires: Causes?

Manor Hotel Fire

Location : Kamias Road, Quezon City

Date/Time : 18 0412H August 2001

Cause of Fire: Electrical Short Circuit

Casualty : 75 persons

Injured : 73 Persons

Est. Damages:

The Fire was put under control in one hour and 16 minutes after the

first firetruck has arrived. Most of the fatalities died of suffocation.

Electrical Short Circuit

Page 63: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Fire exit at the 3rd Floor without stairs

Page 64: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Ozone Disco Fire

Location : 57-A Timog Ave., Quezon City

Date/Time : 19 2405H March 1996

Cause of Fire: Electrical Malfunction (overloading)

Casualty : 162 persons

Injured : 100 persons m/l

Est. Damages: 15 Million m/l

Electrical Malfunction

(overloading)

Page 65: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

OZONE DISCO FIRE

Page 66: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

Be electrically safe, not sorry!

Page 67: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety

“ENGINEERING

WITHOUT SAFETY IS

A FAILURE”

Page 68: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety
Page 69: Engr. HIPOLITO A. LEONCIO Chairman, Electrical Safety and ...iiee.org.ph/wp-content/uploads/2015/06/Electrical-Safety-and... · properties are lost due to fires ... electrical safety