Upload
doankhanh
View
215
Download
2
Embed Size (px)
Citation preview
CHAPTER FOUR:
• LIGHTING FIXTURES
• ELECTRIC MOTORS
• LIGHT BULBS
• WIRE AND CABLE
• CORDS
• WIRING DEVICES
• BATTERIES
• TELEPHONES & ACCESSORIES
ELECTRICALSupplies
44Copyright © 1992, 1995, 2004 National Retail Hardware Association
E L E C T R I C A L S U P P L I E S
2
■ The consumer trend in the elec-trical category is shifting towardhigher-end products that havemodel variety and energy-savingfeatures. Energy-efficient lightingproducts are finally beginning tocatch on with consumers, long after the 1992 passage of the NationalEnergy Policy Act, which required lighting manufacturers to replaceoutdated lamps with brighter, more energy-efficient models.
The National Electrical Manufacturers Association, using moneyfrom manufacturers, has boosted demand by conducting a nation-al promotional campaign to inform consumers about the benefitsof energy efficiency.
The Environmental Protection Agency (EPA) further helped mattersin 1997 by creating its Energy Star® label, which manufacturers mayvoluntarily display on energy-efficient lighting fixtures if they meetprogram guidelines. Fixtures carrying this label can trim the cost oflighting high-use areas, such as bathrooms and kitchens, by 50 per-cent to 60 percent. In addition, bulbs and lamps for these fixtures lastthree times longer than incandescent bulbs.
Another key trend in the category is increased demand for low-voltage outdoor lighting. Motion-sensor lights are popular withconsumers concerned about home security.
Many consumers are scared of electrical projects, and for validreasons. Retailers should remind consumers of the dangers posedby household electrical systems. For example, tell consumers toshut off electrical power at the fuse or circuit breaker box beforebeginning any wiring project. And make sure they consult localbuilding codes before embarking on an electrical project.
ELECTRICALSupplies
LIGHTING FIXTURES
■ INTERIOR LIGHTINGInterior lighting must satisfy two require-
ments: function and design. A customer
replacing an existing fixture will be con-
cerned mainly with the design, whereas a
person remodeling or adding a room may be
concerned with both function and design.
Along with design and function, many cus-
tomers are becoming more concerned about
conserving energy. Lighting takes only 12
percent to 15 percent of the electricity used
in a home. Customers are finding ways to
reduce this expense by using more efficient
lighting and advanced lighting controls.
Task lighting gives localized light for specif-
ic activities such as reading, writing, sewing
and food preparation. The light should cover
the entire task area and be located so shadows
are reduced to a minimum. Under-cabinet
lighting is a popular form of task lighting in
kitchens or under shelves.
General or ambient lighting provides
comfortable background brightness in a
room. Light reflected from walls and ceilings
or from large sources overhead reduces light-
ing contrasts and contributes to the comfort
of the environment.
Accent or specialty lighting cre-
ates a mood and adds interest to a
room. This kind of lighting is pri-
marily for decorative effects and
should be used in conjunction
with task and general lighting.
Track lights, a system of movable
lights wired to a metal track, make
a great accent lighting choice for
living rooms, bedrooms and din-
ing rooms. Track lighting is avail-
able in many colors, sizes and
shapes, is easy to install and flexi-
ble since the lights can be moved
around and repositioned.
Recessed can lighting and sur-face-mounted fixtures are one way
to provide ambient lighting.
Increased amounts of light are
achieved using additional fixtures.
This should be strictly observed
because of the heat produced. Maximum
wattage limitations are indicated on all fix-
tures and should be followed. Recessed light-
ing is good for rooms with low ceilings and
can be used to supplement existing light in
kitchens and bathrooms.
No-glare lighting is also available in over-
head fixtures, undercabinet lights and desk
lamps. No-glare lighting fixtures are
designed with a louver that cuts off high-
angle light to provide glare-free, true-color
lighting. No-glare lighting works well to pre-
vent eye fatigue in home offices where com-
puters are used. For more information, click
(Installing Wall or Ceiling Fixtures)The following guidelines suggest lighting
standards for various rooms.
Living AreasPermanent lighting fixtures are not a
major consideration here because so many
homes depend on table or floor lamps. Wall
lighting (fluorescent tubes shielded by a cor-
nice or valance) and recessed down lights
are frequently used permanent fixtures.
Track lighting is also applicable.
Place light sources at various heights with-
in the room to add visual interest. Use
translucent shades on table lamps to con-
tribute to the ambient light level. Use a
halogen, floor-mounted directional fixture
under a large plant to create an artistic pat-
tern on the ceiling.
A room larger than 225 sq. ft. will require
separately controlled wall lights along two
walls or multiple ceiling fixtures rather than
a single light source.
BedroomsBedrooms under 150 sq. ft. use a total of
120 to 200 watts in a ceiling fixture, 4' to 9'
of wall lighting or one 150-watt recessed fix-
ture. Over 150 sq. ft. use 120 to 200 watts in
a ceiling fixture, 12' to 16' of wall lighting,
or five to eight 20- to 75-watt reflector bulbs.
For closets, use a 40- to 60-watt fixture
and 60 to 100 watts in walk-in closets. These
should be ceiling mounted at least 18" from
clothing or stored items, or use a 20-watt
fluorescent above the door header.
BathroomsOverall lighting should consist of at least
one recessed 75-watt unit for each curtained
tub or shower area. If the lavatory counter is
wider than 3', overhead fluorescent tubes
should be installed along the entire length
of the counter in a soffit extending at least
18" from the wall. Smaller lavatory areas
need 20-watt fluorescent tubes mounted on
either side of the mirror and cen-
tered 60" from the floor.
A ceiling fixture over the lavato-
ry mirror can provide extra light.
KitchensEvery 50 sq. ft. of floor space
needs about 150 watts of incan-
descent or 50 watts of fluorescent
light from a ceiling fixture.
Additional fixtures should be
installed over sinks, work areas,
etc. A 20-watt fluorescent tube,
mounted under cabinets above
the countertop, is considered ade-
quate for every 3' of counter space
to be lighted. Light the sink area
using recessed halogen or fluores-
cent valance lighting. Fluorescent
strip lights can be concealed
above cabinets to provide soft,
indirect illumination. Suspend
E L E C T R I C A L S U P P L I E S
3
GENERAL LIGHTING SUGGESTIONS
Here are a few general guidelines to help consumers begin their planning.The light sources, lighting fixtures and construction of the home, as well asthe materials and colors of the furnishings, will affect the lighting plan.
INCANDESCENT BULBS
14, 15 watts—Use in multiple-socket hallway fixtures, small decorativewall and table lamps, recessed aisle or step lights.
40, 55, 60 watts—Wall fixtures and sconces, multiple-socket ceilingfixtures and floor or table lamps, pole and tree lamps, recessed showerlights, single- and multiple-socket bathroom mirror fixtures.
70, 75, 95, 100 watts—Ceiling, wall and pendant fixtures.
150, 200 watts—Single-socket ceiling fixtures; floor, table and desklamps where three-way flexibility is not desired.
170, 250 watts—Portable table, floor and desk lamps with single-setting sockets.
THREE-WAY BULBS
30, 70, 100 watts—Portable dresser, table and hanging wall lamps.
50, 100, 150 watts—Floor, desk, table, double-dresser portable lamps.
100, 200, 300 watts—Large floor lamps with mogul (large) sockets.
decorative pendant lighting with compact
fluorescent globes over the table or island
for visual interest and energy savings.
Dining AreasA single ceiling fixture or hanging lamp
with at least 150 watts of incandescent light-
ing will usually suffice for an average dining
area. However, layering with light from a
variety of sources will provide flexibility for
creating different moods. The best choice is
to install a dimmer switch to control light
levels. Chandeliers with open sockets should
contain decorative bulbs. When using down
lighting over the dining room table, be care-
ful not to create dark shadows that might be
unbecoming to guests. Halogen directional
bulbs can be used in adjustable accent lights
to highlight plants, artwork or special fur-
nishings. In addition, china cabinets can be
lighted from within with small halogen or
miniature fluorescent bulbs.
Recreation AreasRelatively even lighting throughout the
room can be accomplished with one
recessed incandescent box, with a 100-watt
bulb for every 40 sq. ft. The number of fix-
tures can be reduced by using fluorescent
tubes, which produce as much as four times
the light of incandescents.
HallwaysUse ceiling-mounted fixtures with 75 to
100 watts for every 10' of hall or one
recessed fixture with 75 to 100 watts for
every 8'. Locate fixtures near closets or pow-
der rooms. For halls that need light all day,
recommend fluorescent fixtures; this saves
energy and reduces bulb replacement. Wall
sconces can add a warm, welcoming touch
to a foyer. Place wall or ceiling-mounted
lights and switches at the top and bottom of
stairs for safety.
Laundry AreasCenter a diffusing fixture with 60 to 80
watts of fluorescent or 120 to 150 watts of
incandescent light over appliances.
■ OUTDOOR LIGHTINGOutdoor lighting primarily serves a securi-
ty function. There are four basic types of
outdoor lighting: area, motion, landscapeand entrance/exit lighting.
There are a wide variety of systems for
outdoor lighting, including: high–intensity
discharge (HID) systems for mercury, metal
halide and high–pressure sodium light
sources; incandescent and tungsten halogen
fixtures; low-voltage lighting systems; and
incandescent or halogen PAR spotlights and
floodlights.
HID lighting provides considerably greater
illumination than other lighting commonly
available. Its cost is also higher, although
operating costs for lumens output is general-
ly less. Lumens are the measurement of light
output. Locate fixtures at both ends of the
house for better spread of light over the
entire yard. Many outdoor lighting units are
equipped with a photoelectric cell to turn
the fixture on at sunset and off at sunrise.
Timers are also available for outdoor units.
Fixtures to be used outdoors must seal
moisture and dust from wiring and switches.
Photocells provide automatic activation
from dusk to dawn.
Brass, aluminum, copper and baked-finish
metals as well as non-metallic products will
withstand extremes of outdoor exposure best
and offer long product life.
Outdoor lighting options have expanded
with the advent of low-voltage lighting. A
low-voltage system of six fixtures, for exam-
ple, usually uses less electricity than a 60-
watt bulb. It makes maximum use of elec-
tricity by splitting the light source.
A power pack is the heart of the low-
voltage system and should be located out-
doors by installing a weatherproof outlet
cover to keep snow and rain out. Because
of the low voltage, users will not receive
an electric shock even if they touch the
bare wires or cut a buried cable with a
garden tool. Consequently, these systems
are harmless to children and pets and do
not require cables to be buried. Power
packs typically range from 88-watt capaci-
ty up to 900-watt capacity.
To determine which transformer you will
need, add up the wattage of all the lamps
you plan to use—otherwise known as the
total nominal wattage (TNW). The total load
wattage of the lamps should not be less than
half of the transformer’s TNW or volt-
amperes (VA) rating, nor should it exceed
the transformer’s maximum capacity. If the
TNW is too high, divide the electrical load
between two transformers, or use a more
powerful one.
The first fixture should be installed at
least 1' above the ground and at least 10'
from the power pack. Low-voltage cable
transmits the electricity through a weather-
resistant, self-sealing stranded copper wire
between 12-gauge and 18-gauge. On runs
over 150' or when 10 or more lamps are con-
nected to one line, consider using heavier
cable (12- or 14-gauge), which reduces volt-
age drop and produces greater efficiency
from the lamps. A cable connector is used to
quickly join separate cable lengths or to split
cables going different directions.
The low-voltage lamp can be one of sever-
al types. Bayonet base lamps feature a cop-
per base that twists into the fixture socket,
while the wedge base lamp plugs into the
socket. Halogen lamps provide the most
energy efficiency. Remote photo control
automatically turns lights on at dark and off
during daylight hours. For more informa-
tion, click (Installing OutdoorWiring/Lighting).
Area LightingSpot and floodlights, along with tradi-
tional yard and security lighting, are used as
decorative lighting for landscaping, architec-
ture or holiday decorations. Colored lenses
can enhance different features; a green lens,
for example, will brighten foliage while
detracting from reddish objects.
Weatherproof sockets are essential here
because the fixture is often mounted near
the ground and pointed upward, exposing
the socket opening to rain and dirt. Most
outdoor lighting fixtures should be installed
only when the ground is completely dry,
although low-voltage systems can often be
installed anytime. Always consult the manu-
facturer’s instructions.
Well lights are designed to be buried,
and they cast light upward to create spe-
cial effects—for example, highlighting
landscaping.
E L E C T R I C A L S U P P L I E S
4
Motion LightingMotion sensors are popular accessories
to low-voltage outdoor lighting. They
attach to a power pack and mount on
walls or fences 6’ to 8' above the ground.
By detecting heat and motion up to 40'
away, they can cover 600 sq. ft. of proper-
ty to guard against intrusion.
Motion sensors are used with incandes-
cent, halogen and fluorescent bulbs.
When used in combination with a switch,
the user can manually switch on the
motion detector light.
Indoor motion sensors are also available
that automatically turn on a light when
someone enters a room.
Landscape LightingLandscape lighting is designed to accent
or light steps and pathways. It also serves a
decorative function and is relatively easy to
install. Advise customers not to hook up
landscape lighting with extension cords,
which are for temporary use only.
Mushroom lights, named for their sloped
shades, are commonly used along pathways
or in gardens. The bulb ranges from 5 watts
to 60 watts, and light is reflected downward
to give a soft illumination to the immediate
area near the fixture. Opaque, tiered lens
attachments shield light from the eyes and
direct it downward.
Bollard lights are cylindrical in shape,
with the faceted lens being part of that
cylinder. The lens diffuses light in a 360°
pattern to create a soft glow. Lens shields
can limit lighting to a 180° range.
Globe lights have spherical lenses, so they
cast light in all directions, providing subtle
illumination that can cover a large area
without glare. They are often used around
outdoor living areas.
Deck lights are designed to fit under
steps, benches and railings. They can be
mounted in many other ways as well.
Many other kinds of fixtures are also
made to be recessed into steps or planters
to directly illuminate pathways.
What follows are some common lighting
techniques used in landscape lighting.
Down lighting—shines light down from
large trees or eaves onto surfaces below
the light source to create safer passage-
ways at night. Down lighting is used to
outline driveways and walkways, mark
garden paths and flowerbeds, and to
accent patios and decks.
Uplighting—places fixtures in the ground
and directs light upward to create a dramatic
focal point that accentuates the detail in a
trellis or archway, illuminates fountains and
statuary or highlights small trees and shrubs.
Front lighting—positions light sources in
front of an object to highlight important
features and details.
Back lighting—illuminates objects or
plants from the back to highlight architec-
tural features and eliminates darkened areas
E L E C T R I C A L S U P P L I E S
5
WHERE TO USE BULBS
SPECIAL-PURPOSE BULBS
TYPE AND WATTAGE WHERE TO USE
Reflector Bulbs (2-1/2" dia.) Pole and tree lamps. Track lighting and recessed downlights(cans).
Reflector Floods (3-3/4" dia.) Track lighting and recessed downlights (cans).
Reflector Spots (3-3/4" dia.) Track lighting and recessed downlighting (cans).
Reflector Floods (5" dia.) Track lighting and recessed downlights (cans).
Reflector Spots (5" dia.) Track lighting and recessed downlighting (cans).
Floodlight Bulbs (4-3/4" dia.) Exposed weatherproof sockets under eaves, on garages,porches and other outdoor locations. Bullet-shaped outdoorfloodlight fixtures.
Bug Lights (yellow coating) In fixtures on patios, porches and entrances to houses.
Post Light Bulbs For post lights and coach lanterns.
Plant Lights Special color bulb finish enhances plant appearance, helps growth.
Rough Service Workshop, utility area, garage. Usually used on “troublelight” extension cord.
High-Intensity Bulbs Replacement bulbs for high-intensity portable lamps, theyprovide supplementary lighting for sewing, manicuring,hobby work and other close-up tasks.
Night Lights Use in plug-in fixtures in bedrooms, bathrooms and hallways.
Garage Door Opener Bulb Built to take shock and vibration.
Appliance Bulbs For ovens, refrigerators, freezers, microwaves, saunas andrange hoods.
Showcase Tubular Bulbs Approximately 6” long, frosted and clear. Use for picturelights, piano lights, aquariums, range hoods. Regular (medi-um) base.
Always check the fixture for required diameter and wattage limitations before recommending any ofthese bulbs. In general, floods are used for wide area lighting, spots are used for accent lighting.
FLUORESCENT BULBS
TYPE AND WATTAGE WHERE TO USE
Cool White Use for work areas only.
Warm White Good for living areas. Will harmonize with incandescent light-ing. Not for use where color discrimination is important.
Soft White The recommended fluorescent for living areas, baths,kitchens. Good color rendering. Harmonizes with incandes-cent lighting.
Different wattage tubes are different lengths. It is important to purchase the right length tube to fitthe desired fixture. Fluorescent tubes come in a variety of “white” colors. Use these guidelines to selectthe correct “white” tube for your use.
SOURCE: GE LIGHTING
behind large bushes and around doors and
windows for security purposes.
Area lighting—uses a floodlight or anoth-
er source of wide light to illuminate large
areas for evening entertaining.
Safety lighting—provides light for certain
areas, such as paths or steps, so people can
navigate safely.
Also available are landscape boulders that
blend naturally into the environment and
glow from within, casting illumination for
pathways. The faux boulders contain low-
voltage lamps and UL-listed components
that are easy to wire, can be installed on
their own system or added to an existing
low-voltage system.
Entrance/Exit LightingLight each entrance to illuminate the door
and to identify callers clearly. Recommend
wall lanterns, 25 watts to 60 watts, on each
side of the front door, centered 66" above
standing level.
For secondary entrances, recommend a
single fixture on the latch side of the
door. Lanterns with concealed downlights
light up wall-mounted house numbers as
well as the lock.
Suspended or over-door lanterns should
allow the light to flow downward. Wall-
mounted lanterns above doors should
accommodate 75 watts to 100 watts;
lanterns suspended from a ceiling 100
watts to 150 watts. With shallow, close-to-
ceiling fixtures for a porch, recommend
60 watts to 100 watts.
Exit or emergency signs are used to
identify exit areas in commercial build-
ings. Internally lighted models are the
most common.
LIGHT BULBS
There are three main types of light bulbs:
incandescent, fluorescent and high-intensitydischarge (HID). Generally, the higher the
wattage, the greater the light output.
Bulb FinishesOriginally, only clear glass was used to
make incandescent bulbs, which left the
bright filament exposed and resulted in a
harsh, glaring light. To remedy this, special
finishes are used to reduce the glare by dif-
fusing the light.
Clear glass is still used in applications
where accurate light control is desired and
in decorative lighting.
A frosted finish used to be the most com-
mon. Light loss averages less than 0.5 per-
cent due to the frosted finish.
Today, light diffusion is usually accom-
plished by applying a coating of fine powder
to the inside surface of the bulb. This coat-
ing provides a softer, more even distribution
of light and reduces glare. Inside-coated
bulbs are made in colors as well as white. A
variety of colors are available in outside-
coated bulbs which can be either transparent
or translucent.
Bulbs can be made to direct the light by
applying a reflecting material to the inside
surface of the bulb, or in the case of R, PAR
and sealed beam, light can also be directed
by beveled cuts on the surface of the bulb.
General Classes of Light BulbsBulbs come in a variety of shapes, sizes
and designs, each with a different purpose.
Bulb shapes have letter codes that corre-
spond to a general guideline. For example,
"C" refers to cone-shaped bulbs and "T" to
tubular bulbs.
General service is the Type A (arbitrary)
bulb used for lower-wattage bulbs from
about 15 watts to 200 watts. This type is
normally used for home lighting.
Vibration service is used on machinery or
where continuous vibration could cause
early failure of the filament. These bulbs
have lower lighting efficiency.
Rough service bulbs withstand shocks and
bumps. The relatively long filament is securely
mounted with many supports but has a lower
efficiency than general and vibration service
bulbs. They are used in workshops and
garages and with trouble lights.
Appliance bulbs are for ovens, refrigerators,
freezers, microwave ovens and range hoods.
Special coated bulbs are covered with a
Teflon™ or silicon protective material to
prevent shattering and to resist breakage
upon contact with water. They are recom-
mended for use in trouble lights and out-
door fixtures.
Decorative bulbs with clear or coated flame-
shaped glass, smooth B-type glass, C-line glass
with bent tip bulbs and globe-shaped bulbs
are useful in chandeliers and wall bracket fix-
tures where fashion is important.
Reflector® bulbs are usually made of “soft”
E L E C T R I C A L S U P P L I E S
6
CHECKLIST FOR OSHA STANDARDS
OSHA (Occupational Safety and HealthAdministration) standards affect the physicalfacilities of retail stores, but some of the rulesmake good safety sense for customers whoare embarking on do-it-yourself electricalprojects. Following are 10 OSHA rules thatcan be adapted as safety tips for consumers.
1. Be sure all electrical installations arein accordance with the NationalElectrical Code.
2. All live parts of electrical equipmentoperating at 50V or more must beguarded against accidental contact.
3. Protect all equipment against over-current.
4. Overcurrent devices in damp andwet locations must be of the typeapproved for this use.
5. Fuses and circuit breakers must belocated and shielded to preventburns or injuries.
6. All fixed electrical equipment mustbe grounded.
7. All electrical equipment—air con-ditioners, sump pumps, portabletools, others—must be effectivelygrounded.
8. All boxes and fittings in wet locationsmust be waterproof.
9. All electrical outlet boxes must bedurably and legibly marked with themanufacturer’s name and/or trade-mark. They must be rigidly andsecurely fastened to the surface towhich they are mounted. All outletboxes must have a cover.
10. Flexible cords must be in a continu-ous length when used-withoutsplices. They cannot be worn,frayed or taped. They must be con-nected so that tension will not betransmitted to joints or terminalscrews. Flexible cords cannot beused where fixed wiring is required.
glass for indoor service as a directional light
source with a built-in reflector. These are
available as spot or floodlights.
Projector (PAR) bulbs are made of hard
heat-resistant glass molded into a reflector
and lens that are sealed together. Most are
weather-resistant.
Elliptical reflector bulbs are shaped differ-
ently than the parabolic reflector bulbs,
bringing light to a focus a couple of inches
in front of the bulb. Less light is wasted in
deep-baffle fixtures, and glare is reduced in
downlight fixtures.
Light Bulb BasesLight bulbs come with a variety of bases
for use in different fixtures. The following
are the most commonly used base types:
Candelabra is a screw base used for spe-
cialty chandeliers and decorative lighting. It
is the smallest base for 120V lamps.
Intermediate is a screw base with applica-
tions similar to the candelabra bulb.
Medium is a screw base, standard on most
general-service bulbs of 300 watts and under.
It has a high degree of interchangeability in
bulb applications.
Mogul bases are used for larger, heavy-
duty bulbs rated at 300 watts and higher.
Skirted screw base is used on bulbs where
the neck is too large to fit into the desired
size base or where additional space between
filament and bulb terminals is desired.
Three-contact bases are used for three-
way bulbs that contain two separate fila-
ments in one bulb. They are similar to other
screw bases, but use an extra ring contact to
light wattage filaments separately or in com-
bination for three light levels.
Bayonet bases are used on specialty lamps
such as vacuum cleaners, sewing machines
and low-voltage bulbs. It provides a more
secure contact by using two small protrud-
ing pins on the sides of the base that fit into
slots in the socket.
Medium bi-post base is used for higher-
current bulbs.
■ INCANDESCENT BULBSIncandescent bulbs produce light by pass-
ing current through a thin coil of wire called
a filament. As the wire heats, it becomes
white hot and emits visible light.
Incandescent bulbs come in two types:
vacuum filled and halogen gas filled.
They are mainly used for general and task
lighting around the house.
Incandescent bulbs offer many advan-
tages: a concentrated light source that is easy
to direct; instant lighting; a wide assortment
of sizes, shapes and colors; easy mainte-
nance; and low initial cost.
Moreover, incandescent lighting is flexi-
ble, particularly since light levels (propor-
tional to wattage) for a given bulb-holder
can be changed simply by using the desired
wattage bulb. However, users should be care-
ful not to exceed bulb wattage recommenda-
tions for a fixture. Underwriters Laboratories
(UL) tags on fixtures designate the maxi-
mum allowable wattage. A mercury or fluo-
rescent system is typically limited to a single
bulb size.
An incandescent bulb can operate on
either direct current (DC) or alternating cur-
rent (AC). Wattage indicates the amount of
electric power used by a bulb to produce
light. Roughly speaking, the higher the
wattage, the greater the light output. Some
bulbs, however, produce more light output
per watt than others do.
Standard household bulbs have an aver-
age life of 750 to 1,000 hours, which can
be lengthened or shortened by the treat-
E L E C T R I C A L S U P P L I E S
7
1. Single-Contact Bayonet Incandescent Base
2. Candelabra Incandescent Base
3. Double-Contact Bayonet Incandescent Base
4. Intermediate Incandescent Base
5. Medium Incandescent Base
6. Medium Skirted Incandescent Base
7. Three-Contact Medium Incandescent Base
8. Mogul Incandescent Base
9. Three-Contact Mogul Incandescent Base
10. Circline Florescent Base
11. Medium Bi-Pin Fluorescent Base
12. Four-Pin Fluorescent Base
13. Recessed D.C. Fluorescent Base
14. Two-Pin Single-End Fluorescent Base
15. Four-Pin Single-End Fluorescent Base
6 7 8
1 2 3 4 5
9 10 11
12 13 14 15
LIGHT BULB BASES
COMPARING LAMP EFFICIENCIES
SupportWires
ExhaustTube
Base
Fuse
Heat DeflectingDisc
Button
Lead-inWires
Stem Press
FillingGlass
GLASS BULB
Filament
LAMP TYPE LUMENS PER WATT
Incandescent . . . . . . . . . . . . . . .18
Halogen . . . . . . . . . . . . . . . . . . .25
Mercury Vapor . . . . . . . . . . . . . .63
Fluorescent . . . . . . . . . . . . . . . .100
Metal Halide . . . . . . . . . . . . . . .125
High Pressure Sodium . . . . . . . .140
Low Pressure Sodium . . . . . . . .200
ment they receive. For example, a 120V
bulb operating on a 125V circuit may pro-
duce more light but won’t last as long as
one on a 120V circuit.
Long-life bulbs, which may last up to
twice as long as ordinary bulbs, have heavier
filaments that do not burn out as quickly.
However, these bulbs do not produce as
much light as standard bulbs.
Manufacturers disclose average light out-
put (in lumens) and average bulb life (in
hours) on package labeling.
The filament vaporizes as a result of cur-
rent flowing through it, and generally, the
bulb “burns out.” Three-way bulbs lose two
light levels when one filament burns out
because two filaments are used in the bulb
separately for two of the levels and together
for the third.
Bulb designations denote size and shape.
The figure following the bulb shape letter
designation is the bulb’s maximum diameter
in eighths of an inch. Thus, A-19 would
mean an A-shaped bulb with a diameter of
19 x 1/8", or 2-3/8".
Most standard bulb envelopes are made of
lime glass, but bulbs that must withstand
greater heat are made of harder, heat-resist-
ant glass. Hard-glass envelopes are used in
many high-wattage bulbs and in bulbs rec-
ommended for outdoor use where there is
danger of thermal shock from condensation.
Incandescent bulbs turn black as they
near the end of their lifetimes. Customers
should consider replacing darkened bulbs, as
they use the same amount of electricity to
produce less light.
■ HALOGEN BULBSHalogen bulbs are technologically
advanced incandescent bulbs used in resi-
dential and commercial applications. As
with incandescent bulbs, light is produced
by passing current through a coiled tungsten
wire, but the tungsten wire is enclosed in a
small quartz or high-temperature glass tube,
which is then filled with gases, including a
halogen gas.
The advantages of tungsten halogen bulbs
compared with standard incandescent bulbs
include less loss of light over lamp life;
smaller physical size for better directional
light control; whiter, brighter light; more
light per watt; and longer life. Like incandes-
cents, halogen lights have the advantage of
instant-on light. They are easy to use with
dimmers for energy savings.
Typical halogen lamps last 2,000 to 4,000
hours compared to 750 to 1,000 hours for
incandescent lamps. Wattage levels for home
use run from 5 watts to 500 watts.
Halogen bulbs are more energy-efficient
than standard incandescent bulbs. They gen-
erate up to 30 percent more light for the
same electricity. In addition, because their
bulbs blacken much less than incandescents,
they stay brighter as they age.
Halogen bulbs are available for accent and
task lighting and for general lighting appli-
cations. Since their brilliant, white light reg-
isters true colors, they are excellent for dis-
plays. Shading is important because of halo-
gen’s intense brightness. They are available
in A-type equivalent bulbs, PAR spotlights
and floodlights in a variety of sizes, as well
as low-voltage spotlights and floodlights.
Advise customers not to touch the glass
on halogen bulbs.
■ FLUORESCENT BULBS The two main types of fluorescent bulbs
are tubular and compact fluorescent.Fluorescent bulbs are used in commercial,
institutional, industrial and residential light-
ing. The popularity of the fluorescent bulb is
due to its high efficiency in producing light,
resulting in low lighting energy costs.
Fluorescent bulbs produce up to 105 lumens
per watt, compared with a 100-watt, type A
incandescent, which produces around 18
lumens per watt.
A fluorescent also has long lamp life,
relatively low brightness and low heat
content and glare compared with incan-
descent lamps. Fluorescents work well for
area lighting, especially in kitchen, bath
and task areas.
In a fluorescent bulb, current flows
through an atmosphere of inert gas and
mercury vapor, producing ultraviolet ener-
gy that is invisible to the human eye. A
phosphor coating on the inside of the
tube transforms the ultraviolet energy
into visible light.
Fluorescent bulbs can vary from straight
tubes 6" to 96" long to U-shaped tubes and
circular tubes. Wattages for home use range
from 4 to 75 watts.
Tubes also come in a variety of diameters.
Several common types are available in
reduced-wattage versions that consume 15
percent to 20 percent less energy.
The most common tube is the 1-1/2" used
in most bulbs from 15" to 96" long. The
smallest diameter is 1/2", used in low-
wattage twin tube designs. The largest is 2-
1/8" used for some high-wattage, non-resi-
dential installations.
Fluorescent bulbs are available in many
shades of white, as well as colors determined
by the type of phosphor used in the bulb.
These colors are indicated by the color ren-
dering index number printed on the bulb.
E L E C T R I C A L S U P P L I E S
8
COMPACT FLUORESCENT SHAPES
INCANDESCENT SHAPES
“A” Type Flame
PAR-30Reflector(indoor)
R-40 Reflector
Tubular Bulge Tube(LT-10)
Screw BaseLamp
Screw BaseBulb
PAR-30Reflector(outdoor)
LIGHT BULB SHAPES
HID SHAPES
Screw BaseCircular Tube
EBT
The higher the number, the more accurate
the color produced. Soft white fluorescent
bulbs are recommended for living areas,
baths and kitchens since they offer good
color rendering. Warm white bulbs, 3000K
and lower, emphasize reds and yellows and
are good for living areas, although not in
areas where color discrimination is impor-
tant. Cool white bulbs, 4000K and higher,
emphasize blues and greens and are used for
work areas.
There are a few important limits to the
use of fluorescent lamps. Because they use a
ballast, they can be dimmed only with spe-
cial equipment that is relatively expensive.
Standard household fluorescents are also
sensitive to temperature and therefore work
best indoors. High-output fluorescents are
for outdoor use and commercial application.
Ballasts have sound ratings— “A” is the
quietest; “C” is the loudest. If a customer is
complaining about the noise made by fluo-
rescent bulbs, suggest replacing the ballast.
The main objection to fluorescents in the
past has been their unflattering color. New,
color-corrected tubes overcome this draw-
back with recent developments in phosphor
technology. Premium types use rare-earth
phosphors to offer superior color that blends
beautifully with incandescents.
Electrical connections to the bulbs are
made to the bases at each end. The most
common is the two-pin base, designated
miniature bi-pin for small diameter bulbs,
medium bi-pin for average-size bulbs and
the mogul bi-pin for industrial bulbs. Single-
pin bases are used for instant-start bulbs,
and recessed double-contact bases are used
on rapid–start bulbs longer than 48".
Ballast OperationBecause fluorescent lamps are arc dis-
charge devices, they require special auxiliary
equipment to provide reliable starting and
to assure proper electrical operation. The
principle function of the ballast is to hold
operating current within proper limits and
to provide enough voltage to start the lamp.
Initially, all fluorescent lamps used a
“starter” or time-delay switch, which
allowed the electrodes to heat up prior to
the lamp starting. The starter is a small sil-
ver-colored cylinder found mostly in older
fluorescent lamps. When the lamp in an
older fluorescent begins to flicker, both the
tube and the starter should be replaced.
Starterless operation is achieved with
instant-start and rapid-start ballast designs.
Instant-start ballasts provide sufficient volt-
age to start fluorescent lamps without pre-
heating and are commonly used with single-
pin lamps and some special lamp types.
Rapid-start ballasts heat the cathodes con-
tinuously from a low-voltage transformer
within the ballast. This is the most common
type of ballast in use today for 40-watt
lamps and for all lamps that use recessed
double-contact bases.
Reduced-wattage lamps operate on most
existing ballasts, which can reduce wattage
14 to 20 percent. In addition, new ballasts
developed to minimize the wattage con-
sumed by the ballast itself further reduce
electrical consumption.
Compact FluorescentsCompact fluorescent bulbs offer different
style and performance from standard fluo-
rescent bulbs. Their color nearly equals Soft
White incandescents, and they offer superior
energy efficiency and long life.
The new compacts can be used in many
household fixtures. Circular units are
already familiar in ceiling fixtures and
artists’ lamps; new applications are wall
sconces, table lamps, lanterns, desk lights
and outdoor fixtures. Compact fluores-
cents feature sizes and shapes to match
most incandescent bulbs including one
that resembles a standard household bulb.
They can be as small as 4.5" long, and
some are the same size as their incandes-
cent counterparts. Not all fixtures
designed for incandescents may have
enough room inside the shade or glass for
the bulb.
Compact fluorescents cannot be
dimmed. Their life will be maximized if
they are used in locations where a light
stays on for hours at a time.
Compact fluorescent lamps typically last
7,000 to 10,000 hours, which is nine to 13
times longer than comparable incandescent
lamps. Energy efficiency can go up to 105
lumens per watt. Wattages for home use
range from 7 to 27 watts.
Reflector-shaped compact fluorescents can
replace standard R30 and R40 shaped incan-
descent reflector bulbs. Globe-shaped com-
pact fluorescents can replace standard G25
bath and vanity globes or G30 decorative
globes that are used in pendants. Decorator
or flame-shaped bulbs can replace similar
incandescent bulbs in chandeliers, sconces
and outdoor fixtures. Stick-shaped compact
fluorescents can replace standard Type “A”
E L E C T R I C A L S U P P L I E S
9
GLOSSARY OF ELECTRICAL STANDARDS
UL—Underwriters Laboratories Inc. is a not-for-profit independent testing laboratory.Manufacturers submit products to UL for testing. “UL-listed” means that the merchandise meetsminimum safety standards and is suitable and safe if used for the purpose for which it wasintended by the manufacturer.
ANSI—American National Standards Institute is a non-profit organization that coordinates thevoluntary development of national standards by industry, establishes national consensus stan-dards and represents United States’ interests in international technical standardization. Its stan-dards are developed and used voluntarily, becoming mandatory only when adopted by govern-ment bodies, such as the Consumer Product Safety Commission.
NEMA—National Electrical Manufacturers Association writes performance standards for prod-ucts. These standards are formed by committees that reach a consensus on individual matters. Atypical committee consists of manufacturers, industries that will use the product, UnderwritersLaboratories and other standard-setting groups. Consumer organizations are also on the com-mittee where matters that apply to them are considered.
NEC—National Electrical Code is based on safe, functional wiring methods and is updated everythree years. Many cities and states require that wiring conform to NEC specifications. Local andstate codes and ordinances also supplement the NEC.
CSA—Canadian Standards Association is an independent, not-for-profit Canadian organizationthat is similar to UL of the United States.
bulbs in portable lamps, while twist-shaped
compact fluorescents can replace standard
Type “A” bulbs in virtually any application.
There are also household-shaped compact
fluorescents that make ideal replacements
where the bulbs are visible in the fixture.
When choosing a compact fluorescent
bulb to replace an incandescent bulb,
compare the lumen output of the two
bulbs. For maximum energy efficiency,
select a bulb with the highest lumens and
lowest wattage combination. For example,
replace a 100-watt incandescent house-
hold lamp that produces 1,600 lumens
with a 25-watt compact fluorescent lamp
that also produces 1,600 lumens.
■ HIGH-INTENSITYDISCHARGE LIGHTING
High-intensity discharge (HID) bulbs pro-
duce light in a manner often described as
“lightning in a bottle.” As in fluorescent
bulbs, current flows through a conducting
gas and ballasts are required to start the
bulb and to control its operation. Unlike
fluorescent, most of the light comes from
the arc itself rather than through the
work of the phosphor.
The highest-efficiency light sources (the
most light per watt) are members of HID
families. The four basic HID types are
mercury vapor, metal halide, high-pres-
sure sodium and low-pressure sodium.
HID bulbs are primarily used for area
and security lighting. They feature a lifes-
pan of 20,000 to 24,000 hours. They come
in a variety of shapes and in medium and
mogul bases.
Mercury vapor lighting is used for exte-
rior area and security lighting, such as
dusk-to-dawn residential lighting.
Mercury vapor lamps provide twice the
light output per watt as incandescent
lamps. Along with the higher output, they
also have a longer lamp life, in some cases
up to 30 times as long. They are also more
expensive than incandescent or fluores-
cent. Mercury vapor bulbs produce a
bluish white color.
Self-ballasted mercury lamps can be
used with a ballast in incandescent fix-
tures and are available for 120V systems
in the lower wattages (up to 250 watts)
and for 240V systems in both lower and
higher wattages. These lamps deliver
slightly more light output per watt as the
incandescent lamps but have the long life
of mercury lamps.
Lighting systems that provide three to
six times the light output per watt of
incandescent lamps can replace incandes-
cent, mercury and self-ballasted mercury
systems. These metal halide and
high–pressure sodium (HPS) lamps require
specific ballasts, but offer major energy
savings to users.
The metal halide lamps feature medium
efficiency, with 50 to 110 lumens per
watt. They provide good color characteris-
tics (similar to cool white fluorescent
lamps) along with higher light output.
The high-pressure sodium lamps pro-
vide even higher light output per watt
than metal halide (50 to 150 lumens per
watt), with a golden yellow light.
Residential applications include security
and landscape lighting.
Low-pressure sodium bulbs feature the
highest efficiency, with 100 to 180 lumens per
watt. They produce an orange light.
When replacing HID bulbs, it is neces-
sary to use the exact bulb.
Energy-Saving BulbsCompact fluorescent bulbs can be
screwed into a standard incandescent
base. In addition to energy savings, their
main advantage is longevity. The lamps
give as much or more light as an incan-
descent bulb, with about 1/4 the wattage.
The bulb’s life is approximately 7,000 to
10,000 hours.
Energy-saving incandescent bulbs general-
ly provide nearly the same amount of light
output as conventional 60- and 100-watt
bulbs but use fewer watts.
Energy-saving PAR spot and floodlights
combine a special reflector design with
lower wattage to provide almost the same
amount of useful light, using considerably
less electrical energy.
Lighting takes approximately 12 percent
to 15 percent of the electricity used in a
home. However, the following will help cus-
tomers economize on the lighting portion of
an electricity bill:
o Turn off lights when you do not need
them.
o Use dimmers, when desirable.
o Use photoelectric cells or timers to turn
outdoor lights on and off automatically.
o Use reflector bulbs, especially for task and
E L E C T R I C A L S U P P L I E S
10
SELLING TIPS FOR ELECTRICAL PROJECTS
You can further both your sales and your “know-how” image by making sure the customer has every-thing needed for the job. Here is a checklist of items to go over in the store.
CABLE—Are they buying enough to reach the distance of the circuit? Allow at least 10 percentexcess to accommodate bends. Also, make sure the wire will handle the amount of amperage itwill be expected to draw. Explain that lower resistance wire, while more expensive initially, willsave money by reducing power loss or blown fuses and will increase safety.
BOXES—Go over the proposed circuit with the customer. They will need a box for every outlet,fixture, splice or other break in the cable.
WIRE CONNECTORS—At least two of these are required at every cable splice. Most light fixturesare pre-wired and must be spliced onto the circuit cable. Sockets and switches do not requireconnectors since cable is usually mounted directly to the device.
INSULATED STAPLES—These will be needed to mount the cable to the studs. Make sure theyare the right size for the type of cable being used.
INSULATED TAPE—Necessary for wrapping splices or taping any electrical wires.
TOOLS—Wire cutters, strippers stapler and screwdrivers are all part of the electrician's toolbox.
WALL PLATES—Does the customer have the right number and configuration of wall plates tomatch the fixtures being installed?
LIGHT BULBS—Most lighting fixtures are sold without bulbs. Does the customer have the prop-er size and number for the fixtures being purchased?
Two-Conductor CableTwo-conductor cable has one black wire
and one white wire. The black wire is always
the “hot” wire and must be fused. The white
is always neutral and must never be fused.
When current bridges the gap from the
110V hot wire to the neutral, it results in a
110V input to the appliance.
Three-Conductor CableThree-conductor cable contains a red
wire in addition to black and white. The
black and red wires are “hot,” carrying
110V each, and both must be fused. The
white remains neutral.
Bridging either 110V wire to the neutral
wire produces 110V. Bridging both 110V
wires results in 220V. This three-wire circuit
is increasingly common in home wiring; it
accommodates major 220V appliances, such
as ranges and air conditioners.
Grounding WiresBoth two- and three-conductor cables can
carry grounding wires, which provide a path
of least resistance from the frame or case of
an appliance to the ground to guard against
electric shocks.
The electric motor in a refrigerator, for
instance, might develop a current leak to the
frame of the appliance. A person touching
the refrigerator could create a path for the
current to pass to the ground. Consequently,
he would receive a shock.
A grounding wire, attached to the frame
of the refrigerator and directly to the
ground, would provide a lower resistance
path than the person. The electricity could
then pass safely to the ground.
The National Electrical Code (NEC) was
changed in 1996 to require a separate
ground wire for certain appliances to ground
their frames. If your customers are wiring for
120/240V or 120/208V ranges, wall-mount-
ed ovens, counter-mounted stoves or clothes
dryers, they need the separate ground wire.
Thermostat CablesThermostat cables are used in low-voltage
control, alarm and communication systems.
Most common types are braided, twisted
and plastic-jacketed types.
All three use solid copper conductors and
are twisted and insulated with plastic.
Twisted cable, which has no outer braid,
is used in doorbells, burglar alarms, intercom
telephones and public address systems.
Braided cable is covered with cotton
braid and is used primarily in thermostat
controls and other low-voltage, remote
control circuits.
Plastic-jacketed cable is also used in simi-
lar low-voltage applications.
Although thermostat cable is low voltage,
it carries a UL-listing for being flame-retar-
dant since it is installed in the wall. Wiring
used in security alarm and smoke detection
systems must be UL-listed.
TV Wire and AccessoriesTelevision lead-in wire connects the
receiving set to the antenna. Good quality
300-ohm wire is used for both VHF and
UHF receivers.
A TV set coupler is a loss-producing device
for connecting two or more TV receivers to
the same antenna. The loss introduced into
the circuit is small, but can be critical in
“fringe area” reception. In such areas, cus-
tomers should be told of this small loss and
to expect a slight reduction in signal
strength at the receiver.
A lightning arrestor mounts on the out-
side of the house as close to the TV receiver
as possible to protect the receiver against
lightning damage. The lead-in wire is
attached to proper contacts and the ground
rod to ground connector. Lightning will
jump the gap inside the arrestor and flow
into the earth if the circuit is properly
installed.
Home NetworkingMultiple computers in the home, satellite
dishes, cable TV, sophisticated audio systems
and home theaters have given rise to the
desire for home networks.
The heart of these systems is the network-ing hub. Usually thought of in conjunction
with computers, the home network hub dif-
fers in that it provides central control of
computers, peripherals, phones, TVs and
audio components. This is the unit where
most of the wiring from different locations
comes together to meet.
Most home networks use coaxial,
Category 3 and Category 5 cable. Coaxial
cable is used for TVs, VCRs and satellite
equipment. Category 3 cable is used for
telephones while Category 5 is used for
telephone, fax and computer systems.
Some cables combine different functions
into one cable.
“Structured” wiring refers to a bundle of
cables that runs from the networking hub to
meet a home’s future information-carrying
needs. This wire bundle may consist of some
combination of Category 5 cables, fiber-
optic lines, Category 3 cables and coaxial
lines. New home construction and renova-
tion jobs should try to accommodate wiring
in this fashion to meet the bandwidth needs
of digital transmissions.
Jacks are used to terminate the cable.
E L E C T R I C A L S U P P L I E S
12
USE COMMON SENSE TO AVOID ELECTRICAL HAZARDS
Stress to your customers that they use common sense when working with electricity. Beforeproceeding with any electrical work, make sure the main disconnect on the service entrancepanel is at the “off” position or pull the main fuses if the panel is the cartridge fuse type.
When working on individual receptacles or light switches, turn off the circuit breaker for the cir-cuit being worked on, and test with a test light before handling bare wires.
Other tips:
• Never stand on wet or damp floors when working at the service entrance on any electricaldevice. Wear rubber gloves and stand on a rubber mat for added safety.
• To avoid overloaded circuits, never use a fuse which has a higher amperage rating than therating on the wire for the circuit.
• Never run more appliances from one receptacle than the amperage rating for that outlet.
• Never use a penny or tinfoil in a service panel instead of a fuse.
There are different jacks for telephones,
computers, satellite, audio and video equip-
ment. Many of these jacks and cable connec-
tors require special tools for installation.
Patch cords are used to connect different
computer and audio/video devices with one
another or with a central networking device
such as a hub.
Binding posts are used to connect bare
speaker wire, while F-Connectors are used
with coaxial cable.
Home Wiring TestersNew tools and testers are making the job
of installing and maintaining household
wiring and home networks easier and safer.
Non-contact voltage testers allow you
to see if a line is carrying current without
touching the line. Features include audi-
ble and visual alarms, battery-checking
circuitry and a size that is small enough
to fit into a pocket.
Circuit analyzers and receptacle testersare designed to determine if circuits are
wired properly. They plug into any grounded
electrical receptacle and test receptacle
wiring and grounding in standard and GFCI
outlets. A convenient chart and lights tell
you if the circuit is wired properly, if the
wiring is reversed, the ground is not working
or if there is an open line.
A ground fault receptacle tester and ana-lyzer performs the same functions for GFCI
receptacles plus it also tests the ground fault
feature. Similar tools are available for tele-
phone and computer lines.
Circuit trackers easily locate circuits with-
out turning off breakers or fuses. They fea-
ture a transmitter that is plugged into a live
outlet. A receiver is used at the service panel
to identify the circuit into which the trans-
mitter is plugged. Some models incorporate
a visual and an audio indicator. Adapter kits
allow you to identify light switches and light
bulb sockets.
An in-wall pipe and wire detectorlocates metal objects and live unshielded
conductors behind drywall, paneling and
plaster walls.
■ CORDSElectrical cords provide a path for current
to travel from a fixed outlet to an appliance.
The type of cord needed for a given job
is determined by the amperage drawn by
the appliance, whether the appliance is
grounded and the degree of physical pro-
tection required.
Extension CordsExtension cords are for temporary power
only. Make sure the customer uses the right
size for the application. Outdoor and
indoor/household types are available, as well
as commercial cords with heavier gauges,
higher amp ratings and extra flexibility.
Indoor extension cords come in two-
wire and three-wire cords in lengths from
6' to 15' with 6' and 9' being the most
popular lengths. White and brown are the
basic colors.
Outdoor extension cords are used for out-
door power tools and exterior lighting. They
come in 16/3, 14/3 and 12/3 wire, and the
most common lengths are from 25' to 100'.
Heavy-duty extension cords should be used
with high-wattage appliances. Be sure to
match the construction of the cable to the
job. SJT round cord is better able to with-
stand the constant flexing of use with power
tools than SPT2.
Any UL-listed cord will carry a UL label
near the female end. Many companies are
now using an alternative method of label-
ing allowed by UL, which permits the UL
markings to be molded into the cord
ends. This ensures a permanent marking
that cannot be provided with a label. It is
important to check for this UL insignia,
whether it is a label or a permanent mark-
ing. Non-listed cords can be similar in
appearance to listed ones.
To be UL-listed for outdoor use, three-wireround cords must have connector and cap
molded to the cord and a lip on the end of
the connector to prevent misuse. Beginning
in 1998, UL-listed outdoor cords began
appearing with the “SJTW” marking on the
cord, not “SJTW-A” as was previously used.
For a period of time, either marking will be
acceptable for outdoor use.
Grounding cords are available in both
heavyweight and heavy-duty construction
differing from standard cords, because they
have three conductors instead of two and
are equipped with a three-prong grounding
plug and connector.
An assortment of specialty extension
cords includes:
Step-saver cords—have built-in pendant
switches to control appliances and lamps
across the room.
Wind-up reels—keep tangled, foot-catch-
ing cords off the floor.
In recommending a proper extension cord,
pass along these buying and safety tips:
E L E C T R I C A L S U P P L I E S
13
TYPES OF CABLE AND CORD
Non-Metallic Sheath Cable
Armored Cable
Type SPT Cord
Type S and SJ Cord
Type HPD Cord
AMPERAGE RATINGS FOR CORD
AWG WIRE # MINIMUM AMPERAGE
0 . . . . . . . . . . . . . . . . . . . . . . . . .125
2 . . . . . . . . . . . . . . . . . . . . . . . . . .95
4 . . . . . . . . . . . . . . . . . . . . . . . . . .70
6 . . . . . . . . . . . . . . . . . . . . . . . . . .55
8 . . . . . . . . . . . . . . . . . . . . . . . . . .40
10 . . . . . . . . . . . . . . . . . . . . . . . . .30
12 . . . . . . . . . . . . . . . . . . . . . . . . .25
14 . . . . . . . . . . . . . . . . . . . . . . . . .18
16 . . . . . . . . . . . . . . . . . . . . . . . . .13
18 . . . . . . . . . . . . . . . . . . . . . . . . .10
E L E C T R I C A L S U P P L I E S
14
CORD, WIRE AND INSULATION
DESIGNATOR TYPE OF INSULATION GENERAL USE
WIRE
R Rubber All-purpose building wire, 600V, 60°C.
RH Rubber & cotton braid Same as R with heat resistance to 75°C.
RW Rubber Same as R with moisture resistance.
RHH Rubber & cotton braid Same as R with heat resistance to 90°C.
RHW Rubber & cotton braid Same as R with heat and moisture resistance to 75°C wet or dry.
RH/RW Rubber & cotton braid Same as R but 75°C dry and 60°C wet.
T Thermoplastic vinyl All-purpose building wire, 60°C.
THW Thermoplastic vinyl Same capacity as RHW.
TW Thermoplastic vinyl Same as RW.
WP Cotton braid Weatherproof for suspended outdoor use.
NONMETALLIC CABLE
NM Paper overlaid with cotton For dry use only, 60°C. Braid or plastic
NMC Plastic or neoprene coating Wet or dry use, 60°C. Only cable approved for barns.
USE Rubber & neoprene Underground service entrance. Fusing or additional covering not required.
UF Thermoplastic Underground feeder and branch cable. Can be buried but must be fused.
ARMORED CABLE
ACT Armored cable on plastic Branch circuits and feeders. Insulated wires.
ACU Armored cable on rubber Same as ACT. Insulated wires.
CORDS
C Rubber & cotton braid Lamps and portable appliances in dry areas, 300V and 600V, 60°C.
HPN Neoprene Same as HPD with moisture resistance.
SP-1 Rubber Lightweight for lamps, clocks, etc., 300V.
SP-2 Rubber Same as SP-1 with heavier construction for more general use, 300V.
SP-3 Rubber Heavier construction than SP-2 for use with refrigerators, air conditioners, etc., 300V.
SPT-1, SPT-2, SPT-3 Thermoplastic Correspond to SP-1, SP-2 and SP-3.
S Rubber and jute twine Heavy duty for power tools, battery chargers, etc., 600V.
SJ Rubber and jute twine Same as S but only 300V.
SJO Rubber and jute twine Same as SJ but oil resistant, 300V.
AWG 0 2 4 6 8 10 12 14 16 18
Actual Size
Maximum amperage 125 95 70 55 40 30 25 18 13 10
Actual size of copper wires and maximum amperage allowed in permanent installation.
o Advise customers to follow manufacturer
recommendations for outdoor use and to
not use a household extension cord out-
doors.
o Damaged or worn extension cords should
be replaced, not repaired. Replace older
cords that are non-polarized and don’t
have safety closures.
o Know the length of cord needed and elec-
trical load it can carry. Cord should reach
easily from wall outlet to appliance. Never
put two short cords together to obtain
needed length.
o Only use an extension cord that has been
tested by a nationally recognized testing
laboratory such as UL, CSA or ITS.
o Keep cords out of the reach of children
and out of high-traffic areas where people
might trip over them.
o Never remove the third prong or cut
down the blade of a plug to fit a non-
polarized receptacle.
o Do not cover cords with carpet, furniture
or appliances.
o Cord should be permanently bonded
to the plug and the connector to
ensure a good connection and no
exposed wiring.
Appliance CordsAppliance cords combine cord and con-
nector. The difference between cord sets can
be in type of connector and/or cord used.
Free-end attachment cord sets without
connectors are used in re-wiring direct
attachment irons, toasters and similar small
appliances. They have pre-tinned ends to
speed up wiring.
Range and Dryer CordsRange and dryer cords are free-end types,
commonly called “pigtails,” attached direct-
ly to the appliance. Free ends are fitted with
cable terminals that connect to screw termi-
nals of the appliance to assure positive con-
nections. A metal clamp attached to the
cable serves as a strain relief at the point
where the cable enters an appliance and a
cord protector.
Heavy-duty attachment plugs for
ranges and dryers are much larger than
standard attachment plugs. Most are “L”
shaped with a power cord feeding out
the side of the plug.
Sizes range from 30 amps for dryers and
small ranges to 50 amps for larger ranges.
The different amperage attachment plugs are
not interchangeable because of a difference
in their configuration.
A recent change in the National
Electrical Code requires new range and
dryer receptacle installations to be 3-pole,
4-wire grounding receptacles. The neutral
(grounded circuit conductor) can no
longer be used to ground the frames of
electrical ranges and dryers.
Heating TapesThe primary function of heating tape is
to protect pipes from freezing. Today
there are heating tapes to warm the soil
for growing plants as well as tapes for pre-
venting water damage caused by snow
and ice buildup. They are all designed for
quick and easy installation.
Tapes are automatic, constant-heat or self-
regulating. A thermostat controls an auto-
matic tape. Constant-heat tape must be
manually turned on and off as the tempera-
ture changes. A self-regulating tape is made
of semi-conductive plastic that adjusts to
outside temperatures.
Other CordsPlastic parallel cord can be sold off the roll
for use with lamps, radios and other small
appliances. Plastic bell wire is used for bells,
buzzers, chimes, toy electric trains and other
similar systems and hook-ups.
■ WIRING DEVICESWires and cable form circuits to carry
electricity through a building. Wiring
devices described here are used to control
current flow and provide access points so
electricity can be used to power appli-
ances and lights.
SwitchesA switch controls power to lights and
devices by turning off the hot side of the cir-
cuit. Selection depends on design and load
capacity. For more information, click
(Installing or Replacing ElectricSwitches).
Conventional SwitchesA conventional switch makes or breaks
contact when a mechanically connected
tumbler or toggle bridges or breaks the line
contacts in the switch.
A single-pole switch is simplest and most
frequently used in the home, controlling
current on one circuit from one point. It fea-
tures two terminal screws.
Double-pole switches have four termi-
nal screws.
A three-way switch controls one circuit
from two separate points, such as a garage
light that can be turned on or off from the
house or the garage.
Four-way switches are used in connection
with three-way switches to control one cir-
cuit from three or more points.
Single-pole and three-way switches are
available with lighted handles that glow in
the dark.
Dimmer SwitchesDimmer switches control the amount of
current in a lighting circuit, allowing the
user to control the degree of light from off
to full capacity.
Some dimmers control the amount of
voltage going to the lamp, increasing or
reducing the amount of light given off.
Other dimmers control a portion of each
alternating current cycle applied to the
lamp. This means a solid state dimmer turns
the light off and on approximately 120
times per second. The on-off rate has no
noticeable effect on the life of the bulb or
on the eyes of persons in the room.
One undesirable side effect of this on-off
cycle is interference on AM radios. Some
dimmers have radio/TV filters and printed
circuitry. There are table lamp dimmers and
dimmers that wire parallel into the lamp
cord. In addition, use of a dimmer will cause
some light bulbs to “hum.” The sound is cre-
ated from the turning on and off of the A.C.
sine wave. The rapid switching causes the
tungsten filament to resonate. Filament hum
is typical with inexpensive lamps that are
commonly installed in new construction.
The hum can be greatly reduced by upgrad-
ing to a lamp with a heavier filament.
It is also normal for a dimmer to get warm
E L E C T R I C A L S U P P L I E S
15
during operation, which is why dimmers are
built with a heat sink. If the load is not over
the wattage rating of the dimmer and is a
proper load for which the dimmer is
designed to control, the dimmer does not
need to be replaced.
There are several styles of wall dimmer
switches available. The most popular include
a push on-off/dial-to-dim type, a rotary full-
range type, a slide type and a toggle type
that offers full-range control but uses toggle
motion instead of a dial.
Dimmers also come in single-pole or
three-way construction. If two, three-way
switches are involved, only one of them can
be a dimmer. Otherwise, the setting will not
work, although some toggle dimmers allow
two three-way switches to be used.
An air gap switch is built into all dim-
mers as a safety feature to ensure that
power can be removed to the output—this
is a UL requirement.
Specialty SwitchesRocker switch—used in place of a stan-
dard wall switch, it is activated with a push-
button mechanism. Useful near a doorway
or area where hands might be full or for
appearance and for range hood and appli-
ances.
Delayed-action switch—circuit remains
active for a few minutes after switch is
thrown. Useful in garage or breezeway,
allowing individual to get into the house
before light goes out.
Programmable memory switch—set to go
on and off at specific times for security or
safety purposes.
Photoelectric switch—operates by light
striking cell. Usually used on yard lights.
Daylight turns circuit off; it goes back on at
dusk. Circuit usually has a delay device to
prevent passing headlights from turning
light off.
Motion switch—turns the light on as you
enter the room. Used for both convenience
and security. Can be used to replace existing
wall switches.
Illuminated switch—is available in two
types. One has a small light that is on when
the switch is off so it can be easily found;
these are usually used at entrances to rooms
and in hallways. Pilot light switches are on
when the light is off and usually used for
out-of-sight lights such as those in the base-
ment, garage and attic.
Outdoor switch—enables electrical power
to be used for outside applications. They fea-
ture a turning lever inside a weatherproof
box cover with a toggle switch.
A second type of tamper-resistant outlet
utilizes an overlapping shutter system
that limits improper access to its ener-
gized contacts.
Voice-activated switch—offers a hands-
free approach to illuminating dark areas
quickly and safely. Voice-activated switch-
es incorporate the latest technology in
speech recognition to enable homeowners
to control the brightness of the lights.
Used in place of any standard wall switch,
they can be programmed with any com-
mand or language.
Silent switch—provides the same operation
as many of the other switches with little or
no noise. Silent switches are either mechani-
cal or solid state. The mechanical switch is
almost identical to the regular switch except
E L E C T R I C A L S U P P L I E S
16
Single PoleSwitch
Two SwitchesGroundingOutlet
Double Outlet
OUTLETS AND SOCKETS
Keyless CeilingLampholder
Pull ChainSocket
Pull Chain CeilingLampholder
3-waySocket
Push-ThroughSocket
WeatherproofPigtail Socket
Duplex receptacle 2-pole, 3-wire
grounding
Cord switch
OFF
LOOP HOLE
STRIP #14W
IREST
RIP
#12 WIRE
STRIP #14WIR
ESTRIP#12 WIRE
LOOP HOLE
Single-polegrounding switch
Three-way lighted toggle grounding
switch
TOP
STR
IP#1
2 WIRE
STRIP #14W
IRE
2 single-pole switches 3 single-pole switches
Weather protective cover for
single receptacle
TOP
Single-pole AC quiet switch
Three-way AC quiet switch
KEYKEY
STRIP#14
WIR
E STRIP#12
WIRE
6A 125V AC, 3A 25 0V AC, 3A 125VT
SWITCHES
for an extra bumper to reduce the noise. Prior
to 1991, silent switches contained mercury
and used no springs or mechanical devices.
This resulted in smooth, silent operation and
long life. Due to health concerns they were
removed from the market.
ReceptaclesThe wall receptacle, or outlet, taps the cir-
cuit to provide electrical power at a given
location. The slots in the outlet are designed
to match the plug blades of the appliance or
extension cord. Building codes specify num-
ber and spacing of outlets.
Receptacles come in flush- and surface-
mounted designs. Flush-mounted (recessed)
is the style most commonly used for perma-
nent installations.
Configuration of a receptacle refers to the
arrangement of slots or openings on the face
of the outlet. These arrangements vary
according to voltage and current rating of
the receptacle.
The most common configuration is three-
wire grounded. The most common outlets
used in homes are standard 15-amp, 125V,
three-wire designs. All outlets must be
grounded (three prongs).
A single- or double-wipe contact refers to
the area of the inserted prong on which con-
tact is made. In the case of a double wipe
contact, contact is made on both sides of
each blade.
All outlets should have a faceplate to help
prevent exposure to “live” wiring.
There are three basic ways to terminate
wiring in wall receptacles. First is the con-
ventional binding-screw method where
wires are stripped, looped and placed under
binding screws and then secured by tighten-
ing down screws.
Second is the pressure-lock method,
which eliminates binding screws. In this
method, connection is made by inserting a
stripped conductor, which pushes the con-
ductor into and against the terminal chan-
nel for a strong connection. Release slots
permit easy removal of conductors.
A third method involves clamp-type ter-
minals. Stripped wire is inserted into an
open clamp beneath a screw that is then
turned down to lock connection.
Some receptacles have small “pilot” or
guide lights. Appliance receptacles consist of
one vertical slot and two slanted slots and
are designed to be surface-mounted.
Specialty receptacles include twist lock,
childproof, surge suppressor, isolated ground
and RV.
Any flush-mounted receptacle may be
installed outdoors if covered by a protective
plate. These weatherproof covers have
hinged or threaded caps that cover the out-
let face. A self-sealing gasket fits between
the plates and the wall surface to add fur-
ther protection.
Safety outlets have spring-loaded caps to
prevent children from inserting objects into
them. To insert an attachment plug, its
prongs must be placed into the slots of the
protective cap, then turned 90 degrees or
until the slots of the outlet are exposed.
When the plug is withdrawn, the cover
automatically returns to its original protec-
tive position. A slight variation of this uses
an overlapping shutter system.
A second type of safety outlet utilizes a
cam to make an internal electrical con-
nection only when both blades are prop-
erly inserted.
Ground Fault CircuitInterrupters
Even with proper wiring and fusing or cir-
cuit breaking equipment, danger exists from
ground faults, which are the most common
cause of electrical shock.
Ground fault occurs when a person comes
into contact with a live
electrical wire. This can
happen by touching an
exposed wire, or by operat-
ing a faulty appliance or
power tool. Worn insula-
tion, hidden damage or
faulty connections can
make the metal housing of an appliance a
hot electrical conductor. Technically, this
happens when a wire develops a small leak
that will flow to the ground through any
path, including a human body. This can
cause serious shock, even death. Ground
faults can also cause electrical fires.
This hazard is so serious that the National
Electrical Code requires all new homes to be
equipped with ground fault circuit inter-
rupters (GFCI) in bathroom, kitchen, work-
room, outdoor, basement and crawl space,
garage and swimming pool receptacles. It is
a good idea to suggest that homeowners
install such a device in older homes. The
GFCI interrupts power quickly enough to
help prevent someone from receiving a
lethal dose of electricity.
GFCIs are available in receptacles, mod-
ules, breakers and extension cords.
Receptacles work for 15- or 20-amp circuits.
GFCIs should be tested monthly to ensure
they are working properly.
For convenience, a portable GFCI can
be plugged into any existing outlets,
either two-wire or three-wire, without
rewiring. Circuit breaker GFCIs can be
added in electrical panels to replace ordi-
nary circuit breakers. They should be
installed by a qualified electrician.
Surge SuppressorsWith increasing use of home computers
and other sensitive electronic home enter-
tainment equipment, there is a growing
need for protection from voltage surges,
often called spikes or transients. Surge pro-
tection is also needed because of the sheer
number of
potentially
destructive
spikes and
surges that occur in the home every day.
Surges can cause equipment to malfunction
and in severe cases cause catastrophic dam-
age or fire.
A surge is a transient increase of current,
voltage or power on an electrical system.
The larger, more destructive surges, generally
caused by lighting, can reach thousands of
volts. Surges can also come from utility
transformer switching, air conditioner opera-
tion, inductive and power switching, distant
lightning strikes and static discharges. They
put extreme stress on solid-state compo-
nents. Unchecked, such surges can quickly
destroy wiring, appliances, telephones and
other electrical devices.
Transient voltage surge suppressors (TVSS)
help protect sensitive electronic equipment.
E L E C T R I C A L S U P P L I E S
17
1
51
2
3
4
2
3
51
2
3
4
Surge protector power strip
Ground fault circuit interrupter
Surge protectors limit surge voltages by
discharging surge currents to ground.
Proper grounding is the strongest prereq-
uisite for proper surge protection.
The key component in almost all surge
protectors is metal oxide varisters (MOVs).
Under normal conditions, MOVs offer
high resistance to currents, preventing
normal currents from discharging to the
ground. Under surge conditions—typically
115 percent or more of a normal cur-
rent—the MOV’s resistance drops within
nanoseconds, creating a path with far less
resistance than the facility’s wiring for the
current to flow to the ground.
Basically, there are two types of sup-
pressors. One—also known as a surge
strip—is similar to a grounding adapter,
and the appliance plugs into it at the wall
outlet. Surge strips are not capable of sup-
pressing a powerful surge. The other type,
designed primarily to prevent lightning
damage, is mounted at the service panel
and protects the home where the electric,
telephone and cable lines enter. The
Institute of Electronics and Electrical
Engineers recommend whole-house surge
suppression as the most effective way to
protect against damage in the home.
Some of these suppressors also feature
filters that reduce or eliminate line noise
distortion that is picked up on radios, tel-
evisions and tape recorders. These filters
also help guard against accidental data
loss in home computers triggered by
spikes or line noise.
A whole-house surge protector mount-
ed at the service panel also protects sec-
ondary distribution wiring and electrical
appliances such as ovens, air condition-
ers, dishwashers and refrigerators from
most sudden power surges. To
increase the protection of elec-
tronic equipment, it is also rec-
ommended that a plug-in surge
suppressor be installed at the
point of use to supplement a sec-
ondary surge arrester.
Surge protectors are rated in
Joules and clamping voltages.
Once surge protection has been
provided at the maximum levels,
the unit must be replaced. Look for audi-
ble or visual indicators.
When selling surge protection devices,
stress the low cost of these products com-
pared to the high cost of repairing or
replacing branch wiring and electrical
appliances and equipment. However, a
surge protector will not protect against a
direct lightning strike.
Transfer SwitchesTransfer switches have become more
popular for new construction and after-
market installations due to weather
storms or accidental power outages.
Transfer switches are wired up to specific
load center circuits that will be utilized
when there is an emergency power out-
age. A portable generator is then plugged
into it and the switch transfers generator
power through the home’s existing electri-
cal circuits. There is no backfeed when
power is restored. Transfer switches elimi-
nate unnecessary extension cords and are
easy to install. Available in choice of
watts and number of circuits, plus option-
al accessories.
LampholdersLampholders are devices with a screw
base that hold light bulbs. Some have
switches to turn them on and off.
Lampholder sockets come in two basic
styles: single and multiple holders. The
most popular styles are twin light,
adapter, keyless, pull-chain tap socket,
push switch and turnkey.
A socket has three principal parts: shell,
cap and interior. The cap has three basic
styles: pendant, nozzle and side outlet. A
pendant is used with a suspended socket;
a cord enters through the top. Side outlet
fits cords coming through the side. Nozzle
caps are used on table lamps where cord
feeds through the bottom.
The shell is the body of the socket. It can
be brass, brass-finished, nickel-finished alu-
minum or plastic. Shell liner, interior and
cap may be disassembled for wiring.
Other sockets include pigtail weather-
proof, which comes with two short leads
for splicing into a power source.
Similar to the pigtail is the pin type,
but tightening down the top and forcing
contact pins into wire makes contact.
The most common size sold is medium
base (such as on 60- and 100-watt bulbs).
Other principal sizes are large-base mogul,
used on three-way floor lamps; and inter-
mediate, which is used on outdoor
Christmas tree bulbs, candelabra and
some night lights.
Appliance and HeaterConnectors
Connectors are used to connect older
style, heat-generating, small household
appliances with heat-resistant neoprene-
type HPN cords.
The connectors are molded of strong,
heat-resistant materials and come in a vari-
ety of styles, such as switchless, armored (or
heavily protected), side outlet and monop-
ull. All have spring cord protectors.
There are two standard sizes: 11/16"
and the miniature 1/2". Standard 11/16"
connectors generally fit on irons and
toasters. The 1/2" connectors are for cof-
feemakers, corn poppers, some electric
skillets and other similar appliances.
Bulb Life ExtendersExtenders have different
designs. One screws into a reg-
ular socket like a socket
adapter; the other is a small
disc placed in the base of the
socket before the bulb is insert-
ed. Bulbs last up to 30 times
longer than in standard sock-
ets; extenders should be recom-
mended for use where the bulb
burns continuously.
E L E C T R I C A L S U P P L I E S
18
Lampholder with pull cord
Keyless lampholderFluorescent lampholder
LAMP HOLDERS
Boxes, Fittings and ConduitAccording to the National Electrical
Code, every break or termination in an
electric cable must be enclosed in an
appropriate box. This rule applies to
switches and fixture connections as well
as to splices and junctions.
Wall boxes, ceiling boxes (junctionboxes) and weatherproof (outdoor) boxesare the main types of electrical boxes.
The three types of boxes are switch and
outlet, ceiling and utility boxes. Some are
made of galvanized steel with knockouts
to bring cable into the box. Non-metallic
(plastic) boxes are also available. Clamps
are included in some boxes to hold cables
in place.
Switch boxes are 2" x 3" in size and can be
used to house receptacles (outlets) as well as
wall switches. Switch boxes are designed so
that two or more may be fastened together
to form a larger box. The side walls must be
removed where the boxes join.
Octagonal ceiling boxes are used primarily
in ceilings to hold overhead light fixtures
and splices.
Utility boxes are used for the same pur-
pose as switch boxes, but their rounded cor-
ners make them suitable for surface wiring.
All boxes require covers. Box covers can
be made of metal or plastic and come in sev-
eral different shapes. The box covers may be
solid or feature knockouts for receptacles.
Electrical fittings are used to couple, con-
nect, fasten or ground conduit or cable.
Refer to local codes for requirements.
Cable is sometimes held in place by straps
or staples that are designed to handle differ-
ent sizes and is terminated by the use of
cable connectors. A number of other fittings
are available for service entrance installa-
tions, for grounding purposes or for haz-
ardous locations. Fittings can be installed
easily with a screwdriver, hammer or pliers.
Conduit is a raceway in which wires are
installed and protected. Types of conduit
include metal, non-metallic and flex. Each
conduit and size requires its own family
of fittings.
Metal conduit can be electrical metallic
tube (EMT); intermediate metallic conduit
(IMC); rigid or surface raceway.
Non-metallic conduit can be surface race-
way or polyvinyl chloride (PVC).
Flex conduit types include flexible
(steel and aluminum); electrical non-
metallic tube (ENT); and liquid tight
(metallic and non-metallic).
Conduit can be held in place by a variety
of straps and hangers that are designed to fit
a specific size diameter. The diameter of rigid
and EMT conduit differs, so the correct strap
or hanger must be specified. Lengths of con-
duit are joined together by couplings (either
rigid or EMT) and terminated by connectors.
Couplings and connectors generally are
either a set-screw type, threaded for rigid
conduit or rain-tight compression type for
damp locations.
PVC, EMT with rain tight fittings, liquid
tight, rigid and IMC conduit can be used
outdoors. For underground applications,
only PVC and rigid conduit can be used.
Surface Wiring DevicesSurface wiring switches, receptacles, lamp-
holders, etc., are installed entirely on the
surface of the wall as opposed to a normal
flush-mounted installation.
The device includes a box, cover and elec-
trical device in one unit. The unit is molded
of an attractive and sturdy plastic insulating
material, which makes it suitable for use in
the home as well as in barns, garages and
basements.
On-the-wall wiring systems created for
do-it-yourselfers allow the consumer to
run electrical wires to the point of use in
the home without breaking into the wall
or ceiling.
These systems have adapters that alter
existing outlet boxes, so consumers can tap
wires off them and snap together vinyl
channels that carry the wires to the new
outlet or switch. The channels hide unsight-
ly wiring and can be painted to blend into
any decor. Quick and easy installation and
economy are its major advantages.
Fuses and Circuit BreakersA fuse or circuit breaker box, commonly
called a main service entrance panel or load
center, is located between incoming power
lines and house wiring. It divides the main
power line into branch circuits. Load center
applications vary, depending on local codes.
Fuses and circuit breakers are safety
devices that break an electrical circuit
when it is overloaded. The fuse or circuit
breaker is sized to protect the branch cir-
cuit wiring between the breaker and the
outlet and does not protect anything
plugged into the outlet.
Circuit breakers come in three main types:
single, double and thin.
You can generally tell if a fuse is blown
by looking at it. If the fuse is blackened,
that indicates a short circuit has occurred;
if the metal is melted, then an overload
has occurred.
E L E C T R I C A L S U P P L I E S
19
WET LOCATION ONLYWHEN COVER CLOSED
Weather protective cover forduplex receptacle
3-hole outlet box4-hole outlet box 5-hole outlet box
BOXES AND COVERS
Switch Box
Utility Box Cover
BOXES AND ACCESSORIES
Octagon Box
Utility Box
There are several types of fuses. Plug fusesare available in 5- to 30-amp sizes and are
the most commonly used fuse.
Another fuse is the Type S, which pro-
vides a minimum time delay for the starting
of small household motors. Type S fuses pre-
vent anyone from replacing a lower-rated
fuse with a higher one. It consists of two
parts: the fuse and the adapter, which has a
different diameter for each fuse ampere rat-
ing. Once an adapter of a particular size has
been inserted into the fuse socket, it cannot
be removed and only the same rating fuses
can be used in that socket.
Cartridge fuses are used in high-current
applications, such as the main service box
and in clamp- or bar-type fuse boxes that
serve electric ranges, water heaters, clothes
dryers and air conditioners. Round cartridge
fuses have ratings to 60 amps; greater capaci-
ty (to 600 amps) requires a cartridge fuse
with knife-edge contacts.
A screw-in breaker can replace a fuse.
When a circuit malfunctions, a button on
this device pops out; it must be pushed in
to reset.
A circuit breaker contains a bi-metal strip
that breaks the circuit when current exceeds
a predetermined rating. A broken circuit is
indicated by the breaker’s switch being in
the mid-point position. This is commonly
referred to as a “tripped” breaker.
After the overload has been corrected, reset
the circuit breaker by switching it to the “off”
position and then to the “on” position.
Arc-Fault Circuit Interrupters Existing circuit breaker technology does
not protect against an occurrence known as
an arc fault. Arc faults are believed to cause a
significant percentage of the more than
43,000 electrical home fires, 330 deaths and
1,800 injuries annually.
An arc fault can occur when insulation
around cords, wires or cables is damaged or
deteriorates. In many cases, arc faults are the
results of aging wire. Arc faults can flare at
temperatures in excess of 10,000°F, igniting
surrounding combustible material.
In many cases, conventional circuit break-
ers do not respond quickly enough to arc
fault situations. By the time a circuit breaker
responds, a fire may have begun to smolder.
An arc-fault circuit interrupter (AFCI) is
a device that recognizes the unique char-
acteristics of many types of arcing faults
and acts instantly to interrupt the circuit.
In some devices, the arc-fault circuit inter-
rupter is integrated into state-of-the-art
circuit breaker design.
In 1999, the National Electrical Code
mandated that arc-fault interrupters be
installed on all 15- and 20-amp circuits in
bedroom outlets in new home construc-
tion starting in 2002. Some states mandat-
ed the change earlier.
Now available is a combination
AFCI/GFCI circuit breaker that is certified
by Underwriter’s Laboratories. The breaker
protects against electrical fires and dan-
gerous electrical shock hazards, enhancing
electrical safety in the home. It also sim-
plifies the installation process for electri-
cal contractors since there is no need to
wire two separate devices.
Wall PlatesWall plates include all plates used to fin-
ish or cover switches, receptacles or combi-
nation devices. Standard plastic wall platesare constructed with durable, smooth sur-
faces. Builders in new homes often install
inexpensive ones. There are also designer
and decorator plates, switches and recepta-
cles with smooth plastic faces in contempo-
rary colors.
Chrome-plated wall plates are made of
steel and brightly finished for lasting appear-
ance and durability.
Decorative wall plates come in many
styles and materials such as ceramic, alu-
minum, brass, wrought iron, stainless steel,
copper, wood and die-cast metals. Die-cast
products include switch and receptacle
plates made in finishes and designs to match
other functional hardware items such as
door handles, cabinetware and bath fixtures.
TimersTimers turn on lights and appliances at
specified intervals and times, making them a
useful security product. They are available
for outdoor or indoor applications and can
be electronic or mechanical. Spring-wound
timers for bath fans and spas have a manual
on-off switch.
Doorbell EquipmentIf not battery operated, doorbells require
AC step-down transformers to reduce house-
hold voltage to the proper operating voltage.
Standard doorbells operate at 10V or 16V.
Some doorbells may require other voltages,
depending on the design. Step-down trans-
formers should be UL-listed. The doorbells
themselves are safe, low-voltage devices that
do not require UL inspection.
Single or multiple-stranded bell wire is
used between the doorbell, the transformer
and the push buttons.
Push buttons are easily installed and
replaced. Bulb life for lighted push buttons is
approximately three to five years, and
replacement bulbs are available. Push but-
tons are available in lighted or unlighted,
recessed or surface-mounted styles.
Non-electric chimes are also available.
Wireless doorbells are all on the same fre-
quency, although some offer adjustable fre-
quencies. For more information, click
(Installing Doorbells).
Plugs, Adapters and TapsPlugs connect devices to the power sup-
ply through a receptacle. The typical plug
includes two blades or prongs, a molded
plastic body holding the two blades apart
and a blade/cord connection within the
plug body. When inserted into an outlet,
the blades become energized. Electricity
flows through the blades, through the
E L E C T R I C A L S U P P L I E S
20
Toggle Switch Plate
Weatherproof Outlet Plate
WALL PLATES
Combination Wall Plate
Double Outlet Plate
blade/cord connection and through the
cord, thus energizing the appliance.
Plugs come in polarized and non-polar-
ized varieties. Polarization helps reduce
the potential for shock. With polarized
plugs, one blade is wider than the other.
Three-conductor plugs are automatically
polarized because they can only be insert-
ed one way. Two-prong plugs do not have
a grounding pin.
Older homes may not have polarized
receptacle outlets. If not, the receptacles
will not accept polarized plugs. A quali-
fied electrician should replace the old
receptacles and put in wiring consistent
with polarization.
Choose the plug based on the gauge of
wire on the appliance or tool. Male plugshave prongs while female connectorshave slots.
There are plugs for different applica-
tions, such as exterior, interior and
marine. A twist lock prevents accidental
disconnection.
Attachment plugs fit on the ends of
cords of portable appliances and permit
them to be connected to wall receptacles
or extension cords. Plugs and connectors
are used to build extension cords or for
replacement on extension cords.
The arrangements of slots and blades
on connectors, receptacles and plugs must
match the configuration of the devices
with which they will be used. The number
of slots or prongs on these devices must
be the same as the number of wires in
associated cords.
Socket adapters screw into the socket,
while taps plug into the outlet.
Adapters are generally used for tempo-
rary application to provide two outlets
where a light socket is in use.
Taps are used to increase the number of
attachment plugs that can be used on a
single receptacle face.
Caution must be exercised when tap-
ping additional attachment plugs into the
same line. If the power rating of the cir-
cuit is exceeded, fuses will blow (if the cir-
cuit is properly fused).
Multiple taps plug into existing outlets
and can accommodate four to six plugs.
Some come with built-in surge protectors.
Other types of taps are table and cube.
Plug-in strips feature multiple outlets
placed at regular intervals. If used in a
workshop, it should have grounded out-
lets and be attached to a grounded circuit.
Quick-Clamp DevicesQuick-clamp devices do away with
screw terminals and the necessity of strip-
ping wire. If a plug needs replacing, insert
the cord into the clamping mechanism as
shown on the instructions. The clamp
forces the cord into the proper position
and onto sharp contact points that pierce
the insulation and make contact with the
conductors.
Clamp devices include both attachment
plugs and cord connectors of various
styles. They are used with portable lamps
and small appliances. They cannot be
used on kitchen or large appliances
because of their low amperage rating.
Wire Nuts/ConnectorsInsulated wire nuts or connectors are
used to connect wire ends that have been
twisted together inside a lighting fixture
or box. The size of the wire nut or con-
nector must correspond to the size wire
being used. Connectors are used to con-
nect heat-generating, small household
appliances with heat-resistant neoprene-
type HPN cords.
The connectors are molded of strong,
heat-resistant materials and come in a
variety of styles, such as switchless,
armored (or heavily protected), side outlet
and monopull. All have spring cord pro-
tectors. An offset wing design on some
models provides increased torque with
reduced wear on fingers. A hex head
enables nut driver and automated use.
There are two standard sizes: 11/16"
and the miniature 1/2". Standard 11/16"
connectors generally fit on irons and
toasters. The 1/2" connectors are for cof-
fee makers, corn poppers, some electric
skillets and other similar appliances.
TELEPHONES ANDACCESSORIES
■ TELEPHONES Consumers look at telephone purchases
much the same way as they look at other
home electronics purchases. They want a
quality product sold by a reputable retail-
er. Service backup is important because
telephone owners are responsible for their
own repairs, just as they are for any other
kind of equipment they own. If the tele-
phone breaks, they take it back to the
store that sold it.
Telephones contain microprocessors
and other electronic parts. New and more
sophisticated features are being added.
As telephones become more complicat-
ed, they require more sales attention.
Consumers need to be shown how to use
the additional features. If they will be
installing, replacing or rewiring, they may
need instruction in these areas, too. To
stock the telephones and accessories most
needed in your market, study the demo-
graphics of the area. Cordless phones may
work well in suburban and rural homes,
but are sometimes subject to interference
in urban areas.
Affluent areas may be a good market for
accessories such as telephone-answering
devices, while low-cost compact electronic
“disposable” phones may appeal more to
a middle-class market.
Beyond the basics, consumers can buy cord-
less phones, automatic redialing phones and
E L E C T R I C A L S U P P L I E S
21
Straight plug Grounding adapter
6-outlet tap C t N 44023-outlet tap
PLUGS AND TAPS
combination clock-radio phones.
Here are important points to keep in mind
when selling phones and accessories.
Telephone companies require con-
sumers to report their ringer equivalency
number (REN). This REN is published on
the instruction sheet or phone unit hous-
ing. Standard AT&T phones have REN rat-
ings of one. Compact, low-cost models may
have as low as .7 REN or as high as 1.3 REN.
If the REN on one line exceeds 4.0, the
phones will not ring.
There are two basic types of phones:
pushbutton tone and dial pulse. The dial-
pulse phone looks like a pushbutton tone,
but its pushbuttons technically dial the
phone. It doesn't process a call as fast as
the pushbutton tone.
Dial pulse gives the convenience of the
pushbutton-tone type of dialing without
higher monthly costs. It should be noted
too that pushbutton-tone phones are
required to access long-distance services.
Consumers should also be aware that
installing a pushbutton-tone phone
means they must also be receiving this
type of service from the phone company.
Cordless telephone systems incorporate
a base station connected to the telephone
line and a wireless handset. The distance
a cordless phone will work away from the
base station varies. It may be as little as
50' or phones with antennas may work as
far away as 1,000'.
Elevating the base station and placing it
away from other reception barriers can
improve cordless phone performance. One
word of warning: In most cordless
phones, ringers are located in the ear-
piece. The ring registers nearly 130 deci-
bels, and if the phone is picked up and
the switch not turned from “standby” to
“talk” position, a phone ring could dam-
age hearing.
Cordless phones are powered by
rechargeable nickel-cadmium or nickel-
metal hydride batteries. The length of
time required to recharge and the length
of time between rechargings will vary.
Therefore, it is necessary to read the
instructions with the individual product
to see how long to charge and how sensi-
tive the battery is to frequent rechargings.
Some nickel-cadmium batteries will
“remember” how much time elapsed
between chargings and if they are
recharged too often, will shorten the
length of time they hold a charge.
Eventually the batteries will have to be
replaced, but most phones will take sever-
al hundred chargings.
■ ACCESSORIES Accessories are available in either “mod-
ular” or “conventional” designs.
Installation of a conventional system
requires no more than a screwdriver.
Accessories are used in conjunction with
standard telephones, using standard four-
prong plug configuration, spade-tipped
wires or hard wiring.
All wiring in the phone base, handset
and wall receptacle can be replaced by
matching the colored wires. But it is
important that store employees know
enough to help d-i-yers with wiring infor-
mation and connection procedures on the
models you stock.
Plugs and jacks provide the connection
for standard telephone and extension
cord hook-ups. They may also be attached
to existing cords, adding versatility to
existing phones.
No tools are needed for modular con-
nections; the system was designed to
allow “snap-fit” connection of miniature
plugs with mating hardware. The follow-
ing connections are available using the
snap-fit modular concept:
Coil cord—old cords can be removed by
depressing a clip and pulling the plug out of
the phone’s base and handset. The new cord
is then pushed into place until it locks.
Straight-line cords—plugs are clipped
into the base of the phone and the wall
receptacle.
Extension cords—cords are equipped
with modular plugs that snap into a wall
receptacle while a modular jack accepts
the line cord from the existing telephone.
Modular adapter—allows phones with
modular line cords to be plugged into a
four-pronged conventional plug that
matches the holes of conventional tele-
phone jacks.
Modular plug and conventional jack—
allows connection of conventional four-
pronged plug extended line cords to mod-
ular jacks so that conventional phones
can be plugged into modular connections.
Modular coupler—allows connection of
modular plug-ended cords to each other
to extend the phone system.
Duplex modular adapter—allows two
modular extensions to be run off one
modular unit. For instance, allows you to
connect a telephone and telephone-
answering device to the same phone line.
Retrofit modular adapter—allows con-
ventional telephones with spade-tipped
conductors to be connected to modular
jack assemblies without tools.
Surface wall-mount jack assembly—
allows conversion of conventional termi-
nal blocks to a modular jack.
Portable wall-mount jack assembly—
E L E C T R I C A L S U P P L I E S
22
ENVIRONMENATL CONCERN ALERT
Many states are enacting legislation con-cerning dry-cell and rechargeable batteries.Current legislative topics include mercury inbatteries, batteries for cordless tools andappliances and battery recycling.
Mercury will have to be eliminated frombatteries. This will probably reduce the per-formance and increase the cost. Batteriesin cordless power tools and appliances willhave to be removable. And nickel-cadmiumbatteries will have to be recycled throughbattery retailers.
Be sure you know the laws regarding thesetopics in your area.
SPECIFICATIONS FORCYLINDRICAL BATTERIES
AA (Penlight) . . . . . . . . . .1.2**, 1.4*, 1.5AAA . . . . . . . . . . . . . . . . .1.5C . . . . . . . . . . . . . . . . . . .1.2**D . . . . . . . . . . . . . . . . . .1.2**, 1.4*, 1.5N . . . . . . . . . . . . . . . . . .1.5
*Mercury cell**Nickel-cadmium cell
allows connection of modular plug-ended
line cords in any location to convert four-
hole jack to a modular design.
Flush wall-mount jack assembly—allows
flush-mounted connection of plug-ended
modular line cords for initial installation
or conversion from existing wall recepta-
cles. Can be connected in parallel when
more than one jack is required.
Wall-mount modular patio jack—weath-
erproof assembly accepts plug-end modu-
lar line cords.
■ ANSWERING DEVICES The kind of telephone answering
device you recommend will depend in
large part on the kind of use the cus-
tomer expects of it. Models vary by price
and optional features.
Basic digital units do not require a tape
recorder or tape to handle incoming mes-
sages. In most models, total answer time
is limited, but more sophisticated units
will allow for messages of varying lengths.
Features which differentiate models
include:
Leaving messages—some units permit
the user to leave a digital or tape-recorded
message.
Dictation—some units double as dictat-
ing machines with no time limit on
recording. A switch will stop and start the
answer tape.
Announce only—for messages that
require no response, such as announce-
ments of when the owner will return.
Ring-response adjustment—allows
machine to wait to answer call until
phone has rung up to 10 times. An advan-
tage since it eliminates connecting and
disconnecting unit each time owner
leaves and returns.
Remote pick-up—allows owner to pick
up messages from a distance by telephon-
ing the answering unit.
Extended recording—allows user to
record a complete two-way conversation
without being cut off after allotted mes-
sage time.
Monitor—allows user to listen, unde-
tected, to incoming messages as callers
leave them. Listener can pick up phone
and interrupt recording message, if
desired, or simply let it be recorded.
Some phone companies still require an
Authorized Protective Connection
Module, if the answering device could
produce excess voltage on the telephone
line. The APCM plugs directly into the
phone jack.
■ BATTERIESGeneral-purpose and heavy-duty battery
systems serve a variety of functions.
General-purpose batteries provide 1.5V to
510V. They have good shelf life but
decreased efficiency at high-current
drains. They drop voltage gradually with
use and operate poorly in low tempera-
tures. They are available in a variety of
shapes from small pen cells to huge emer-
gency lighting batteries. Their uses range
from camera flashbulbs to radios and
flashlights.
General-purpose and heavy-duty batter-
ies are designed for light moderate to
E L E C T R I C A L S U P P L I E S
23
GLOSSARY OF ELECTRICAL TERMS
ALTERNATING CURRENT—Abbreviated “AC.” A current of electricity that alternates at a rate of60 hertz (cycles per second). It flows first in one direction, then in the other. Only at very low fre-quencies is this charge visible to the eye through the flickering of lamps.
AMPERE—Abbreviated “amp.” A measure of the flow of electrical current through a wire.
BALLAST—A form of transformer used in fluorescent lamp circuits to control current and keep itwithin specific operating limits.
CANDLEPOWER—A measure of the intensity of light produced by a source. One candlepowercorresponds approximately to the light produced in any one direction by an ordinary candle.
DIRECT CURRENT—Abbreviated “DC.” A flow of electric current continues in one direction aslong as the circuit is closed.
FOOTCANDLE—The unit used to measure how much total light is reaching a surface, such as awall or table. One footcandle is the amount of illumination falling on a one-square-foot surfacefrom a standard candle located 1 foot away.
FUSE—A replaceable safety device used to break the flow of current when a circuit becomesoverloaded.
GROUNDING—Connects the electrical system with the earth to prevent damage or shock.Ground wires are usually bare.
HOT WIRE—A power-carrying wire (usually in red or black) as distinguished from the “neutral”wire (usually white).
KILOWATT—1,000 watts. From “watt” and Greek word “kilo,” meaning 1,000.
KILOWATT HOURS—Abbreviated “kwh.” A 1,000-watt lamp burning one hour will use one kilo-watt hour of electricity. If the rate were 3 cents per kwh, the cost would be 3 cents per hour tooperate.
LAMP—Technical word meaning light bulb or tube—the part that shines until it burns out. Itcan also refer to a type of fixture, such as a desk lamp.
LUMEN—A unit that expresses the total quantity of light given off by a source regardless ofdirection. A lumen is defined as the amount of light falling on a surface of one square foot, everypoint of which is one foot away from a source of one candlepower.
NEUTRAL WIRE—A wire that runs from an appliance or device to make uninterrupted connec-tion back to the power source. The opposite of a “hot” wire that carries power from the electri-cal source to the appliance.
NOMINAL LAMP LIFE—A rated average bulb life that is obtained through closely controlledtests.
OHM—A unit of electrical resistance. (Electrical resistance is the opposition by a material to theflow of electrical current.)
TRANSFORMER—Steps up or steps down amount of alternating current available from circuit tothat required by the appliance.
VOLT—Amount of pressure needed to push electricity through a wire.
WATT—The unit of measurement of electrical power. Calculated by multiplying volts timesamperes. For instance, 746 watts equal one electrical horsepower.
heavy-current drain equipment. They, too,
are available in a variety of sizes and
shapes providing from 1.5V to 9V. They
have a good shelf life and maintain volt-
age better under load than general-purpose
batteries. They are used in flashlights, calcu-
lators, motor-driven toys, electronic games
and portable compact disc players.
Alkaline batteries are the longest-lasting
all-purpose batteries. They are designed
for high- and continuous-current drain
applications. Voltage ranges from 1.5V to
9V. The average cell holds 90 percent of
its energy for two to three years on the
shelf. Alkaline batteries are disposable and
operate well in low temperatures. Uses
include tape recorders, remote controls,
portable communications systems, radios,
television sets and shavers.
Lithium batteries are more expensive but
can hold their power for eight to 10 years,
unused. They are designed for cameras,
watches and other items that use a small
amount of current repeatedly over a long
period of time. They are available in 9V.
Heavy-duty batteries have a short life
compared to alkaline batteries and work
best for low-drain applications such as
remote controls and wall clocks.
Miniature zinc air batteries are designed
to provide power to miniature hearing aids.
They can be directly substituted for silver
oxide or mercuric oxide batteries in most
hearing aid applications. They are activated
by removing the covering from the air
access hole. They are available in common
hearing aid battery sizes.
Improved cell construction and advanced
use of titanium and lithium technology
have resulted in new premium batteries that
offer long-lasting performance for use in
high-drain devices.
Nearly 80 percent of all batteries sold
are in the AA and AAA sizes. Some batter-
ies come with a gauge-style tester so the
user knows how much power remains in
the battery.
Household batteries should be stored in
a dry place at room temperature. Make
sure not to mix battery types in the same
device and never mix new and old batter-
ies in the same device. Do not dispose of
any battery type in a large group since
they can come into contact with one
another. Always take precautions when
handling exposed battery chemicals.
Battery chemicals should not be placed
near the eyes or ingested by any means.
Mercury BatteriesMercury (and silver) batteries are used to
power hearing aids, electronic watches, cal-
culators and other electronic equipment
where small size and long life are critical.
They maintain a constant voltage for the
entire life cycle.
Concern over the environment has led
manufacturers to design mercury-free batter-
ies for household use.
Rechargeable BatteriesAlthough nickel-cadmium (Ni-Cd) bat-
teries are most commonly used in
rechargeable applications, other kinds are
available, including alkaline and lead-
acid. The major drawback to rechargeable
alkaline batteries is fewer recharging
cycles. Nickel-metal hydride (Ni-MH) bat-
teries have emerged as a viable alternative
to Ni-Cd batteries since they outlast Ni-Cd
batteries by up to 40 percent.
Ni-MH cells are available in AA, AAA, C,
D and 9-volt sizes. Ni-MH batteries offer
superior performance for use with high-
drain applications such as flash cameras
(including digital) and camcorders.
Rechargeable batteries are not charged
before purchase and must be charged for
approximately eight to 12 hours before
using. Some rechargeable batteries are now
available with shorter charging times.
Rechargeable batteries will lose their charge
if not used for an extended period (30 to 60
days) and should be charged every month
for best performance. Some batteries can be
recharged 800 to 1,000 times and will last
up to four years.
They offer “overcharge” capability,
which means they can stay on house cur-
rent for long periods without damaging
the cell. Like mercury batteries, nickel-
cadmium cells maintain constant voltage
for their full life span.
Nickel-cadmium batteries are perma-
nently built into a number of cordless
tools and appliances. In addition to the
larger batteries, nickel-cadmium batteries
are available in D, C, AA, AAA and 9V
sizes with chargers.
Battery recharging systems include the
charger and charging module. The module
is available in four sizes to hold AA, C, D or
9V batteries. The charger should be used
only with batteries specifically designated as
rechargeable. These are sometimes known as
secondary batteries. Trying to charge non-
rechargeable batteries can cause leakage and
possible cell rupture.
Lead-acid batteries are built into tools.
These batteries, about the size of a D bat-
tery, won’t leak, don’t vent explosive gas or
corrosive fumes, offer lengthy shelf life and
cost about half as much as nickel-cadmium.
Life span is 200 to 500 cycles, but they will
lose power gradually with age and use.
A national program has been started to
recycle rechargeable batteries. Retailers can
participate at no cost. For more informa-
tion, contact the non-profit Rechargeable
Battery Recycling Corp. at (877) 723-1297 or
visit www.rbrc.org/diy.
Electric MotorsThere are two basic motors found most
frequently in household applications—split
phase and universal.
The split-phase motor is the simplest. It
contains no brushes or commutator and
comes in one-third or less horsepower. At
full speed, the split-phase motor is able to
develop as much power as any other type,
but it is not capable of starting heavy loads
such as pumps or compressors. It functions
best when maximum load is applied at full
speed, such as in sanders, grinders and light
power tools.
Universal motors do not run at a constant
speed but slow as the load increases in some
instances from 15,000 rpm without a load
to 500 rpm under heavy load.
For this reason the motor is unsuitable for
many jobs. It is used only where the load is
reasonably constant and predetermined, such
as in sewing machines, vacuum cleaners, fans,
etc. It is the only type of motor that can be
controlled by a rheostat.
E L E C T R I C A L S U P P L I E S
24