8
1 Effective 1-28-2011 951 Old Rand Rd Suite 116 Wauconda IL 60084 P 847-487-5599 F 847-487-0909 www.midwest-control.com TECHNICAL DATA Eaton Magnetic Starters Cutler Hammer® A27 & B27 Definite Purpose Starters From Eaton Combine the Features and Flexibility of the C25 Definite Purpose Contactors and the XT Series Bi-Metallic Ambient Compensated Overload Relays UL Recognized Components UL File #E-1491, Guide NLDX2 CSA Certified Components File #LR353, Guide 380W-1.14 Class 3211 04 Class 10 Trip Class Bi-Metallic Ambient Compensated Operated Trip Free Mechanism Shrouded or Finger Proof Terminals to Reduce Possibility of Electrical Shock Single Phase Sensitivity Definite Purpose Starters Include NEMA 1 General Purpose Enclosure Standard Stake On Incoming Line For Auxiliary Components 1Hp - 15Hp 208/230V, 1HP - 30Hp 460V 1Hp - 10Hp 230V Single Phase IEC Starters ECX Series 20Hp - 30Hp 208/230V & 40hp - 60Hp 460V Non Reversing IEC Contactors NEMA 1 General Purpose Enclosure Standard Optional Enclosures NEMA 12 & 4X Available No Heaters Required RoHS Compliant UL Recognized & CSA Certified Definite Purpose Starters UL Listed IEC Starters Inventory Flexibility

Eaton Magnetic Starters - Hydra Flow · PDF fileEffective 1-28-2011 1 951 Old Rand Rd Suite 116 Wauconda IL 60084 P 847-487-5599 F 847-487-0909 TECHNICAL DATA Eaton Magnetic Starters

Embed Size (px)

Citation preview

Page 1: Eaton Magnetic Starters - Hydra Flow · PDF fileEffective 1-28-2011 1 951 Old Rand Rd Suite 116 Wauconda IL 60084 P 847-487-5599 F 847-487-0909 TECHNICAL DATA Eaton Magnetic Starters

1 Effective 1-28-2011

951 Old Rand Rd Suite 116 Wauconda IL 60084

P 847-487-5599 F 847-487-0909

www.midwest-control.com

TEC

HN

ICA

L D

ATA

Eaton Magnetic Starters

Cutler Hammer® A27 & B27 Definite Purpose Starters From Eaton Combine the Features and Flexibility of the C25 Definite Purpose Contactors and the XT Series Bi-Metallic Ambient Compensated Overload Relays

• UL Recognized Components UL File #E-1491, Guide NLDX2

• CSA Certified Components File #LR353, Guide 380W-1.14 Class 3211 04

• Class 10 Trip Class

• Bi-Metallic Ambient Compensated Operated

• Trip Free Mechanism

• Shrouded or Finger Proof Terminals to Reduce Possibility of Electrical Shock

• Single Phase Sensitivity Definite Purpose Starters Include

• NEMA 1 General Purpose Enclosure Standard

• Stake On Incoming Line For Auxiliary Components

• 1Hp - 15Hp 208/230V, 1HP - 30Hp 460V

• 1Hp - 10Hp 230V Single Phase IEC Starters ECX Series

• 20Hp - 30Hp 208/230V & 40hp - 60Hp 460V

• Non Reversing IEC Contactors

• NEMA 1 General Purpose Enclosure Standard

• Optional Enclosures NEMA 12 & 4X Available

• No Heaters Required • RoHS Compliant • UL Recognized & CSA Certified Definite Purpose Starters • UL Listed IEC Starters • Inventory Flexibility

Page 2: Eaton Magnetic Starters - Hydra Flow · PDF fileEffective 1-28-2011 1 951 Old Rand Rd Suite 116 Wauconda IL 60084 P 847-487-5599 F 847-487-0909 TECHNICAL DATA Eaton Magnetic Starters

2 Effective 1-28-2011

951 Old Rand Rd Suite 116 Wauconda IL 60084

P 847-487-5599 F 847-487-0909

www.midwest-control.com

Definite Purpose Starter Selection Chart NEMA 1 Enclosure

Three Phase Starters

Starter Size Contactor FLA

A27CGD15 15

A27CGD25 25

A27CGF30 30

A27CGF40 40

A27CGF45 45

Single Phase Starters

Starter Size Contactor FLA

B27CGD15 15

B27CGD25 25

B27CGF30 30

B27CGF40 40

B27CGF45 45

HP 208V 230V 460V 230V 1 Phase

1.0 A27CGD15B006 A27CGD15B006

A27CGD15C2P4

1.5 A27CGD15B010 A27CGD15C004

2.0 A27CGD15B010

B27CGD15B016

3.0 A27CGD15B016 A27CGD15C006 B27CGD25B024

5.0 A27CGD25B024 A27CGD25B016 A27CGD15C010 B27CGF30B040

7.5 A27CGD25B032 A27CGD25B024 A27CGD25C016

B27CGF40B040

10 A27CGF30B040 A27CGF30B040 B27CGF45B057

10 A27CGF40B040 A27CGF40B040

15 A27CGF45B057 A27CGF45B057 A27CGF30C024

20

A27CGF40C040

25 A27CGF45C040

30

**For Larger HP Not Shown See Page 4 for IEC Starters**

B27CGD15B010

The Starter Overload Ranges Selected Are An Average Rating. These Ratings Could Be High or Low for a Specific Motor For Fully Reliable Motor Protection It is Best to Select Your Starter Based on the Full Load Current Rating As Shown on the Motor Name Plate See Chart On Page 3 for Specific Overload Range

Page 3: Eaton Magnetic Starters - Hydra Flow · PDF fileEffective 1-28-2011 1 951 Old Rand Rd Suite 116 Wauconda IL 60084 P 847-487-5599 F 847-487-0909 TECHNICAL DATA Eaton Magnetic Starters

3 Effective 1-28-2011

951 Old Rand Rd Suite 116 Wauconda IL 60084

P 847-487-5599 F 847-487-0909

www.midwest-control.com

TEC

HN

ICA

L D

ATA

*27CGD (15 - 25 FLA) *27CGF (30 - 45 FLA) A 2P4

Starter Size Coil Voltage Overload Code

15

Inductive Full Load Amp

A 120V

B 208V/230V

C 460V

Code For Use With Contactor

Amp Range Overload

Range

2P4

15 - 25A

1.6 - 2.4

004 2.4 – 4

006 4 – 6

010 6 - 10

016 10 - 16

024 16 - 24

032 24 - 32

024 30 - 45A

16 - 24

040 24 - 40

057 40 - 57

Definite Purpose Model Number Explanation

A Three Phase

B Single Phase 15

25

30

40

45

Overload Ranges Have Been Selected by Hp, Voltage and NEMA FLA Other Overload Ranges Are Available Consult Midwest Control

Nema 1 Enclosure A (Width)

B (Height)

C (Depth)

E (Mounting)

G (Mounting)

15, 25, & 30 FLA 5.63 10.17 5.81 8.00 4.50

40, & 45 FLA 7.64 13.27 6.67 10.75 6.00

Definite Purpose Starter Dimensions

Page 4: Eaton Magnetic Starters - Hydra Flow · PDF fileEffective 1-28-2011 1 951 Old Rand Rd Suite 116 Wauconda IL 60084 P 847-487-5599 F 847-487-0909 TECHNICAL DATA Eaton Magnetic Starters

4 Effective 1-28-2011

951 Old Rand Rd Suite 116 Wauconda IL 60084

P 847-487-5599 F 847-487-0909

www.midwest-control.com

IEC Starter Selection Chart

Three Phase Starters

Starter Size

Contactor FLA

ECX09L 65

ECX09M 80

ECX09P 115

ECX09 1 E

Starter Type Enclosure Voltage Code

M

Contactor FLA

A

Plain Cover

A

No Disconnect

V

Overload Range

HP 208V 230V 460V

25 ECX09M1EAA-V ECX09M1BAA-U

30 ECX09P1EAA-V ECX09M1BAA-V

50 ECX09L1CAA-R

60 ECX09M1CAA-V

20 ECX09L1EAA-R ECX09L1BAA-R

40 ECX09L1CAA-R

X=XT IEC Non

Reversing Starter

L = 65 M = 80

P = 115

A = 120V B = 230V C = 460V E = 208V

R = 50-65 U = 50-70 V =70-100

IEC Model Number Explanation

IEC Starters Are Also Available In a NEMA 12 (Dust Tight) & NEMA 4X Enclosures ( Water Tight) When Ordering NEMA 4 Please Specify 304 Stainless Steel Enclosure or Non Metallic Enclosure Please Consult Midwest Control for Pricing

General Purpose

Shown With Optional HOA Switch

Page 5: Eaton Magnetic Starters - Hydra Flow · PDF fileEffective 1-28-2011 1 951 Old Rand Rd Suite 116 Wauconda IL 60084 P 847-487-5599 F 847-487-0909 TECHNICAL DATA Eaton Magnetic Starters

5 Effective 1-28-2011

951 Old Rand Rd Suite 116 Wauconda IL 60084

P 847-487-5599 F 847-487-0909

www.midwest-control.com

TEC

HN

ICA

L D

ATA

NEMA 1 Field Installed Accessories

Description Model No. Part No.

Start/Stop Switch Includes Mounting Flange All Models C400GK1-GD

H-O-A Selector Switch w/Mounting Flange All Models C400GK3-GD

Test/Off/Auto Push Button Spring Return From Test All Models C400GK6-GD

Auxiliary Contact (Side Mount) 1NO (A27, B27) C320KG1

1NO, 1NC (A27, B27) C320KG3

Auxiliary Contact (Side Mount) 1NO, 1NC (ECX) XTCEXSBN11

We Recommend 1NO, 1NC Auxiliary Contact When Installing the Above Accessories on the A27 and B27 Series

Contactor

Start/Stop Switch H-O-A Selector Switch Auxiliary Contact

Replacement Contactors

Part No. Model No. FLA

Replacement Contactor With Coil for Definite Purpose Starters

C25DND315x A27CGD15, B27CGD15 15

C25DND325x A27CGD25, B27CGD25 25

C25DND330x A27CGF30, B27CGF30 30

C25DNF340x A27CGF40, B27CGF40 40

C25DNJ350x A27CGF45, B27CGF45 45

Replacement Contactor With Coil for IEC Starters

XTCE065D00E ECX09L1EAA 208V

65 XTCE065D00B ECX09L1BAA 230V

XTCE065D00C ECX09L1CAA 460V

XTCE065D00A ECX09L1AAA 120V

XTCE080F00E ECX09M1EAA 208V

80 XTCE080F00B ECX09M1BAA 230V

XTCE080F00C ECX09M1CAA 460V

XTCE080F00A ECX09M1AAA 120V

XTCE115G00B ECX09P1EAA 208V 115

XTCE115G00A ECX09P1AAA 120V

**Replace the X On the Definite Purpose Contactors With the Appropriate Letter for the Required Voltage

Code Voltage

A 120V

B 208V/230V

C 460V

** Test/Off Auto Button Not Shown

Page 6: Eaton Magnetic Starters - Hydra Flow · PDF fileEffective 1-28-2011 1 951 Old Rand Rd Suite 116 Wauconda IL 60084 P 847-487-5599 F 847-487-0909 TECHNICAL DATA Eaton Magnetic Starters

6 Effective 1-28-2011

951 Old Rand Rd Suite 116 Wauconda IL 60084

P 847-487-5599 F 847-487-0909

www.midwest-control.com

Replacement Coils For Definite Purpose Starters

Part No. Voltage Model No.

9-3185-2 208/230V

A27CGD15B, A27CGD25B, A27CGF30B, A27CGF40B B27CGD15B, B27CGD25B, B27CGF30B, B27CGF40B

9-3186-2 A27CGF45B, B27CGF45B

9-3185-3

460V A27CGD15C, A27CGD25C, A27CGF30C, A27CGF40C

9-3186-3 A27CGF45C

9-3185-1 110V

A27CGD15A, A27CGD25A, A27CGF30A, A27CGF40A B27CGD15A, B27CGD25A, B27CGF30A, B27CGF40A

9-3186-1 A27CGF45A, B27CGF45A

Replacement Coils for IEC Starter

Part No. Voltage Model No.

XTCERENCOILDE

208V

ECX09L1EAA

XTCERENCOILFE ECX09M1EAA

XTCERENCOILGB ECX09P1EAA

XTCERENCOILDB 230V

ECX09L1BAA

XTCERENCOILFB ECX09M1BAA

XTCERENCOILDC 460V

ECX09L1CAA

XTCERENCOILFC ECX09M1CAA

XTCERENCOILDA

120V

ECX09L1AAA

XTCERENCOILFA ECX09M1AAA,

XTCERENCOILGA ECX09P1AAA

Page 7: Eaton Magnetic Starters - Hydra Flow · PDF fileEffective 1-28-2011 1 951 Old Rand Rd Suite 116 Wauconda IL 60084 P 847-487-5599 F 847-487-0909 TECHNICAL DATA Eaton Magnetic Starters

951 Old Rand Rd Suite 116 Wauconda IL 60084

P 847-487-5599 F 847-487-0909

www.midwest-control.com

TEC

HN

ICA

L D

ATA

7

Definite Purpose Replacement Overloads

Replacement Overloads for 15-25 Amp Contactors

Overload Code Range Part No.

2P4 1.6 – 2.4 XTOB2P4CC1-DP

004 2.4 – 4 XTOB004CC1-DP

006 4 – 6 XTOB006CC1-DP

010 6 – 10 XTOB010CC1-DP

016 10 – 16 XTOB016CC1-DP

024 16 – 24 XTOB024CC1-DP

032 24 – 32 XTOB032CC1-DP

Replacement Overloads for 30-45 Amp Contactors

024 16 – 24 XTOB024DC1-DP

040 24 – 40 XTOB040DC1-DP

057 40 – 57 XTOB057DC1-DP

IEC Starters Replacement Overloads

Overload Code Range Part No.

R 50 – 65 XTOB065DC1

U 50 – 70 XTOB070GC1

V 70 – 100 XTOB100GC1

Page 8: Eaton Magnetic Starters - Hydra Flow · PDF fileEffective 1-28-2011 1 951 Old Rand Rd Suite 116 Wauconda IL 60084 P 847-487-5599 F 847-487-0909 TECHNICAL DATA Eaton Magnetic Starters

8 Effective 1-28-2011

Cross Reference Chart NEMA FLA Siemens No. Siemens FLA GE No. GE FLA Cutler Hammer Cutler Hammer FLA

208V

1.0Hp 4.8

LAC00L1L 10 A27CGD15B006 15

1.5Hp 6.9 LAC00L1M 10 A27CGD15B010 15

2.0Hp 7.8 LAC00L1M 10 A27CGD15B010 15

3.0Hp 11 LAC01L1N 13.8 A27CGD15B016 15

5.0Hp 17.5 LAC02L1S 17.5 A27CGD25B024 25

Up to 7.5Hp 25.3 16AF35BG4 25 LAC04L1U 32 A27CGD25B032 25

Up to 10Hp 32.2 16BF35BG4 30 LAC04L1V 32 A27CGF30B040 30

Up to 10Hp 32.2 16CF35BG4 40 LAC04L1V 32 A27CGF40B040 40

Up to 15Hp 48.3 16DF35BG4 50 LAC06L2G 48 A27CGF45B057 45

Up to 20Hp 62.1 16EF35BG4 60 LAC07L2H 62 EXC09L1EAA-R 65

Up to 25Hp 78.2 16FE35BG4 75 LAC09L2J 80 ECX09M1EAA-V 80

Up to 30Hp 92 16GE35BG 90 LAC10L2L 96 ECX09P1EAA-V 115

230V

1.0Hp 4.2

LAC00S1L 10 A27CGD15B006 15

1.5Hp 6 LAC00S1L 10 A27CGD15B006 15

2.0Hp 6.8 LAC00S1M 10 A27CGD15B010 15

3.0Hp 9.6 LAC00S1N 10 A27CGD15B010 15

5.0Hp 15.2 LAC02S1P 17.5 A27CGD25B016 25

Up to 7.5Hp 22 16AF35BG4 25 LAC25S1T 22 A27CGD25B024 25

Up to 10Hp 28 16BF35BG4 30 LAC04S1V 32 A27CGF30B040 30

Up to 10Hp 28 16CF35BG4 40 LAC04S1V 32 A27CGF40B040 40

Up to 15Hp 42 16DF35BG4 50 LAC06S2E 48 A27CGF45B057 45

Up to 20Hp 54 16EF35BG4 60 LAC07S2G 62 ECX09L1BAA-R 65

Up to 25Hp 68 16FE35BG 75 LAC08S2J 68 ECX09M1BAA-U 80

Up to 30Hp 80 16GE35BG 90 LAC09S2J 80 ECX09M1BAA-V 80

460V

1.0Hp 2.1

LAC00U1H 10 A27CGD15C2P4 15

1.5Hp 3.0 LAC00U1K 10 A27CGD15C004 15

2.0Hp 3.4 LAC00U1K 10 A27CGD15C004 15

3.0Hp 4.8 LAC00U1L 10 A27CGD15C006 15

5.0Hp 7.6 LAC00U1M 10 A27CGD15C010 15

7.5Hp 11 LAC01U1N 13.8 A27CGD25C016 25

Up to 10Hp 14 16AF35BH4 25 LAC02U1P 17.5 A27CGD25C016 25

Up to 15Hp 21 16BF35BH4 30 LAC25U1T 22 A27CGF30C024 30

Up to 20Hp 27 16CF35BH4 40 LAC04U1V 32 A27CGF40C040 40

Up to 25Hp 34 LAC45UIW 34 A27CCF45C040 45

Up to 30Hp 40 16DF35BH4 50 LAC06U2E 48 A27CGF45C040 45

Up to 40Hp 52 16EF35BH4 60 LAC07U2G 62 ECX09L1CAA-R 65

Up to 50Hp 65 16FE35BH 75 LAC08U2H 68 ECX09L1CAA-R 65

Up to 60Hp 77 16GE35BH 90 LAC09U2J 80 ECX09M1CAA-V 80

230V Single Phase

1.0Hp 8

B27CGD15B010 15

1.5Hp 10 B27CGD15B010 15

2.0Hp 12 16BF15BG8 30 B27CGD15B016 15

3.0Hp 17

B27CGD25B024 25

5.0Hp 28 B27CGF30B040 30

7.5Hp 40 16CF15BG8 40 B27CGF40B040 40

10Hp 50 16DF15BG8 50 B27CGF45B057 45

The Starter Overload Ranges Selected Are An Average Rating. These Ratings Could Be High or Low for a Specific Motor. For Fully Reliable Motor Protection It is Best to Select Your Starter Based on the Full Load Current Rating As Shown on the Motor Name Plate