EMUA Connection

Embed Size (px)

Citation preview

  • 7/21/2019 EMUA Connection

    1/12

    Protocol

    Type

    Setting of the 4-bit DIP Switch of the

    SW_ADDR

    GSM/CDM

    A

    0001

    WCDMA 0010

    0 ON

    1 OFF

    EMUA HUAWEI

    ON

    1 2 3 4

  • 7/21/2019 EMUA Connection

    2/12

    INSTALLATION OF EMUA

    DC-PDU

    Kabel monitor alarm di konek pada UPEU port MON1

    Kabel monitor alarm di konek pada UPEU port MON1

    Power utk EMUA dikonek pada port Spare pada DC-PDU

  • 7/21/2019 EMUA Connection

    3/12

    Sensor Alarm Box EMU

    Number Position

    7 Rectifier Failure S1 SW12A_1 disesuaikan 0

    4 Heat Detector Active S2 SW12A_2 disesuaikan 1

    6 Door Open S3 SW12A_3 disesuaikan 2

    1 PLN Power Failure S4 SW12A_4 disesuaikan 3

    5 Smoke Alarm S5 SW12A_5 disesuaikan 4

    8 DC power too low S7 SW12A_7 disesuaikan 6

    2 DC Fan active S8 SW12A_8 disesuaikan 7

    Temperature & Humadity DEFAULT SWTHE 1 & 2 ON

    Infrared DEFAULT SWBKE_3 OFF

    Waterlog DEFAULT SWBKE_1 OFF

    3 AC #1

    9 AC #2

    Smoke Alarm DEFAULT SWBKE_2 ON

    Access Equipment DEFAULT SWBKE_4 ON

    SW12A_6 disesuaikan

    LSA Box

    Port No.

    EAC

    S6

    Type : EMUA

    Extended Boolean

    Port No. (BTS

    Scripts)Alarm Description Physical portDIP Switch

  • 7/21/2019 EMUA Connection

    4/12

    script:

    set cbtsenvswtextport:btsid=xxx,portid=0,opmode=def,alminfo="Rectifier Failure",confirm=y;

    set cbtsenvswtextport:btsid=xxx,portid=1,opmode=def,alminfo="Heat Detector Active",confirm=y;

    set cbtsenvswtextport:btsid=xxx,portid=2,opmode=def,alminfo="Door Open",confirm=y;

    set cbtsenvswtextport:btsid=xxx,portid=3,opmode=def,alminfo="PLN Power Failure",confirm=y;

    set cbtsenvswtextport:btsid=xxx,portid=4,opmode=def,alminfo="Smoke alarm",confirm=y;

    set cbtsenvswtextport:btsid=xxx,portid=6,opmode=def,alminfo="DC Power Too Low",confirm=y;

    set cbtsenvswtextport:btsid=xxx,portid=7,opmode=def,alminfo="DC FAN Active",confirm=y;

    S4

    S7

    S8

    S2

    S5

    S3

    S1

    S6

  • 7/21/2019 EMUA Connection

    5/12

  • 7/21/2019 EMUA Connection

    6/12

    Water Log Sensor NC SW_BKE_1 OFF enable ON disable

    Smoke Detect Alarm NC SW_BKE_2 ON enable

    Infrared NC SW_BKE_3 OFF enable ON disable

    Door Open NC SW_BKE_4 ON enable OFF disable

    status DIP switch statusSensor Relay SW_BKE DIP switch

  • 7/21/2019 EMUA Connection

    7/12

  • 7/21/2019 EMUA Connection

    8/12

    Water Log

    dari kiri kekanan:

    putih, hijau, merah, konek ke water sensor

  • 7/21/2019 EMUA Connection

    9/12

    Temperature & Humadity

    T+ T- RH+ RH-

  • 7/21/2019 EMUA Connection

    10/12

    Infra Red

    + R

    NCTAMP

  • 7/21/2019 EMUA Connection

    11/12

    For Implementation Only used 4 Relays. There are :

    Relay 1 : Power Failure / AC Mains

    Relay 2 : High / Under Voltage

    Relay 3 : Rectifier Failure / Rectifier module broken

    Relay 4 : BLVD

    Number Position7 Rectifier Failure NC S 1 SW12 A1 up

    8 DC Power Too Low NC S 7 SW12 A7 up

    PS48180-1800-X6

    LSA Box Port No 8

    EAC Box

    PortDIP Switch

    LSA Box

    Port No.

    Censors

    Alarm DescriptionRelay

    Position

    2

    3

    3

    2

    2

    3

    Jumper

    LSA Box Port 7

  • 7/21/2019 EMUA Connection