9
6 Preliminary Load Calculations 6.1.0 Introduction 6.1.1 Prescriptive Unit Lighting Power Allowance (ULPA) (W/ft 2 ), Gross Lighted Area of Total Building 6.1.2 Typical Appliance/General-Purpose Receptacle Loads (Excluding Plug-In-Type A/C and Heating Equipment) 6.1.3 Typical Apartment Loads 6.1.4 Typical Connected Electrical Load for Air Conditioning Only 6.1.5 Central Air Conditioning Watts per SF, BTUs per Hour per SF of Floor Area, and SF per Ton of Air Conditioning 6.1.6 All-Weather Comfort Standard Recommended Heat-Loss Values 6.1.7 Typical Power Requirement (kW) for High-Rise Building Water Pressure–Boosting Systems 6.1.8 Typical Power Requirement (kW) for Electric Hot Water–Heating System 6.1.9 Typical Power Requirement (kW) for Fire Pumps in Commercial Buildings (Light Hazard) 6.1.10 Typical Loads in Commercial Kitchens 6.1.11 Comparison of Maximum Demand 6.1.12 Connected Load and Maximum Demand by Tenant Classification 6.1.13 Factors Used in Sizing Distribution-System Components 6.1.14 Factors Used to Establish Major Elements of the Electrical System Serving HVAC Systems 6.1.15 Service Entrance Peak Demand (Veterans Administration) 6.1.16 Service Entrance Peak Demand (Hospital Corporation of America) 6.1.0 Introduction The following tables are provided to assist the user in estimating preliminary loads for various building types. Considerable judgment should be used in the application of these data. Power densities typically are given in watts per square foot (W/ft 2 ) or volt-amperes per square foot (VA/ft 2 ) and are used interchangeably because unity power factor is assumed for preliminary load calculations. These tables give estimated connected loads. To these the user must apply a demand factor to estimate the actual demand load. Demand factors for buildings typically range between 50 and 80 percent of the connected load. For most building types, the demand factor at the service where the maximum diversity is experienced is usually 60 to 75 percent of the connected load. Specific portions of the system may have much higher demand factors, even approaching 100 percent. Section 6.1

Electrical Load Factors for building load calculations

Embed Size (px)

DESCRIPTION

This is useful for calculating load requirements of high rise commercial towers.

Citation preview

  • 6Preliminary Load Calculations

    6.1.0 Introduction6.1.1 Prescriptive Unit Lighting Power Allowance (ULPA) (W/ft2), Gross

    Lighted Area of Total Building6.1.2 Typical Appliance/General-Purpose Receptacle Loads (Excluding

    Plug-In-Type A/C and Heating Equipment)6.1.3 Typical Apartment Loads6.1.4 Typical Connected Electrical Load for Air Conditioning Only6.1.5 Central Air Conditioning Watts per SF, BTUs per Hour per SF of Floor

    Area, and SF per Ton of Air Conditioning6.1.6 All-Weather Comfort Standard Recommended Heat-Loss Values6.1.7 Typical Power Requirement (kW) for High-Rise Building Water

    PressureBoosting Systems6.1.8 Typical Power Requirement (kW) for Electric Hot WaterHeating System6.1.9 Typical Power Requirement (kW) for Fire Pumps in Commercial

    Buildings (Light Hazard)6.1.10 Typical Loads in Commercial Kitchens6.1.11 Comparison of Maximum Demand6.1.12 Connected Load and Maximum Demand by Tenant Classification6.1.13 Factors Used in Sizing Distribution-System Components6.1.14 Factors Used to Establish Major Elements of the Electrical System

    Serving HVAC Systems6.1.15 Service Entrance Peak Demand (Veterans Administration)6.1.16 Service Entrance Peak Demand (Hospital Corporation of America)

    6.1.0 IntroductionThe following tables are provided to assist the user in estimating preliminaryloads for various building types. Considerable judgment should be used in theapplication of these data. Power densities typically are given in watts per squarefoot (W/ft2) or volt-amperes per square foot (VA/ft2) and are used interchangeablybecause unity power factor is assumed for preliminary load calculations.

    These tables give estimated connected loads. To these the user must apply ademand factor to estimate the actual demand load. Demand factors for buildingstypically range between 50 and 80 percent of the connected load. For most buildingtypes, the demand factor at the service where the maximum diversity is experiencedis usually 60 to 75 percent of the connected load. Specific portions of the system mayhave much higher demand factors, even approaching 100 percent.

    Section

    6.1

    CH06_Hickey 11/15/01 11:21 AM Page 6.1

  • 6.1.1 Prescriptive Unit Lighting Power Allowance(ULPA) (W/ft2), Gross Lighted Area of Total Building

    6.2 Section Six

    TABLE 6.1.1

    TABLE 6.1.2

    6.1.2 Typical Appliance/General-PurposeReceptacle Loads (Excluding Plug-In-TypeA/C and Heating Equipment)

    (From IEEE Std. 241-1990. Copyright 1990 IEEE. All rights reserved.)

    CH06_Hickey 11/15/01 11:21 AM Page 6.2

  • Preliminary Load Calculations 6.3

    6.1.3 Typical Apartment Loads

    TABLE 6.1.3

    TABLE 6.1.4

    6.1.4 Typical Connected ElectricalLoad for Air Conditioning Only

    (From IEEE Std. 241-1990. Copyright 1990 IEEE. All rights reserved.)

    (From IEEE Std. 241-1990. Copyright 1990 IEEE. All rights reserved.)

    CH06_Hickey 11/15/01 11:21 AM Page 6.3

  • 6.1.5 Central Air Conditioning Watts per SF,BTUs per Hour per SF of Floor Area, andSF per Ton of Air Conditioning

    6.4 Section Six

    TABLE 6.1.5

    TABLE 6.1.6

    6.1.6 All-Weather Comfort StandardRecommended Heat-Loss Values

    (From IEEE Std. 241-1990. Copyright 1990 IEEE. All rights reserved.)

    CH06_Hickey 11/15/01 11:21 AM Page 6.4

  • 6.1.8 Typical Power Requirement (kW)for Electric Hot WaterHeating System

    Preliminary Load Calculations 6.5

    TABLE 6.1.7

    TABLE 6.1.8

    TABLE 6.1.9

    6.1.7 Typical Power Requirement (kW) for High-Rise Building Water PressureBoosting Systems

    6.1.9 Typical Power Requirement (kW) for FirePumps in Commercial Buildings (Light Hazard)

    (From IEEE Std. 241-1990. Copyright 1990 IEEE. All rights reserved.)

    (From IEEE Std. 241-1990. Copyright 1990 IEEE. All rights reserved.)

    (From IEEE Std. 241-1990. Copyright 1990 IEEE. All rights reserved.)

    CH06_Hickey 11/15/01 11:21 AM Page 6.5

  • 6.1.10 Typical Loads in Commercial Kitchens

    6.6 Section Six

    TABLE 6.1.10

    TABLE 6.1.11

    Note: As an alternative to the preceding table, you may use 25 W/ft2 forcommercial kitchens using natural gas for cooking or 125 W/ft2 for electriccooking. The applicable square footage in calculating kitchen floor areashould include cooking and preparation, dishwashing, storage, walk-inrefrigerators and freezers, food serving lines, tray assembly, and offices.

    6.1.11 Comparison of Maximum Demand

    (From IEEE Std. 241-1990. Copyright 1990 IEEE. All rights reserved.)

    (From IEEE Std. 241-1990. Copyright 1990 IEEE. All rights reserved.)

    CH06_Hickey 11/15/01 11:21 AM Page 6.6

  • 6.1.12 Connected Load and MaximumDemand by Tenant Classification

    Preliminary Load Calculations 6.7

    TABLE 6.1.12

    TABLE 6.1.13

    6.1.13 Factors Used in SizingDistribution-System Components

    (From IEEE Std. 241-1990. Copyright 1990 IEEE. All rights reserved.)

    (From IEEE Std. 602-1996. Copyright 1996 IEEE. All rights reserved.)

    CH06_Hickey 11/15/01 11:21 AM Page 6.7

  • 6.1.14 Factors Used to Establish Major Elements ofthe Electrical System Serving HVAC Systems

    6.8 Section Six

    TABLE 6.1.14

    TABLE 6.1.15

    Note: For a primary cooling system comprised of electrical centrifugalchillers, chilled water pumps, condenser water pumps, and cooling towerfans, a factor of 1.7 kVA/ton provides a good estimate.

    (From IEEE Std. 602-1996. Copyright 1996 IEEE. All rights reserved.)

    (From IEEE Std. 602-1996. Copyright 1996 IEEE. All rights reserved.)

    6.1.15 Service Entrance Peak Demand(Veterans Administration)

    CH06_Hickey 11/15/01 11:21 AM Page 6.8

  • 6.1.16 Service Entrance Peak Demand(Hospital Corporation of America)

    Preliminary Load Calculations 6.9

    TABLE 6.1.16

    (From IEEE Std. 602-1996. Copyright 1996 IEEE. All rights reserved.)

    CH06_Hickey 11/15/01 11:21 AM Page 6.9

    Front MatterTable of Contents6. Preliminary Load Calculations6.1.0 Introduction6.1.1 Prescriptive Unit Lighting Power Allowance (ULPA) (W/ft2), Gross Lighted Area of Total Building6.1.2 Typical Appliance/General-Purpose Receptacle Loads (Excluding Plug-In-Type A/C and Heating Equipment)6.1.3 Typical Apartment Loads6.1.4 Typical Connected Electrical Load for Air Conditioning Only6.1.5 Central Air Conditioning Watts per SF, BTUs per Hour per SF of Floor Area, and SFper Ton of Air Conditioning6.1.6 All-Weather Comfort Standard Recommended Heat-Loss Values6.1.7 Typical Power Requirement (kW) for High-Rise Building Water Pressure - Boosting Systems6.1.8 Typical Power Requirement (kW) for Electric Hot Water - Heating System6.1.9 Typical Power Requirement (kW) for Fire Pumps in Commercial Buildings (Light Hazard)6.1.10 Typical Loads in Commercial Kitchens6.1.11 Comparison of Maximum Demand6.1.12 Connected Load and Maximum Demand by Tenant Classification6.1.13 Factors Used in Sizing Distribution-System Components6.1.14 Factors Used to Establish Major Elements of the Electrical System Serving HVAC Systems6.1.15 Service Entrance Peak Demand (Veterans Administration)6.1.16 Service Entrance Peak Demand (Hospital Corporation of America)

    Index