Engineering Guide Comments

Embed Size (px)

Citation preview

  • 8/6/2019 Engineering Guide Comments

    1/101

    Compliments of:

  • 8/6/2019 Engineering Guide Comments

    2/101

    Revision 0 - i - October 2003

    FOUNDATION fieldbusSystem Engineering Guidelines

    (AG-181) Revision 0

    This preface, as well as all footnotes and annexes, is included for information purposes and isnot part of AG-181.

    This document has been prepared under the direction of the End User Advisory Council(EUAC) of the Fieldbus Foundation. To be of real value, it should not be static but should besubject to periodic review. Toward this end, the foundation welcomes all comments andcriticisms and asks that they be addressed to:

    Chairman

    End User Advisory Council

    Fieldbus Foundation

    9005 Mountain Ridge Drive

    Bowie Building - Suite 190

    Austin, Texas 78759-5316 USA

    Tel: 512.794.8890

    Fax 512.794.8893

    E-mail: [email protected].

    Visit our Worldwide Web Site:

    www.fieldbus.org

    This document in its present revision and at time of publication recognizes that High SpeedEthernet (HSE) products are available from the Fieldbus Foundation and its members. Thenext revision of this document will incorporate guidelines for the installation andimplementation of HSE.

    The use of specific Vendor/Manufacturers in this document does not entail implicitendorsement of the product over other similar products by the authors or the FieldbusFoundation. Individuals using this document are encouraged to seek out equivalent functionequipment from other sources of which the authors may be unaware. To assist in our efforts to

    make this document as relevant as possible, should such equipment be known to a user of thisdocument please forward that information to the address given above.

  • 8/6/2019 Engineering Guide Comments

    3/101

    Revision 0 - ii - October 2003

    It is the policy of Fieldbus Foundation to encourage and welcome the participation of allconcerned individuals and interests in the development of FOUNDATION fieldbus standards,recommended practices, and technical reports. Participation in the Fieldbus Foundation

    standards-making process by an individual in no way constitutes endorsement by the employerof that individual, of the Fieldbus Foundation, or of any of the standards, recommendedpractices, and technical reports that the Fieldbus Foundation develops.

    The Fieldbus Foundation would like to thank the End User Advisory Council and the membersof the End User Council who have committed so much time and effort to the preparation of thisguide.

    In particular the Foundation wishes to acknowledge the following individuals without whosededication this Guide would not have been possible:

    Ian Verhappen (Editor) ICE-Pros, Inc. Chairman, EUAC, CanadaChris Baltus DSM EUAC, EuropeJohn Bazley Beca Simons EUC, Australia

    Ambrose Hargan CSBP EUC, AustraliaHenry Marks Marks & Associates EUC, USANorihko EGI IT Engineering (Retired) EUC, JapanNola Ogar BP Group EUC, USADeon Rae Chevron Texaco EUC, USAJim Russel Keyfleet Pty Ltd EUAC, AustraliaHerman Storey Shell Global Solutions EUAC, USARon Szanyi ExxonMobil Director, Fieldbus Foundation

    Al Chan Canadian Natural Resources Ltd EUC, Canada

    0 October 2003 Original Release IV

    Rev. No. Date Description By

  • 8/6/2019 Engineering Guide Comments

    4/101

    Revision 0 - iii - October 2003

    Caution

    The use of this guide may involve hazardous materials, operations or equipment. The guidecannot anticipate all possible applications or address all possible safety issues associated withuse in hazardous conditions. The user of this guide must exercise sound professional

    judgment concerning its use and applicability under the users particular circumstances andaccording to their established corporate policies and procedures. The user must also considerthe applicability of any governmental regulatory limitations and established safety and healthpractices before implementing this standard.

    Disclaimer of Warranties

    This document is informative only and is provided on an as is bases only. The document maybe subject to future additions, modifications or corrections without notice. The FieldbusFoundation disclaims all warranties of any kind, express or implied, including any warranty ofmerchantability or fitness for a particular purpose, for this document. IN NO EVENT WILL THEFIELDBUS FOUNDATION BE RESPONSIBLE FOR ANY LOSS OR DAMAGE ARISING OUTOF OR RESULTING FROM ANY DEFECT, ERROR OR OMISSION IN THIS DOCUMENT ORFROM ANYONES USE OR RELIANCE ON THIS DOCUMENT.

  • 8/6/2019 Engineering Guide Comments

    5/101

    Revision 0 - iv - October 2003

    How To Use This Document

    This document reflects standard industry practices for the application FOUNDATION fieldbus H1projects at time of publication. As this is a living document it will be maintained and updatedperiodically to reflect changes in the technology including the adoption and application of HighSpeed Ethernet (HSE).

    The authors recognize that each facility planning to or installing a FOUNDATION fieldbus projectmay not wish to adhere to all the recommendations as reflected in this guideline. Towards thatend, the Council recommends that rather than change this document, which has several cross-references, that the user instead prepares a forward clearly identifying those sections to bemodified or applied in a different way. An example of this follows:

    XYZ Company applies Section 6.3.3 to provide additional grounding protection for fielddevices."

    Recommended changes additions or suggestions should be forwarded via email to:[email protected]

  • 8/6/2019 Engineering Guide Comments

    6/101

    Revision 0 - v - October 2003

    1.0 Introduction...........................................................................................................1

    1.1 Contents ...........................................................................................................1

    1.2 Purpose ............................................................................................................21.3 Scope................................................................................................................2

    2.0 References ............................................................................................................3

    3.0 Definitions .............................................................................................................4

    Abbreviations..........................................................................................................12

    4.0 Field Device Requirements..................................................................................14

    4.1 Support for FOUNDATION fieldbus Functionality..................................................14

    4.2 Device Diagnostics ...........................................................................................16

    4.3 Field Device Power...........................................................................................17

    4.4 Service Conditions............................................................................................18

    4.5 Logical Field Devices........................................................................................18

    4.6 Factory Configuration........................................................................................19

    5.0 Ancillary Device Requirements ...........................................................................20

    5.1 Bulk Power Supplies.........................................................................................20

    5.2 FOUNDATION fieldbus Power Supply/Conditioner (FFPS)...................................20

    5.3 FOUNDATION fieldbus Terminators .....................................................................21

    5.4 FOUNDATION fieldbus Repeaters........................................................................21

    5.5 FOUNDATION fieldbus Wire .................................................................................225.6 FOUNDATION fieldbus Junction Boxes ................................................................22

    6.0 Fieldbus Segment Design Guidelines.................................................................23

    6.1 FOUNDATION fieldbus Segment Topology...........................................................23

    6.2 FOUNDATION fieldbus Wiring ..............................................................................24

    6.3 FOUNDATION fieldbus Power, Grounding & Lighting Protection..........................27

    6.4 FOUNDATION fieldbus Segment Risk Management ............................................30

    6.5 Intrinsically Safe (IS) Installations.....................................................................33

    6.6 Fieldbus Intrinsically Safe Concept (FISCO) Installations.................................34

    6.7 FOUNDATION fieldbus Loading and Calculations ................................................36

    6.8 FOUNDATION fieldbus Segment Naming Convention..........................................38

    7.0 Host System Requirements .................................................................................39

    7.1 Use of Standard Products.................................................................................39

    7.2 Spare Capacity and Expansion.........................................................................39

    7.3 Interoperability ..................................................................................................39

    7.4 Host Interoperability Support Test (HIST) Description ......................................39

  • 8/6/2019 Engineering Guide Comments

    7/101

    Revision 0 - vi - October 2003

    7.5 Support for FOUNDATION fieldbus Functionality..................................................42

    7.6 Configuration Tool.............................................................................................42

    7.7 Redundancy & Robustness ..............................................................................447.8 Troubleshooting, Maintenance and Diagnostics ...............................................45

    7.9 Advanced Diagnostics and Computer Based Maintenance ..............................45

    7.10 Evaluation Guidelines .....................................................................................46

    8.0 Software Configuration Guidelines.....................................................................48

    8.1 Control System Graphics ..................................................................................48

    8.2 Node Addressing and Naming Conventions .....................................................48

    8.3 Control Functionality Location...........................................................................51

    8.4 Configuration Options and Defaults ..................................................................52

    8.5 Alarms and Alerts..............................................................................................52

    8.6 Segment Communications and Scheduling ......................................................54

    8.7 Data Import and Export.....................................................................................58

    8.8 Operator Display...............................................................................................58

    8.9 Software Revision.............................................................................................59

    8.10 System Management ......................................................................................60

    8.11 Control and Data Handling..............................................................................60

    8.12 System Configuration Tools............................................................................63

    8.13 Displays ..........................................................................................................66

    9.0 Documentation Requirements.............................................................................69

    9.1 Drawings...........................................................................................................71

    9.2 Control Narrative...............................................................................................71

    9.3 Instrument Index/Database...............................................................................71

    9.4 Instrument Data Sheets ....................................................................................71

    9.5 Material Requisitions.........................................................................................71

    9.6 Manufacturer Documentation............................................................................71

    9.7 Maintenance Manuals.......................................................................................72

    10.0 Factory Acceptance Testing Requirements .......................................................7310.1 Introduction .....................................................................................................73

    10.2 Factory Staging...............................................................................................73

    10.3 Assumptions ...................................................................................................73

    10.4 Factory Acceptance Test (FAT) Requirements...............................................74

    10.5 FAT Procedure................................................................................................75

    11.0 Site Installation Guidelines..................................................................................79

  • 8/6/2019 Engineering Guide Comments

    8/101

    Revision 0 - vii - October 2003

    11.1 Introduction .....................................................................................................79

    11.2 Network Installations.......................................................................................79

    11.3 Cable Test Procedure.....................................................................................7911.4 Segment Checkout Procedure........................................................................83

    11.5 Loop Checkout/Site Integration Tests .............................................................86

    11.6 Hot Cutover.....................................................................................................88

    11.7 Bench Simulation Testing ...............................................................................89

    11.8 System Development Room ...........................................................................89

    11.9 MCC Testing...................................................................................................89

    11.10 Provision of Spares.......................................................................................89

    11.11 Removal of Redundant Equipment ...............................................................90

  • 8/6/2019 Engineering Guide Comments

    9/101

    Revision 0 - 1 - October 2003

    1.1 CONTENTSThe FOUNDATION fieldbus EngineeringGuideline is separated into sections. The

    following is an explanation of the intent ofeach chapter:

    Section 01 Introduction and ScopeThe purpose and scope of the FOUNDATIONfieldbus Engineering Guidelines.

    Section 02 ReferencesReferences used to compile FOUNDATIONfieldbus Engineering Guidelines.

    Section 03 DefinitionsTerms used specifically with FOUNDATIONfieldbus technology.

    Section 04 Field Device RequirementsFunctional requirements of the field deviceswhen used to implement FOUNDATIONfieldbus technology.

    Section 05 Ancillary DeviceRequirementsFunctional requirements of the ancillarycomponents such as bulk power suppliesand power conditioners for use withFOUNDATION fieldbus technologyimplementation.

    Section 06 Network/Segment DesignGuidelinesInformation, explanations & guidelines foruse when designing FOUNDATION fieldbusnetworks/segments.

    Section 07 Host System RequirementsFunctional requirements of the host systemwhen used to implement FOUNDATIONfieldbus technology.

    Section 08 Software ConfigurationGuidelinesInformation, explanations and guidelines for

    use when configuring control system soft-ware for use in a strategy that incorporatesFOUNDATION fieldbus. Items covered includecontrol module configuration, function blockimplementation, condition-based monitoringsoftware configuration, and alarmmanagement and configuration.

    Section 09 DocumentationRequirementsRequired documentation for use when

    designing and maintaining FOUNDATIONfieldbus technology. Documentation suchas control philosophy, P&IDs & instrumentlocation drawings is covered in this chapter.

    Section 10 Factory Acceptance Test(FAT) RequirementsTasks and functions required to FAT acontrol system utilizing FOUNDATION fieldbustechnology.

    Section 11 Site InstallationRequirementsInformation and procedures for use wheninstalling fieldbus networks. This sectionalso specifies the procedures required tocheck out a FOUNDATION fieldbus system, aswell as identifying required tools for use ininstalling and maintaining FOUNDATIONfieldbus equipment.

  • 8/6/2019 Engineering Guide Comments

    10/101

    Revision 0 - 2 - October 2003

    1.2 PURPOSEThe FOUNDATION fieldbus SystemEngineering Guideline is intended to

    compliment the principals existing series ofinstrument specifications. It details howfieldbus devices are specified, installed,configured, commissioned, and maintaineddifferently than conventional analog or"smart" instruments.

    Since this guideline covers several different"topics" it has been separated into anumber of individual parts, one for each ofthe components of its "life cycle."

    This Engineering Guideline addresses theimplementation of FOUNDATION fieldbusonly. Other fieldbus technologies exist thatmay be integrated to the basic processcontrol system, if the engineering designrequires. FOUNDATION fieldbus is primarilyused to replace the traditional analoginput/output signal types. FOUNDATIONfieldbus technology is charted by theFieldbus Foundation.

    This guideline deliberately uses the termsfieldbus and Fieldbus. Lower case fieldbusrefers to the generic use of the term and isapplicable to all fieldbuses defined in theIEC documentation. Upper case Fieldbusrefers specifically to FOUNDATION fieldbus.

    1.3 SCOPEDefinition of the design, specification,installation, configuration, commissioningand maintenance for a FOUNDATIONfieldbus-based control systems.

    This guideline will only discuss the voltagemode (parallel coupling) mediumattachment unit, as defined in ISA 50.02,operating at a signal speed of 31.25 kilobitsper second (i.e., H1). This revision of thespecification does not cover the High

    Speed Ethernet (HSE) version ofFOUNDATION fieldbus.

    FOUNDATION fieldbus systems includeinstruments and hosts that cover allapplications and aspects of instrumentationand control. Therefore, it is intended that allFOUNDATION instrumentation and controlsystem standards apply to FOUNDATIONfieldbus systems, except as noted herein.Note, however, that only those standardscalled out by name within this document arespecifically referenced.

    Subject to the disclaimer at the front of thisdocument, this Engineering Guideline is foruse by both the contractor and controlsystem vendor.

    1.3.1 GeneralFieldbus is an all digital, two-way multi-dropcommunications link among intelligentsmart field devices and automationsystems. FOUNDATION Fieldbus is the Local

    Area Network (LAN) for instruments used in

    process automation with built-in capabilityto distribute the control application acrossthe network.

    1.3.3 Project ConsiderationAs with any new project it is critical that theright skill sets be brought forth for theproject. The same is true for a Fieldbusproject. Experience has shown that trainingof all members of the project team,engineers, maintenance personnel, andoperations staff is critical to the projectsuccess. This training should be provided atthe front end of the project to minimizerework as this information is gained throughexperience.

    Bringing in the right consultants at keyjunctures in the project to review and adviseon the next steps is also often a prudentinvestment.

  • 8/6/2019 Engineering Guide Comments

    11/101

    Revision 0 - 3 - October 2003

    2.0 Other References

    2.1 Fieldbus Foundation Specifications2.1.1 FF-569 Host Interoperability Support Test

    2.2 Industry Codes and Standards

    2.2.1 IEC 61158-1:Introductory Guide

    2.2.2 IEC 61158-2:Physical Layer Specification and Service Definition

    2.2.3 IEC 61158-3:Data Link Layer (DLL) Service Definition

    2.2.4 IEC 61158-4:Data Link Layer (DLL) Protocol Specification

    2.2.5 IEC 61158-5:Application Layer Service Specification

    2.2.6 IEC 61158-6:Application Layer Protocol Specification

    2.2.7 IEC 61158-7:System Management

    2.2.8 IEC 61158-8:Conformance Testing

    Note that the parts dealing with the DDL and the Application Layer contain parallel sections foreight different protocols, including FOUNDATION fieldbus.

    De facto standards are available from the Fieldbus Foundation that will comply with and becompatible with the IEC 61158 suite of standards.

    2.3 Other References

    2.3.1 Fieldbus Technical Overview Understanding Fieldbus Technology Fisher Rosemount

    2.3.2 Yokogawa TI 38K02A01-01E Fieldbus Book A Tutorial

    2.3.3 FOUNDATION fieldbus Wiring Design & Installation GuidelinesAuthor Relcom, Inc.ISBN Download @ http://www.relcominc.com/download/fbguide.pdf

    2.3.4 Fieldbuses for Process Control: Engineering, Operation and MaintenanceAuthor Jonas Berge

    ISBN 1-55617-760-7 (note ISA publication) Also available in Chinese

    2.3.5 Industrial Ethernet Planning and Installation GuideSponsoring Organization: IAONA e.VDownload @ http://www.iaona-eu-com

    2.3.6 FOUNDATION Fieldbus: A Pocket GuideAuthors Ian Verhappen, Augusto PereiraISBN 1-55617-775-5 (note ISA publication) Also available in Portuguese

  • 8/6/2019 Engineering Guide Comments

    12/101

    Revision 0 - 4 - October 2003

    3.0 Definitions

    3.1 General DefinitionsThe definitions below shall be included ifthe words defined are used in the Code ofPractice.

    The Contractoris the party that carries outall or part of the design, engineering,procurement, construction, commissioningor management of a project, or operation ormaintenance of a facility.

    The Principal may undertake all or part ofthe duties of the Contractor.

    The Manufacturer/Supplieris the party thatmanufactures or supplies equipment andservices to perform the duties specified bythe Contractor.

    The Principalis the party that initiates theproject and ultimately pays for its designand construction. The Principal willgenerally specify the technical

    requirements. The Principal may alsoinclude an agent or consultant authorized toact for, and on behalf of, the Principal.

    The words shall/must/willindicate amandatory requirement.

    The word shouldindicates an acceptablecourse of action or feature based on pastproject implementations.

    The words may/can indicate oneacceptable course of action.

    3.2 FOUNDATION fieldbus DefinitionsThe following represent definitions of termscommonly encountered in the use andapplication of Fieldbus technology. Acomprehensive list of definitions related toFOUNDATION fieldbus can be found on the

    Fieldbus Foundation web site atwww.fieldbus.org.

    A

    Acyclic PeriodThat portion of the communication cycletime, during which information other thanPublish/Subscribe data is transmitted.Typical information transmitted during thistime includes Alarms/Events, Maintenance/Diagnostic information, Programinvocations, Permissives/Interlocks, Displayinformation, Trend Information and

    Configuration.

    Application LayerA layer in the communication stackcontaining the object dictionary.

    Automation SystemA process automation, control, anddiagnostic system that is composed ofdistinct modules. These modules may bephysically and functionally distributed over

    the plant area. The automation systemcontains all the modules and associatedsoftware required to accomplish theregulatory control and monitoring of aprocess plant. This definition of automationsystem excludes field instruments, remoteterminal units, auxiliary systems andmanagement information systems.

    Auto SenseCapability by the system to automatically

    detect and recognize any hardware uponaddition to or removal from the systemwithout any user intervention.

    Auxiliary SystemA control and/or monitoring system that isstand-alone, performs a specialized task,and communicates with the automationsystem.

  • 8/6/2019 Engineering Guide Comments

    13/101

    Revision 0 - 5 - October 2003

    B

    Basic DeviceA Basic Device is any device not having thecapability to control communications on anH1 fieldbus segment.

    BrickFully connectorised passive junctionlocated on the bus.

    BusA H1 fieldbus cable between a host andfield devices connected to multiple

    segments, sometimes through the use ofrepeaters.

    C

    Capabilities FileA Capabilities File describes thecommunication objects in a fieldbus device.

    A configuration device can use DeviceDescription (DD) Files and Capabilities

    Files to configure a fieldbus system withouthaving the fieldbus devices online.

    Common File Format File (CFF)A software file used by the host to know thedevice detailed FF capabilities withoutrequiring the actual device. This file formatis used for Capabilities and Value files.

    Communications StackLayered software supporting communi-cation between devices. A CommunicationsStack is device communications software,which provides encoding and decoding ofUser Layer messages, deterministic controlof message transmission, and messagetransfer.

    ConfigurableThe capability to select and connectstandard hardware modules to create a

    system; or the capability to changefunctionality or sizing of software functionsby changing parameters without having tomodify or regenerate software.

    ConfigurationThe physical installation of hardwaremodules to satisfy system requirements; orthe selection of software options to satisfysystem requirements.

    ConnectorA Connector is a coupling device used toconnect the wire medium to a fieldbusdevice or to another segment of wire.

    ConsoleA collection of one or more workstationsand associated equipment such as printersand communications devices used by anindividual to interact with the automationsystem and perform other functions.

    Control LoopA Control Loop is a group of FunctionBlocks (FBs) that execute at a specifiedrate within a fieldbus device or distributedacross the fieldbus network.

    CouplerA Coupler is a physical interface between atrunk and spur, or a trunk and a device.

    Cycle

    The scanning of inputs, execution ofalgorithms and transmission of outputvalues to devices.

  • 8/6/2019 Engineering Guide Comments

    14/101

  • 8/6/2019 Engineering Guide Comments

    15/101

    Revision 0 - 7 - October 2003

    Commentary:Network Management (NM) permitsFOUNDATIONNetwork Manager (NMgr)

    entities to conduct management operationsover the network using Network Management

    Agents (NMAs). Each NMA is responsiblefor managing the communications within adevice. The NMgr and NMA communicatethrough use of the FMS and VirtualCommunications Relationship (VCR).

    FISCOFieldbus Intrinsic Safe COncept. Allowsmore power to an IS segment for approved

    FISCO devices, allowing for more devicesper IS segment.

    Commentary:FISCO eliminates the requirement ofcalculating entity parameters of capacitanceand inductance when designing networks.

    Flexible Function Block (FFB)A Flexible Function Block (FFB) is similar toa Standard FB, except that an application-

    specific algorithm created by a program-ming tool determines the function of theblock, the order and definition of the blockparameters, and the time required toexecute the block. Flexible Function Blocks(FFBs) are typically used for control ofdiscrete processes and for hybrid (batch)processes. A Programmable LogicController (PLC) can be modeled as aFlexible Function Block device.

    FNICOFieldbus Non-Incendive COncept. Allowsmore power to a Fieldbus segment in aZone 2 Area thus allowing for more devicesper segment.

    G

    GatewayTranslates another protocol to Fieldbus, forexample HART to Fieldbus or Modbus toFieldbus.

    H

    H1H1 is a term used to describe a fieldbusnetwork operating at 31.25 kbit/second.

    H1 Field DeviceAn H1 Field Device is a fieldbus deviceconnected directly to an H1 fieldbus.Typical H1 Field Devices are valves andtransmitters.

    H1 RepeaterAn H1 Repeater is an active, bus-poweredor non-bus-powered device used to extendthe range over which signals can becorrectly transmitted and received for a

    given medium. A maximum of fourRepeaters and/or active Couplers can beused between any two devices on an H1fieldbus network. Repeaters connectsegments together to form larger networks.

    High Speed Ethernet (HSE)High Speed Ethernet (HSE) is the FieldbusFoundation's backbone network runningEthernet and IP.

    HISTHost Interoperability Support Testperformed by the foundation to test hostconformance to the FF specifications.

    HSE Field DeviceAn HSE Field Device is a fieldbus deviceconnected directly to a High SpeedEthernet (HSE) fieldbus. Typical HSE FieldDevices are HSE Linking Devices, HSE

  • 8/6/2019 Engineering Guide Comments

    16/101

    Revision 0 - 8 - October 2003

    Field Devices running Function Blocks(FBs), and Host Computers.

    HSE Linking DeviceAn HSE Linking Device is a device usedto interconnect H1 fieldbus networks/segments to High Speed Ethernet (HSE)to create a larger system.

    HSE SwitchAn HSE Switch is standard Ethernetequipment used to interconnect multipleHigh Speed Ethernet (HSE) devices suchas HSE Linking Devices and HSE Field

    Devices to form a larger HSE network.

    I

    Input/Output (I/O) Subsystem InterfaceAn Input/Output (I/O) Subsystem Interfaceis a device used to connect other types ofcommunications protocols to a fieldbussegment or segments. Refer also toGateway.

    InterchangeabilityInterchangeability is the capability tosubstitute a device from one manufacturerwith that of another manufacturer on afieldbus network without loss of functionalityor degree of integration.

    InstantiableThe ability, for function block, to createmultiple tagged function blocks of differenttypes from a library as required by

    application. Quantity per device restrictedby device memory and other resources

    InteroperabilityInteroperability is the capability for a devicefrom one manufacturer to interact with thatof another manufacturer on a fieldbusnetwork without loss of functionality.

    ISIntrinsic Safety

    ITKInteroperability Test Kit used by thefoundation to tick mark devices andconfirms compliance with the relevantFOUNDATION fieldbus standards. This is apass/fail test. Only devices passing the fullsuite of tests receive the FF "tick mark."

    J

    Junction Box / Quick Connection StationA junction box station allows for quickinstallation of four to eight field instrumentsvia Terminal connectors.

    K

    L

    Link

    A Link is the logical medium by which H1Fieldbus devices are interconnected. It iscomposed of one or more physicalsegments interconnected by bus,Repeaters or Couplers. All of the deviceson a link share a common schedule, whichis administered by that link's current LAS. Itis the data link layer name for a network.

    Link Active Scheduler (LAS)A Link Active Scheduler (LAS) is a

    deterministic, centralized bus scheduler thatmaintains a list of transmission times for alldata buffers in all devices that need to becyclically transmitted. Only one Link Master(LM) device on an H1 fieldbus Link can befunctioning as that link's LAS.

  • 8/6/2019 Engineering Guide Comments

    17/101

    Revision 0 - 9 - October 2003

    Link Master (LM)A Link Master (LM) is any device containingLink Active Scheduler (LAS) functionality

    that can control communications on an H1fieldbus Link. There must be at least oneLM on an H1 Link; one of those LM deviceswill be elected to serve as LAS.

    Link ObjectsA Link Object contains information to linkFunction Block (FB) Input/Output (I/O)parameters in the same device andbetween different devices. The Link Objectlinks directly to a Virtual Communications

    Relationship (VCR).

    M

    MAC AddressA unique hardware address given to eachEthernet interface chip.

    MethodsMethods are an optional (but highlydesirable) addition to Device Descriptions(DDs). Methods are used to define/automate procedures (such as calibration)for operation of field devices.

    ModeControl block operational condition, such asmanual, automatic, or cascade.

    N

    NetworkA network as applied in this document, isthe termination of one or more fieldbussegments into an interface card of the hostsystem.

    Commentary:In this document, as has become industry

    practice, the term segment is used to

    represent a cable and devices installedbetween a pair of terminators.

    Network Management (NM)Network Management (NM) permitsFOUNDATION fieldbus Network Manager(NMgr) entities to conduct managementoperations over the network by usingNetwork Management Agents (NMAs).Each Network Management Agent (NMA) isresponsible for managing the communica-tions within a device. The NMgr and NMAcommunicate through use of the FieldbusMessaging Specification (FMS) and Virtual

    Communications Relationship (VCR).

    Noise AVAverage noise in the network during thesilence period between frames.

    O

    Object DictionaryAn Object Dictionary (OD) contains all

    Function Block (FB), Resource Block (RB)and Transducer Block (TB) parametersused in a device. Through these para-meters, the blocks may be accessed overthe fieldbus network.

    OPC (Object Linking and Embedding forProcess Control)Software application which allows bi-directional data flow between two separateapplications. These applications may berunning on the same or on separateservers.

    Operator ConsoleA console used by an operator to performthe functions required to monitor andcontrol his assigned units.

  • 8/6/2019 Engineering Guide Comments

    18/101

    Revision 0 - 10 - October 2003

    P

    Physical LayerThe Physical Layer receives messagesfrom the Communications Stack andconverts the messages into physical signalson the fieldbus transmission medium, andvice-versa.

    Q

    Quiescent CurrentThe device power consumption, the current

    drawn while the device is not transmitting.Shall be as low as possible to enable manydevices and long wires, particularly inintrinsic safety.

    R

    Redundant ConfigurationA system/subsystem configuration thatprovides automatic switchover, in the event

    of a failure, without loss of a systemfunction.

    Regulatory ControlThe functions of process measurement,control algorithm execution, and finalcontrol device manipulation that provideclosed loop control of a plant process.

    Resource Block (RB)A Resource Block (RB) describescharacteristics of the fieldbus device such

    as the device name, manufacturer andserial number. There is only one ResourceBlock (RB) in a device.

    S

    SchedulesSchedules define when Function Blocks(FBs) execute and when data and status ispublished on the bus.

    SegmentA Segment is a section of an H1 fieldbusthat is terminated in its characteristicimpedance. Segments can be linked byRepeaters to form a longer H1 fieldbus.Each Segment can include up to 32 H1devices.

    Commentary:In this document, as has become industry

    practice, the term segment is used torepresent a cable and devices installedbetween a pair of terminators. The Fieldbusspecifications use the term network todescribe the system of devices though thisdocument uses the terms interchangeably.

    See ANSI/ISA50.02, Part 2 (IEC 61158-2):

    SEGMENT = The section of a fieldbus thatis terminated in its characteristicimpedance. Segments are linked byrepeaters to form a complete fieldbus.Several communication elements may beconnected to the trunk at one point using amulti-port coupler. An active coupler maybe used to extend a spur to a length thatrequires termination to avoid reflections anddistortions. Active repeaters may be used toextend the length of the trunk beyond that

    of a single segment as permitted by thenetwork configuration rules. A fully loaded(maximum number of connected devices)31,25 kbit/s voltage-mode fieldbus segmentshall have a total cable length, includingspurs, between any two devices, of up to 1900 m. there shall not be a nonredundantsegment between two redundant segments.

  • 8/6/2019 Engineering Guide Comments

    19/101

    Revision 0 - 11 - October 2003

    Self-DiagnosticThe capability of an electronic device tomonitor its own status and indicate faults

    that occur within the device.

    SpliceA Splice is an H1 Spur measuring less than1 m (3.28 ft.) in length.

    SpurA Spur is an H1 branch line connecting tothe Trunk that is a final circuit. A Spur canvary in length from 1 m (3.28 ft.) to 120 m(394 ft.).

    Standard Function Block (FB)Standard Function Blocks (FBs) are builtinto fieldbus devices as needed to achievethe desired control functionality. Automationfunctions provided by Standard FBs include

    Analog Input (AI), Analog Output (AO) andProportional/Integral/Derivative (PID)control. The Fieldbus Foundation hasreleased specifications for 21 types ofStandard FBs. There can be many types of

    FBs in a device. The order and definition ofStandard FB parameters are fixed anddefined by the specifications.

    Rate/Stale CountThis is a number corresponding to theallowable missed communications before adevice will shed mode. This is basically aWatchdog Timer.

    System Management (SM)System Management (SM) synchronizesexecution of Function Blocks (FBs) and thecommunication of Function Block (FB)parameters on the fieldbus, and handlespublication of the time of day to all devices,automatic assignment of device addresses,and searching for parameter names or"tags" on the fieldbus.

    T

    TagA collection of attributes that specify eithera control loop or a process variable, or ameasured input, or a calculated value, orsome combination of these, and allassociated control and output algorithms.Each tag is unique.

    Tag IdThe unique alphanumeric code assigned toinputs, outputs, equipment items, andcontrol blocks. The tag ID might include the

    plant area identifier.

    TerminatorImpedance-matching module used at ornear each end of a transmission line thathas the same characteristic impedance ofthe line. Terminators are used to minimizesignal distortion, which can cause dataerrors by converting between currentvariations and voltage variations. H1terminators also have another even more

    important function. It converts the currentsignal transmitted by one device to avoltage signal that can be received by alldevices on the network.

    TopologyShape and design of the fieldbus network(for example, tree branch, daisy chain,point-to-point, bus with spurs, etc.).

    Transducer Block (TB)

    A Transducer Block (TB) decouplesFunction Blocks (FBs) from the localInput/Output (I/O) functions required to readsensors and command output hardware.Transducer Blocks (TBs) containinformation such as calibration date andsensor type. There is usually one TBchannel for each input or output of aFunction Block (FB).

  • 8/6/2019 Engineering Guide Comments

    20/101

    Revision 0 - 12 - October 2003

    TransmitterA Transmitter is an active fieldbus devicecontaining circuitry, which applies a digital

    signal on the bus.

    TrunkA Trunk is the main communicationhighway between devices on an H1 fieldbusnetwork. The Trunk acts as a source ofmain supply to Spurs on the network.

    U

    User ApplicationThe User Application is based on "blocks,"including Resource Blocks (RBs), FunctionBlocks (FBs) and Transducer Blocks (TBs),which represent different types ofapplication functions.

    User LayerThe User Layer provides scheduling ofFunction Blocks (FBs), as well as DeviceDescriptions (DDs), which allow the hostsystem to communicate with deviceswithout the need for custom programming.

    V

    Virtual Communication Relationship(VCR)Configured application layer channels thatprovide for the transfer of data betweenapplications. FOUNDATION fieldbus describesthree types of VCRs: Publisher/ Subscriber,

    client/Server, and Source/Sink.

    Virtual Field Device (VFD)A Virtual Field Device (VFD) is used toremotely view local device data describedin the object dictionary. A typical device willhave at least two Virtual Field Devices(VFDs).

    W

    WizardA Wizard is a means of automatingprocedures in Windows. Wizards can beused to implement methods.

    WorkstationA set of electronic equipment including, at aminimum, one monitor, keyboard(s) andassociated pointing device(s).

    X

    Y

    Z

  • 8/6/2019 Engineering Guide Comments

    21/101

    Revision 0 - 13 - October 2003

    Abbreviations Description

    AI Analogue Input

    AO Analogue Output

    BPS Bulk Power Supply

    CAPEX Capital Expenditure

    CCR Central Control Room

    C/S Client/Server

    CFF Common File Format

    DCS Distributed Control System / Digital Control System

    DI Discrete InputDD Device Description

    DLL Data Link Layer

    DO Discrete Output

    EDDL Enhanced Device Description Language

    ESD Emergency Shut Down

    FAR Field Auxiliary Room

    FAS Fieldbus Access Sublayer

    FB Function Block

    FF FOUNDATION Fieldbus

    FFB Flexible Function Block

    FFPS FOUNDATION Fieldbus Power Supply

    F&G Fire and Gas

    HIST Host Interoperability Support Testing

    HMI Human Machine Interface

    HSE High Speed EthernetIEC International Electro technical Commission.

    I/O Input Output

    IPF Instrument Protective Function

    IS Intrinsic Safety

    IT Information Technology

    ITC Individual Twisted Cable

  • 8/6/2019 Engineering Guide Comments

    22/101

    Revision 0 - 14 - October 2003

    Abbreviations Description

    ITK Interoperability Test Kit

    LAS Link Active Schedule

    LM Link Master

    MAI Multi Analogue Input

    MAO Multi Analogue Output

    ML Manual Loader

    MV Manipulated Variable (controller output)

    NM Network Management

    OD Object DictionaryOPEX Operational Expenditure

    PCS Process Control System

    PAS Process Automation System

    P/S Publish/Subscribe

    PD Proportional / Derivative Control

    P&ID Process & Instrumentation Diagram

    PID Proportional / Integral / Derivative Control

    PTB Physikalisch-Technische Bundesanstalt

    PV Process Variable

    PLC Programmable Logic Controller

    RA Ratio

    RB Resource Block

    SIL Safety Integrity Level

    SM System Management

    SP Set PointSS Safety Systems

    TB Transducer Block

    TCoO Total Cost of Ownership

    TPE ThermoPlastic Elastomer

    VCR Virtual Communication Resource

  • 8/6/2019 Engineering Guide Comments

    23/101

    Revision 0 - 15 - October 2003

    4.1 Support for FOUNDATION fieldbusFunctionality

    All Fieldbus instruments should support

    Methods to allow automation of onlineprocedures (such as calibration) from theHost.

    4.1.1 Fieldbus RegistrationAll devices must as a minimum satisfy therequirements of the fieldbus registrationlaboratory. In the case of the FieldbusFoundation, this is the FF check marklogo and listing on the approved devices listmaintained on their web site

    (www.fieldbus.org). This verifiesinteroperability of devices as indicated inthe following example:

    Example 4.1 FOUNDATIONfieldbus Check Mark Logo

    4.1.2 Fieldbus Function BlocksThe following function blocks are defined bythe Fieldbus Foundation. Not all of thesefunction blocks are available for use in allfield devices, and some are not availableand/or do not yet have interoperability tests.

    Standard Function Blocks:FF-891: Function Blocks Part 2 definesthese. The ten standard Function Blocksare as follows:

    AI - Analog Input

    AO - Analog Output

    B - Bias

    CS - Control Selector

    DI - Discrete Input

    DO - Discrete Output

    ML - Manual LoaderPD - Proportional/Derivative Control

    PID - Proportional/Integral/Derivative Control

    RA - Ratio

    Advanced Function Blocks:Advanced Function Blocks are defined inFF-892: Function Blocks Part 3 are asfollows:

    Pulse Input

    Complex AO Complex DO

    Step Output PID

    Device Control

    Setpoint Ramp

    Splitter

    Input Selector

    Signal Characterizer

    Dead Time

    Calculate

    Lead/Lag

    Arithmetic

    Integrator

    Timer

    Analog Alarm

    Discrete Alarm

    Analog Human Interface

    Discrete Human Interface

    Additional Function Blocks:Function Blocks are defined in FF-892:Function Blocks Part 4 are as follows:

    Multiple Analog Input

    Multiple Analog Output

    Multiple Digital Input

    Multiple Digital Output

  • 8/6/2019 Engineering Guide Comments

    24/101

    Revision 0 - 16 - October 2003

    Flexible Function Blocks are defined inFF-892: Function Blocks Part 5 asfollows:

    Flexible Function Block (IEC 1131Logic)

    Commentary:It can be seen from the list that FunctionBlock types are not suitable or available forall instruments. It is therefore essential tomake a considered choice when specifyingthe Function Blocks to be included invarious field device types. Although it isappropriate to host most of these blocks incontrollers, field devices on H1 networks/segments due to the availability of devices,may be limited to the following blocks: AI fortransmitters, AO and PID for Valves, andDI/DO for discrete devices. See Section 8.3and Section 8.6 for further guidance on useof field device function blocks. FurtherFunction Blocks are likely to be added inthe future, it is therefore wise to checkFunction Block availability with theinstrument manufacturer at the time of

    purchase, thus ensuring that the featuresdesired are available for use.

    Function Block Testing:The Fieldbus Foundation tests of FunctionBlocks only confirm that they are presentand how their external interface behaves,not how well they work internally. Eachmanufacturer can configure the internaloperations of Function Blocks as they wishand will in fact do so since this will provide

    them a competitive advantage. It is thusworthwhile to check which manufacturergives the best result in regards tomacrocycle efficiency and the needs of yourprocess.

    Example:Each manufacturer can implement the PIDalgorithm with unique equations while still

    providing control in a PID block.

    4.1.3 User Application BlocksFunction Blocks handle the control strategy.The Function Block diagram is a graphicalprogramming language for building controlstrategies.

    There are two kinds of blocks that are foundin FOUNDATION fieldbus devices: Deviceapplication blocks, where the execution of

    these blocks uses predefined schedulingspecified by the device manufacturers andare used to configure devices, these arethe:

    Resource Block

    Transducer Block

    Function Blocks (FBs) whoseschedule and usage is completelyuser-configurable.

    4.1.4 Resource BlockThe Resource Block (RB) describescharacteristics of the fieldbus device suchas the device name, manufacturer, andserial number. The following should beconsidered for design purposes:

    The user cannot make modifications.

    User can change parameters.

    There is only one RB in a device.

    The RB is the only obligatory block in

    FF devices. The RB contains ID information and

    general information related to thewhole resource or state of theresource (no real details about devicefunctionality).

  • 8/6/2019 Engineering Guide Comments

    25/101

    Revision 0 - 17 - October 2003

    Consider this: contains overall healthand operational status, contains writeprotection and enabling of simulation

    etc.

    4.1.5 Transducer BlocksThe Transducer Block (TB) containsinformation such as calibration date andsensor type.

    TBs decouple FBs from the local Input/Output (I/O) functions required to readsensors and command output hardware.I.e. this is where parameterization,

    calibration and diagnostics for the deviceis done.

    There is typically one TB channel for eachinput or output channel of a device (thismay differ for some devices).

    4.1.6 Function BlocksFunction Blocks (FBs) should be used inuser-defined function block applications toprovide various functions required in a

    control system (for example, input, output,signal selection, and other control actions).I.e. function blocks are the control strategy.The Fieldbus Foundation has definedseveral device profiles outlining the "root"requirement for several device types. Thisincludes pressure, temperature, valves andsome others. It is a good idea to usedevices that conform to thesespecifications.

    FBs are built into fieldbus devices, asneeded, to achieve the desired controlfunctionality. Section 4.1.2 provides a list ofstandard, advanced, and multiple I/O FBs.

    Commentary:The Fieldbus Foundation has defineddozens of standard function blocks.

    Additional function blocks may be definedand implemented by each manufacturer to

    accommodate individual control strategiesand signal processing needs.

    Each manufacturer configures the internaloperations of FBs as they wish looking forcompetitive advantage. FF organizationtests only confirm that FBs are present andhow their external interface behaves, nothow well they work internally. It may be agood idea to as far as possible only usestandard blocks in the control strategy.Because enhanced blocks (standard blockswith additional parameters) haveextensions that are unique to each

    manufacturer, it becomes much moredifficult to replace a device that usesenhanced blocks. Devices with"instantiable" blocks have the advantagethat they typically support both the standardblock (e.g. PID) plus enhanced blocks (e.g.enhanced PID with some additionalfeatures). This way it becomes easy tochose standard blocks whenever sufficient,and enhanced blocks only when reallyrequired. Thus instantiable blocks make

    interchangeability much easier.

    4.2 Device DiagnosticsThe diagnostics shall be able to provide keyinformation on the ability of the device tomeasure or control the process, includingbut not limited to basic device failurediagnostics and advanced diagnostics. Thetypes of diagnostics required are explainedin the following sections.

    Basic Diagnostics:Basic diagnostics are the device failurediagnostics that shall be viewable from anyprocess control host. They help determinecommon problems with the device,communication path, and host. Diagnosticsthat indicate a device failure shall force theaffected loop into MAN (Manual) forTransmitters and IMAN the PID block in theoutput device, typically a valve.

  • 8/6/2019 Engineering Guide Comments

    26/101

    Revision 0 - 18 - October 2003

    Advanced Diagnostics:Advanced diagnostics include full devicediagnostics so that the device health can be

    determined without removing it from theprocess. Advanced diagnostics come in twoforms, online and off-line.

    Online:Online diagnostics perform their functionwhile the device is performing its normalfunction, and provide the capability toalert operations in real time if a problemneeds attention. This function providesone of the primary benefits of FOUNDATION

    Fieldbus and should be supported by allfield devices as rapidly as possible.

    Offline:Offline tests provide limited benefits andmay not justify their cost.

    FF devices should be capable of supportingincremental device description (DD) forextra functionality and/or software revisionsin device memory.

    Capabilities include the followingdiagnostics and should provide keyinformation on the impact that an outputdevice has on the process, including but notlimited to:

    Position accuracy

    Operating resolution

    Total valve travel

    Packing friction and Hysteresis

    Static and sliding friction Dead band

    The following types of diagnostics shouldbe provided:

    Public Diagnostics:Output device diagnostics that are viewablefrom any process control host. They help

    determine common problems with valve,actuator, and host.

    Advanced Diagnostics:Full output device diagnostics thatdetermine output device health withoutremoving it from the line. Advanceddiagnostics come in two forms dynamicscan and step scan. Dynamic scan (onlineor offline method): cycles output device andin one test collects all parameters for drivesignal, dynamic error band, output signal,and output device signature. Step scan(online or offline method): test moves

    output device in unique patterns, which helpexamine devices action in specific areas oftravel. This action shall be passwordprotected and require approval of a processoperator before implementation.

    Process Diagnostics:Test that is run as the process is running.This test moves output device within arange until the process exceeds itsconfigured maximum deviation. It allows

    maintenance personnel to compare hostaction, actuator action, output deviceaction, and process action.

    Process diagnostics helps determines thefollowing:

    Is the output device sticking? Howmuch? Where?

    Is the output device controlling theprocess for small variations?

    Is the output device properly sized?

    4.3 Field Device PowerFieldbus devices may be powered eitherfrom the segment (bus), or locally powered,depending on the device design. If at allpossible field devices should be buspowered.

  • 8/6/2019 Engineering Guide Comments

    27/101

    Revision 0 - 19 - October 2003

    Commentary:Bus-powered devices typically require 10-30 mA of current at between 9 and 32 volts.

    Devices should strive for minimum powerconsumption, without negatively impactingdesired functionality.

    4.3.1 PolarityFieldbus devices communication signalshall be polarity insensitive.

    Commentary:Some older FF devices were polarity

    sensitive and if installed incorrectly couldcause network problems.

    4.3.2 2-WireField devices shall be loop powered fromthe host control system. Fieldbus devicesshall work with voltages of 932 VDC.

    Commentary:The 9 VDC specified is a minimum: it ishighly desirable that a margin of at least 1 V

    (i.e. a minimum of 10 VDC) be maintainedat the field end of the bus. Some devices donot conform to FF standards and require 11volts to operate. Any segment designed tooperate below 15V normally should carry awarning about additional loads in thesegment documentation. Minimum segmentvoltage should always be shown in thenetwork/segment documentation.

    4.3.3 4-WireExternally powered devices (e.g. 4-wiredevices) with FOUNDATION fieldbus shouldhave isolation between external power andFieldbus signal inputs.

    4.3.4 Short-circuit ProtectionDevices should work with 60 mA currentlimiting short-circuit protection though a limitof 40 mA is preferred.

    Commentary:For practical purposes this means alldevices shall draw no more than 50 mA

    since approximately 10 mA is needed toactivate the short-circuit protection circuitry.

    4.4 Service ConditionsSpecific Fieldbus conditions should notrelax any device requirements specified inother corporate specifications related tosensor or component selection.

    4.4.1 GeneralThe equipment shall be designed to

    withstand vibration forces of up to 1.0 gover the range of 5 to 100 Hz, and for a5 msec duration a vibration force of 4.0 gover the same range. Networks, Data, I/Ohighways are required to have an approvedtype of electrical isolation at the point ofconnection to the Host System hardware,Fieldbus junction box, and the fieldinstrument.

    4.4.3 Electrical Certification (Hazardous

    Area Classification)All devices shall be certified by a nationalrecognized testing laboratory and labeledfor Area classification (Zone or Division)where they will be installed.

    4.5 Logical Field DevicesA Fieldbus device is divided into two ormore Logical Field Devices, each of whichis called a Virtual Field Device (VFD).These Logical Field Devices are:

    The Management VFD containing thedevices physical and resource data.Resource data includes the VirtualCommunication Resources (VCRs).

    One of more Function BlockApplication Processes (FBAP VFD).

    Each device has a set number of VCRs asdoes each host system and each publish/

  • 8/6/2019 Engineering Guide Comments

    28/101

    Revision 0 - 20 - October 2003

    subscribe relationship link to another deviceor the host consumes one VCR. It istherefore important to be aware of the VCR

    availability in a device. Refer to Section8.6.6 for more information on VCRs.

    4.6 Factory ConfigurationInternal software of fieldbus instrumentsshould be configured by the manufacturer,including at least the following information:

    Serial number

    Tag name

    Process use description

  • 8/6/2019 Engineering Guide Comments

    29/101

    Revision 0 -21- October 2003

    5.1 Bulk Power Supplies

    5.1.1 The 24 VDC bulk power supplies

    shall be redundant.

    Commentary:FFPS require an input voltage of 2035VDC. Unless an appropriate DC bus existsin the plant, the BPS provides the powerconversion from 240/120 VAC to 24 VDC.

    Bus Power after conditioning is oftenapproximately 19 VDC.

    5.1.2 Two separate, independent, powercircuits should source power the BulkSupply. The Bulk Supply can be fed fromUPS power or the bulk supply can includebattery backup.

    5.1.3 Overcurrent protection shall beprovided for each feed supplying power toFF power conditioners.

    5.1.4 The negative leg of the Bulk Supplyshall be grounded.

    5.1.5 The Bulk Supply may be eitherdedicated solely to the fieldbus network orshared between the fieldbus network andconventional I/O.

    5.1.6 If the site has an existing powersupply for conventional 4-20 mAinstrumentation, this power supply may beused to supply the FFPSs. The availablespare capacity of the power supplies shall

    be verified to meet the FFPS demands. TheEnd User representative shall approve, inwriting, the use of the existing powersupply.

    5.2 FOUNDATION fieldbus Power Supply/Conditioner (FFPS)

    5.2.1 One (1) Fieldbus PowerSupply/Conditioner is required for eachfieldbus network/segment.

    Commentary:If an ordinary power supply were to be usedto power the Fieldbus, the power supplywould absorb signals on the cable becauseit would try to maintain a constant voltagelevel. For this reason, an ordinary powersupply has to be conditioned for Fieldbus.Putting an inductor between the powersupply and the Fieldbus wiring is a way toisolate the Fieldbus signal from the low

    impedance of the bulk supply. The inductorlets the DC power on the wiring but

    prevents signals from going into the powersupply.

    In practice, a real inductor is not used.Inductors cause undesirable ringing onFieldbus segments. The electronic circuit

    provides isolation of the Fieldbus circuitsfrom ground, current limiting to the segmentif the cable is shorted, and a high

    impedance for the Fieldbus signals.

    5.2.2 Fieldbus Power Supplies/Conditioners should be redundant, loadsharing, and output current limited.

    5.2.3 FF Power Conditioners shouldprovide impedance matching required forFF signals.

    5.2.4 Fieldbus PowerSupplies/Conditioners should be poweredfrom the primary and secondary(redundant) bulk power supplies. Thesemay be linked primary-to-primary andsecondary to secondary if desired.

    5.2.5 FF Power Conditioners units may beconnected together with common BulkPower Supply feeds, and common alarms.No more than eight (8) FF Power

  • 8/6/2019 Engineering Guide Comments

    30/101

    Revision 0 -22- October 2003

    conditioners units may be connectedtogether. The primary and secondary BulkSupply can feed both ends of the

    connected FF Power conditioners.

    Commentary:Some manufacturers redundant powersupplies (FFPS) can be ordered with pre-made wiring jumpers. The jumpers areused to efficiently distribute power and toseries alarm to multiple (connected) FFPSunits. In this way, a number of redundantFFPS may be fed from two primary and twosecondary BPS feeds.

    5.2.6 Failure or faults in any of theredundant FF Power conditioners shall beannunciated in the host system. A commonalarm for all FF Power conditioners in asingle cabinet may be used.

    5.3 FOUNDATION fieldbus Terminators

    5.3.1 Each fieldbus segment must haveexactly two terminators. The wiring between

    the two terminators is defined as the trunk.

    5.3.2 It is recommended that allterminators located in the field should beinstalled in a junction box; no terminatorsare to be installed in the FF devices.

    Commentary:When a signal travels on a cable andencounters a discontinuity, such as an opencircuit or short, it produces a reflection. The

    portion of the signal that echoes from the

    discontinuity travels in the oppositedirection. The reflection is a form of noisethat distorts the signal. A terminator is usedto prevent a reflection at the ends of afieldbus cable. A fieldbus terminatorconsists of a 1F capacitor in series with a100 Ohm resistor. Some of the wiringcomponents previously discussed mayhave terminators built into them, (e.g.

    FFPS). These terminators may bepermanently installed, turned on or off usinga dipswitch, or placed into use by a wiring

    jumper. The terminator on an H1 segmentserves as a current shunt.

    The following figure is for information onlyto show schematically the electricalequivalence of a terminator. Users shouldNOTfabricate their own terminators as perthis diagram.

    Figure 5.1 - Fieldbus Terminating Electrical Circuit

    5.4 FOUNDATION fieldbus Repeaters

    5.4.1 Repeaters replace one of the fielddevices in the network count, allowing theaddition of the equivalent of an entire newsegment by effectively splitting the networkinto a number of smaller segments.

    5.4.2 By adding a repeater, a new segmentcan be connected and terminators arerequired on each end of this new segment.

    5.4.3 Repeaters also provide the capabilityto increase the number of devices on anetwork to a maximum of 240 devices.

    Commentary:The host system and network schedule limitwill likely be exceeded before the physicalmaximum number of devices is reached.

  • 8/6/2019 Engineering Guide Comments

    31/101

    Revision 0 -23- October 2003

    5.4.4 When Fieldbus Repeaters are usedthe Principal engineer is to be informed andit is to be clearly marked on the associated

    network drawing.

    Typical uses:If a segment (network) needs to extendfurther than the 1900 meter lengthconstraint, then a repeater may beconsidered. The repeated segment designmust be reviewed and approved in writingfrom the Principal.

    The most common use of repeaters is not

    to get longer distance, but to join ISsegments together. Because an entitybarrier only supports 3-4 devices manybarriers are needed on a network to getloading of 16 devices per network.

    Commentary:In the cases where it is economically

    justified, a repeater may be considered toextend the total segment length. This wouldtypically be in cases where the H1 interface

    card cannot be located relatively close tothe process, (e.g. flare systems).

    Repeaters clean up the signal, by boostingit, re-timing it, and thereby improving thereliability of the communications. A repeatercan be used in cases with wire less than1900 m to improve network robustness.

    5.5 FOUNDATION fieldbus WireFF wire is discussed in Section 6.2. Referalso to Section 6.3.7.

    5.6 FOUNDATION fieldbus Junction BoxesIt is recommended that all trunk and spurconnections in the field junction boxes,including pass-through trunk pairs withoutspurs, be terminated on wiring blocksspecifically made for FOUNDATION fieldbusnetworks. An alternate connection may beprovided by weatherproof molded bricks

    that can be used without a junction box withfactory molded plug connectors.

    Commentary:Fieldbus supports the use of traditionalterminal blocks though the User must beaware that the wiring of all devices to thenetwork is done via parallel connections.

    The wiring block/Junction Box or Brickshould meet the following requirements:

    Two (2) dedicated connections for theFieldbus homerun/trunk cable.

    Integral short-circuit protector for spurconnections, maximum current to spuris limited by the area classification andcurrent available to the network. Spurcircuits shall have a non-incendiverating.

    Commentary:The short-circuit protector can be aconnected to the terminating block at thehomerun or main network cable.

    Pluggable (removable) trunk andspur connectors.

    An indicator for each spur connectionindicating when a spur is shorted andis in overcurrent mode.

    Indication when bus power isavailable.

    Electrical regulatory (e.g. CSA or FM)approved for Ex n; Class I, Division 2,Groups B, C, D or Zone 2, IIA, IIB, IIC.

    Wire capacity: 12-24 AWG. Temperature range: -45 to +70C.

    DIN rail mounting (terminal blocks).

    Available in four (4) spur, six (6) spurand eight (8) spur configurations.

  • 8/6/2019 Engineering Guide Comments

    32/101

    Revision 0 -24- October 2003

    Exception:Inactive spare Fieldbus trunk pairs may beterminated on conventional terminal blocks,

    per End User standards.

    Commentary:Wiring Blocks with integral short-circuit

    protectors will prevent a fault (short-circuit)in the device or spur cable run frombringing the entire FF segment down.Typically an additional 10mA load is addedwhen this spur is short-circuited.

    The system design should be well under-

    stood before the network and individualsegment design is started. The P&IDs,Instrument Location drawings and PlotPlans are needed to effectively designfieldbus segments.

    Commentary:Prior to defining Fieldbus segments, the

    process control strategy should becomplete, the P&IDs available, andinstruments selected with locations

    determined. This is a necessary conditionto allow for the design of control in the field,which requires all devices for the loop to be

    part of the same network/segment.

  • 8/6/2019 Engineering Guide Comments

    33/101

    Revision 0 -25- October 2003

    6.1 FOUNDATION fieldbusNetwork/Segment TopologyThe fieldbus installation shall use the Tree,

    Spur or Combination topology. Do not usethe daisy chain topology.

    Commentary:Components of fieldbus segments can beconnected together in various topologies.The topology selected is usually, though notalways1 driven by the physical devicelocation in order to reduce installation costs.Hence, control narratives and plot plans areused in addition to P&ID's and instrument

    indexes in the design of a fieldbus segment.

    Spur connections shall be connected tocurrent limiting connections to the bus toprovide short-circuit protection and toprovide the ability to work on field deviceswithout a hot work permit. This currentlimiting connection should provide a non-incendive or intrinsically safe connection tothe field device.

    Commentary:The drops and current limiting can beprovided by terminal blocks in junctionboxes or by bricks that are field-mounted.

    The connection from the marshallingcabinet/host to the first junction box in thefield for the topologies shown in 6.1.2,6.1.3, and 6.1.4 are often provided by amulti-pair, individually shielded cable of thesame type (ITC) and wire gauge used forthe individual network and spur wires.

    6.1.1 Point-to-Point TopologyThis topology consists of a network havingonly two devices. The network could beentirely in the field (e.g. a transmitter and

    1

    The desire to implement control in the field will drivethe need to connect all the devices for the affectedloop to reside on the same segment.

    valve, with no connection beyond the two)or it could be a field device connected to ahost system (doing control or monitoring).

    This topology is illustrated below andshould not be used. It is not an economicdesign except as listed below.

    Figure 6.1 Example of Point-to-Point Topology

    Commentary:Until such time as the FOUNDATIONfieldbusfor Safety specification is complete, this isthe only way in which a user may wish toself-certify and apply Fieldbus technology ina safety application.

    6.1.2 Tree Topology (Chicken Foot)

    This topology consists of a single fieldbussegment connected to a common junctionbox to form a network. This topology can beused at the end of a home run cable. It ispractical if the devices on the samesegment are well separated but in thegeneral area of the junction box. Whenusing this topology, the maximum spurlengths must be considered. Maximum spurlengths are discussed in 6.2.4. Thistopology is illustrated below in figure 6.2.

    Figure 6.2 Example of Tree (Chickens Foot) Topology

  • 8/6/2019 Engineering Guide Comments

    34/101

    Revision 0 -26- October 2003

    This is the preferred topology to be used forreuse of existing wiring, as it is most similarto the conventional installation and will

    therefore provide the optimal use of existinginfrastructure.

    Tree branch topology should be used forthe following situations:

    Retrofit installations

    High density of fieldbus devices in aparticular area

    High Speed Ethernet (HSE) is beingused

    This topology also allows maximumflexibility when configuring and assigningdevices to networks/segments.

    6.1.3 Spur TopologyThis topology consists of fieldbus devicesthat are connected to a multi-drop bussegment through a length of cable called aspur. This technology is technicallyacceptable but not generally a good

    economic choice.

    Figure 6.3 Example of Spur Topology

    Bus with spur topology should be used innew installations that have a low density ofdevices in an area. Spurs shall be

    connected to current-limiting connections(30 mA, or as appropriate for the device ona particular spur) to the bus as this providesShort-circuit protection.

    6.1.4 Combination Topology:Combinations of the above topologies mustfollow all the rules for maximum fieldbusnetwork/segment length, and include the

    length of spurs in the total lengthcalculation. These types of topologies arepreferred for designs using bricks with tray

    cable. Spurs are permitted to extend onlyfrom trunk lines and not from other spurlines.

    Figure 6.4 Example of Combination Topology

    6.1.5 Daisy Chain TopologyThis topology consists of a network/segment that is routed from device todevice, and is connected at the terminals ofthe fieldbus device. This topology isillustrated below in figure 6.5. This topologyshould not be used, as it is unacceptablefor maintenance purposes.

    Commentary:The daisy chain topology is not usedbecause devices cannot be added orremoved from a network/segment duringoperation without disrupting service to otherdevices. Similarly, failure of one device willimpact all other devices downstream ofthe failed field device.

    Figure 6.5 Example of Daisy Chain Topology

  • 8/6/2019 Engineering Guide Comments

    35/101

    Revision 0 -27- October 2003

    6.2 FOUNDATION fieldbus Wiring

    6.2.1 Cable Types

    For new installations or to get maximumperformance for a FOUNDATION fieldbusNetwork, individually shielded twisted-pairoverall screened cable designed especiallyfor FOUNDATION fieldbus may be used.However, specially designed FF cable doesnot always provide significant benefits overstandard tray cable that is available at amore attractive price.

    Commentary:

    Twisted pair wire is used rather than a pairof parallel wires to reduce external noisefrom getting onto the wires. A shield overthe twisted pairs further reduces noisesusceptibility.

    Wire Size18 GA (0.8 mm2)

    Shield

    90% coverage

    Attenuation 3 db/km at 39 kHz

    MaximumCapacitance

    150 pF/m

    CharacteristicImpedance

    100 Ohms +/- 20%at 31.25 kHz

    Table 6.1 Typical FF cable characteristics per IECPhysical Layer Standard

    Type Meters / Feet ImpedanceOhms

    Resistivity Attenuation (db/km)

    Description

    A 1900 / 6270 100 22 3 Individual shielded pairs

    B 1200 / 3960 100 56 5 Multiple pairs with overallshield

    C 400 /1320 Unknown 132 8 Multiple pairs with no shield

    D 200 / 660 Unknown 20 8 Multiconductor, no pairing

    Table 6.2 Fieldbus Cable Specifications

    If the project is not using one of the cabletypes specified above, the cable should be

    tested before it is installed with inducedFieldbus signals at the anticipatedmaximum length plus 25%. Tests shallinclude signal captures at the Power Supplyoutlet, as well as at the remote end of thecable.

    Cables for FF installations shall be labeledType ITC (16 Gauge) and shall be installedin tray or conduit. All cables shall be single

    or multiple twisted pair with an individualshield for each pair. Multi-pair cables shallhave an additional overall shield.

    Fieldbus cable is to be unique in color andcan be easily distinguished fromconventional 420 mA cable.

  • 8/6/2019 Engineering Guide Comments

    36/101

    Revision 0 -28- October 2003

    Commentary:Facilities will continue to have 420 mAsignals for some time as fieldbus

    technology develops, hence the advantageof having the cable differentiated. Thisdifferentiation can be at the cable ends onlythrough the use of lugs or colored heatshrink markers.

    Fieldbus signals and 4-20 mA signals maybe run together in multiconductor cables

    provided each wire pair is individuallyshielded. This may be convenient when itis necessary to install a conventional

    instrument in the field until such time as aFieldbus version of the device becomesavailable. Once the Fieldbus device isavailable it is possible to swing the deviceover to the Fieldbus Network in the FieldJunction box.

    Cables shall have thermoplastic elastomer(TPE) flame-retardant insulation andcomply with color conventions andpolarities of existing facility. Cable should

    be as follows: Suitable for the electrical area

    classification

    Suitable for outdoor use in cable trays

    Cable jacket shall be flame-retardant poly-vinyl chloride (PVC).

    6.2.2 Distance ConstraintsThe maximum allowed length of a fieldbussegment is 1900 meters (6232 ft.) except

    where repeaters are installed. This totalsegment length is computed by adding thelength of the main trunk line and all thespurs that extend from it.

    Total Segment Length = Trunk + All Spurs

    Commentary:The maximum length given is specified inthe ISA 50.02 Fieldbus standard. From field

    experience these lengths have been foundto be conservative. As stated in thisspecification, the length of a segment islimited by voltage drop and signal quality(i.e. attenuation and distortion). As the EndUser gains field experience these lengthlimits may be revised to reflect real worldexperience. See 6.7.4 for furtherinformation on signal attenuation limits tosegment length.

    6.2.3 Homerun Cable (Trunk)Either prefabricated molded cables orindustry standard 16 AWG multi-pair,individually shielded cable for analogsignals shall be used for all trunk wiring.Cable routing should conform to siteEngineering Specifications. Runs parallel tohigh power cables should be minimized,and adequate spacing and shielding shouldbe employed.

    Ten percent (10%) spare pairs should beprovided for all muiltipair Fieldbus segmenttrunk cables, with a minimum of one sparepair. This requirement includes spares ontrunk cable runs between marshalling racksand junction boxes, and between junctionboxes.

    Commentary:The decision to use multi-pair or single pairtrunk cabling depends on the number of

    networks/segments installed in the fieldarea. Typically, the trunk cable will be amulti-pair cable if more than onenetwork/segment is required in the area orthe network/segment in the area would beloaded to maximum. Facilities may havetheir own rules relative to spare capacityrequirements upon completion of a project.This is suggested as a guideline in caseswhere a standard has not been established.

  • 8/6/2019 Engineering Guide Comments

    37/101

    Revision 0 -29- October 2003

    6.2.3.1 When installing FOUNDATIONfieldbus in a Brownfield Facility, the existinghomerun cables shall be tested for

    suitability for reuse. This test can be doneusing the Relcom FBT-3 and FBT-5 cabletesting tools.

    Commentary:At present these are the only known simplehandheld test products available for thisservice.

    6.2.4 SpursA spur can vary in length from 1 meter to

    200 meters (656 ft.). A spur that is less than1 meter is considered a splice.

    Commentary:A spur that is less than two hundred (200)meters is negligible as a transmission lineand can accurately be modeled as anequivalent capacitor. Note: quarter-wavelength at H1 frequencies is in excessof 2 kilometers. The spur length allowancesgiven in this document are considerably

    more generous than allowed by the FFwiring guide provided by Relcom; however,these allowances are based ontransmission line theory, lab tests, and fieldinstallation experience. Strictly following theoriginal ISA 50 wiring guide can placeunnecessary and costly restrictions on FFfield wiring.

    Only one (1) FOUNDATION fieldbus deviceshall be connected to each spur.

    Commentary:Since a short-circuit protection wiring blockis being used, the segment design is limitedto one (1) device per spur.

    The maximum spur length shall be 200meters (656 ft.). The spur length is thelength of the cable from the wiring block tothe FF device.

    Commentary:A spur is a drop-off of the main trunk line.The trunk is considered to be the main

    cable run and will contain segmentterminators at each end.

    While un-terminated spur lengths up to 200meters are allowed, any spur over 100meters (328 ft.) requires Principal approval.The intent of the selected multi-drop buswiring method is to eliminate the need forlong spur lengths and to keep spurs underthe recommended length of 30 meters(98 ft.) or less. Longer spurs may be

    needed to keep the bus out of high-riskareas.

    6.3 FOUNDATION Fieldbus Power,Grounding & Lightning Protection

    6.3.1 PowerFieldbus devices may be powered eitherfrom the segment (bus), or locally powered,depending on the device design.

    Commentary:Bus-powered devices typically require 10-30 mA of current at between 9 and 32 volts.

    Any network/segment designed to operatebelow 15V normally should carry a warningabout additional loads in the networkdocumentation. Minimum network/segmentvoltage should always be shown in thenetwork documentation.

    The total current draw from all devices onthe network must not exceed the rating ofthe FOUNDATION fieldbus Power Supply.The network/segment design must take intoaccount:

    Total device quiescent current draw

    One spur short-circuit fault (i.e. ~10mA additional current draw)

    25% additional current load above thetwo (2) previous requirements

  • 8/6/2019 Engineering Guide Comments

    38/101

    Revision 0 -30- October 2003

    The number of bus-powered (two-wire)devices on a segment is limited by thefollowing factors:

    Output voltage of the FOUNDATIONfieldbus Power Supply.

    Current consumption of each device.

    Location of device on the network/segment, (i.e. voltage drop).

    Location of the FOUNDATION fieldbusPower Supply.

    Resistance of each section of cable,(i.e. cable type).

    Minimum operating voltage of eachdevice.

    Additional current consumption due toone spur short-circuit fault, ~10 mA.

    Commentary:The length of a fieldbus wiring system andthe number of devices on a network/segment are limited by power distribution,attenuation and signal distortion. ISA 50.02estimates how long a fieldbus cable can be

    and still have adequate signal quality, (i.e.acceptable attenuation and distortionCalculating power distribution for anetwork/segment is relatively simple andcan be easily performed.

    The number of devices on a network mustalso consider the Device Criticality tomanage the risk associated with a potentialsingle point failure. Refer to Section 6.4below.

    6.3.2 PolarityWiring polarity shall be maintainedthroughout the segment design andinstallation.

    Commentary:Wiring polarity is critical because someFieldbus devices are polarity sensitive.

    Wired with the wrong polarity, a device maynot operate.

    6.3.3 GroundingThe instrument signal conductors must notbe used as a ground. Instrument safetygrounds must be made through a separateconductor outside of the signal cable.Fieldbus devices shall not connect eitherconductor of the twisted pair to ground atany point in the network. The Fieldbussignals are applied and preserveddifferentially throughout the network.

    An alternate method of grounding that is

    applied in Europe is represented in thefigure 6.6.

    Segment Termination

    PowerSupply

    UnitorFF

    Interface

    100

    1.0 F

    FieldDevice

    100

    1.0 F

    Practice to avoidbuild-up of DCand reduce EMI

    Figure 6.6 Alternate Segment Termination

    Network cable shield shall be earthed/grounded in one location only, at the fieldtermination assembly (host) end. At a fieldinstrument, cable shield shall not beconnected to the instrument earth/ground or

    chassis.

    CommentaryThis is consistent with the practiceemployed for conventional instrumentationsystems. Shielding over the twisted pairwires is to keep out noise that mightinterfere with the signals.

  • 8/6/2019 Engineering Guide Comments

    39/101

    Revision 0 -31- October 2003

    Instrument signal conductors shall not beused as an earth/ground. If an instrumentsafety earth/ground is required, it shall be

    made through a separate conductor. Theconductor may be in the same cable as theinstrument signal conductors and shield,but shall be located outside the shieldwithin this cable.

    Fieldbus devices should not connect eitherconductor of the twisted pair to earth/ground at any point in the network.

    Commentary:

    The earthing/grounding of either fieldbusconductor would be expected to cause alldevices on that bus network/segment tolose communications for the period that theconductor is earthed/grounded.

    6.3.4 ShieldingThe instrument shield shall be terminated atthe host (power conditioner) end of thenetwork in the marshalling cabinet and shallnot be connected to ground at any other

    place. If a multiple home run cable goes toa field junction box, do not attach the cableshield wires from different networkstogether. This creates ground loops andnoise onto the network.

    6.3.5 Lightning/Surge ProtectionWhere surge protection is deemednecessary (e.g. areas of high lightningincidence, or where large inductive loadsare started and stopped), surge protectionshould be provided. This surge suppressionshall consist of low-capacitance siliconavalanche diodes or spark gaps, wired forboth normal- and common-mode protection,connected to the electrical safety groundgrid. Typical installations will be on fielddevices installed in tank farms or on top ofdistillation columns.

    It is vitally important that the surgesuppression device does not measurablyattenuate the Fieldbus signal.

    Commentary:The expected surge values on signalconductors within shields, provided that thegrounding practice for shields is followed,should be low. A surge rating of 1 kA for an8/20S wave shape should be adequate.

    Avalanche diodes generally fail to short-circuit. Where this is a concern, the surgesuppression devices may be connected via

    a series fuse.

    6.3.6 TerminatorsAll terminators located in the field shall beinstalled in a junction box. Terminatorsshould not be installed in the Fieldbusdevices.

    Commentary:A cable signal encountering a discontinuity,such as a wire open or short, produces a

    reflection. The reflection is a form of noisethat distorts the original signal. Aterminator, consisting of a capacitor inseries with a resistor, is used at the ends ofa Fieldbus cable, to prevent a reflection.

    6.3.7 Repeaters

    Commentary:Repeaters replace one of the field devicesin the physical device count, allowing theaddition of the equivalent of an entire new

    segment. By adding a repeater, a newsegment is created. Repeaters can be usedto split a network into smaller segments.

    If a repeater is added to the network, a newsegment is connected, and the followingshould apply:

  • 8/6/2019 Engineering Guide Comments

    40/101

    Revision 0 -32- October 2003

    The newly created segment should haveterminators at both ends. Repeatersshould be considered as a field device in

    the physical device count. The number ofdevices on the network may be increasedto the maximum determined by the fieldbus type.

    Note: The host system and networkschedule limit will likely be exceeded longbefore the physical maximum number ofdevices is reached.

    Using barriers with built-in repeaters one

    gets four (4) devices per barrier and therepeater function permits four (4)hazardous area segments to be joined toform a network of sixteen (16) devicesgoing to the host.

    Actual number of devices may vary,depending on fieldbus type, type of powersupply, and power consumption of the fielddevice itself.

    Power supplies shall comply withIEC 61158-2 criteria and performancerequirements, with preferentialconsideration given to the low-powersignaling option.

    Power conditioners should be redundantunits that provide flawless transfer fromone unit to the other. Primary andsecondary sources shall be physicallyseparated, not sharing a commonbackplane or AC source. Power supply maybe connected anywhere on a bus network/segment.

    In practice, power supply will probably bean integral element of the host controlsystems manufacturer.

    6.4 FOUNDATION fieldbus Segment RiskManagementEach end user facility shall identify and

    document a risk assessment philosophy(method) by which Fieldbus devices areassigned to network/segments.

    Existing plant risk area or card loadingmethods in place may be used. Thephilosophy shall consider network/segmentsegregation, multiple segments per H1 port,etc. The risk assessment ranking should beclearly shown on the network/segmentdrawings. Topology design should minimize

    single points of failure.

    The following valve criticality rating andnetwork/segment loading method should beused. The valve and associated measure-ment criticality shall be defined for prudentloading of Fieldbus segments. The followingratings should be assigned to each valveand segment.

    Commentary:

    The design restrictions are intended tominimize the effect of human error andinteroperability problems from affecting

    plant reliability. The intent of Level 1 and 2designs is to keep the number and varietyof devices on a ne