FMI Energy Conference 2006 HVAC Load Calculations Perry Morrow & John Parker Brandt Engineering, Inc. Richmond, Virginia

31104944 HVAC Load Calculations Guide

Embed Size (px)

Citation preview

Page 1: 31104944 HVAC Load Calculations Guide

FMI Energy Conference 2006

HVACLoad Calculations

Perry Morrow & John ParkerBrandt Engineering, Inc.

Richmond, Virginia

Page 2: 31104944 HVAC Load Calculations Guide

Key Concepts to Consider as we look at Load Calculations

• Interior Design Criteria• Exterior Design Criteria• Kitchen Hoods and Make Up air• Walls that aren’t as well insulated as they

appear.

Page 3: 31104944 HVAC Load Calculations Guide

Why are Supermarket loads Unique?

Page 4: 31104944 HVAC Load Calculations Guide

Why is moisture control important?

Illustration provided by Todd Smith of Munters Corporation.

Page 5: 31104944 HVAC Load Calculations Guide

Where does the moisture come from?

• Infiltration• Ventilation• Makeup Air• Miscellaneous Loads

Page 6: 31104944 HVAC Load Calculations Guide

Makeup Air

• There have been many attempts at using tempered makeup air. This one appears the most successful; however, some of the humid air introduced here doesn’t go out the hood.

Image Courtesy of Food Service Technology Center publication

Design Guide 2 - Optimizing Makeup Air

Page 7: 31104944 HVAC Load Calculations Guide

Summer Weather Data – Richmond, VA & Phoenix, AZ

Data From 2005 Ashrae Fundamentals CD

Page 8: 31104944 HVAC Load Calculations Guide

HVAC Load Basic Terms• Zone: A single area with

similar thermal and use characteristics.

• Envelope Loads or • Skin Loads: Loads

associated with the Roof, Walls, Windows, Doors, Floor and Partitions.

• Infiltration: Air that leaks into a building through the building envelope.

• Humidity: The quantity of water vapor present in air. It can be expressed as an absolute, specificor a relative value.

Page 9: 31104944 HVAC Load Calculations Guide

Humidity Measurement Terms• Absolute humidity is the actual mass of water vapor present in the air water

vapor mixture. The absolute humidity may be expressed in pounds of water vapor (lb).

• Specific Humidity Ratio or Humidity Ratio is the ratio between the actual mass of water vapor present in moist air - to the mass of the dry air. Humidity Ratio is normally expressed in pounds of water vapor per pound of dry air or in Grains of moisture per pound of dry air. There are approximately 7000 grains in a pound.

• Relative Humidity: The ratio of the amount of water vapor in the air at a specific temperature to the maximum amount that the air could hold at that temperature, expressed as a percentage.

• Dew Point temperature: The temperature below which moisture will condense out of air. - Air at a given Humidity Ratio has a constant Dew Point. If air is cooled below this point, moisture condenses out thus changing its humidity ratio.

Definitions courtesy of wikipedia.org and .engineeringtoolbox.com

Page 10: 31104944 HVAC Load Calculations Guide

Relative Humidity vs. Humidity Ratio

As a given mass of moisture laden air is heated or cooled the air volume changes but the moisture does not. Thus there is a changein Relative Humidity, without a change in actual water content.

The mass of both water and air remain unchanged, so the humidityratio (Grains/Lb ) does not change. If the air continues to cool, the relative humidity will reach 100% and water will begin to condense on surfaces at 63oF so this is the Dew Point of the air.

Page 11: 31104944 HVAC Load Calculations Guide

Load Calculation Methods

• Manual Calculations• Spreadsheet• Specialized Software:

Elite Software - Chvac - Commercial HVAC Loads

Carrier - Hourly Analysis ProgramTrane - Trace family of programsDepartment of Energy – ENERGYPlus, BLAST

and DOE-2. Text based software with graphic interfaces sold by 3rd party software vendors.

Page 12: 31104944 HVAC Load Calculations Guide

Loads the New Way

Screen Capture from Carrier Hourly Analysis Program © Carrier Corporation

Page 13: 31104944 HVAC Load Calculations Guide

HVAC Load Basics

Although HVAC load calculation includes a significant amount of number crunching, it begins with digging out the answers to a number of questions.

A lack of good information up front can mean bad answers at the end of the process.

Garbage In = Garbage Out

Page 14: 31104944 HVAC Load Calculations Guide

HVAC Load Questions1

1. Establish allowable Indoor Temperature and Humidity Range.

2. Determine Outdoor Weather Conditions to use. Choices are 0.4%, 1% and 2% Ashrae data or Other.

3. Determine mass and insulation value of all building envelope components (Walls, Roof, Glass, Doors…).

4. Determine all internal load components (Anything that consumes electricity, gas, solid fuel or food. Also anything that has energy piped to it or away from it.).

5. Calculate heat flow into and out of each zone, at summer and winter outdoor weather conditions, varying temperature and sun location for each hour of the day and each day or month of the year.

6. Repeat steps 4 & 5 for every zone (thermally similar space of interest) in the building.

Page 15: 31104944 HVAC Load Calculations Guide

ASHRAE Indoor Air Temperature and Humidity Recommendations

• … The industry chose 75°F db and 64°F wb (55% rh, 57.5°F dew point{71.8 grains}) as summer design conditions. This is the ambient condition at which refrigeration load for food store display refrigerators is normally rated. Store humidity is one of the most critical variables that can affect performance of display refrigerators and refrigeration systems.

Excerpt from 2006 ASHRAE Refrigeration Handbook, Chapter 46

Page 16: 31104944 HVAC Load Calculations Guide

60%

70%

80%

90%

100%

110%

30 40 50 60 70 80

Refrigerated Case Loads

Data From 2003 ASHRAE Applications Handbook 2.3

Perc

ent L

oad

36.7 42.3 48.5 53 57.2 60.8 Dew Point (oF)

Humidity Ratio (gr./LB)

Page 17: 31104944 HVAC Load Calculations Guide

$8,000

$10,000

$12,000

$14,000

$16,000

$18,000

$20,000

$22,000

$24,000

$26,000

$28,000

$30,000

$32,000

$34,000

40 42 44 46 48 50 52 54 56 58 60

Store Dewpoint Setpoint

Ener

gy C

ost t

o op

erat

e A

/C fo

r 1

year

(exc

lude

s au

xila

ry h

eat c

ost)

BALTIMORE MIAMI

In Miami $3,000 A/C

energy COST if “setpoint” is 50 versus 58

dewpoint

In Baltimore $400 A/C

energy COST if “setpoint” is 50 versus 58

dewpointIn Miami: 90% of a year the store needs humidity control

In Baltimore: 45% of a year the store needs humidity

controlBuilding HVAC Cost vs. Store Dewpoint

Building HVAC Cost vs. Store Dewpoint

Excerpt from 2002 FMI Presentation by Lee Churchill of Seasons-4 Inc.

Page 18: 31104944 HVAC Load Calculations Guide

$70,000

$72,000$74,000

$76,000$78,000

$80,000$82,000

$84,000$86,000

$88,000$90,000$92,000

$94,000$96,000

$98,000$100,000

$102,000$104,000

$106,000$108,000

$110,000

40 42 44 46 48 50 52 54 56 58 60

Store Dewpoint SETPOINT

Cos

t to

Ope

rate

3 R

acks

(ann

ual)

Baltimore, MDMiami, FLSalt Lake CityPittsburg, PAHouston, TX

In Baltimore $8,000 rack

energy savings if “setpoint” is 50 versus 58

dewpoint

In Miami $18,000 rack

energy savings if “setpoint” is 50 versus 58

dewpoint

Excerpt from 2002 FMI Presentation by Lee Churchill of Seasons-4 Inc.

Rack Energy Cost vs. Store Dewpoint

Page 19: 31104944 HVAC Load Calculations Guide

HVAC + Rack Energy Cost vs. Store Dewpoint

$80,000

$85,000

$90,000

$95,000

$100,000

$105,000

$110,000

$115,000

$120,000

$125,000

$130,000

40 42 44 46 48 50 52 54 56 58 60

Store Dewpoint SETPOINT

Cos

t to

Ope

rate

3 R

acks

& A

/C (a

nnua

l)

Baltimore, MDMiami, FL

Excerpt from 2002 FMI Presentation by Lee Churchill of Seasons-4 Inc.

Conclusion to study: 50 F dewpoint is an optimum setpoint

Page 20: 31104944 HVAC Load Calculations Guide

HVAC Load Questions 2

1. Establish allowable Indoor Temperature and Humidity Range.

2. Determine Outdoor Weather Conditions to use. Choices are 0.4%, 1% and 2% Ashrae data or Other.

3. Determine mass and insulation value of all building envelope components (Walls, Roof, Glass, Doors…).

4. Determine all internal load components (Anything that consumes electricity, gas, solid fuel or food. Also anything that has energy piped to it or away from it.).

5. Calculate heat flow into and out of each zone, at summer and winter outdoor weather conditions, varying temperature and sun location for each hour of the day and each day or month of the year.

6. Repeat steps 4 & 5 for every zone (thermally similar space of interest) in the building.

Page 21: 31104944 HVAC Load Calculations Guide

ASHRAE Weather Data• 2 Types of Summer Data• Cooling Dehumidification

DB / MCWB & DP / MCDB

# of Hours Exceeding Summer Data– 0.4% 35 hr/Yr– 1% 88 hr/Yr– 2% 175 hr/Yr

• Types of Winter Data# of Hours Exceeding Winter Data– 99% 88 hr/Yr– 99.6% 35 hr/Yr

Page 22: 31104944 HVAC Load Calculations Guide

2005 Ashrae Example Weather Data

Page 23: 31104944 HVAC Load Calculations Guide

Hours by City

7,000 to 9,000

6,000 to 6,999

5,000 to 5,999

4,000 to 4,999

3,000 to 3,999

2,000 to 2,999

1,000 to 1,999

0 to 999

Dehumidification Hours by City

• Based on 74oF/55% RH • ( 67.5 Gr/lb ) Internal Set point

Illustration provided by Munters Corporation.

Page 24: 31104944 HVAC Load Calculations Guide

2005 Richmond, VA Summer Weather

0.4%

1.0%

Page 25: 31104944 HVAC Load Calculations Guide

Carrier Hourly Analysis Program – Opening Screen

Page 26: 31104944 HVAC Load Calculations Guide

HAP – Weather Input

Page 27: 31104944 HVAC Load Calculations Guide

HVAC Load Questions 3

1. Establish allowable Indoor Temperature and Humidity Range.

2. Determine Outdoor Weather Conditions to use. Choices are 0.4%, 1% and 2% Ashrae data or Other.

3. Determine mass and insulation value of all building envelope components (Walls, Roof, Glass, Doors…).

4. Determine all internal load components (Anything that consumes electricity, gas, solid fuel or food. Also anything that has energy piped to it or away from it.).

5. Calculate heat flow into and out of each zone, at summer and winter outdoor weather conditions, varying temperature and sun location for each hour of the day and each day or month of the year.

6. Repeat steps 4 & 5 for every zone (thermally similar space of interest) in the building.

Page 28: 31104944 HVAC Load Calculations Guide

Typical Wall Constructions

Illustration from 2001 Ashrae Fundamentals Handbook, Chapter 25 Illustration from 2005 Ashrae Fundamentals Handbook, Chapter 25

Page 29: 31104944 HVAC Load Calculations Guide

HAP – Wall Construction

Page 30: 31104944 HVAC Load Calculations Guide

Similar Calculation for 6” Metal Studs with R-19 insulation, No Insulated Sheathing

Simplified parallel Path calculation for Example purposes.

See 2005 Ashrae Fundamentals, Chapter 25 Modified Zone Method for less conservative method.

Page 31: 31104944 HVAC Load Calculations Guide

Insulated CMU WallsR-12 or R-5 ?

• CMU walls exhibit similar thermal bridging to the Stud Wall example with the addition of heat flow parallel to the wall surface around the insulated cores.

• One insulating product’s published data indicates a 12” CMU wall with their product including air film coefficients provides R-12.5. The fine print indicates that more detailed calculations are available. We requested the calculations, they indicate R=9.6.

• Often for structural reasons, one in four of the CMU cores are grouted solid and have rebar added. This added thermal bridging brings the wall assembly down to approximately R=5.1

• Note that the problem is not with the insulating material, but with the fact that there are numerous paths around the insulation.

Illustration from 2005 Ashrae Fundamentals Handbook, Chapter 25

Page 32: 31104944 HVAC Load Calculations Guide

Carrier Hourly Analysis Program – Opening Screen

• Information describing the Roof, Windows, Doors and any overhangs (Canopies) are entered in the library so they will be available as we define spaces.

• When equipment will be operated, when the lights are programmed to be on, and estimated hourly occupancy rates are entered under schedules.

Page 33: 31104944 HVAC Load Calculations Guide

HAP – Space General

Page 34: 31104944 HVAC Load Calculations Guide

Ventilation Air

The minimum quantity of ventilation air required is set by the building code in most areas. In most spaces, this is defined as X cfm / person. In some spaces, usually ones that are sparsely populated, ventilation rates may be set on a cfm / sq. ft. (floor area) basis.

In general, people exhale a predictable quantity of CO2 as they breathe. The CO2 level can be monitored and used to control outdoor air dampers to reduce the amount of Ventilation air during lightly occupied hours.

Page 35: 31104944 HVAC Load Calculations Guide

HVAC Load Questions 4

1. Establish allowable Indoor Temperature and Humidity Range.

2. Determine Outdoor Weather Conditions to use. Choices are 0.4%, 1% and 2% Ashrae data or Other.

3. Determine mass and insulation value of all building envelope components (Walls, Roof, Glass, Doors…).

4. Determine all internal load components (Anything that consumes electricity, gas, solid fuel or food. Also anything that has energy piped to it or away from it.).

5. Calculate heat flow into and out of each zone, at summer and winter outdoor weather conditions, varying temperature and sun location for each hour of the day and each day or month of the year.

6. Repeat steps 4 & 5 for every zone (thermally similar space of interest) in the building.

Page 36: 31104944 HVAC Load Calculations Guide

Internal LoadsMixed (Contain Sensible & Latent Components)

• People• Steam table• Holding Cabinets• Coffee Brewer• Case Credits

Dry (Sensible Heat)• Lights • Equipment:

– Self Contained Display Cases

– Slicers, Registers, Computers

• Hooded Equipment– Broilers– Ranges– Ovens

Page 37: 31104944 HVAC Load Calculations Guide

HAP - Internal

Page 38: 31104944 HVAC Load Calculations Guide

Hooded Loads – Where Applicable

• Spreadsheets or pads of paper are good ways to total the various components that make up the Miscellaneous portion of the internal load.

Page 39: 31104944 HVAC Load Calculations Guide

Case Credit - Summary

• Case Credits can be calculated a number of different ways that will be discussed in up coming slides.

Page 40: 31104944 HVAC Load Calculations Guide

Non-Hooded Loads and Totals

Page 41: 31104944 HVAC Load Calculations Guide

Case Credit Calculation Simplified Method

• We have seen this fairly simple method recommended by at least one refrigerated case manufacturer and more than one client. Although relatively simple, the results appear to be fairly accurate.

Page 42: 31104944 HVAC Load Calculations Guide

Case Credit Calculation Ashrae Method

Ashrae publishes a table listing Sensible and Latent Case Credit values on a BTU/Foot basis for various case types. Some case manufacturers have this type of data available for their specific cases.

Page 43: 31104944 HVAC Load Calculations Guide

Case Credit Calculation BTU / Ft & Return Air

One client has taken the BTU/LF or Ashrae method a step further. This calculation bases the case credits on a btu/lf method and then assigns only a portion of this credit to the space. Where under case returns are utilized, the remainder of the credit is assigned to the unit cooling coil.

Page 44: 31104944 HVAC Load Calculations Guide

HAP - Wall

Page 45: 31104944 HVAC Load Calculations Guide

HAP – Roof

Page 46: 31104944 HVAC Load Calculations Guide

HAP - Infiltration

Page 47: 31104944 HVAC Load Calculations Guide

Infiltration

• From Carrier HAP 4.20a - Help File– Items in the CFM/sqft column define infiltration in terms of airflow per

unit of exterior wall area. Because infiltration occurs through exterior walls - especially through windows and doors in these walls - rule of thumb infiltration rates are sometimes tabulated in this CFM/sqft format.

• From: Ashrae 2005 Fundamentals – Chapter 27, Page 23– NONRESIDENTIAL AIR LEAKAGE– …Typical air leakage values per unit wall area at 0.30 in. of water are

0.10, 0.30, and 0.60 cfm/ft2 for tight, average, and leaky walls, respectively.

Wall Construction Infiltration rate (cfm/ft2) Tight 0.10Average 0.30Leaky 0.60

Page 48: 31104944 HVAC Load Calculations Guide

HAP - Floor

Page 49: 31104944 HVAC Load Calculations Guide

HAP – Partition Input

• Partitions are internal walls, ceilings or floors that separate conditioned spaces from un-conditioned or partially conditioned spaces. Machine rooms and Receiving Areas can be partition loads to the adjacent spaces. These walls should be insulated.

Page 50: 31104944 HVAC Load Calculations Guide

HAP – Partition U Value Calculation

• Use the built in Wall and Roof property calculation portions of the program to calculate the U-Value for any partitions. Manually transfer this data to the partition tab of the space input form.

Page 51: 31104944 HVAC Load Calculations Guide

HVAC Load Questions 5

1. Establish allowable Indoor Temperature and Humidity Range.

2. Determine Outdoor Weather Conditions to use. Choices are 0.4%, 1% and 2% Ashrae data or Other.

3. Determine mass and insulation value of all building envelope components (Walls, Roof, Glass, Doors…).

4. Determine all internal load components (Anything that consumes electricity, gas, solid fuel or food. Also anything that has energy piped to it or away from it.).

5. Calculate heat flow into and out of each zone, at summer and winter outdoor weather conditions, varying temperature and sun location for each hour of the day and each day or month of the year.

6. Repeat steps 4 & 5 for every zone (thermally similar space of interest) in the building.

Page 52: 31104944 HVAC Load Calculations Guide

HVAC Load Questions 6

1. Establish allowable Indoor Temperature and Humidity Range.

2. Determine Outdoor Weather Conditions to use. Choices are 0.4%, 1% and 2% Ashrae data or Other.

3. Determine mass and insulation value of all building envelope components (Walls, Roof, Glass, Doors…).

4. Determine all internal load components (Anything that consumes electricity, gas, solid fuel or food. Also anything that has energy piped to it or away from it.).

5. Calculate heat flow into and out of each zone, at summer and winter outdoor weather conditions, varying temperature and sun location for each hour of the day and each day or month of the year.

6. Repeat steps 4 & 5 for every zone (thermally similar space of interest) in the building.

Page 53: 31104944 HVAC Load Calculations Guide

Systems 1

• After all spaces to be conditioned have been entered, we can begin grouping them together into zones and systems.

• Only spaces with similar thermal and occupancy characteristics should be grouped together as a zone. There will be one thermostat per zone generally

• The systems usually correspond to air handling units. These can be split systems, central station air handling units or rooftop units..

• A typical rooftop unit or split system can only serve one zone, and is controlled by one thermostat. So in this case each system consists of only one zone.

• There are other system types that allow one unit to serve multiple zones, but in our experience, they are not often applied to supermarkets.

Page 54: 31104944 HVAC Load Calculations Guide

HAP – System Input General

Page 55: 31104944 HVAC Load Calculations Guide

HAP – System Components

Page 56: 31104944 HVAC Load Calculations Guide

Systems 2

• When we were describing spaces, we entered information that will give us the total outside air required for ventilation.

• In stores with cooking, this is only part of the outside air story. You need make-up air for hoods and other exhaust sources. The software is aware of this, so all you need to do is enter this value as an exhaust quantity as you describe the system.

• If the zones where the exhaust loads occur are open to the main sales area and each other you have a decision to make. Where to allocate the make up air.

• You can either design for one large semi-custom unit capable of handling most of the outside air or multiple semi-custom units.

• If the zones are not open to one another, you have no choice. Make Up air must be provided in the system where it is actually exhausted.

Page 57: 31104944 HVAC Load Calculations Guide

Building Air Balance

Page 58: 31104944 HVAC Load Calculations Guide

HAP – Zone Components

Page 59: 31104944 HVAC Load Calculations Guide

Load Software Air System Sizing Summary Output

Notice Warning

Page 60: 31104944 HVAC Load Calculations Guide

Load Software Air System Design Load Summary

Page 61: 31104944 HVAC Load Calculations Guide

Heating Load Calculation – “Case Credits”• Heating loads are calculated for the maximum required

heating from the system without taking credit for any internal lights, equipment and people. External heating credits such as solar effects are also omitted. Because the software ignores miscellaneous loads while calculating the heating load, the “case credits”, which in heating mode are an additional heating load not a credit, they must be added to the required unit capacity manually.

• If sufficient heat from the refrigeration rack is reclaimed by the mechanical systems, it may not be necessary to increase the unit heating capacity to offset this added heating load. But be careful, often the reclaim heat is not available.

Page 62: 31104944 HVAC Load Calculations Guide

Summary- Pie

• Dry Climate• Humid Climate

119.7 Total Tons0.97 Coil SHR

129.4 Total Tons0.67 Coil SHR

Page 63: 31104944 HVAC Load Calculations Guide

Summary – Stacked Bar

119.7 Total Tons0.97 Coil SHR

129.4 Total Tons0.67 Coil SHR

Page 64: 31104944 HVAC Load Calculations Guide

Take Home Points• Infiltration / Transmission Load thru Walls.• Interior & Exterior Design Conditions• Costs of Controlling vs. Not controlling

space humidity.

Page 65: 31104944 HVAC Load Calculations Guide

CreditsPresentation includes excerpts from:• ASHRAE 2003, 2005 and 2006 Handbooks• Screen Outputs from Carrier Hourly Analysis Program

HAP version 4.20a• Humidity illustrations provided by Todd Smith of Munters

Corporation.• Rack Energy Cost vs. Store Dewpoint data provided by

Lee Churchill of Seasons-4 Inc.

Page 66: 31104944 HVAC Load Calculations Guide

Software Resources• Load & Energy Simulation Software

– Carrier Software - Hourly Analysis Program– US Dept of Energy - EnergyPlus and DOE-2– Elite Software - Chvac - Commercial HVAC– Trane - Trace Family of software

• Psychometric Calculation Tools– PsyCalc98 - Linric Company– PsyFunc is a collection of psychometric

functions for Excel sold by Linric Company.