    Earth Fault protection

    Power Transmissionand Distribution

  • 7/30/2019 Earth FAult Protection_new

    2/12

    Page 2 TLQ 2004 Distance Protection -Earth Fault Protection

    Siemens AG 2006

    Power Transmission and Distribution

    7SA522

    High Resistance Earth Fault Protection: Features

    Earth (zero sequence) current protection, 4 stages 1 and 3 pole tripping with special phase selectors

    3 definite-time stages

    1 inverse-time stage: IEC, logarithmic inverse or ANSI characteristic

    this stage can also be used as a 4th definite-time stage

    Directional determination with 3V0 and/or Ipol of an earthed powertransformer

    Directional determination with V2 and I2 (negative sequence)

    Sensitive 3I0-measurement with a pick-up range: 0.005 A to 100 x In

    Elimination of higher harmonics with special digital filters

    Inrush-stabilisation with I0/100Hz

    Teleprotection: Directional comparison, Blocking or Unblocking

    Operation with weak infeed trip and echo

    Instantaneous trip after switch-onto-fault

  • 7/30/2019 Earth FAult Protection_new

    3/12

    Page 3 TLQ 2004 Distance Protection -Earth Fault Protection

    Siemens AG 2006

    Power Transmission and Distribution

    Example: Single phase fault with infeed from 2 sides

    IL1

    IL2

    IL3

    IEZf

  • 7/30/2019 Earth FAult Protection_new

    4/12

    Page 4 TLQ 2004 Distance Protection -Earth Fault Protection

    Siemens AG 2006

    Power Transmission and Distribution

    Symmetrical Component representation: L1-E Fault

    B

    Pos.Seq.

    I1A

    Neg.Seq.

    ZeroSeq.

    I1BA

    I2A

    I2B

    I0A

    I0B

    3 xR

    Fault

    U0A

    U2A

    U2B

    U0B

  • 7/30/2019 Earth FAult Protection_new

    5/12

    Page 5 TLQ 2004 Distance Protection -Earth Fault Protection

    Siemens AG 2006

    Power Transmission and Distribution

    *)

    I0P U0P U2P

    I0L,

    I2L

    *) not needed for numerical relays,

    U0P may also be internally calculated

    Polarizing Options for Directional Earth Fault

    Relays

  • 7/30/2019 Earth FAult Protection_new

    6/12

    Page 6 TLQ 2004 Distance Protection -Earth Fault Protection

    Siemens AG 2006

    Power Transmission and Distribution

    Directional Characteristic (U0 and IY)

  • 7/30/2019 Earth FAult Protection_new

    7/12Page 7 TLQ 2004 Distance Protection -Earth Fault Protection

    Siemens AG 2006

    Power Transmission and Distribution

    7SA522

    High Resistance Earth Fault Protection: functional

    diagram

    Earth fault

    direction

    =

    EF IE> Echo

    3I0>>>EF>>> Trip

    P

    EFp Trip

    Inrush-stabilisation

    T(3I0/IN)

    T

    Tele-protection

    T

    SOTF

    = &

    &

    3I0>>> Def. Time Stage

    Inverse Time Stage

    &

    &

    P

    >EF>>> block

    Direc. 3I0>>>

    P Direc. 3I0p

    >EFp block

    P 3I0p

    EF Fault Det.

    >EF Trip rel.

    3I0>> Def. Time Stage

    3I0> Def. Time Stage

    = Input signal(binary input)

    P = Parameter = Output Signal(alarm, command)

    P3146 AddTdelay

  • 7/30/2019 Earth FAult Protection_new

    8/12Page 8 TLQ 2004 Distance Protection -Earth Fault Protection

    Siemens AG 2006

    Power Transmission and Distribution

    7SA522 - Directional earth fault protection: Settings

    Settings of the stages:

    Settings for direction:

    General settings:

  • 7/30/2019 Earth FAult Protection_new

    9/12Page 9 TLQ 2004 Distance Protection -Earth Fault Protection

    Siemens AG 2006

    Power Transmission and Distribution

    Principle of phase selection logic with U and I - Example

    L1-E

    UL1E < 0.6 UNOM

    UL2E > 0.7 UNOM

    UL3E > 0.7 UNOM

    IL1E > 2 INOM

    IL2E < 1.2 INOM

    IL3E < 1.2 INOM

    &

    &

    OR

    Select

    L1-E

    with U / I

    If selection with U / I is not successful (U too large or I too small)

    then symmetrical component method is used

  • 7/30/2019 Earth FAult Protection_new

    10/12Page 10 TLQ 2004 Distance Protection -Earth Fault Protection

    Siemens AG 2006

    Power Transmission and Distribution

    Phase Selection Logic - Sequence Components

    L2-E

    L3-E

    L1-E

    I2 = I0

    I2 = a2*I0

    I2 = a*I0

    Angle differenceI2/I0

    Faulty Phase

    -60 .. 60 L1-E

    60 .. 180 L3-E

    180 .. 300 L2-E

  • 7/30/2019 Earth FAult Protection_new

    11/12Page 11 TLQ 2004 Distance Protection -Earth Fault Protection

    Siemens AG 2006Power Transmission and Distribution

    U0P or U2P may fall below critical value (approx. 1 V secondary) and limit

    relay high resistance earth fault sensitivity

    Zero or negative sequence sources to be available behind relay location

    Minimum settings at least > 3 times VT and CT inaccuracies

    Current setting above line unsymmetry (M0 = Z01/Z0 or M2 = Z21/Z1)

    (series compensated lines require higher current setting due to

    possibility of unsymmetrical gap flashover)

    Separate current threshold setting for tele-protection : 3I0 to avoid false operation with CT

    saturation

    DEF protection, Critical application issues

  • 7/30/2019 Earth FAult Protection_new

    12/12Page 12 TLQ 2004 Distance Protection -Earth Fault Protection

    Siemens AG 2006Power Transmission and Distribution

    7SA522 - Earth fault protection

    Directional comparison teleprotection scheme

    rec.

    transm.

    A B

    E/F.

    frwd. TS

    & trip

    rec.

    &1

    E/F.

    frwd.TS

    &trip

    transm&

    1

    *Three-terminal schemes are supported as well

    TS