EDUS371705C-D202002
Engineering Data
Heat Recovery 60 Hz
Design ManualRELQ-TATJA, 208 / 230 VRELQ-TAYDA, 460 VRELQ-TAYCA, 575 V
EDU
S371705C-D
ENG
INEER
ING
DA
TA VR
V Aurora Series R
ELQ-TA
TJA / TA
YDA
/ TAYC
A H
EAT R
ECO
VERY 60 H
z DESIG
N M
AN
UA
L
1
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
Table of Contents
1. FeaturesandBenefits ................................................................................32. Compatibility ...............................................................................................43. Nomenclature .............................................................................................54. Model Names .............................................................................................9
4.1 Outdoor Units ....................................................................................94.2 Indoor Units .....................................................................................104.3 Branch Selector Unit .......................................................................104.4 Air Treatment Equipment ................................................................11
5. External Appearance ................................................................................125.1 Outdoor Units ..................................................................................125.2 Indoor Units .....................................................................................135.3 Branch Selector Unit .......................................................................145.4 Air Treatment Equipment ................................................................14
6. Outdoor Unit Combination ........................................................................157. Interchangeability .....................................................................................168. Capacity Range ........................................................................................17
8.1 Connection Ratio ............................................................................178.2 Capacity Range of Connectable Indoor Units .................................188.3 Limitation of Capacity Index for Heat Recovery ..............................19
9. Specifications ...........................................................................................209.1 RELQ-TATJA ..................................................................................209.2 RELQ-TAYDA .................................................................................229.3 RELQ-TAYCA .................................................................................24
10. Dimensions ...............................................................................................2611. Service Space ..........................................................................................2812. Center of Gravity ......................................................................................3013. Foundation Drawing .................................................................................3214. Piping Diagrams .......................................................................................3315. Wiring Diagrams .......................................................................................3516. Field Wiring ..............................................................................................4517. Electrical Characteristics ..........................................................................47
17.1 RELQ72-120TATJA ........................................................................4717.2 RELQ72-120TAYDA .......................................................................4817.3 RELQ72-120TAYCA .......................................................................49
18. Operation Limits .......................................................................................5019. Low Ambient Cooling Enhancement ........................................................5120. Sound Levels (Reference Data) ...............................................................52
2
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
21. Accessories ..............................................................................................5521.1 Optional Accessories ......................................................................55
22. Selection Procedure .................................................................................5622.1 Selection Procedure ........................................................................56
23. Caution Label ...........................................................................................6223.1 RELQ72-240TATJA / TAYDA / TAYCA ..........................................62
24. Caution for Refrigerant Leaks ..................................................................7124.1 Introduction .....................................................................................7124.2 Procedure for Checking Maximum Concentration ..........................72
25. Safety Devices Setting .............................................................................7425.1 FXFQ-T ...........................................................................................7425.2 FXZQ-TA .........................................................................................7425.3 FXUQ-P ..........................................................................................7425.4 FXEQ-P ...........................................................................................7425.5 FXDQ-M ..........................................................................................7525.6 FXSQ-TA ........................................................................................7525.7 FXMQ-PB ........................................................................................7525.8 FXMQ-M .........................................................................................7525.9 FXHQ-M ..........................................................................................7625.10 FXAQ-P .........................................................................................7625.11 FXLQ-M, FXNQ-M .........................................................................7625.12 FXTQ-TA .......................................................................................7625.13 CXTQ-TA .......................................................................................76
Appendix........................................................................................................771. Introduction ...............................................................................................78
1.1 ED Book List ...................................................................................781.2 Publication List of Engineering Data for VRV Products ..................79
3
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
1. Features and Benefits
The new VRV Aurora Series heat recovery unit demonstrates Daikin's technological leadership by offeringthefirstVRVaircooledsystemthatdeliverseffectiveandefficientheatingdownto−22°FWB(−30°CWB).• Available in 6, 8, 10 ton single modules and 12, 16, 20 ton multi-module systems• First Air Cooled VRVsystemtodeliverheatingdownto−22°F(−30°C)asstandard• Daikin’s patented inverted based vapor injection compressor delivers high heating capacity of up to100%at0°F(−18°C),upto85%at−13°F(−25°C)andupto60%at−22°F(−30°C)
•Refrigerantcooledefficientandstableinverterboardoperation,independentofambientconditions
• Hot gas base pan circuit allows installation without additional drain pan heater• Added peace of mind with ability of Auto changeover to back up (auxiliary) heat•YearroundcomfortandenergyefficiencydeliveredbycombingVRV and Variable Refrigerant
Temperature (VRT) technologies• Designed and optimized for Total Cost of Construction (TCC) and reduced Life Cycle Cost (LCC)•Corrosionresistant,1000hrsaltspraytestedDaikinPEbluefinheatexchanger• Ships factory standard with coil guards• Compatible with the full suite of VRV-IV T-series Branch Selector Boxes• Seamless connection to all VRV M, P and T series indoor units•Easecommissioningwithabilitytoprogramsettingsoffsiteusingnewconfiguratortool•3-digit7-segmentdigitaldisplayontheunitforimprovedandfasterconfiguration,commissioning,
and troubleshooting• Backed by 10 year parts limited warranty and 10 years replacement compressor limited warranty*
* Complete warranty details available from local distributor or manufacturer's representative
4
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
2. Compatibility
208/230 V model 460 V model 575 V modelNew model Current model New model Current model New model Current model
RELQ72TATJA RELQ72TATJU RELQ72TAYDA RELQ72TAYDU RELQ72TAYCA RELQ72TAYCURELQ96TATJA RELQ96TATJU RELQ96TAYDA RELQ96TAYDU RELQ96TAYCA RELQ96TAYCU
RELQ120TATJA RELQ120TATJU RELQ120TAYDA RELQ120TAYDU RELQ120TAYCA RELQ120TAYCURELQ144TATJA RELQ144TATJU RELQ144TAYDA RELQ144TAYDU RELQ144TAYCA RELQ144TAYCURELQ192TATJA RELQ192TATJU RELQ192TAYDA RELQ192TAYDU RELQ192TAYCA RELQ192TAYCURELQ240TATJA RELQ240TATJU RELQ240TAYDA RELQ240TAYDU RELQ240TAYCA RELQ240TAYCU
5
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
3. Nomenclature
Outdoor Unit
Minor revision
Power supply symbolTJ: 3 phase, 208 / 230 V, 60 HzYD: 3 phase, 460 V, 60 HzYC: 3 phase, 575 V, 60 Hz
Indicates minor change category
Indicates major design categoryT: VRV IV
Capacity indication in cooling
RefrigerantQ: R410A
Indicates that this is aREL: Heat recovery air cooled (Cold Climate)
Q TJ AT A240REL
6
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
Indoor Unit
M 54 VJPB UX QF
Standard symbolU: United States of America
Power supply symbolVJ: 1 phase, 208/230 V, 60 HzSBL: 1 phase, 120 V, 60 Hz
Indicates major design category
Capacity indication in cooling05: 5,800 Btu/h 18: 18,000 Btu/h 48: 48,000 Btu/h07: 7,500 Btu/h 24: 24,000 Btu/h 54: 54,000 Btu/h09: 9,500 Btu/h 30: 30,000 Btu/h 60: 60,000 Btu/h12: 12,000 Btu/h 36: 36,000 Btu/h 72: 72,000 Btu/h15: 15,000 Btu/h 42: 42,000 Btu/h 96: 96,000 Btu/h
RefrigerantQ: R410A
ShapeF: Ceiling mounted cassette (Round flow with sensing)Z: VISTA™ 2 × 2 cassette unitU: 4-way blow ceiling-suspendedE: One way blow cassetteD: Slim ceiling mounted ductS: MSP concealed ducted unitM: Ceiling mounted ductH: Ceiling suspendedA: Wall mountedL: Floor standingN: Concealed floor standingT: Air handling unit (FXTQ) Upflow/Downflow (CXTQ)
Series categoryX: Inverter
Unit categoryF: Indoor unit for air cooled typeC: Cased coil unit
7
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
Branch Selector Unit
Power supply symbolVJ: 1 phase, 208 / 230 V, 60 Hz
Indicates major design categoryT: VRV IV (Heat Recovery)
Capacity indication36: 36,000 Btu/h60: 60,000 Btu/h96: 96,000 Btu/h
Refrigerant: R410A
Unit categoryBS: Branch selector unit
BS T VJQ 36
Single Branch Selector Unit (only necessary for Heat Recovery System)
Power supply symbolVJ: 1 phase, 208 / 230 V, 60 Hz
Indicates major design categoryT: VRV IV (Heat Recovery)
Capacity indication of connectable indoor units per branch
Refrigerant: R410A
Number of branches4: 4 branches 6: 6 branches 8: 8 branches10: 10 branches12: 12 branches
Unit categoryBS: Branch selector unit
BS T VJQ12 54
Multi Branch Selector Unit (only necessary for Heat Recovery System)
8
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
Air Treatment Equipment
M 48 VJ UM FX QF
Standard symbolU: United States of America
Power supply symbolVJ: 1 phase, 208 / 230 V, 60 Hz
Outdoor air processing unit
Indicates major design category
Capacity indication in cooling48: 48,000 Btu/h72: 72,000 Btu/h96: 96,000 Btu/h
RefrigerantQ: R410A
ShapeM: Ceiling mounted duct
Series categoryX: Inverter
Unit categoryF: Indoor unit for air cooled type
Outdoor Air Processing Unit
UG300V A M VJ
Standard symbolU: United States of America
Power supply symbolVJ: 1 phase, 208 / 230 V, 60 Hz
Indicates major design category
Airflow rate (H)300: 300 cfm 470: 470 cfm 600: 600 cfm1200: 1,200 cfm
Mounted type
Air
Ventilation
Energy Recovery Ventilator (VAM series)
9
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
4. Model Names4.1 Outdoor Units
Capacity range 6 ton 8 ton 10 ton 12 ton 14 ton 16 ton 18 ton 20 ton Power supply, StandardCapacity index 72 96 120 144 168 192 216 240
Heat recovery 208 / 230 V RELQ 72TA 96TA 120TA 144TA 168TA 192TA 216TA 240TA TJAHeat recovery 460 V RELQ 72TA 96TA 120TA 144TA 168TA 192TA 216TA 240TA YDAHeat recovery 575 V RELQ 72TA 96TA 120TA 144TA 168TA 192TA 216TA 240TA YCA
TJ: 3 phase, 208 / 230 V, 60 HzYD: 3 phase, 460 V, 60 HzYC: 3 phase, 575 V, 60 HzA: Minor revision
Heat Recovery 208 / 230 V
Model name RELQ72TATJA RELQ96TATJA RELQ120TATJAOutdoor unit 1 RELQ72TATJA RELQ96TATJA RELQ120TATJA
Model name RELQ144TATJA RELQ192TATJA RELQ240TATJAOutdoor unit 1 RELQ72TATJA RELQ96TATJA RELQ120TATJAOutdoor unit 2 RELQ72TATJA RELQ96TATJA RELQ120TATJA
Heat Recovery 460 V
Model name RELQ72TAYDA RELQ96TAYDA RELQ120TAYDAOutdoor unit 1 RELQ72TAYDA RELQ96TAYDA RELQ120TAYDA
Model name RELQ144TAYDA RELQ192TAYDA RELQ240TAYDAOutdoor unit 1 RELQ72TAYDA RELQ96TAYDA RELQ120TAYDAOutdoor unit 2 RELQ72TAYDA RELQ96TAYDA RELQ120TAYDA
Heat Recovery 575 V
Model name RELQ72TAYCA RELQ96TAYCA RELQ120TAYCAOutdoor unit 1 RELQ72TAYCA RELQ96TAYCA RELQ120TAYCA
Model name RELQ144TAYCA RELQ192TAYCA RELQ240TAYCAOutdoor unit 1 RELQ72TAYCA RELQ96TAYCA RELQ120TAYCAOutdoor unit 2 RELQ72TAYCA RELQ96TAYCA RELQ120TAYCA
10
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
4.2 Indoor Units
Capacity Range 0.5 ton 0.6 ton 0.8 ton 1 ton 1.25 ton 1.5 ton 2 ton 2.5 ton 3 ton 3.5 ton 4 ton 4.5 ton 5 ton 6 ton 8 ton Power Supply, StandardCapacity Index 5.8 7.5 9.5 12 15 18 20 24 30 36 42 48 54 60 72 96
Ceiling mounted cassette (Roundflowwithsensing)type
FXFQ — 07T 09T 12T 15T 18T — 24T 30T 36T — 48T — — — —
VJU
VISTA™ 2 × 2 cassette unit FXZQ 05TA 07TA 09TA 12TA 15TA 18TA — — — — — — — — — —4-way blow ceiling-suspended type FXUQ — — — — — — 18P 24P 30P 36P — — — — — —
One way blow cassette type FXEQ — 07P 09P 12P 15P 18P — 24P — — — — — — — —Slim ceiling mounted duct type FXDQ — 07M 09M 12M — 18M — 24M — — — — — — — —
MSP concealed ducted unit FXSQ 05TA 07TA 09TA 12TA 15TA 18TA — 24TA 30TA 36TA — 48TA 54TA — — —Ceiling mounted duct type (Middle and high static pressure)
FXMQ — 07PB 09PB 12PB 15PB 18PB — 24PB 30PB 36PB — 48PB 54PB — — —
Ceiling mounted duct type FXMQ — — — — — — — — — — — — — — 72M 96MCeiling suspended type FXHQ — — — 12M — — — 24M — 36M — — — — — —Wall mounted type FXAQ — 07P 09P 12P — 18P — 24P — — — — — — — —Floor standing type FXLQ — 07M 09M 12M — 18M — 24M — — — — — — — —Concealedfloorstandingtype FXNQ — 07M 09M 12M — 18M — 24M — — — — — — — —
Air handling unit FXTQ— — 09TA 12TA — 18TA — 24TA 30TA 36TA 42TA 48TA 54TA 60TA — — VJUA— — 09TA 12TA — 18TA — 24TA 30TA 36TA 42TA 48TA 54TA 60TA — — VJUD
Cased coil unit CXTQ — — — — — — — 24TA — 36TA — 48TA — 60TA — — SBLU
4.3 Branch Selector UnitSingle Branch Selector Unit for Heat Recovery
Series Model name Power supply, StandardHeat recovery BSQ 36T 60T 96T VJ
Note: No interchangeability between BSVQ-PVJU and BSQ-TVJ.
VJ: 1 phase, 208 / 230 V, 60 Hz
Multi Branch Selector Unit for Heat Recovery
Series Model name Power supply, StandardHeat recovery BS 4Q54T 6Q54T 8Q54T 10Q54T 12Q54T VJ
Note: No interchangeability between BSV-Q36PVJU and BS-Q54TVJ.
VJ: 1 phase, 208 / 230 V, 60 Hz
11
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
4.4 Air Treatment EquipmentOutdoor Air Processing Unit
Series Model name Power supply, StandardFXMQ 48MF 72MF 96MF VJU
VJ : 1 phase, 208 / 230 V, 60 HzU(VJU) : Standard symbol
Energy Recovery Ventilator (VAM series)
Series Model name Power supply, StandardVAM 300G 470G 600G 1200G VJU
VJ : 1 phase, 208 / 230 V, 60 HzU(VJU) : Standard symbol
12
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
5. External Appearance5.1 Outdoor UnitsSingle Outdoor Units
RELQ72TATJARELQ96TATJARELQ120TATJA
RELQ72TAYDARELQ96TAYDARELQ120TAYDA
RELQ72TAYCARELQ96TAYCARELQ120TAYCA
6, 8, 10 ton
Double Outdoor Units
RELQ144TATJARELQ192TATJARELQ240TATJA
RELQ144TAYCARELQ192TAYCARELQ240TAYCA
RELQ144TAYDARELQ192TAYDARELQ240TAYDA
12, 16, 20 ton
13
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
5.2 Indoor Units
Ceilingmountedcassette(Roundflowwithsensing)type
FXFQ-T
Shown with BYCQ125B-W1
Ceiling mounted duct type
FXMQ-M
VISTA™ 2 × 2 cassette unit
FXZQ-TA
Shown with BYFQ60C3W1W Shown with BYFQ60C3W1S
Ceiling suspended type
FXHQ-M
4-way blow ceiling-suspended type
FXUQ-P
Wall mounted type
FXAQ-P
One way blow cassette type
FXEQ-P
Floor standing type
FXLQ-M
Slim ceiling mounted duct type
FXDQ-M
Concealedfloorstandingtype
FXNQ-M
MSP concealed ducted unit
FXSQ-TA
Air handling unit
FXTQ-TA
Ceiling mounted duct type (Middle and high static pressure)
FXMQ-PB
Cased coil unit
CXTQ-TA
14
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
5.3 Branch Selector Unit
Single branch selector unit
BSQ-T
Multi branch selector unit
BS-Q54TVJ
5.4 Air Treatment Equipment
Outdoor air processing unit
FXMQ-MF
Energy recovery ventilator (VAM series)
VAM-G
15
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
6. Outdoor Unit Combination
Model nameSystem capacity Number of
unitsModule Outdoor unit multi connection
piping kit *1Ton HP kW 72 96 120RELQ72TATJARELQ72TAYDARELQ72TAYCA
6 7.5 21.1 1 l
—RELQ96TATJARELQ96TAYDARELQ96TAYCA
8 10.0 28.1 1 l
RELQ120TATJARELQ120TAYDARELQ120TAYCA
10 12.5 35.2 1 l
RELQ144TATJARELQ144TAYDARELQ144TAYCA
12 15.0 42.2 2 ll
BHFP26P100UBHFP26P100UA
RELQ192TATJARELQ192TAYDARELQ192TAYCA
16 20.0 56.3 2 ll
RELQ240TATJARELQ240TAYDARELQ240TAYCA
20 25.0 70.3 2 ll
Notes:*1. For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
16
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
7. Interchangeability
Branch selector unit
Outdoor unit
T-series branch selector unit (Reference)P-series branch selector unit
Single branch selector unit
Multi branch selector unit
Single branch selector unit
Multi branch selector unit
BSQ36TVJBSQ60TVJBSQ96TVJ
BS4Q54TVJBS6Q54TVJBS8Q54TVJBS10Q54TVJBS12Q54TVJ
BSVQ36PVJUBSVQ60PVJUBSVQ96PVJU
BSV4Q36PVJUBSV6Q36PVJU
Heat recovery RELQ-TARELQ-TATJA Connectable *1 Connectable *1 Not connectable Not connectableRELQ-TAYDA Connectable *1 Connectable *1 Not connectable Not connectableRELQ-TAYCA Connectable *1 Connectable *1 Not connectable Not connectable
Note:*1. Combination of P-series and T-series of Branch selector units in a single system is not permitted.
Combining the two series may cause malfunction.
17
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
8. Capacity Range8.1 Connection Ratio
Connection ratio =Total capacity index of the indoor units
Capacity index of the outdoor units
TypeMin.
connection ratio
Max. connection ratio
Types of connected indoor units Type of connected air treatment equipment
When using only FXDQ, FXMQ-PB,
FXAQ, FXSQ07-54TA
When using at least one FXZQ05TA, FXSQ05TA,
FXFQ07/09When using other indoor unit models
FXMQ-MF
When FXMQ-MF is only connected
When FXMQ-MF and indoor units are connected
Single outdoor units70% 200% *1
180% *1 200% *1100% 100% *2 *3
Double outdoor units 160% *1 160% *1
Notes:*1. Iftheoperationalcapacityofindoorunitsismorethan130%,lowairflowoperationisenforcedinalltheindoorunits.Fieldsettingnowexiststo
configurethissituation.Forcoolingandheatingmode–seebelow.*2. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total connection capacity of the outdoor-air
processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%. *3. Itispermittedtouseamaximumconnectionratioof130%insomecircumstances–pleasecontactyourlocalDaikinrepresentativeforfurther
details.*4. For indoor units used for cooling only (do not connect to Branch Selector unit when using for heat recovery), total capacity index must be 70%
or less than the capacity index of the outdoor units.
Indoor unit fan tap settingIndoor units fan speed limitation related to connection capacity and outdoor air temperature for energy saving.Default value = 0
Value Indoor unit fan tap setting0 Fan speed is limited to L tap when indoor units capacity ≥ 130%.1 In heating mode, fan speed is limited to L tap when indoor units capacity ≥ 130%.2 Fan speed follows the setting of remote controllers (not limited by indoor units connection capacity).
3FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow85.1°F(29.5°C)andindoorairtemperatureisinconditionA(*).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover90.5°F(32.5°C)orindoorairtemperature is in condition B (**).
4FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow74.3°F(23.5°C)andindoorairtemperatureisinconditionA(*).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover79.7°F(26.5°C)orindoorairtemperature is in condition B (**).
5FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow66.7°F(19.3°C)andindoorairtemperatureisinconditionA(*).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover72.1°F(22.3°C)orindoorairtemperature is in condition B (**).
6 FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow85.1°F(29.5°C).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover90.5°F(32.5°C).
7 FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow74.3°F(23.5°C).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover79.7°F(26.5°C).
8 FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow66.7°F(19.3°C).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover72.1°F(22.3°C).
*IndoorconditionA:Temperaturedifference(indoorairtemperature-settemperature)ismorethan−2.7°F(−1.5°C)andlessthan5.4°F(3°C).**IndoorconditionB:Temperaturedifference(indoorairtemperature-settemperature)is−2.7°F(−1.5°C)orless,or5.4°F(3°C)ormore.
18
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
8.2 Capacity Range of Connectable Indoor Units
Type Ton Capacity index Model name Total capacity index of connectable indoor units *1
Maximum number of connectable indoor units
Single outdoor units
6 72RELQ72TATJA RELQ72TAYDA RELQ72TAYCA
51 to 93 (144) 12
8 96RELQ96TATJA RELQ96TAYDA RELQ96TAYCA
68 to 124 (192) 16
10 120RELQ120TATJA RELQ120TAYDA RELQ120TAYCA
84 to 156 (240) 20
Double outdoor units
12 144RELQ144TATJA RELQ144TAYDA RELQ144TAYCA
101 to 187 (230) 25
16 192RELQ192TATJA RELQ192TAYDA RELQ192TAYCA
135 to 249 (307) 33
20 240RELQ240TATJA RELQ240TAYDA RELQ240TAYCA
168 to 312 (384) 41
Notes:*1. Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single outdoor units, 160% for double
outdoor units, and 130% for triple outdoor units.
19
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
8.3 Limitation of Capacity Index for Heat RecoverySingle Branch Selector Unit
Model BSQ36TVJ BSQ60TVJ BSQ96TVJMaximum number of connectable indoor units 4 8 8Total capacity index of connectable indoor units unit ≤ 36 36 < unit ≤ 60 60 < unit ≤ 96
Multi Branch Selector Unit
Model BS4Q54TVJ BS6Q54TVJ BS8Q54TVJ BS10Q54TVJ BS12Q54TVJMaximum number of connectable indoor units 20 30 40 41 41Maximum number of connectable indoor units per branch 5 5 5 5 5
Number of branches 4 6 8 10 12Maximum capacity index of connectable indoor units 144 or less 216 or less 290 or less 290 or less 290 or less
Maximum capacity index of connectable indoor units per branch (*1) 54 or less 54 or less 54 or less 54 or less 54 or less
Note: *1. When the total capacity of indoor units to be connected downstream is larger than 54 (Max. 96), use a junction pipe kit (KHRP26A250T,
optional parts) to join two connections downstream from the Branch selector unit.
High and low pressuregas pipingSuction gas pipingLiquid piping
Indoor unit(Heating)
Indoor unit(Cooling)
Indoor unit*(Cooling only)
Heat Recovery operation!
* For indoor units used for cooling only (do not connect to Branch selector unit when using for heat recovery), total capacity index must be 70% or less than the capacity index of the indoor units.
Branch Selector unit
Branch Selector unit
Heat Recovery
Outdoor unit
20
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
9. Specifications9.1 RELQ-TATJA
Outdoor Unit Model No. RELQ72TATJA RELQ96TATJA RELQ120TATJAPower supply 3 phase, 208/230 V, 60 Hz 3 phase, 208/230 V, 60 Hz 3 phase, 208/230 V, 60 Hz
H1 Cooling capacity
Nominal Btu/h (kW)
72,000 (21.1) 96,000 (28.1) 120,000 (35.2)Rated 69,000 (20.2) 92,000 (27.0) 114,000 (33.4)
H2 Heating capacity
Nominal Btu/h (kW)
81,000 (23.7) 108,000 (31.7) 135,000 (39.6)Rated 77,000 (22.6) 103,000 (30.2) 129,000 (37.8)
Casing color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
Dimensions: (H × W × D) in. (mm)
66-11/16 × 48-7/8 × 30-3/16(1,694 × 1,242 × 767)
66-11/16 × 48-7/8 × 30-3/16(1,694 × 1,242 × 767)
66-11/16 × 48-7/8 × 30-3/16(1,694 × 1,242 × 767)
Heat exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil
Compressor
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll TypeVolume m³/h 12.7 17.5 23.1Number of revolutions r/min 3,738 3,294 4,350Motor output × number of units kW 3.9 × 1 5.0 × 1 6.6 × 1
Starting method Soft Start Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan Propeller FanMotor output kW 0.8 × 2 0.8 × 2 0.8 × 2
Airflowrate cfm(m³/min) 7,283 (206) 7,989 (226) 8,806 (249)
Drive Direct Drive Direct Drive Direct Drive
Connecting pipes
Liquid pipe in. (mm)
f3/8 (9.5) C1220T(Brazing Connection)
f3/8 (9.5) C1220T (Brazing connection)
f1/2 (12.7) C1220T (Brazing Connection)
Suction gas pipe in. (mm)
f3/4 (19.1) C1220T(Brazing Connection)
f7/8 (22.2) C1220T (Brazing connection)
f1-1/8 (28.6) C1220T(Brazing Connection)
High / Low pressure gas pipe
in. (mm)
f5/8 (15.9) C1220T(Brazing Connection)
f3/4 (19.1) C1220T (Brazing connection)
f3/4 (19.1) C1220T (Brazing Connection)
Weight lbs (kg) 727 (330) 793 (360) 793 (360)Sound pressure level (Reference data) dB (A) 60 (65 H3) 61 (67 H3) 63.5 (67 H3)
Sound power level (Reference data) dB 79 80.5 84.5
Safety devices
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting Device
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting Device
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting DeviceDefrost method Deicer Deicer DeicerCapacity control % 10.7-100 9.4-100 8.6-100
RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 (11.7) 25.8 (11.7) 25.8 (11.7)Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Standard accessoriesInstallation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, Clamps
Notes:H1 Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft.(7.6m),level
difference: 0 ft. (0 m).H2 Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft.(7.6m),level
difference: 0 ft. (0 m).H3 Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound
pressure at those conditions.
C: 4D109459A, C: 4D109460B, C: 4D109461A
21
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
Outdoor unit model No. RELQ144TATJA RELQ192TATJA RELQ240TATJA
Unit combination RELQ72TATJARELQ72TATJA
RELQ96TATJARELQ96TATJA
RELQ120TATJARELQ120TATJA
Power supply 3 phase, 208/230 V, 60 Hz 3 phase, 208/230 V, 60 Hz 3 phase, 208/230 V, 60 Hz
H1 Cooling capacity
Nominal Btu/h (kW)
144,000 (42.2) 192,000 (56.3) 240,000 (70.3)Rated 138,000 (40.4) 184,000 (53.9) 228,000 (66.8)
H2 Heating capacity
Nominal Btu/h (kW)
162,000 (47.5) 216,000 (63.3) 270,000 (79.1)Rated 154,000 (45.1) 206,000 (60.4) 256,000 (75.0)
Casing color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
Dimensions: (H × W × D) in. (mm)
66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16
(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)
66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16
(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)
66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16
(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)
Heat exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil
Compressor
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll TypeVolume m³/h 12.9 + 12.9 17.5 + 17.5 22.4 + 22.4Number of revolutions r/min 3,804 + 3,804 3,294 + 3,294 4,230 + 4,230Motor output × number of units kW 4.0 × 1 + 4.0 × 1 5.0 × 1 + 5.0 × 1 6.5 × 1 + 6.5 × 1
Starting method Soft Start Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan Propeller FanMotor output kW (0.8 × 2) × 2 (0.8 × 2) × 2 (0.8 × 2) × 2
Airflowrate cfm(m³/min) 7,283 + 7,283 (206 + 206) 7,989 + 7,989 (226 + 226) 8,806 + 8,806 (249 + 249)
Drive Direct Drive Direct Drive Direct Drive
Connecting pipes
Liquid pipe in. (mm)
f1/2 (12.7) C1220T (Brazing Connection)
f5/8 (15.9) C1220T (Brazing Connection)
f5/8 (15.9) C1220T (Brazing Connection)
Suction gas pipe in. (mm)
f1-1/8 (28.6) C1220T (Brazing Connection)
f1-1/8 (28.6) C1220T (Brazing Connection)
f1-3/8 (34.9) C1220T (Brazing Connection)
High / Low pressure gas pipe
in. (mm)
f7/8 (22.2) C1220T (Brazing Connection)
f1-1/8 (28.6) C1220T (Brazing Connection)
f1-1/8 (28.6) C1220T (Brazing Connection)
Weight lbs (kg) 727 + 727 (330 + 330) 793 + 793 (360 + 360) 793 + 793 (360 + 360)Sound pressure level (Reference data) dB (A) 63 (68 H3) 64 (70 H3) 67 (70 H3)
Sound power level (Reference data) dB 82 83.5 87.5
Safety devices
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting Device
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting Device
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting DeviceDefrost method Deicer Deicer DeicerCapacity control % 5.4-100 4.7-100 4.3-100
RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7)Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Standard accessoriesInstallation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, Clamps
Notes:H1 Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft.(7.6m),level
difference: 0 ft. (0 m).H2 Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft.(7.6m),level
difference: 0 ft. (0 m).H3 Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound
pressure at those conditions.
C: 4D109462B, C: 4D109463A, C: 4D109464A
22
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
9.2 RELQ-TAYDA
Outdoor unit model No. RELQ72TAYDA RELQ96TAYDA RELQ120TAYDAPower supply 3 phase, 460 V, 60 Hz 3 phase, 460 V, 60 Hz 3 phase, 460 V, 60 Hz
H1 Cooling capacity
Nominal Btu/h (kW)
72,000 (21.1) 96,000 (28.1) 120,000 (35.2)Rated 69,000 (20.2) 92,000 (27.0) 114,000 (33.4)
H2 Heating capacity
Nominal Btu/h (kW)
81,000 (23.7) 108,000 (31.7) 135,000 (39.6)Rated 77,000 (22.6) 103,000 (30.2) 129,000 (37.8)
Casing color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
Dimensions: (H × W × D) in. (mm)
66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)
66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)
66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)
Heat exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil
Compressor
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll TypeVolume m³/h 12.7 17.5 23.1Number of revolutions r/min 3,738 3,294 4,350Motor output × number of units kW 3.9 × 1 5.0 × 1 6.6 × 1
Starting method Soft Start Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan Propeller FanMotor output kW 0.6 × 2 0.6 × 2 0.6 × 2
Airflowrate cfm(m³/min) 7,283 (206) 7,989 (226) 8,806 (249)
Drive Direct Drive Direct Drive Direct Drive
Connecting pipes
Liquid pipe in. (mm)
f3/8 (9.5) C1220T (Brazing Connection)
f3/8 (9.5) C1220T (Brazing Connection)
f1/2 (12.7) C1220T (Brazing Connection)
Suction gas pipe in. (mm)
f3/4 (19.1) C1220T (Brazing Connection)
f7/8 (22.2) C1220T (Brazing Connection)
f1-1/8 (28.6) C1220T (Brazing Connection)
High / Low pressure gas pipe
in. (mm)
f5/8 (15.9) C1220T (Brazing Connection)
f3/4 (19.1) C1220T (Brazing Connection)
f3/4 (19.1) C1220T (Brazing Connection)
Weight lbs (kg) 727 (330) 793 (360) 793 (360)Sound pressure level (Reference data) dB (A) 60 (65 H3) 61 (67 H3) 63.5 (67 H3)
Sound power level (Reference data) dB 79 80.5 84.5
Safety devices
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting Device
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting Device
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting DeviceDefrost method Deicer Deicer DeicerCapacity control % 10.7-100 9.4-100 8.6-100
RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 (11.7) 25.8 (11.7) 25.8 (11.7)Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Standard accessoriesInstallation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, Clamps
Notes:H1 Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft.(7.6m),level
difference: 0 ft. (0 m).H2 Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft.(7.6m),level
difference: 0 ft. (0 m).H3 Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound
pressure at those conditions.
C: 4D109465A, C: 4D109466B, C: 4D109467A
23
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
Outdoor unit model No. RELQ144TAYDA RELQ192TAYDA RELQ240TAYDA
Unit combination RELQ72TAYDARELQ72TAYDA
RELQ96TAYDARELQ96TAYDA
RELQ120TAYDARELQ120TAYDA
Power supply 3 phase, 460 V, 60 Hz 3 phase, 460 V, 60 Hz 3 phase, 460 V, 60 Hz
H1 Cooling capacity
Nominal Btu/h (kW)
144,000 (42.2) 192,000 (56.3) 240,000 (70.3)Rated 138,000 (40.4) 184,000 (53.9) 228,000 (66.8)
H2 Heating capacity
Nominal Btu/h (kW)
162,000 (47.5) 216,000 (63.3) 270,000 (79.1)Rated 154,000 (45.1) 206,000 (60.4) 256,000 (75.0)
Casing color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
Dimensions: (H × W × D) in. (mm)
66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16
(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)
66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16
(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)
66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16
(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)
Heat exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil
Compressor
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll TypeVolume m³/h 12.9 + 12.9 17.5 + 17.5 22.4 + 22.4Number of revolutions r/min 3,804 + 3,804 3,294 + 3,294 4,230 + 4,230Motor output × number of units kW 4.0 × 1 + 4.0 × 1 5.0 × 1 + 5.0 × 1 6.5 × 1 + 6.5 × 1
Starting method Soft Start Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan Propeller FanMotor output kW (0.6 × 2) × 2 (0.6 × 2) × 2 (0.6 × 2) × 2
Airflowrate cfm(m³/min) 7,283 + 7,283 (206 + 206) 7,989 + 7,989 (226 + 226) 8,806 + 8,806 (249 + 249)
Drive Direct Drive Direct Drive Direct Drive
Connecting pipes
Liquid pipe in. (mm)
f1/2 (12.7) C1220T (Brazing Connection)
f5/8 (15.9) C1220T (Brazing Connection)
f5/8 (15.9) C1220T (Brazing Connection)
Suction gas pipe in. (mm)
f1-1/8 (28.6) C1220T (Brazing Connection)
f1-1/8 (28.6) C1220T (Brazing Connection)
f1-3/8 (34.9) C1220T (Brazing Connection)
High / Low pressure gas pipe
in. (mm)
f7/8 (22.2) C1220T (Brazing Connection)
f1-1/8 (28.6) C1220T (Brazing Connection)
f1-1/8 (28.6) C1220T (Brazing Connection)
Weight lbs (kg) 727 + 727 (330 + 330) 793 + 793 (360 + 360) 793 + 793 (360 + 360)Sound pressure level (Reference data) dB (A) 63 (68 H3) 64 (70 H3) 67 (70 H3)
Sound power level (Reference data) dB 82 83.5 87.5
Safety devices
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting Device
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting Device
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting DeviceDefrost method Deicer Deicer DeicerCapacity control % 5.4-100 4.7-100 4.3-100
RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7)Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Standard accessoriesInstallation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, Clamps
Notes:H1 Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft.(7.6m),level
difference: 0 ft. (0 m).H2 Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft.(7.6m),level
difference: 0 ft. (0 m).H3 Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound
pressure at those conditions.
C: 4D109468B, C: 4D109469A, C: 4D109470A
24
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
9.3 RELQ-TAYCA
Outdoor unit model No. RELQ72TAYCA RELQ96TAYCA RELQ120TAYCAPower supply 3 phase, 575 V, 60 Hz 3 phase, 575 V, 60 Hz 3 phase, 575 V, 60 Hz
H1 Cooling capacity
Nominal Btu/h (kW)
72,000 (21.1) 96,000 (28.1) 120,000 (35.2)Rated 69,000 (20.2) 92,000 (27.0) 114,000 (33.4)
H2 Heating capacity
Nominal Btu/h (kW)
81,000 (23.7) 108,000 (31.7) 135,000 (39.6)Rated 77,000 (22.6) 103,000 (30.2) 129,000 (37.8)
Casing color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
Dimensions: (H × W × D) in. (mm)
66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)
66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)
66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)
Heat exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil
Compressor
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll TypeVolume m³/h 12.7 17.5 23.1Number of revolutions r/min 3,738 3,294 4,350Motor output × number of units kW 3.9 × 1 5.0 × 1 6.6 × 1
Starting method Soft Start Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan Propeller FanMotor output kW 0.7 × 2 0.7 × 2 0.7 × 2
Airflowrate cfm(m³/min) 7,283 (206) 7,989 (226) 8,806 (249)
Drive Direct Drive Direct Drive Direct Drive
Connecting pipes
Liquid pipe in. (mm)
f3/8 (9.5) C1220T (Brazing Connection)
f3/8 (9.5) C1220T (Brazing Connection)
f1/2 (12.7) C1220T (Brazing Connection)
Suction gas pipe in. (mm)
f3/4 (19.1) C1220T (Brazing Connection)
f7/8 (22.2) C1220T (Brazing Connection)
f1-1/8 (28.6) C1220T (Brazing Connection)
High / Low pressure gas pipe
in. (mm)
f5/8 (15.9) C1220T (Brazing Connection)
f3/4 (19.1) C1220T (Brazing Connection)
f3/4 (19.1) C1220T (Brazing Connection)
Weight lbs (kg) 727 (330) 793 (360) 793 (360)Sound pressure level (Reference data) dB (A) 60 (65 H3) 61 (67 H3) 63.5 (67 H3)
Sound power level (Reference data) dB 79 80.5 84.5
Safety devices
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting Device
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting Device
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting DeviceDefrost method Deicer Deicer DeicerCapacity control % 10.7-100 9.4-100 8.6-100
RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 (11.7) 25.8 (11.7) 25.8 (11.7)Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Standard accessoriesInstallation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, Clamps
Notes:H1 Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft.(7.6m),level
difference: 0 ft. (0 m).H2 Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft.(7.6m),level
difference: 0 ft. (0 m).H3 Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound
pressure at those conditions.
C: 4D107389C, C: 4D107390D, C: 4D107391C
25
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
Outdoor unit model No. RELQ144TAYCA RELQ192TAYCA RELQ240TAYCA
Unit combination RELQ72TAYCARELQ72TAYCA
RELQ96TAYCARELQ96TAYCA
RELQ120TAYCARELQ120TAYCA
Power supply 3 phase, 575 V, 60 Hz 3 phase, 575 V, 60 Hz 3 phase, 575 V, 60 Hz
H1 Cooling capacity
Nominal Btu/h (kW)
144,000 (42.2) 192,000 (56.3) 240,000 (70.3)Rated 138,000 (40.4) 184,000 (53.9) 228,000 (66.8)
H2 Heating capacity
Nominal Btu/h (kW)
162,000 (47.5) 216,000 (63.3) 270,000 (79.1)Rated 154,000 (45.1) 206,000 (60.4) 256,000 (75.0)
Casing color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
Dimensions: (H × W × D) in. (mm)
66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16
(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)
66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16
(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)
66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16
(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)
Heat exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil
Compressor
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll TypeVolume m³/h 12.9 + 12.9 17.5 + 17.5 22.4 + 22.4Number of revolutions r/min 3,804 + 3,804 3,294 + 3,294 4,230 + 4,230Motor output × number of units kW 4.0 × 1 + 4.0 × 1 5.0 × 1 + 5.0 × 1 6.5 × 1 + 6.5 × 1
Starting method Soft Start Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan Propeller FanMotor output kW (0.7 × 2) × 2 (0.7 × 2) × 2 (0.7 × 2) × 2
Airflowrate cfm(m³/min) 7,283 + 7,283 (206 + 206) 7,989 + 7,989 (226 + 226) 8,806 + 8,806 (249 + 249)
Drive Direct Drive Direct Drive Direct Drive
Connecting pipes
Liquid pipe in. (mm)
f1/2 (12.7) C1220T (Brazing Connection)
f5/8 (15.9) C1220T (Brazing Connection)
f5/8 (15.9) C1220T (Brazing Connection)
Suction gas pipe in. (mm)
f1-1/8 (28.6) C1220T (Brazing Connection)
f1-1/8 (28.6) C1220T (Brazing Connection)
f1-3/8 (34.9) C1220T (Brazing Connection)
High / Low pressure gas pipe
in. (mm)
f7/8 (22.2) C1220T (Brazing Connection)
f1-1/8 (28.6) C1220T (Brazing Connection)
f1-1/8 (28.6) C1220T (Brazing Connection)
Weight lbs (kg) 727 + 727 (330 + 330) 793 + 793 (360 + 360) 793 + 793 (360 + 360)Sound pressure level (Reference data) dB (A) 63 (68 H3) 64 (70 H3) 67 (70 H3)
Sound power level (Reference data) dB 82 83.5 87.5
Safety devices
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting Device
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting Device
High Pressure Switch, Fan Driver Overload Protector,
Overcurrent Fuse, Inverter Overload Protector,
Leak Detecting DeviceDefrost method Deicer Deicer DeicerCapacity control % 5.4-100 4.7-100 4.3-100
RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7)Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Standard accessoriesInstallation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, Clamps
Notes:H1 Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft.(7.6m),level
difference: 0 ft. (0 m).H2 Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft.(7.6m),level
difference: 0 ft. (0 m).H3 Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound
pressure at those conditions.
C: 4D107392D, C: 4D107393C, C: 4D107394D
26
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
10. Dimensions
RELQ72-120TATJA / TAYDA / TAYCA
C: 3
D10
7340
A
A
AA
A
AA
A
AA
A
AA
27
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ144-240TATJA / TAYDA / TAYCA
C: 3
D10
7341
C
Not
es :
1. H
eigh
ts o
f wal
ls o
f thi
s ex
ampl
e;Fr
ont :
59
in. (
1500
mm
)S
uctio
n si
de :
19-5
/8 in
. (50
0 m
m)
Sid
e : H
eigh
t unr
estri
cted
The
inst
alla
tion
spac
e sh
own
in th
is fi
gure
is b
ased
on
the
cond
ition
of c
oolin
g op
erat
ion
at th
e ou
tdoo
r air
tem
pera
ture
of 9
5°FD
B (3
5°C
DB
).Th
e in
stal
latio
n sp
ace
of s
uctio
n si
de s
how
n ab
ove
mus
t be
expa
nded
in th
e fo
llow
ing
case
.· D
esig
n ou
tdoo
r tem
pera
ture
bec
omes
ove
r 95°
FDB
(35°
CD
B).
· Ope
ratin
g ov
er m
ax. o
pera
ting
load
(In
case
of c
ausi
ng a
hea
vy h
eatin
g lo
ad a
t ind
oor u
nit s
ide)
2. If
the
abov
e w
all h
eigh
ts a
re e
xcee
ded
then
h2/
2 an
d h1
/2 s
houl
d be
add
ed to
the
front
and
suc
tion
side
ser
vice
spac
es re
spec
tivel
y as
sho
wn
in th
e fo
llow
ing
figur
e.3.
Whe
n in
stal
ling
the
units
the
mos
t app
ropr
iate
pat
tern
sho
uld
be s
elec
ted
from
“Ins
talla
tion
and
repa
ir sp
ace
draw
ing”
in o
rder
to o
btai
n th
e be
st fi
t in
the
spac
e av
aila
ble
alw
ays
bear
ing
in m
ind
the
need
to le
ave
enou
gh ro
omfo
r a p
erso
n to
pas
s be
twee
n un
its a
nd w
all a
nd fo
r the
air
to c
ircul
ate
freel
y.(If
mor
e un
its a
re to
be
inst
alle
d th
an a
re s
how
n in
“Ins
talla
tion
and
repa
ir sp
ace
draw
ing”
, you
r lay
out s
houl
d ta
keac
coun
t of t
he p
ossi
bilit
y of
sho
rt ci
rcui
ting.
)4.
The
uni
ts s
houl
d be
inst
alle
d to
leav
e su
ffici
ent s
pace
at t
he fr
ont f
or th
e on
site
refri
gera
nt p
ipin
g w
ork
to b
e ca
rrie
dou
t com
forta
bly.
AA A A A A A A A A
A A A A A A A A A
A A A A A A A A
28
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
11. Service Space
RELQ72-240TATJA / TAYDA / TAYCA
C: 3
D08
5503
H
Uni
t : in
. (m
m)
Not
es:
1. H
eigh
ts o
f wal
ls in
cas
e of
Pat
tern
s 1
and
2;Fr
ont :
59
in. (
1500
mm
)Su
ctio
n si
de :
19-5
/8 in
. (50
0 m
m)
Side
: H
eigh
t unr
estri
cted
The
inst
alla
tion
spac
e sh
own
in th
is fi
gure
is b
ased
on
the
cond
ition
of c
oolin
g op
erat
ion
at th
e ou
tdoo
r air
tem
pera
ture
of 9
5 °FD
B (3
5°C
DB)
. Th
e in
stal
latio
n sp
ace
of s
uctio
n si
de s
how
n ab
ove
mus
t be
expa
nded
in th
e fo
llow
ing
case
.∙D
esig
n ou
tdoo
r tem
pera
ture
bec
omes
ove
r 95°
FDB
(35°
CD
B).
∙Ope
ratin
g ov
er m
ax. o
pera
ting
load
(In
case
of c
ausi
ng a
hea
vy h
eatin
g lo
ad a
t ind
oor u
nit s
ide)
2. If
the
abov
e w
all h
eigh
ts a
re e
xcee
ded
then
h2/
2 an
d h1
/2 s
houl
d be
add
ed to
the
front
and
suc
tion
side
ser
vice
spa
ces
resp
ectiv
ely
as s
how
n in
the
follo
win
g fig
ure.
3. W
hen
inst
allin
g th
e un
its th
e m
ost a
ppro
pria
te p
atte
rn s
houl
d be
sel
ecte
d fro
m "I
nsta
llatio
n an
d re
pair
spac
e dr
awin
g" in
ord
er to
obt
ain
the
best
fit i
n th
e sp
ace
avai
labl
e al
way
s be
arin
g in
min
d th
e ne
ed to
leav
e en
ough
room
for a
per
son
to p
ass
betw
een
units
and
wal
l and
for t
he a
ir to
circ
ulat
e fre
ely.
(If m
ore
units
are
to b
e in
stal
led
than
are
sho
wn
in "I
nsta
llatio
n an
d re
pair
spac
e dr
awin
g", y
our l
ayou
t sho
uld
take
acc
ount
of t
he p
ossi
bilit
y of
sho
rt ci
rcui
ting.
)4.
The
uni
ts s
houl
d be
inst
alle
d to
leav
e su
ffici
ent s
pace
at t
he fr
ont f
or th
e on
site
refri
gera
nt p
ipin
g w
ork
to b
e ca
rried
out
com
forta
bly.
29
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ72-240TATJA / TAYDA / TAYCA
Not
es:
1. H
eigh
ts o
f wal
ls in
cas
e of
Pat
tern
s 1
and
2;Fr
ont :
59
in. (
1500
mm
)Su
ctio
n si
de :
19-5
/8 in
. (50
0 m
m)
Side
: H
eigh
t unr
estri
cted
The
inst
alla
tion
spac
e sh
own
in th
is fi
gure
is b
ased
on
the
cond
ition
of c
oolin
g op
erat
ion
at th
e ou
tdoo
r air
tem
pera
ture
of 9
5 °FD
B (3
5°C
DB)
. Th
e in
stal
latio
n sp
ace
of s
uctio
n si
de s
how
n ab
ove
mus
t be
expa
nded
in th
e fo
llow
ing
case
.∙D
esig
n ou
tdoo
r tem
pera
ture
bec
omes
ove
r 95°
FDB
(35°
CD
B).
∙Ope
ratin
g ov
er m
ax. o
pera
ting
load
(In
case
of c
ausi
ng a
hea
vy h
eatin
g lo
ad a
t ind
oor u
nit s
ide)
2. If
the
abov
e w
all h
eigh
ts a
re e
xcee
ded
then
h2/
2 an
d h1
/2 s
houl
d be
add
ed to
the
front
and
suc
tion
side
ser
vice
spa
ces
resp
ectiv
ely
as s
how
n in
the
follo
win
g fig
ure.
3. W
hen
inst
allin
g th
e un
its th
e m
ost a
ppro
pria
te p
atte
rn s
houl
d be
sel
ecte
d fro
m "I
nsta
llatio
n an
d re
pair
spac
e dr
awin
g" in
ord
er to
obt
ain
the
best
fit i
n th
e sp
ace
avai
labl
e al
way
s be
arin
g in
min
d th
e ne
ed to
leav
e en
ough
room
for a
per
son
to p
ass
betw
een
units
and
wal
l and
for t
he a
ir to
circ
ulat
e fre
ely.
(If m
ore
units
are
to b
e in
stal
led
than
are
sho
wn
in "I
nsta
llatio
n an
d re
pair
spac
e dr
awin
g", y
our l
ayou
t sho
uld
take
acc
ount
of t
he p
ossi
bilit
y of
sho
rt ci
rcui
ting.
)4.
The
uni
ts s
houl
d be
inst
alle
d to
leav
e su
ffici
ent s
pace
at t
he fr
ont f
or th
e on
site
refri
gera
nt p
ipin
g w
ork
to b
e ca
rried
out
com
forta
bly.
C: 3
D08
5503
H
Uni
t : in
. (m
m)
30
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
12. Center of Gravity
RELQ72TATJA / TAYDA / TAYCA
4D107384
31
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ96-120TATJA / TAYDA / TAYCA
4D107385
32
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
13. Foundation Drawing
RELQ72-120TATJA / TAYDA / TAYCA
C: 3
D08
5480
F
A A A AA A
A A A
A A AA
AAA
A
A A
33
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
14. Piping Diagrams
RELQ72TATJA / TAYDA / TAYCA
3D10
7166
34
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ96-120TATJA / TAYDA / TAYCA
3D10
7167
35
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
15. Wiring Diagrams
RELQ72TATJA
C: 2
D11
2580
C
1. T
HIS
WIR
ING
DIA
GR
AM
AP
PLI
ES
ON
LY T
O T
HE
OU
TDO
OR
UN
IT.
2.
: F
IELD
WIR
ING
,
: TE
RM
INA
L B
LOC
K,
: C
ON
NE
CTO
R,
: T
ER
MIN
AL,
: PR
OTE
CTI
VE
GR
OU
ND
(SC
RE
W),
:
NO
ISE
LES
S G
RO
UN
D.
3. W
HE
N U
SIN
G T
HE
OP
TIO
NA
L A
DA
PTE
R, R
EFE
R T
O T
HE
INS
TALL
ATIO
N M
AN
UA
L O
F TH
E O
PTI
ON
AL
AD
AP
TER
.4.
FO
R C
ON
NE
CTI
ON
WIR
ING
TO
IND
OO
R-O
UTD
OO
R T
RA
NS
MIS
SIO
N F
1·F2
, OU
TDO
OR
-OU
TDO
OR
TR
AN
SM
ISS
ION
F1·
F2,
OU
TDO
OR
-MU
LTI T
RA
NS
MIS
SIO
N Q
1·Q
2, R
EFE
R T
O T
HE
INS
TALL
ATIO
N M
AN
UA
L. 5
. HO
W T
O U
SE
BS
1~3
SW
ITC
H, R
EFE
R T
O “S
ER
VIC
E P
RE
CA
UTI
ON
S” L
AB
EL
ON
C
ON
TRO
L B
OX
CO
VE
R.
6. W
HE
N O
PE
RAT
ING
, DO
N'T
SH
OR
TCIR
CU
IT T
HE
PR
OTE
CTI
ON
DE
VIC
E (S
1PH
). 7
. CO
LOR
S B
LK :
BLA
CK
; R
ED
: R
ED
; B
LU :
BLU
E ;
WH
T : W
HIT
E ;
GR
N :
GR
EE
N ;
GR
Y : G
RAY
; Y
LW :
YE
LLO
W.
8. C
LAS
S 2
WIR
E
NO
TES
)
36
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ72TATJA A1P PRINTED CIRCUIT BOARD (MAIN) R12T THERMISTOR (COMP. SUCTION)A2P PRINTED CIRCUIT BOARD (NOISE FILTER) R13T THERMISTOR (RECEIVER GAS PURGE)A3P PRINTED CIRCUIT BOARD (INV) R14T THERMISTOR (M1C BODY)A4P, A5P PRINTED CIRCUIT BOARD (FAN) R15T THERMISTOR (LEAK DETECTION)A6P PRINTED CIRCUIT BOARD (SUB) R16T THERMISTOR (EVT)A7P PRINTED CIRCUIT BOARD (ABC I/P) R21T THERMISTOR (M1C DISCHARGE)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) R71T THERMISTOR (L1R)C1 CAPACITOR (A3P) R72T THERMISTOR (L2R)DS1, DS2 DIP SWITCH (A1P) S1NPH PRESSURE SENSOR (HIGH)E1HC, E2HC CRANKCASE HEATER S1NPL PRESSURE SENSOR (LOW)F1U FUSE (A1P, A6P) S1PH PRESSURE SWITCH (HIGH)F2U FUSE (A1P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)F101U FUSE (A4P, A5P) SHT1 CURRENT SENSOR (A3P) F4U, F5U FUSE (A2P) T1A CURRENT SENSORHAP PILOTLAMP (A1P, A3P~A6P) (SERVICE MONITOR-GREEN) V1D DIODE (A3P)K3R MAGNETIC RELAY (A3P) V1R POWER MODULE (A3P)K1M MAGNETIC CONTACTOR (A3P) V3R POWER MODULE (A4P, A5P)K3R MAGNETIC RELAY (Y1S) (A1P) X1A, X2A CONNECTOR (M1F)K4R MAGNETIC RELAY (Y2S) (A1P) X3A, X4A CONNECTOR (M2F)K6R MAGNETIC RELAY (OPTION) (A1P) X6A CONNECTOR (CHECK THE RESIDUAL CHARGE)K7R MAGNETIC RELAY (E1HC, E2HC) (A1P) X13A, X14A CONNECTOR (E1HC, E2HC)K8R MAGNETIC RELAY (Y7S) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K9R MAGNETIC RELAY (Y4S) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K11R MAGNETIC RELAY (Y3S) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A7P)K12R MAGNETIC RELAY (Y5S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K13R MAGNETIC RELAY (Y6S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K84R MAGNETIC RELAY (A3P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)L1R, L2R REACTOR Y4E ELECTRIC EXPANSION VALVE (INJECTION)M1C MOTOR (COMPRESSOR) Y5E ELECTRIC EXPANSION VALVE (REFRIGERANT COOLING)M1F, M2F MOTOR (FAN) Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)PS SWITCHING POWER SUPPLY (A1P, A3P, A6P) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y1S SOLENOID VALVE (OS OIL RETURN 1)Q1RP REVERSE PHASE PROTECTOR CIRCUIT (A1P) Y2S SOLENOID VALVE (HOT GAS BYPASS)R1 RESISTOR (CURRENT LIMITING) (A3P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R2 RESISTOR (CURRENT SENSOR) (A4P, A5P) Y4S 4 WAY VALVE (HP/LP GAS)R1T THERMISTOR (AIR) Y5S 4 WAY VALVE (HEAT EXC. LOWER)R3T THERMISTOR (RECEIVER INLET) Y6S 4 WAY VALVE (HEAT EXC. UPPER)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R5T THERMISTOR (HEAT EXC. LIQUID LOWER) Z1C~Z6C NOISE FILTER (FERRITE CORE)R6T THERMISTOR (SUBCOOL GAS) ZF NOISE FILTER (A2P) (WITH SURGE ABSORBER)R7T THERMISTOR (SUBCOOL LIQUID) CONNECTOR FOR OPTIONAL ACCESSORIESR8T THERMISTOR (HEAT EXC. GAS UPPER) X37A CONNECTOR (POWER ADAPTER) (A1P)R9T THERMISTOR (HEAT EXC. GAS LOWER) COOL/HEAT SELECTORR10T THERMISTOR (SUCTION) S1S SELECTOR SWITCH (FAN/COOL·HEAT)R11T THERMISTOR (DEICER) S2S SELECTOR SWITCH (COOL/HEAT)
C: 2D112580C
37
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ96-120TATJA
C: 2
D11
2581
C
1. T
HIS
WIR
ING
DIA
GR
AM
AP
PLI
ES
ON
LY T
O T
HE
OU
TDO
OR
UN
IT.
2.
: F
IELD
WIR
ING
,
: TE
RM
INA
L B
LOC
K,
: C
ON
NE
CTO
R,
: T
ER
MIN
AL,
: PR
OTE
CTI
VE
GR
OU
ND
(SC
RE
W),
:
NO
ISE
LES
S G
RO
UN
D.
3. W
HE
N U
SIN
G T
HE
OP
TIO
NA
L A
DA
PTE
R, R
EFE
R T
O T
HE
INS
TALL
ATIO
N M
AN
UA
L O
F TH
E O
PTI
ON
AL
AD
AP
TER
.4.
FO
R C
ON
NE
CTI
ON
WIR
ING
TO
IND
OO
R-O
UTD
OO
R T
RA
NS
MIS
SIO
N F
1·F2
, OU
TDO
OR
-OU
TDO
OR
TR
AN
SM
ISS
ION
F1·
F2,
OU
TDO
OR
-MU
LTI T
RA
NS
MIS
SIO
N Q
1·Q
2, R
EFE
R T
O T
HE
INS
TALL
ATIO
N M
AN
UA
L. 5
. HO
W T
O U
SE
BS
1~3
SW
ITC
H, R
EFE
R T
O “S
ER
VIC
E P
RE
CA
UTI
ON
S” L
AB
EL
ON
C
ON
TRO
L B
OX
CO
VE
R.
6. W
HE
N O
PE
RAT
ING
, DO
N'T
SH
OR
TCIR
CU
IT T
HE
PR
OTE
CTI
ON
DE
VIC
E (S
1PH
). 7
. CO
LOR
S B
LK :
BLA
CK
; R
ED
: R
ED
; B
LU :
BLU
E ;
WH
T : W
HIT
E ;
GR
N :
GR
EE
N ;
GR
Y : G
RAY
; Y
LW :
YE
LLO
W.
8. C
LAS
S 2
WIR
E
NO
TES
)
38
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ96-120TATJA A1P PRINTED CIRCUIT BOARD (MAIN) R12T THERMISTOR (COMP. SUCTION)A2P PRINTED CIRCUIT BOARD (NOISE FILTER) R13T THERMISTOR (RECEIVER GAS PURGE)A3P PRINTED CIRCUIT BOARD (INV) R14T THERMISTOR (M1C BODY)A4P, A5P PRINTED CIRCUIT BOARD (FAN) R15T THERMISTOR (LEAK DETECTION)A6P PRINTED CIRCUIT BOARD (SUB) R16T THERMISTOR (EVT)A7P PRINTED CIRCUIT BOARD (ABC I/P) R21T THERMISTOR (M1C DISCHARGE)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) R71T THERMISTOR (POWER MODULE) (A3P) C1 CAPACITOR (A3P) R72T THERMISTOR (DIODE) (A3P) C2 CAPACITOR (A2P) S1NPH PRESSURE SENSOR (HIGH)DS1, DS2 DIP SWITCH (A1P) S1NPL PRESSURE SENSOR (LOW)E1HC, E2HC CRANKCASE HEATER S1PH PRESSURE SWITCH (HIGH)F1U FUSE (A1P, A2P, A6P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)F2U FUSE (A1P, A2P) T1A CURRENT SENSORF3U FUSE (A2P) T2A, T3A CURRENT SENSOR (A3P) F4U, F5U FUSE (X2M) V1D DIODE (A3P)F101U FUSE (A4P, A5P) V1R DIODE BRIDGEHAP PILOTLAMP (A1P, A3P~A6P) (SERVICE MONITOR-GREEN) V2R POWER MODULE (A3P)K1M MAGNETIC CONTACTOR (A4P) V3R POWER MODULE (A4P, A5P)K3R MAGNETIC RELAY (Y1S) (A1P) X1A, X2A CONNECTOR (M1F)K4R MAGNETIC RELAY (Y2S) (A1P) X3A, X4A CONNECTOR (M2F)K5R MAGNETIC RELAY (A3P) X13A, X14A CONNECTOR (E1HC, E2HC)K6R MAGNETIC RELAY (OPTION) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K7R MAGNETIC RELAY (E1HC, E2HC) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K8R MAGNETIC RELAY (Y7S) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A7P)K9R MAGNETIC RELAY (Y4S) (A1P) X2M TERMINAL BLOCK (FUSE)K11R MAGNETIC RELAY (Y3S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K12R MAGNETIC RELAY (Y5S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K13R MAGNETIC RELAY (Y6S) (A1P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)K84R MAGNETIC RELAY (A3P) Y4E ELECTRIC EXPANSION VALVE (INJECTION)L1R REACTOR Y5E ELECTRIC EXPANSION VALVE (REFRIGERANT COOLING)M1C MOTOR (COMPRESSOR) Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)M1F, M2F MOTOR (FAN) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)PS SWITCHING POWER SUPPLY (A1P, A3P, A6P) Y1S SOLENOID VALVE (OS OIL RETURN 1)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y2S SOLENOID VALVE (HOT GAS BYPASS)Q1RP REVERSE PHASE PROTECTOR CIRCUIT (A1P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R1 RESISTOR (CURRENT LIMITING) (A3P) Y4S 4 WAY VALVE (HP/LP GAS)R2 RESISTOR (CURRENT SENSOR) (A4P, A5P) Y5S 4 WAY VALVE (HEAT EXC. LOWER)R1T THERMISTOR (AIR) Y6S 4 WAY VALVE (HEAT EXC. UPPER)R3T THERMISTOR (RECEIVER INLET) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) Z1C~Z8C NOISE FILTER (FERRITE CORE)R5T THERMISTOR (HEAT EXC. LIQUID LOWER) Z1F NOISE FILTERR6T THERMISTOR (SUBCOOL GAS) ZF NOISE FILTER (A2P) (WITH SURGE ABSORBER)R7T THERMISTOR (SUBCOOL LIQUID) CONNECTOR FOR OPTIONAL ACCESSORIESR8T THERMISTOR (HEAT EXC. GAS UPPER) X37A CONNECTOR (POWER ADAPTER) (A1P)R9T THERMISTOR (HEAT EXC. GAS LOWER) COOL/HEAT SELECTORR10T THERMISTOR (SUCTION) S1S SELECTOR SWITCH (FAN/COOL·HEAT)R11T THERMISTOR (DEICER) S2S SELECTOR SWITCH (COOL/HEAT)
C: 2D112581C
39
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ72TAYDA
C: 2
D11
2582
D
1. T
HIS
WIR
ING
DIA
GR
AM
AP
PLI
ES
ON
LY T
O T
HE
OU
TDO
OR
UN
IT.
2.
: F
IELD
WIR
ING
,
: TE
RM
INA
L B
LOC
K,
: C
ON
NE
CTO
R,
: T
ER
MIN
AL,
: PR
OTE
CTI
VE
GR
OU
ND
(SC
RE
W),
:
NO
ISE
LES
S G
RO
UN
D.
3. W
HE
N U
SIN
G T
HE
OP
TIO
NA
L A
DA
PTE
R, R
EFE
R T
O T
HE
INS
TALL
ATIO
N M
AN
UA
L O
F TH
E O
PTI
ON
AL
AD
AP
TER
.4.
FO
R C
ON
NE
CTI
ON
WIR
ING
TO
IND
OO
R-O
UTD
OO
R T
RA
NS
MIS
SIO
N F
1·F2
, OU
TDO
OR
-OU
TDO
OR
TR
AN
SM
ISS
ION
F1·
F2,
OU
TDO
OR
-MU
LTI T
RA
NS
MIS
SIO
N Q
1·Q
2, R
EFE
R T
O T
HE
INS
TALL
ATIO
N M
AN
UA
L. 5
. HO
W T
O U
SE
BS
1~3
SW
ITC
H, R
EFE
R T
O “S
ER
VIC
E P
RE
CA
UTI
ON
S” L
AB
EL
ON
C
ON
TRO
L B
OX
CO
VE
R.
6. W
HE
N O
PE
RAT
ING
, DO
N'T
SH
OR
TCIR
CU
IT T
HE
PR
OTE
CTI
ON
DE
VIC
E (S
1PH
). 7
. CO
LOR
S B
LK :
BLA
CK
; R
ED
: R
ED
; B
LU :
BLU
E ;
WH
T : W
HIT
E ;
GR
N :
GR
EE
N ;
GR
Y : G
RAY
; Y
LW :
YE
LLO
W.
8. C
LAS
S 2
WIR
E
NO
TES
)
40
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ72TAYDAA1P PRINTED CIRCUIT BOARD (MAIN) R10T THERMISTOR (SUCTION)A2P PRINTED CIRCUIT BOARD (NOISE FILTER) R11T THERMISTOR (DEICER)A3P PRINTED CIRCUIT BOARD (INV) R12T THERMISTOR (COMP. SUCTION)A4P, A5P PRINTED CIRCUIT BOARD (FAN) R13T THERMISTOR (RECEIVER GAS PURGE)A6P PRINTED CIRCUIT BOARD (SUB) R14T THERMISTOR (M1C BODY)A7P PRINTED CIRCUIT BOARD (ABC I/P) R15T THERMISTOR (LEAK DETECTION)A8P PRINTED CIRCUIT BOARD (CURRENT LIMITING) R16T THERMISTOR (EVT)A9P PRINTED CIRCUIT BOARD (NOISE FILTER) R21T THERMISTOR (M1C DISCHARGE)A10P PRINTED CIRCUIT BOARD (OPEN PHASE PROTECTION) S1NPH PRESSURE SENSOR (HIGH)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) S1NPL PRESSURE SENSOR (LOW)C47, C48 CAPACITOR (A3P) S1PH PRESSURE SWITCH (HIGH)DS1, DS2 DIP SWITCH (A1P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)E1HC, E2HC CRANKCASE HEATER T1A CURRENT SENSORF1U FUSE (A1P, A6P) T1R TRANSFORMER (460 V / 230 V)F2U FUSE (A1P) V1R DIODE BRIDGE (A3P)F101U FUSE (A4P, A5P) V1R POWER MODULE (A4P, A5P)F401U, F403U FUSE (A2P) V2R POWER MODULE (A3P)F601U FUSE (A3P) X1A, X2A CONNECTOR (M1F)HAP PILOTLAMP (A1P, A3P~A6P) (SERVICE MONITOR-GREEN) X3A, X4A CONNECTOR (M2F)K1M MAGNETIC CONTACTOR (A3P) X5A CONNECTOR (CHECK THE RESIDUAL CHARGE)K1M MAGNETIC CONTACTOR (A8P) X7A, X8A CONNECTOR (T1R)K3R MAGNETIC RELAY (A3P) X9A, X11A CONNECTOR K3R MAGNETIC RELAY (Y1S) (A1P) X13A, X14A CONNECTOR (E1HC, E2HC)K4R MAGNETIC RELAY (Y2S) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K6R MAGNETIC RELAY (OPTION) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K7R MAGNETIC RELAY (E1HC, E2HC) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A7P)K8R MAGNETIC RELAY (Y7S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K9R MAGNETIC RELAY (Y4S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K11R MAGNETIC RELAY (Y3S) (A1P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)K12R MAGNETIC RELAY (Y5S) (A1P) Y4E ELECTRIC EXPANSION VALVE (INJECTION)K13R MAGNETIC RELAY (Y6S) (A1P) Y5E ELECTRIC EXPANSION VALVE (REFRIGERANT COOLING)L1R REACTOR Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)M1C MOTOR (COMPRESSOR) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)M1F, M2F MOTOR (FAN) Y1S SOLENOID VALVE (OS OIL RETURN 1)PS SWITCHING POWER SUPPLY (A1P, A3P, A6P) Y2S SOLENOID VALVE (HOT GAS BYPASS)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R1 RESISTOR (CURRENT LIMITING) (A8P) Y4S 4 WAY VALVE (HP/LP GAS)R24 RESISTOR (CURRENT SENSOR) (A4P, A5P) Y5S 4 WAY VALVE (HEAT EXC. LOWER)R313 RESISTOR (CURRENT SENSOR) (A3P) Y6S 4 WAY VALVE (HEAT EXC. UPPER)R865, R867 RESISTOR (A3P) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R1T THERMISTOR (AIR) Z1C, Z2C NOISE FILTER (FERRITE CORE)R3T THERMISTOR (RECEIVER INLET) ZF NOISE FILTER (A2P, A9P) (WITH SURGE ABSORBER)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) CONNECTOR FOR OPTIONAL ACCESSORIESR5T THERMISTOR (HEAT EXC. LIQUID LOWER) X37A CONNECTOR (POWER ADAPTER) (A1P)R6T THERMISTOR (SUBCOOL GAS) COOL/HEAT SELECTORR7T THERMISTOR (SUBCOOL LIQUID) S1S SELECTOR SWITCH (FAN/COOL·HEAT)R8T THERMISTOR (HEAT EXC. GAS UPPER) S2S SELECTOR SWITCH (COOL/HEAT)R9T THERMISTOR (HEAT EXC. GAS LOWER)
C: 2D112582D
41
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ96-120TAYDA
C: 2
D11
2583
D
1. T
HIS
WIR
ING
DIA
GR
AM
AP
PLI
ES
ON
LY T
O T
HE
OU
TDO
OR
UN
IT.
2.
: F
IELD
WIR
ING
,
: TE
RM
INA
L B
LOC
K,
: C
ON
NE
CTO
R,
: T
ER
MIN
AL,
: PR
OTE
CTI
VE
GR
OU
ND
(SC
RE
W),
:
NO
ISE
LES
S G
RO
UN
D.
3. W
HE
N U
SIN
G T
HE
OP
TIO
NA
L A
DA
PTE
R, R
EFE
R T
O T
HE
INS
TALL
ATIO
N M
AN
UA
L O
F TH
E O
PTI
ON
AL
AD
AP
TER
.4.
FO
R C
ON
NE
CTI
ON
WIR
ING
TO
IND
OO
R-O
UTD
OO
R T
RA
NS
MIS
SIO
N F
1·F2
, OU
TDO
OR
-OU
TDO
OR
TR
AN
SM
ISS
ION
F1·
F2,
OU
TDO
OR
-MU
LTI T
RA
NS
MIS
SIO
N Q
1·Q
2, R
EFE
R T
O T
HE
INS
TALL
ATIO
N M
AN
UA
L. 5
. HO
W T
O U
SE
BS
1~3
SW
ITC
H, R
EFE
R T
O “S
ER
VIC
E P
RE
CA
UTI
ON
S” L
AB
EL
ON
C
ON
TRO
L B
OX
CO
VE
R.
6. W
HE
N O
PE
RAT
ING
, DO
N'T
SH
OR
TCIR
CU
IT T
HE
PR
OTE
CTI
ON
DE
VIC
E (S
1PH
). 7
. CO
LOR
S B
LK :
BLA
CK
; R
ED
: R
ED
; B
LU :
BLU
E ;
WH
T : W
HIT
E ;
GR
N :
GR
EE
N ;
GR
Y : G
RAY
; Y
LW :
YE
LLO
W.
8. C
LAS
S 2
WIR
E
NO
TES
)
42
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ96-120TAYDAA1P PRINTED CIRCUIT BOARD (MAIN) R12T THERMISTOR (COMP. SUCTION)A2P PRINTED CIRCUIT BOARD (NOISE FILTER) R13T THERMISTOR (RECEIVER GAS PURGE)A3P PRINTED CIRCUIT BOARD (INV) R14T THERMISTOR (M1C BODY)A4P, A5P PRINTED CIRCUIT BOARD (FAN) R15T THERMISTOR (LEAK DETECTION)A6P PRINTED CIRCUIT BOARD (SUB) R16T THERMISTOR (EVT)A7P PRINTED CIRCUIT BOARD (ABC I/P) R21T THERMISTOR (M1C DISCHARGE)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) R71T THERMISTOR (POWER MODULE) (A3P) C48, C51 CAPACITOR (A3P) R72T THERMISTOR (DIODE) (A3P) C404 CAPACITOR (A2P) S1NPH PRESSURE SENSOR (HIGH)DS1, DS2 DIP SWITCH (A1P) S1NPL PRESSURE SENSOR (LOW)E1HC, E2HC CRANKCASE HEATER S1PH PRESSURE SWITCH (HIGH)F1U FUSE (A1P, A3P, A6P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)F2U FUSE (A1P) T1A CURRENT SENSORF101U FUSE (A4P, A5P) T1R TRANSFORMER (460 V / 230 V)F404U FUSE (A2P) V1D DIODE (CURRENT LIMITING) (A3P)F410U, F412U FUSE (A2P) V1R DIODE BRIDGEHAP PILOTLAMP (A1P, A3P~A6P) (SERVICE MONITOR-GREEN) V1R POWER MODULE (A4P, A5P)K1M MAGNETIC CONTACTOR V2R POWER MODULE (A3P)K3R MAGNETIC RELAY (A3P) X1A, X2A CONNECTOR (M1F)K3R MAGNETIC RELAY (Y1S) (A1P) X3A, X4A CONNECTOR (M2F)K4R MAGNETIC RELAY (Y2S) (A1P) X5A CONNECTOR (CHECK THE RESIDUAL CHARGE)K6R MAGNETIC RELAY (OPTION) (A1P) X6A, X7A CONNECTOR (T1R)K7R MAGNETIC RELAY (E1HC, E2HC) (A1P) X13A, X14A CONNECTOR (E1HC, E2HC)K8R MAGNETIC RELAY (Y7S) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K9R MAGNETIC RELAY (Y4S) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K11R MAGNETIC RELAY (Y3S) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A7P)K12R MAGNETIC RELAY (Y5S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K13R MAGNETIC RELAY (Y6S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K84R MAGNETIC RELAY (A3P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)L1R REACTOR Y4E ELECTRIC EXPANSION VALVE (INJECTION)M1C MOTOR (COMPRESSOR) Y5E ELECTRIC EXPANSION VALVE (REFRIGERANT COOLING)M1F, M2F MOTOR (FAN) Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)PS SWITCHING POWER SUPPLY (A1P, A3P, A6P) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y1S SOLENOID VALVE (OS OIL RETURN 1)R1 RESISTOR (CURRENT LIMITING) (A3P) Y2S SOLENOID VALVE (HOT GAS BYPASS)R24 RESISTOR (CURRENT SENSOR) (A4P, A5P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R131, R133 RESISTOR (A3P) Y4S 4 WAY VALVE (HP/LP GAS)R401 RESISTOR (CURRENT SENSOR) (A3P) Y5S 4 WAY VALVE (HEAT EXC. LOWER)R1T THERMISTOR (AIR) Y6S 4 WAY VALVE (HEAT EXC. UPPER)R3T THERMISTOR (RECEIVER INLET) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) Z1C~Z3C NOISE FILTER (FERRITE CORE)R5T THERMISTOR (HEAT EXC. LIQUID LOWER) ZF NOISE FILTER (A2P) (WITH SURGE ABSORBER)R6T THERMISTOR (SUBCOOL GAS) CONNECTOR FOR OPTIONAL ACCESSORIESR7T THERMISTOR (SUBCOOL LIQUID) X37A CONNECTOR (POWER ADAPTER) (A1P)R8T THERMISTOR (HEAT EXC. GAS UPPER) COOL/HEAT SELECTORR9T THERMISTOR (HEAT EXC. GAS LOWER) S1S SELECTOR SWITCH (FAN/COOL·HEAT)R10T THERMISTOR (SUCTION) S2S SELECTOR SWITCH (COOL/HEAT)R11T THERMISTOR (DEICER)
C: 2D112583D
43
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ72-120TAYCA
C: 2
D11
2579
C
1. T
HIS
WIR
ING
DIA
GR
AM
AP
PLI
ES
ON
LY T
O T
HE
OU
TDO
OR
UN
IT.
2.
: F
IELD
WIR
ING
,
: TE
RM
INA
L B
LOC
K,
: C
ON
NE
CTO
R,
: T
ER
MIN
AL,
: PR
OTE
CTI
VE
GR
OU
ND
(SC
RE
W),
:
NO
ISE
LES
S G
RO
UN
D.
3. W
HE
N U
SIN
G T
HE
OP
TIO
NA
L A
DA
PTE
R, R
EFE
R T
O T
HE
INS
TALL
ATIO
N M
AN
UA
L O
F TH
E O
PTI
ON
AL
AD
AP
TER
.4.
FO
R C
ON
NE
CTI
ON
WIR
ING
TO
IND
OO
R-O
UTD
OO
R T
RA
NS
MIS
SIO
N F
1·F2
, OU
TDO
OR
-OU
TDO
OR
TR
AN
SM
ISS
ION
F1·
F2,
OU
TDO
OR
-MU
LTI T
RA
NS
MIS
SIO
N Q
1·Q
2, R
EFE
R T
O T
HE
INS
TALL
ATIO
N M
AN
UA
L. 5
. HO
W T
O U
SE
BS
1~3
SW
ITC
H, R
EFE
R T
O “S
ER
VIC
E P
RE
CA
UTI
ON
S” L
AB
EL
ON
C
ON
TRO
L B
OX
CO
VE
R.
6. W
HE
N O
PE
RAT
ING
, DO
N'T
SH
OR
TCIR
CU
IT T
HE
PR
OTE
CTI
ON
DE
VIC
E (S
1PH
). 7
. CO
LOR
S B
LK :
BLA
CK
; R
ED
: R
ED
; B
LU :
BLU
E ;
WH
T : W
HIT
E ;
GR
N :
GR
EE
N ;
GR
Y : G
RAY
; Y
LW :
YE
LLO
W.
8. C
LAS
S 2
WIR
E
NO
TES
)
44
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ72-120TAYCAA1P PRINTED CIRCUIT BOARD (MAIN) R12T THERMISTOR (COMP. SUCTION)A2P, A3P PRINTED CIRCUIT BOARD (NOISE FILTER) R13T THERMISTOR (RECEIVER GAS PURGE)A4P PRINTED CIRCUIT BOARD (INV) R14T THERMISTOR (M1C BODY)A5P, A6P PRINTED CIRCUIT BOARD (FAN) R15T THERMISTOR (LEAK DETECTION)A7P PRINTED CIRCUIT BOARD (SUB) R16T THERMISTOR (EVT)A8P PRINTED CIRCUIT BOARD (ABC I/P) R21T THERMISTOR (M1C DISCHARGE)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) S1NPH PRESSURE SENSOR (HIGH)C1 CAPACITOR (A4P) S1NPL PRESSURE SENSOR (LOW)DS1, DS2 DIP SWITCH (A1P) S1PH PRESSURE SWITCH (HIGH)E1HC, E2HC CRANKCASE HEATER SEG1~SEG3 7-SEGMENT DISPLAY (A1P)F1U FUSE (A1P, A4P, A7P) T1A CURRENT SENSORF2U FUSE (A1P) T1R TRANSFORMER (575 V / 220 V)F101U FUSE (A2P, A5P, A6P) V1D DIODE (A4P)
F100U, F104U, F105U FUSE (A2P)
V1R POWER MODULE (A4P)V1R POWER MODULE (A5P, A6P)
F1UT THERMAL FUSE (A4P) V1T TRANSISTOR (A4P)HAP PILOTLAMP (A1P, A4P~A7P) (SERVICE MONITOR-GREEN) X1A, X2A CONNECTOR (M1F, M2F)K1M MAGNETIC CONTACTOR (A4P) X5A CONNECTOR (CHECK THE RESIDUAL CHARGE)K3R MAGNETIC RELAY (Y1S) (A1P) X3A, X4A CONNECTOR (T1R)K4R MAGNETIC RELAY (Y2S) (A1P) X13A, X14A CONNECTOR (E1HC, E2HC)K6R MAGNETIC RELAY (OPTION) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K7R MAGNETIC RELAY (E1HC, E2HC) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K8R MAGNETIC RELAY (Y7S) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A8P)K9R MAGNETIC RELAY (Y4S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K11R MAGNETIC RELAY (Y3S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K12R MAGNETIC RELAY (Y5S) (A1P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)K13R MAGNETIC RELAY (Y6S) (A1P) Y4E ELECTRIC EXPANSION VALVE (INJECTION)L1R REACTOR Y5E ELECTRIC EXPANSION VALVE (REFRIGERANT COOLING)M1C MOTOR (COMPRESSOR) Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)M1F, M2F MOTOR (FAN) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)PS SWITCHING POWER SUPPLY (A1P, A4P, A7P) Y1S SOLENOID VALVE (OS OIL RETURN 1)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y2S SOLENOID VALVE (HOT GAS BYPASS)R1 RESISTOR (CURRENT LIMITING) (A4P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R2 RESISTOR (CURRENT SENSOR) (A4P, A5P, A6P) Y4S 4 WAY VALVE (HP/LP GAS)R1T THERMISTOR (AIR) Y5S 4 WAY VALVE (HEAT EXC. LOWER)R3T THERMISTOR (RECEIVER INLET) Y6S 4 WAY VALVE (HEAT EXC. UPPER)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R5T THERMISTOR (HEAT EXC. LIQUID LOWER) Z1C~Z3C NOISE FILTER (FERRITE CORE)R6T THERMISTOR (SUBCOOL GAS) ZF NOISE FILTER (A2P, A3P) (WITH SURGE ABSORBER)R7T THERMISTOR (SUBCOOL LIQUID) CONNECTOR FOR OPTIONAL ACCESSORIESR8T THERMISTOR (HEAT EXC. GAS UPPER) X37A CONNECTOR (POWER ADAPTER) (A1P)R9T THERMISTOR (HEAT EXC. GAS LOWER) COOL/HEAT SELECTORR10T THERMISTOR (SUCTION) S1S SELECTOR SWITCH (FAN/COOL·HEAT)R11T THERMISTOR (DEICER) S2S SELECTOR SWITCH (COOL/HEAT)
C: 2D112579D
45
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
16. Field Wiring
RELQ72-120TATJA / TAYDA / TAYCA
C: 3
D10
7344
A
Not
es 1
) All
wiri
ng, c
ompo
nent
s an
d m
ater
ials
to b
e pr
ocur
edon
the
site
mus
t com
ply
with
the
appl
icab
le lo
cal a
nd n
atio
nal c
odes
.2)
Use
cop
per c
ondu
ctor
s on
ly.3)
As
for d
etai
ls, s
ee w
iring
dia
gram
.4)
Fie
ld w
iring
dia
gram
is to
be
used
as
a gu
idel
ine
only.
Wiri
ng s
houl
d co
mpl
y w
ith a
pplic
able
loca
l and
nat
iona
l cod
es.
5) U
nit s
hall
be g
roun
ded
in c
ompl
ianc
e w
ith th
e ap
plic
able
loca
l and
nat
iona
l cod
es.
6) W
iring
sho
wn
are
gene
ral p
oint
s-of
-con
nect
ion
guid
es o
nly
and
are
not i
nten
ded
for o
r to
incl
ude
all d
etai
ls fo
r a s
peci
fic in
stal
latio
n.7)
Be
sure
to in
stal
l the
sw
itch
and
the
fuse
/bre
aker
to th
e po
wer
line
of e
ach
piec
e of
equ
ipm
ent.
8) In
stal
l the
mai
n sw
itch
that
can
inte
rrup
t all
the
pow
er s
ourc
es in
an
inte
grat
ed
man
ner b
ecau
se th
is s
yste
m c
onsi
sts
of th
e eq
uipm
ent u
tiliz
ing
the
mul
tiple
po
wer
sou
rces
.9)
If th
ere
exis
ts th
e po
ssib
ility
of r
ever
sed
phas
e, lo
st p
hase
, mom
enta
ry b
lack
out
or th
e po
wer
goe
s on
and
off
whi
le th
e pr
oduc
t is
oper
atin
g, a
ttach
a re
vers
ed
phas
e pr
otec
tion
circ
uit l
ocal
ly.R
unni
ng th
e pr
oduc
t in
reve
rsed
pha
se m
ay b
reak
the
com
pres
sor a
nd o
ther
pa
rts.
46
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ144-240TATJA / TAYDA / TAYCA
C: 3
D10
7345
A
Not
es 1
) All
wiri
ng, c
ompo
nent
s an
d m
ater
ials
to b
e pr
ocur
edon
the
site
mus
t com
ply
with
the
appl
icab
le lo
cal a
nd n
atio
nal c
odes
.2)
Use
cop
per c
ondu
ctor
s on
ly.3)
As
for d
etai
ls, s
ee w
iring
dia
gram
.4)
Fie
ld w
iring
dia
gram
is to
be
used
as
a gu
idel
ine
only.
Wiri
ng s
houl
d co
mpl
y w
ith a
pplic
able
loca
l and
nat
iona
l cod
es.
5) U
nit s
hall
be g
roun
ded
in c
ompl
ianc
e w
ith th
e ap
plic
able
loca
l and
nat
iona
l cod
es.
6) W
iring
sho
wn
are
gene
ral p
oint
s-of
-con
nect
ion
guid
es o
nly
and
are
not i
nten
ded
for o
r to
incl
ude
all d
etai
ls fo
r a s
peci
fic in
stal
latio
n.7)
Be
sure
to in
stal
l the
sw
itch
and
the
fuse
/bre
aker
to th
e po
wer
line
of e
ach
piec
e of
equ
ipm
ent.
8) In
stal
l the
mai
n sw
itch
that
can
inte
rrup
t all
the
pow
er s
ourc
es in
an
inte
grat
ed
man
ner b
ecau
se th
is s
yste
m c
onsi
sts
of th
e eq
uipm
ent u
tiliz
ing
the
mul
tiple
po
wer
sou
rces
.9)
If th
ere
exis
ts th
e po
ssib
ility
of r
ever
sed
phas
e, lo
st p
hase
, mom
enta
ry b
lack
out
or th
e po
wer
goe
s on
and
off
whi
le th
e pr
oduc
t is
oper
atin
g, a
ttach
a re
vers
ed
phas
e pr
otec
tion
circ
uit l
ocal
ly.R
unni
ng th
e pr
oduc
t in
reve
rsed
pha
se m
ay b
reak
the
com
pres
sor a
nd o
ther
pa
rts.
47
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
17. Electrical Characteristics17.1 RELQ72-120TATJA
Model nameUnits Power supply Comp. OFM
SCCRHz Volts Min. Max. MCA MOP RLA kW FLA
RELQ72TATJA 60 208/230 187 253 60.8 70 20.7 0.8 × 2 2.9 × 2
SCCR kA rms, Symmetrical
@600 V MAX: 5
RELQ96TATJA 60 208/230 187 253 76.5 80 36.8 0.8 × 2 2.9 × 2RELQ120TATJA 60 208/230 187 253 83.4 90 39.3 0.8 × 2 2.9 × 2
RELQ144TATJARELQ72TATJA
60 208/230 187 253 60.8 + 60.8 70 + 70 21.6 +
21.6 (0.8 × 2) × 2 (2.9 × 2) × 2RELQ72TATJA
RELQ192TATJARELQ96TATJA
60 208/230 187 253 76.5 + 76.5 80 + 80 38.1 +
38.1 (0.8 × 2) × 2 (2.9 × 2) × 2RELQ96TATJA
RELQ240TATJARELQ120TATJA
60 208/230 187 253 83.4 + 83.4 90 + 90 40.4 +
40.4 (0.8 × 2) × 2 (2.9 × 2) × 2RELQ120TATJA
Symbols:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protector (A)RLA: Rated Load Amps. (A)OFM: Outdoor Fan MotorkW: Rated Motor Output (kW)FLA: Full Load Amps. (A)SCCR: Short-Circuit Current Rating
Notes:1. RLA is based on the following conditions. Indoortemp.80°FDB(26.7°CDB)/67°FWB(19.4°CWB) Outdoortemp.95°FDB(35.0°CDB)
2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.
3. The maximum percent unbalance of phase voltage shall be 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.
C: 4D120034
48
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
17.2 RELQ72-120TAYDA
Model nameUnits Power supply Comp. OFM
SCCRHz Volts Min. Max. MCA MOP RLA kW FLA
RELQ72TAYDA 60 460 416 508 28.1 35 9.4 0.6 × 2 1.0 × 2
SCCR kA rms, Symmetrical
@600 V MAX: 5
RELQ96TAYDA 60 460 416 508 39.8 45 16.6 0.6 × 2 1.0 × 2RELQ120TAYDA 60 460 416 508 43.4 50 17.8 0.6 × 2 1.0 × 2
RELQ144TAYDARELQ72TAYDA
60 460 416 508 28.1 + 28.1 35 + 35 9.8 +
9.8 (0.6 × 2) × 2 (1.0 × 2) × 2RELQ72TAYDA
RELQ192TAYDARELQ96TAYDA
60 460 416 508 39.8 + 39.8 45 + 45 17.3 +
17.3 (0.6 × 2) × 2 (1.0 × 2) × 2RELQ96TAYDA
RELQ240TAYDARELQ120TAYDA
60 460 416 508 43.4 + 43.4 50 + 50 18.3 +
18.3 (0.6 × 2) × 2 (1.0 × 2) × 2RELQ120TAYDA
Symbols:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protector (A)RLA: Rated Load Amps. (A)OFM: Outdoor Fan MotorkW: Rated Motor Output (kW)FLA: Full Load Amps. (A)SCCR: Short-Circuit Current Rating
Notes:1. RLA is based on the following conditions. Indoortemp.80°FDB(26.7°CDB)/67°FWB(19.4°CWB) Outdoortemp.95°FDB(35.0°CDB)
2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.
3. The maximum percent unbalance of phase voltage shall be 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.
C: 4D120038
49
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
17.3 RELQ72-120TAYCA
Model nameUnits Power supply Comp. OFM
SCCRHz Volts Min. Max. MCA MOP RLA kW FLA
RELQ72TAYCA 60 575 518 632 21.6 25 7.5 0.7 × 2 1.0 × 2
SCCR kA rms, Symmetrical
@600 V MAX: 5
RELQ96TAYCA 60 575 518 632 28.5 35 13.3 0.7 × 2 1.0 × 2RELQ120TAYCA 60 575 518 632 31.2 40 14.2 0.7 × 2 1.0 × 2
RELQ144TAYCARELQ72TAYCA
60 575 518 632 21.6 + 21.6 25 + 25 7.8 +
7.8 (0.7 × 2) × 2 (1.0 × 2) × 2RELQ72TAYCA
RELQ192TAYCARELQ96TAYCA
60 575 518 632 28.5 + 28.5 35 + 35 13.8 +
13.8 (0.7 × 2) × 2 (1.0 × 2) × 2RELQ96TAYCA
RELQ240TAYCARELQ120TAYCA
60 575 518 632 31.2 + 31.2 40 + 40 14.6 +
14.6 (0.7 × 2) × 2 (1.0 × 2) × 2RELQ120TAYCA
Symbols:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protector (A)RLA: Rated Load Amps. (A)OFM: Outdoor Fan MotorkW: Rated Motor Output (kW)FLA: Full Load Amps. (A)SCCR: Short-Circuit Current Rating
Notes:1. RLA is based on the following conditions. Indoortemp.80°FDB(26.7°CDB)/67°FWB(19.4°CWB) Outdoortemp.95°FDB(35.0°CDB)
2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.
3. The maximum percent unbalance of phase voltage shall be 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.
C: 4D120041
50
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
18. Operation Limits
RELQ72-240TATJA / TAYDA / TAYCA
3D107374
51
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
19. Low Ambient Cooling Enhancement
RELQ72-240TATJA / TAYDA / TAYCA
RELQ-T series include a feature for Low Ambient Cooling. The function enhances RELQ-T series as follows:
• Allowsoperationto−4°FDB(−20°CDB)ambienttemperatureincoolingmode.(Normallimitis23°FDB(−5°CDB).)• Operationbelow23°FDB(−5°CDB)requirestheadditionofwindcoversontotheoutdoorunit.*
Application Rules: • Total connection index of each system is limited to 50-130% when height difference is 0-194 ft. (0-50 m), 80-130% when 194-
295 ft. (50-90 m).• All units on the system must be connected to a Branch Selector Box, Low ambient cooling is only available on indoor unit
connected to a single branch selector box. Single and Multi-port Branch Selector Boxes may be combined on one system but all indoor units connected to a multi branch selector box will operate as standard without the low ambient cooling function.
• Functionisengagedbyafieldsettingontheoutdoorunit(toenableLowAmbientCooling)andadipswitchsettingisnecessaryonthe Single Branch Selector Boxes BSQ-T series serving the indoor units NOT subject to Low Ambient Cooling requirements.
• Duringoperationbelow23°FDB(−5°CDB),theavailablecoolingcapacitydecreasesasfollows: 14°FDB(−10°CDB)-Reducesto80%ofnominal. 5°FDB(−15°CDB)-Reducesto65%ofnominal. −4°FDB(−20°CDB)-Reducesto60%ofnominal.(OnlyapplicabletoSingle-portBranchSelectorBoxes)
• The operating sound level of the Single Branch Selector Boxes BSQ-T series could increase 3 dB(A) higher than maximum while the system is operating in the Low Ambient Cooling mode. It is recommended to locate units away from zones sensitive to sound levels.
• Allowable height difference between outdoor and indoor units (when outdoor unit is below) is limited to 130 ft. (40 m). (Normal limit is 195 ft. (60 m).) * Contact your local Daikin representative for wind cover specification requirements and part numbers.
52
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
20. Sound Levels (Reference Data)
RELQ72TATJA / TAYDA / TAYCA
4D107376A
53
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ96TATJA / TAYDA / TAYCA
4D107377A
54
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
RELQ120TATJA / TAYDA / TAYCA
4D107378A
55
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
21. Accessories21.1 Optional AccessoriesRELQ120TATJA / TAYDA / TAYCA
Optional accessories
RELQ72TATJARELQ96TATJARELQ72TAYDARELQ96TAYDARELQ72TAYCARELQ96TAYCA
RELQ120TATJARELQ120TAYDARELQ120TAYCA
RELQ144TATJARELQ192TATJARELQ240TATJARELQ144TAYDARELQ192TAYDARELQ240TAYDARELQ144TAYCARELQ192TAYCARELQ240TAYCA
Distributive piping
REFNET header
KHRP25M33H9, KHRP25M33HA (Max.8 branch)
KHRP25M33H9, KHRP25M33HA (Max.8 branch)
KHRP25M72H9, KHRP25M72HA (Max.8 branch)
KHRP25M33H9, KHRP25M33HA (Max.8 branch)
KHRP25M72H9, KHRP25M72HA (Max.8 branch)
KHRP25M73HU9, KHRP25M73HUA (Max.8 branch)
REFNET joint
KHRP25A22T9, KHRP25A22TA KHRP25A33T9, KHRP25A33TA
KHRP25A22T9, KHRP25A22TA KHRP25A33T9, KHRP25A33TA
KHRP25M72TU9, KHRP25M72TUA
KHRP25A22T9, KHRP25A22TA KHRP25A33T9, KHRP25A33TA
KHRP25M72TU9, KHRP25M72TUA KHRP25M73TU9, KHRP25M73TUA
Outdoor unit multi connection piping kit — — BHFP26P100U, BHFP26P100UA
C: 3D091328H
56
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
22. Selection Procedure22.1 Selection Procedure22.1.1 Flowchart
Provisionally select outdoor unit type and size based on limitation of connection ratio
Correct for cooling & heating capacity of the outdoor unit by the following items
VRV system selection is complete.
Confirm that the number of indoor units connected to the outdoor unit is within limitation.
Corrected capacity of the outdoor unit ≥ Required total heat load to the outdoor unit
2) Use the system peak load1) Use the sum of the peak load of each room
Define required total heat load to outdoor unit
Indoor unit capacity corrected for indoor air temperature (WB) ≥ Required heat load × Safety factor for the indoor units
Yes
No
-Piping length, level difference-Piping heat loss-Safety factor for the outdoor unit-Defrost (only for heating capacity)
-Outdoor air temperature-Indoor air temperature-Connection ratio
Given conditions:· Design temperature and humidity (indoor & outdoor)· Required heat load of each room· System peak load (if necessary)· Piping length, level difference· Specifications of indoor units (type and number)
Define safety factor for the indoor units and outdoor unit
[1] Given conditions
[2] Selection of indoor units
[3] Selection of outdoor unit
57
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
22.1.2 Selection ExampleThe following is a selection example based on total heat load for cooling.
Room ARoom H Room G
Room F
Room B Room ERoom C Room D
Floor plan
[1] Given conditions-Design conditionsIndoorairtemperature:67°FWB/80°FDB,Outdoorairtemperature:93°FDB
-Determine peak load of each room (and system peak load if necessary)
-Required heat load of each roomTime Room A Room B Room C Room D Room E Room F Room G Room H Total9:00 16.4 16.5 10.4 10.4 30.9 30.8 10.0 10.0 135.4
12:00 22.4 24.4 17.3 17.3 25.1 23.2 13.7 13.7 157.114:00 30.7 32.2 16.8 16.8 24.9 23.4 14.1 14.1 173.016:00 36.1 36.4 13.3 13.3 21.5 21.2 13.0 13.0 167.8
Total heat load (MBH)
From the above heat load calculation, the maximum heat load for the system (system peak load) is 173.0 MBH.
Level difference120 ft.
Select VRV indoor units FXMQ-PB series for each room.
Equivalent pipe length 200 ft.
-Safety factorIn this example, safety factor is not used. (i. e., safety factor = 1.0)
[2] Selection of indoor unitsCalculate total heat capacity of indoor units corrected for indoor air temperature.In case design temperature of the indoor air falls between temperatures listed in the table, calculate the capacity by interpolation.The corrected total heat capacity of indoor units shall satisfy the maximum heat load of each room.
58
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
Capacity table of indoor unitCooling Capacity
Model Capacity indication
Indoorairtemp.°FWB(Te:43°F(6°C))61 64 67 70 72 75
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH
FXMQ07PBVJU 07 5.7 5.5 6.4 5.9 7.2 6.1 7.3 6.5 7.4 5.8 7.6 5.8 FXMQ09PBVJU 09 7.5 6.9 8.5 7.3 9.5 7.8 9.7 8.1 9.8 7.1 10.0 7.2FXMQ12PBVJU 12 9.5 8.5 10.7 9.1 12.0 9.7 12.2 10.0 12.4 9.2 12.6 9.2FXMQ15PBVJU 15 11.2 10.2 12.7 10.7 14.2 11.4 14.5 11.6 14.7 11.5 14.9 9.6 FXMQ18PBVJU 18 14.2 13.9 16.1 14.7 18.0 15.6 18.4 16.1 18.6 14.6 18.9 12.1FXMQ24PBVJU 24 19.0 16.5 21.5 17.7 24.0 18.8 24.5 19.2 24.8 17.9 25.3 20.1FXMQ30PBVJU 30 23.7 20.8 26.8 22.3 30.0 23.8 30.6 24.4 31.0 22.5 31.6 22.5FXMQ36PBVJU 36 28.4 25.0 32.2 26.9 36.0 28.8 36.7 30.0 37.2 27.7 37.9 27.7FXMQ48PBVJU 48 37.9 31.3 43.0 33.6 48.0 35.8 49.0 36.9 49.6 34.7 50.5 33.2FXMQ54PBVJU 54 42.6 35.2 48.3 37.8 54.0 40.3 55.1 41.5 55.8 39.0 56.8 37.4
TC : Total capacity: MBHSHC : Sensible heat capacity: MBH
Selection results of indoor units
Room A Room B Room C Room D Room E Room F Room G Room HMax. heat load (MBH) 36.1 36.4 17.3 17.3 30.9 30.8 14.1 14.1
Selected IDU FXMQ48PBVJU FXMQ48PBVJU FXMQ18PBVJU FXMQ18PBVJU FXMQ36PBVJU FXMQ36PBVJU FXMQ15PBVJU FXMQ15PBVJUCorrected TC (MBH) 48.0 48.0 18.0 18.0 36.0 36.0 14.2 14.2
* In case of selection based on Total Heat Load and Sensible Heat Load, select indoor units which satisfy not only the Total Heat Load but also the Sensible Heat Load of each room. The sensible heat capacity of indoor units is to be corrected for indoor air temperature. If the design temperature of indoor air falls between temperatures listed in table, calculate sensible heat capacity by using the bypass factor calculated by interpolation for each indoor air temperature.
[3] Selection of outdoor unit[3] –1 Define the required total heat load from the indoor units to the outdoor unitDefinetherequiredtotalheatload(A)basedon(1)thesumofthepeakloadofeachroomor(2)thesystempeakload.In this example, select an outdoor unit by (2).Therefore, (A) = 173.0 MBH
59
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
[3] –2 Provisionally select outdoor unit(1) Calculate CI (Capacity Index) of the selected indoor units.
CI of VRV indoor units CI of FXMQ15PBVJU = 15 CI of FXMQ18PBVJU = 18 CI of FXMQ36PBVJU = 36 CI of FXMQ48PBVJU = 48
Capacity Range 0.5 ton 0.6 ton 0.8 ton 1 ton 1.25 ton 1.5 ton 2 ton 2.5 ton 3 ton 3.5 ton 4 ton 4.5 ton 5 ton 6 ton 8 ton Power Supply, StandardCapacity Index 5.8 7.5 9.5 12 15 18 20 24 30 36 42 48 54 60 72 96
Ceiling Mounted Duct Type (Middle and High Static Pressure)
FXMQ — 07PB 09PB 12PB 15PB 18PB — 24PB 30PB 36PB — 48PB 54PB — — — VJU
Calculate the total CI of the indoor units.Total CI = 15 × 2 + 18 × 2 + 36 × 2 + 48 × 2 = 234
(2) Provisionally select an outdoor unit based on the total CI of the indoor units
The connection ratio of RELQ-TA shall be between 70% and 130%.As the total CI of the indoor units is 234, outdoor units from 16 ton to 20 ton are connectable.Start from 16 ton which is the smallest outdoor unit.
(3) Confirm that the number of the connected indoor units is within the limitation.
The number of the connected indoor units = 8
The max. number of connectable indoor units of 16 ton outdoor unit = 33
60
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
[3] –3 Calculate the corrected capacity of the outdoor unit.-Calculate the connection ratio of the system.Total CI = 234, CI of RELQ192TAYDA = 192Connection ratio = 234 / 192 = 122%
- Using the capacity table of the outdoor unit, calculate the capacity (B) corrected for outdoor air temperature, indoor air temperature, and connection ratio.
* �In case the outdoor air temperature, the indoor air temperature, or the connection ratio falls between temperatures listed in the table, calculate the capacity by interpolation.
RELQ192TATJA / TAYDA / TAYCA Cooling Capacity for Standard Condition (Te: 43°F)
120% 122% 130%
201 (B) 205
Connection ratio
Cooling capacity
(B)=201+(205–201)×(122–120)/(130–120)=201.8
61
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
-Confirmcapacitycorrectionfactorbypipinglengthandleveldifference(K1)
(K1) = 0.924
0.924
-Calculate capacity correction factor by piping heat loss (K2)(K2)=1+(heatlossfactorperfeetofpiping×(equivalentpipinglength–25ft.))/100
Incoolingmode,heatlossfactorperfeetat93°Fiscalculatedasbelow.(R) Heat loss factor per feet = 0.072*2 + (0.098*1–0.072*2) × (93*3–86*4) / (95*5–86*4) = 0.0922
Using “Equivalent piping length = 200 ft” and “Heat loss factor per feet = 0.0922”, (K2)=1+(0.0922×(200–25))/100=1.161
Cooling Ambient temperature
Heat loss factor per feet of piping (%)
Heating Ambient temperature
Heat loss factor per feet of piping (%)
5°F 14°F 23°F 32°F 41°F 50°F 59°F 68°F0.328 0.305 0.282 0.256 0.233 0.210 0.187 0.161
41°F
0.000
50°F
0.000
59°F
0.013
68°F
0.030
77°F
0.046
86°F*4
0.072*2
93°F*3
(R)
95°F*5
0.098*1
104°F
0.125
-Calculate the corrected capacity of RELQ192TAYCA (C) by using (K1) and (K2).Corrected capacity of RELQ192TAYCA (C) = (B) × (K1) / (K2) (add defrost correction factor for heating capacity)Therefore (C) = 201.8 × 0.924 / 1.161 = 160.6 MBH
If the corrected capacity (C) is the same or greater than the required total heat load (A), selection is complete.If(C)<(A),returntoProcedure[3]–2andprovisionallyselectalargeroutdoorunit.In this example, 160.6 MBH (C) < 173.0 MBH (A), so need to select a larger outdoor unit.
The capacity of RELQ240TAYCA at the same condition is 186.3 MBH, which is more than the heat load (A): 173.0 MBH.So the selection is complete.
62
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
23. Caution Label23.1 RELQ72-240TATJA / TAYDA / TAYCA
3P558142-1B
63
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
1P385984-1A
64
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
1P385984-1A
65
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
1P385984-1A
66
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
1P385984-1A
67
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
1P385984-1A
68
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
1P385984-1A
69
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
3P385987-1A
70
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
3P385987-1A
71
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
24. Caution for Refrigerant Leaks24.1 Introduction
The installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available.
The VRV System, like other air conditioning systems, uses R410A as refrigerant. R410A itself is an entirely safe non-toxic, non-combustible refrigerant.Neverthelesscaremustbetakentoensurethatairconditioningfacilitiesareinstalledinaroomwhichissufficientlylarge.Thisassuresthat the maximum concentration level of refrigerant gas is not exceeded, in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards.
Maximum concentration levelThe maximum charge of refrigerant and the calculation of the maximum concentration of refrigerant is directly related to the humanly occupied space in to which it could leak.The unit of measurement of the concentration is lbs./ft.3 (kg/m3) (the weight in Ibs. (kg) of the refrigerant gas in 1 ft.3 (1 m3) volume of the occupied space).Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required.
Direction of therefrigerant flow
Room where refrigerant leak has occurred(outflow of all the refrigerant from the system)
Pay special attention to places, such as basements, etc. where refrigerant could stay, since refrigerant is heavier than air.
72
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
24.2 Procedure for Checking Maximum Concentration
Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply.Step1: Calculate the amount of refrigerant (lbs. (kg)) charged to each system separately.
Amount of refrigerant in a single unitsystem (amount of refrigerant withwhich the system is charged beforeleaving the factory)
+
Additional charging amount (amountof refrigerant added locally inaccordance with the length or diameterof the refrigerant piping)
= Total amount of refrigerant (lbs. (kg))in the system
Note:Where a single refrigerant facility is divided into 2 entirely independent refrigerant systems then use the amount of refrigerant with which each separate system is charged.
Step 2: Calculate the smallest room volume (ft.3(m3)) In case like the following, calculate the volume of (a), (b) as a single room or as the smallest room. (a) Where there are no smaller room divisions.
(b)Wherethereisaroomdivisionbutthereisanopeningbetweentheroomssufficientlylargetopermitafreeflowofairbackandforth.
Opening betweenrooms
Partition
(Where there is an opening without a door or where there are openings above and below the door which are each equivalent in size to 0.15% ormoreofthefloorarea.)
(c) Where there is a gas leak detection alarm device linked to a mechanical ventilator in the smallest room then the next smallest room will become the measurement target.
73
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
Step 3: Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above.
Total volume of refrigerant in therefrigerant system
≤ Maximum concentration level (lbs./ft.3(kg/m3))Size (ft.3(m3)) of the smallest room in whichthere is an indoor unit installed
If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so until the result falls short of the maximum concentration.
Step 4: Dealing with the situations where the result exceeds the maximum concentration level. Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise
the system. Please consult your Daikin supplier.
74
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
25. Safety Devices Setting25.1 FXFQ-T
Model FXFQ07TVJU FXFQ09TVJU FXFQ12TVJU FXFQ15TVJU FXFQ18TVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F(°C) – – – – –Fan motor thermal protector °F(°C) – – – – –Fan motor thermal fuse °F(°C) – – – – –
Model FXFQ24TVJU FXFQ30TVJU FXFQ36TVJU FXFQ48TVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F(°C) – – – –Fan motor thermal protector °F(°C) – – – –Fan motor thermal fuse °F(°C) – – – –
C: 3D086932C
25.2 FXZQ-TA
Model FXZQ05TAVJU FXZQ07TAVJU FXZQ09TAVJU FXZQ12TAVJU FXZQ15TAVJU FXZQ18TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AFan motor thermal fuse °F(°C) – – – – – –Fan motor thermal protector °F(°C) – – – – – –Drain pump fuse °F(°C) – – – – – –
C: 4D110603
25.3 FXUQ-P
Model FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F(°C) – – – –Fan motor thermal protector °F(°C) – – – –Fan motor thermal fuse °F(°C) – – – –
C: 3D090213
25.4 FXEQ-P
Model FXEQ07PVJU FXEQ09PVJU FXEQ12PVJU FXEQ15PVJU FXEQ18PVJU FXEQ24PVJUPrinted circuit board fuse A1P 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Fan motor thermal protector °F(°C)OFF: 223±9
(106±5)ON: 205±27
(96±15)
OFF: 223±9(106±5)
ON: 205±27(96±15)
OFF: 223±9(106±5)
ON: 205±27(96±15)
OFF: 223±9(106±5)
ON: 205±27(96±15)
OFF: 223±9 (106±5)
ON: 205±27(96±15)
OFF: 223±9(106±5)
ON: 205±27(96±15)
C: 4D098709
75
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
25.5 FXDQ-M
Model FXDQ07MVJU FXDQ09MVJU FXDQ12MVJU FXDQ18MVJU FXDQ24MVJUPrinted circuit board fuse A1P 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A
Fan motor thermal protector °F OFF: 266±9ON: 181±27
OFF: 266±9ON: 181±27
OFF: 266±9ON: 181±27
OFF: 266±9ON: 181±27
OFF: 266±9ON: 181±27
C: 3D051758
25.6 FXSQ-TA
Model FXSQ05TAVJU FXSQ07TAVJU FXSQ09TAVJU FXSQ12TAVJU FXSQ15TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) — — — — —
Model FXSQ18TAVJU FXSQ24TAVJU FXSQ30TAVJU FXSQ36TAVJU FXSQ48TAVJU FXSQ54TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) — — — — — —
3D112398
25.7 FXMQ-PB
Model FXMQ07PBVJU FXMQ09PBVJU FXMQ12PBVJU FXMQ15PBVJU FXMQ18PBVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) 293 (145) 293 (145) 293 (145) 293 (145) 293 (145)
Model FXMQ24PBVJU FXMQ30PBVJU FXMQ36PBVJU FXMQ48PBVJU FXMQ54PBVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) 293 (145) 293 (145) 293 (145) 293 (145) 293 (145)
C: 3D086916B
25.8 FXMQ-M
Model FXMQ72MVJU FXMQ96MVJUPrinted circuit board fuse 250 V, 5 A 250 V, 5 AFan motor thermal fuse °F – –
Fan motor thermal protector °F OFF: 275±14(ON: 189±27)
OFF: 275±14(ON: 189±27)
76
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
25.9 FXHQ-M
Model FXHQ12MVJU FXHQ24MVJU FXHQ36MVJUPrinted circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 AFan motor thermal fuse °F – – –
Fan motor thermal protector °F OFF: 266±9ON: 176±36
OFF: 266±9ON: 176±36
OFF: 266±9ON: 176±36
C: 3D049334A
25.10 FXAQ-P
Model FXAQ07PVJU FXAQ09PVJU FXAQ12PVJU FXAQ18PVJU FXAQ24PVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AFan motor thermal fuse °F – – – – –Fan motor thermal protector °F – – – – –
C: 4D047085D
25.11 FXLQ-M, FXNQ-M
Model FXLQ07MVJUFXNQ07MVJU
FXLQ09MVJUFXNQ09MVJU
FXLQ12MVJUFXNQ12MVJU
FXLQ18MVJUFXNQ18MVJU
FXLQ24MVJUFXNQ24MVJU
Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A
Fan motor thermal protector °F(°C)OFF: 275±18
(135±10)ON: 248 (120)
or less
OFF: 275±18(135±10)
ON: 248 (120)or less
OFF: 275±18(135±10)
ON: 248 (120)or less
OFF: 275±18(135±10)
ON: 248 (120)or less
OFF: 275±18(135±10)
ON: 248 (120)or less
C: 3D045646B
25.12 FXTQ-TA
Model FXTQ09TAVJUA FXTQ12TAVJUA FXTQ18TAVJUA FXTQ24TAVJUA FXTQ30TAVJUAModel (with factory disconnect) FXTQ09TAVJUD FXTQ12TAVJUD FXTQ18TAVJUD FXTQ24TAVJUD FXTQ30TAVJUD
Printed circuit board fuse (F1U) 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 APrinted circuit board fuse (F2U) 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AOthers Blower motor, Fan driver overload protector
Model FXTQ36TAVJUA FXTQ42TAVJUA FXTQ48TAVJUA FXTQ54TAVJUA FXTQ60TAVJUAModel (with factory disconnect) FXTQ36TAVJUD FXTQ42TAVJUD FXTQ48TAVJUD FXTQ54TAVJUD FXTQ60TAVJUD
Printed circuit board fuse (F1U) 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 APrinted circuit board fuse (F2U) 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AOthers Blower motor, Fan driver overload protector
25.13 CXTQ-TA
Model CXTQ24TASBLU CXTQ36TASBLU CXTQ48TASBLU CXTQ60TASBLUPrinted circuit board fuse (F1U) 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 APrinted circuit board fuse (F2U) 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
77
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
Appendix
1. Introduction ...............................................................................................781.1 ED Book List ...................................................................................781.2 Publication List of Engineering Data for VRV Products ..................79
78
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
1. Introduction1.1 ED Book List
Design Manual ..................................................... RELQ-TA ......EDUS371705C-D (This booklet)
Capacity Table Book
Heat Recovery .................................................... RELQ-TA ..........EDUS371705C-C
Installation
Heat Pump, Heat Recovery .....................................................................EDUS371848-N
Indoor Units
Ceiling Mounted Cassette Type (Round Flow with Sensing) ....... FXFQ-T ..... EDUS391400A-F14
VISTA™ 2 × 2 Cassette Unit .................................. FXZQ-TA .......... EDUS391776-F9
4-Way Blow Ceiling-Suspended Type ...................... FXUQ-P ........ EDUS391437-F15
One Way Blow Cassette Type ................................ FXEQ-P ........ EDUS391533-F16
Slim Ceiling Mounted Duct Type ............................. FXDQ-M ........... EDUS39-600-F2
MSP Concealed Duct Unit ..................................... FXSQ-TA ........ EDUS391777-F17
Ceiling Mounted Duct Type .................................... FXMQ-PB ........ EDUS391503A-F4
Ceiling Mounted Duct Type .................................... FXMQ-M ....... EDUS39-900A-F11
Ceiling Suspended Type ....................................... FXHQ-M ........... EDUS39-600-F5
Wall Mounted Type .............................................. FXAQ-P .......... EDUS391100-F6
Floor Standing Type / Concealed Floor Standing Type ........ FXLQ-MFXNQ-M .......... EDUS391502-F7
Air Handling Unit .................................................. FXTQ-TA ....Engineering Data FXTQ-TA
Cased Coil Unit ................................................... CXTQ-TA ....Engineering Data CXTQ-TA
Branch Selector Unit
Single Branch Selector Unit ................................... BSQ-T ............ EDUS391434-B
Multi Branch Selector Unit ..................................... BS-Q54T ............ EDUS391434-B
Air Treatment Equipment
Outdoor Air Processing Unit ................................... FXMQ-MF ....... EDUS39-900A-F10
Energy Recovery Ventilator .................................... VAM-G ............. EDUS711116A
Controls .............................................................................................. EDUS721909-T
Remote Controller
Navigation Remote Controller ................................. BRC1E73 ............... EDUS721438
79
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
1.2 Publication List of Engineering Data for VRV Products
Shaded sections indicate Engineering Data Book/s published for this series.Timing of publication is subject to change without notice.
Outdoor Unit
Refrigerant Category Product series Type Volts Model name Area Book category Book No. Published in
R410A
Air cooled
VRV IV-X
H/R208/230 V460 V575 V
REYQ-XATJA, XAYDA, XAYCA USA Canada
Design manual EDUS371848A-DJan.2020
Capacity table EDUS371848A-C
H/P
208/230 V460 V RXYQ-XATJA, XAYDA USA
CanadaDesign manual EDUS341923-D
Nov.2019Capacity table EDUS341923-C
575 V RXYQ-XAYCA CanadaDesign manual EDUS341928-DCapacity table EDUS341928-C
VRV IV
H/R
208/230 V460 V REYQ-TATJA, TAYDA USA
CanadaDesign manual EDUS371704C-D
Feb.2020Capacity table EDUS371704C-C
575 V REYQ-TAYCA CanadaDesign manual EDUS371706C-DCapacity table EDUS371706C-C
H/P
208/230 V 460 V RXYQ-TATJA, TAYDA USA
CanadaDesign manual EDUS341703B-D
Jan.2020Capacity table EDUS341703B-C
575 V RXYQ-TAYCA CanadaDesign manual EDUS341824A-DCapacity table EDUS341824A-C
VRV Aurora
H/R208/230 V460 V575 V
RELQ-TATJA, TAYDA, TAYCA USACanada
Design manual EDUS371705C-DFeb.2020
Capacity table EDUS371705C-C
H/P208/230 V460 V575 V
RXLQ-TATJA, TAYDA, TAYCA USACanada
Design manual EDUS341819A-DJan.2020
Capacity table EDUS341819A-C
VRV IV-S H/P 208/230 V RXTQ36TAVJ9ARXTQ48/60TAVJUA
USA Canada
Design manual EDUS331608C-DFeb.2020
Capacity table EDUS331608C-CInstallation for all VRV air cooled type Installation EDUS371848-N Aug.2019
Water cooled
VRV-W H/P H/R
208/230 V460 V575 V
RWEQ-TATJU, TAYDU, TAYCU RWEQ-TATJA, TAYDA
USA Canada
Design manual EDUS301864A-DJan.2020
Capacity table EDUS301864A-C
Installation for all VRV water cooled type Installation EDUS301864-N Aug.2019
Note:C/O: Cooling only, H/P: Heat pump, H/R: Heat covery
80
RELQ-TATJA / TAYDA / TAYCA EDUS371705C-D
Indoor Unit and Other Products
Refrigerant Product category Product type Model name Area Book No. Published in
R410A
VRV Indoor units
Ceiling Mounted Cassette Type (Round Flow with Sensing) FXFQ07-48TVJU USA EDUS391400A-F14 May 2018
VISTA™ 2 x 2 Cassette Unit FXZQ05-18TAVJU USA EDUS391776-F9 Mar.2018
4-Way Blow Ceiling- Suspended Type FXUQ18-36PVJU USA EDUS391437-F15 May 2015
One Way Blow Cassette Type FXEQ07-24PVJU USA EDUS391533-F16 Oct.2015Slim Ceiling Mounted Duct Type FXDQ07-24MVJU USA EDUS39-600-F2 Sep.2006MSP Concealed Ducted Unit FXSQ05-54TAVJU USA EDUS391777-F17 Mar.2018
Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503A-F4 May 2018
Ceiling Mounted Duct Type FXMQ72/96MVJU USA EDUS39-900A-F11 May 2010Ceiling Suspended Type FXHQ12-36MVJU USA EDUS39-600-F5 Sep.2006Wall Mounted Type FXAQ07-24PVJU USA EDUS391100-F6 Jan.2012Floor Standing Type Concealed Floor Standing Type
FXLQ07-24MVJU FXNQ07-24MVJU USA EDUS391502-F7 Jul.2015
Air Handling Unit FXTQ09-60TAVJUA FXTQ09-60TAVJUD USA Engineering Data
FXTQ-TA Sep.2016
Outdoor Air Processing Unit FXMQ48-96MFVJU USA EDUS39-900A-F10 May 2010Single Branch Selector Unit BSQ36-96TVJ USA EDUS391434-B Aug.2015Multi Branch Selector Unit BS4-12Q54TVJ USA EDUS391434-B Aug.2015
Cased Coil Unit CXTQ24-60TASBLU USA Engineering Data CXTQ-TA —
Controls and
networks
Remote controllers Control devices Adaptors
BRC1E71, BRC4C/7C/7E, BRC2A71 DCS302C71, DCS301C71, DST301BA61, DCS601C71 KRP1C74/75
USA EDUS721909-T Dec.2019
Navigation remote controller BRC1E73 USA EDUS721438 Apr.2015intelligent Touch Manager DCM601A71, DCM601A72 USA EDUS721212 Oct.2012intelligent Touch Controller DCS601C71 USA EDUS72-608 Dec.2006Interface for use in BACnet® DMS502B71 USA EDUS72-749 Oct.2007
Option for all type For indoor and outdoor units USA OHUS07-1 Nov.2007Energy Recovery Ventilator (VAM) VAM300-1200GVJU USA EDUS711116A Jun.2017
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.
Cautions on product corrosion
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
©All rights reserved 02/20 FS