The Emergency Voice Communications System (EVCS) Network 8 is for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required. Features Fully monitored stand alone system Complies with BS5839 Part 9 Fully addressable Duplex two way communication System flexibility Multiple line conversations Up to 8 master handsets Up to 256 outstations In addition to Type A and Type B Outstation can also monitor Emergency Assist Alarms (using a 2 core radial) Designed to comply with BS5839 Part 9 2003 the EVCS is a fixed, secure, bi-directional fully-duplex voice communication system, to assist fire fighters within high rise buildings or large sites where radio communication may not be possible. Where both a fire telephone and disabled refuge system are fitted to a building BS 5839 Part 9 specifies these should form a single system. The EVCS consists of three main components; the master handset (EVCS-MS), the exchanges units (EVCS-XC), and outstations (type A or type B as appropriate). Control of EVCS is simplicity itself, the master handset has a clear, four line backlit display which shows the calling outstation name in plain text. Calls can be made to outstations by either dialling the number of the unit, or choosing the name from a text dialling directory, with conference calling possible. Each Exchange unit connects to a data highway and is locally powered, with internal battery backup from a monitored, maintained sealed lead acid battery. Up to eight lines can be connected to each distributed exchange, and each line can have up to four phones (BS5839 Part 9 recommends one phone per line, however this facility is required in some retro fits). Two types of user outstation are available as described in BS5839 Part 9, Type A uses handsets, either flush or surface mounting. Type B outstations are hands free units with echo cancellation and noise reduction. All EVCS handsets have a ‘T’ coil for hearing aid users. Installation Master Handsets and exchange units are connected on a single data highway consisting of 2 x 4 core fire rated cables. Up to 8 Master Handsets and 32 exchanges may be connected to this highway. Master Handsets may be desk or wall mounted and has a 19” rack mounting option. Exchange units are supplied in a mild steel enclosure suitable for wall mounting. Each Exchange unit has 8 outstation lines for connection of Type A (telephone), Type B (hands free) stations or Emergancy Assist Alarm systems. These are connected to the Exchange unit with a 2 core fire rated cable with field wiring when an outstation is connected. Emergency Voice Communication Systems EVCS Network 8 Data Sheet This document is not intended to be used for installation purposes. Every care has been taken in the preparation of this document but no liability can be accepted for the use of the information therein. Design features may be changed or amended without prior notice. For more information, contact: NOTIFIER. Charles Avenue, Burgess Hill, West Sussex, RH15 9UF. United Kingdom Phone: +44 (0) 1444 230 300 Fax: +44 (0) 1444 230 888 ISO9001 Design, Manufacture and Supply to Quality Manage- ment Systems Certified to ISO9001:1994 Page 1 of 11 - 990-130_0213 www.notifierfiresystems.co.uk

Emergency Voice Communication Systems EVCS Network 8 · PDF fileThe Emergency Voice Communications System ... to assist fire fighters within high rise buildings or large ... Emergency

  • Upload
    dohuong

  • View
    241

  • Download
    4

Embed Size (px)

Citation preview

Page 1: Emergency Voice Communication Systems EVCS Network 8 · PDF fileThe Emergency Voice Communications System ... to assist fire fighters within high rise buildings or large ... Emergency

The Emergency Voice Communications System (EVCS) Network 8 is for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.

Features• Fully monitored stand alone system

• Complies with BS5839 Part 9

• Fully addressable

• Duplex two way communication

• Systemflexibility

• Multiple line conversations

• Up to 8 master handsets

• Up to 256 outstations

• In addition to Type A and Type B Outstation can also

monitor Emergency Assist Alarms (using a 2 core radial)

DesignedtocomplywithBS5839Part92003theEVCSisafixed,secure, bi-directional fully-duplex voice communication system, toassistfirefighterswithinhighrisebuildingsorlargesiteswhereradiocommunicationmaynotbepossible.WherebothafiretelephoneanddisabledrefugesystemarefittedtoabuildingBS5839Part9specifiestheseshouldformasinglesystem.

The EVCS consists of three main components; the master handset (EVCS-MS), the exchanges units (EVCS-XC), and outstations (type A or type B as appropriate).

Control of EVCS is simplicity itself, the master handset has a clear, four line backlit display which shows the calling outstation name in plain text. Calls can be made to outstations by either dialling the number of the unit, or choosing the name from a text dialling directory, with conference calling possible.

Each Exchange unit connects to a data highway and is locally powered, with internal battery backup from a monitored, maintained sealed lead acid battery. Up to eight lines can be connected to each distributed exchange, and each line can have up to four phones (BS5839 Part 9 recommends one phone per line,howeverthisfacilityisrequiredinsomeretrofits).

Two types of user outstation are available as described in BS5839Part9,TypeAuseshandsets,eitherflushorsurfacemounting. Type B outstations are hands free units with echo cancellation and noise reduction. All EVCS handsets have a ‘T’ coil for hearing aid users.

InstallationMaster Handsets and exchange units are connected on a single datahighwayconsistingof2x4corefireratedcables.Upto8Master Handsets and 32 exchanges may be connected to this highway. Master Handsets may be desk or wall mounted and has a 19” rack mounting option. Exchange units are supplied in a mild steel enclosure suitable for wall mounting.

Each Exchange unit has 8 outstation lines for connection of Type A (telephone), Type B (hands free) stations or Emergancy Assist Alarm systems. These are connected to the Exchange unitwitha2corefireratedcablewithfieldwiringwhenanoutstation is connected.

Emergency Voice Communication SystemsEVCS Network 8Data Sheet

This document is not intended to be used for installation purposes. Every care has been taken in the preparation of this document but no liability can be accepted for the use of the information therein. Design features may be changed or amended without prior notice. For more information, contact: NOTIFIER. Charles Avenue, Burgess Hill, West Sussex, RH15 9UF. United KingdomPhone: +44 (0) 1444 230 300 Fax: +44 (0) 1444 230 888

ISO9001Design, Manufacture and

Supply to Quality Manage-mentSystemsCertifiedto

ISO9001:1994

Page 1 of 11 - 990-130_0213 www.notifierfiresystems.co.uk

Page 2: Emergency Voice Communication Systems EVCS Network 8 · PDF fileThe Emergency Voice Communications System ... to assist fire fighters within high rise buildings or large ... Emergency

SpecificationsEVCS Master Handset - EVCS-MSMechanical Specification• Dimensions: Height: 268 mm Width: 275 mm Depth: 85 mm • Weight: 1.49 kg

Indication and Controls• Fault LEDs 4 off yellow (General, Panel, Supply & Exchange)• Status LEDs 4 off green (Healthy, AC, DC & Network)• LCD High contrast blue/white LCD, four line twenty-character 5x8 pixel format• Keyboard 12 key telephone style• Navigation 3 keys (Left, Accept,Right)

Network Cables• Type Fire rated (some installations will require enhanced cabling).• Cores 1 off four Pair (eg Draka 91-0245) or 2 off four core 1mm CSA Soft Skin or 4 off 1 Pair MICC Twisted• Distance 500M soft skin, 300M MICC• Monitoring Data and phantom voltage

Electrical Specification

Power Supply• Source Network Port x2• Voltage 11V to 18V DC• Current 88mA @ 12V

Processing• Clock 16MHz• Memory 4K RAM 20K EEProm 128K Flash• Monitoring Asynchronous Watchdog checksum on EEPROM & Flash

Standards Compliance• EMC EN55103-1,EN55103-2• Product Family BS5839-pt9, BS9999

EVCS Network 8 Master Handset - EVCS-MSEVCS Network 8 is a system for larger Disabled Refuge and Emergency telephone installations. Its distributed loop architecture provides a competitive system from 8 to 256 communication points as well as multiple control locations.

ControloftheEVCSissimplicityitself.TheNetwork8SystemMasterHandsetallowsswiftidentificationofoutstations via its on-board directory and clear backlit display. The master console has a clear four line backlit display which shows the calling outstation name in plain text, and calls can be made to outstations by either dialling the number of the unit, or choosing the name from a text dialling directory.

TheEVCSNetwork8systemalsoenablesNotifierEmergencyAssistAlarmsystemstobeconnecteddirectly.

Page 2 of 11 - 990-130_0213 www.notifierfiresystems.co.uk

Page 3: Emergency Voice Communication Systems EVCS Network 8 · PDF fileThe Emergency Voice Communications System ... to assist fire fighters within high rise buildings or large ... Emergency

SpecificationsEVCS Master Handset - EVCS-MSWMMechanical Specification• Dimensions: Height: 300 mm Width: 300 mm Depth: 90 mm • Weight: 6.5 kg• Material Zintec, Texture Powder Coated, RAL7032

Indication and Controls• Fault LEDs 4 off yellow (General, Panel, Supply & Exchange)• Status LEDs 4 off green (Healthy, AC, DC & Network)• LCD High contrast blue/white LCD, four line twenty-character 5x8 pixel format• Keyboard 12 key telephone style• Navigation 3 keys (Left, Accept,Right)

Network Cables• Type Fire rated (some installations will require enhanced cabling).• Cores 1 off four Pair (eg Draka 91-0245) or 2 off four core 1mm CSA Soft Skin or 4 off 1 Pair MICC Twisted• Distance 500M soft skin, 300M MICC• Monitoring Data and phantom voltage

Electrical Specification

Power Supply• Source Network Port x2• Voltage 11V to 18V dc• Current 88mA @ 12V dc

Processing• Clock 16MHz• Memory 4K RAM 20K EEProm 128K Flash• Monitoring Asynchronous Watchdog checksum on EEPROM & Flash

Standards Compliance• EMC EN55103-1,EN55103-2• Product Family BS5839-pt9, BS9999

EVCS Network 8 Master Handset Wall Mounted - EVCS-MSWMEVCS Network 8 is a system for larger Disabled Refuge and Emergency telephone installations. Its distributed loop architecture provides a competitive system from 8 to 256 communication points as well as multiple control locations.

ControloftheEVCSissimplicityitself.TheNetwork8SystemMasterHandsetallowsswiftidentificationofoutstations via its on-board directory and clear backlit display. The master console has a clear four line backlit display which shows the calling outstation name in plain text, and calls can be made to outstations by either dialling the number of the unit, or choosing the name from a text dialling directory.

Thewallmountcaseismadefrompowdercoatedzintecandisfittedwith20mmcableknockoutsforallcablesneeded.

TheEVCSNetwork8systemalsoenablesNotifierEmergencyAssistAlarmsystemstobeconnecteddirectly.

300mm

300mm 90mm

Page 3 of 11 - 990-130_0213 www.notifierfiresystems.co.uk

Page 4: Emergency Voice Communication Systems EVCS Network 8 · PDF fileThe Emergency Voice Communications System ... to assist fire fighters within high rise buildings or large ... Emergency

SpecificationsEVCS Network 8 Exchange Unit - EVCS-XCMechanical Specification• Dimensions: Height: 296 mm Width: 210 mm Depth: 82 mm • Weight: 1.6 kg

Indication and Controls• Fault LEDs 10 off yellow (General, PSU, 8 lines) • Status LEDs 2 off green (AC & DC)• Settings 8 way DIP switch

Outstation Cables• Grade Enhanced• Cable (per Line) 1 off 2 core (twisted for MICC)• Distance (per leg) 500M soft Skin types, 300M MICC• Monitoring DC open, short & earth

Network Cables• Type Enhanced• Cores 1 off four pair (eg Draka 91-0245) or 2 off four core 1mm CSA Soft Skin or 4 off 1 Pair MICC Twisted• Distance 500M soft Skin, 300M MICC

Electrical Specification

Power Supply• Voltage 230V AC ± 20%• Current 11mA• Battery 12V SLA 3.2AH• Charger 1A Controlled Impedance• Monitoring Open, Short & High Impedance cell

Standards Compliance• EMC EN55103-1,EN55103-2• LVD EN61000-3-2, EN61000-3-3, EN60950 • Product Family BS5839-pt9, BS9999, EN54-4

EVCS Network 8 Exchange Unit - EVCS-XCTheNetworkExchangeUnitdeliversanefficientsolutionforlargerEVCSsites.ProvidingapowersupplyforSystem Master Handsets, its distributed loop based architecture provides a competitive scalable system for up to 256 communication points. Each Exchange unit sits on a data highway and is locally powered, with internal battery backup from a monitored, maintained sealed lead acid battery. Up to eight lines can be connected to each distributed exchange, and each line is fully monitored for Open, Short or Earth faults.

The network comprises a line or ring of 8 cores (see below), each leg can be up-to 500M depending on cable type. A ring topology is recommended by 5839 pt9. Line cables consist of a single two core enhanced cable, either soft skin types or MICC and only 1mm CSA is required.

Uptothirty-twoNetwork8Exchangescanbefittedtoathesystemgivingamaximumsystemsizeof256independent lines.

Page 4 of 11 - 990-130_0213 www.notifierfiresystems.co.uk

Page 5: Emergency Voice Communication Systems EVCS Network 8 · PDF fileThe Emergency Voice Communications System ... to assist fire fighters within high rise buildings or large ... Emergency

Page 5 of 11 - 990-130_0213 www.notifierfiresystems.co.uk

SpecificationsEVCS Type A OutstationMechanical Specification - EVCS-HSP (Surface Mounting)• Dimensions: Height: 320 mm Width: 152 mm Depth: 85 mm • Weight: 1.4 Kg (no batteries)

Mechanical Specification - EVCS-HFP (Flush Mounting)• Dimensions (with bezel): Height: 334 mm Width: 191 mm Depth: 85 mm • Dimensions (backbox hole): Height: 320 mm Width: 152 mm Depth: 85 mm • Weight: 1.4 Kg (no batteries)

Features• Telephone type handset• Automatic dialling to Master Handset when ‘off hook’• Telecoil for hearing impaired users• Magnetic push catch door

Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault

Status LED• Flashing when ringing• Dimly lit to indicate surveillance

Standards• EMC: EN 55103-1 & EN 55103-2• LVD: EN 60950• Product Family: BS 5839-9 & BS 9999 & EN 60118-4

Surface mounting enclosure

Flush mounting enclosure

Type A Outstation - EVCS-HSP & EVCS-HFP The EVCS Type A outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.

The Type A outstation is a monitored phone handset providing full duplex speech capability. The unit is available asasurfacemountingorflushmountingunitcasedinametalwallmountingenclosure.

The EVCS type A Outstation is a slick compact unit which offers easy access via a magnetic push catch door and a unique front levelling system allowing the back box to be mounted at a slight angle whilst still retaining a true front face and door.

Compatible with all EVC systems for use as a standard Fire Telephone or Disabled Refuge call point.

334mm

191mm 85mm

320mm

152mm 85mm

EVCS-HFPSS Flush Mount

EVCS-HSPSS Surface Mount

Page 6: Emergency Voice Communication Systems EVCS Network 8 · PDF fileThe Emergency Voice Communications System ... to assist fire fighters within high rise buildings or large ... Emergency

Page 6 of 11 - 990-130_0213 www.notifierfiresystems.co.uk

SpecificationsEVCS Type A Outstation Stainless SteelMechanical Specification - EVCS-HSPSS (Surface Mounting)• Dimensions: Height: 320 mm Width: 152 mm Depth: 85 mm • Weight: 1.4 Kg (no batteries)

Mechanical Specification - EVCS-HFPSS (Flush Mounting)• Dimensions (with bezel): Height: 334 mm Width: 191 mm Depth: 85 mm • Dimensions (backbox hole): Height: 320 mm Width: 152 mm Depth: 85 mm • Weight: 1.4 Kg (no batteries)

Features• Telephone type handset• Automatic dialling to Master Handset when ‘off hook’• Telecoil for hearing impaired users• Magnetic push catch door

Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault

Status LED• Flashing when ringing• Dimly lit to indicate surveillance

Standards• EMC: EN 55103-1 & EN 55103-2• LVD: EN 60950• Product Family: BS 5839-9 & BS 9999 & EN 60118-4

Type A Outstation Stainless Steel - EVCS-HSPSS & EVCS-HFPSS The EVCS Type A outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.

The Type A outstation is a monitored phone handset providing full duplex speech capability. The unit is available asasurfacemountingorflushmountingunitcasedinametalwallmountingenclosure.

The EVCS type A Outstation is a slick compact unit which offers easy access via a magnetic push catch door and a unique front levelling system allowing the back box to be mounted at a slight angle whilst still retaining a true front face and door.

Compatible with all EVC systems for use as a standard Fire Telephone or Disabled Refuge call point.

334mm

191mm 85mm

320mm

152mm 85mm

EVCS-HFPSS Flush Mount

EVCS-HSPSS Surface Mount

Page 7: Emergency Voice Communication Systems EVCS Network 8 · PDF fileThe Emergency Voice Communications System ... to assist fire fighters within high rise buildings or large ... Emergency

Page 7 of 11 - 990-130_0213 www.notifierfiresystems.co.uk

SpecificationsType A Outstation IP65 Lockable Surface MountMechanical Specification - EVCS-HFW• Dimensions: Height: 300 mm Width: 200 mm Depth: 120 mm • Weight: 2.5 Kg• Material Zintec, Powder coated

• Colour RAL7035 Grey

Outstation Cables• Type Enhanced• Cores 2 core 1mm or 1.5mm• Distance 500m

Features• Telephone type handset• Automatic dialling to Master Handset when ‘off hook’• Telecoil for hearing impaired users• Fittedwithastandardfiremanskeylocktopreventunauthoriseduse

Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault

Status LED• Flashing when ringing• Dimly lit to indicate surveillance

Standards• EMC EN55103-1, EN55103-2• LVD EN60950• Product Family: BS 5839-9 & BS 9999 & EN 60118-4

Mounting The UnitThe Handset should be mounted at a height of either 1200mm from the fioor,orona1400mmcentrelinetocomplywiththerequirementsofBuilding Regulations Document M (Access for the Disabled). The back box has four indented feet to allow mounting on uneven walls.If the unit is to be used as a refuge point suitable space must be allowed to the side of the unit to allow a wheelchair to be parked for using the system.

Type A Outstation IP65 Lockable Surface Mount - EVCS-HFW The EVCS Type A outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.

The Type A outstation is a monitored phone handset providing full duplex speech capability. The unit is available asasurfacemountingorflushmountingunitcasedinametalwallmountingenclosure.

TheEVCS-HFWisatypeAEVCSoutstationcompatiblewiththeNotifierCompactandNetworksystems.ItissuppliedinanIP65casefittedwithastandardfiremanskeylocktopreventunauthoriseduse.

300m

m

200mm 120mm

Page 8: Emergency Voice Communication Systems EVCS Network 8 · PDF fileThe Emergency Voice Communications System ... to assist fire fighters within high rise buildings or large ... Emergency

SpecificationsType B OutstationMechanical Specification• Dimensions: Height: 133 mm Width: 133 mm Depth: 45 mm • Weight: 1.1Kg • Construction Zintec powder coated • Colour Green, Red or Stainless Steel

Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault

Outstation Cables• Cores 2 core 1mm or 1.5mm• Distance 500m

Indications & Controls• Status LEDs2offred-flasheslocation, lights solid in use• Call Press to call button• Cancel Press to cancel button

Hands Free Communications• Push button dialling to EVCS Master Handset• Echo cancellation• Noise reduction• Induction loop output for hearing impaired users• Push button cancel• Braille Signage

Standards• EMC: EN55103-1 & EN55103-2 • LVD: EN60950• Product Family: BS5839 Pt9 & BS9999

Mounting The UnitAll Type B Outstations should be mounted at a height of either 1200mm fromthefloor,orona1400mmcentrelinetocomplywiththerequirementsof Building Regulations Document M (access for the disabled).The back box has 4 indented feet to allow mounting on uneven walls.TypeBOutstationscanbeflushmountedbycuttingahole133mmx133mmand45mmdeep,andusingthestainlesssteelbezeltofinishthe surround.

Type B Outstation - EVCS-HSBG, EVCS-HSB, EVCS-HSFSSThe EVCS Type B outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.

TheTypeBoutstationisafixed,monitoredandmaintained,bi-directional,fullduplexvoicecommunicationsystemtoassisttheorderlyevacuationofdisabledormobilityimpairedpeopleandenhancefirefighterscommunication during emergencies.

Please note: When choosing the outstation type for use with an EVCS we recommend reading Section 11 of BS5839-9:2003 which deals with outstation types. Type B outstations can only be used where the background noise is below 40dBA (therefore there can be no sounder or voice alarm coverage in the area).

Page 8 of 11 - 990-130_0213 www.notifierfiresystems.co.uk

Page 9: Emergency Voice Communication Systems EVCS Network 8 · PDF fileThe Emergency Voice Communications System ... to assist fire fighters within high rise buildings or large ... Emergency

SpecificationsJack Plate Mechanical Specification• Dimensions: Height: 86 mm Width: 86 mm Depth: 25 mm • Weight: 140g • Construction Brushed stainless steel

Outstation Cables• Cores 2 core 1mm or 1.5mm • Distance 500m• End of Line 10K 1/4 W

Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault

Roaming Handset Mechanical Specification• Dimensions: Height: 210 mm Width: 66 mm Depth: 45 mm • Weight: 700g • Construction ABS UL90V1• Connection 1/4” mono neutrik heavy duty jack

Standards Compliance• EMC EN55103-1,EN55103-2• LVD EN60950

Controls

• Call Automatic off hook dialing

Roaming Handset and Jack PlateThe Roaming Handset and Jack plate are designed to provide a cost effective solution for Fire Telephones in highrisebuildings.Notifier’srangeofEVCSsystemscoverawiderangeofbuildingsizesprovidinghighqualityfull duplex Emergency Voice Communication.

The Roaming Handset is used along with the Jack Plate for Emergency Voice Communication System installationsincountrieswhosefirecodesallowforRoamingHandsets*.Whenusedtogether,theRoamingHandset and Jack Plate form a Type A Outstation which is compatible with all EVCS systems.

Low noise high quality telephone jack with Telecoil for hearing impaired users.

Stainlesssteeljackplatecanbesurfaceorflushmounted

*TheseunitsarenotsuitableforinstallationintheUKtoBS5839Pt9

Page 9 of 11 - 990-130_0213 www.notifierfiresystems.co.uk

Page 10: Emergency Voice Communication Systems EVCS Network 8 · PDF fileThe Emergency Voice Communications System ... to assist fire fighters within high rise buildings or large ... Emergency

SpecificationsEmergency Assist Alarm Kit EVCS-TA

Features• Monitored to BS 5839-9

• Remote powered from EVCS exchange

• Dual loop pull cord

• High contrast labels

• Braille on cancel plate

• Blue indication

Benefits• No PSU is required remote powered by

EVCS system

• All calls from disabled toilets and refuge points monitored from one location

• Tactile braille signage to assist partially sighted people

Page 10 of 11 - 990-130_0213 www.notifierfiresystems.co.uk

Over door indicator

Dimensions: Width:Height:Depth:

87 mm87 mm31.5 mm

ElectricalSpecification: Operating voltage: 12V dc (nominal)

Physical: Construction: PC

Cancel button

Dimensions: Width:Height:Depth:

87 mm87 mm25 mm

ElectricalSpecification: Operating voltage: 12V dc (nominal)

Physical: Construction: PC

Pull cord unit

Dimensions: Width:Height:Depth:

87 mm87 mm30.5 mm

ElectricalSpecification: Operating voltage: 12V dc (nominal)

Physical: Construction: PC

Wiring Guide Using 2 Core Cable

+-

+-

Power Supply

12V +-

+-

+-+

-

Over DoorIndicator

CancelUnit

Pull Cord Unit

IN

IN

OUT

OUT

OUT INEVCS Exchange Over Door IndicatorOver Door Indicator Cancel UnitCancel Unit Pull Cord Unit

Emergency Assist Alarm Kit - EVCS-TATheEmergencyassistalarmkithasbeenspecificallydesignedtointegratedisabledcallfunctionsintotheEVCSNetworkorEVCSCompact ranges providing the perfect solution for conformity with the Building regulations Document M and Equality Act 2010.

The Emergency Assist Alarm Kit solution is fully monitored and battery backed by the EVCS system, saving local power supplies and givingconfidenceinthesystemintegrity.

The Emergency Assist Alarm Kit shows up as a call on the EVCS system, but has no speech path so a conversation cannot be had with the occupant, use of the Type B Outstations would allow this.

www.notifierfiresystems.co.uk

Page 11: Emergency Voice Communication Systems EVCS Network 8 · PDF fileThe Emergency Voice Communications System ... to assist fire fighters within high rise buildings or large ... Emergency

Product Range at a Glance

Part Number

EVCS Master Handset Desk/Wall Mount EVCS-MS

Network 8 Master Handset Wall Mounted EVCS-MSWM

8 Way Exchange Unit/Charger. EVCS-XC

Flush Outstation Push Door. Type A EVCS-HFP

Flush Outstation Type A, Push Door, Stainless Steel EVCS-HFPSS

Surface Outstation. Push Door. Type A EVCS-HSP

Surface Outstation Type A, Push Door, Stainless Steel EVCS-HSPSS

Weatherproof Type A Outstation EVCS-HFW

Surface Outstation, Type B, Green EVCS-HSBG

Surface Outstation, Type B, Red EVCS-HSB

Surface Outstation, Type B Stainless Steel EVCS-HSFSS

Wall Jack Outlet Point EVCS-WJP

Loose Handset with Jack Lead EVCS-HLJ

Emergency Assist Alarm Kit (without PSU) EVCS-TA

EVCS-HSBStainlessSteelflushmountingbezel EVCS-VCFHB

EVCS-MS Rackmount Kit 6U. EVCS-RM

Charles AvenueBurgess HillW. SussexRH15 9UF