2
Sensibilidad (A) Sensivity P23261 WRU-10 K 0.03-3A 0.03 , 0.1, 0.3 , 0.5 , 1 , 3 INS , SEL , 0.02 , 0.1, 0.2 , 0.3 , 0.4 , 0.5 , 0.75 , 1 Electronic earth leakage protection relay with earth leakage reclosing WRU-10 K 0.03 - 3A M049A01-03-18A PRELIMINARY CONSIDERATIONS VERIFICATION UPON RECEPTION Ensure that : - The unit meets the specifications described in your order. - The unit has not suffered any damage during transport. You may download more information from our website: www.circutor.es SAFETY PRECAUTIONS In order to ensure that the unit is used safely, all people installing or handling it must follow the general safety measures and warnings described in this quick guide. The WRU-10k is a unit designed specifically to be installed in an electric panel or enclosure, and is attached to the DIN rail or panel via an accessory. It has an LED (ON) indicating the presence of voltage. Even if this LED is not on, the user must still verify that the unit is disconnected from all power supplies INSTALLATION AND START-UP IMPORTANT ! ! GENERAL DESCRIPTION Installation on the DIN rail. All active conductors that supply the loads, or the section of the installation that requires earth leakage protection with this unit must pass through the hole. In single-phase installations (phase and neutral, L and N), three-phase installations (phases L1, L2, and L3) or three-phase plus neutral (L1, L2, L3 and N). Depending on the insulation level of the wiring, four cables with a cross-section of 35 2 2 mm can be passed through, but 25 mm cables are recommended. All connections must remain inside the electric panel. Remember that when the unit is connected, touching the terminals, opening the covers or removing elements may provide access to parts that are hazardous to touch. Do not use the unit until it is fully installed. The unit must be connected to a fuse-protected power circuit in accordance with its power supply range and consumption. In turn, the power circuit must be equipped with a circuit breaker switch or 2 equivalent device to disconnect the unit from the power supply network. A cable section of 1-1.5 mm is recommended for wiring. The recommended torque is 0.5-0.6 Nm and insulation should be removed from 7 mm of cable This quick guide contains information and warnings that must be followed by the user to ensure safe operation of the unit. The unit should not be used under normal operating conditions until it is installed in its final location in the electric panel. When it is likely that the unit has lost its safety protection (visible signs of damage), it should be disconnected from the power supply. In such a case, contact a qualified service technician or our S.A.T. (Technical Assistance Service). UNIT INSTALLATION Technical Assistance Service (S.A.T.) If you have any questions about the operation of the unit or any failures, contact our technical assistance service Tel: 902 449 459 (Barcelona), SPAIN Tel: (+34) 93 745 29 00 (out of SPAIN) email: [email protected] Vial Sant Jordi s/n 08232 Viladecavalls (Bacelona) SPAIN Wheight : 168 gr REC - DELAY SETTINGS - SETUP MENU ROTATION - AUTO/MAN SETTINGS - UNIT LOCKING SETTINGS REC REC REC R . DESCRIPTION OF THE LEDS AND BUTTONS Indication of the unit status via display and 2 LEDs. Settings and programming of the unit via 5 buttons. TEST and RESET of the unit via 2 buttons. - SETUP PROGRAMMING - CHANGE SCREEN - GREEN LED: Unit ON - RED LED, trip. - blinking LED: Manual reclosing.l - LED Interlocking of Reclosings - RESET BUTTON - TEST BUTTON LED / DISPLAY INDICATIONS. - RELAY TRIPPED. The display/LED changes from green to red. The cause for the trip is shown. - STATUS BETWEEN RECLOSINGS. LED indicates interlocking when blinking. - . INTERLOCKING SIGNALS LED not blinking. The maximum number of automatic reclosings, as configured, has been reached. - NO. OF RECLOSINGS, Partial, by pressing the PROG button (floating page), it indicates the configured reclosing sequence. Total, by pressing the PROG button twice (set page). . RECLOSING THE UNIT - DUE TO TRIP / INTERLOCKING FROM RECLOSINGS. 1. Enabled. Automatic (TRIP due to leakage current, but not locked). 2. Manually RESET the unit. 3. Remote trip signal. Input 1-2. It only recloses via remote signal. In cases 2 and 3, the partial reclosing system meter goes to zero. ( t , I ,Rec and std/+ ) d d RELAY PARAMETER SETTINGS - , t . d TRIP DELAY SETTINGS . When you push and hold the td key, the message and . two values appear on the screen The smaller indicates the current configured value and t . d the larger indicates the values to be configured which you can toggle through by pressing When the selected value is displayed, wait for the unit to validate the value as having been saved to the settings by showing the SAVE message. - , I . I d d SENSITIVITY SETTINGS Pressing the I key performs the operation with the same modus operandi as the previous setting. - , std/+ . CONTACT STATUS SIGNALLING Pressing this key selects the status of the output relay contacts that signal interlocking. (Std) (+) NA . NC nothing appears on the display and NO the symbol appears - . CONFIGURE AUTOMATIC RECLOSING, MANUAL Before pressing REC you must unlock the security lock. When REC is pressed, the automatic reclosings for differential relay trips are activated on the main screen. REC The Test trip (red button) may only be manually reclosed by pressing the RESET key (Case 2) PROG SETUP SETTINGS SREC NO. RECLOSINGS SEQUENCE TIMES RESET TIME REC 2 30 20 seg + 40 seg + 28 x 5 min 15 min FACTORY PRESETS The unit can reset to its factory-installed values in a SETUP sub-menu. Press and hold PROG and then press to get to the FACT sub-menu. When the device is reset, the total td reclosings meter goes to zero and the relay is reset. By pressing and holding the td and Id keys for more than 2 seconds, you can lock the setup menu. It shows BLOQ YES if it is locked, BLOQ NO if not. MENU LOCKING/UNLOCKING Test TEST Leakage current Instantaneous value Trip cause Display message Dif/ value Differential Magnetotérmica MAG Other display MESSAGES SAVE EXIT OVR Validates configuration values Leaves programming mode Value reading out of range Parameters Non-configurable values Trip current 30 mA Trip time INS Código Tipo Sensibilidad (A) Retardo disparo (seg.) Code Type Sensitivity Tripping delay To operate downstream from the WRU-10 k relay safely, manually lower the Kopps circuit breaker switch SAT 1 - General unit error. Disconnect the unit and call the Technical Assistance Service (SAT). SAT 2 - Factory-installed values, a memory reading / writing problem has caused the unit to reset to its factory-installed values. The message SAT 2 is shown on the display until an operator pushes the RESET button. SAFE DISCONNECTION ERROR MESSAGES 1-2 5 6 7 8 9 10 11 12 EXTERNAL RESET DESCRIPTION OF THE TERMINALS RELAY OUTPUT CONTACT LOCKING NC RELAY OUTPUT CONTACT LOCKING POWER SUPPLY 230 Vac (PHASE or NEUTRAL) POWER SUPPLY 230 Vac ( NEUTRAL or PHASE) RELAY OUTPUT CONTACT TRIP NO RELAY OUTPUT CONTACT TRIP SHARED RELAY OUTPUT CONTACT TRIP NO CIRCUIT BREAKER STATUS Voltage-free, uninsulated Nominal Current: 0.25 Aac Rated Voltage: 230 Vac Nominal Load: 62.5 V·A Protected by varistor: 420 Vc.a.-10Ac.a l: 5 Ac.a Nominal Current l: 250 Vc.a Rated Voltage : 1.250 V·A Nominal Load - SENSITIVITY SETTINGS PROG Type A super-immunised electronic earth leakage relay with 28 mm built-in toroidal. Device with AUTOMATIC EARTH LEAKAGE RECLOSING. Symbol in the LCD. It has a programmable output relay for tripping the main relay. It REC has a voltage-free input for external tripping and rearming. Assembly on DIN rail 46277 (EN 50022) or on a 72 x 72 panel using an accessory (M5ZZF1). The display shows settings values and instantaneous leakage current values (TRMS). If the unit is used in a manner other than that specified by the manufacturer, its protection may be compromised. Unit power supply Operating conditions Safety WIRING USING PLUG-IN TERMINALS Voltage 230 Vc.a. +/- 30% Frequency 50/60 Hz Power 4,5 VA Temperature -20....+ 70º C Relative humidity 5.... 95% Max. working altitude 2.000m Protection IP20 Category III, 300 Vac EN61010 Double-insulated electric shock protection class II Immunised against shock waves up to 2kV FEATURES IMPORTANT! Use the button to move through the sub-menus, PROG and use the button to display the values to be selected. Press to validate a value. The unit PROG saves the value and displays SAVE, exiting programming mode. If the keypad is inactive for some time, the unit will automatically exit programming mode and show EXIT on the display without changing the configuration.

Electronic earth leakage protection relay with earth ...docs.circutor.com/docs/M049A01-03.pdf · CONNECTION DIAGRAMS SETUP MENU PLUG-IN TERMINALS Earth leakage protection and automatic

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Electronic earth leakage protection relay with earth ...docs.circutor.com/docs/M049A01-03.pdf · CONNECTION DIAGRAMS SETUP MENU PLUG-IN TERMINALS Earth leakage protection and automatic

Sensibilidad (A) Sensivity

P23261WRU-10 K

0.03-3A 0.03 , 0.1, 0.3 , 0.5 , 1 , 3 INS , SEL , 0.02 , 0.1, 0.2 , 0.3 , 0.4 , 0.5 , 0.75 , 1

Electronic earth leakage protection relay with earth leakage reclosing WRU-10 K 0.03 - 3A

M049A01-03-18A

PRELIMINARY CONSIDERATIONS VERIFICATION UPON RECEPTION

Ensure that : - The unit meets the specifications described in your order. - The unit has not suffered any damage during transport.

You may download more information from our website: www.circutor.es

SAFETY PRECAUTIONSIn order to ensure that the unit is used safely, all people installing or handling it must follow the general safety measures and warnings described in this quick guide.

The WRU-10k is a unit designed specifically to be installed in an electric panel or enclosure, and is attached to the DIN rail or panel via an accessory. It has an LED (ON) indicating the presence of voltage. Even if this LED is not on, the user must still verify that the unit is disconnected from all power supplies

INSTALLATION AND START-UP

IMPORTANT !

!

GENERAL DESCRIPTION

Installation on the DIN rail. All active conductors that supply the loads, or the section of the installation that requires earth leakage protection with this unit must pass through the hole. In single-phase installations (phase and neutral, L and N), three-phase installations (phases L1, L2, and L3) or three-phase plus neutral (L1, L2, L3 and N). Depending on the insulation level of the wiring, four cables with a cross-section of 35

2 2mm can be passed through, but 25 mm cables are recommended. All connections must remain inside the electric panel. Remember that when the unit is connected, touching the terminals, opening the covers or removing elements may provide access to parts that are hazardous to touch. Do not use the unit until it is fully installed. The unit must be connected to a fuse-protected power circuit in accordance with its power supply range and consumption. In turn, the power circuit must be equipped with a circuit breaker switch or

2equivalent device to disconnect the unit from the power supply network. A cable section of 1-1.5 mm is recommended for wiring. The recommended torque is 0.5-0.6 Nm and insulation should be removed from 7 mm of cable

This quick guide contains information and warnings that must be followed by the user to ensure safe operation of the unit. The unit should not be used under normal operating conditions until it is installed in its final location in the electric panel.

When it is likely that the unit has lost its safety protection (visible signs of damage), it should be disconnected from the power supply. In such a case, contact a qualified service technician or our S.A.T. (Technical Assistance Service).

UNIT INSTALLATION

Technical Assistance Service (S.A.T.)If you have any questions about the operation of the unit or any failures, contact our technical assistance service

Tel: 902 449 459 (Barcelona), SPAIN Tel: (+34) 93 745 29 00 (out of SPAIN)email: [email protected]

Vial Sant Jordi s/n08232 Viladecavalls (Bacelona) SPAIN

Wheight : 168 gr

REC

- DELAY SETTINGS - SETUP MENU ROTATION

- AUTO/MAN SETTINGS

- UNIT LOCKING SETTINGS

REC

REC

REC

R

. DESCRIPTION OF THE LEDS AND BUTTONS

Indication of the unit status via display and 2 LEDs. Settings and programming of the unit via 5 buttons. TEST and RESET of the unit via 2 buttons.

- SETUP PROGRAMMING

- CHANGE SCREEN

- GREEN LED: Unit ON- RED LED, trip.

- blinking LED: Manual reclosing.l- LED Interlocking ofReclosings

- RESET BUTTON

- TEST BUTTON

LED / DISPLAY INDICATIONS.- RELAY TRIPPED. The display/LED changes from green to red. The cause for the trip is shown.

- STATUS BETWEEN RECLOSINGS.LED indicates interlocking when blinking.

- . INTERLOCKING SIGNALS LED not blinking. The maximum number of automatic reclosings, as configured, has been reached.- NO. OF RECLOSINGS, Partial, by pressing the PROG button (floating page), it indicates the configured reclosing sequence. Total, by pressing the PROG button twice (set page).

.RECLOSING THE UNIT- DUE TO TRIP / INTERLOCKING FROM RECLOSINGS. 1. Enabled.Automatic (TRIP due to leakage current, but not locked). 2. Manually RESET the unit. 3. Remote trip signal. Input 1-2. It only recloses via remote signal. In cases 2 and 3, the partial reclosing system meter goes to zero.

( t , I ,Rec and std/+ )d dRELAY PARAMETER SETTINGS - , t . dTRIP DELAY SETTINGS . When you push and hold the td key, the message and PROG

. two values appear on the screen The smaller indicates the current configured value and t . d the larger indicates the values to be configured which you can toggle through by pressing When the selected value is displayed, wait for the unit to validate the value as having been saved to the settings by showing the SAVE message.- , I . I d dSENSITIVITY SETTINGS Pressing the I key performs the operation with the same modus operandi as the previous setting.- , std/+ . CONTACT STATUS SIGNALLING Pressing this key selects the status of the output relay contacts that signal interlocking. (Std) (+) NA .NC nothing appears on the display and NO the symbol appears- . CONFIGURE AUTOMATIC RECLOSING, MANUAL Before pressing REC you must unlock the security lock. When REC is pressed, the automatic reclosings for differential relay trips are activated on the main screen.

REC

The Test trip (red button) may only be manually reclosed by pressing the RESET key (Case 2)

PROGSETUP SETTINGS

SREC NO. RECLOSINGS SEQUENCE TIMES RESET TIME

REC

2 30 20 seg + 40 seg + 28 x 5 min 15 min

FACTORY PRESETS

The unit can reset to its factory-installed values in a SETUP sub-menu. Press and hold PROG and then press to get to the FACT sub-menu. When the device is reset, the total td

reclosings meter goes to zero and the relay is reset.

By pressing and holding the td and Id keys for more than 2 seconds, you can lock the setup menu. It shows BLOQ YES if it is locked, BLOQ NO if not.

MENU LOCKING/UNLOCKING

Test TEST

Leakage current Instantaneous value

Trip cause Display message

Dif/ valueDifferential

Magnetotérmica MAG

Other display MESSAGES

SAVEEXITOVR

Validates configuration valuesLeaves programming mode

Value reading out of range

Parameters Non-configurable values

Trip current 30 mA

Trip time INS

Código Tipo Sensibilidad (A) Retardo disparo (seg.) Code Type Sensitivity Tripping delay

To operate downstream from the WRU-10 k relay safely, manually lower the Kopps circuit breaker switch

SAT 1 - General unit error. Disconnect the unit and call the Technical Assistance Service (SAT).SAT 2 - Factory-installed values, a memory reading / writing problem has caused the unit to reset to its factory-installed values. The message SAT 2 is shown on the display until an operator pushes the RESET button.

SAFE DISCONNECTION

ERROR MESSAGES

1-2

56

78

9

10

11

12

EXTERNAL RESET

DESCRIPTION OF THE TERMINALS

RELAY OUTPUT CONTACT LOCKING NC RELAY OUTPUT CONTACT LOCKING

POWER SUPPLY 230 Vac (PHASE or NEUTRAL)

POWER SUPPLY 230 Vac ( NEUTRAL or PHASE)

RELAY OUTPUT CONTACT TRIP NO

RELAY OUTPUT CONTACT TRIP SHARED

RELAY OUTPUT CONTACT TRIP NO

CIRCUIT BREAKER STATUS

Voltage-free, uninsulated

Nominal Current: 0.25 Aac

Rated Voltage: 230 Vac

Nominal Load: 62.5 V·A

Protected by varistor: 420 Vc.a.-10Ac.a

l: 5 Ac.aNominal Current

l: 250 Vc.aRated Voltage

: 1.250 V·ANominal Load

- SENSITIVITY SETTINGS

PROG

Type A super-immunised electronic earth leakage relay with 28 mm built-in toroidal. Device with AUTOMATIC EARTH LEAKAGE RECLOSING.

Symbol in the LCD. It has a programmable output relay for tripping the main relay. It REC

has a voltage-free input for external tripping and rearming. Assembly on DIN rail 46277 (EN 50022) or on a 72 x 72 panel using an accessory (M5ZZF1). The display shows settings values and instantaneous leakage current values (TRMS).

If the unit is used in a manner other than that specified by the manufacturer, its protection may be compromised.

Unit power supply Operating conditions Safety

WIRING USING PLUG-IN TERMINALS

Voltage 230 Vc.a. +/- 30% Frequency 50/60 HzPower 4,5 VA

Temperature -20....+ 70º C Relative humidity 5.... 95% Max. working altitude 2.000mProtection IP20

Category III, 300 Vac EN61010Double-insulated electric shock protection class IIImmunised against shock waves up to 2kV

FEATURES

IMPORTANT!

Use the button to move through the sub-menus, PROG and use the button to display the values to be selected. Press to validate a value. The unit PROGsaves the value and displays SAVE, exiting programming mode. If the keypad is inactive for some time, the unit will automatically exit programming mode and show EXIT on the display without changing the configuration.

Page 2: Electronic earth leakage protection relay with earth ...docs.circutor.com/docs/M049A01-03.pdf · CONNECTION DIAGRAMS SETUP MENU PLUG-IN TERMINALS Earth leakage protection and automatic

CONNECTION DIAGRAMS

SETUP MENU

PLUG-IN TERMINALS

Earth leakage protection and automatic reclosing via an external circuit breaker element associated with output 9-11.

Kopps circuit breaker

ACCESSORIES

PROGRAMMING RECLOSING SEQUENCES AND AUTO/MANUAL

Electronic earth leakage protection relay with earth leakage reclosing WRU-10 K 0.03 - 3A

NL1 L2 L3

CARGA / USE

ON / OFF externoExternal ON/OFF

WRU-10

4 5 6 3

9 10 117 8

1 2

3

1

2

12

RECREC

Automatic reclosing activated

CIRCUIT BREAKER MCB. 2 POLES WITH NO EXTERNAL SIGNALLING

CIRCUIT BREAKER MCB. 4 POLES WITH NO EXTERNAL SIGNALLING

Type Code In (A)

MCB.P C-2p -6A [*] P20210 6

MCB.P C-2p -10A [*] P20211 10

MCB.P C-2p -16A [*] P20213 16

MCB.P C-2p -20A [*] P20214 20

MCB.P C-2p -25A [*] P20215 25

MCB.P C-2p -32A [*] P20216 32

MCB.P C-2p -40A [*] P20217 40

MCB.P C-2p -50A [*] P20218 50

MCB.P C-2p -63A [*] P20219 63

Type Code In (A)

MCB.P C-3p+N-10A [*] P20221 10

MCB.P C-3p+N-16A [*] P20223 16

MCB.P C-3p+N-20A [*] P20224 20

MCB.P C-3p+N-25A [*] P20225 25

MCB.P C-3p+N-32A [*] P20226 32

MCB.P C-3p+N-40A [*] P20227 40

MCB.P C-3p+N-50A [*] P20228 50

MCB.P C-3p+N-63A [*] P20229 63

CIRCUIT BREAKER MCB TECHNICAL FEATURES

CIRCUIT BREAKER

REMOTE CONTROL

Control current 1.5 A

Activation impulse 20 ms

Deactivation impulse 20 ms

MECHANICAL FEATURES

Assembled DIN rail

Mechanical w orking life 20000 operations

Weig 2 poles : 375g / 4 poles: 615 g

Dimensions 52.9x85x72,9 mm

Protection degree IP 20 (DIN 40050)

M049A01-03-18A

No CNo

CONTACTS 230V~; 5A

CONTACTS 230V~; 0,25A

R

Gauges In (A)

Nominal cut-off power

Control voltage

Working frequency

Operating temperature

Storage temperature

6 -10 -16 -20 -25 -32 -40 -50 -63

6 …63 A : 10 kA

210... 240 Vac

50/60 Hz

-25....+55 ºC

-40....+ 70 ºC