Upload
doanphuc
View
239
Download
2
Embed Size (px)
Citation preview
EasyLogic™ PM2200 seriesUser manual
NHA2778902-00
11/2015
www.schneider-electric.com
Legal InformationThe Schneider Electric brand and any registered trademarks of Schneider ElectricIndustries SAS referred to in this guide are the sole property of Schneider ElectricSA and its subsidiaries. They may not be used for any purpose without the owner'spermission, given in writing. This guide and its content are protected, within themeaning of the French intellectual property code (Code de la propriétéintellectuelle français, referred to hereafter as "the Code"), under the laws ofcopyright covering texts, drawings and models, as well as by trademark law. Youagree not to reproduce, other than for your own personal, noncommercial use asdefined in the Code, all or part of this guide on any medium whatsoever withoutSchneider Electric's permission, given in writing. You also agree not to establishany hypertext links to this guide or its content. Schneider Electric does not grantany right or license for the personal and noncommercial use of the guide or itscontent, except for a non-exclusive license to consult it on an "as is" basis, at yourown risk. All other rights are reserved.
Electrical equipment should be installed, operated, serviced, and maintained onlyby qualified personnel. No responsibility is assumed by Schneider Electric for anyconsequences arising out of the use of this material.
As standards, specifications, and designs change from time to time, please ask forconfirmation of the information given in this publication.
Safety informationImportant information
Read these instructions carefully and look at the equipment to become familiar withthe device before trying to install, operate, service or maintain it. The followingspecial messages may appear throughout this bulletin or on the equipment to warnof potential hazards or to call attention to information that clarifies or simplifies aprocedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates thatan electrical hazard exists which will result in personal injury if the instructions arenot followed.
This is the safety alert symbol. It is used to alert you to potential personal injuryhazards. Obey all safety messages that follow this symbol to avoid possible injuryor death.
DANGERDANGER indicates a hazardous situation which, if not avoided, will result in deathor serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result inminor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please note
Electrical equipment should be installed, operated, serviced and maintained onlyby qualified personnel. No responsibility is assumed by Schneider Electric for anyconsequences arising out of the use of this material. A qualified person is one whohas skills and knowledge related to the construction, installation, and operation ofelectrical equipment and has received safety training to recognize and avoid thehazards involved.
NHA2778902–00 3
NoticesFCC
This equipment has been tested and found to comply with the limits for a Class Adigital device, pursuant to Part 15 of the FCC rules. These limits are designed toprovide reasonable protection against harmful interference when the equipment isoperated in a commercial environment. This equipment generates, uses, and canradiate radio frequency energy and, if not installed and used in accordance withthe instruction manual, may cause harmful interference to radio communications.Operation of this equipment in a residential area is likely to cause harmfulinterference in which case the user will be required to correct the interference at hisown expense.
The user is cautioned that any changes or modifications not expressly approved bySchneider Electric could void the user’s authority to operate the equipment.
This digital apparatus complies with CAN ICES-3 (A) /NMB-3(A).
4 NHA2778902–00
Table of Contents
FCC.....................................................................................................4
Safety precautions ......................................................................................9Introduction ................................................................................................10
Meter overview.........................................................................................10Meter Features.........................................................................................10Feature summary .....................................................................................10
.......................................................................................................... 11Meter configuration...................................................................................13Firmware consideration.............................................................................13
Harware References ................................................................................14PM2200 meter models and accessories .....................................................14
Meter models .....................................................................................14Meter accessories...............................................................................14
Supplemental information..........................................................................14LED indicators..........................................................................................14
Alarm / energy pulsing LED .................................................................15Heartbeat / serial communications LED ................................................15Balanced 3-phase Wye system with 2 CTs............................................17Balanced 3-phase Wye or Delta system with 1CT..................................17
RS-485 wiring ..........................................................................................17RS-485 cable .....................................................................................18RS-485 terminals ................................................................................18
Pulse output.............................................................................................18I/O Modules .............................................................................................18
Configuring optional I/O module using ION Setup..................................18
Meter Display.............................................................................................20Display overview ......................................................................................20LED indicators..........................................................................................20
Alarm / energy pulsing LED .................................................................20Heartbeat / serial communications LED ................................................20
Notification icons ......................................................................................21Meter display language .............................................................................21Meter screen navigation............................................................................21
Navigation symbols.............................................................................22Meter screen menus overview .............................................................22
Setting up the display................................................................................22
Basic setup ................................................................................................24Configuring basic setup parameters using the display .................................24Configuring advanced setup parameters using the display...........................26Setting the rate.........................................................................................26Setting up regional settings .......................................................................27Setting up the screen passwords ...............................................................28
Lost password ....................................................................................28Setting the clock .................................................................................28
Alarms.........................................................................................................30Alarms overview.......................................................................................30Alarm types..............................................................................................30
NHA2778902–00 5
Unary alarms............................................................................................30Available unary alarms ........................................................................30
Digital alarms ...........................................................................................30Digital alarm with setpoint delay ...........................................................30Available digital alarms........................................................................31
Standard alarms.......................................................................................31Example of over and under setpoint (standard) alarm operation..............31Maximum allowable setpoint ................................................................32Available standard alarms ...................................................................33
Alarm priorities .........................................................................................34Multiple alarm considerations...............................................................35
Alarm setup overview................................................................................35Built-in error-checking .........................................................................35
LED alarm indicator ..................................................................................37Configuring the LED for alarms using the display...................................37Configuring the LED for alarms using ION Setup ...................................37
Alarm display and notification ....................................................................37Alarm icon ..........................................................................................38Alarm / energy pulsing LED .................................................................38Alarm screens ....................................................................................38Active alarms......................................................................................38Alarm details ......................................................................................38
Active alarms list and alarm history log .......................................................38Alarms counters .......................................................................................39
Alarms rollover value...........................................................................39Resetting alarms using ION Setup .............................................................39
Meter logging.............................................................................................40Logs overview ..........................................................................................40Setting up the data log ..............................................................................40Saving the data log contents using ION Setup ............................................40Alarm log .................................................................................................41
Measurements and calculations .............................................................42Meter Initialization.....................................................................................42Real-time readings ...................................................................................42Energy measurements..............................................................................42Min/max values ........................................................................................42Power demand .........................................................................................42
Power demand calculation methods .....................................................43Block interval demand .........................................................................43Synchronized demand.........................................................................44Thermal demand ................................................................................44
Current demand .......................................................................................45Predicted demand...............................................................................45Peak demand .....................................................................................45
Timer.......................................................................................................46Active load timer .................................................................................46Meter operation timer ..........................................................................46Run Time ...........................................................................................46
Power quality .............................................................................................47Harmonics overview .................................................................................47
6 NHA2778902–00
Total harmonic distortion ...........................................................................47Harmonic content calculations .............................................................47THD% calculations..............................................................................47
Displaying harmonics data ........................................................................47
Maintenance and upgrades.....................................................................49Maintenance overview ..............................................................................49Troubleshooting LED indicators .................................................................49Meter memory ..........................................................................................49Meter battery............................................................................................49Viewing firmware version, model and serial number ....................................50Firmware upgrades...................................................................................50Technical assistance.................................................................................50
Verifying accuracy.....................................................................................51Overview of meter accuracy ......................................................................51Accuracy test requirements .......................................................................51
Signal and power source .....................................................................51Control equipment ..............................................................................51Environment .......................................................................................51Reference device or energy standard ...................................................52
Verifying accuracy test ..............................................................................52Required pulses calculation for accuracy verification testing ........................53Total power calculation for accuracy verification testing ...............................54Percentage error calculation for accuracy verification testing .......................54Accuracy verification test points .................................................................54Energy pulsing considerations ...................................................................55VTand CTconsiderations..........................................................................55Example calculations ................................................................................56
Adjustments to allow energy pulsing at the pulse outputs .......................56Typical sources of test errors .....................................................................57
Power and power factor ...........................................................................58Power and power factor ............................................................................58Current phase shift from voltage ................................................................58Real, reactive and apparent power (PQS)...................................................58
Power flow .........................................................................................59Power factor (PF) .....................................................................................59
True PF and displacement PF..............................................................59Power factor sign convention ...............................................................59Power factor min/max convention.........................................................60Power factor register format.................................................................60
Meter specifications..................................................................................62Specifications...........................................................................................62
Mechanical characteristics...................................................................62Electrical characteristics ......................................................................62Environmental characteristics ..............................................................64EMC (electromagnetic compatibility)* ...................................................64Safety ................................................................................................64RS-485 communications .....................................................................65Pulse output .......................................................................................65Real-time clock ...................................................................................65
NHA2778902–00 7
Safety precautions
Safety precautionsInstallation, wiring, testing and service must be performed in accordance with alllocal and national electrical codes.
DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E in the USA, CSA Z462 or applicablelocal standards.
• Turn off all power supplying this device and the equipment in which it isinstalled before working on the device or equipment.
• Always use a properly rated voltage sensing device to confirm that all poweris off.
• Treat communications and I/O wiring connected to multiple devices ashazardous live until determined otherwise.
• Do not exceed the device’s ratings for maximum limits.• Never short the secondary of a potential/voltage transformer (PT/VT).• Never open circuit a current transformer (CT).• Always use grounded external CTs for current inputs.• Replace all devices, doors and covers before turning on power to this
equipment.Failure to follow these instructions will result in death or serious injury.
NOTE: See IEC 60950-1:2005, Annex W for more information on communicationsand I/O wiring connected to multiple devices.
WARNINGUNINTENDED OPERATION• Do not use this device for critical control or protection applications where
human or equipment safety relies on the operation of the control circuit.• Do not rely solely on data displayed on the display or in software to determine
if this device is functioning correctly or complying with all applicablestandards.
• Do not use data displayed on the display or in software as a substitute forproper workplace practices or equipment maintenance.
Failure to follow these instructions can result in death, serious injury, orequipment damage.
NHA2778902–00 9
Introduction
Introduction
Meter overviewThe PM2200 series meters are digital meters that offer comprehensive 3-phaseelectrical instrumentation and load management facilities in a compact and ruggedpackage.
The meters offer value for the demanding needs of your energy monitoring andcost management applications. All meters in the PM2200 series range comply withClass 1, or Class 0.5S accuracy standards and feature high quality, reliability andaffordability in a compact and easy to install format.
Meter FeaturesThe PM2200 series meter supports many features, a few of the features are listedbelow:• Self guided LCD display and navigation• Energy accounting and balancing• Measurement of both True PF and Displacement PF• Active, reactive, and apparent energy readings• Min/Max values of instantaneous parameters with timestamp.• Cyber security: The meter enables disabling the RS-485 port through front
panel keys against unauthorized access. This feature can also be used fortoggling between the RTU devices in case of limited availability of nodes insoftware system.
You can use the meter as a stand-alone device, but its extensive capabilities arefully realized when used as part of an energy management system.
For applications, feature details and the most current and complete specificationsof the PM2200 meters, see the EasyLogic PM2000 series technical datasheet atwww.schneider-electric.com.
Feature summary
Parameter PM2210 PM2220 PM2230
Accuracy Class for Wh Class 1 Class 1 Class 0.5S
Accuracy Class for VARh 1.0 1.0 1.0
Sampling rate per cycle 64 64 64
Current:• Per-phase and 3 phase average• Calculated neutral current
ü ü ü
Voltage:• V L-N - per-phase and 3 phase average• V L-L - per-phase and 3 phase average
ü ü ü
Power Factor• Per phase and 3 phase total
True PF True PFDisplacement PF
True PFDisplacement PF
Frequency ü ü ü
Power:• Active power (kW) - Phase wise and total• Apparent power (kVA) - Phase wise and total• Reactive power (kVAR) - Phase wise and total
ü ü ü
3 Phase unbalance Current CurrentVoltage
CurrentVoltage
10 NHA2778902–00
Introduction
Parameter PM2210 PM2220 PM2230
Demand parameters (kW, kVA, kVAR, I)• Last demand• Present demand• Predictive demand• Peak demand: Timestamp for peak demand*
ü
(no timestamp)ü ü
Energy: kWh, kVAh, kVARh (4 Quadrant)• Delivered (Import / Forward)• Received (Export / Reverse)
DeliveredReceived
DeliveredReceivedTotal*
Net*
Last cleared (Old)*
DeliveredReceivedTotal*
Net*
Last cleared (Old)*
THD:• Voltage L-N• Voltage L-L• Current per phase
ü ü ü
Individual Harmonics — Up to 15th oddharmonics
Up to 31st oddharmonics
Min / Max with timestamp• V L-L average• V L-N average• Current average• Frequency• Active power, Total• Apparent power, Total• Reactive power, Total• Power factor, Total
— ü ü
Communication POP RS-485 Modbus RTU RS-485 Modbus RTU
Expandable Analog IO modules (1 input & 1 output) — — ü
Expandable Analog IO modules (2 inputs & 2 outputs) — — ü
Expandable Digital IO modules (2 inputs & 2 outputs) — — ü
Data Logging• Energy (W, VA, VAR): Delivered / Received• Power: Active / Apparent / Reactive• Demand (W, VA, VAR, A): Last / Present / Predictive
— — ü
* Indicates features that can be read through communication only
Measured parametersEnergy
The meter provides bi-directional, 4-quadrant, Class 1 / Class 0.5S accurateenergy metering.
The meter stores all accumulated active, reactive, and apparent energyparameters in nonvolatile memory:• kWh, kVARh, kVAh delivered• kWh, kVARh, kVAh received• kWh, kVARh, kVAh delivered + received• kWh, kVARh, kVAh delivered – received
NHA2778902–00 11
Introduction
Demand
The meter provides last, present, predicted, and maximum (peak) demand values,and a timestamp when the maximum (peak) demand occurred.
The meter supports standard demand calculation methods, including sliding block,fixed block, rolling block, thermal and synchronized.
Peak demand registers can be reset manually (password protected).
Demand measurements include:• W, VAR, VA demand total• Amps demand average
Instantaneous
The meter provides highly accurate 1-second measurements, average values,including true RMS, per phase and total for:• Per phase and average voltage (line-to-line, line-to-neutral)• Per phase and average current, and neutral current• Per phase and total power (VA, W, Var)• True and displacement power factor• System frequency
Power quality
The meter provides complete harmonic distortion metering, recording, and real-time reporting, up to the 15th harmonic for PM2220 and up to 31st harmonic forPM2230 for all voltage and current inputs.
The following power quality measurements are available:• PM2220: Individual odd harmonics up to 15th order (Voltage and current, per
phase)• PM2230: Individual odd harmonics up to 31st order (Voltage and current, per
phase)• Total harmonic distortion (THD%) for current and voltage (displays line-to-line
or line-to-neutral, based on selected system configuration)
Data recording
The meter stores each new minimum and new maximum value with date andtimestamp for all instantaneous values and for each phase.
The meter also records the following:• Alarms (with 1s timestamping)• Parameters configured for data logging• Data, alarm history, and diagnostics logs
Input/output
The meter supports optional input and output capabilities.
Other measurements
Additional measurements recorded by the meter include several timers.
These timers include:• I/O timer shows how long an input or output has been ON.• Operating timer shows how long the meter has been powered.
12 NHA2778902–00
Introduction
• Load timer shows how much time a load has been running, based on thespecified minimum current for the load timer setpoint setting.
Data display and analysis toolsPower Monitoring Expert
StruxureWare™ Power Monitoring Expert is a complete supervisory softwarepackage for power management applications. The software collects and organizesdata gathered from your facility’s electrical network and presents it as meaningful,actionable information via an intuitive web interface.
Power Monitoring Expert communicates with devices on the network to provide:• Real-time monitoring through a multi-user web portal• Trend graphing and aggregation• Power quality analysis and compliance monitoring• Preconfigured and custom reportingSee the StruxureWare™ Power Monitoring Expert online help for instructions onhow to add your meter into its system for data collection and analysis.
PowerScada Expert
StruxureWare™ PowerScada Expert is a complete real-time monitoring and controlsolution for large facility and critical infrastructure operations.
It communicates with your meter for data acquisition and real-time control. You canuse PowerScada Expert for:• System supervision• Real-time and historical trending, event logging and waveform capture• PC-based custom alarmsSee the StruxureWare™ PowerScada Expert online help for instructions on how toadd your meter into its system for data collection and analysis.
Meter configurationMeter configuration can be performed through the display or PowerLogic™ IONSetup.
ION Setup is a meter configuration tool that can be downloaded for free atwww.schneider-electric.com.
See the ION Setup online help or in the ION Setup device configuration guide. Todownload a copy, go to www.schneider-electric.com and search for ION Setupdevice configuration guide.
Firmware considerationThis user manual is written to be used with meter firmware 1.00.00 or later.
NHA2778902–00 13
Harware References
Harware References
PM2200 meter models and accessoriesThe meter is available in several different models with optional accessories thatprovide various mounting options.
Meter models
Model Commercial reference Description
PM2210 METSEPM2210 Front panel mount, 96 x 96 mm form factor, EasyLogic VAF Powerand Energy meter with THD and POP. Complies with accuracy class1.
PM2220 METSEPM2220 Front panel mount, 96 x 96 mm form factor, EasyLogic VAF Powerand Energy meter with RS-485 communication and odd harmonicsup to 15th order. Complies with accuracy class 1.
PM2230 METSEPM2230 Front panel mount, 96 x 96 mm form factor, EasyLogic VAF Powerand Energy meter with RS-485 communication and odd harmonicsup to 31st order. Complies with accuracy class 0.5S.
Meter accessories
Model Commercial reference Description
2 Channel Digital InputOutput Module
METSEPM2KDGTLIO22 Digital I/O module with 2 channel input and output.
2 Channel Analog InputOutput Module
METSEPM2KANLGIO22 Analog I/O module with 2 channel input and output.
1 Channel Analog InputOutput Module
METSEPM2KANLGIO11 Analog I/O module with single channel input and output.
NOTE: The I/O modules are supported by PM2230/PM2130 meter models only.
See the PM2000 series catalog pages, available from www.schneider-electric.com,or consult your local Schneider Electric representative for information aboutmounting adapters available for your meter.
Supplemental informationThis document is intended to be used in conjunction with the installation sheet thatships in the box with your meter and accessories.
See your device’s installation sheet for information related to installation.
See your product’s technical datasheet at www.schneider-electric.com for the mostup-to-date and complete specifications.
See your product’s catalog pages at www.schneider-electric.com for informationabout your device, its options and accessories.
You can download updated documentation from www.schneider-electric.com orcontact your local Schneider Electric representative for the latest information aboutyour product.
LED indicatorsThe LED indicators alert or inform you of meter activity.
14 NHA2778902–00
Harware References
A Alarm / energy pulsing LED
B Heartbeat / serial communications LED
Alarm / energy pulsing LED
The alarm / energy pulsing LED can be configured for alarm notification or energypulsing.
When configured for alarm notification, this LED blinks every one second indicatingthat a high, medium or low priority alarm is tripped. The LED provides a visualindication of an active alarm condition or an inactive but unacknowledged highpriority alarm.
When configured for energy pulsing, this LED flashes at a rate proportional to theamount of energy consumed. This is typically used to verify the power meter’saccuracy.
Heartbeat / serial communications LED
The heartbeat / serial communications LED blinks to indicate the meter’s operationand serial Modbus communications status.
The LED blinks at a slow, steady rate to indicate the meter is operational. The LEDflashes at a variable, faster rate when the meter is communicating over a Modbusserial communications port.
You cannot configure this LED for other purposes.
NOTE: A heartbeat LED that remains lit and does not blink (or flash) can indicate ahardware problem.
Meter wiring considerationsDirect connect voltage limits
You can connect the meter’s voltage inputs directly to the phase voltage lines ofthe power system if the power system’s line-to-line or line-to-neutral voltages donot exceed the meter’s direct connect maximum voltage limits.
The meter's voltage measurement inputs are rated by the manufacturer for up to277 V L-N / 480 V L-L. However, the maximum voltage allowed for directconnection may be lower, depending on the local electrical codes and regulations.As per installation category II / III the maximum voltage on the meter voltagemeasurement inputs should not exceed 277 V L-N / 480 V L-L for CAT III and 347V L-N / 600 V L-L for CAT II.
If your system voltage is greater than the specified direct connect maximumvoltage, you must use VTs (voltage transformers) to step down the voltages.
NHA2778902–00 15
Harware References
Power systemdescription
Meter setting Symbol Direct connect maximum (UL / IEC) # of VTs (ifrequired)
Display(meter)
Display(communication)
Installationcategory III
Installationcategory II
Single-phase 2-wire line-to-neutral
1P.LN 1PH 2Wire L-N ≤ 277 V L-N ≤ 347 V L-N 1 VT
Single-phase 2-wire line-to-line
1P.LL 1PH 2Wire L-L 480 V L-L 600 V L-L 1 VT
Single-phase 3-wire line-to-linewith neutral
1P.3L 1PH 3Wire L-Lwith N
≤ 277 V L-N / 480V L-L
≤ 347 V L-N / 600V L-L
2 VT
3-phase 3-wireDeltaungrounded
3P.3L 3PH 3WireUngrounded Delta
480 V L-L 600 V L-L 2 VT
3-phase 3-wireDelta cornergrounded
3PH 3Wire CornerGrounded Delta
480 V L-L 600 V L-L 2 VT
3-phase 3-wireWye ungrounded
3PH 3WireUngrounded Wye
480 V L-L 600 V L-L 2 VT
3-phase 3-wireWye grounded
3PH 3WireGrounded Wye
480 V L-L 600 V L-L 2 VT
3-phase 3-wireWye resistance-grounded
3PH 3WireResistanceGrounded Wye
480 V L-L 600 V L-L 2 VT
3-phase 4-wireopen Deltacenter-tapped
3P.4L 3PH 4Wire Center-Tapped OpenDelta
N
240 V L-N / 480 VL-L
240 V L-N / 480 VL-L
3 VT
16 NHA2778902–00
Harware References
Power systemdescription
Meter setting Symbol Direct connect maximum (UL / IEC) # of VTs (ifrequired)
Display(meter)
Display(communication)
Installationcategory III
Installationcategory II
3-phase 4-wireDelta center-tapped
3PH 4Wire Center-Tapped Delta
N
240 V L-N / 480 VL-L
240 V L-N / 480 VL-L
3 VT
3-phase 4-wireungrounded Wye
3PH 4WireUngrounded Wye
≤ 277 V L-N / 480V L-L
≤ 347 V L-N / 600V L-L
3 VTor 2 VT
3-phase 4-wiregrounded Wye
3PH 4WireGrounded Wye
N
≤ 277 V L-N / 480V L-L
≤ 347 V L-N / 600V L-L
3 VTor 2 VT
3-phase 4-wireresistance-grounded Wye
3PH 4WireResistanceGrounded Wye
N
≤ 277 V L-N / 480V L-L
≤ 347 V L-N / 600V L-L
3 VTor 2 VT
Balanced system considerations
In situations where you are monitoring a balanced 3-phase load, you may chooseto connect only one or two CTs on the phase(s) you want to measure, and thenconfigure the meter so it calculates the current on the unconnected currentinput(s).
NOTE: For a balanced 4-wire Wye system, the meter’s calculations assume thatthere is no current flowing through the neutral conductor.
Balanced 3-phase Wye system with 2 CTs
The current for the unconnected current input is calculated so that the vector sumfor all three phases equal zero.
Balanced 3-phase Wye or Delta system with 1CT
The currents for the unconnected current inputs are calculated so that theirmagnitude and phase angle are identical and equally distributed, and the vectorsum for all three phase currents equal zero.
NOTE: You must always use 3 CTs for 3-phase 4-wire center-tapped Delta orcenter-tapped open Delta systems.
RS-485 wiringConnect the devices on the RS-485 bus in a point-to-point configuration, with the(+) and (-) terminals from one device connected to the corresponding (+) and (-)terminals on the next device.
NHA2778902–00 17
Harware References
RS-485 cable
Use a shielded 2 twisted pair or 1.5 twisted pair RS-485 cable to wire the devices.Use one twisted pair to connect the (+) and (-) terminals, and use the otherinsulated wire to connect the C terminals
The total distance for devices connected on an RS-485 bus should not exceed1200 m (4000 ft).
RS-485 terminals
C Common. This provides the voltage reference (zero volts) for the data plus and data minussignals
Shield. Connect the bare wire to this terminal to help suppress signal noise that may bepresent. Ground the shield wiring at one end only (either at the master or the last slavedevice, but not both.
- Data minus. This transmits/receives the inverting data signals.
+ Data plus. This transmits/receives the non-inverting data signals.
NOTE: If some devices in your RS-485 network do not have the C terminal, usethe bare wire in the RS-485 cable to connect the C terminal from the meter to theshield terminal on the devices that do not have the C terminal.
Pulse outputThe meter is equipped with one pulse output port (D1+, D1-).
You can configure the pulse outputs for use in the following application:• energy pulsing applications, where a receiving device determines energy usage
by counting the k_h pulses coming from the meter’s pulse output port.One pulse output can handle voltage less than or equal to 40 V DC (20 mAmaximum). For higher voltage applications, use an external relay in the switchingcircuit.
D1+
≤40V
≤20mA
D1-
(60)
(61)
I/O ModulesThe PM2230 meter supports additional I/O modules. This section supplements theoption module installation sheets and provides additional information regardingphysical characteristics and capabilities of the I/O module.
The I/O modules come in the following variants:• Single channel analog I/O module• Two channel analog I/O module• Two channel digital I/O module
Configuring optional I/O module using ION Setup
You can configure the optional I/O module using ION Setup.
18 NHA2778902–00
Harware References
The available analog and digital I/O modules can be connected to the base of yourmeter.
Calculate your zero scale and full scale values based on the analog source and theinput range of your meter.
Make sure that the input port that you want to use is properly configured andconnected to a valid external signal source.
1. Start ION Setup and connect to your meter.
2. Open I/O Setup and select the required input or output parameter you want toconfigure.
3. Select an input or output channel and click Edit. The setup screen is displayed.4. Configure the parameter and click OK.
Below are the associated parameter lists for analog IO:• Current: Phase wise• Current Average• Current Unbalance: Phase wise• Current Unbalance Worst• Voltage L-L: Phase wise• Voltage L-L Avg• Voltage L-N: Phase wise• Voltage L-N Avg• Voltage Unbalance L-L: Phase wise• Voltage Unbalance L-LWorst• Voltage Unbalance L-N: Phase wise• Voltage Unbalance L-N Worst• Active Power: Phase wise• Active Power Total• Reactive Power: Phase wise• Reactive Power Total• Apparent Power: phase wise• Apparent Power Total• PF Total• Frequency
NHA2778902–00 19
Meter Display
Meter Display
Display overviewThe display (integrated or remote) lets you use the meter to perform various taskssuch as setting up the meter, displaying data screens, acknowledging alarms, orperforming resets.
C
G EF
D
B
A
H
A Navigation / menu selectionbuttons
B Heartbeat / communicationsLED (green)
C Alarm / energy pulsing LED(orange)
D Navigation symbols or menuoptions
E Right notification area
F Screen title
G Left notification area
H Cursor
LED indicatorsThe LED indicators alert or inform you of meter activity.
A Alarm / energy pulsing LED
B Heartbeat / serial communications LED
Alarm / energy pulsing LED
The alarm / energy pulsing LED can be configured for alarm notification or energypulsing.
When configured for alarm notification, this LED blinks every one second indicatingthat a high, medium or low priority alarm is tripped. The LED provides a visualindication of an active alarm condition or an inactive but unacknowledged highpriority alarm.
When configured for energy pulsing, this LED flashes at a rate proportional to theamount of energy consumed. This is typically used to verify the power meter’saccuracy.
Heartbeat / serial communications LED
The heartbeat / serial communications LED blinks to indicate the meter’s operationand serial Modbus communications status.
20 NHA2778902–00
Meter Display
The LED blinks at a slow, steady rate to indicate the meter is operational. The LEDflashes at a variable, faster rate when the meter is communicating over a Modbusserial communications port.
You cannot configure this LED for other purposes.
NOTE: A heartbeat LED that remains lit and does not blink (or flash) can indicate ahardware problem.
Notification iconsTo alert you about meter state or events, notification icons appear at the top left ortop right corner of the display screen.
Icon Description
The wrench icon indicates that the power meter is in an overvoltagecondition or requires maintenance. It could also indicate that theenergy LED is in an overrun state.
The alarm icon indicates an alarm condition has occurred.
Meter display languageIf your meter is equipped with a display screen, you can configure the meter todisplay the measurements in one of several languages.
The following languages are available:• English• French• Spanish• German• Portuguese• Russian• Chinese
Meter screen navigationThe meter’s buttons and display screen allow you to navigate data and setupscreens, and to configure the meter’s setup parameters.
A Press the button below theappropriate menu to view thatscreen
B Press the right arrow to viewmore screens
C In setup mode, a small rightarrow indicates the selectedoption
D In setup mode, a small downarrow indicates that there areadditional parameters to display.The down arrow disappearswhen there are no moreparameters to display.
E In setup mode, press the buttonunder Edit to change thatsetting
NHA2778902–00 21
Meter Display
Navigation symbols
Navigation symbols indicate the functions of the associated buttons on yourmeter’s display.
Symbol Description Actions
Right arrow Scroll right and display more menu items or move cursorone character to the right
Up arrow Exit screen and go up one level
Small downarrow
Move cursor down the list of options or display more itemsbelow
Small up arrow Move cursor up the list of items or display more itemsabove
Left arrow Move cursor one character to the left
Plus sign Increase the highlighted value or show the next item in thelist.
Minus sign Show the previous item in the list
When you reach the last screen, press the right arrow again to cycle through thescreen menus.
Meter screen menus overview
All meter screens are grouped logically, according to their function.
You can access any available meter screen by first selecting the Level 1 (top level)screen that contains it.
Level 1 screen menus - IEEE title [IEC title]
Maint
Amps [I] Volts [U-V] Energy [E] PF Hz [F]
Clock
Power [PQS] THD
UnbalMnMxAlarmTimer
Harm
Rate 12AM I/O
Setting up the displayYou can change the display screen’s settings, such as contrast, backlight timeout,and screen timeout .
1. Navigate toMaint > Setup.2. Enter the setup password (default is “0”), then press OK.3. Navigate to HMI > Disp.4. Move the cursor to point to the parameter you want to modify, then press Edit.5. Modify the parameter as required, then press OK.6. Move the cursor to point to the next parameter you want to modify, press Edit,
make your changes, then press OK.7. Press the up arrow to exit.
22 NHA2778902–00
Meter Display
8. Press Yes to save your changes.
Display settings available using the display
Parameter Values Description
Contrast 1 - 9 Increase or decrease the value to increase or decreasethe display contrast.
Bcklght Timeout(min)
0 - 60 Set how long (in minutes) before the backlight turns offafter a period of inactivity. Setting this to “0” disables thebacklight timeout feature (i.e., backlight is always on).
Screen Timeout(min)
0 - 60 Set how long (in minutes) before the screen turns offafter a period of inactivity. Setting this to “0” disables thescreen timeout feature (i.e., display is always on).
To configure the display using ION Setup, see the “PM2000” topic in the IONSetup online help or in the ION Setup device configuration guide, available fordownload at www.schneider-electric.com.
NHA2778902–00 23
Basic setup
Basic setup
Configuring basic setup parameters using the displayYou can configure basic meter parameters using the display.
Proper configuration of the meter’s basic setup parameters is essential foraccurate measurement and calculations. Use the Basic Setup screen to define theelectrical power system that the meter is monitoring.
If standard (1-sec) alarms have been configured and you make subsequentchanges to the meter’s basic setup, all alarms are disabled to prevent undesiredalarm operation.
NOTICEUNINTENDED EQUIPMENT OPERATION• Verify all standard alarms settings are correct and make adjustments as
necessary.• Re-enable all configured alarms.Failure to follow these instructions can result in equipment damage.
After saving the changes, confirm all configured standard alarm settings are stillvalid, reconfigure them as required, and re-enable the alarms.
1. Navigate toMaint > Setup.2. Enter the setup password (default is “0”), then press OK.3. Navigate toMeter > Basic.4. Move the cursor to point to the parameter you want to modify, then press Edit.5. Modify the parameter as required, then press OK.6. Move the cursor to point to the next parameter you want to modify, press Edit,
make your changes, then press OK.
24 NHA2778902–00
Basic setup
7. Press Yes to save your changes.
Basic setup parameters available using the display
Values Description
Power SystemSelect the power system type (power transformer) the meter is wired to.
1PH2W LN Single-phase 2-wire line-to-neutral
1PH2W LL Single-phase 2-wire line-to-line
1PH3W LL with N Single-phase 3-wire line-to-line with neutral
3PH3W Dlt Ungnd 3-phase 3-wire ungrounded delta
3PH3W Dlt Crnr Gnd 3-phase 3-wire corner grounded delta
3PH3WWye Ungnd 3-phase 3-wire ungrounded wye
3PH3WWye Gnd 3-phase 3-wire grounded wye
3PH3WWye Res Gnd 3-phase 3-wire resistance-grounded wye
3PH4W Opn Dlt Ctr Tp 3-phase 4-wire center-tapped open delta
3PH4W Dlt Ctr Tp 3-phase 4-wire center-tapped delta
3PH4WWye Ungnd 3-phase 4-wire ungrounded wye
3PH4WWye Gnd 3-phase 4-wire grounded wye
3PH4WWye Res Gnd 3-phase 4-wire resistance-grounded wye
VT ConnectSelect how many voltage transformers (VT) are connected to the electrical power system.
Direct Con Direct connect; no VTs used
2VT 2 voltage transformers
3VT 3 voltage transformers
VT Primary (V)
1 to 1,000,000 Enter the size of the VT primary, in Volts.
VT Secondary (V)
100, 110, 115, 120 Select the size of the VTsecondary, in Volts.
CTon TerminalDefine how many current transformers (CT) are connected to the meter, and which terminals they are connected to.
I1 1 CTconnected to I1 terminal
I2 1 CTconnected to I2 terminal
I3 1 CTconnected to I3 terminal
I1 I2 2 CTconnected to I1, I2 terminals
I2 I3 2 CTconnected to I1, I3 terminals
I1 I3 2 CTconnected to I2, I3 terminals
I1 I2 I3 3 CTconnected to I1, I2, I3 terminals
CT Primary (A)
1 to 32767 Enter the size of the CT primary, in Amps.
CT Secondary (A)
1, 5 Select the size of the CTsecondary, in Amps.
Sys Frequency (Hz)
50, 60 Select the frequency of the electrical power system, in Hz.
Phase Rotation
ABC, CBA Select the phase rotation of the 3-phase system.
NHA2778902–00 25
Basic setup
Configuring advanced setup parameters using the displayYou can configure a subset of advanced parameters using the display.
1. Navigate toMaint > Setup.2. Enter the setup password (default is “0”), then press OK.3. Navigate toMeter > Advan.4. Move the cursor to point to the parameter you want to modify, then press Edit.5. Modify the parameter as required, then press OK.6. Move the cursor to point to the next parameter you want to modify, press Edit,
make your changes, then press OK.7. Press Yes to save your changes.
Advanced setup parameters available using the display
Parameter Values Description
Label — This label identifies the device, e.g., “Power Meter”. Youcannot use the display to edit this parameter. Use IONSetup to change the device label.
Load TimerSetpt (A)
0 - 9 Specifies the minimum average current at the loadbefore the timer starts. The meter begins counting thenumber of seconds the load timer is on (i.e., wheneverthe readings are equal to or above this average currentthreshold.
Pk I dmd forTDD (A)
0 - 9 Specifies the minimum peak current demand at the loadfor inclusion in total demand distortion (TDD)calculations. If the load current is below the minimumpeak current demand threshold, the meter does not usethe readings to calculate TDD. Set this to “0” (zero) if youwant the power meter to use the metered peak currentdemand for this calculation.
Setting the rateThe Rate setup screens allow you to set the different rate parameters.
1. Navigate toMaint > Setup.2. Enter the setup password (default is “0”), then press OK.3. Navigate to Rate.4. Move the cursor to point to Rate1 or Rate2 to modify, then press Edit.5. Move the cursor to point to Channel or Factor per (k__h) to modify, then press
Edit.6. Modify the parameter as required, then press OK.7. Press up arrow and press Yes to save your changes.
26 NHA2778902–00
Basic setup
8. Press the up arrow to exit.
Parameter Values Description
Label Rate1: CO2EmissionRate2: EnergyCost
You can edit the label using ION Setup
Channel None, ActiveDel, Active Rec,Active Del +Rec, ReactiveDel, ReactiveRec, ReactiveDel + Rec,Apparent Del,Apparent Rec,Apparent Del +Rec
Select a channel from the list.
Factor per (k__h)
0.000 to99999.999
You can edit the factor value between 0.000 to99999.999.
To configure the Rate using ION Setup, see the “PM2000 series meter” topic inthe ION Setup online help or in the ION Setup device configuration guide,available for download at www.schneider-electric.com.
Setting up regional settingsYou can change the regional settings to localize the meter screens and displaydata in a different language, using local standards and conventions.
NOTE: In order to display a different language other than those listed in theLanguage setup parameter, you need to download the appropriate language file tothe meter using the firmware upgrade process.
1. Navigate toMaint > Setup.2. Enter the setup password (default is “0”), then press OK.3. Navigate to HMI > Region.4. Move the cursor to point to the parameter you want to modify, then press Edit.5. Modify the parameter as required, then press OK.6. Move the cursor to point to the next parameter you want to modify, press Edit,
make your changes, then press OK.7. Press the up arrow to exit.
8. Press Yes to save your changes.
Regional settings available using the display
Parameter Values Description
Language English US,French,Spanish,German,Portuguese,Chinese,Russian
Select the language you want the meter to display.
Date Format MM/DD/YY, YY/MM/DD, DD/MM/YY
Set how you want the date to be displayed, e.g., month/day/year.
Time Format 24Hr, AM/PM Set how you want the time to be displayed, e.g.,17:00:00 or 5:00:00 PM.
HMI Mode IEC, IEEE Select the standards convention used to display menunames or meter data.
NHA2778902–00 27
Basic setup
Setting up the screen passwordsIt is recommended that you change the default password in order to preventunauthorized personnel from accessing password-protected screens such as thediagnostics and reset screens.
This can only be configured through the front panel. The factory-default setting forall passwords is “0” (zero).
1. Navigate toMaint > Setup.2. Enter the setup password (default is “0”), then press OK.3. Navigate to HMI > Pass.4. Move the cursor to point to the parameter you want to modify, then press Edit.
Parameter Values Description
Setup 0000 - 9999 Sets the password for accessing the meter setupscreens (Maint > Setup).
Energy Resets 0000 - 9999 Sets the password for resetting the meter’s accumulatedenergy values.
Demand Resets 0000 - 9999 Sets the password for resetting the meter’s recordedpeak demand values.
Min/Max Resets 0000 - 9999 Sets the password for resetting the meter’s recordedminimum and maximum values.
5. Modify the parameter as required, then press OK.6. Move the cursor to point to the next parameter you want to modify, press Edit,
make your changes, then press OK.7. Press the up arrow to exit.
8. Press Yes to save your changes.
Lost password
Visit www.schneider-electric.com for support and assistance with lost passwordsor other technical problems with the meter.
Make sure you include your meter’s model, serial number and firmware version inyour email or have it readily available if calling Technical Support.
Setting the clock
The Clock setup screens allow you to set the meter’s date and time.
1. Navigate toMaint > Setup.2. Enter the setup password (default is “0”), then press OK.3. Navigate to Clock.4. Move the cursor to point to the parameter you want to modify, then press Edit.5. Modify the parameter as required, then press OK.6. Press Yes to save your changes.7. Move the cursor to point to the next parameter you want to modify, press Edit,
make your changes, then press OK.8. Press the up arrow to exit.
28 NHA2778902–00
Basic setup
9. Press Yes to save your changes.
Parameter Values Description
Date DD/MM/YY, MM/DD/YY, YY/MM/DD
Set the current date using the format displayed onscreen, where DD = day, MM = month and YY = year.
Time HH:MM:SS (24hour format),HH:MM:SS AMor PM
Use the 24-hour format to set the current time in UTC(GMT).
Meter Time GMT, Local Select GMT to display the current time in UTC(Greenwich Mean Time zone). To display local time, setthis parameter to Local, then use GMT Offset (h) todisplay local time in the proper time zone.
To configure the clock using ION Setup, see the “PM2000 series meter” topic inthe ION Setup online help or in the ION Setup device configuration guide,available for download at www.schneider-electric.com.
NHA2778902–00 29
Alarms
Alarms
Alarms overviewAn alarm is the meter’s means of notifying you when an alarm condition isdetected, such as an error or an event that falls outside of normal operatingconditions.
You can configure your meter to generate and display high, medium and lowpriority alarms when predefined events are detected in the meter’s measuredvalues or operating states. Your meter also logs the alarm event information. Yourmeter comes with many alarms. Some alarms are preconfigured, while othersneed to be configured before your meter can generate alarms. Your meter’s defaultalarms can be customized, as needed, such as changing the priority. You cancreate custom alarms using the advanced features of your meter.
Alarm typesYour meters supports a number of different alarm types.
Type Number
Unary 4
Digital 2
Standard 14
Unary alarmsA unary alarm is the simplest type of alarm — it monitors a single behavior, eventor condition.
Available unary alarms
Your meter has a set of 4 unary alarms.
Alarm label Description
Meter Power Up Meter powers on after losing control power.
Meter Reset Meter resets for any reason.
Meter Diagnostic Meter’s self-diagnostic feature detects a problem.
Phase Reversal Meter detects a phase rotation different than expected.
Digital alarmsDigital alarms monitor the ON or OFF state of the meter’s digital inputs.
Digital alarm with setpoint delay
To prevent false triggers from erratic signals, you can set up pickup and dropouttime delays for the digital alarm.
30 NHA2778902–00
Alarms
EV1 EV2
0
1∆T1 ∆T2
∆T3
A Pickup setpoint (1 = ON) ΔT2 Dropout time delay (in seconds)
B Dropout setpoint (0 = OFF) EV2 End of alarm condition
ΔT1 Pickup time delay (in seconds) ΔT3 Alarm duration (in seconds)
EV1 Start of alarm condition
NOTE: To prevent filling the alarm log with nuisance alarm trips, the digital alarm isautomatically disabled if the digital input changes state more than 4 times in onesecond or more than 10 times in ten seconds.
Available digital alarms
Your meter has a set of 2 digital alarms.
Alarm label Description
Digital Alarm S1 Digital input 1
Digital Alarm S2 Digital input 2
Standard alarmsStandard alarms are setpoint-driven alarms monitor certain behaviors, events orunwanted conditions in your electrical system.
Standard alarms have a detection rate equal to the 50/60 meter cycle, which isnominally 1 second if the meter’s frequency setting is configured to match thesystem frequency (50 or 60 Hz).
Many of the standard alarms are three-phase alarms. Alarm setpoints areevaluated for each of the three phases individually, but the alarm is reported as asingle alarm. The alarm pickup occurs when the first phase exceeds the alarmpickup magnitude for the pickup time delay. The alarm is active as long as anyphase remains in an alarm state. The alarm dropout occurs when the last phasedrops below the dropout magnitude for the dropout time delay.
Example of over and under setpoint (standard) alarm operation
The meter supports over and under setpoint conditions on standard alarms.
A setpoint condition occurs when the magnitude of the signal being monitoredcrosses the limit specified by the pickup setpoint setting and stays within that limitfor a minimum time period specified by the pickup time delay setting.
The setpoint condition ends when the magnitude of the signal being monitoredcrosses the limit specified by dropout setpoint setting and stays within that limit fora minimum time period specified by dropout time delay setting.
Over setpoint
When the value rises above the pickup setpoint setting and remains there longenough to satisfy the pickup time delay period (ΔT1), the alarm condition is set toON. When the value falls below the dropout setpoint setting and remains there
NHA2778902–00 31
Alarms
long enough to satisfy the dropout time delay period (ΔT2), the alarm condition isset to OFF.
EV1 EV2
∆T1∆T2
∆T3
Max1
Max2
A Pickup setpoint
B Dropout setpoint
ΔT1 Pickup time delay period (in seconds)
EV1 Start of alarm condition
ΔT2 Dropout time delay (in seconds)
EV2 End of alarm condition
ΔT3 Alarm duration (in seconds)
Max1 Maximum value recorded during pickup period
Max2 Maximum value recorded during alarm period
The meter records the date and time when the alarm event starts (EV1) and whenit ends (EV2). The meter also performs any task assigned to the event, such asoperating a digital output. The meter also records maximum values (Max1, Max2)before, during or after the alarm period.
Under setpoint
When the value falls below the pickup setpoint setting and remains there longenough to satisfy the pickup time delay period (ΔT1), the alarm condition is set toON. When the value rises above the dropout setpoint setting and remains therelong enough to satisfy the dropout time delay period (ΔT2), the alarm condition isset to OFF.
EV1 EV2
∆T1
∆T2
∆T3
Min1Min2
A Pickup setpoint
B Dropout setpoint
ΔT1 Pickup time delay period (in seconds)
EV1 Start of alarm condition
ΔT2 Dropout time delay (in seconds)
EV2 End of alarm condition
ΔT3 Alarm duration (in seconds)
Min1 Maximum value recorded during pickup period
Min2 Maximum value recorded during alarm period
The meter records the date and time when the alarm event starts (EV1) and whenit ends (EV2). The meter also performs any task assigned to the event, such asoperating a digital output. The meter also records minimum values (Min1, Min2)before, during or after the alarm period.
Maximum allowable setpoint
The meter is programmed to help prevent user data entry errors, with set limits forthe standard alarms.
The maximum setpoint value you can enter for some of the standard alarmsdepends on the voltage transformer ratio (VT ratio), current transformer ratio (CTratio), system type (i.e., number of phases) and/or the maximum voltage andmaximum current limits programmed at the factory.
NOTE: VT ratio is the VT primary divided by the VTsecondary and CT ratio is theCT primary divided by the CTsecondary.
32 NHA2778902–00
Alarms
Standard alarm Maximum setpoint value
Over Phase Current (maximum current) x (CT ratio)
Under Phase Current (maximum current) x (CT ratio)
Over Voltage L-L (maximum voltage) x (VT ratio)
Under Voltage L-L (maximum voltage) x (VT ratio)
Over Voltage L-N (maximum voltage) x (VT ratio)
Under Voltage L-N (maximum voltage) x (VT ratio)
Over Active Power (maximum voltage) x (maximum current) x (number of phases)
Over Reactive Power (maximum voltage) x (maximum current) x (number of phases)
Over Apparent Power (maximum voltage) x (maximum current) x (number of phases)
Available standard alarms
Your meter has a set of standard alarms.
NOTE: Some alarms do not apply to all power system configurations. For example,line-to-neutral voltage alarms cannot be enabled on 3-phase delta systems. Somealarms use the system type and the VTor CT ratio to determine the maximumallowed setpoint.
Alarm label Valid range and resolutionUnits
ION Setup Display ION Setup Display
Over Phase Current Over Current, Ph 0.000 to 99999.000 0 to 99999 A
Under Phase Current Under Current, Ph 0.000 to 99999.000 0 to 99999 A
Over Voltage L-L Over Voltage, L-L 0.00 to 999999.00 0 to 999999 V
Under Voltage L-L Under Voltage, L-L 0.00 to 999999.00 0 to 9999999 V
Over Voltage L-N Over Voltage, L-N 0.00 to 999999.00 0 to 9999999 V
Under Voltage L-N Under Voltage L-N 0.00 to 999999.00 0 to 9999999 V
Over Active Power Over kW 0.0 to 9999999.0 0 to 9999999 kW
Over Reactive Power Over kVAR 0.0 to 9999999.0 0 to 9999999 kVAR
Over Apparent Power Over kVA 0.0 to 9999999.0 0 to 9999999 kVA
Leading True PF Lead PF, True -1.00 to -0.01 and 0.01 to 1.00 —
Lagging True PF Lag PF, True -1.00 to -0.01 and 0.01 to 1.00 —
Over Frequency Over Frequency 0.000 to 99.000 Hz
Under Frequency Under Frequency 0.000 to 99.000 Hz
Over Voltage THD Over Voltage THD 0.000 to 99 %
Power factor (PF) alarms
You can set up a Leading PF or Lagging PF alarm to monitor when the circuit’spower factor goes above or below the threshold you specify.
The Leading PF and Lagging PF alarms use the power factor quadrants as thevalues on the y-axis, with quadrant II on the lowest end of the scale, followed byquadrant III, quadrant I, and finally quadrant IV on the highest end of the scale.
Quadrant PF values Lead/Lag
II 0 to -1 Leading (capacitive)
III -1 to 0 Lagging (inductive)
NHA2778902–00 33
Alarms
Quadrant PF values Lead/Lag
I 0 to 1 Lagging (inductive)
IV 1 to 0 Leading (capacitive)
Leading PF alarm
The Leading PF alarm monitors an over setpoint condition.
∆T3∆T2
∆T1
EV1 EV2
II
IV
I
III
0
-1
0
+1
0
A Pickup setpoint ΔT2 Dropout time delay (in seconds)
B Dropout setpoint EV2 End of alarm condition
ΔT1 Pickup delay period (in seconds) ΔT3 Alarm duration (in seconds)
EV1 Start of alarm condition
Lagging PF alarm
The Lagging PF alarm monitors an under setpoint condition.
II
IV ∆T3
∆T2
∆T1
EV1 EV2
I
III
0
-1
0
+1
0
A Pickup setpoint ΔT2 Dropout time delay (in seconds)
B Dropout setpoint EV2 End of alarm condition
ΔT1 Pickup delay period (in seconds) ΔT3 Alarm duration (in seconds)
EV1 Start of alarm condition
Alarm prioritiesEach alarm has a priority level that you can use to distinguish between events thatrequire immediate action and those that do not require action.
Alarm priority Alarm display notification and recording method
Alarm LED Alarm icon Alarm details Alarm logging
High Blinks while the alarm isactive.
Blinks while the alarm isactive. Alarm icon remainsdisplayed untilacknowledged.
Click Details to displaywhat caused the alarm topickup or drop off. ClickAck to acknowledge thealarm.
Recorded in alarm log.
Medium Blinks while the alarm isactive.
Blinks while the alarm isactive.
Click Details to displaywhat caused the alarm topickup or drop off.
Recorded in alarm log.
34 NHA2778902–00
Alarms
Alarm priority Alarm display notification and recording method
Alarm LED Alarm icon Alarm details Alarm logging
Low Blinks while the alarm isactive.
Blinks while the alarm isactive.
Click Details to displaywhat caused the alarm topickup or drop off.
Recorded in alarm log.
None No activity None None Recorded in event logonly.
NOTE: The alarm LED notification only occurs if the alarm / energy pulsing LED isconfigured for alarming.
Multiple alarm considerations
If multiple alarms with different priorities are active at the same time, the displayshows the alarms in the order they occurred.
Alarm setup overviewYou can use ION Setup to configure unary, digital or standard (1-Sec) alarms.
If you make changes to the basic meter setup, all alarms are disabled to preventundesired alarm operation.
NOTICEUNINTENDED EQUIPMENT OPERATION• Verify all alarm settings are correct and make adjustments as necessary.• Re-enable all configured alarms.Failure to follow these instructions can result in incorrect alarm functions.
Built-in error-checking
ION Setup dynamically checks incorrect setup combinations. When you enable analarm, you must set up the pickup and dropout limits to acceptable values first inorder to exit the setup screen.
Setting up alarms using ION Setup
You can use ION Setup to create and set up alarms.
1. Start ION Setup and connect to your meter.
2. Open the Alarming screen.3. Select the alarm you want to configure and click Edit.4. Configure the setup parameters as explained in the different alarm setup
sections.
See the ION Setup Device Configuration guide for more information.
Unary alarm setup parameters
Configure the unary alarm setup parameters as required.
ION Setup controls are shown in parentheses.
NHA2778902–00 35
Alarms
Setting Option or range Description
Enable Yes (checked) or No (cleared) This enables or disables the alarm.
Priority High, Medium, Low, None This sets the alarm priority and notificationoptions.
Select Dig Output (Outputs) NoneDigital Output D1Digital Output D2Digital Output D1 & D2
Select the digital output(s) you want tocontrol when the alarm is triggered.
Digital alarm setup parameters
Configure the digital alarm setup parameters as required.
ION Setup controls are shown in parentheses.
Setting Option or range Description
Enable Yes (checked) or No (cleared) This enables or disables the alarm.
Priority High, Medium, Low, None This sets the alarm priority and notificationoptions.
Pickup Setpoint (Setpoint Pickup) On, Off Use this setting to control when to trip thealarm, based on the state of the digital input(On or Off).
Pickup Time Delay (Delay) 0 to 999999 This specifies the number of seconds thedigital input must be in the alarm pickupstate before the alarm is tripped.
Dropout Time Delay (Setpoint DropoutDelay)
0 to 999999 This specifies the number of seconds thedigital input must be out of the alarm pickupstate before the alarm turns off.
Select Dig Output (Outputs) NoneDigital Output D1Digital Output D2Digital Output D1 & D2
Select the digital output(s) you want tocontrol when the alarm is triggered.
Standard (1-Sec) alarm setup parameters
Configure the standard alarm setup parameters as required.
ION Setup controls are shown in parentheses.
NOTE: It is recommended that you use ION Setup to configure standard (1-Sec)alarms. ION Setup supports a higher resolution to allow you to specify moredecimal places when setting up the pickup setpoint and dropout setpoint values forcertain measurements.
Setting Option or range Description
Enable Yes (checked) or No (cleared) This enables or disables the alarm.
Priority High, Medium, Low, None This sets the alarm priority and notificationoptions.
Pickup Setpoint (Pickup Limit) Varies depending on the standard alarm youare setting up
This is the value (magnitude) you define asthe setpoint limit for triggering the alarm. For“over” conditions, this means the value hasgone above the Pickup limit. For “under”conditions, this means the value has gonebelow the Pickup limit.
Pickup Time Delay (Delay) 0 to 999999 This specifies the number of seconds thesignal must stay above the pickup setpoint(for “over” conditions), or below the pickupsetpoint (for “under” conditions) before thealarm is tripped.
Dropout Setpoint (Dropout Limit) Varies depending on the standard alarm youare setting up
This is the value (magnitude) you define asthe limit for dropping out of the alarmcondition. For “over” conditions, this means
36 NHA2778902–00
Alarms
Setting Option or range Description
the value has gone below the Dropout limit.For “under” conditions, this means the valuehas gone above the Pickup limit.
Dropout Time Delay (Delay) 0 to 999999 This specifies the number of seconds thesignal must stay below the dropout setpoint(for “over” conditions), or above the dropoutsetpoint (for “under” conditions) before thealarm condition is ended.
PU Set Point Lead/Lag (Lead, Lag) Lead or Lag Applies to PF (power factor) alarms only.Use this to set the PF value and quadrant toset the pickup setpoint for an over PFcondition (PF Leading) or under PFcondition (PF Lagging).
DO Set Point Lead/Lag (Lead, Lag) Lead or Lag Applies to PF (power factor) alarms only.Use this to set the PF value and quadrant toset the dropout setpoint for an over PFcondition (PF Leading) or under PFcondition (PF Lagging).
Select Dig Output (Outputs) NoneDigital Output D1Digital Output D2Digital Output D1 & D2
Select the digital output(s) you want tocontrol when the alarm is triggered.
LED alarm indicatorYou can use the meter’s alarm / energy pulsing LED as an alarm indicator.
When set to detect alarms, the LED blinks to indicate an alarm condition.
Configuring the LED for alarms using the display
You can use the meter display to configure the alarm / energy pulsing LED foralarming.
1. Navigate to theMaint > Setup > LED.2. Set the mode to Alarm, then press OK.3. Press the up arrow to exit. Press Yes to save your changes.
Configuring the LED for alarms using ION Setup
You can use the ION Setup to configure your meter’s LED for alarming.
1. Open ION Setup and connect to your meter. See the ION Setup Help forinstructions.
2. Navigate to Energy Pulsing.3. Select Front Panel LED and click Edit.4. Set the control mode to Alarm and click OK.5. Click Send to save your changes.
Alarm display and notificationThe meter notifies you when an alarm condition is detected.
NHA2778902–00 37
Alarms
Alarm icon
When a low, medium or high priority alarm is tripped, this symbol appears at thetop right corner of the display screen, indicating that an alarm is active:
For high priority alarms, the alarm icon remains displayed until you acknowledgethe alarm.
Alarm / energy pulsing LED
If configured for alarming, the alarm / energy pulsing LED also flashes to indicatethe meter has detected an alarm condition.
Alarm screens
If your meter is equipped with a display, you can use the buttons to navigate to thealarm setup or display screens.
Active alarms
When a pickup event occurs, the active alarm list appears on the meter display’sActive Alarms screen. Press Detail to see more event information.
Alarm details
Details about the alarms can be viewed using:• the active alarms (Active), alarm history (Hist), alarm counters (Count) and
unacknowledged alarms (Unack) screens on the meter display, or
Active alarms list and alarm history logEach occurrence of a low, medium or high priority alarm is stored in the activealarms list and recorded in the alarm history log.
The active alarm list holds 40 entries at a time. The list works as a circular buffer,replacing old entries as new entries over 40 are entered into the active alarms list.The information in the active alarms list is volatile and reinitializes when the meterresets.
The alarm history log holds 40 entries. The log also works as a circular buffer,replacing old entries with new entries. The information in the alarm history log isnonvolatile and is retained when the meter resets.
Viewing active alarm details using the display
When an alarm condition becomes true (alarm = ON), the alarm is displayed on theactive alarms screen.
Alarms are displayed sequentially in the order of their occurrence, regardless ofpriority. The alarm details show the date and time of the alarm event, the type ofevent (for example, pickup or unary), which phase the alarm condition wasdetected on, and the value that caused the alarm condition.
NOTE: Alarm details are not available if the alarm priority is set to None.
The alarm details (for low, medium and high priority alarms) are also recorded inthe alarm history log.
38 NHA2778902–00
Alarms
1. Navigate to Alarm > Active.2. Select the alarm you want to view (the latest ones appear on top).
3. Press Detail.
NOTE: For unacknowledged high priority alarms, the Ack option appears onthis screen. Press Ack to acknowledge the alarm, or return to the previousscreen if you do not want to acknowledge the alarm.
Viewing alarm history details using the display
The alarm history log keeps a record of active alarms and past alarms.
When an active alarm condition becomes false (alarm = OFF), the event isrecorded in the alarm history log and alarm notification (alarm icon, alarm LED) isturned off.
Alarms are displayed sequentially in the order of their occurrence, regardless ofpriority. The alarm details show the date and time of the alarm event, the type ofevent (for example, dropout or unary), which phase the alarm condition wasdetected on, and the value that caused the alarm condition to turn ON or OFF.
NOTE: Alarm details are not available if the alarm priority is set to None.
1. Navigate to Alarm > Hist.2. Select the alarm you want to view (the latest ones appear on top).
3. Press Detail.
NOTE: For unacknowledged high priority alarms, the Ack option appears onthis screen. Press Ack to acknowledge the alarm, or return to the previousscreen if you do not want to acknowledge the alarm.
Alarms countersEvery occurrence of each type of alarm is counted and recorded in the meter.
Alarms rollover value
The alarm counters roll over to zero after reaching the value 9999.
Resetting alarms using ION SetupUse ION Setup to reset alarms.
You can also reset alarms using the meter display.
1. Connect to your meter in ION Setup.
2. Open theMeter Resets screen.3. Select the alarm parameters to clear and click Reset.
NHA2778902–00 39
Meter logging
Meter logging
Logs overviewThis chapter briefly describes the following logs of the meter:• Alarm log• User-defined data logLogs are files stored in the non-volatile memory of the meter and are referred to as“on-board logs”.
Setting up the data logYou can select up to 13 items to record in the data log and the frequency (logginginterval) that you want those values updated.
Use ION Setup to configure data logging.
NOTICEDATA LOSS
Save the contents of the data log before configuring it.
Failure to follow these instructions can result in data loss.
1. Start ION Setup and open your meter in setup screens mode (View > SetupScreens). See the ION Setup Help for instructions.
2. Double-click Data Log #1.3. Set up the logging frequency and measurements/data to log.
4. Click Send to save the changes to the meter.
Parameter Values Description
Status Enable, Disable Set this parameter to enableor disable data logging in themeter.
Interval 15 minutes, 30 minutes, 60minutes
Select a time value to set thelogging frequency.
Channels Items available for loggingcan vary based on the metertype.
Select an item to record fromthe “Available” column, thenclick the double-right arrowbutton to move the item to the“Selected” column.To remove an item, select itfrom the “Selected” columnthen click the double-leftarrow button.
Saving the data log contents using ION SetupYou can use ION Setup to save the contents of the data log.
1. Start ION Setup and open your meter in data screens mode (View > DataScreens. See the ION Setup help for instructions.
2. Double-click Data Log #1 to retrieve the records.
40 NHA2778902–00
Meter logging
3. Once the records have finished uploading, right-click anywhere in the viewerand select Export CSV from the popup menu to export the entire log.
NOTE: To export only selected records in the log, click the first record you wantto export, hold down the SHIFT key and click the last record you want to export,then select Export CSV from the popup menu.
4. Navigate to the folder where you want to save the data log file, then click Save.
Alarm logAlarm records are stored in the meter’s alarm history log.
By default, the meter can log the occurrence of any alarm condition. Each time analarm occurs it is entered into the alarm log. The alarm log in the meter stores thepickup and dropout points of alarms along with the date and time associated withthese alarms. You can view and save the alarm log to disk, and reset the alarm logto clear the data out of the meter’s memory.
The meter stores alarm log data in non-volatile memory. The size of the alarm logis fixed at 40 records.
NHA2778902–00 41
Measurements and calculations
Measurements and calculations
Meter InitializationMeter Initialization is a special command that clears the meter’s energy, power,demand values, and meter operation timer.
It is common practice to initialize the meter after its configuration is completed,before adding it to an energy management system.
After configuring all the meter setup parameters, navigate through the differentmeter display screens and make sure the displayed data is valid then performmeter initialization.
NOTE: You can perform meter initialization using ION setup and securedcommand interface.
Real-time readingsThe meter measures currents and voltages, and reports in real time the RMS (RootMean Squared) values for all three phases and neutral.
The voltage and current inputs are continuously monitored at a sampling rate of 64samples per cycle. This amount of resolution helps enable the meter to providereliable measurements and calculated electrical values for various commercial,buildings and industrial applications.
Energy measurementsThe meter provides fully bi-directional, 4-quadrant energy metering.
The meter stores all accumulated active, reactive and apparent energymeasurements in nonvolatile memory:• kWh, kVARh, kVAh (delivered and received)• kWh, kVARh, kVAh net (delivered - received)• kWh, kVARh, kVAh absolute (delivered + received)All energy parameters represent the total for all three phases.
Min/max valuesWhen the readings reach their lowest or highest value, the meter updates andsaves these min/max (minimum and maximum) quantities with date and time ofoccurrence in non-volatile memory.
The meter’s real-time readings are updated once every 50 cycles for 50 Hzsystems, or once every 60 cycles for 60 Hz systems.
Power demandPower demand is a measure of average power consumption over a fixed timeinterval.
NOTE: If not specified, references to “demand” are assumed to mean “powerdemand.”
The meter measures instantaneous consumption and can calculate demand usingvarious methods.
42 NHA2778902–00
Measurements and calculations
Power demand calculation methods
Power demand is calculated by dividing the energy accumulated during a specifiedperiod by the length of that period.
How the meter performs this calculation depends on the method and timeparameters you select (for example, timed rolling block demand with a 15-minuteinterval and 5-minute subinterval).
To be compatible with electric utility billing practices, the meter provides thefollowing types of power demand calculations:• Block interval demand• Synchronized demand• Thermal demandYou can configure the power demand calculation method from the display orsoftware.
Block interval demand
For block interval demand method types, you specify a period of time interval (orblock) that the meter uses for the demand calculation.
Select/configure how the meter handles that interval from one of these differentmethods:
Type Description
Timed Sliding Block Select an interval from 1 to 60 minutes (in 1-minute increments). If theinterval is between 1 and 15 minutes, the demand calculationupdates every 15 seconds. If the interval is between 16 and 60minutes, the demand calculation updates every 60 seconds. Themeter displays the demand value for the last completed interval.
Timed Block Select an interval from 1 to 60 minutes (in 1-minute increments). Themeter calculates and updates the demand at the end of each interval.
Timed Rolling Block Select an interval and a subinterval. The subinterval must divideevenly into the interval (for example, three 5-minute subintervals for a15-minute interval). Demand is updated at the end of eachsubinterval. The meter displays the demand value for the lastcompleted interval.
Block interval demand example
The following illustration shows the different ways power demand is calculatedusing the block interval method. In this example, the interval is set to 15 minutes.
Timed Sliding Block
15 30 45 60 . . .
Demand value is the average for the last completed interval
Time (sec)
Calculation updates every 15 seconds
15-minute interval
NHA2778902–00 43
Measurements and calculations
Timed Block
15 30 45
Demand value isthe average for thelast completedinterval
Time(min)
Calculation updates atthe end of the interval
15-minute interval 15-minute interval 15-min
Timed Rolling Block
15 540320 35 4025
Demand value is the average for the last completed interval
Time(min)
Calculation updates at the end of the subinterval (5 minutes)
15-minute interval
Synchronized demand
You can configure the demand calculations to be synchronized using an externalpulse input, a command sent over communications, or the device’s internal real-time clock.
Type Description
Commandsynchronized demand
This method allows you to synchronize the demand intervals of multiplemeters on a communications network. For example, if a programmablelogic controller (PLC) input is monitoring a pulse at the end of a demandinterval on a utility revenue meter, you can program the PLC to issue acommand to multiple meters whenever the utility meter starts a newdemand interval. Each time the command is issued, the demand readingsof each meter are calculated for the same interval.
Clock synchronizeddemand
This method allows you to synchronize the demand interval to the meter’sinternal real-time clock. This helps you synchronize the demand to aparticular time, typically on the hour (for example, at 12:00 am). If youselect another time of day when the demand intervals are to besynchronized, the time must be specified in minutes from midnight. Forexample, to synchronize at 8:00 am, select 480 minutes.
NOTE: For these demand types, you can choose block or rolling block options. Ifyou select a rolling block demand option, you need to specify a subinterval.
Thermal demand
Thermal demand calculates the demand based on a thermal response, whichimitates the function of thermal demand meters.
The demand calculation updates at the end of each interval. You can set thedemand interval from 1 to 60 minutes (in 1-minute increments).
Thermal demand example
The following illustration shows the thermal demand calculation. In this example,the interval is set to 15 minutes. The interval is a window of time that moves acrossthe timeline. The calculation updates at the end of each interval.
44 NHA2778902–00
Measurements and calculations
Last completeddemand interval
Time(minutes)
next15-minute
interval
15-minuteinterval
% o
f Loa
d
99%
90%
Current demandThe meter calculates current demand using the block interval, synchronized orthermal demand methods.
You can set the demand interval from 1 to 60 minutes in 1 minute increments (forexample, 15 minutes).
Predicted demand
The meter calculates predicted demand for the end of the present interval for kW,kVAR, and kVA demand, taking into account the energy consumption so far withinthe present (partial) interval and the present rate of consumption.
Predicated demand is updated according to the update rate of your meter.
The following illustration shows how a change in load can affect predicted demandfor the interval. In this example, the interval is set to 15 minutes.
1:00 1:06 1:15
A Beginning of interval E Change in load
B Demand for last completed interval F Predicted demand if load is addedduring interval; predicted demandincreases to reflect increased demand
C 15-minute interval G Predicted demand if no load is added
D Partial interval H Time
Peak demand
The meter records the peak (or maximum) values for kWD, kVARD, and kVADpower (or peak demand).
The peak for each value is the highest average reading since the meter was lastreset. These values are maintained in the meter’s non-volatile memory.
The meter also stores the date and time when the peak demand occurred.
NHA2778902–00 45
Measurements and calculations
TimerThe meter supports an active load timer, meter operation timer, and run hour.
The timer data can be read through register map.
Active load timer
Active load timer shows how much time a load has been running, based on thespecified minimum current for the load timer setpoint setting.
Meter operation timer
Meter operating timer shows how long the meter has been powered up.
Run Time
Run time shows how much time a load has been running, based on accumulatedenergy - received and delivered.
46 NHA2778902–00
Power quality
Power quality
Harmonics overviewThis section describes the meter’s power quality features and how to accesspower quality data. The meter measures voltage and current harmonics up to the15th harmonic and 31st harmonic (PM2130 only), and calculates Total HarmonicDistortion (THD%).
Harmonics are integer multiples of the fundamental frequency of the powersystem. Harmonics information is required for compliance to system power qualitystandards such as EN50160 and meter power quality standards such as IEC61000-4-30.
The meter measures fundamental and higher harmonics relative to thefundamental frequency. The meter’s power system setting defines which phasesare present and determines how line-to-line or line-to-neutral voltage harmonicsand current harmonics are calculated.
Harmonics are used to identify whether the supplied system power meets requiredpower quality standards, or if non-linear loads are affecting your power system.Power system harmonics can cause current flow on the neutral conductor, anddamage to equipment such as increased heating in electric motors. Powerconditioners or harmonic filters can be used to minimize unwanted harmonics.
Total harmonic distortionTotal harmonic distortion (THD) is a measure of the total per-phase voltage orcurrent harmonic distortion present in the power system.
THD provides a general indication of the quality of a waveform. THD% iscalculated for each phase of both voltage and current.
Harmonic content calculations
Harmonic content (HC) is equal to the RMS value of all the non-fundamentalharmonic components in one phase of the power system.
The meter uses the following equation to calculate HC:
HC = (H2)2 + (H3)2 + (H4)2 ...
THD% calculations
THD% is a quick measure of the total distortion present in a waveform and is theratio of harmonic content (HC) to the fundamental harmonic (H1).
The meter uses the following equation to calculate THD%:
THDHC
H1
-------- 100= x
Displaying harmonics dataThe meter displays voltage and current THD% data on the front panel, while thephase wise THD% data can be read through communication.
1. Navigate to THD.2. Press Amps, V L-L, or V L-N to view current or voltage THD%.
NHA2778902–00 47
Power quality
3. Press Up arrow to exit the page.
48 NHA2778902–00
Maintenance and upgrades
Maintenance and upgrades
Maintenance overviewThe meter does not contain any user-serviceable parts. If the meter requiresservice, contact your local Schneider Electric Technical Support representative.
NOTICEMETER DAMAGE• Do not open the meter case.• Do not attempt to repair any components of the meter.Failure to follow these instructions can result in equipment damage.
Do not open the meter. Opening the meter voids the warranty.
Troubleshooting LED indicatorsAbnormal heartbeat / serial communications LED behavior could mean potentialproblems with the meter.
Problem Probable causes Possible solutions
LED flash rate does not changewhen data is sent from the hostcomputer.
Communications wiring If using a serial-to-RS-485converter, trace and check thatall wiring from the computer tothe meter is properlyterminated.
Internal hardware problem Perform a hard reset: turn offcontrol power to the meter,then re-apply power. If theproblem persists, contactTechnical Support.
Heartbeat / serialcommunications LED remainslit and does not flash ON andOFF
Internal hardware problem Perform a hard reset: turn offcontrol power to the meter,then re-apply power. If theproblem persists, contactTechnical Support.
Heartbeat / serialcommunications LED flashes,but the display is blank.
Display setup parametersincorrectly set
Review display parametersetup.
If the problem is not fixed after troubleshooting, contact Technical Support for helpand ensure you have your meter’s firmware version, model and serial numberinformation available.
Meter memoryThe meter stores configuration and logging information in non-volatile memory anda long-life memory chip.
The meter uses its non-volatile memory (NVRAM) to retain all data and meteringconfiguration values.
Meter batteryThe internal battery in the meter keeps its clock running and helps maintain thetime even when the meter is powered down.
NHA2778902–00 49
Maintenance and upgrades
The life expectancy of the meter’s internal battery is estimated to be over 3 yearsat 25 °C under typical operating conditions.
Viewing firmware version, model and serial numberYou can view the meter’s firmware version, model and serial number from thedisplay panel.
1. Navigate toMaint > Diag.2. Press Info to view meter model, serial number, date of manufacturing, OS
version, and RS version.
3. Press Up to exit.
Firmware upgradesThere are a number of reasons why you may want to upgrade your meter’sfirmware.• Improve meter performance (e.g., optimize processing speed)• Enhance existing meter features and functions• Add new functionality to the meter• Achieve compliance to new industry standards
Technical assistanceVisit www.schneider-electric.com for support and assistance with lost passwordsor other technical problems with the meter.
Make sure you include your meter’s model, serial number and firmware version inyour email or have it readily available if calling Technical Support.
50 NHA2778902–00
Verifying accuracy
Verifying accuracy
Overview of meter accuracyAll meters are tested and verified at the factory in accordance with InternationalElectrotechnical Commission (IEC) and Institute of Electrical and ElectronicsEngineers (IEEE) standards.
Your meter typically does not require re-calibration. However, in some installationsa final accuracy verification of the meters is required, especially if the meters willbe used for revenue or billing applications.
Accuracy test requirementsThe most common method for testing meter accuracy is to apply test voltages andcurrents from a stable power source and compare the meter’s readings withreadings from a reference device or energy standard.
Signal and power source
The meter maintains its accuracy during voltage and current signal sourcevariations but its energy pulsing output needs a stable test signal to help produceaccurate test pulses. The meter’s energy pulsing mechanism needs approximately10 seconds to stabilize after every source adjustment.
The meter must be connected to control power in order to conduct accuracyverification testing. Refer to your meter’s installation documentation for powersupply specifications.
DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Verify the device’s power source meets the specifications for your device’spower supply.
Failure to follow these instructions will result in death or serious injury.
Control equipment
Control equipment is required for counting and timing the pulse outputs from anenergy pulsing LED.• Most standard test benches have an arm equipped with optical sensors to
detect LED pulses (the photodiode circuitry converts detected light into avoltage signal).
• The reference device or energy standard typically has digital inputs that candetect and count pulses coming from an external source (i.e., the meter’s pulseoutput).
NOTE: The optical sensors on the test bench can be disrupted by strong sourcesof ambient light (such as camera flashes, florescent tubes, sunlight reflections,floodlights, etc.). This can cause test errors. Use a hood, if necessary, to block outambient light.
Environment
The meter should be tested at the same temperature as the testing equipment.The ideal temperature is about 23 ºC (73 ºF). Make sure the meter is warmed upsufficiently before testing.
NHA2778902–00 51
Verifying accuracy
A warm-up time of 30 minutes is recommended before beginning energy accuracyverification testing. At the factory, the meters are warmed up to their typicaloperating temperature before calibration to help ensure that the meters will reachtheir optimal accuracy at operating temperature.
Most high precision electronic equipment requires a warm up time before itreaches its specified performance levels. Energy meter standards allow themanufacturers to specify meter accuracy derating due to ambient temperaturechanges and self-heating.
Your meter complies with and meets the requirements of these energy meteringstandards.
For a list of accuracy standards that your meter complies to, contact your localSchneider Electric representative or download the meter brochure from www.schneider-electric.co.in.
Reference device or energy standard
To help ensure the accuracy of the test, it is recommended that you use areference device or reference energy standard with a specified accuracy that is 6to 10 times more accurate than the meter under test. Before you start testing, thereference device or energy standard should be warmed up as recommended by itsmanufacturer.
NOTE: Verify the accuracy and precision of all measurement equipment used inaccuracy testing (for example, voltmeters, ammeters, power factor meters).
Verifying accuracy testThe following tests are guidelines for accuracy testing your meter; your meter shopmay have specific testing methods.
DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E in the USA, CSA Z462 or applicablelocal standards.
• Turn off all power supplying this device and the equipment in which it isinstalled before working on the device or equipment.
• Always use a properly rated voltage sensing device to confirm that all poweris off.
• Do not exceed the device’s ratings for maximum limits.• Verify the device’s power source meets the specifications for your device’s
power supply.Failure to follow these instructions will result in death or serious injury.
1. Turn off all power supplying this device and the equipment in which it is installedbefore working on the device or equipment.
2. Use a properly rated voltage sensing device to confirm that all power is off.
52 NHA2778902–00
Verifying accuracy
3. Connect the test voltage and current source to the reference device or energystandard. Ensure all voltage inputs to the meter under test are connected inparallel and all current inputs are connected in series.
V1V2 V3 VN
A1 A2 A3+ - + - + -
V1 V2 V3 VNA1 A2 A3
+ - + - + -
V1 V2 V3 VN A1 A2 A3+ - + - + -
A Reference device or energy standard
B Test voltage and current source
C Meter under test
4. Connect the control equipment used for counting the standard output pulsesusing one of these methods:
Option Description
Energy pulsing LED Align the red light sensor on the standard test bench armature over theenergy pulsing LED.
Pulse output Connect the meter’s pulse output to the standard test bench pulsecounting connections.
NOTE:When selecting which method to use, be aware that energy pulsingLEDs and pulse outputs have different pulse rate limits.
5. Before performing the verification test, let the test equipment power up themeter and apply voltage for at least 30 seconds. This helps stabilize the internalcircuitry of the meter.
6. Configure the meter’s parameters for verifying accuracy testing.
7. Depending on the method selected for counting the energy pulses, configurethe meter’s energy pulsing LED or one of the pulse outputs to perform energypulsing. Set the meter’s energy pulse constant so it is in sync with the referencetest equipment.
8. Perform accuracy verification on the test points. Run each test point for at least30 seconds to allow the test bench equipment to read an adequate number ofpulses. Allow 10 seconds of dwell time between test points.
Required pulses calculation for accuracy verification testingAccuracy verification test equipment typically requires you to specify the number ofpulses for a specific test duration.
The reference test equipment typically requires you to specify the number ofpulses required for a test duration of “t” seconds. Normally, the number of pulsesrequired is at least 25 pulses, and the test duration is greater than 30 seconds.
Use the following formula to calculate the required number of pulses:
Number of pulses = Ptot x K x t/3600
Where:
NHA2778902–00 53
Verifying accuracy
• Ptot = total instantaneous power in kilowatts (kW)• K = the meter’s pulse constant setting, in pulses per kWh• t = test duration, in seconds (typically greater than 30 seconds)
Total power calculation for accuracy verification testingAccuracy verification testing supplies the same test signal (total power) to both theenergy reference/standard and the meter under test.
Total power is calculated as follows, where:• Ptot = total instantaneous power in kilowatts (kW)• VLN = test point line-to-neutral voltage in volts (V)• I = test point current in amps (A)• PF = power factorThe result of the calculation is rounded up to the nearest integer.
For a balanced 3–phase Wye system:
Ptot = 3 x VLN x I x PF x 1 kW/1000 W
NOTE: A balanced 3–phase system assumes that the voltage, current and powerfactor values are the same for all phases.
For a single-phase system:
Ptot = VLN x I x PF x 1 kW/1000W
Percentage error calculation for accuracy verification testingAccuracy verification testing requires you to calculate the percentage errorbetween the meter being tested and the reference/standard.
Calculate the percentage error for every test point using the following formula:
Energy error = (EM - ES) / ES x 100%
Where:• EM = energy measured by the meter under test• ES = energy measured by the reference device or energy standard.NOTE: If accuracy verification reveals inaccuracies in your meter, they may becaused by typical sources of test errors. If there are no sources of test errorspresent, please contact your local Schneider Electric representative.
Accuracy verification test pointsThe meter should be tested at full and light loads and at lagging (inductive) powerfactors to help ensure testing over the entire range of the meter.
The test amperage and voltage input rating are labeled on the meter. Refer to theinstallation sheet or data sheet for your meter’s nominal current, voltage andfrequency specifications.
54 NHA2778902–00
Verifying accuracy
Watt-hour test point Sample accuracy verification test point
Full load 100% to 200% of the nominal current, 100% of the nominal voltage andnominal frequency at unity power factor or one (1).
Light load 10% of the nominal current, 100% of the nominal voltage and nominalfrequency at unity power factor or one (1).
Inductive load (laggingpower factor)
100% of the nominal current, 100% of the nominal voltage and nominalfrequency at 0.50 lagging power factor (current lagging voltage by 60°phase angle).
VAR-hour test point Sample accuracy verification test point
Full load 100% to 200% of the nominal current, 100% of the nominal voltage andnominal frequency at zero power factor (current lagging voltage by 90°phase angle).
Light load 10% of the nominal current, 100% of the nominal voltage and nominalfrequency at zero power factor (current lagging voltage by 90° phaseangle).
Inductive load (laggingpower factor)
100% of the nominal current, 100% of the nominal voltage and nominalfrequency at 0.87 lagging power factor (current lagging voltage by 30°phase angle).
Energy pulsing considerationsThe meter’s energy pulsing LED and pulse outputs are capable of energy pulsingwithin specific limits.
Description Energy pulsing LED Pulse output
Maximum pulse frequency 35 Hz 20 Hz
Minimum pulse constant 1 pulse per k_h
Maximum pulse constant 9,999,000 pulses per k_h
The pulse rate depends on the voltage, current and PF of the input signal source,the number of phases, and the VTand CT ratios.
If Ptot is the instantaneous power (in kW) and K is the pulse constant (in pulses perkWh), then the pulse period is:
Pulse period (in seconds)3600
K x Ptot1
Pulse frequency (Hz)= =
VTand CTconsiderationsTotal power (Ptot) is derived from the values of the voltage and current inputs atthe secondary side, and takes into account the VTand CT ratios.
The test points are always taken at the secondary side, regardless of whether VTsor CTs are used.
If VTs and CTs are used, you must include their primary and secondary ratings inthe equation. For example, in a balanced 3-phase Wye system with VTs and CTs:
Ptot = 3 x VLN xVTp
VTsx I x
CTp
CTsx PF x
1 kW1000 W
where Ptot = total power, VTp = VT primary, VTs = VTsecondary, CTp = CT primary,CTs = CTsecondary and PF = power factor.
NHA2778902–00 55
Verifying accuracy
Example calculationsThis example calculation shows how to calculate power, pulse constants andmaximum pulse frequency, and how to determine a pulse constant that reducesthe maximum pulse frequency.
A balanced 3-phase Wye system uses 480:120 volt VTs and 120:5 amp CTs. Thesignals at the secondary side are 119 volts line-to-neutral and 5.31 amps, with apower factor of 0.85. The desired pulse output frequency is 20 Hz (20 pulses persecond).1. Calculate the typical total output power (Ptot):
Ptot = 3 x 119 x 480120
x 5.31 x 1205
x 0.85 x 1 kW1000 W
= 154.71 kW
2. Calculate the pulse constant (K):
K =3600 x (pulse frequency)
Ptot= 3600 seconds/hour x 20 pulses/second
154.71 kW
K = 465.5 pulses / kWh
3. At full load (120% of nominal current = 6 A) and power factor (PF = 1), calculatethe maximum total output power (Pmax):
Pmax = 3 x 119 x 480120
x 6 x 1005
x 1 x 1 kW1000 W
= 205.6 kW
4. Calculate the maximum output pulse frequency at Pmax:
Maximum pulse frequency = K x Pmax3600
= 465.5 pulses / kWh x 205.6 kW3600 seconds/hour
Maximum pulse frequency = 26.6 pulses/second = 26.6 Hz
5. Check the maximum pulse frequency against the limits for the LED and pulseoutputs:• 26.6 Hz ≤ LED maximum pulse frequency (35 Hz)• 26.6 Hz > pulse output maximum pulse frequency (20 Hz)NOTE: The maximum pulse frequency is within the limits for LED energypulsing. However, the maximum pulse frequency is greater than the limits forpulse output energy pulsing. Pulse output frequencies greater than 20 Hz willsaturate the pulse output and cause it to stop pulsing. Therefore in thisexample, you can only use the LED for energy pulsing.
Adjustments to allow energy pulsing at the pulse outputs
If you want to use the pulse output, you must reduce the output pulse frequency soit is within the limits.
Using the values from the above example, the maximum pulse constant for thepulse output is:
Kmax = 3600 x (pulse output maximum pulse frequency)
Pmax= 3600 x 20
205.6
Kmax = 350.14 pulses per kWh
1. Set the pulse constant (K) to a value below Kmax, for example, 300 pulses/kWh. Calculate the new maximum output pulse frequency at Pmax:
New maximum pulse frequency = K x Pmax3600
= 300 pulses/kWh x 205.6 kW3600 seconds/hour
New maximum pulse frequency = 17.1 pulses/second = 17.1 Hz
56 NHA2778902–00
Verifying accuracy
2. Check the new maximum pulse frequency against the limits for the LED andpulse outputs:• 17.1 Hz ≤ LED maximum pulse frequency (35 Hz)• 17.1 Hz ≤ pulse output maximum frequency (20 Hz)As expected, changing K to a value below Kmax allows you to use the pulseoutput for energy pulsing.
3. Set the new pulse constant (K) on your meter.
Typical sources of test errorsIf you see excessive errors during accuracy testing, examine your test setup andtest procedures to eliminate typical sources of measurement errors.
Typical sources of accuracy verification testing errors include:• Loose connections of voltage or current circuits, often caused by worn-out
contacts or terminals. Inspect terminals of test equipment, cables, test harnessand the meter under test.
• Meter ambient temperature is significantly different than 23 °C (73 °F).• Floating (ungrounded) neutral voltage terminal in any configuration with
unbalanced phase voltages.• Inadequate meter control power, resulting in the meter resetting during the test
procedure.• Ambient light interference or sensitivity issues with the optical sensor.• Unstable power source causing energy pulsing fluctuations.• Incorrect test setup: not all phases connected to the reference device or the
energy standard. All phases connected to the meter under test should also beconnected to the reference meter/standard.
• Moisture (condensing humidity), debris or pollution present in the meter undertest.
NHA2778902–00 57
Power and power factor
Power and power factor
Power and power factorThe sampled measurements taken at the meter’s voltage and current inputsprovide data for calculating power and power factor.
In a balanced 3-phase alternating current (AC) power system source, the ACvoltage waveforms on the current-carrying conductors are equal but offset by one-third of a period (a phase angle shift of 120 degrees between the three voltagewaveforms).
Current phase shift from voltageElectrical current can lag, lead, or be in phase with the AC voltage waveform, andis typically associated with the type of load — inductive, capacitive or resistive.
For purely resistive loads, the current waveform is in phase with the voltagewaveform. For capacitive loads, current leads voltage. For inductive loads, currentlags voltage.
The following diagrams show how voltage and current waveforms shift based onload type under ideal (laboratory) conditions.
Current and voltage in phase (resistive) Current leads voltage (capacitive) Current lags voltage (inductive)
Real, reactive and apparent power (PQS)A typical AC electrical system load has both resistive and reactive (inductive orcapacitive) components.
Real power, also known as active power (P) is consumed by resistive loads.Reactive power (Q) is either consumed by inductive loads or generated bycapacitive loads.
Apparent power (S) is the capacity of your measured power system to provide realand reactive power.
The units for power are watts (W or kW) for real power P, vars (VAR or kVAR) forreactive power Q, and volt-amps (VA or kVA) for apparent power S.
58 NHA2778902–00
Power and power factor
+Q(+kVAR, +kVARh)
-P
(-kW, -kWh)
-Q(-kVAR, -kVARh)
+P
(+kW, +kWh)
Active power (W)Exported/received
Apparent power (VA)
Rea
ctiv
e po
wer
(V
AR
)Im
port
ed/d
eliv
ered
Quadrant 3PF laggingPower factor sign convention:
IEEE = −IEC = −
Quadrant 4PF leadingPower factor sign convention:
IEEE = +IEC = +
Quadrant 1PF laggingPower factor sign convention:
IEEE = −IEC = +
Quadrant 2PF leadingPower factor sign convention:
IEEE = +IEC = −
90°
0°180°
270°
Apparent power (VA)
Rea
ctiv
e po
wer
(V
AR
)Im
port
ed/d
eliv
ered
Active power (W)Exported/received
Rea
ctiv
e po
wer
(V
AR
)E
xpor
ted/
rece
ived
Appar
ent p
ower
(VA)
Appar
ent p
ower
(VA)
Active power (W)Imported/delivered
Active power (W)Imported/delivered
Rea
ctiv
e po
wer
(V
AR
)E
xpor
ted/
rece
ived
Power flow
Positive real power P(+) flows from the power source to the load. Negative realpower P(-) flows from the load to the power source.
Power factor (PF)Power factor (PF) is the ratio of real power (P) to apparent power (S).
Power factor is provided as a number between -1 and 1 or as a percentage from-100% to 100%, where the sign is determined by the convention.
PF PS---=
An ideal, purely resistive load has no reactive components, so its power factor isone (PF = 1, or unity power factor). Inductive or capacitive loads introduce areactive power (Q) component to the circuit which causes the PF to become closerto zero.
True PF and displacement PF
The meter supports true power factor and displacement power factor values:• True power factor includes harmonic content.• Displacement power factor only considers the fundamental frequency.NOTE: Unless specified, the power factor displayed by the meter is true powerfactor.
Power factor sign convention
Power factor sign (PF sign) can be positive or negative, and is defined by theconventions used by the IEEE or IEC standards.
You can set the power factor sign (PF sign) convention that is used on the displayto either IEC or IEEE.
NHA2778902–00 59
Power and power factor
PF sign convention: IEC
PF sign correlates with the direction of real power (kW) flow.• Quadrant 1 and 4: Positive real power (+kW), the PF sign is positive (+).• Quadrant 2 and 3: Negative real power (-kW), the PF sign is negative (-).
PF sign convention: IEEE
PF sign is correlates with the PF lead/lag convention, in other words, the effectiveload type (inductive or capacitive):• For a capacitive load (PF leading, quadrant 2 and 4), the PF sign is positive (+).• For an inductive load (PF lagging, quadrant 1 and 3), the PF sign is negative (-).
Power factor min/max convention
The meter uses a specific convention for determining the power factor minimumand maximum values.• For negative PF readings, the minimum PF value is the measurement closest to
-0 for PF readings between -0 to -1. For positive PF readings, the minimum PFvalue is the measurement closest to +1 for PF readings between +1 to +0.
• For negative PF readings, the maximum PF value is the measurement closestto -1 for PF readings between -0 to -1. For positive PF readings, the maximumPF value is the measurement closest to +0 for PF readings between +1 to +0.
1.0
-0.4 .4
.6
.8
-0.6
-0.8
+0
.2
-0
-0.2
-1.0
Power factor register format
The meter performs a simple algorithm to the PF value then stores it in the PFregister.
Each power factor value (PF value) occupies one floating point register for powerfactor (PF register). The meter and software interpret the PF register for allreporting or data entry fields according to the following diagram:
60 NHA2778902–00
Power and power factor
Quadrant 3
0 to -1 -1 to 0 0 to +1 +1 to 0
0 -1 0 +1 0
-2 -1 0 +1 +2
0
-1
0
+1
5.0+5.0-
+0.5-0.5
-2 to -1 -1 to 0 0 to +1 +1 to +2
-2 +2
-1
0 0
+1
-0.5 +0.5
+1.5-1.5
Quadrant 2 Quadrant 1 Quadrant 4
Quadrant 2 Quadrant 1
Quadrant 3 Quadrant 4
Quadrant 2-1 ≤ PF ≤ 0
Quadrant 10 ≤ PF ≤ 1
Quadrant 3
-1 ≤ PF ≤ 0
Quadrant 4
0 ≤ PF ≤ 1
-2 ≤ PF register ≤ -1 2 ≤ PF register ≤ 1
-1 ≤ PF register ≤ 0 0 ≤ PF register ≤ 1
PF register
PF Value
The PF value is calculated from the PF register value using the following formulae:
Quadrant PF range PF register range PF formula
Quadrant 1 0 to +1 0 to +1 PF value = PF registervalue
Quadrant 2 -1 to 0 -1 to 0 PF value = PF registervalue
Quadrant 3 0 to -1 -2 to -1 PF value = (-2) - (PFregister value)
Quadrant 4 +1 to 0 +1 to +2 PF value = (+2) - (PFregister value)
NHA2778902–00 61
Meter specifications
Meter specifications
SpecificationsThe specifications contained in this section are subject to change without notice.
For installation and wiring information, refer to the meter installation sheet.
Mechanical characteristics
IP degree of protection (IEC 60529-1) Front display: IP51Meter body: IP30
Panel thickness maximum 6.0 mm (0.25 in) maximum
Mounting position Vertical
Display type LCD display: Monochrome graphical LCD
Keypad 4 button with intuitive navigation
Front panel LED indicators Green LED (heartbeat / serial communications activity)Amber LED (alarm / energy pulse output)
Weight ~ 300 gms
Dimensions W x H x D 96 x 96 x 73 mm max
Protection features Password protected for set-up parameters
Electrical characteristics
Measurement accuracy
Current, Phase ± 0.5% for Class 1.0 and Class 0.5S
Voltage L-N, L-L ± 0.5% for Class 1.0 and Class 0.5S
Power Factor ± 0.01 count for Class 1.0 and Class 0.5S
Power PM2210, PM2220:• Active power: ± 1% for Class 1.0 and Class 0.5S• Reactive power: ± 1% for Class 1.0 and Class 0.5S• Apparent power: ± 1% for Class 1.0 and Class 0.5SPM2230:• Active power: ± 0.5% for Class 1.0 and Class 0.5S• Reactive power: ± 1% for Class 1.0 and Class 0.5S• Apparent power: ± 0.5% for Class 1.0 and Class 0.5S
Frequency ± 0.05% for Class 1.0 and Class 0.5S
Active Energy Class 0.5S as per IEC 62053-22 and Class 1.0 as per IEC 62053-21 for both 5 A and 1 A*nominal CT.* For 1 A CT nominal, additional error of ±1% from 50 mA to 150 mA, ±2% for current > 10 mA to< 50 mA
Reactive Energy Class 1.0 as per IEC 62053-24 for 5 A nominal CT
THD and Individual HarmonicV & A
± 5% FS for THD and individual harmonics up to 15th order
Voltage inputs
VT primary 999 kV L-L max, starting voltage depends on VT ratio
V nominal 277 V L-N / 480 V L-L
Measured V with full range 35 - 480 V L-L (20 - 277 V L-N), CAT III35 - 600 V L-L (20 - 347 V L-N), CAT II
62 NHA2778902–00
Meter specifications
Voltage inputs
Permanent overload 750 VAC L-L
Impedance ≥ 5 MΩ
Frequency 50 / 60 Hz nominal ± 5%
VA burden < 0.2 VA at 240 VAC L-N
Current inputs
CT ratings Primary adjustable 1 A to 32767 ASecondary 1 A or 5 A I-nominal
Measured current 5 mA to 6 A
Withstand Continuous 12 A; 50 A at 10 sec/hr, 500 A at 1 sec/hr
Impedance < 0.3 mΩ
Frequency 50 / 60 Hz nominal
VA Burden < 0.024 VA at 6 A
AC control power - PM2210/PM2220
Operating range 44 - 277 V L-N ± 10%
Burden < 6 VA at 277 V L-N
Frequency range 45 - 65 Hz ± 5%
Ride-through time 100 ms typical at 230 VAC and maximum burden100 ms typical at 277 VAC and maximum burden
AC control power - PM2230
Operating range 80 - 277 V L-N ± 10%
Burden < 8 VA at 277 V L-N
Frequency range 45 - 65 Hz ± 5%
Ride-through time 100 ms typical at 230 VAC and maximum burden100 ms typical at 277 VAC and maximum burden
DC control power - PM2210/PM2220
Operating range 44 - 277 V DC ± 10%
Burden < 2 W at 277 V DC
Ride-through time 50 ms typical at 125 V DC and maximum burden
DC control power - PM2230
Operating range 100 - 277 V DC ± 10%
Burden < 3.3 W at 277 V DC
Ride-through time 50 ms typical at 125 V DC and maximum burden
Displays update
Instantaneous 1 s
Demand 15 s
Harmonics 5 s
NHA2778902–00 63
Meter specifications
Wiring configuration
User programmable 1ph 2W, L-N1ph 2W, L-L1ph 3W, L-L with N (2 phase)3ph 3W, Delta, Ungrounded3ph 3W, Delta, Corner Grounded3ph 3W, Wye, Ungrounded3ph 3W, Wye Grounded3ph 3W, Wye, Resistance Grounded3ph 4W, Open Delta, Center-Tapped3ph 4W, Delta, Center-Tapped3ph 4W, Wye, Ungrounded3ph 4W, Wye Grounded3ph 4W, Wye, Resistance Grounded
Environmental characteristics
Operating temperature -10 °C to +60 °C (14 °F to 140 °F)
Storage temperature -25 °C to +70 °C (-13 °F to 158 °F)
Humidity rating 5% to 95% RH at 50 °C (122 °F) (non-condensing)
Pollution degree 2
Altitude < 2000 m (6562 ft)
Location Not suitable for wet locations
Product life > 7 years
EMC (electromagnetic compatibility)*
Electrostatic discharge IEC 61000-4-2
Immunity to radiated field IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to impulse waves IEC 61000-4-5
Conducted immunity IEC 61000-4-6
Immunity to magnetic field IEC 61000-4-8
Immunity to voltage dips IEC 61000-4-11
Emissions (IEC61326-1) Emissions FCC Part 15 Class A/CE
* - Tested as per IEC 61326-1 standard for Emission
Safety
Europe CE, as per IEC 61010-1 Ed-3
US and Canada cULus per UL 61010-1CAN / CSA-C22.2 No. 61010-1, for 600 VAC
Measurement category (Voltage andCurrent inputs)
CAT III up to 480 V L-LCAT II up to 600 V L-L
Overvoltage category (Control power) CAT III up to 300 V L-N
Dielectric As per IEC / UL 61010-1 Ed-3
Protective Class II, Double insulated for user accessible parts
Other certification C-Tick (RCM)
64 NHA2778902–00
Meter specifications
RS-485 communications
Number of ports 1
Maximum cable length 1200 m (4000 ft)
Maximum number of devices (unitloads)
Up to 32 devices on the same bus
Parity Even, Odd, None (1 stop bit for Odd or Even parity; 2 stop bits for None)
Baud rate 4800, 9600, 19200, 38400
Isolation 2.5 kV RMS, double insulated
Pulse output
Pulse output (POP) Max 40 V DC, 20 mA20 ms ON timeConfigurable pulse weight from 1 to 9999000 (pulse/ k_h)
Real-time clock
Battery backup time 3 years
NHA2778902–00 65
Schneider Electric35 rue Joseph Monier92500 Rueil MalmaisonFrance
+ 33 (0) 1 41 29 70 00
www.schneider-electric.com
As standards, specifications, and design change from time to time,please ask for confirmation of the information given in this publication.
© 2015 – 2015 Schneider Electric. All rights reserved.
NHA2778902–00