Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
TOLL 877 743-2762 FREE
Shear Transfer Systems, Inc. 9845 Santa Fe Ave East, Hesperia, CA 92345
www.shearmax.com
760-949-4191 phone 760-948-5330 fax
2015 IBC 2016 CBC
2017 LABC
ICC-ES ESR-1727
ENGINEER AND ARCHITECT REFERENCE GUIDE TO
ICC-ES ESR 1727
FRONT COVER
1. PANEL CONFIGURATIONS 2. PORTAL PANEL 78” & 90” VALUES 3. STANDARD PANELS 8’ to 11’ VALUES 4. STANDARD PANELS 12’ to 15’ VALUES 5. STANDARD PANELS 16’ to 19’ VALUES 6. STANDARD PANELS 20’ & NOTES 7. ALTERNATIVES FOR MORE LOAD 8. WIND LOADS 9. COMPRESSION LOADS POSTS 10. COMPRESSION LOADS PANEL 11. PANEL SPECIFYING 12. DETAILS 2012 IBC SM1 13. DETAILS 2012 IBC SM2 14. DETAILS 2012 IBC SM3 BACK COVER
ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR ALL-INCLUSIVE DETAILS AND USAGE.
SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016
SHEARMAX PANEL TYPES AND OPTIONS (REFERENCE FIGURE 2 & 3) (Wa = Wn – 3”) PANEL ASPECT RATIO = Ha / Wa = αp
PAGE 1
ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION November 01, 2008
OUT-OF-PLANE AND COMPRESSION LOADS MUST BE CHECKED. The Project Engineer/Governing Agencies may use their discretion/engineering judgment regarding post bracing. The accompanying color-codes designate recommended post options (found throughout this guide) for post sections not fully braced by other methods. Recommendations are based upon full compression load on post(s) from in-plane racking shear and/or load on post(s) from typical out-of-plane wind loads. Post sections may need to be braced or increased for other conditions.
POST OPTIONS ARE DESIGNED TO INCREASE THE STANDARD POST CROSS SECTION OF A STANDARD SHEARMAX PANEL AND INCREASE THE CAPACITY OF THE POST FOR COMPRESSION LOADING AND/OR OUT OF PLANE LOADING. SEE PAGE 6 FIGURE 3 FOR MORE INFORMATION.
RECOMMENDED OPTIONS
STD NO OPTION
OPTIONS RARELY REQUIRED 6-10 ft (Not Shown)
STD 2x4 OPTION
2x4 NAIL-ON OPTION RECOMMENDED - 10-11 ft
STD 2x6 OPTION
2x6 NAIL-ON OPTION RECOMMENDED - 11-14 ft
EC6 OPTION
EC6 OPTION RECOMMENDED 14-17 ft
EC8 OPTION
EC8 OPTION RECOMMENDED 17-20 ft
STD 2x4 OPTION STD 2X6 OPTION EC6 OPTION EC8 OPTION NAIL-ON NAIL-ON
FIELD MODIFIED BY OTHERS FACTORY ATTACHED
NOMINAL GARAGE DOOR HEIGHT
7’ GARAGE DOOR 6” CURB
8’ GARAGE DOOR 6” CURB
SHEARMAX PORTAL PANELS: REFERENCE TABLE 1 ‘PORTAL’ panels are sized for garage doors heights of 7’ & 8’ when used with a 6” stem wall.
Any SHEARMAX panel may be used in a portal or non-portal condition without a change in load capacity. The allowable loads for Portal Panels do not use a moment connection between the top of panel and the supported header. All SHEARMAX
panels have ‘stand alone’ values. Portal reductions required by agencies such as L.A. City or L.A. County are not required. PANEL DIMENSIONS ALLOWABLE IN-PLANE SHEAR LOAD AND DRIFT
2015 IBC Seismic (R=6.5) 2015 IBC Wind SHEAR (Lbs.) SHEAR (Lbs.)
SHEAR-MAX
MODEL THICK-NESS
WIDTH NOMINAL
ACTUAL HEIGHT
LBS / FT TOTAL DRIFT (IN.)
LBS / FT TOTAL DRIFT (IN.)
SM16-78 16'' 990 1320 0.37 1275 1700 0.53 SM18-78 18’’ 1100 1650 0.36 1425 2135 0.53 SM21-78 21'' 1230 2155 0.35 1565 2735 0.52 SM24-78 24'' 1065 2125 0.28 1330 2655 0.40 SM28-78 28'' 1085 2530 0.25 1355 3165 0.36 SM32-78 32'' 1100 2935 0.23 1375 3670 0.34 SM36-78 36'' 1115 3340 0.22 1390 4175 0.32 SM42-78 42'' 1130 3950 0.22 1410 4935 0.31 SM48-78
3 ½”
48''
6'-6" (78")
S T D
S T D
1140 4555 0.21
S T D
S T D
1425 5695 0.31 SM16-90 16'' 815 1085 0.42 1050 1400 0.60 SM18-90 18'' 910 1365 0.41 1180 1770 0.60 SM21-90 21'' 1030 1805 0.40 1345 2350 0.60 SM24-90 24'' 1065 2125 0.37 1330 2655 0.53 SM28-90 28'' 1085 2530 0.33 1355 3165 0.47 SM32-90 32'' 1100 2935 0.30 1375 3670 0.43 SM36-90 36'' 1115 3340 0.28 1390 4175 0.41 SM42-90 42'' 1130 3950 0.26 1410 4935 0.38 SM48-90
3 ½”
48''
7’-6" (90")
S T D
S T D 1140 4555 0.25
S T D
S T D 1425 5695 0.37
- Hold-down Anchor tension load = 9,500 Lbs. - Alternate tension loads may be calculated based on (Vall or Vdesign) x αP. - Wood post to wood post width (minus hold-downs) is 3 in. less than nominal width dimension. - For increased out-of-plane loads and/or vertical loads Refer to Figure 3 (page 6) for Alternate Panel Options. - For custom height load values round up to next foot, or call for exact value
PANEL MODEL DESIGNATIONS: REFERENCE FIGURE 1 (for all panels)
SM XX - YY — CUSTOM HT — TF — EC(6 or 8) (CUSTOM OPTION CODES)
SM SHEARMAX PRODUCT IDENTIFIER XX NOMINAL OVERALL WIDTH (in.)—Outside-to-Outside of hold-downs YY HEIGHT (Feet or Inches)—Nominal Panel Height - when specified in ‘Feet’
Actual Panel Height - when specified in ‘Inches’
CUSTOM HT CUSTOM HEIGHT—Panel Heights not listed in Table 2. Net Height may be specified.
TF TRIM-FIT (TF) PANEL—Short point height required. 3:12 Maximum Slope
EC6 FACTORY ENHANCED CROSS-SECTION—EC6 (5-in net thickness) EC8 FACTORY ENHANCED CROSS-SECTION—EC8 (7 ½-in net thickness)
Example – SM 24 – 10 SHEARMAX 24” WIDE – 10’ NOMINAL WALL OR PANEL HEIGHT (9’ 9 ¾” NET PANEL HEIGHT)
Example – SM 24 - 175 ¾” – TF – EC6 or SM 24 – 15 (175 ¾”) – TF – EC6 SHEARMAX 24” WIDE – CUSTOM OPTIONS: NET HEIGHT 175 ¾” – TRIM FIT (175 ¾” SHORT POINT) – EC6 OPTION
PAGE 2 ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES
REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016
NOMIMAL HEIGHT
8’ 9’ 10’
11’
SHEARMAX STANDARD & TRIM-FIT PANELS – 8’ to 11’: REFERENCE TABLE 2 PANEL DIMENSIONS ALLOWABLE IN-PLANE SHEAR LOAD AND DRIFT
2015 IBC Seismic (R=6.5) 2015 IBC Wind SHEAR (Lbs.) SHEAR (Lbs.)
SHEAR-MAX
MODEL THICK-NESS
WIDTH NOMINAL
ACTUAL HEIGHT
LBS / FT TOTAL DRIFT (IN.) LBS / FT TOTAL
DRIFT (IN.)
SM16-8 16” 695 925 0.38 875 1165 0.52 SM18-8 18” 785 1175 0.38 995 1490 0.52 SM21-8 21” 895 1565 0.37 1140 1995 0.52 SM24-8 24” 985 1970 0.36 1265 2525 0.52 SM28-8 28” 1080 2520 0.35 1355 3165 0.51 SM32-8 32” 1100 2935 0.32 1375 3670 0.47 SM36-8 36” 1115 3340 0.30 1390 4175 0.44 SM42-8 42” 1130 3950 0.28 1410 4935 0.41 SM48-8
3 ½”
48”
7'-9 ¾” (93 ¾”)
S T D
S T D
1140 4555 0.27
S T D
S T D
1425 5695 0.39 SM16-9 16” 595 790 0.43 745 990 0.59 SM18-9 18” 670 1005 0.43 845 1270 0.59 SM21-9 21” 770 1350 0.42 985 1720 0.59 SM24-9 24” 855 1710 0.41 1095 2190 0.59 SM28-9 28” 945 2200 0.40 1200 2805 0.59 SM32-9 32” 975 2600 0.37 1220 3250 0.53 SM36-9 36” 985 2960 0.34 1235 3700 0.49 SM42-9 42” 1000 3500 0.31 1250 4375 0.45 SM48-9
3 ½”
48”
8’-9 ¾” (105 ¾”)
S T D
S T D
1010 4035 0.29
S T D
S T D
1260 5045 0.43 SM16-10 16” 510 680 0.48 640 855 0.65 SM18-10 18” 580 870 0.47 735 1100 0.65 SM21-10 21” 675 1180 0.47 855 1500 0.65 SM24-10 24” 750 1500 0.46 960 1920 0.65 SM28-10 28” 830 1940 0.44 1075 2505 0.65 SM32-10 32” 875 2335 0.42 1095 2920 0.61 SM36-10 36” 885 2660 0.38 1110 3325 0.56 SM42-10 42” 900 3145 0.35 1125 3930 0.50 SM48-10
3 ½”
48”
9'-9 ¾” (117 ¾”)
S T D
S T D
910 3630 0.32
S T D
S T D
1135 4535 0.47
SM16-11 16” 445 595 0.54 560 745 0.72 SM18-11 18” 510 765 0.53 645 965 0.72 SM21-11 21” 590 1035 0.51 755 1320 0.72 SM24-11 24” 665 1325 0.50 850 1700 0.72 SM28-11 28” 740 1725 0.49 955 2225 0.72 SM32-11 32” 795 2120 0.47 995 2650 0.69 SM36-11 36” 805 2410 0.43 1005 3015 0.62 SM42-11 42” 815 2850 0.39 1020 3565 0.56 SM48-11
3 ½”
48”
10'-9 ¾” (129 ¾”)
2 X 4
N A I L - O N 825 3290 0.36
2 X 4
N A I L - O N 1030 4115 0.52
For custom height load values round up to next foot, or call if exact value needed. 2012 IBC Seismic CODE VALUES 2012 IBC Wind CODE VALUES
STD OPTIONS RARELY REQUIRED – 6-10 ft 2x4 2x4 NAIL-ON OPT. RECOMMENDED -10-11 ft 2x6 2x6 NAIL-ON OPT. RECOMMENDED - 11-14 ft EC6 EC6 OPTION RECOMMENDED - 14-17 ft EC8 EC8 OPTION RECOMMENDED - 17-20 ft
OUT-OF-PLANE AND COMPRESSION LOADS MUST BE CHECKED. The Project Engineer/Governing Agencies may use their discretion/engineering judgment regarding post bracing. The accompanying color-codes designate recommended post options (found throughout this guide) for post sections not fully braced by other methods. Recommendations are based upon full compression load on post(s) from in-plane racking shear and/or load on post(s) from typical out-of-plane wind loads. Post sections may need to be braced or increased for other conditions.
PAGE 3
ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016
NOMINAL HEIGHT
12’
13’
14’ 15’
SHEARMAX STANDARD & TRIM-FIT PANELS – 12’ to 15’: REFERENCE TABLE 2 PANEL DIMENSIONS ALLOWABLE IN-PLANE SHEAR LOAD AND DRIFT
2015 IBC Seismic (R=6.5) 2015 IBC Wind SHEAR (Lbs.) SHEAR (Lbs.)
SHEAR-MAX
MODEL THICK-NESS
WIDTH NOMINAL
ACTUAL HEIGHT
LBS / FT TOTAL
DRIFT (IN.) LBS / FT TOTAL
DRIFT (IN.)
SM16-12 16” 390 520 0.58 490 655 0.79 SM18-12 18” 450 675 0.58 570 855 0.79 SM21-12 21” 525 920 0.56 670 1175 0.79 SM24-12 24” 590 1180 0.55 760 1515 0.79 SM28-12 28” 660 1545 0.54 855 1995 0.79 SM32-12 32” 720 1920 0.52 910 2425 0.77 SM36-12 36” 735 2210 0.48 920 2760 0.70 SM42-12 42” 745 2610 0.43 935 3265 0.62 SM48-12
3 ½”
48”
11'-9 ¾” (141 ¾”)
2 X 6
N A I L - O N 755 3010 0.39
2 X 6
N A I L - O N 940 3765 0.57
SM16-13 16” 350 465 0.64 440 585 0.85 SM18-13 18” 400 600 0.63 505 760 0.85 SM21-13 21” 470 825 0.61 600 1050 0.85 SM24-13 24” 535 1065 0.60 680 1360 0.85 SM28-13 28” 600 1395 0.59 770 1800 0.85 SM32-13 32” 655 1740 0.57 840 2235 0.85 SM36-13 36” 680 2035 0.54 850 2545 0.78 SM42-13 42” 690 2410 0.48 860 3010 0.69 SM48-13
3 ½”
48”
12’-9 ¾” (153 ¾”)
2 X 6
N A I L - O N 695 2775 0.43
2 X 6
N A I L - O N 870 3470 0.63
SM16-14 16” 310 415 0.69 390 520 0.92 SM18-14 18” 360 540 0.68 455 685 0.92 SM21-14 21” 425 745 0.67 540 945 0.92 SM24-14 24” 480 960 0.65 615 1230 0.92 SM28-14 28” 540 1265 0.63 700 1635 0.92 SM32-14 32” 595 1585 0.62 770 2055 0.92 SM36-14 36” 630 1890 0.60 785 2360 0.87 SM42-14 42” 635 2230 0.52 795 2790 0.76 SM48-14
3 ½”
48”
13'-9 ¾” (165 ¾”)
2 X 6
N A I L - O N 645 2575 0.48
2 X 6
N A I L - O N 805 3220 0.69
SM16-15 16” 280 375 0.74 355 470 0.99 SM18-15 18” 325 490 0.73 410 615 0.99 SM21-15 21” 385 675 0.72 490 855 0.99 SM24-15 24” 440 875 0.70 560 1115 0.99 SM28-15 28” 495 1155 0.68 640 1490 0.99 SM32-15 32” 545 1450 0.67 705 1880 0.99 SM36-15 36” 585 1750 0.65 735 2200 0.96 SM42-15 42” 595 2080 0.58 745 2600 0.84 SM48-15
3 ½”
48”
14'-9 ¾” (177 ¾”)
E C 6
E C 6
600 2405 0.52
E C 6
E C 6
750 3005 0.76 For custom height load values round up to next foot, or call if exact value needed. 2012 IBC Seismic CODE VALUES 2012 IBC Wind CODE VALUES
STD OPTIONS RARELY REQUIRED – 6-10 ft 2x4 2x4 NAIL-ON OPT. RECOMMENDED - 10-11 ft 2x6 2x6 NAIL-ON OPT. RECOMMENDED - 11-14 ft EC6 EC6 OPTION RECOMMENDED - 14-17 ft EC8 EC8 OPTION RECOMMENDED - 17-20 ft
OUT-OF-PLANE AND COMPRESSION LOADS MUST BE CHECKED. The Project Engineer/Governing Agencies may use their discretion/engineering judgment regarding post bracing. The accompanying color-codes designate recommended post options (found throughout this guide) for post sections not fully braced by other methods. Recommendations are based upon full compression load on post(s) from in-plane racking shear and/or load on post(s) from typical out-of-plane wind loads. Post sections may need to be braced or increased for other conditions.
PAGE 4
ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016
NOMINAL HEIGHT
16’ 17’ 18’ 19’
SHEARMAX STANDARD & TRIM-FIT PANELS – 16’ to 19’: REFERENCE TABLE 2 PANEL DIMENSIONS ALLOWABLE IN-PLANE SHEAR LOAD AND DRIFT
2015 IBC Seismic (R=6.5) 2015 IBC Wind SHEAR (Lbs.) SHEAR (Lbs.)
SHEAR-MAX
MODEL THICK-NESS
WIDTH NOMINAL
ACTUAL HEIGHT
LBS / FT TOTAL DRIFT (IN.) LBS / FT TOTAL
DRIFT (IN.)
SM16-16 16” 255 340 0.79 320 425 1.05 SM18-16 18” 295 445 0.78 375 560 1.05 SM21-16 21” 350 615 0.77 445 780 1.05 SM24-16 24” 400 800 0.75 510 1020 1.05 SM28-16 28” 455 1060 0.73 585 1365 1.05 SM32-16 32” 500 1335 0.72 645 1725 1.05 SM36-16 36” 540 1615 0.70 690 2065 1.05 SM42-16 42” 555 1950 0.63 695 2440 0.92 SM48-16
3 ½”
48”
15'-9 ¾” (189 ¾”)
E C 6
E C 6
565 2250 0.57
E C 6
E C 6
705 2815 0.82 SM16-17 16” 235 310 0.85 295 390 1.12 SM18-17 18” 270 405 0.84 340 510 1.12 SM21-17 21” 320 560 0.81 410 715 1.12 SM24-17 24” 370 735 0.80 470 935 1.12 SM28-17 28” 420 975 0.78 540 1255 1.12 SM32-17 32” 460 1230 0.76 595 1590 1.12 SM36-17 36” 500 1495 0.75 645 1940 1.12 SM42-17 42” 525 1835 0.69 655 2295 1.00 SM48-17
3 ½”
48”
16’-9 ¾” (201 ¾”)
E C 6
E C 6
530 2115 0.62
E C 6
E C 6
660 2645 0.90
SM16-18 16” - - - 265 355 1.19 SM18-18 18” 245 370 0.88 310 465 1.19 SM21-18 21” 295 515 0.86 375 655 1.19 SM24-18 24” 340 675 0.85 430 860 1.19 SM28-18 28” 385 900 0.83 495 1160 1.19 SM32-18 32” 430 1140 0.81 555 1475 1.19 SM36-18 36” 460 1385 0.80 600 1800 1.19 SM42-18 42” 495 1730 0.75 620 2165 1.09 SM48-18
3 ½”
48”
17'-9 ¾” (213 ¾”)
E C 8
E C 8
500 1995 0.67
E C 8
E C 8
625 2495 0.97 SM16-19 16” - - - 245 325 1.25 SM18-19 18” 225 340 0.93 285 430 1.25 SM21-19 21” 270 475 0.92 345 605 1.25 SM24-19 24” 315 625 0.90 400 795 1.25 SM28-19 28” 360 835 0.88 460 1075 1.25 SM32-19 32” 400 1060 0.86 515 1370 1.25 SM36-19 36” 430 1295 0.85 560 1675 1.25 SM42-19 42” 470 1640 0.81 585 2050 1.18 SM48-19
3 ½”
48”
18'-9 ¾” (225 ¾”)
E C 8
E C 8
475 1890 0.72
E C 8
E C 8
590 2365 1.05 For custom height load values round up to next foot, or call if exact value needed. 2012 IBC Seismic CODE VALUES 2012 IBC Wind CODE VALUES
STD OPTIONS RARELY REQUIRED – 6-10 ft 2x4 2x4 NAIL-ON OPT. RECOMMENDED - 10-11 ft 2x6 2x6 NAIL-ON OPT. RECOMMENDED - 11-14 ft EC6 EC6 OPTION RECOMMENDED - 14-17 ft EC8 EC8 OPTION RECOMMENDED - 17-20 ft
OUT-OF-PLANE AND COMPRESSION LOADS MUST BE CHECKED. The Project Engineer/Governing Agencies may use their discretion/engineering judgment regarding post bracing. The accompanying color-codes designate recommended post options (found throughout this guide) for post sections not fully braced by other methods. Recommendations are based upon full compression load on post(s) from in-plane racking shear and/or load on post(s) from typical out-of-plane wind loads. Post sections may need to be braced or increased for other conditions.
PAGE 5
ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016
ESTDSTDESTD C
EEC8CEC8EEC8
EC8
EC6 EEC6CEC6E
EC6
STD
OSB - TYP.
STDCSTDE 2x4STD E 2x4
STD
STD 2x6
E 2x6STD STDC
STD 2x4
E 2x6
#1 DFL BONDED - TYP.
#3 DFL MIN. (INCLUDES STUD,
#2 DFL NAILED - TYP.
#1 DFL BONDED - TYP.
CONST. & STD.) NAILED - TYP.
Notes: Hold-down Anchor tension load is 9,500Lbs. Alternate tension loads may be calculated based on (Vall or Vdesign) x αP. Wood post to wood post width (less hold-downs) is 3 in. less than nominal width. Refer to Table 3, page 9 & 10, for allowable compression loads, Table 4, page 8, for maximum design wind speeds. For optional post configurations for increased out-of-plane loads and/or vertical loads refer to Figure 3 this page. Actual height for Trim-Fit (TF) Panels used in design shall equal the greatest height of the sloped panel. Refer to Figure 2 (page 1) for details of determining the (TF) Panels.
SHEARMAX STANDARD & TRIM-FIT PANELS – 20’: REFERENCE TABLE 2 PANEL DIMENSIONS ALLOWABLE IN-PLANE SHEAR LOAD AND DRIFT
2015 IBC Seismic (R=6.5) 2015 IBC Wind SHEAR (Lbs.) SHEAR (Lbs.)
SHEAR-MAX
MODEL THICK-NESS
WIDTH NOMINAL
ACTUAL HEIGHT
LBS / FT TOTAL DRIFT (IN.) LBS / FT TOTAL
DRIFT (IN.)
SM16-20 16” - - - 225 300 1.32 SM18-20 18” 210 315 0.99 265 395 1.32 SM21-20 21” 250 440 0.97 320 560 1.32 SM24-20 24” 290 580 0.95 370 740 1.32 SM28-20 28” 335 780 0.94 430 1000 1.32 SM32-20 32” 370 990 0.92 480 1275 1.32 SM36-20 36” 400 1205 0.89 520 1565 1.32 SM42-20 42” 440 1545 0.87 555 1945 1.28 SM48-20
3 ½”
48”
19'-9 ¾” (237 ¾”)
E C 8
E C 8 450 1795 0.78
E C 8
E C 8 560 2245 1.13
For custom height load values round up to next foot, or call for exact value. 2012 IBC Seismic CODE VALUES 2012 IBC Wind CODE VALUES
STD OPTIONS RARELY REQUIRED – 6-10 ft 2x4 2x4 NAIL-ON OPT. RECOMMENDED - 10-11 ft 2x6 2x6 NAIL-ON OPT. RECOMMENDED - 11-14 ft EC6 EC6 OPTION RECOMMENDED - 14-17 ft EC8 EC8 OPTION RECOMMENDED - 17-20 ft
OUT-OF-PLANE AND COMPRESSION LOADS MUST BE CHECKED. The Project Engineer/Governing Agencies may use their discretion/engineering judgment regarding post bracing. The accompanying color-codes designate recommended post options (found throughout this guide) for post sections not fully braced by other methods. Recommendations are based upon full compression load on post(s) from in-plane racking shear and/or load on post(s) from typical out-of-plane wind loads. Post sections may need to be braced or increased for other conditions.
STD
2x4
2x6
EC6
EC8
Center post included on all Panels when Nominal Panel Width > 28”. Field-Modified: 1 - 2x4 DF STUD or STANDARD min. continuous from top of panel to top of hold-down with 2 rows of 10d commons @ 6” o.c. staggered. Field-Modified: 1 - 2x6 DF #2 min. continuous from top of panel to top of hold-down with 2 rows of 10d commons @ 6” o.c. staggered.
EC6-Factory-Fabricated: 1 - 2x4 DF #1 bonded (glued) & screwed to Standard Posts EC8-Factory-Fabricated: 2 - 2x4 DF #1 bonded (glued) & screwed to Standard Posts
20’
PAGE 6
ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016
NOMINAL HEIGHT
NA I L -ON
NA I L -ON
Second Story Applications Want to achieve similar shear capacity as squash block systems but have concerns about wood shrinkage? Simplify the load path and take advantage of custom heights by using tall panels from concrete to second floor top plate, or, if one is not enough, consider using back-to-back panels instead of stacked panels. The first floor panel experiences no reduced shear capacity or “R” value due to the second story panel load. Since panel widths and locations can be independent of one another, design flexibility is almost limitless.
Back-to-Back Panels Panel heights or vertical load from above causing the need for an EC6 or EC8 option? Consider placing panels Back-to-Back for twice the shear capacity for only about 25% more cost than EC8 option
SUGGESTED ALTERNATIVES TO ACHIEVE MORE LOAD
PAGE 7
ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION November 01, 2008
Custom Heights NO EXTRA CHARGE
2015 IBC CONVERSION: [(MPH)2 X 1.6]0.5 2009 IBC MAXIMUM BASIC WIND SPEED(3-Sec. Gust) for SHEARMAX Panels(mph):
PANEL CONFIGURATION (Refer to Figure 3-Page 6) / EXPOSURE CATEGORIES (Refer to IBC Section 1609.4) STANDARD AND TRIM-FIT (TF) PANEL (16 inches on center stud spacing) / values assume no stud along side of panel – 1st stud 16’’ away
Field Modified Post Enhancement Factory Fabricated Post Enhancement STD 2x4 OPTION (NAIL-ON) 2x6 OPTION (NAIL-ON) EC6 OPTION EC8 OPTION
NOMINAL HEIGHT
B C D B C D B C D B C D B C D
8’ 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 9’ 170 160 150 170 170 160 170 170 170 170 170 170 170 170 170
10’ 150 140 120 170 150 140 170 160 150 170 170 170 170 170 170 11’ 130 120 100 140 130 120 150 140 130 170 170 160 170 170 170 12’ 110 110 90 130 110 100 130 120 110 170 160 150 170 170 170 13’ 100 90 — 110 100 90 120 100 90 160 150 140 170 170 170 14’ 90 — — 100 90 — 100 90 85 150 140 120 170 170 160 15’ -— — — 90 — — 90 85 — 140 130 110 170 170 150 16’ — — — — — — — — — 130 110 100 170 150 140 17’ — — — — — — — — — 120 100 90 160 140 130 18’ — — — — — — — — — 100 90 85 150 130 120 19’ — — — — — — — — — 90 85 — 140 120 110 20’
— — — — — — — — — 90 — — 130 120 110 ‘Value’ SUPPLEMENTAL BRACING RECOMMENDED
— BRACING REQUIRED
OUT-OF-PLANE AND COMPRESSION LOADS MUST BE CHECKED.The Project Engineer/Governing Agencies may use their discretion/engineering judgment regarding post bracing. The accompanying color-codes designate recommended post options (found throughout this guide) for post sections not fully braced by other methods. Recommendations are based upon full compression load on post(s) from in-plane racking shear and/or load on post(s) from typical out-of-plane wind loads. Post sections may need to be braced or increased for other conditions.
SPACING TYP16" O.C.
SPACING TYP16" O.C.
PAGE 8
ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016
Tall Walls
Brace taller panels with adjacent walls to save the cost of an EC6 or EC8 option.
Column with draft stop bracing panel shown at left.
Raised Floor
Achieve about 30% more shear capacity over squash block systems by using a custom height panel from stem wall to top plate. Also allows for use in cripple wall situations.
ALLOWABLE COMPRESSION LOAD PER VERTICAL POST: REFERENCE TABLE 3
ALLOWABLE NET COMPRESSION LOADS (Lbs.) STD 2x4 OPTION (NAIL-ON) 2x6 OPTION (NAIL-ON) EC6 OPTION EC8 OPTION NOMINAL
HEIGHT END POST
CENTER POST
END POST
CENTER POST
END POST
CENTER POST
END POST
CENTER POST
END POST
CENTER POST
78” * 6,550 10,300 6,550 10,300 6,550 10,300 9,830 13,600 13,115 16,850 8’ 3,800 10,300 5,850 10,300 6,550 10,300 9,830 13,600 13,115 16,850 9’ 1,700 8,200 3,600 8,200 6,550 8,200 9,830 13,600 13,115 16,850
10’ 100 6,650 1750 6,650 6,550 6,650 9,830 13,600 13,115 16,850 11’ — 5,450 250 5,450 6,550 5,450 9,050 13,100 13,115 16,850 12’ — 4,550 — 4,550 5,950 4,550 6,850 11,100 13,115 16,850 13’ — 3,850 — 3,850 4,200 3,850 5,000 9,500 13,115 16,850 14’ — 3,300 — 3,300 2,750 3,300 3,450 8,200 13,115 16,850 15’ — — — — — — 2,200 7,150 12,000 15,150 16’ — — — — — — 1,100 6,300 10,000 13,450 17’ — — — — — — 200 5,550 8,250 12,000 18’ — — — — — — — 4,950 6,750 10,750 19’ — — — — — — — 4,450 5,450 9,700 20’
— — — — — — — — 4,300 8,750 ALLOWABLE NET COMPRESSION LOADS ARE THE MAXIMUM VERTICAL LOADS THAT CAN BE ADDED TO THE POSTS WHEN THE MAXIMUM ALLOWABLE SHEAR LOAD IS APPLIED TO THE TOP OF THE PANEL. CAUTION: SOME MANUFACTURES LIST GROSS ALLOWABLE VERTICAL LOADS IN ICC-ES REPORTS. THESE GROSS ALLOWABLE LOADS MUST BE REDUCED BY THE VERTICAL LOAD IN THE POSTS RESULTING FROM PANEL OVERTURNING.
‘Value’ SUPPLEMENTAL BRACING RECOMMENDED * IF PANEL IS FULLY BRACED BY OTHERS USE 78” VALUES — BRACING REQUIRED
PANEL WIDTH32" to 48"
PANEL WIDTH
LOAD
LOAD
LOAD
LOAD
LOAD
16" to 28"
END
POST TYP.
CEN
TER PO
ST TYP.
END
POST TYP.
END
POST TYP.
END
POST TYP.
O.S.B.PANE(TYP.)
O.S.B.PANE(TYP.)
O.S.B.PANE(TYP.)
**LOAD
**LOAD
**LOAD
** DISTRIBUTE LOAD TO POSTS USING STATICS
PANEL WIDTH32" to 48"
PANEL WIDTH16" to 28"
O.S.B.PANE(TYP.)
O.S.B.PANE(TYP.)
O.S.B.PANE(TYP.)
LOAD
LOAD
END
POST TYP.
CEN
TER PO
ST TYP.
END
POST TYP.
LOAD
NO NO NOLOAD
LOAD
LOAD
END
POST TYP.
END
POST TYP.
HEAD
LOAD
LOAD
TRIM-FITTRIM-FIT
HEAD
PAGE 9
ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION November 01, 2008
OUT-OF-PLANE AND COMPRESSION LOADS MUST BE CHECKED. The Project Engineer/Governing Agencies may use their discretion/engineering judgment regarding post bracing. The accompanying color-codes designate recommended post options (found throughout this guide) for post sections not fully braced by other methods. Recommendations are based upon full compression load on post(s) from in-plane racking shear and/or load on post(s) from typical out-of-plane wind loads. Post sections may need to be braced or increased for other conditions.
STD- OPTIONS RARELY REQUIRED – 6-10 ft
2x4 2x4 NAIL-ON OPTION RECOMMENDED – 10-11 ft
2x6 2x6 NAIL-ON OPTION RECOMMENDED – 11-14 ft
EC6 EC6 OPTION RECOMMENDED – 14-17 ft
EC8 EC8 OPTION RECOMMENDED – 17-20 ft
ESTDSTDESTD C
EEC8CEC8EEC8
EC8
EC6 EEC6CEC6E
EC6
STD
OSB - TYP.
STDCSTDE 2x4STD E 2x4
STD
STD 2x6
E 2x6STD STDC
STD 2x4
E 2x6
#1 DFL BONDED - TYP.
#3 DFL MIN. (INCLUDES STUD,
#2 DFL NAILED - TYP.
#1 DFL BONDED - TYP.
CONST. & STD.) NAILED - TYP.
PORTAL BEAM CONDITION
END
POST TYP.
END
POST TYP.
CEN
TER PO
ST TYP.
PANEL WIDTH32" to 48"
(TYP.)PANEO.S.B.
(TYP.)PANEO.S.B.O.S.B.
PANE(TYP.)
PANEL WIDTH16" to 28"
END
POST TYP.
END
POST TYP.
LOAD
PORTAL BEAM PORTAL BEAM
LOAD
ALLOWABLE COMPRESSION LOAD PER PANEL: REFERENCE TABLE 3
ALLOWABLE NET COMPRESSION LOADS (Lbs.) STD 2x4 OPTION (NAIL-ON) 2x6 OPTION (NAIL-ON) EC6 OPTION EC8 OPTION NOMINAL
HEIGHT PANEL WIDTH 16” to 28”
PANEL WIDTH 32” to 48”
PANEL WIDTH 16” to 28”
PANEL WIDTH32” to 48”
PANEL WIDTH 16” to 28”
PANEL WIDTH 32” to 48”
PANEL WIDTH 16” to 28”
PANEL WIDTH 32” to 48”
PANEL WIDTH 16” to 28”
PANEL WIDTH 32” to 48”
78” * 13,100 23,400 13,100 23,400 13,100 23,400 19,660 33,260 25,740 42,590 8’ 10,350 20,650 12,400 22,700 13,100 23,400 19,660 33,260 25,740 42,590 9’ 8,250 16,450 10,150 18,350 13,100 21,300 19,660 33,260 25,740 42,590
10’ 5,675 12,325 8,300 14,950 13,100 19,750 19,660 33,260 25,740 42,590 11’ 4,725 10,175 5,950 11,400 13,100 18,550 18,880 31,980 25,740 42,590 12’ 4,025 8,575 4,900 9,450 12,500 17,050 16,680 27,780 25,740 42,590 13’ 3,475 7,325 4,250 8,100 10,750 14,600 14,450 23,950 25,740 42,590 14’ 3,025 6,325 3,700 7,000 9,300 12,600 11,875 20,075 25,740 42,590 15’ — — — — — — 9,700 16,850 24,625 39,775 16’ — — — — — — 7,800 14,100 22,625 36,075 17’ — — — — — — 6,200 11,750 20,575 32,575 18’ — — — — — — 5,400 10,350 18,025 28,775 19’ — — — — — — 4,875 9,325 15,775 25,475 20’
— — — — — — — — 13,750 22,500 ALLOWABLE NET COMPRESSION LOADS ARE THE MAXIMUM VERTICAL LOADS THAT CAN BE ADDED TO THE POSTS WHEN THE MAXIMUM ALLOWABLE SHEAR LOAD IS APPLIED TO THE TOP OF THE PANEL. CAUTION: SOME MANUFACTURES LIST GROSS ALLOWABLE VERTICAL LOADS IN ICC-ES REPORTS. THESE GROSS ALLOWABLE LOADS MUST BE REDUCED BY THE VERTICAL LOAD IN THE POSTS RESULTING FROM PANEL OVERTURNING.
‘Value’ SUPPLEMENTAL BRACING RECOMMENDED * IF PANEL IS FULLY BRACED BY OTHERS USE 78” VALUES — BRACING REQUIRED
STD
EC6
EC8
2 X 4
2 X 6
PAGE 10
ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION November 01, 2008
N A I L - O N N A I L - O N
SUGGESTED SPECIFICATION STANDARDS
SM16T
SM11 & 2
1 & 2SM1
4,6,7
8
BASIC PANEL INSTALL DETAILS ON SITE PANEL ADJUSTMENTS
RAISED FLOOR DETAILS
16'' WIDE PANEL WITH A STANDARD 8' WALL
3 & 5
SM16-8
FOUNDATION PLAN
FRAMING PLAN
SM24-10 CUSTOM HEIGHT (FIELD VERIFY)
3 & 5
24'' WIDE PANEL WITH A CUSTOM HEIGHT
FRAMING PLAN
SM32-13-W / STD 2X6 (NAIL-ON)
3 & 5
32'' WIDE PANEL WITH A STANDARD 13' WALL
FRAMING PLAN
3 & 5
FRAMING PLANAND WITH STD 2X6 NAIL-ON OPTION
ORSM24-111'' CUSTOM HEIGHT
36'' WIDE TRIM-FIT (TF) PANEL - 110" LOW POINT
SM36-110" (LOW POINT) - TFOR
SM36-11 CUSTOM HEIGHT-TF (FIELD VERIFY)
TRIM-FIT (TF) PANEL PANEL CONFIGURATIONS / POST SECTIONS(POST OPTIONS: STD 2x4, STD 2x6, EC6, EC8)
DETAIL KEY
SM XX - YYSM SHEARMAX PRODUCT IDENTIFIERXX NOMINAL OVERALL WIDTH (Inches)YY NOMINAL HEIGHT * (Feet)
SM XX T
T REUSABLE TEMPLATE IDENTIFIERXX BASE PLATE (SYSTEM) WIDTHSM SHEARMAX PRODUCT IDENTIFIER
SPECIFICATION IN BLACK - COMMENTARY IN GREEN
1 1/2" BOTTOM PLATE PLUS THE STANDARD STUD
8' = 92 1/4", 9' = 104 1/4"
PLUS 12" TO 140 1/4" FOR EVERY FOOT PAST 12'
YY IF NET PANEL HEIGHT IS NOT SPECIFIED ININCHES THEN CODE THE HEIGHT IN NOMINAL
XX NOMINAL OVERALL WIDTH (Inches)SM SHEARMAX PRODUCT IDENTIFIERSM XX - YY
YY NOMINAL HEIGHT OR CUSTOM HEIGHTXX NOMINAL OVERALL WIDTH (Inches)SM SHEARMAX PRODUCT IDENTIFIERSM XX - YY - ' POST OPTION '
FRAMING PLAN
48'' WIDE PANEL RAISED FLOOR 122" NET HEIGHT
83 & 5
PROPER ANCHOR BOLT LENGTH ANDMODEL CODE IS FOUND IN DETAIL
1SM1
FEET (ROUNDED UP) AND ADD 'FIELD VERIFY'
W / STD 2X4 NIAL-ONW / STD 2X6 NAIL-ONEC6EC8
POST OPTION TYPES:
YY THE HEIGHT OF A TRIM-FIT IS SPECIFIED 2 WAYS:
SM XX - YY - TFSM SHEARMAX PRODUCT IDENTIFIERXX NOMINAL OVERALL WIDTH (Inches)
(SEE BELOW)TF TRIM-FIT IDENTIFIER
2) WHEN A 'NET' HEIGHT (Inches) IS USEDIT IS AT THE LOW POINT OF THE SLOPE
1) WHEN THE 'NOMINAL' HEIGHT (Feet) ISUSED IT IS AT THE PANELS' HIGH POINT(ROUNDED UP TO WHOLE FEET) AND
TYPICAL FOR NEW POUR CONDITIONS
* NOMINAL WALL HEIGHT IN FEET ASSUMES:
STANDARD STUD LENGTH:10' = 116 1/4", 11' = 128 1/4", 12' = 140 1/4"
SM24-11 CUSTOM HEIGHT (FIELD VERIFY)
SM24-122'' CUSTOM HEIGHTOR
FEET (ROUNDED UP) AND ADD ' FIELD VERIFY '.
SM SHEARMAX PRODUCT IDENTIFIERXX NOMINAL OVERALL WIDTH (Inches)
INCHES THEN CODE THE HEIGHT IN NOMINALYY IF NET PANEL HEIGHT IS NOT SPECIFIED IN
SM XX - YY
THE PANEL HEIGHT FOR RAISED FLOOR ISSPECIFIED THE SAME AS A CUSTOM HEIGHT
16'' TEMPLATE FOR 16" PANEL
FRAMING PLAN (PLAN VIEW)
FOUNDATION PLAN (PLAN VIEW)
STANDARD PANEL
REUSABLE TEMPLATE
CUSTOM HEIGHTS
RAISED FLOOR
POST OPTIONSTRIM FIT
SPECIFICATION IN BLACK - COMMENTARY IN GREEN SPECIFICATION IN BLACK - COMMENTARY IN GREEN
1 - HIGH POINT
2 - LOW POINT
' FIELD VERIFY ' IS ADDED
YY SPECIFICATION FOR TRIM FIT PANELS
BASIC CONCRETE DEAILS 3 & 5SM2 SM2
SM311
SM39
SM310
SM3TWO-STORY CONDITION
SM2 SM2
SM29
SM3 SM210
SM3
SM2 SM3
PAGE 11
ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION November 01, 2008
SHEA
RM
AX T
EMPL
ATE
5/8"
Ø X
10"
AN
CH
OR
BO
LT
5/8"
Ø A
NC
HO
R B
OLT
NU
T
SHEA
RM
AX T
EMPL
ATE
SHEA
RM
AX H
OLD
DO
WN
CO
UPL
ER
LOW
ER N
UT(B
OLT
LEN
GTH
)
SHEA
RM
AX H
OLD
DO
WN
BO
LT
CO
LOR
CO
DED
SLE
EVE
WAS
HER
(DIS
POSA
BLE)
NYL
ON
BO
LT (D
ISPO
SABL
E)
SHEA
RM
AX H
OLD
DO
WN
FOO
TIN
G A
S R
EQU
IRED
(2) P
ER T
EMPL
ATE
BOLT
ASS
EMBL
Y
QTY
. VAR
IES
PER
SIZ
E
QTY
. VAR
IES
PER
SIZ
E
W/ 5
" EM
BED
MEN
T
W/ 5
" EM
BED
MEN
T
SHEA
RM
AX T
EMPL
ATE
5/8"
Ø X
10"
AN
CH
OR
BO
LTS
5/8"
Ø X
10"
AN
CH
OR
BO
LTS
SHEA
RM
AX H
OLD
DO
WN
FOO
TIN
G A
S R
EQU
IRED
2X4
SCR
EED
BO
ARD
(2) P
ER T
EMPL
ATE
BOLT
ASS
EMBL
Y
FOR
M B
OAR
D S
IZE
VAR
IES
DR
AW
N B
Y:
CH
ECK
ED B
Y:
SHEE
T N
UM
BER
:
SM1
OWNER / APPLICANT:PROJECT:
DRAWING:
CO
ND
ITIO
NS D
O E
XIST
, IT
IS T
HE
RES
PON
SIBI
LITY
OF
THE
CO
NTRA
CTO
R T
O N
OTI
FY T
HE
DES
IGN
PRO
FESS
ION
AL, A
RC
HITE
CT,
3. T
HIS
PR
ODU
CT,
IS P
ART
OF
AN O
VER
ALL
LATE
RAL
FORC
E R
ESIS
TIN
G S
YSTE
M, W
HIC
H SH
ALL
ALW
AYS
BE R
EVIE
WED
AND
SPE
CIF
IED
TIO
N O
F TH
IS P
RO
DUC
T AN
D/ O
R A
NY
CO
MPO
NEN
T AF
FEC
TIN
G T
HE S
HEA
RMAX
SYS
TEM
. IF
ANY
DIS
CREP
ANCI
ES A
ND/O
R A
DVE
RSE
4. T
HE C
ON
TRAC
TOR
IS R
ESPO
NSI
BLE
TO V
ERIF
Y AL
L DI
MEN
SIO
NS, C
ON
DIT
IONS
, AN
D PO
SITI
ONS
OF
SHEA
RMAX
, ETC
., PR
IOR
TO IN
STAL
LA-
2x U
P TO
14
1228
30SM
30F
BOAR
D
ASTM
A44
9
SM60
FSM
54F
SM48
FSM
42F
SM36
F
3/4"
DIA
. AN
CH
OR
BO
LT
2x U
P TO
20
2x U
P TO
26
2x U
P TO
32
2x U
P TO
38
2x U
P TO
44
SHEA
RM
AX A
NC
HO
R N
UT
DET
AIL
18 24 30 36 42
34 40 46 52 586054484236
EMBE
DM
ENT
SHEA
R C
ON
E
1 3/
4" R
OU
ND
NU
T1
1/2"
SQ
UAR
E O
R
13"
7/8" MIN.
SM26
FSM
22F
CO
DE
BOLT
STO
CK
BOLT
LEN
GTH
S - C
UST
OM
LEN
GTH
S AR
E AV
AILA
BLE
3/4"
DIA
. AST
M A
449,
STU
D T
YPE
BOLT
(TYP
.)SH
EAR
MAX
CIP
HO
LD-D
OW
N A
NCH
OR
BO
LT
2x U
P TO
10
SIZE
OF
FOR
M2n
d PO
UR
MAX
IMU
M
THIC
KNES
S
8 42x
UP
TO 6
MAX
IMU
M
BOAR
D(S
)EM
BED
MEN
TTO
TAL
BOLT
20 242622
LEN
GTH
BOLT
TOTA
L
BOLT
LEN
GTH
- N
OT
PAN
ELD
EPTH
DET
ERM
INES
AN
CHO
RSH
EAR
CO
NE
EMBE
DM
ENT
FOR
M
SIZE
(WID
TH O
R H
EIG
HT)
1. S
HEA
RM
AX
PAN
ELS
ARE
MAN
UFA
CTU
RED
AN
D TR
ADEM
ARKE
D BY
SHE
AR T
RAN
SFER
SYS
TEM
S, IN
C.
BY A
DES
IGN
PR
OFE
SSIO
NAL
, ARC
HITE
CT,
AN
D/O
R E
NG
INEE
R O
F R
ECO
RD
AN
D AP
PRO
VED
BY
REQ
UIR
ED A
GEN
CIE
S.
5. S
HEA
R T
RAN
SFER
SYS
TEM
S, IN
C. R
ESER
VES
THE
RIG
HT
TO C
HAN
GE
DESI
GN
S, S
PECI
FIC
ATIO
NS,
AN
D/O
R M
ODE
LSAN
D/O
R E
NG
INEE
R O
F R
ECO
RD, A
ND/
OR
LO
CAL
BUIL
DIN
G O
FFIC
IALS
FO
R C
LAR
IFIC
ATIO
NS
PRIO
R TO
CO
NST
RUC
TIO
N.
2. S
HEA
RM
AX P
ANEL
S AR
E LI
STED
BY
ICC
-ES
IN E
VALU
ATIO
N R
EPO
RT
ESR
-172
7.
6. 1
-INC
H =
25.
4 M
M -
DRA
WIN
GS
NO
T TO
SC
ALE
WIT
HOU
T N
OTI
CE
OR
LIA
BILI
TY.
2
REV
ISED
01/
01/0
8
2
REV
ISED
03/
20/0
6
1
ORG
INIA
L
02/
01/0
6
NO
.
REV
ISIO
N
DA
TE
MAX
ICC
ESR-
1727
TM
SM 1 - 2015 IBC OR 2016 CBC PAGE 12 ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE.
SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016
SHEA
RM
AX P
ANEL
A35'
s O
N S
TEPP
EDFA
CE
- REF
ER T
O
DBL
2x6
(MIN
) PLA
TE
SMTC
, LTP
4 O
R A
LT. C
ON
N. A
SSP
ECIF
IED
ON
FLU
SH F
ACE
SM
TC T
OP
PLAT
E C
ON
NEC
TOR
DR
AG M
EMBE
RC
OLL
ECTO
R O
RD
OU
BLE
TOP
PLAT
E,
SH
EAR
MAX
PAN
EL
2 x
STU
D W
ALL
CO
NC
RET
E C
UR
BTO
P O
F SL
AB O
R
STA
ND
AR
D W
ALL
IN
STA
LLAT
ION
PER
TAB
LE 1
OR
ALT
ERN
ATE
AS
SPE
CIF
IED
DO
UBL
E TO
P PL
ATE
SMTC
, LTP
4 O
R A
LT. C
ON
N. A
SSP
ECIF
IED
ON
FLU
SH F
ACES
CO
NN
. AS
SPEC
IFIE
D
AS S
PEC
IFIE
D
TABL
E 1
OR
2x K
ING
STU
D
ALTE
RN
ATE
SMTC
PER
NO
TE:
REF
ER T
O P
LAN
FO
R P
RO
PER
GR
ADE
BEAM
REQ
UIR
EMEN
TS
SEC
TIO
N A
-A
TYPI
CA
L P
OR
TAL
CO
ND
ITIO
N &
C
OR
NE
R C
ON
DIT
ION
SH
OW
N
PAN
EL F
RO
NT
A
STEM
WA
LL
FOU
ND
ATIO
N
PAN
EL F
RO
NT
(DES
IGN
BY
OTH
ERS)
PON
Y SH
EAR
WA
LL C
ON
DIT
ION
OPT
ION
AL J
AMB
2x F
ILLE
R P
IEC
ESU
GG
EST
ED
SH
EAR
MAX
PAN
EL
DO
UBL
E TO
P PL
ATE,
CO
LLE
CTO
R O
RD
RAG
MEM
BER
SHEA
RM
AX P
ANEL
ON
FLU
SH F
ACES
HEA
DER
7 1/
2"
SMTC
CO
NN
ECTO
R (N
TS)
SPEC
IFIE
D O
N F
LUSH
FAC
ES
MTC
, LTP
4 O
R A
LT. C
ON
N. A
S
16"
24
(ON
E SM
TC O
R T
WO
A35
's P
ER
SHEA
RM
AX P
ANEL
HEA
DER
OR
BEA
M
SMTC
, LTP
4 O
R A
LT.
A35'
s O
N S
TEPP
ED F
ACE
-R
EFER
TO
TAB
LE 1
6x B
EAM
OR
HEA
DER
28"
32"
36"
42"
48"
5443
18"
21"
24"
2 332
WH
EN A
SH
IM IS
INST
ALLE
D, F
ILL
ALL
TRIA
NG
ULA
RH
OLE
S W
ITH
16d
SIN
KER
NAI
LS -
REF
ER T
O D
ETAI
L 6
FAC
ILIT
ATE
INST
ALLI
NG
SM
TC C
ON
NEC
TOR
PIEC
E M
AY B
E FO
LDED
90
OU
T-O
F-PL
ANE
TO6 1/2"
O
2. M
IXIN
G O
F SM
TC, A
35 &
LTP
4
3. O
NE
SMTC
EQ
UAL
S TW
O A
35
4. N
AIL
SM
TC's
WIT
H 1
0d C
OM
MO
N
LTP4
DO
NO
T EQ
UAL
ON
E SM
TC
[(0.1
48) x
1 1
/2"]
OR
16d
GV
OR
LTP
4 BU
T TW
O A
35 O
R8 9 10 12
SID
E M
INIM
UM
)
IS A
LLO
WED
5 6 6 7
TABL
E 1
TABL
E 1
- TO
P-O
F-PA
NE
L C
ON
NEC
TOR
S
1. A
PPLY
EVE
NLY
AC
RO
SS P
ANEL
NO
TES:
A
SM2
PAN
EO
.S.B
.
(TY
P.)
EXC
EPT
AS N
OTE
D, I
N A
NY
LOC
ATIO
NO
NE
RO
UN
D H
OLE
SHIM
PAN
EFR
AMIN
G M
EMBE
R E
XCEP
T AS
PAN
EA3
5'S
ON
STE
PPED
FAC
EBO
TH F
LUSH
FAC
ES
WH
EN S
HIM
MIN
G P
ANEL
TO
TO
P PL
ATE
SMTC
PLA
CE
MEN
T IS
CR
ITIC
ALA
LL N
AILS
MU
ST H
AVE
PRO
PER
EN
BED
MEN
T IN
TO W
OO
D F
IBER
S
1. A
LL N
AIL
HO
LES
MU
ST
BE F
ILLE
D A
ND
FIR
MLY
EM
BED
DE
D IN
TO S
OLI
D W
OO
D W
ITH
10
NAI
LS M
IN.
2. A
LL D
IAM
ON
D S
HAP
PED
HO
LES
MU
ST B
E FI
LLED
WIT
H 1
6d G
VS W
HEN
USE
D A
S PA
RT
OF
INTO
PAN
EL H
EAD
AN
D 9
NAI
LS M
IN. I
NTO
DBL
TO
P PL
ATE
PER
SM
TC C
ON
NEC
TOR
.
SHIM
REQ
UIR
ED N
O. O
F N
AILS
PER
SM
TC.
NO
TES:
3. A
LL P
ANEL
S M
AY B
E TR
IMM
ED 1
/4" T
OP
AND
/OR
BO
TTO
M
SEC
TIO
N B
-B
CO
NN
ECTO
R B
OTH
SID
ESFI
LL A
LL N
AIL
HO
LES
SMTC
TO
P P
LATE
SHEA
RM
AX P
ANEL
4x H
EAD
ER/B
EAM
SHEA
RM
AX P
ANEL
WID
TH =
WID
TH O
F BE
AM/H
EAD
ERTH
ICKN
ESS
= 1
1/2
" MAX
.SH
IM M
EMBE
RSH
IM M
EMBE
R
SHIM
MEM
BER
WID
TH =
WID
TH O
F BE
AM/H
EAD
ERTH
ICK
NES
S =
1 1/
2" M
AX.
SHEA
RM
AXPA
NEL
OSB
PAN
EA
35'S
ON
STE
PPED
FAC
EU
SE 1
6d G
VS F
OR
VER
TIC
AL
NAI
LIN
G
SHEA
RM
AX P
ANEL
BELO
W
FOR
ALL
PAN
EL W
IDTH
S:AN
Y O
R A
LL O
SB P
ANE
S M
AY H
AVE
ON
ER
OU
ND
HO
LE IN
AN
Y LO
CAT
ION
AS
SHO
WN
. HO
LE M
UST
NO
T PE
NET
RAT
EAN
Y FR
AMIN
G M
EMBE
R.
PAN
EO
.S.B
.
(TYP
.)
ON
LY
LIM
ITS
OF
TYPI
CAL
FLU
SH F
ACE
- FIL
L A
LL N
AIL
HO
LES
SMTC
TO
P PL
ATE
CO
NN
ECTO
R
6x (O
R L
ARG
ER) B
EAM
/HEA
DER
SHEA
RM
AX P
ANEL
VER
TIC
AL N
AIL
ING
USE
16d
GVS
FO
R(T
YP.
)
1" MAX.(25.4 MM)
NO
TED
BEL
OW
. M
IN. H
OLE
CEN
TER
PO
ST
BOTT
OM
BLO
CKI
NG
MEM
BER
SPAC
ING
IS F
OU
R T
IMES
HO
LE D
IA.
END
PO
STS:
SH
ALL
NO
T BE
FIEL
D D
RIL
LED
BEL
OW
BO
TTO
MBL
OC
KIN
G M
EMBE
R
(TYP
.)
the
3/4"
nut
s &
bolts
and
pro
ceed
with
nor
mal
inst
alat
ion
met
hods
.ho
les
(whi
le ro
tate
ing
the
hold
-dow
n) to
pro
perly
alig
n. R
etig
hten
an
chor
bol
t. P
ush
the
pane
l in
and
out w
ithin
the
slot
ed a
ncho
r bol
t th
e H
old-
dow
n D
evic
e to
the
post
, and
atta
ch to
the
hold
-dow
n PR
OC
EDU
RE:
Loo
sen
the
3/4"
nut
s &
bolts
that
are
use
d to
atta
ch
FIEL
D A
DJU
STM
ENT
1:
PAN
EL M
ISAL
IGN
ED IN
TH
E PL
ANE
SM
TC T
OP
PLAT
E C
ON
N.
DO
UBL
E TO
P PL
ATE
SHIM
MEM
BER
BOLT
S N
OT
CAS
T IN
PLA
NE
OF
WA
LL
OF
THE
WA
LL.
SMTC
TO
P PL
ATE
CO
NN
ECTO
RFL
USH
FAC
E - F
ILL
ALL
NAI
L H
OLE
S
DBL
2x6
PLA
TE (O
R L
ARG
ER)
O.S
.B.
THR
OU
GH
CEN
TER
LIN
E O
F AN
Y
1" (2
5.4
MM
) DIA
. FAC
TOR
YD
RIL
LED
AC
CES
S H
OLE
STY
PIC
AL IN
ALL
PO
STS
AN
D
1" (2
5.4
MM
) MAX
. DIA
. HO
LE(S
)
ALLO
WAB
LE F
IELD
BLO
CKI
NG
DR
ILLE
D H
OLE
S
O.S
.B.
BO
LTS
NO
T LE
VEL
(WA
LL N
OT
PLU
MB)
END
VIE
W
SID
E VI
EW O
F U
NLE
VEL
BASE
(EXA
GG
ERAT
ED F
OR
VIE
WIN
G)
LIN
ETR
IM
1/4"
max
.
SHIM
SST
EEL
PLAC
E ST
EEL
SHIM
S U
P TO
1/4
" TH
ICK
UN
DER
PO
ST T
HAT
NEE
DS
TO B
E SH
IMM
ED
DRAWING:
PROJECT: OWNER / APPLICANT:
SHEE
T N
UM
BER:
CHEC
KED
BY
:
DRA
WN
BY
:
VER
SIO
N 0
3-01
-08
N
UTS
(B) O
N H
OLD
-DO
WN
BO
LTS
(C)
H
OLD
-DO
WN
AN
CH
OR
BO
LT (E
).
W
ITH
WA
LL L
INE.
8. T
HR
EAD
NU
TS (H
) ON
TO A
NC
HO
R B
OLT
S (A
).
6. R
ETIG
HTE
N N
UTS
(B) O
N T
HE
HO
LD-D
OW
N
HO
LD-D
OW
N A
NC
HO
R B
OLT
(E).
5. A
TTAC
H H
OLD
-DO
WN
DEV
ICE
(D) T
O T
HE
CIP
1. P
LAC
E PA
NEL
OVE
R T
OP
OF
CIP
AN
CH
OR
BO
LTS
(A).
2. W
HER
E P
ANEL
REA
LIG
NM
ENT
IS R
EQ
UIR
ED, L
OO
SEN
3. M
OV
E PA
NEL
IN O
R O
UT
WIT
HIN
N T
HE
LIM
ITS
OF
THE
4. R
OTA
TE H
OLD
-DO
WN
DEV
ICE
(D) T
O A
LIG
N W
ITH
CIP
S
LOTT
ED A
NC
HO
R B
OLT
HO
LES
TO A
LIG
N P
ANEL
7. P
LAC
E O
UT-
OF-
PLAN
E BE
ARIN
G P
LATE
S (F
) OVE
R
TO
P O
F AN
CH
OR
BO
LTS
(A) A
ND
NA
IL (G
) IN
PLA
CE
D ECFGH
B
B
OLT
S (C
)
CO
ND
ITIO
NS
DO
EXI
ST, I
T IS
TH
E R
ESPO
NSI
BILI
TY O
F TH
E C
ON
TRAC
TOR
TO
NO
TIFY
TH
E D
ESIG
N P
ROFE
SSIO
NAL,
AR
CHIT
ECT,
3. T
HIS
PR
ODU
CT,
IS P
ART
OF
AN O
VER
ALL
LATE
RAL
FO
RCE
RES
ISTI
NG
SYS
TEM
, WHI
CH
SH
ALL
ALW
AYS
BE R
EVIE
WED
AND
SPE
CIF
IED
TIO
N O
F TH
IS P
RO
DU
CT
AND
/ OR
AN
Y C
OM
PON
ENT
AFFE
CTI
NG
TH
E SH
EAR
MAX
SYS
TEM
. IF
ANY
DIS
CREP
ANC
IES
AND/
OR
AD
VER
SE4.
TH
E C
ON
TRAC
TOR
IS R
ESPO
NSI
BLE
TO V
ERIF
Y AL
L D
IMEN
SIO
NS,
CO
ND
ITIO
NS,
AN
D PO
SITI
ON
S O
F SH
EAR
MAX
, ETC
., PR
IOR
TO
INST
ALLA
-
1. S
HEA
RM
AX
PAN
ELS
ARE
MAN
UFA
CTU
RED
AN
D T
RAD
EMAR
KED
BY S
HEAR
TR
ANSF
ER S
YSTE
MS,
INC
.
BY A
DES
IGN
PR
OFE
SSIO
NAL
, AR
CH
ITEC
T, A
ND
/OR
EN
GIN
EER
OF
REC
OR
D AN
D A
PPR
OVE
D B
Y RE
QUI
RED
AG
ENCI
ES.
5. S
HEA
R T
RAN
SFER
SYS
TEM
S, IN
C. R
ESER
VES
THE
RIG
HT
TO C
HAN
GE
DES
IGN
S, S
PEC
IFIC
ATIO
NS,
AN
D/O
R M
OD
ELS
AND/
OR
EN
GIN
EER
OF
REC
OR
D, A
ND
/OR
LO
CAL
BU
ILD
ING
OFF
ICIA
LS F
OR
CLA
RIF
ICAT
ION
S PR
IOR
TO
CO
NSTR
UCTI
ON
.
2. S
HEA
RM
AX P
ANEL
S AR
E LI
STED
BY
ICC-
ES IN
EVA
LUAT
ION
REP
ORT
ESR
-172
7.
6. 1
-INC
H =
25.
4 M
M -
DRA
WIN
GS
NOT
TO S
CAL
EW
ITH
OU
T N
OTI
CE
OR
LIA
BILI
TY.
MAX
NO
.
REV
ISIO
N
DA
TE
1
ORG
INIA
L
2/0
1/06
ICC
ESR-
1727
TM
SM 2 - 2015 IBC OR 2016 CBC PAGE 13 ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE.
SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016
PAN
EL F
RO
NT
SEC
TIO
N B
-B
#1 D
FL B
ON
DED
- TY
P.
#1 D
FL B
ON
DED
- TY
P.
SEC
TIO
N B
-B
SEC
TIO
N A
-A
EEC
6
PAN
EL F
RO
NT
SEC
TIO
N A
-ASE
CTI
ON
A-A
OR
CO
NC
RET
ETO
P O
F S
LAB
2 x
STU
D W
ALL
OR
CO
LLE
CTO
RPL
ATE
, HEA
DER
,D
OU
BLE
TOP
CU
RB
PAN
ELSH
EAR
MAX
SM
TC T
OP
OF
PAN
EL C
ON
NEC
TOR
PER
TA
BLE
1, O
R A
LTER
NAT
EA
S S
PEC
IFIE
D
MIN
. EAC
H S
IDE
WO
OD
ME
MB
ERC
ON
TIN
UO
US
FR
OM
TOP
OF
PAN
EL T
OTO
P O
F PA
NEL
HO
LD-
DO
WN
. N
AIL
WIT
H 1
0d
STAG
GER
ED.
CO
MM
ON
S @
6" O
.C.
MIN
. EAC
H S
IDE
ON
E 2x
6 D
F #2
STD
E 2x
6ST
D
DO
UBL
E TO
PP
LATE
, HEA
DER
,O
R C
OLL
ECTO
R
SEC
TIO
N B
-B
STD
STD
STD
EC
OSB
- TY
P.
E
STD
STD
ON
E 2x
4 D
F #3
DO
UB
LE T
OP
PLA
TE, H
EAD
ER,
OR
CO
LLEC
TOR
STD
2x6
SEC
TIO
N B
-BEC
8 E
STD
CST
DE
2x6
STD
SEC
TIO
N B
-B
#2 D
FL N
AILE
D -
TYP.
2x4
PER
DET
AIL
5 O
R A
LTE
RN
ATE
RIM
BLO
CK
TRE
ATED
PLA
TE S
HA
LL B
E D
ESI
GN
ED B
Y O
THER
S.
2. S
HEA
R T
RAN
SFE
R F
RO
M T
HE
RIM
BLO
CK
TO
TH
E R
IM J
OIS
T O
RN
OTE
S: 1
. TH
E R
IM B
LOC
K SU
PPO
RTS
FLO
OR
SH
EAT
HIN
G A
DJ.
TO
PAN
EL.
FRO
NT
VIEW
A
FDN
./GR
AD
E BE
AM
CO
NST
. & S
TD.)
NAI
LED
- TY
P.#3
DFL
MIN
. (IN
CLU
DES
STU
D,
E 2
x4S
TD
BAC
K VI
EW
STD
CE
2x4
STD
SEC
TIO
N A
-A
FLO
OR
SH
EETI
NG
STE
M W
ALL
TREA
TED
PLA
TE
RIM
JO
IST
BOTT
OM
PLA
TE
SEC
TIO
N A
-A
RIM
BLO
CK
BEAMWAL
LS
TEM
GR
AD
ED
RAG
MEM
BER
CO
LLE
CTO
R O
RD
OU
BLE
TO
P P
LATE
,C
ON
NE
CTO
R A
S SP
EC
IFIE
D
AFL
OO
R S
HEE
TIN
GSH
EET
ING
JOIS
T
ATT
ACH
MEN
TJO
IST
FLO
OR
SH
EAR
MAX
RIM
JO
IST
PAN
EL
TRE
ATED
PLA
TESM
TC T
OP
PLA
TE C
ON
NEC
TOR
JOIS
T
EC6 C
EC6 E
SHEARMAX DETAILS
ANY
NE
CE
SSAR
Y S
TRA
PPIN
G O
R B
RAC
ING
.FR
AMIN
G C
ON
ECTI
ON
S, B
LOC
KIN
G, A
ND
ENG
INE
ER O
F R
ECO
RD
SH
ALL
SPE
CIF
Y
TYP
ICA
L FO
UN
DAT
ION
AN
D B
ASE
PLA
TE IN
STAL
LATI
ON
CH
ECK
ED B
Y:
SHEE
T N
UM
BER
:
DR
AW
N B
Y:
SM3
VER
TIC
AL
SU
PPO
RT
FRAM
ING
i.e.
NA
ILIN
G, S
CR
EWS,
BO
LTS,
FAC
E M
OU
NTE
D L
EDG
ER
FRAM
ING
BY
OTH
ER
SJO
IST
ATTA
CH
ME
NT
SEC
TIO
N A
-A
JOIS
T
2x6
HE
AD M
EMBE
R(S
)
FIEL
D-IN
STAL
LED
TO F
ILL
VOID
2x4
SILL
ME
MBE
R(S
)
TWO
2x4
(EC
8)O
NE
2x4
(EC
6) O
R
FILL
HEA
D M
EMBE
RAT
TAC
HED
BE
FOR
EC
ON
NEC
TOR
STO
P O
F PA
NEL
TO F
ILL
VOID
.
IS A
DD
ED.
1st F
LOO
R
B
2x K
ING
STU
D A
ND
1st F
LOO
R IS
RE
CO
MM
END
ED.
2x F
ULL
HE
IGH
T FR
OM
TO
P
NAI
LS 6
" O.C
. AN
D S
TAG
GER
ED.
ATTA
CH
EA
CH
WIT
H 1
0d C
OM
MO
N
PLAT
E O
N E
AC
H S
IDE
ATO
F H
OLD
-DO
WN
TO
TO
P
A
FIEL
D-IN
STAL
LED
DO
UBL
E T
OP
PLA
TE, H
EAD
ER,
OR
CO
LLEC
TOR
EC8
EC8 C EC
8E
EC6
2nd
FLO
OR
B
DR
AG
ME
MBE
R
OTH
ERS
FRAM
ING
BY
STR
AP
BY O
THER
S
SH
EAR
MAX
PAN
EL
AFULL
HEI
GH
T
STR
UC
TUR
AL C
ALC
SAT
TAC
H L
ED
GER
PER
BA
SH
EAR
MAX
2x K
ING
STU
D A
ND
1st F
LOO
R IS
REC
OM
MEN
DE
D.
2x F
ULL
HEI
GH
T FR
OM
TO
P
NAI
LS 6
" O.C
. AN
D S
TAG
GER
ED.
ATT
AC
H E
AC
H W
ITH
10d
CO
MM
ON
PLA
TE O
N E
ACH
SID
E AT
OF
HO
LD-D
OW
N T
O T
OP
STR
AP B
Y O
THE
RS
3x B
LOC
K - A
S N
EED
ED
FRAM
ING
BY
OTH
ER
S
DR
AG
MEM
BER
BA
1st F
LOO
RB
Y O
THER
S
2nd
FLO
OR
PAN
EL
OWNER / APPLICANT:
@ E
ACH
4x
VER
TIC
AL R
ECO
MM
EMD
EDA
TTAC
H W
ITH
4 1
0d (0
.148
" x 3
") FA
CE
MO
UN
TED
LED
GER
FULL
HEI
GH
T
SEC
TIO
N B
-B
1st F
LOO
R
2nd
FLO
OR
FRAM
ING
BY
OTH
ERS
JOIS
T
PROJECT:
DRAWING:
SM
TC E
AC
H S
IDE
MAX
TIO
N O
F TH
IS P
RO
DU
CT
AND
/ OR
AN
Y C
OM
PON
ENT
AFFE
CTI
NG
TH
E SH
EAR
MAX
SYS
TEM
. IF
AN
Y D
ISC
REP
ANC
IES
AND
/OR
AD
VER
SE
6. 1
-INC
H =
25.
4 M
M -
DR
AW
ING
S N
OT
TO S
CAL
E
AND
/OR
EN
GIN
EER
OF
REC
OR
D, A
ND
/OR
LO
CAL
BU
ILD
ING
OFF
ICIA
LS F
OR
CLA
RIF
ICAT
ION
S P
RIO
R T
O C
ON
STR
UC
TIO
N.
5. S
HEA
R T
RAN
SFER
SYS
TEM
S, IN
C. R
ESER
VES
THE
RIG
HT
TO C
HA
NG
E D
ESIG
NS,
SPE
CIF
ICAT
ION
S, A
ND
/OR
MO
DEL
S
CO
ND
ITIO
NS
DO
EXI
ST, I
T IS
TH
E R
ESPO
NSI
BILI
TY O
F TH
E C
ON
TRAC
TOR
TO
NO
TIFY
TH
E D
ESIG
N P
RO
FESS
ION
AL, A
RC
HIT
ECT,
SEC
TIO
N A
-AA
12"M
AX
3"
NO
CU
T ZO
NE
TRIM
TO
FIT
SLO
PE
TRIM
-AB
LE H
EAD
SHE
ARM
AX P
ANEL
DBL
TO
P PL
ATE
CO
NC
RE
TE C
UR
BTO
P O
F SL
AB O
R
TRIM
TO
FIT
SLO
PE
TRIM
-ABL
E H
EAD
SHE
ARM
AX P
ANEL
2 x
STU
D W
ALL
DR
AG M
EMB
ERC
OLL
EC
TOR
OR
DO
UB
LE T
OP
PLA
TE,
CO
NN
EC
TOR
AS
SPE
CIF
IED
SMTC
TO
P P
LATE
CO
NN
ECTO
RPE
R D
ETA
IL 5
OR
ALT
ER
NAT
E
WIT
HO
UT
NO
TIC
E O
R L
IABI
LITY
.
AS
MA
RKE
D IN
RED
SHE
ARM
AX
PAN
ELSH
EAR
MAX
PAN
EL
TRIM
ABL
E H
EAD
AR
EA -
3/12
PIT
CH
MAX
. TR
IM T
OM
ATE
WIT
H B
OT.
OF
DB
L. T
OP
PLA
TE O
R C
OLL
ECTO
R
A
NO
CU
T ZO
NE
VER
SIO
N 0
3-01
-08
NO
.
REV
ISIO
N
DA
TE
1
O
RGIN
IAL
6/0
1/05
ICC
ESR
-172
7
2. S
HEA
RM
AX P
ANEL
S AR
E LI
STED
BY
ICC
-ES
IN E
VALU
ATIO
N R
EPO
RT
ESR
-172
7.
4. T
HE
CO
NTR
ACTO
R IS
RES
PO
NSI
BLE
TO V
ERIF
Y AL
L D
IMEN
SIO
NS,
CO
ND
ITIO
NS,
AN
D P
OSI
TIO
NS
OF
SHEA
RM
AX, E
TC.,
PRIO
R T
O IN
STAL
LA-
BY A
DES
IGN
PR
OFE
SSIO
NAL
, AR
CH
ITE
CT,
AN
D/O
R E
NG
INEE
R O
F R
ECO
RD
AN
D A
PPR
OVE
D B
Y R
EQU
IRED
AG
ENC
IES.
3. T
HIS
PR
OD
UC
T, IS
PAR
T O
F AN
OVE
RAL
L LA
TER
AL F
OR
CE
RES
ISTI
NG
SYS
TEM
, WH
ICH
SH
ALL
ALW
AYS
BE R
EVIE
WED
AN
D S
PEC
IFIE
D
1. S
HEA
RM
AX
PAN
ELS
ARE
MAN
UFA
CTU
RED
AN
D T
RAD
EMAR
KED
BY
SHEA
R T
RAN
SFER
SYS
TEM
S, IN
C.
ATM
SM 3 - 2015 IBC OR 2016 CBC PAGE 14 ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE.
SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016
ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION November 01, 2008
SHEARMAX FIELD REP ASSISTING WITH
INSTALLATION OF CUSTOM HEIGHT TRIM-FIT PANEL.
(SM24–168 –TF)
24’’x14’ 0’’ Panel FIELD TRIMMED TO A 3/12 Pitch
STANDARD PANEL WIDTHS: 16”, 18”, 21”, 24”, 28”,
32”, 36”, 42”, 48”
STANDARD PORTAL PANELS: 78”, 90”
7’ & 8’ GARAGE DOOR ON 6” STEM WALL
NOMINAL PANEL HEIGHTS: 8’, 9’, 10’, 11’, 12’, 13’, 14’,
15’, 16’, 17’, 18’, 19’, 20’
CUSTOM PANEL HEIGHTS: 6’ to 20’
ANY STANDARD WIDTH - NO EXTRA COST / NO MINIMUM QTY. REQUIRED / 3-5 WORKING DAYS
TRIM-FIT: UP TO 3/12 PITCH
ANY PANEL HEIGHT 6’ T0 20’ WITH ANY STANDARD WIDTH 16” TO 48”
SECOND STORY & RAISED FLOOR APPLICATIONS
NO WOOD SHRINKAGE ISSUES NO WOOD CRUSHING
NO PANEL LOAD REDUCTION
IAS ACCREDITED TEST FACILITY
MANUFACTURING PLANT
COMPATIBILITY
SHEARMAX panel proprietary components are individually tested to insure capacities well beyond the ultimate shear demand of the panel as a system. Though not required by ICC-ES under AC 130, this testing enables SHEARMAX panels to exhibit excellent reliability and increased ductile response.
When resisting lateral loading, SHEARMAX Panels respond similar to a standard sheathed code shear wall making them highly compatible. Both demonstrate the ability to produce inelastic response and still carry load beyond the code allowable drift while resisting catastrophic failure.
Through our testing of competitors prefabricated lateral force resisting systems we have observed catastrophic failures (hold-down anchor bolts, hold-downs, posts, and sheeting separation), in addition to, lack of ductility or the inability to produce an inelastic response.
It is our opinion that combining a competitor’s prefabricated lateral force resisting systems with standard sheathed code shear walls or a SHEARMAX panel system is NOT RECOMMENDED. A subsequent failure of any non-ductile systems would overload any remaining ductile systems and result in catastrophic structural failure.