EEV-KITEEV-KITGeneral InformationGeneral Information
Preliminary information, all of contents are subject to final confirmation by MHI 2
Contents 1. What it EEV-KIT
2. What is the direct expansion type air handling unit ( DX AHU )3. Feature of EEV-KIT
4. Usage note
5. Composition of EEV-KIT and component formation
6. Selection standard of heat exchanger
Preliminary information, all of contents are subject to final confirmation by MHI 3
1. What is EEV-KIT • EEV-KIT is the control kit for operating the locally
provided AHU and/or fan coil unit with direct expansion heat exchanger coils in connection with KXE6 system.
• EEV-KIT is composed of, EEV-Control ASSY and EEV-Set.• EEV-Control ASSY: Following 2 types
• EEV-Set: Select from following 3 types according to the coil capacity
Type EEV6-71-E EEV6-160-E EEV6-280-E
Capacity P22 - P71 P80 - P160 P224 - P280
EEVKIT6-E-M EEVKIT6-E-C
Single 1unit-Multi units *Multi 1unit (for master) Multi units (for slave)
Refrigerationsystem
EEV-Control ASSY
* Connectable refrigeration system is one system only. In case that the refrigeration system is multiple, be sure to use the EEV-Control ASSY for multiple refrigeration system.
EEV-Control BOX
Sensor ( 5pcs)
Thi-AThi-R1
Thi-R2Thi-R3
Thi-AF
EEV-Set
Strainer
EEV
Strainer
EEV-KITEEV-Control Unit
EEV-Control ASSY
Preliminary information, all of contents are subject to final confirmation by MHI 4
2. What is the direct expansion type air handling unit system
直膨エアハン
33 Available to connect multipleAvailable to connect multiplerefrigeration systems (Max. 8 systems)refrigeration systems (Max. 8 systems)to one air handling unit to one air handling unit
22 Applied direct expansion type Applied direct expansion type coils for heat exchanger in coils for heat exchanger in the AHUthe AHU
11 Applied air cooled typeApplied air cooled typeheat pump outdoor unitheat pump outdoor unitfor heat sourcefor heat source
Exhaust air fan
Supply air fan
Total heat exchanger
Nonwoven filter
Control box
Cell type filter
VAV or CAV is available
Direct expansion type coil
Water evaporating
type humidifier
Outdoor unit
Return Air
SupplyAir
(Cool/Heat)
Exhaust Air
Outdoor Air
Direct expansion typeAir handling unit
System feature
System feature
System feature
Max. capacityMax. capacity =1088=1088 kWkW (( 136kW×8)136kW×8) :: cooling cooling capacitycapacity
Preliminary information, all of contents are subject to final confirmation by MHI 5
3. Feature of EEV-KIT • EEV-KIT is applied the controlling technology of KXE6. Accordingly it is able to connect to the superlink system
through superlink adaptor.• Remote controller for KXE6 can be used.• Operation command to the indoor fan is transmitted
from EEV-Control Unit. Power source for indoor fan motor should be provided separately.
• Switching between return air temperature control and supply air temperature control is available.
Preliminary information, all of contents are subject to final confirmation by MHI 6
4. Usage note • Be sure to apply the 2 temperature sensors for detecting
return/supply air temperature and the 3 heat exchanger temperature sensors for detecting entrance, intermediate and exit temperature of the heat exchanger. Be sure to check whether the sensors can detect the temperatures correctly.
• DX heat exchanger is designed and produced locally according to the local requirement. However be sure to follow MHI’s selection standard.
• If using EEV-KIT, be sure to submit the Check Sheet prepared by MHI after filling in all the necessary items. Otherwise you may not have any technical support for after sales service from MHI.
Preliminary information, all of contents are subject to final confirmation by MHI 7
5. Composition of EEV-KIT and component formation
5.1. EEV-CONTROL ASSY
No. Part name Part No. Pcs. Remarks
①- 1 CONTROL UNIT PCH501A017AB 1 For multiple refrigerant system only
②- 1 SENSOR ASSY PCH551A010 1 Thi-A (for return air temp.)
②- 2 SENSOR ASSY PCH551A011 1 Thi-AF (for supply air temp.)
Model A: EEVKIT6-E-M (Master EEV-Control ASSY)
Note 1. This control unit is used for multiple refrigeration
system only.2. 2. In case of multiple refrigeration system, this
control unit must be used as Master EEV-Control.
Preliminary information, all of contents are subject to final confirmation by MHI 8
5. Composition of EEV-KIT and component formation
5.1. EEV-CONTROL ASSY
No. Part name Part No. Pcs. Remarks
①- 2 CONTROL UNIT PCH501A017L 1
②- 1 SENSOR ASSY PCH551A010 1 Thi-A (for retern air temp.)
②- 2 SENSOR ASSY PCH551A011 1 Thi-AF (for supply air temp.)
③ SENSOR ASSY PCH551A012 1 Thi-R1, R2, R3
④ SPRING LEAF PSA941F001 3 For Thi-R1, R2, R3
Model B: EEVKIT6-E-C (EEV-Control ASSY or Slave EEV-Control ASSY)
Note 1. This control unit is used for single refrigeration system (EEV-Control
ASSY) and for multiple refrigeration system (as Slave EEV-Control ASSY)
2. In case of multiple refrigeration system use, -1 and -2 are not used. ② ②3. Capacity setting at factory default is 280. Please change setting to the
required capacity, if it is different.4. Number of Pcs shown in the above table is for one set of heat
exchanger.
Preliminary information, all of contents are subject to final confirmation by MHI 9
5. Composition of EEV-KIT and component formation
①-1 CONTROL UNIT ( for multiple refrigeration system only)
Indoor fan motoroperation command
Signal lineRemote controller line
Master control PCB
Power line *1 Single phase 220-240V (50Hz)
*1) The power for indoor fan motor is not included
Sensor for supply air Sensor for return air
Terminal block for optional input/output signal( For CnT2 and CnN)
Terminal block for signal cable and remote controller cable
Terminal block for power cablePCH501A017AB
Preliminary information, all of contents are subject to final confirmation by MHI 10
5. Composition of EEV-KIT and component formation ①-2 CONTROL UNIT (Common use for single and multi system )
Indoor fan motoroperation command* (*for single system only)
Signal lineRemote controller line* (*for single system only)
Control PCB
Power line *1 Single phase 220-240V (50Hz)
*1) The power for indoor fan motor is not included
Sensor for supply air*Sensor for return air* (*for single system only)
Terminal block for signal cable and remote controller cable* (*for single system only)
Terminal block for power cable
Sensor for heat exchanger Coil for EEV
PCH501A017L
Preliminary information, all of contents are subject to final confirmation by MHI 11
5. Composition of EEV-KIT and component formation
② SENSOR ASSY : Return/Supply air sensor②-1 Part No. of return air sensor: PCH551A010
Black
Blue
Color tape for discrimination
Black
②-2 Part No. of supply air sensor:PCH551A011
Yellow
Preliminary information, all of contents are subject to final confirmation by MHI 12
5. Composition of EEV-KIT and component formation
③ SENSOR ASSY : Heat exchanger temperature sensor
Part No. of heat exchanger sensor: PCH551A012
Color tape for discrimination
Sensor part Connector part
Black
Black
Gray
Yellow
Red
Yellow
Preliminary information, all of contents are subject to final confirmation by MHI 13
5. Composition of EEV-KIT and component formation
④ SPRING, LEAF
Leaf Spring
Sensor Holder *
Heat Exchanger Temp. Sensor
Discrimination Tape With/Without
Mounting Method ofHeat Exchanger Temp. Sensor
* Sensor Holder : Provided locally
Sensor φ Material
For Thi- R3 φ 9.52 x 0.6t
For Thi- R1 and - R2 φ 8.0 x 0.6tCopper tube
PSA941F001
Preliminary information, all of contents are subject to final confirmation by MHI 14
5. Composition of EEV-KIT and component formation
5.2. EEV-SET EEV6-71-E EEV6-160-E EEV6-280-E
⑤ -1 VALVE, BODY (EXP) ASSY PCH387F018 1
⑤ -2 VALVE, BODY (EXP) ASSY PCH387F019 1
⑤ -3 VALVE, BODY (EXP) ASSY PCH387F019A 1
VALVE, BODY (EXP) SSA387F047A ( 1 )
VALVE, BODY (EXP) SSA387F045 ( 1 )
VALVE, BODY (EXP) SSA387F049A ( 1 )
STRAINER SSA357A005B ( 1 ) ( 1 ) ( 1 )
STRAINER SSA357A005T ( 1 ) ( 1 )
STRAINER SSA357A005AC ( 1 )
⑥- 1 COIL, SOLENOID PCH387F002 1
⑥- 2 COIL, SOLENOID PCH387F002A 1 1
No. Part name Part No.Model Name
Note 1. Please select suitable components according to the required capacity. 2. Number of Pcs shown in the above table is for one set of heat exchanger. 3. Number of Pcs in ( ) is just for reference. These parts are included in VALVE, BODY (EXP) ASSYs respectively.
Preliminary information, all of contents are subject to final confirmation by MHI 15
5. Composition of EEV-KIT and component formation
⑤ VALVE, BODY (EXP) ASSY : Electronic Expansion Valve ASSY
⑤-1 PCH387F018 (for EEV6-71-E)
Preliminary information, all of contents are subject to final confirmation by MHI 16
5. Composition of EEV-KIT and component formation
⑤ VALVE, BODY (EXP) ASSY : Electronic Expansion Valve ASSY
⑤-2 PCH387F019 (for EEV6-160-E)⑤-3 PCH387F019A (for EEV6-280-E)
For EEV6-160-EFor EEV6-280-E
Preliminary information, all of contents are subject to final confirmation by MHI 17
5. Composition of EEV-KIT and component formation
VALVE, BODY (EXP) : Electronic Expansion Valve
EEV6-71-E(P22-P71)
EEV6-160-E(P80-P160)
EEV6-280-E(P224-P280)
SSA387F047A SSA387F045 SSA387F049A
Preliminary information, all of contents are subject to final confirmation by MHI 18
5. Composition of EEV-KIT and component formation STRAINER
Part No. of Strainer: SSA357A005B SSA357A005T SSA357A005AC
Preliminary information, all of contents are subject to final confirmation by MHI 19
5. Composition of EEV-KIT and component formation
⑥ COIL, SOLENOID : EEV Coil
For EEV6-71-E(P22-P71)
For EEV6-160-E & EEV6-280-E(P80-P160) (P224-P280)
SSA382F002 SSA382F002A
SSA382F210T(Solenoid coil)
SSA382F210C(Solenoid coil)
SSA971K116(Insulation tube)
PCH504A053(Wiring assy)
SSA971K116(Insulation tube)
PCH504A053(Wiring assy)
Note: Do not place the interconnector at the air passageway considering no water intrusion into the connector. If place it at the air passageway, be sure to protect it from water intrusion.
Interconnector
Preliminary information, all of contents are subject to final confirmation by MHI 20
6. Selection standard of heat exchanger 6.1 Required specifications #1
m3/h
Pa
m3/h
Pa
kW
kW
℃DB
℃WB
Winter ℃DB
External static pressure
External static pressure
Air volume
m3/h
Supply air(SA)
Return air(RA)
Return airtemperature
Directexpansion type
heatexchanger coil
Air volume
Summer
Outdoor air(OA)
Intake air volume
Heating capacity
Cooling capacity
Dx AHU can be designed freely according to the required specifications.
For designing the heat exchanger, following design information is required.
Others ( )
Others ( )
Natural evaporating type
Steam spray type
kg/h
Filter
Humidifier
High performance(Colorimetric method 65%)
Pre-filter
High performance(Colorimetric method 90%)
Electrode steam generator
Humidifyingvolume
< Required specifications #1>
Please refer to check sheet
We pass you an example of
a sample sheet
Preliminary information, all of contents are subject to final confirmation by MHI 21
6. Selection standard of heat exchanger 6.1 Required specifications #2
With Without
OA volume m3/h
Exhaust air volume m3/h
Inverter control With Without
Others ( )
Total heatexchanger
Installation place
Corrosion protection type Specialspecifications
Spring type
Rubber pad type
Anti-vibrationdevice
Maker standard type
Outdoor Indoor
℃DB
℃WB
℃DB
℃WB
Summer
Winter
Designcondition ofoutdoor airtemperature
< Required specifications #2>
Note: Especially the design condition of outdoor air temperature mentioned above is important for designing direct expansion type heat exchanger.
Attention: Please select the heat exchanger, fan, EEV-KIT and etc. by clarifying the required specifications before designing.
Please refer to check sheet
We pass you an example of
a sample sheet
Preliminary information, all of contents are subject to final confirmation by MHI 22
・ Design standard for air conditioning unit (indoor air circulation type) and for OA processing unit (outdoor air intake type) are different. In case of OA processing unit, the design standard should be changed by selecting on the capacity basis (A) or on air flow volume basis (B).・ Design standard for each unit type is shown as follows.
6. Selection standard of heat exchanger
6.2.1. Design standard of heat exchanger
Front air speed Front area of heat exchanger
1 Air conditioning unit 2.3m/s 0.025m2/kW *1
2 OA processing unit A 1.2m/s 0.020m2/kW *2
3 OA processing unit B 2.1m/s 0.015m2/kW *2
Unit typeDesign standard Case
No.
*1. Temperature condition is JIS rated condition (See item 6-2)- for details) ④*2. Temperature condition is JIS conformed condition (See item 5 for details)
・ The 3-row heat exchanger coil is design standard. (4-row or 6-row coil like water heat exchanger coil is not effective.) ・ The number of circuit is designed on 10 circuits per 25kW
(equivalent to 10HP) of capacity basis withφ9.52 diameter of hair pin tube.
Be sure to select the distributor in order not to make no temperature difference among the circuits.
6.2. Designing method of heat exchanger
Preliminary information, all of contents are subject to final confirmation by MHI 23
6. Selection standard of heat exchanger
6.2.2. Design standard of heat exchanger volumeStandard of heat exhanger volume
80
130
180
230
280
330
0 10 20 30 40 50 60
Cooling capacity (kW)
Vo
lum
e/ k
W(c
m3/
kW)
(Note)
・ The heat exchanger volume should be selected between the upper limit (blue line) and lower limit (red dotted line).
・ If the heat exchanger volume is too much, the required refrigerant volume is increased so that it will affect to the reliability of the system.
Be sure to conform to MHI design standard of heat exchanger volume.
6.2. Designing method of heat exchanger
Preliminary information, all of contents are subject to final confirmation by MHI 24
・ 3 sets of heat exchanger temp. sensors are required for each heat exchanger coil (indoor unit).
・ The heat exchanger temp. sensors are attached to EEVKIT6-E-C.
・ The mounting position of each heat exchanger temp. sensor is shown in following table.
6. Selection standard of heat exchanger
6.3 .1. Mounting standard of heat exchanger temp. sensors
・ The control range (accuracy) of heat exchanger temp. sensors (Thi-R1, -R2, -R3) is from 0 to 63(±2) .℃ ℃・ The usage range of heat exchanger temp. sensors is from -30 to +72 .℃ ℃
Sensor Mounting position
Thi-R1 On the U-bend section
Thi-R2 On the capillary tube section of distributor
Thi-R3 On the header section
6.3. Guidelines of mounting heat exchanger temp. sensors
Preliminary information, all of contents are subject to final confirmation by MHI 25
6. Selection standard of heat exchanger
6.3 .2. Mounting position of temperature sensors
Supply air temperature sensor
( Thi- AF)
Sensor on capillary tube ( Thi-R2 )
EEV
Sensor on header( Thi-R3 )
Distributor
Return air temperature sensor
( Thi- A)
Sensor on U-bend ( Thi-R 1)
AIR AIR
6.3. Guidelines of mounting heat exchanger temp. sensors