Page 1: Energy Management & Utilization

Energy Management & Utilization

Chapter 5

Energy Management in Buildings

Prof. Dr. Ugur Atikol, cea Director of EMU Energy Research Centre

Page 2: Energy Management & Utilization

Energy Utilization in Buildings

Electric energy or work

Thermal energy (using fuels such as LPG, natural gas, diesel oil etc)

Thermal energy losses or gains from the envelope

Page 3: Energy Management & Utilization

Energy Efficiency in Buildings Making more use of the available energy or doing the

same amount of work with less energy Example: Washing the same laundry with less electricity in

a washing machine

Energy conversion

device

Energy Input

Useful Energy Output or Work Done

Lost or Wasted Energy

𝑬𝑬𝑬𝑬𝑬𝑬𝑬𝑬𝑬𝑬 =𝑼𝑼𝑬𝑬𝑼𝑼 𝑬𝑬𝑬𝑬𝑬𝑬 𝑶𝑼𝑶𝑶𝑼𝑶

𝑬𝑬𝑬𝑬𝑬𝑬 𝑰𝑬𝑶𝑼𝑶

Page 4: Energy Management & Utilization

Why buildings are important? Buildings consume large amounts of eneregy everywhere

in the world. Buildings account for roughly 40% of all U.S. energy use

Source: http://howcanihelpsandiego.com/lighter-side-of-green/

Page 5: Energy Management & Utilization

Energy Use in Buildings Residences: Depending on seasons heaters, air conditioners, lighting, washing

machines, television sets etc are used

Figures show the end-uses of residences in 1996 for N. Cyprus (Source: Atikol et al., 1999)

Page 6: Energy Management & Utilization

Energy Use in Buildings Hotels: Depending on seasons heaters, air conditioners, lighting,

refrigeration, television sets etc are used

Figures show the end-uses of hotels in 1997 for N. Cyprus (Source: Atikol, 2004)

Space Heating

Cold Room

Refrigeration

Lighting

Water Heating

0

2

4

6

8

10

12

14

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24Hours

Dem

and,

MW

Water HeatingLightingRefrigerationCold RoomSpace Heating

Air Conditioning

Lighting

Water Heating

0

5

10

15

20

25

30

35

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24Hours

Dem

and,

MW

Water HeatingLightingRefrigeratorsCold RoomsAir Conditioning

Page 7: Energy Management & Utilization

Energy Efficiency Opportunities in Buildings

Building Operation Building Envelope HVAC Systems HVAC Distribution Systems Water Heating Systems Lighting Systems Power Systems Energy Management Control Systems Heat Recovery Systems

Page 8: Energy Management & Utilization

Renewable Energy and Energy Efficiency

Source: http://lunar.thegamez.net/greentechnology/energy-efficient-house-plans/specialise-in-and-only-allow-house-designs-that-are-energy-efficient-1263x1040.jpg

Page 9: Energy Management & Utilization

Building Opperation

When the building is not occupied, the building systems should be turned off or their operation reduced to a

minimum.

Page 10: Energy Management & Utilization

Building Envelope Energy is saved when the heat exchange between the

building and the outside environment is reduced and/or solar and internal heat gains are controlled.

Winter heat losses Summer heat gains

Page 11: Energy Management & Utilization

Building Envelope Energy is saved when the heat exchange between the

building and the outside environment is reduced and/or solar and internal heat gains are controlled.

•Thermal insulation •Infiltration control •Roof color •Solar gains •Window shading •Landscaping •Window quality •Heat bridge

Page 12: Energy Management & Utilization

F - 12

Building Envelope

Thermal Insulation

1) Cushion, 2) Beam rafter, 3) Roofmate* PS thermal resistance board 4) Water proofing membrane 5) Tilling battens 6) Counter battens 7) Face wood 8) Roof cover (roof tiles, schingle)

Source:http://www.bulak.net/dow_roofmate_ps_Eng.asp

Page 13: Energy Management & Utilization

Building Envelope Insulation: Multilayer Plane Walls

totalRTT

Q 2,1, ∞∞ −=

AhAkL

AkL

Ah

RRRRR convwallwallconvtotal

22

2

1

1

1

2,2,1,1,

11 +++=

+++=

U-value = 1/Rtotal Such that:

)( 2,1, ∞∞ −××= TTAUQ

Page 14: Energy Management & Utilization

Building Envelope

Windows: Multi-glazing Windows

)( 2,1, ∞∞ −××= TTAUQ

( )4 4rad s surrQ A T Tεσ= −

Radiation heat transfer:

Heat losses through windows:

Page 15: Energy Management & Utilization

Heat loss through a single pane window Glass area: A = 0.8m × 1.5m = 1.2 m2

k = 0.78 W/m-oC. o

,1 2 o 21

1 1 0.08333 C/W(10W/m . C)(1.2m )i convR R

h A= = = =

oo 2

0.008m 0.00855 C/W(0.78W/m. C)(1.2m )glass

LRk

= = =

o,2 2 o 2

2

1 1 0.02083 C/W(40W/m . C)(1.2m )o convR R

h A= = = =

,1 ,2o

0.08333 0.00855 0.02083 0.1127 C/W

total conv glass convR R R R= + + = + +=

o,1 ,2

o[20 ( 10)] C 266W0.1127 C/Wtotal

T TQ

R∞ ∞− − −

= = =

,1 1 o1 1 ,1

,1

2.2 Cconvconv

T TQ T T QR

R∞

−= → = − = − Formation of fog or frost on the

surface

Building Envelope: Example

Page 16: Energy Management & Utilization

Heat loss through a double pane window o

,11

1 0.08333 C/Wi convR Rh A

= = =

o11 3

1

0.00427 C/WglassLR R R

k A= = = =

o22

2

0.3205 C/WairLR R

k A= = =

o,2

2

1 0.02083 C/Wo convR Rh A

= = =o

,1 ,1 ,2 ,2 0.4332 C/Wtotal conv glass air glass convR R R R R R= + + + + =o

,1 ,2o

[20 ( 10)] C 69.2W0.4332 C/Wtotal

T TQ

R∞ ∞− − −

= = =

which is 1/4th of the previous result. Inner surface temperature of the window:

o1 1 ,1 14.2 CconvT T QR∞= − = no fogging

Building Envelope: Example

Page 17: Energy Management & Utilization

HVAC Systems Use efficient equipment

Ventilation requirements must be correctly determined

Efficiently designed distribution system

Controls for efficiency

Pay attention to hours of operation

Building envelope

Page 18: Energy Management & Utilization

Fuel Flow pipe

Return pipe

To radiotors, fan convectors or floor heating

Central heating Boiler

Central Heating with Boilers

Pump

η = 0.83 – 0.95

Burner

Central Heating with Boilers

Page 19: Energy Management & Utilization

Condensing Boiler Flue gases

Fan

Water vapor from the exhaust gas is turned into liquid condensate

Efficiency is typically greater than 90%

Source: http://ddhltd.co.uk/condensing-boiler/

Page 20: Energy Management & Utilization

HVAC Systems

Pump

AHU

FCU-1 FCU-2 FCU-3

Duct

Cool Air

Flow

Return

Flow water ~ 7 deg C Return water ~ 13 deg C

Central Cooling with Chillers

COP = 2.5 – 3.5

Page 21: Energy Management & Utilization

HVAC Systems

Room Thermostat

3-way valve

Flow

Ret

urn

Fan Condensate tray

3-way valve

Fan-coil connection

Page 22: Energy Management & Utilization

HVAC Systems

Eva

pora

tor

Con

dens

er

Compressor

Expansion valve

120 kPa -20oC

800 kPa 60oC

800 kPa 30oC

120 kPa -25oC

Heat absorbed by evaporator

Heat rejected by condenser

Gas line

Liquid line

Gas line

Liquid line

Refrigeration Cycle

Page 23: Energy Management & Utilization

Variable Speed Drives (VSDs) for Energy Efficiency in HVAC Systems Large savings can be achieved by using variable

speed drives for fans, compressors and pumps. The cube law says:

Example: If fan speed is reduced by a half, the power consumed is reduced by 1

8.

[ ][ ]3

3

old

new

old

new

RPMRPM

kWkW

=

HVAC Systems

Page 24: Energy Management & Utilization

HVAC Systems

Con

dens

er

Compressor (Variable speed drive)

Expansion valves

Atmosphere

Eva

pora

tor

Eva

pora

tor

Eva

pora

tor

Variable Refrigerant Volume (VRV) System

Page 25: Energy Management & Utilization

HVAC Systems

Outdoor unit comprise of • condenser (evaporator) • compressor • Fans

Warm Air Flow

Cool Air Flow

Indoor units comprise of: • expansion valve • evaporator (condenser) • fan

Fans

VRV System in summer mode

Page 26: Energy Management & Utilization

Atmosphere

HVAC Systems

Eva

pora

tor

Con

dens

er

Compressor

Expansion valve

Ground or Water

reservoir Heat Heat

Energy storage: Water tank

Flow

to fa

n-co

ils

Ret

urn

from

fan-

coils

Water cooling/heating with chillers or heat pump systems

Page 27: Energy Management & Utilization

HVAC Systems

Room Thermostat

3-way valve

Flow

Ret

urn

Fan Condensate tray

3-way valve

Fan-coil connection

Page 28: Energy Management & Utilization

HVAC Systems

Eva

pora

tor

Compressor (Variable speed drive)

Expansion valve E

vapo

rato

r

Eva

pora

tor

Con

dens

er

Heat

Energy sink: Water reservoir

Ground or Water Source VRV System

Page 29: Energy Management & Utilization

Heating and Cooling Degree Days

Used to evaluate effects of weather Heating and cooling degree days (HDD, CDD) Balance point temperature, Tbal is defined as that value of

the outdoor temperature, where (for a specified value of indoor temperature, Ti) the total heat loss is equal to the free heat gain (from the sun, occupants etc.)

The standard value of the balance point temperature is 18,3 °C

If Ktot is the total heat loss of the building:

gainbalitot QTTK =− )(

Page 30: Energy Management & Utilization

Heating and Cooling Degree Days To = Average daily temperature HDD = balance point temp – average daily temperature

Daily high temperature: 6,7 °C Daily low temperature: -2,2 °C Daily average temperature = (6,7 – 2,2) / 2 = 2,2 HDD = 18,3 – 2,2 = 16,1 HDD for the day

For 365 days:

Heating is only needed when To drops below Tbal

∑=

−=365

1, )(

jjobal TTHDD

Page 31: Energy Management & Utilization

Heating and Cooling Degree Days For estimating annual heating that uses a heating system with

efficiency η :

Degree-days for a balance temperature of 18oC in Europe or 65oF (18.3oC) in the United States have been widely tabulated.

HDDKQ totyrh ×=

η,

Page 32: Energy Management & Utilization

Estimating Annual Boiler Energy with HDD method

Annual heat loss through a building component:

𝑸𝑳Whyear

= 𝑼W

m2℃× 𝑨(m2) × 𝑯𝑯𝑯

℃ daysyear

× 24h

day

QL

THIGH

TLOW

Heat loss

Wall with U-value

Qout

Qin

𝑸𝒐𝑼𝑶 = 𝑸𝑳 𝜂 =

𝑄𝑜𝑜𝑜𝑄𝑖𝑖

To find primary energy required:

𝑸𝑬𝑬 =𝑸𝒐𝑼𝑶

𝜼=𝑸𝑳

𝜼

Page 33: Energy Management & Utilization

Water heating energy is conserved by reducing load requirements, reducing distribution losses, and improving the efficiency of the

water heating systems.

•Flow Restrictors •Tank and Pipe Insulation •Supply Temperatures

•Leaks and Drips •Seasonal Operation •Equipment Efficiency

Water Heating Systems

Page 34: Energy Management & Utilization

Hot water generation with central boiler

Fuel

Hot Water Cylinder

Flow

Return

Indirect heating

To radiotors, fan convectors or floor heating

Central heating Boiler

Water Heating Systems

Pump

Photovoltaic panels

Solar Collectors

η = 0.83 – 0.95

η = 0.80 – 0.85

η = 0.15 – 0.20 Burner

Page 35: Energy Management & Utilization

Warm air

Cool air

Water Heating Systems Hot water generation with heat pump (COP = 3.0 – 5.0)

Page 36: Energy Management & Utilization

Water Heating Systems

Eva

pora

tor

Con

dens

er

Compressor

Expansion valve

Heat Heat

Energy source: Water reservoir or Lake or sea

Energy storage: Water tank

Hot

wat

er o

utle

t

Col

d w

ater

inle

t Water source heat pump system (COP = 4.0 – 7.0)

Solar electricity

Page 37: Energy Management & Utilization

Proper lighting levels Higher lamp efficiency Reduced operating hours Daylighting Lighting maintenance

Lighting Systems

Page 38: Energy Management & Utilization

Power Factor Correction (High efficiency motors, ballasts, correction devices)

Improving Efficiency (Transformers, motor sizing, efficiency, and VSD)

Demand Control Cogeneration

Power Systems

100 MWh Fuel

Cogeneration 35 % Electrical efficiency 50 % Thermal efficiency

35 MWh

Power

50 MWh Heat

15 MWh Losses

Page 39: Energy Management & Utilization

Efficiency with Cogeneration

Source: http://www.nscusa.com/chp/pmicogeneration.aspx

Page 40: Energy Management & Utilization

Recuperator: A recuperator is a special purpose counter-flow heat exchanger used to recover waste heat from exhaust gases. In many types of processes, combustion is used to generate heat, and the recuperator

serves to recuperate, or reclaim this heat, in order to reuse or recycle it.

Flue type recuperator Radiation type recuperator

(Source: www.koreathermal.co.kr)

Heat Recovery Systems

Page 41: Energy Management & Utilization

Heat Recovery Systems Heat recovery opportunities exist where there is a

need to reject heat from a constant supply of high energy fluid such as air, water, or refrigerant.

Possible opportunities are: Hot drain water Boiler stack or blow down Exhaust air Laundry air and water Refrigeration and process load

Page 42: Energy Management & Utilization

Heat Recovery heat pump or VRV System Cooling from evaporator and heating from condenser at

the same time Sometimes the condenser is designed to heat water

Page 43: Energy Management & Utilization

Heat Recovery Systems

Exhaust air heat recovery systems

Page 44: Energy Management & Utilization

Heat Recovery Ventillation System

Outdoors 3oC

Indoors 21oC

Fresh air supply 17oC

Exhaust 7oC

Page 45: Energy Management & Utilization

Building Energy Management Systems Managing the energy and other needs in buildings

efficiently and intelligently can have considerable benefits. A building energy management system(BEMS) is a

sophisticated method to monitor and control the building's energy needs.

A computer based control system installed in buildings.