16
TOLL 877 743-2762 FREE Shear Transfer Systems, Inc. 9845 Santa Fe Ave East, Hesperia, CA 92345 www.shearmax.com 760-949-4191 phone 760-948-5330 fax 2015 IBC 2016 CBC 2017 LABC ICC-ES ESR-1727 ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES ESR 1727 FRONT COVER 1. PANEL CONFIGURATIONS 2. PORTAL PANEL 78” & 90” VALUES 3. STANDARD PANELS 8’ to 11’ VALUES 4. STANDARD PANELS 12’ to 15’ VALUES 5. STANDARD PANELS 16’ to 19’ VALUES 6. STANDARD PANELS 20’ & NOTES 7. ALTERNATIVES FOR MORE LOAD 8. WIND LOADS 9. COMPRESSION LOADS POSTS 10. COMPRESSION LOADS PANEL 11. PANEL SPECIFYING 12. DETAILS 2012 IBC SM1 13. DETAILS 2012 IBC SM2 14. DETAILS 2012 IBC SM3 BACK COVER ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR ALL-INCLUSIVE DETAILS AND USAGE. SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016

ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

TOLL 877 743-2762 FREE

Shear Transfer Systems, Inc. 9845 Santa Fe Ave East, Hesperia, CA 92345

www.shearmax.com

760-949-4191 phone 760-948-5330 fax

2015 IBC 2016 CBC

2017 LABC

ICC-ES ESR-1727

ENGINEER AND ARCHITECT REFERENCE GUIDE TO

ICC-ES ESR 1727

FRONT COVER

1. PANEL CONFIGURATIONS 2. PORTAL PANEL 78” & 90” VALUES 3. STANDARD PANELS 8’ to 11’ VALUES 4. STANDARD PANELS 12’ to 15’ VALUES 5. STANDARD PANELS 16’ to 19’ VALUES 6. STANDARD PANELS 20’ & NOTES 7. ALTERNATIVES FOR MORE LOAD 8. WIND LOADS 9. COMPRESSION LOADS POSTS 10. COMPRESSION LOADS PANEL 11. PANEL SPECIFYING 12. DETAILS 2012 IBC SM1 13. DETAILS 2012 IBC SM2 14. DETAILS 2012 IBC SM3 BACK COVER

ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR ALL-INCLUSIVE DETAILS AND USAGE.

SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016

Page 2: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

SHEARMAX PANEL TYPES AND OPTIONS (REFERENCE FIGURE 2 & 3) (Wa = Wn – 3”) PANEL ASPECT RATIO = Ha / Wa = αp

PAGE 1

ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION November 01, 2008

OUT-OF-PLANE AND COMPRESSION LOADS MUST BE CHECKED. The Project Engineer/Governing Agencies may use their discretion/engineering judgment regarding post bracing. The accompanying color-codes designate recommended post options (found throughout this guide) for post sections not fully braced by other methods. Recommendations are based upon full compression load on post(s) from in-plane racking shear and/or load on post(s) from typical out-of-plane wind loads. Post sections may need to be braced or increased for other conditions.

POST OPTIONS ARE DESIGNED TO INCREASE THE STANDARD POST CROSS SECTION OF A STANDARD SHEARMAX PANEL AND INCREASE THE CAPACITY OF THE POST FOR COMPRESSION LOADING AND/OR OUT OF PLANE LOADING. SEE PAGE 6 FIGURE 3 FOR MORE INFORMATION.

RECOMMENDED OPTIONS

STD NO OPTION

OPTIONS RARELY REQUIRED 6-10 ft (Not Shown)

STD 2x4 OPTION

2x4 NAIL-ON OPTION RECOMMENDED - 10-11 ft

STD 2x6 OPTION

2x6 NAIL-ON OPTION RECOMMENDED - 11-14 ft

EC6 OPTION

EC6 OPTION RECOMMENDED 14-17 ft

EC8 OPTION

EC8 OPTION RECOMMENDED 17-20 ft

STD 2x4 OPTION STD 2X6 OPTION EC6 OPTION EC8 OPTION NAIL-ON NAIL-ON

FIELD MODIFIED BY OTHERS FACTORY ATTACHED

Page 3: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

NOMINAL GARAGE DOOR HEIGHT

7’ GARAGE DOOR 6” CURB

8’ GARAGE DOOR 6” CURB

SHEARMAX PORTAL PANELS: REFERENCE TABLE 1 ‘PORTAL’ panels are sized for garage doors heights of 7’ & 8’ when used with a 6” stem wall.

Any SHEARMAX panel may be used in a portal or non-portal condition without a change in load capacity. The allowable loads for Portal Panels do not use a moment connection between the top of panel and the supported header. All SHEARMAX

panels have ‘stand alone’ values. Portal reductions required by agencies such as L.A. City or L.A. County are not required. PANEL DIMENSIONS ALLOWABLE IN-PLANE SHEAR LOAD AND DRIFT

2015 IBC Seismic (R=6.5) 2015 IBC Wind SHEAR (Lbs.) SHEAR (Lbs.)

SHEAR-MAX

MODEL THICK-NESS

WIDTH NOMINAL

ACTUAL HEIGHT

LBS / FT TOTAL DRIFT (IN.)

LBS / FT TOTAL DRIFT (IN.)

SM16-78 16'' 990 1320 0.37 1275 1700 0.53 SM18-78 18’’ 1100 1650 0.36 1425 2135 0.53 SM21-78 21'' 1230 2155 0.35 1565 2735 0.52 SM24-78 24'' 1065 2125 0.28 1330 2655 0.40 SM28-78 28'' 1085 2530 0.25 1355 3165 0.36 SM32-78 32'' 1100 2935 0.23 1375 3670 0.34 SM36-78 36'' 1115 3340 0.22 1390 4175 0.32 SM42-78 42'' 1130 3950 0.22 1410 4935 0.31 SM48-78

3 ½”

48''

6'-6" (78")

S T D

S T D

1140 4555 0.21

S T D

S T D

1425 5695 0.31 SM16-90 16'' 815 1085 0.42 1050 1400 0.60 SM18-90 18'' 910 1365 0.41 1180 1770 0.60 SM21-90 21'' 1030 1805 0.40 1345 2350 0.60 SM24-90 24'' 1065 2125 0.37 1330 2655 0.53 SM28-90 28'' 1085 2530 0.33 1355 3165 0.47 SM32-90 32'' 1100 2935 0.30 1375 3670 0.43 SM36-90 36'' 1115 3340 0.28 1390 4175 0.41 SM42-90 42'' 1130 3950 0.26 1410 4935 0.38 SM48-90

3 ½”

48''

7’-6" (90")

S T D

S T D 1140 4555 0.25

S T D

S T D 1425 5695 0.37

- Hold-down Anchor tension load = 9,500 Lbs. - Alternate tension loads may be calculated based on (Vall or Vdesign) x αP. - Wood post to wood post width (minus hold-downs) is 3 in. less than nominal width dimension. - For increased out-of-plane loads and/or vertical loads Refer to Figure 3 (page 6) for Alternate Panel Options. - For custom height load values round up to next foot, or call for exact value

PANEL MODEL DESIGNATIONS: REFERENCE FIGURE 1 (for all panels)

SM XX - YY — CUSTOM HT — TF — EC(6 or 8) (CUSTOM OPTION CODES)

SM SHEARMAX PRODUCT IDENTIFIER XX NOMINAL OVERALL WIDTH (in.)—Outside-to-Outside of hold-downs YY HEIGHT (Feet or Inches)—Nominal Panel Height - when specified in ‘Feet’

Actual Panel Height - when specified in ‘Inches’

CUSTOM HT CUSTOM HEIGHT—Panel Heights not listed in Table 2. Net Height may be specified.

TF TRIM-FIT (TF) PANEL—Short point height required. 3:12 Maximum Slope

EC6 FACTORY ENHANCED CROSS-SECTION—EC6 (5-in net thickness) EC8 FACTORY ENHANCED CROSS-SECTION—EC8 (7 ½-in net thickness)

Example – SM 24 – 10 SHEARMAX 24” WIDE – 10’ NOMINAL WALL OR PANEL HEIGHT (9’ 9 ¾” NET PANEL HEIGHT)

Example – SM 24 - 175 ¾” – TF – EC6 or SM 24 – 15 (175 ¾”) – TF – EC6 SHEARMAX 24” WIDE – CUSTOM OPTIONS: NET HEIGHT 175 ¾” – TRIM FIT (175 ¾” SHORT POINT) – EC6 OPTION

PAGE 2 ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES

REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016

Page 4: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

NOMIMAL HEIGHT

8’ 9’ 10’

11’

SHEARMAX STANDARD & TRIM-FIT PANELS – 8’ to 11’: REFERENCE TABLE 2 PANEL DIMENSIONS ALLOWABLE IN-PLANE SHEAR LOAD AND DRIFT

2015 IBC Seismic (R=6.5) 2015 IBC Wind SHEAR (Lbs.) SHEAR (Lbs.)

SHEAR-MAX

MODEL THICK-NESS

WIDTH NOMINAL

ACTUAL HEIGHT

LBS / FT TOTAL DRIFT (IN.) LBS / FT TOTAL

DRIFT (IN.)

SM16-8 16” 695 925 0.38 875 1165 0.52 SM18-8 18” 785 1175 0.38 995 1490 0.52 SM21-8 21” 895 1565 0.37 1140 1995 0.52 SM24-8 24” 985 1970 0.36 1265 2525 0.52 SM28-8 28” 1080 2520 0.35 1355 3165 0.51 SM32-8 32” 1100 2935 0.32 1375 3670 0.47 SM36-8 36” 1115 3340 0.30 1390 4175 0.44 SM42-8 42” 1130 3950 0.28 1410 4935 0.41 SM48-8

3 ½”

48”

7'-9 ¾” (93 ¾”)

S T D

S T D

1140 4555 0.27

S T D

S T D

1425 5695 0.39 SM16-9 16” 595 790 0.43 745 990 0.59 SM18-9 18” 670 1005 0.43 845 1270 0.59 SM21-9 21” 770 1350 0.42 985 1720 0.59 SM24-9 24” 855 1710 0.41 1095 2190 0.59 SM28-9 28” 945 2200 0.40 1200 2805 0.59 SM32-9 32” 975 2600 0.37 1220 3250 0.53 SM36-9 36” 985 2960 0.34 1235 3700 0.49 SM42-9 42” 1000 3500 0.31 1250 4375 0.45 SM48-9

3 ½”

48”

8’-9 ¾” (105 ¾”)

S T D

S T D

1010 4035 0.29

S T D

S T D

1260 5045 0.43 SM16-10 16” 510 680 0.48 640 855 0.65 SM18-10 18” 580 870 0.47 735 1100 0.65 SM21-10 21” 675 1180 0.47 855 1500 0.65 SM24-10 24” 750 1500 0.46 960 1920 0.65 SM28-10 28” 830 1940 0.44 1075 2505 0.65 SM32-10 32” 875 2335 0.42 1095 2920 0.61 SM36-10 36” 885 2660 0.38 1110 3325 0.56 SM42-10 42” 900 3145 0.35 1125 3930 0.50 SM48-10

3 ½”

48”

9'-9 ¾” (117 ¾”)

S T D

S T D

910 3630 0.32

S T D

S T D

1135 4535 0.47

SM16-11 16” 445 595 0.54 560 745 0.72 SM18-11 18” 510 765 0.53 645 965 0.72 SM21-11 21” 590 1035 0.51 755 1320 0.72 SM24-11 24” 665 1325 0.50 850 1700 0.72 SM28-11 28” 740 1725 0.49 955 2225 0.72 SM32-11 32” 795 2120 0.47 995 2650 0.69 SM36-11 36” 805 2410 0.43 1005 3015 0.62 SM42-11 42” 815 2850 0.39 1020 3565 0.56 SM48-11

3 ½”

48”

10'-9 ¾” (129 ¾”)

2 X 4

N A I L - O N 825 3290 0.36

2 X 4

N A I L - O N 1030 4115 0.52

For custom height load values round up to next foot, or call if exact value needed. 2012 IBC Seismic CODE VALUES 2012 IBC Wind CODE VALUES

STD OPTIONS RARELY REQUIRED – 6-10 ft 2x4 2x4 NAIL-ON OPT. RECOMMENDED -10-11 ft 2x6 2x6 NAIL-ON OPT. RECOMMENDED - 11-14 ft EC6 EC6 OPTION RECOMMENDED - 14-17 ft EC8 EC8 OPTION RECOMMENDED - 17-20 ft

OUT-OF-PLANE AND COMPRESSION LOADS MUST BE CHECKED. The Project Engineer/Governing Agencies may use their discretion/engineering judgment regarding post bracing. The accompanying color-codes designate recommended post options (found throughout this guide) for post sections not fully braced by other methods. Recommendations are based upon full compression load on post(s) from in-plane racking shear and/or load on post(s) from typical out-of-plane wind loads. Post sections may need to be braced or increased for other conditions.

PAGE 3

ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016

Page 5: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

NOMINAL HEIGHT

12’

13’

14’ 15’

SHEARMAX STANDARD & TRIM-FIT PANELS – 12’ to 15’: REFERENCE TABLE 2 PANEL DIMENSIONS ALLOWABLE IN-PLANE SHEAR LOAD AND DRIFT

2015 IBC Seismic (R=6.5) 2015 IBC Wind SHEAR (Lbs.) SHEAR (Lbs.)

SHEAR-MAX

MODEL THICK-NESS

WIDTH NOMINAL

ACTUAL HEIGHT

LBS / FT TOTAL

DRIFT (IN.) LBS / FT TOTAL

DRIFT (IN.)

SM16-12 16” 390 520 0.58 490 655 0.79 SM18-12 18” 450 675 0.58 570 855 0.79 SM21-12 21” 525 920 0.56 670 1175 0.79 SM24-12 24” 590 1180 0.55 760 1515 0.79 SM28-12 28” 660 1545 0.54 855 1995 0.79 SM32-12 32” 720 1920 0.52 910 2425 0.77 SM36-12 36” 735 2210 0.48 920 2760 0.70 SM42-12 42” 745 2610 0.43 935 3265 0.62 SM48-12

3 ½”

48”

11'-9 ¾” (141 ¾”)

2 X 6

N A I L - O N 755 3010 0.39

2 X 6

N A I L - O N 940 3765 0.57

SM16-13 16” 350 465 0.64 440 585 0.85 SM18-13 18” 400 600 0.63 505 760 0.85 SM21-13 21” 470 825 0.61 600 1050 0.85 SM24-13 24” 535 1065 0.60 680 1360 0.85 SM28-13 28” 600 1395 0.59 770 1800 0.85 SM32-13 32” 655 1740 0.57 840 2235 0.85 SM36-13 36” 680 2035 0.54 850 2545 0.78 SM42-13 42” 690 2410 0.48 860 3010 0.69 SM48-13

3 ½”

48”

12’-9 ¾” (153 ¾”)

2 X 6

N A I L - O N 695 2775 0.43

2 X 6

N A I L - O N 870 3470 0.63

SM16-14 16” 310 415 0.69 390 520 0.92 SM18-14 18” 360 540 0.68 455 685 0.92 SM21-14 21” 425 745 0.67 540 945 0.92 SM24-14 24” 480 960 0.65 615 1230 0.92 SM28-14 28” 540 1265 0.63 700 1635 0.92 SM32-14 32” 595 1585 0.62 770 2055 0.92 SM36-14 36” 630 1890 0.60 785 2360 0.87 SM42-14 42” 635 2230 0.52 795 2790 0.76 SM48-14

3 ½”

48”

13'-9 ¾” (165 ¾”)

2 X 6

N A I L - O N 645 2575 0.48

2 X 6

N A I L - O N 805 3220 0.69

SM16-15 16” 280 375 0.74 355 470 0.99 SM18-15 18” 325 490 0.73 410 615 0.99 SM21-15 21” 385 675 0.72 490 855 0.99 SM24-15 24” 440 875 0.70 560 1115 0.99 SM28-15 28” 495 1155 0.68 640 1490 0.99 SM32-15 32” 545 1450 0.67 705 1880 0.99 SM36-15 36” 585 1750 0.65 735 2200 0.96 SM42-15 42” 595 2080 0.58 745 2600 0.84 SM48-15

3 ½”

48”

14'-9 ¾” (177 ¾”)

E C 6

E C 6

600 2405 0.52

E C 6

E C 6

750 3005 0.76 For custom height load values round up to next foot, or call if exact value needed. 2012 IBC Seismic CODE VALUES 2012 IBC Wind CODE VALUES

STD OPTIONS RARELY REQUIRED – 6-10 ft 2x4 2x4 NAIL-ON OPT. RECOMMENDED - 10-11 ft 2x6 2x6 NAIL-ON OPT. RECOMMENDED - 11-14 ft EC6 EC6 OPTION RECOMMENDED - 14-17 ft EC8 EC8 OPTION RECOMMENDED - 17-20 ft

OUT-OF-PLANE AND COMPRESSION LOADS MUST BE CHECKED. The Project Engineer/Governing Agencies may use their discretion/engineering judgment regarding post bracing. The accompanying color-codes designate recommended post options (found throughout this guide) for post sections not fully braced by other methods. Recommendations are based upon full compression load on post(s) from in-plane racking shear and/or load on post(s) from typical out-of-plane wind loads. Post sections may need to be braced or increased for other conditions.

PAGE 4

ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016

Page 6: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

NOMINAL HEIGHT

16’ 17’ 18’ 19’

SHEARMAX STANDARD & TRIM-FIT PANELS – 16’ to 19’: REFERENCE TABLE 2 PANEL DIMENSIONS ALLOWABLE IN-PLANE SHEAR LOAD AND DRIFT

2015 IBC Seismic (R=6.5) 2015 IBC Wind SHEAR (Lbs.) SHEAR (Lbs.)

SHEAR-MAX

MODEL THICK-NESS

WIDTH NOMINAL

ACTUAL HEIGHT

LBS / FT TOTAL DRIFT (IN.) LBS / FT TOTAL

DRIFT (IN.)

SM16-16 16” 255 340 0.79 320 425 1.05 SM18-16 18” 295 445 0.78 375 560 1.05 SM21-16 21” 350 615 0.77 445 780 1.05 SM24-16 24” 400 800 0.75 510 1020 1.05 SM28-16 28” 455 1060 0.73 585 1365 1.05 SM32-16 32” 500 1335 0.72 645 1725 1.05 SM36-16 36” 540 1615 0.70 690 2065 1.05 SM42-16 42” 555 1950 0.63 695 2440 0.92 SM48-16

3 ½”

48”

15'-9 ¾” (189 ¾”)

E C 6

E C 6

565 2250 0.57

E C 6

E C 6

705 2815 0.82 SM16-17 16” 235 310 0.85 295 390 1.12 SM18-17 18” 270 405 0.84 340 510 1.12 SM21-17 21” 320 560 0.81 410 715 1.12 SM24-17 24” 370 735 0.80 470 935 1.12 SM28-17 28” 420 975 0.78 540 1255 1.12 SM32-17 32” 460 1230 0.76 595 1590 1.12 SM36-17 36” 500 1495 0.75 645 1940 1.12 SM42-17 42” 525 1835 0.69 655 2295 1.00 SM48-17

3 ½”

48”

16’-9 ¾” (201 ¾”)

E C 6

E C 6

530 2115 0.62

E C 6

E C 6

660 2645 0.90

SM16-18 16” - - - 265 355 1.19 SM18-18 18” 245 370 0.88 310 465 1.19 SM21-18 21” 295 515 0.86 375 655 1.19 SM24-18 24” 340 675 0.85 430 860 1.19 SM28-18 28” 385 900 0.83 495 1160 1.19 SM32-18 32” 430 1140 0.81 555 1475 1.19 SM36-18 36” 460 1385 0.80 600 1800 1.19 SM42-18 42” 495 1730 0.75 620 2165 1.09 SM48-18

3 ½”

48”

17'-9 ¾” (213 ¾”)

E C 8

E C 8

500 1995 0.67

E C 8

E C 8

625 2495 0.97 SM16-19 16” - - - 245 325 1.25 SM18-19 18” 225 340 0.93 285 430 1.25 SM21-19 21” 270 475 0.92 345 605 1.25 SM24-19 24” 315 625 0.90 400 795 1.25 SM28-19 28” 360 835 0.88 460 1075 1.25 SM32-19 32” 400 1060 0.86 515 1370 1.25 SM36-19 36” 430 1295 0.85 560 1675 1.25 SM42-19 42” 470 1640 0.81 585 2050 1.18 SM48-19

3 ½”

48”

18'-9 ¾” (225 ¾”)

E C 8

E C 8

475 1890 0.72

E C 8

E C 8

590 2365 1.05 For custom height load values round up to next foot, or call if exact value needed. 2012 IBC Seismic CODE VALUES 2012 IBC Wind CODE VALUES

STD OPTIONS RARELY REQUIRED – 6-10 ft 2x4 2x4 NAIL-ON OPT. RECOMMENDED - 10-11 ft 2x6 2x6 NAIL-ON OPT. RECOMMENDED - 11-14 ft EC6 EC6 OPTION RECOMMENDED - 14-17 ft EC8 EC8 OPTION RECOMMENDED - 17-20 ft

OUT-OF-PLANE AND COMPRESSION LOADS MUST BE CHECKED. The Project Engineer/Governing Agencies may use their discretion/engineering judgment regarding post bracing. The accompanying color-codes designate recommended post options (found throughout this guide) for post sections not fully braced by other methods. Recommendations are based upon full compression load on post(s) from in-plane racking shear and/or load on post(s) from typical out-of-plane wind loads. Post sections may need to be braced or increased for other conditions.

PAGE 5

ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016

Page 7: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

ESTDSTDESTD C

EEC8CEC8EEC8

EC8

EC6 EEC6CEC6E

EC6

STD

OSB - TYP.

STDCSTDE 2x4STD E 2x4

STD

STD 2x6

E 2x6STD STDC

STD 2x4

E 2x6

#1 DFL BONDED - TYP.

#3 DFL MIN. (INCLUDES STUD,

#2 DFL NAILED - TYP.

#1 DFL BONDED - TYP.

CONST. & STD.) NAILED - TYP.

Notes: Hold-down Anchor tension load is 9,500Lbs. Alternate tension loads may be calculated based on (Vall or Vdesign) x αP. Wood post to wood post width (less hold-downs) is 3 in. less than nominal width. Refer to Table 3, page 9 & 10, for allowable compression loads, Table 4, page 8, for maximum design wind speeds. For optional post configurations for increased out-of-plane loads and/or vertical loads refer to Figure 3 this page. Actual height for Trim-Fit (TF) Panels used in design shall equal the greatest height of the sloped panel. Refer to Figure 2 (page 1) for details of determining the (TF) Panels.

SHEARMAX STANDARD & TRIM-FIT PANELS – 20’: REFERENCE TABLE 2 PANEL DIMENSIONS ALLOWABLE IN-PLANE SHEAR LOAD AND DRIFT

2015 IBC Seismic (R=6.5) 2015 IBC Wind SHEAR (Lbs.) SHEAR (Lbs.)

SHEAR-MAX

MODEL THICK-NESS

WIDTH NOMINAL

ACTUAL HEIGHT

LBS / FT TOTAL DRIFT (IN.) LBS / FT TOTAL

DRIFT (IN.)

SM16-20 16” - - - 225 300 1.32 SM18-20 18” 210 315 0.99 265 395 1.32 SM21-20 21” 250 440 0.97 320 560 1.32 SM24-20 24” 290 580 0.95 370 740 1.32 SM28-20 28” 335 780 0.94 430 1000 1.32 SM32-20 32” 370 990 0.92 480 1275 1.32 SM36-20 36” 400 1205 0.89 520 1565 1.32 SM42-20 42” 440 1545 0.87 555 1945 1.28 SM48-20

3 ½”

48”

19'-9 ¾” (237 ¾”)

E C 8

E C 8 450 1795 0.78

E C 8

E C 8 560 2245 1.13

For custom height load values round up to next foot, or call for exact value. 2012 IBC Seismic CODE VALUES 2012 IBC Wind CODE VALUES

STD OPTIONS RARELY REQUIRED – 6-10 ft 2x4 2x4 NAIL-ON OPT. RECOMMENDED - 10-11 ft 2x6 2x6 NAIL-ON OPT. RECOMMENDED - 11-14 ft EC6 EC6 OPTION RECOMMENDED - 14-17 ft EC8 EC8 OPTION RECOMMENDED - 17-20 ft

OUT-OF-PLANE AND COMPRESSION LOADS MUST BE CHECKED. The Project Engineer/Governing Agencies may use their discretion/engineering judgment regarding post bracing. The accompanying color-codes designate recommended post options (found throughout this guide) for post sections not fully braced by other methods. Recommendations are based upon full compression load on post(s) from in-plane racking shear and/or load on post(s) from typical out-of-plane wind loads. Post sections may need to be braced or increased for other conditions.

STD

2x4

2x6

EC6

EC8

Center post included on all Panels when Nominal Panel Width > 28”. Field-Modified: 1 - 2x4 DF STUD or STANDARD min. continuous from top of panel to top of hold-down with 2 rows of 10d commons @ 6” o.c. staggered. Field-Modified: 1 - 2x6 DF #2 min. continuous from top of panel to top of hold-down with 2 rows of 10d commons @ 6” o.c. staggered.

EC6-Factory-Fabricated: 1 - 2x4 DF #1 bonded (glued) & screwed to Standard Posts EC8-Factory-Fabricated: 2 - 2x4 DF #1 bonded (glued) & screwed to Standard Posts

20’

PAGE 6

ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016

NOMINAL HEIGHT

NA I L -ON

NA I L -ON

Page 8: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

Second Story Applications Want to achieve similar shear capacity as squash block systems but have concerns about wood shrinkage? Simplify the load path and take advantage of custom heights by using tall panels from concrete to second floor top plate, or, if one is not enough, consider using back-to-back panels instead of stacked panels. The first floor panel experiences no reduced shear capacity or “R” value due to the second story panel load. Since panel widths and locations can be independent of one another, design flexibility is almost limitless.

Back-to-Back Panels Panel heights or vertical load from above causing the need for an EC6 or EC8 option? Consider placing panels Back-to-Back for twice the shear capacity for only about 25% more cost than EC8 option

SUGGESTED ALTERNATIVES TO ACHIEVE MORE LOAD

PAGE 7

ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION November 01, 2008

Page 9: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

Custom Heights NO EXTRA CHARGE

2015 IBC CONVERSION: [(MPH)2 X 1.6]0.5 2009 IBC MAXIMUM BASIC WIND SPEED(3-Sec. Gust) for SHEARMAX Panels(mph):

PANEL CONFIGURATION (Refer to Figure 3-Page 6) / EXPOSURE CATEGORIES (Refer to IBC Section 1609.4) STANDARD AND TRIM-FIT (TF) PANEL (16 inches on center stud spacing) / values assume no stud along side of panel – 1st stud 16’’ away

Field Modified Post Enhancement Factory Fabricated Post Enhancement STD 2x4 OPTION (NAIL-ON) 2x6 OPTION (NAIL-ON) EC6 OPTION EC8 OPTION

NOMINAL HEIGHT

B C D B C D B C D B C D B C D

8’ 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 9’ 170 160 150 170 170 160 170 170 170 170 170 170 170 170 170

10’ 150 140 120 170 150 140 170 160 150 170 170 170 170 170 170 11’ 130 120 100 140 130 120 150 140 130 170 170 160 170 170 170 12’ 110 110 90 130 110 100 130 120 110 170 160 150 170 170 170 13’ 100 90 — 110 100 90 120 100 90 160 150 140 170 170 170 14’ 90 — — 100 90 — 100 90 85 150 140 120 170 170 160 15’ -— — — 90 — — 90 85 — 140 130 110 170 170 150 16’ — — — — — — — — — 130 110 100 170 150 140 17’ — — — — — — — — — 120 100 90 160 140 130 18’ — — — — — — — — — 100 90 85 150 130 120 19’ — — — — — — — — — 90 85 — 140 120 110 20’

— — — — — — — — — 90 — — 130 120 110 ‘Value’ SUPPLEMENTAL BRACING RECOMMENDED

— BRACING REQUIRED

OUT-OF-PLANE AND COMPRESSION LOADS MUST BE CHECKED.The Project Engineer/Governing Agencies may use their discretion/engineering judgment regarding post bracing. The accompanying color-codes designate recommended post options (found throughout this guide) for post sections not fully braced by other methods. Recommendations are based upon full compression load on post(s) from in-plane racking shear and/or load on post(s) from typical out-of-plane wind loads. Post sections may need to be braced or increased for other conditions.

SPACING TYP16" O.C.

SPACING TYP16" O.C.

PAGE 8

ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016

Tall Walls

Brace taller panels with adjacent walls to save the cost of an EC6 or EC8 option.

Column with draft stop bracing panel shown at left.

Raised Floor

Achieve about 30% more shear capacity over squash block systems by using a custom height panel from stem wall to top plate. Also allows for use in cripple wall situations.

Page 10: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

ALLOWABLE COMPRESSION LOAD PER VERTICAL POST: REFERENCE TABLE 3

ALLOWABLE NET COMPRESSION LOADS (Lbs.) STD 2x4 OPTION (NAIL-ON) 2x6 OPTION (NAIL-ON) EC6 OPTION EC8 OPTION NOMINAL

HEIGHT END POST

CENTER POST

END POST

CENTER POST

END POST

CENTER POST

END POST

CENTER POST

END POST

CENTER POST

78” * 6,550 10,300 6,550 10,300 6,550 10,300 9,830 13,600 13,115 16,850 8’ 3,800 10,300 5,850 10,300 6,550 10,300 9,830 13,600 13,115 16,850 9’ 1,700 8,200 3,600 8,200 6,550 8,200 9,830 13,600 13,115 16,850

10’ 100 6,650 1750 6,650 6,550 6,650 9,830 13,600 13,115 16,850 11’ — 5,450 250 5,450 6,550 5,450 9,050 13,100 13,115 16,850 12’ — 4,550 — 4,550 5,950 4,550 6,850 11,100 13,115 16,850 13’ — 3,850 — 3,850 4,200 3,850 5,000 9,500 13,115 16,850 14’ — 3,300 — 3,300 2,750 3,300 3,450 8,200 13,115 16,850 15’ — — — — — — 2,200 7,150 12,000 15,150 16’ — — — — — — 1,100 6,300 10,000 13,450 17’ — — — — — — 200 5,550 8,250 12,000 18’ — — — — — — — 4,950 6,750 10,750 19’ — — — — — — — 4,450 5,450 9,700 20’

— — — — — — — — 4,300 8,750 ALLOWABLE NET COMPRESSION LOADS ARE THE MAXIMUM VERTICAL LOADS THAT CAN BE ADDED TO THE POSTS WHEN THE MAXIMUM ALLOWABLE SHEAR LOAD IS APPLIED TO THE TOP OF THE PANEL. CAUTION: SOME MANUFACTURES LIST GROSS ALLOWABLE VERTICAL LOADS IN ICC-ES REPORTS. THESE GROSS ALLOWABLE LOADS MUST BE REDUCED BY THE VERTICAL LOAD IN THE POSTS RESULTING FROM PANEL OVERTURNING.

‘Value’ SUPPLEMENTAL BRACING RECOMMENDED * IF PANEL IS FULLY BRACED BY OTHERS USE 78” VALUES — BRACING REQUIRED

PANEL WIDTH32" to 48"

PANEL WIDTH

LOAD

LOAD

LOAD

LOAD

LOAD

16" to 28"

END

POST TYP.

CEN

TER PO

ST TYP.

END

POST TYP.

END

POST TYP.

END

POST TYP.

O.S.B.PANE(TYP.)

O.S.B.PANE(TYP.)

O.S.B.PANE(TYP.)

**LOAD

**LOAD

**LOAD

** DISTRIBUTE LOAD TO POSTS USING STATICS

PANEL WIDTH32" to 48"

PANEL WIDTH16" to 28"

O.S.B.PANE(TYP.)

O.S.B.PANE(TYP.)

O.S.B.PANE(TYP.)

LOAD

LOAD

END

POST TYP.

CEN

TER PO

ST TYP.

END

POST TYP.

LOAD

NO NO NOLOAD

LOAD

LOAD

END

POST TYP.

END

POST TYP.

HEAD

LOAD

LOAD

TRIM-FITTRIM-FIT

HEAD

PAGE 9

ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION November 01, 2008

Page 11: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

OUT-OF-PLANE AND COMPRESSION LOADS MUST BE CHECKED. The Project Engineer/Governing Agencies may use their discretion/engineering judgment regarding post bracing. The accompanying color-codes designate recommended post options (found throughout this guide) for post sections not fully braced by other methods. Recommendations are based upon full compression load on post(s) from in-plane racking shear and/or load on post(s) from typical out-of-plane wind loads. Post sections may need to be braced or increased for other conditions.

STD- OPTIONS RARELY REQUIRED – 6-10 ft

2x4 2x4 NAIL-ON OPTION RECOMMENDED – 10-11 ft

2x6 2x6 NAIL-ON OPTION RECOMMENDED – 11-14 ft

EC6 EC6 OPTION RECOMMENDED – 14-17 ft

EC8 EC8 OPTION RECOMMENDED – 17-20 ft

ESTDSTDESTD C

EEC8CEC8EEC8

EC8

EC6 EEC6CEC6E

EC6

STD

OSB - TYP.

STDCSTDE 2x4STD E 2x4

STD

STD 2x6

E 2x6STD STDC

STD 2x4

E 2x6

#1 DFL BONDED - TYP.

#3 DFL MIN. (INCLUDES STUD,

#2 DFL NAILED - TYP.

#1 DFL BONDED - TYP.

CONST. & STD.) NAILED - TYP.

PORTAL BEAM CONDITION

END

POST TYP.

END

POST TYP.

CEN

TER PO

ST TYP.

PANEL WIDTH32" to 48"

(TYP.)PANEO.S.B.

(TYP.)PANEO.S.B.O.S.B.

PANE(TYP.)

PANEL WIDTH16" to 28"

END

POST TYP.

END

POST TYP.

LOAD

PORTAL BEAM PORTAL BEAM

LOAD

ALLOWABLE COMPRESSION LOAD PER PANEL: REFERENCE TABLE 3

ALLOWABLE NET COMPRESSION LOADS (Lbs.) STD 2x4 OPTION (NAIL-ON) 2x6 OPTION (NAIL-ON) EC6 OPTION EC8 OPTION NOMINAL

HEIGHT PANEL WIDTH 16” to 28”

PANEL WIDTH 32” to 48”

PANEL WIDTH 16” to 28”

PANEL WIDTH32” to 48”

PANEL WIDTH 16” to 28”

PANEL WIDTH 32” to 48”

PANEL WIDTH 16” to 28”

PANEL WIDTH 32” to 48”

PANEL WIDTH 16” to 28”

PANEL WIDTH 32” to 48”

78” * 13,100 23,400 13,100 23,400 13,100 23,400 19,660 33,260 25,740 42,590 8’ 10,350 20,650 12,400 22,700 13,100 23,400 19,660 33,260 25,740 42,590 9’ 8,250 16,450 10,150 18,350 13,100 21,300 19,660 33,260 25,740 42,590

10’ 5,675 12,325 8,300 14,950 13,100 19,750 19,660 33,260 25,740 42,590 11’ 4,725 10,175 5,950 11,400 13,100 18,550 18,880 31,980 25,740 42,590 12’ 4,025 8,575 4,900 9,450 12,500 17,050 16,680 27,780 25,740 42,590 13’ 3,475 7,325 4,250 8,100 10,750 14,600 14,450 23,950 25,740 42,590 14’ 3,025 6,325 3,700 7,000 9,300 12,600 11,875 20,075 25,740 42,590 15’ — — — — — — 9,700 16,850 24,625 39,775 16’ — — — — — — 7,800 14,100 22,625 36,075 17’ — — — — — — 6,200 11,750 20,575 32,575 18’ — — — — — — 5,400 10,350 18,025 28,775 19’ — — — — — — 4,875 9,325 15,775 25,475 20’

— — — — — — — — 13,750 22,500 ALLOWABLE NET COMPRESSION LOADS ARE THE MAXIMUM VERTICAL LOADS THAT CAN BE ADDED TO THE POSTS WHEN THE MAXIMUM ALLOWABLE SHEAR LOAD IS APPLIED TO THE TOP OF THE PANEL. CAUTION: SOME MANUFACTURES LIST GROSS ALLOWABLE VERTICAL LOADS IN ICC-ES REPORTS. THESE GROSS ALLOWABLE LOADS MUST BE REDUCED BY THE VERTICAL LOAD IN THE POSTS RESULTING FROM PANEL OVERTURNING.

‘Value’ SUPPLEMENTAL BRACING RECOMMENDED * IF PANEL IS FULLY BRACED BY OTHERS USE 78” VALUES — BRACING REQUIRED

STD

EC6

EC8

2 X 4

2 X 6

PAGE 10

ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION November 01, 2008

N A I L - O N N A I L - O N

Page 12: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

SUGGESTED SPECIFICATION STANDARDS

SM16T

SM11 & 2

1 & 2SM1

4,6,7

8

BASIC PANEL INSTALL DETAILS ON SITE PANEL ADJUSTMENTS

RAISED FLOOR DETAILS

16'' WIDE PANEL WITH A STANDARD 8' WALL

3 & 5

SM16-8

FOUNDATION PLAN

FRAMING PLAN

SM24-10 CUSTOM HEIGHT (FIELD VERIFY)

3 & 5

24'' WIDE PANEL WITH A CUSTOM HEIGHT

FRAMING PLAN

SM32-13-W / STD 2X6 (NAIL-ON)

3 & 5

32'' WIDE PANEL WITH A STANDARD 13' WALL

FRAMING PLAN

3 & 5

FRAMING PLANAND WITH STD 2X6 NAIL-ON OPTION

ORSM24-111'' CUSTOM HEIGHT

36'' WIDE TRIM-FIT (TF) PANEL - 110" LOW POINT

SM36-110" (LOW POINT) - TFOR

SM36-11 CUSTOM HEIGHT-TF (FIELD VERIFY)

TRIM-FIT (TF) PANEL PANEL CONFIGURATIONS / POST SECTIONS(POST OPTIONS: STD 2x4, STD 2x6, EC6, EC8)

DETAIL KEY

SM XX - YYSM SHEARMAX PRODUCT IDENTIFIERXX NOMINAL OVERALL WIDTH (Inches)YY NOMINAL HEIGHT * (Feet)

SM XX T

T REUSABLE TEMPLATE IDENTIFIERXX BASE PLATE (SYSTEM) WIDTHSM SHEARMAX PRODUCT IDENTIFIER

SPECIFICATION IN BLACK - COMMENTARY IN GREEN

1 1/2" BOTTOM PLATE PLUS THE STANDARD STUD

8' = 92 1/4", 9' = 104 1/4"

PLUS 12" TO 140 1/4" FOR EVERY FOOT PAST 12'

YY IF NET PANEL HEIGHT IS NOT SPECIFIED ININCHES THEN CODE THE HEIGHT IN NOMINAL

XX NOMINAL OVERALL WIDTH (Inches)SM SHEARMAX PRODUCT IDENTIFIERSM XX - YY

YY NOMINAL HEIGHT OR CUSTOM HEIGHTXX NOMINAL OVERALL WIDTH (Inches)SM SHEARMAX PRODUCT IDENTIFIERSM XX - YY - ' POST OPTION '

FRAMING PLAN

48'' WIDE PANEL RAISED FLOOR 122" NET HEIGHT

83 & 5

PROPER ANCHOR BOLT LENGTH ANDMODEL CODE IS FOUND IN DETAIL

1SM1

FEET (ROUNDED UP) AND ADD 'FIELD VERIFY'

W / STD 2X4 NIAL-ONW / STD 2X6 NAIL-ONEC6EC8

POST OPTION TYPES:

YY THE HEIGHT OF A TRIM-FIT IS SPECIFIED 2 WAYS:

SM XX - YY - TFSM SHEARMAX PRODUCT IDENTIFIERXX NOMINAL OVERALL WIDTH (Inches)

(SEE BELOW)TF TRIM-FIT IDENTIFIER

2) WHEN A 'NET' HEIGHT (Inches) IS USEDIT IS AT THE LOW POINT OF THE SLOPE

1) WHEN THE 'NOMINAL' HEIGHT (Feet) ISUSED IT IS AT THE PANELS' HIGH POINT(ROUNDED UP TO WHOLE FEET) AND

TYPICAL FOR NEW POUR CONDITIONS

* NOMINAL WALL HEIGHT IN FEET ASSUMES:

STANDARD STUD LENGTH:10' = 116 1/4", 11' = 128 1/4", 12' = 140 1/4"

SM24-11 CUSTOM HEIGHT (FIELD VERIFY)

SM24-122'' CUSTOM HEIGHTOR

FEET (ROUNDED UP) AND ADD ' FIELD VERIFY '.

SM SHEARMAX PRODUCT IDENTIFIERXX NOMINAL OVERALL WIDTH (Inches)

INCHES THEN CODE THE HEIGHT IN NOMINALYY IF NET PANEL HEIGHT IS NOT SPECIFIED IN

SM XX - YY

THE PANEL HEIGHT FOR RAISED FLOOR ISSPECIFIED THE SAME AS A CUSTOM HEIGHT

16'' TEMPLATE FOR 16" PANEL

FRAMING PLAN (PLAN VIEW)

FOUNDATION PLAN (PLAN VIEW)

STANDARD PANEL

REUSABLE TEMPLATE

CUSTOM HEIGHTS

RAISED FLOOR

POST OPTIONSTRIM FIT

SPECIFICATION IN BLACK - COMMENTARY IN GREEN SPECIFICATION IN BLACK - COMMENTARY IN GREEN

1 - HIGH POINT

2 - LOW POINT

' FIELD VERIFY ' IS ADDED

YY SPECIFICATION FOR TRIM FIT PANELS

BASIC CONCRETE DEAILS 3 & 5SM2 SM2

SM311

SM39

SM310

SM3TWO-STORY CONDITION

SM2 SM2

SM29

SM3 SM210

SM3

SM2 SM3

PAGE 11

ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION November 01, 2008

Page 13: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

SHEA

RM

AX T

EMPL

ATE

5/8"

Ø X

10"

AN

CH

OR

BO

LT

5/8"

Ø A

NC

HO

R B

OLT

NU

T

SHEA

RM

AX T

EMPL

ATE

SHEA

RM

AX H

OLD

DO

WN

CO

UPL

ER

LOW

ER N

UT(B

OLT

LEN

GTH

)

SHEA

RM

AX H

OLD

DO

WN

BO

LT

CO

LOR

CO

DED

SLE

EVE

WAS

HER

(DIS

POSA

BLE)

NYL

ON

BO

LT (D

ISPO

SABL

E)

SHEA

RM

AX H

OLD

DO

WN

FOO

TIN

G A

S R

EQU

IRED

(2) P

ER T

EMPL

ATE

BOLT

ASS

EMBL

Y

QTY

. VAR

IES

PER

SIZ

E

QTY

. VAR

IES

PER

SIZ

E

W/ 5

" EM

BED

MEN

T

W/ 5

" EM

BED

MEN

T

SHEA

RM

AX T

EMPL

ATE

5/8"

Ø X

10"

AN

CH

OR

BO

LTS

5/8"

Ø X

10"

AN

CH

OR

BO

LTS

SHEA

RM

AX H

OLD

DO

WN

FOO

TIN

G A

S R

EQU

IRED

2X4

SCR

EED

BO

ARD

(2) P

ER T

EMPL

ATE

BOLT

ASS

EMBL

Y

FOR

M B

OAR

D S

IZE

VAR

IES

DR

AW

N B

Y:

CH

ECK

ED B

Y:

SHEE

T N

UM

BER

:

SM1

OWNER / APPLICANT:PROJECT:

DRAWING:

CO

ND

ITIO

NS D

O E

XIST

, IT

IS T

HE

RES

PON

SIBI

LITY

OF

THE

CO

NTRA

CTO

R T

O N

OTI

FY T

HE

DES

IGN

PRO

FESS

ION

AL, A

RC

HITE

CT,

3. T

HIS

PR

ODU

CT,

IS P

ART

OF

AN O

VER

ALL

LATE

RAL

FORC

E R

ESIS

TIN

G S

YSTE

M, W

HIC

H SH

ALL

ALW

AYS

BE R

EVIE

WED

AND

SPE

CIF

IED

TIO

N O

F TH

IS P

RO

DUC

T AN

D/ O

R A

NY

CO

MPO

NEN

T AF

FEC

TIN

G T

HE S

HEA

RMAX

SYS

TEM

. IF

ANY

DIS

CREP

ANCI

ES A

ND/O

R A

DVE

RSE

4. T

HE C

ON

TRAC

TOR

IS R

ESPO

NSI

BLE

TO V

ERIF

Y AL

L DI

MEN

SIO

NS, C

ON

DIT

IONS

, AN

D PO

SITI

ONS

OF

SHEA

RMAX

, ETC

., PR

IOR

TO IN

STAL

LA-

2x U

P TO

14

1228

30SM

30F

BOAR

D

ASTM

A44

9

SM60

FSM

54F

SM48

FSM

42F

SM36

F

3/4"

DIA

. AN

CH

OR

BO

LT

2x U

P TO

20

2x U

P TO

26

2x U

P TO

32

2x U

P TO

38

2x U

P TO

44

SHEA

RM

AX A

NC

HO

R N

UT

DET

AIL

18 24 30 36 42

34 40 46 52 586054484236

EMBE

DM

ENT

SHEA

R C

ON

E

1 3/

4" R

OU

ND

NU

T1

1/2"

SQ

UAR

E O

R

13"

7/8" MIN.

SM26

FSM

22F

CO

DE

BOLT

STO

CK

BOLT

LEN

GTH

S - C

UST

OM

LEN

GTH

S AR

E AV

AILA

BLE

3/4"

DIA

. AST

M A

449,

STU

D T

YPE

BOLT

(TYP

.)SH

EAR

MAX

CIP

HO

LD-D

OW

N A

NCH

OR

BO

LT

2x U

P TO

10

SIZE

OF

FOR

M2n

d PO

UR

MAX

IMU

M

THIC

KNES

S

8 42x

UP

TO 6

MAX

IMU

M

BOAR

D(S

)EM

BED

MEN

TTO

TAL

BOLT

20 242622

LEN

GTH

BOLT

TOTA

L

BOLT

LEN

GTH

- N

OT

PAN

ELD

EPTH

DET

ERM

INES

AN

CHO

RSH

EAR

CO

NE

EMBE

DM

ENT

FOR

M

SIZE

(WID

TH O

R H

EIG

HT)

1. S

HEA

RM

AX

PAN

ELS

ARE

MAN

UFA

CTU

RED

AN

D TR

ADEM

ARKE

D BY

SHE

AR T

RAN

SFER

SYS

TEM

S, IN

C.

BY A

DES

IGN

PR

OFE

SSIO

NAL

, ARC

HITE

CT,

AN

D/O

R E

NG

INEE

R O

F R

ECO

RD

AN

D AP

PRO

VED

BY

REQ

UIR

ED A

GEN

CIE

S.

5. S

HEA

R T

RAN

SFER

SYS

TEM

S, IN

C. R

ESER

VES

THE

RIG

HT

TO C

HAN

GE

DESI

GN

S, S

PECI

FIC

ATIO

NS,

AN

D/O

R M

ODE

LSAN

D/O

R E

NG

INEE

R O

F R

ECO

RD, A

ND/

OR

LO

CAL

BUIL

DIN

G O

FFIC

IALS

FO

R C

LAR

IFIC

ATIO

NS

PRIO

R TO

CO

NST

RUC

TIO

N.

2. S

HEA

RM

AX P

ANEL

S AR

E LI

STED

BY

ICC

-ES

IN E

VALU

ATIO

N R

EPO

RT

ESR

-172

7.

6. 1

-INC

H =

25.

4 M

M -

DRA

WIN

GS

NO

T TO

SC

ALE

WIT

HOU

T N

OTI

CE

OR

LIA

BILI

TY.

2

REV

ISED

01/

01/0

8

2

REV

ISED

03/

20/0

6

1

ORG

INIA

L

02/

01/0

6

NO

.

REV

ISIO

N

DA

TE

MAX

ICC

ESR-

1727

TM

SM 1 - 2015 IBC OR 2016 CBC PAGE 12 ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE.

SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016

Page 14: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

SHEA

RM

AX P

ANEL

A35'

s O

N S

TEPP

EDFA

CE

- REF

ER T

O

DBL

2x6

(MIN

) PLA

TE

SMTC

, LTP

4 O

R A

LT. C

ON

N. A

SSP

ECIF

IED

ON

FLU

SH F

ACE

SM

TC T

OP

PLAT

E C

ON

NEC

TOR

DR

AG M

EMBE

RC

OLL

ECTO

R O

RD

OU

BLE

TOP

PLAT

E,

SH

EAR

MAX

PAN

EL

2 x

STU

D W

ALL

CO

NC

RET

E C

UR

BTO

P O

F SL

AB O

R

STA

ND

AR

D W

ALL

IN

STA

LLAT

ION

PER

TAB

LE 1

OR

ALT

ERN

ATE

AS

SPE

CIF

IED

DO

UBL

E TO

P PL

ATE

SMTC

, LTP

4 O

R A

LT. C

ON

N. A

SSP

ECIF

IED

ON

FLU

SH F

ACES

CO

NN

. AS

SPEC

IFIE

D

AS S

PEC

IFIE

D

TABL

E 1

OR

2x K

ING

STU

D

ALTE

RN

ATE

SMTC

PER

NO

TE:

REF

ER T

O P

LAN

FO

R P

RO

PER

GR

ADE

BEAM

REQ

UIR

EMEN

TS

SEC

TIO

N A

-A

TYPI

CA

L P

OR

TAL

CO

ND

ITIO

N &

C

OR

NE

R C

ON

DIT

ION

SH

OW

N

PAN

EL F

RO

NT

A

STEM

WA

LL

FOU

ND

ATIO

N

PAN

EL F

RO

NT

(DES

IGN

BY

OTH

ERS)

PON

Y SH

EAR

WA

LL C

ON

DIT

ION

OPT

ION

AL J

AMB

2x F

ILLE

R P

IEC

ESU

GG

EST

ED

SH

EAR

MAX

PAN

EL

DO

UBL

E TO

P PL

ATE,

CO

LLE

CTO

R O

RD

RAG

MEM

BER

SHEA

RM

AX P

ANEL

ON

FLU

SH F

ACES

HEA

DER

7 1/

2"

SMTC

CO

NN

ECTO

R (N

TS)

SPEC

IFIE

D O

N F

LUSH

FAC

ES

MTC

, LTP

4 O

R A

LT. C

ON

N. A

S

16"

24

(ON

E SM

TC O

R T

WO

A35

's P

ER

SHEA

RM

AX P

ANEL

HEA

DER

OR

BEA

M

SMTC

, LTP

4 O

R A

LT.

A35'

s O

N S

TEPP

ED F

ACE

-R

EFER

TO

TAB

LE 1

6x B

EAM

OR

HEA

DER

28"

32"

36"

42"

48"

5443

18"

21"

24"

2 332

WH

EN A

SH

IM IS

INST

ALLE

D, F

ILL

ALL

TRIA

NG

ULA

RH

OLE

S W

ITH

16d

SIN

KER

NAI

LS -

REF

ER T

O D

ETAI

L 6

FAC

ILIT

ATE

INST

ALLI

NG

SM

TC C

ON

NEC

TOR

PIEC

E M

AY B

E FO

LDED

90

OU

T-O

F-PL

ANE

TO6 1/2"

O

2. M

IXIN

G O

F SM

TC, A

35 &

LTP

4

3. O

NE

SMTC

EQ

UAL

S TW

O A

35

4. N

AIL

SM

TC's

WIT

H 1

0d C

OM

MO

N

LTP4

DO

NO

T EQ

UAL

ON

E SM

TC

[(0.1

48) x

1 1

/2"]

OR

16d

GV

OR

LTP

4 BU

T TW

O A

35 O

R8 9 10 12

SID

E M

INIM

UM

)

IS A

LLO

WED

5 6 6 7

TABL

E 1

TABL

E 1

- TO

P-O

F-PA

NE

L C

ON

NEC

TOR

S

1. A

PPLY

EVE

NLY

AC

RO

SS P

ANEL

NO

TES:

A

SM2

PAN

EO

.S.B

.

(TY

P.)

EXC

EPT

AS N

OTE

D, I

N A

NY

LOC

ATIO

NO

NE

RO

UN

D H

OLE

SHIM

PAN

EFR

AMIN

G M

EMBE

R E

XCEP

T AS

PAN

EA3

5'S

ON

STE

PPED

FAC

EBO

TH F

LUSH

FAC

ES

WH

EN S

HIM

MIN

G P

ANEL

TO

TO

P PL

ATE

SMTC

PLA

CE

MEN

T IS

CR

ITIC

ALA

LL N

AILS

MU

ST H

AVE

PRO

PER

EN

BED

MEN

T IN

TO W

OO

D F

IBER

S

1. A

LL N

AIL

HO

LES

MU

ST

BE F

ILLE

D A

ND

FIR

MLY

EM

BED

DE

D IN

TO S

OLI

D W

OO

D W

ITH

10

NAI

LS M

IN.

2. A

LL D

IAM

ON

D S

HAP

PED

HO

LES

MU

ST B

E FI

LLED

WIT

H 1

6d G

VS W

HEN

USE

D A

S PA

RT

OF

INTO

PAN

EL H

EAD

AN

D 9

NAI

LS M

IN. I

NTO

DBL

TO

P PL

ATE

PER

SM

TC C

ON

NEC

TOR

.

SHIM

REQ

UIR

ED N

O. O

F N

AILS

PER

SM

TC.

NO

TES:

3. A

LL P

ANEL

S M

AY B

E TR

IMM

ED 1

/4" T

OP

AND

/OR

BO

TTO

M

SEC

TIO

N B

-B

CO

NN

ECTO

R B

OTH

SID

ESFI

LL A

LL N

AIL

HO

LES

SMTC

TO

P P

LATE

SHEA

RM

AX P

ANEL

4x H

EAD

ER/B

EAM

SHEA

RM

AX P

ANEL

WID

TH =

WID

TH O

F BE

AM/H

EAD

ERTH

ICKN

ESS

= 1

1/2

" MAX

.SH

IM M

EMBE

RSH

IM M

EMBE

R

SHIM

MEM

BER

WID

TH =

WID

TH O

F BE

AM/H

EAD

ERTH

ICK

NES

S =

1 1/

2" M

AX.

SHEA

RM

AXPA

NEL

OSB

PAN

EA

35'S

ON

STE

PPED

FAC

EU

SE 1

6d G

VS F

OR

VER

TIC

AL

NAI

LIN

G

SHEA

RM

AX P

ANEL

BELO

W

FOR

ALL

PAN

EL W

IDTH

S:AN

Y O

R A

LL O

SB P

ANE

S M

AY H

AVE

ON

ER

OU

ND

HO

LE IN

AN

Y LO

CAT

ION

AS

SHO

WN

. HO

LE M

UST

NO

T PE

NET

RAT

EAN

Y FR

AMIN

G M

EMBE

R.

PAN

EO

.S.B

.

(TYP

.)

ON

LY

LIM

ITS

OF

TYPI

CAL

FLU

SH F

ACE

- FIL

L A

LL N

AIL

HO

LES

SMTC

TO

P PL

ATE

CO

NN

ECTO

R

6x (O

R L

ARG

ER) B

EAM

/HEA

DER

SHEA

RM

AX P

ANEL

VER

TIC

AL N

AIL

ING

USE

16d

GVS

FO

R(T

YP.

)

1" MAX.(25.4 MM)

NO

TED

BEL

OW

. M

IN. H

OLE

CEN

TER

PO

ST

BOTT

OM

BLO

CKI

NG

MEM

BER

SPAC

ING

IS F

OU

R T

IMES

HO

LE D

IA.

END

PO

STS:

SH

ALL

NO

T BE

FIEL

D D

RIL

LED

BEL

OW

BO

TTO

MBL

OC

KIN

G M

EMBE

R

(TYP

.)

the

3/4"

nut

s &

bolts

and

pro

ceed

with

nor

mal

inst

alat

ion

met

hods

.ho

les

(whi

le ro

tate

ing

the

hold

-dow

n) to

pro

perly

alig

n. R

etig

hten

an

chor

bol

t. P

ush

the

pane

l in

and

out w

ithin

the

slot

ed a

ncho

r bol

t th

e H

old-

dow

n D

evic

e to

the

post

, and

atta

ch to

the

hold

-dow

n PR

OC

EDU

RE:

Loo

sen

the

3/4"

nut

s &

bolts

that

are

use

d to

atta

ch

FIEL

D A

DJU

STM

ENT

1:

PAN

EL M

ISAL

IGN

ED IN

TH

E PL

ANE

SM

TC T

OP

PLAT

E C

ON

N.

DO

UBL

E TO

P PL

ATE

SHIM

MEM

BER

BOLT

S N

OT

CAS

T IN

PLA

NE

OF

WA

LL

OF

THE

WA

LL.

SMTC

TO

P PL

ATE

CO

NN

ECTO

RFL

USH

FAC

E - F

ILL

ALL

NAI

L H

OLE

S

DBL

2x6

PLA

TE (O

R L

ARG

ER)

O.S

.B.

THR

OU

GH

CEN

TER

LIN

E O

F AN

Y

1" (2

5.4

MM

) DIA

. FAC

TOR

YD

RIL

LED

AC

CES

S H

OLE

STY

PIC

AL IN

ALL

PO

STS

AN

D

1" (2

5.4

MM

) MAX

. DIA

. HO

LE(S

)

ALLO

WAB

LE F

IELD

BLO

CKI

NG

DR

ILLE

D H

OLE

S

O.S

.B.

BO

LTS

NO

T LE

VEL

(WA

LL N

OT

PLU

MB)

END

VIE

W

SID

E VI

EW O

F U

NLE

VEL

BASE

(EXA

GG

ERAT

ED F

OR

VIE

WIN

G)

LIN

ETR

IM

1/4"

max

.

SHIM

SST

EEL

PLAC

E ST

EEL

SHIM

S U

P TO

1/4

" TH

ICK

UN

DER

PO

ST T

HAT

NEE

DS

TO B

E SH

IMM

ED

DRAWING:

PROJECT: OWNER / APPLICANT:

SHEE

T N

UM

BER:

CHEC

KED

BY

:

DRA

WN

BY

:

VER

SIO

N 0

3-01

-08

N

UTS

(B) O

N H

OLD

-DO

WN

BO

LTS

(C)

H

OLD

-DO

WN

AN

CH

OR

BO

LT (E

).

W

ITH

WA

LL L

INE.

8. T

HR

EAD

NU

TS (H

) ON

TO A

NC

HO

R B

OLT

S (A

).

6. R

ETIG

HTE

N N

UTS

(B) O

N T

HE

HO

LD-D

OW

N

HO

LD-D

OW

N A

NC

HO

R B

OLT

(E).

5. A

TTAC

H H

OLD

-DO

WN

DEV

ICE

(D) T

O T

HE

CIP

1. P

LAC

E PA

NEL

OVE

R T

OP

OF

CIP

AN

CH

OR

BO

LTS

(A).

2. W

HER

E P

ANEL

REA

LIG

NM

ENT

IS R

EQ

UIR

ED, L

OO

SEN

3. M

OV

E PA

NEL

IN O

R O

UT

WIT

HIN

N T

HE

LIM

ITS

OF

THE

4. R

OTA

TE H

OLD

-DO

WN

DEV

ICE

(D) T

O A

LIG

N W

ITH

CIP

S

LOTT

ED A

NC

HO

R B

OLT

HO

LES

TO A

LIG

N P

ANEL

7. P

LAC

E O

UT-

OF-

PLAN

E BE

ARIN

G P

LATE

S (F

) OVE

R

TO

P O

F AN

CH

OR

BO

LTS

(A) A

ND

NA

IL (G

) IN

PLA

CE

D ECFGH

B

B

OLT

S (C

)

CO

ND

ITIO

NS

DO

EXI

ST, I

T IS

TH

E R

ESPO

NSI

BILI

TY O

F TH

E C

ON

TRAC

TOR

TO

NO

TIFY

TH

E D

ESIG

N P

ROFE

SSIO

NAL,

AR

CHIT

ECT,

3. T

HIS

PR

ODU

CT,

IS P

ART

OF

AN O

VER

ALL

LATE

RAL

FO

RCE

RES

ISTI

NG

SYS

TEM

, WHI

CH

SH

ALL

ALW

AYS

BE R

EVIE

WED

AND

SPE

CIF

IED

TIO

N O

F TH

IS P

RO

DU

CT

AND

/ OR

AN

Y C

OM

PON

ENT

AFFE

CTI

NG

TH

E SH

EAR

MAX

SYS

TEM

. IF

ANY

DIS

CREP

ANC

IES

AND/

OR

AD

VER

SE4.

TH

E C

ON

TRAC

TOR

IS R

ESPO

NSI

BLE

TO V

ERIF

Y AL

L D

IMEN

SIO

NS,

CO

ND

ITIO

NS,

AN

D PO

SITI

ON

S O

F SH

EAR

MAX

, ETC

., PR

IOR

TO

INST

ALLA

-

1. S

HEA

RM

AX

PAN

ELS

ARE

MAN

UFA

CTU

RED

AN

D T

RAD

EMAR

KED

BY S

HEAR

TR

ANSF

ER S

YSTE

MS,

INC

.

BY A

DES

IGN

PR

OFE

SSIO

NAL

, AR

CH

ITEC

T, A

ND

/OR

EN

GIN

EER

OF

REC

OR

D AN

D A

PPR

OVE

D B

Y RE

QUI

RED

AG

ENCI

ES.

5. S

HEA

R T

RAN

SFER

SYS

TEM

S, IN

C. R

ESER

VES

THE

RIG

HT

TO C

HAN

GE

DES

IGN

S, S

PEC

IFIC

ATIO

NS,

AN

D/O

R M

OD

ELS

AND/

OR

EN

GIN

EER

OF

REC

OR

D, A

ND

/OR

LO

CAL

BU

ILD

ING

OFF

ICIA

LS F

OR

CLA

RIF

ICAT

ION

S PR

IOR

TO

CO

NSTR

UCTI

ON

.

2. S

HEA

RM

AX P

ANEL

S AR

E LI

STED

BY

ICC-

ES IN

EVA

LUAT

ION

REP

ORT

ESR

-172

7.

6. 1

-INC

H =

25.

4 M

M -

DRA

WIN

GS

NOT

TO S

CAL

EW

ITH

OU

T N

OTI

CE

OR

LIA

BILI

TY.

MAX

NO

.

REV

ISIO

N

DA

TE

1

ORG

INIA

L

2/0

1/06

ICC

ESR-

1727

TM

SM 2 - 2015 IBC OR 2016 CBC PAGE 13 ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE.

SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016

Page 15: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

PAN

EL F

RO

NT

SEC

TIO

N B

-B

#1 D

FL B

ON

DED

- TY

P.

#1 D

FL B

ON

DED

- TY

P.

SEC

TIO

N B

-B

SEC

TIO

N A

-A

EEC

6

PAN

EL F

RO

NT

SEC

TIO

N A

-ASE

CTI

ON

A-A

OR

CO

NC

RET

ETO

P O

F S

LAB

2 x

STU

D W

ALL

OR

CO

LLE

CTO

RPL

ATE

, HEA

DER

,D

OU

BLE

TOP

CU

RB

PAN

ELSH

EAR

MAX

SM

TC T

OP

OF

PAN

EL C

ON

NEC

TOR

PER

TA

BLE

1, O

R A

LTER

NAT

EA

S S

PEC

IFIE

D

MIN

. EAC

H S

IDE

WO

OD

ME

MB

ERC

ON

TIN

UO

US

FR

OM

TOP

OF

PAN

EL T

OTO

P O

F PA

NEL

HO

LD-

DO

WN

. N

AIL

WIT

H 1

0d

STAG

GER

ED.

CO

MM

ON

S @

6" O

.C.

MIN

. EAC

H S

IDE

ON

E 2x

6 D

F #2

STD

E 2x

6ST

D

DO

UBL

E TO

PP

LATE

, HEA

DER

,O

R C

OLL

ECTO

R

SEC

TIO

N B

-B

STD

STD

STD

EC

OSB

- TY

P.

E

STD

STD

ON

E 2x

4 D

F #3

DO

UB

LE T

OP

PLA

TE, H

EAD

ER,

OR

CO

LLEC

TOR

STD

2x6

SEC

TIO

N B

-BEC

8 E

STD

CST

DE

2x6

STD

SEC

TIO

N B

-B

#2 D

FL N

AILE

D -

TYP.

2x4

PER

DET

AIL

5 O

R A

LTE

RN

ATE

RIM

BLO

CK

TRE

ATED

PLA

TE S

HA

LL B

E D

ESI

GN

ED B

Y O

THER

S.

2. S

HEA

R T

RAN

SFE

R F

RO

M T

HE

RIM

BLO

CK

TO

TH

E R

IM J

OIS

T O

RN

OTE

S: 1

. TH

E R

IM B

LOC

K SU

PPO

RTS

FLO

OR

SH

EAT

HIN

G A

DJ.

TO

PAN

EL.

FRO

NT

VIEW

A

FDN

./GR

AD

E BE

AM

CO

NST

. & S

TD.)

NAI

LED

- TY

P.#3

DFL

MIN

. (IN

CLU

DES

STU

D,

E 2

x4S

TD

BAC

K VI

EW

STD

CE

2x4

STD

SEC

TIO

N A

-A

FLO

OR

SH

EETI

NG

STE

M W

ALL

TREA

TED

PLA

TE

RIM

JO

IST

BOTT

OM

PLA

TE

SEC

TIO

N A

-A

RIM

BLO

CK

BEAMWAL

LS

TEM

GR

AD

ED

RAG

MEM

BER

CO

LLE

CTO

R O

RD

OU

BLE

TO

P P

LATE

,C

ON

NE

CTO

R A

S SP

EC

IFIE

D

AFL

OO

R S

HEE

TIN

GSH

EET

ING

JOIS

T

ATT

ACH

MEN

TJO

IST

FLO

OR

SH

EAR

MAX

RIM

JO

IST

PAN

EL

TRE

ATED

PLA

TESM

TC T

OP

PLA

TE C

ON

NEC

TOR

JOIS

T

EC6 C

EC6 E

SHEARMAX DETAILS

ANY

NE

CE

SSAR

Y S

TRA

PPIN

G O

R B

RAC

ING

.FR

AMIN

G C

ON

ECTI

ON

S, B

LOC

KIN

G, A

ND

ENG

INE

ER O

F R

ECO

RD

SH

ALL

SPE

CIF

Y

TYP

ICA

L FO

UN

DAT

ION

AN

D B

ASE

PLA

TE IN

STAL

LATI

ON

CH

ECK

ED B

Y:

SHEE

T N

UM

BER

:

DR

AW

N B

Y:

SM3

VER

TIC

AL

SU

PPO

RT

FRAM

ING

i.e.

NA

ILIN

G, S

CR

EWS,

BO

LTS,

FAC

E M

OU

NTE

D L

EDG

ER

FRAM

ING

BY

OTH

ER

SJO

IST

ATTA

CH

ME

NT

SEC

TIO

N A

-A

JOIS

T

2x6

HE

AD M

EMBE

R(S

)

FIEL

D-IN

STAL

LED

TO F

ILL

VOID

2x4

SILL

ME

MBE

R(S

)

TWO

2x4

(EC

8)O

NE

2x4

(EC

6) O

R

FILL

HEA

D M

EMBE

RAT

TAC

HED

BE

FOR

EC

ON

NEC

TOR

STO

P O

F PA

NEL

TO F

ILL

VOID

.

IS A

DD

ED.

1st F

LOO

R

B

2x K

ING

STU

D A

ND

1st F

LOO

R IS

RE

CO

MM

END

ED.

2x F

ULL

HE

IGH

T FR

OM

TO

P

NAI

LS 6

" O.C

. AN

D S

TAG

GER

ED.

ATTA

CH

EA

CH

WIT

H 1

0d C

OM

MO

N

PLAT

E O

N E

AC

H S

IDE

ATO

F H

OLD

-DO

WN

TO

TO

P

A

FIEL

D-IN

STAL

LED

DO

UBL

E T

OP

PLA

TE, H

EAD

ER,

OR

CO

LLEC

TOR

EC8

EC8 C EC

8E

EC6

2nd

FLO

OR

B

DR

AG

ME

MBE

R

OTH

ERS

FRAM

ING

BY

STR

AP

BY O

THER

S

SH

EAR

MAX

PAN

EL

AFULL

HEI

GH

T

STR

UC

TUR

AL C

ALC

SAT

TAC

H L

ED

GER

PER

BA

SH

EAR

MAX

2x K

ING

STU

D A

ND

1st F

LOO

R IS

REC

OM

MEN

DE

D.

2x F

ULL

HEI

GH

T FR

OM

TO

P

NAI

LS 6

" O.C

. AN

D S

TAG

GER

ED.

ATT

AC

H E

AC

H W

ITH

10d

CO

MM

ON

PLA

TE O

N E

ACH

SID

E AT

OF

HO

LD-D

OW

N T

O T

OP

STR

AP B

Y O

THE

RS

3x B

LOC

K - A

S N

EED

ED

FRAM

ING

BY

OTH

ER

S

DR

AG

MEM

BER

BA

1st F

LOO

RB

Y O

THER

S

2nd

FLO

OR

PAN

EL

OWNER / APPLICANT:

@ E

ACH

4x

VER

TIC

AL R

ECO

MM

EMD

EDA

TTAC

H W

ITH

4 1

0d (0

.148

" x 3

") FA

CE

MO

UN

TED

LED

GER

FULL

HEI

GH

T

SEC

TIO

N B

-B

1st F

LOO

R

2nd

FLO

OR

FRAM

ING

BY

OTH

ERS

JOIS

T

PROJECT:

DRAWING:

SM

TC E

AC

H S

IDE

MAX

TIO

N O

F TH

IS P

RO

DU

CT

AND

/ OR

AN

Y C

OM

PON

ENT

AFFE

CTI

NG

TH

E SH

EAR

MAX

SYS

TEM

. IF

AN

Y D

ISC

REP

ANC

IES

AND

/OR

AD

VER

SE

6. 1

-INC

H =

25.

4 M

M -

DR

AW

ING

S N

OT

TO S

CAL

E

AND

/OR

EN

GIN

EER

OF

REC

OR

D, A

ND

/OR

LO

CAL

BU

ILD

ING

OFF

ICIA

LS F

OR

CLA

RIF

ICAT

ION

S P

RIO

R T

O C

ON

STR

UC

TIO

N.

5. S

HEA

R T

RAN

SFER

SYS

TEM

S, IN

C. R

ESER

VES

THE

RIG

HT

TO C

HA

NG

E D

ESIG

NS,

SPE

CIF

ICAT

ION

S, A

ND

/OR

MO

DEL

S

CO

ND

ITIO

NS

DO

EXI

ST, I

T IS

TH

E R

ESPO

NSI

BILI

TY O

F TH

E C

ON

TRAC

TOR

TO

NO

TIFY

TH

E D

ESIG

N P

RO

FESS

ION

AL, A

RC

HIT

ECT,

SEC

TIO

N A

-AA

12"M

AX

3"

NO

CU

T ZO

NE

TRIM

TO

FIT

SLO

PE

TRIM

-AB

LE H

EAD

SHE

ARM

AX P

ANEL

DBL

TO

P PL

ATE

CO

NC

RE

TE C

UR

BTO

P O

F SL

AB O

R

TRIM

TO

FIT

SLO

PE

TRIM

-ABL

E H

EAD

SHE

ARM

AX P

ANEL

2 x

STU

D W

ALL

DR

AG M

EMB

ERC

OLL

EC

TOR

OR

DO

UB

LE T

OP

PLA

TE,

CO

NN

EC

TOR

AS

SPE

CIF

IED

SMTC

TO

P P

LATE

CO

NN

ECTO

RPE

R D

ETA

IL 5

OR

ALT

ER

NAT

E

WIT

HO

UT

NO

TIC

E O

R L

IABI

LITY

.

AS

MA

RKE

D IN

RED

SHE

ARM

AX

PAN

ELSH

EAR

MAX

PAN

EL

TRIM

ABL

E H

EAD

AR

EA -

3/12

PIT

CH

MAX

. TR

IM T

OM

ATE

WIT

H B

OT.

OF

DB

L. T

OP

PLA

TE O

R C

OLL

ECTO

R

A

NO

CU

T ZO

NE

VER

SIO

N 0

3-01

-08

NO

.

REV

ISIO

N

DA

TE

1

O

RGIN

IAL

6/0

1/05

ICC

ESR

-172

7

2. S

HEA

RM

AX P

ANEL

S AR

E LI

STED

BY

ICC

-ES

IN E

VALU

ATIO

N R

EPO

RT

ESR

-172

7.

4. T

HE

CO

NTR

ACTO

R IS

RES

PO

NSI

BLE

TO V

ERIF

Y AL

L D

IMEN

SIO

NS,

CO

ND

ITIO

NS,

AN

D P

OSI

TIO

NS

OF

SHEA

RM

AX, E

TC.,

PRIO

R T

O IN

STAL

LA-

BY A

DES

IGN

PR

OFE

SSIO

NAL

, AR

CH

ITE

CT,

AN

D/O

R E

NG

INEE

R O

F R

ECO

RD

AN

D A

PPR

OVE

D B

Y R

EQU

IRED

AG

ENC

IES.

3. T

HIS

PR

OD

UC

T, IS

PAR

T O

F AN

OVE

RAL

L LA

TER

AL F

OR

CE

RES

ISTI

NG

SYS

TEM

, WH

ICH

SH

ALL

ALW

AYS

BE R

EVIE

WED

AN

D S

PEC

IFIE

D

1. S

HEA

RM

AX

PAN

ELS

ARE

MAN

UFA

CTU

RED

AN

D T

RAD

EMAR

KED

BY

SHEA

R T

RAN

SFER

SYS

TEM

S, IN

C.

ATM

SM 3 - 2015 IBC OR 2016 CBC PAGE 14 ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE.

SHEAR TRANSFER SYSTEMS, INC. – VERSION JUNE 01, 2016

Page 16: ENGINEER AND ARCHITECT REFERENCE GUIDE TO ICC-ES …shearmax.com/wp-content/uploads/2016/06/3ENGINEERBROCHUREjune2016.pdf1425 5695 0.37 - Hold-down Anchor tension load = 9,500 Lbs

ALL INFORMATION WITHIN THIS GUIDE IS CONDENSED FOR REFERENCE USE ONLY. ALWAYS REFER TO THE COMPLETE ICC-ES REPORT FOR CORRECT USAGE. - SHEAR TRANSFER SYSTEMS, INC. – VERSION November 01, 2008

SHEARMAX FIELD REP ASSISTING WITH

INSTALLATION OF CUSTOM HEIGHT TRIM-FIT PANEL.

(SM24–168 –TF)

24’’x14’ 0’’ Panel FIELD TRIMMED TO A 3/12 Pitch

STANDARD PANEL WIDTHS: 16”, 18”, 21”, 24”, 28”,

32”, 36”, 42”, 48”

STANDARD PORTAL PANELS: 78”, 90”

7’ & 8’ GARAGE DOOR ON 6” STEM WALL

NOMINAL PANEL HEIGHTS: 8’, 9’, 10’, 11’, 12’, 13’, 14’,

15’, 16’, 17’, 18’, 19’, 20’

CUSTOM PANEL HEIGHTS: 6’ to 20’

ANY STANDARD WIDTH - NO EXTRA COST / NO MINIMUM QTY. REQUIRED / 3-5 WORKING DAYS

TRIM-FIT: UP TO 3/12 PITCH

ANY PANEL HEIGHT 6’ T0 20’ WITH ANY STANDARD WIDTH 16” TO 48”

SECOND STORY & RAISED FLOOR APPLICATIONS

NO WOOD SHRINKAGE ISSUES NO WOOD CRUSHING

NO PANEL LOAD REDUCTION

IAS ACCREDITED TEST FACILITY

MANUFACTURING PLANT

COMPATIBILITY

SHEARMAX panel proprietary components are individually tested to insure capacities well beyond the ultimate shear demand of the panel as a system. Though not required by ICC-ES under AC 130, this testing enables SHEARMAX panels to exhibit excellent reliability and increased ductile response.

When resisting lateral loading, SHEARMAX Panels respond similar to a standard sheathed code shear wall making them highly compatible. Both demonstrate the ability to produce inelastic response and still carry load beyond the code allowable drift while resisting catastrophic failure.

Through our testing of competitors prefabricated lateral force resisting systems we have observed catastrophic failures (hold-down anchor bolts, hold-downs, posts, and sheeting separation), in addition to, lack of ductility or the inability to produce an inelastic response.

It is our opinion that combining a competitor’s prefabricated lateral force resisting systems with standard sheathed code shear walls or a SHEARMAX panel system is NOT RECOMMENDED. A subsequent failure of any non-ductile systems would overload any remaining ductile systems and result in catastrophic structural failure.