SCADAPack E Series IEC 60870-5-101 Slave Technical Reference

CONTROL MICROSYSTEMS SCADA products... for the distance

48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support: 888-226-6876 Canada 888-2CONTROL

Page 2: E Series Iec 60870-5-101 Slave Technical Reference

SCADAPack E Series IEC 60870-5-101 Slave Technical Reference © 2006 Control Microsystems Inc. All rights reserved. Printed in Canada.

Trademarks Control Microsystems, RealFLO, RealPACK, TelePACE, SCADALog, SCADAPack, SCADAPack ES, SCADAPack ER, SCADAPack E Series, SCADAServer, TeleBUS, TeleSAFE Micro 16, SolarPACK, SmartWIRE, 4202GFC, 4202GFC-DS and related product series are registered trademarks of Control Microsystems Inc. All other product names are copyright and registered trademarks or trade names of their respective owners.

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

1

Page 3: E Series Iec 60870-5-101 Slave Technical Reference

TABLE OF CONTENTS

1 OVERVIEW.................................................................................................... 6

2 BASIC FEATURES........................................................................................ 7

2.1 System Capacity ............................................................................................ 7 2.1.1 ASDUs without Time Tag.......................................................................... 7 2.1.2 ASDUs with Time Tags (events)............................................................... 7

3 CONFIGURATION......................................................................................... 8

3.1 Serial Port Configurations .............................................................................. 8

3.2 60870-5-101 System Configurations.............................................................. 9 3.2.1 Master Enabled....................................................................................... 10 3.2.2 Link and ASDU Address ......................................................................... 10 3.2.3 COM Port................................................................................................ 10 3.2.4 Link Address Size ................................................................................... 10 3.2.5 Link Mode ............................................................................................... 10 3.2.6 Link Confirm Timeout.............................................................................. 11 3.2.7 Link Retries............................................................................................. 11 3.2.8 Clock Valid Period .................................................................................. 11 3.2.9 Cyclic Period........................................................................................... 11 3.2.10 Background Period ................................................................................. 11 3.2.11 Short Pulse Duration............................................................................... 11 3.2.12 Long Pulse Duration ............................................................................... 11 3.2.13 Time Format ........................................................................................... 12 3.2.14 Select Required ...................................................................................... 12 3.2.15 Select Timeout........................................................................................ 12 3.2.16 Event Enabled ASDU Types................................................................... 12 3.2.17 System Point Listing ............................................................................... 12

3.3 Individual Point Configurations..................................................................... 14 3.3.1 Binary Points........................................................................................... 14 3.3.2 Analog Points.......................................................................................... 15 3.3.3 Counter Points ........................................................................................ 16

3.4 Applying Configurations ............................................................................... 17

3.5 Configuration Errors ..................................................................................... 18

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

2

Page 4: E Series Iec 60870-5-101 Slave Technical Reference

4 ASDU TYPE – RTU CONFIGURATION POINT MAPPING......................... 19

4.1 Binary Points ................................................................................................ 19 4.1.1 Single Point ASDU Types ....................................................................... 19 4.1.2 Double Point ASDU Types...................................................................... 20

4.2 Analog Points ............................................................................................... 22 4.2.1 Normalized and Scaled ASDU Types ..................................................... 22 4.2.2 Floating Point ASDU Types .................................................................... 22 4.2.3 Step Position ASDU (M_ST_NA_1)........................................................ 22 4.2.4 Quality Descriptor Support...................................................................... 22

4.3 Counter Points ............................................................................................. 23 4.3.1 ASDU Type ID 15: M_IT_NA_1 – Integrated Totals ............................... 23

5 SYSTEM INFORMATION COMMANDS...................................................... 24

5.1 ASDU Type ID 100 : C_IC_NA_1 – Interrogation Command ....................... 24

5.2 ASDU Type ID 101 : C_CI_NA_1 – Counter Interrogation Command ......... 24

5.3 ASDU Type ID 103 : C_CS_NA_1 – Clock Synchronization Command ...... 25

5.4 ASDU Type ID 104: C_TS_NA_1 – Test Command .................................... 25

5.5 ASDU Type ID 105: C_RP_NA_1 – Reset Process Command.................... 25

6 MULTIPLE MASTER SUPPORT................................................................. 26

7 COMMAND LINE DIAGNOSTICS............................................................... 27

7.1 Link Layer Diagnostics (including Bytes)...................................................... 27

7.2 Application Layer Diagnostics ...................................................................... 27

7.3 User Layer Diagnostics ................................................................................ 27

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

3

Page 5: E Series Iec 60870-5-101 Slave Technical Reference

Notes Additional information and changes are periodically made and will be incorporated in new editions of this publication. Control Microsystems may make amendments and improvements in the product(s) and/or program(s) described in this publication at any time.

Requests for technical information on software, SCADAPack E Series RTU products and other publications should be made to our agent (from whom you purchased our products/ publications) or directly to:

Technical; Support

Technical support is available from 8:00 to 18:30 (North America Eastern Time Zone). 1-888-226-6876 [email protected]

Other products referred to in this document are registered trademarks of their respective companies, and may carry copyright notices.

DISCLAIMER

CONTROL MICROSYSTEMS cannot warrant the performance or results you may obtain by using the software or documentation. With respect to the use of this product, in no event shall CONTROL MICROSYSTEMS be liable for any loss of profit or any other commercial damage, including but not limited to special, incidental, consequential or other damages.

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

4

Page 6: E Series Iec 60870-5-101 Slave Technical Reference

Document Revisions

Revision Date Modification Author

1.10 3 February 2006 Initial Release of E Series IEC 60870-5-101 Slave Technical Reference

KN

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

5

Page 7: E Series Iec 60870-5-101 Slave Technical Reference

1 Overview This document describes the functionality of the IEC 60870-5-101 Slave driver in the SCADAPack E Series RTU1.

This document should be read in conjunction with the v7 IEC 60870-5-101 Slave Interoperability document which describes the level of support provided by the E Series RTU, and the IEC 60870-5-101 Companion standard which describes the transmission protocol for Telecontrol equipment and systems.

The IEC 60870-5-101 Slave driver in the RTU was implemented in accordance with the IEC 60870-5-101 Companion standard, as well as the standards defined in IEC 60870-5-1 to IEC 60870-5-5.

IMPORTANT: IEC 60870-5-101 Slave functionality is only activated on the E Series RTUs when appropriately licensed. Requests for licensing can be directed to ...

[email protected]

1 Also referred to simply as ‘the RTU’ throughout this document

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

6

Page 8: E Series Iec 60870-5-101 Slave Technical Reference

2 Basic Features 2.1 System Capacity

2.1.1 ASDUs without Time Tag Each configuration point in the RTU may be configured as an IEC 60870-5-101 Slave point. As there is no fixed limit to the number of configuration points that may exist in the RTU, the real upper bound is determined by available configuration memory and operational issues, i.e. the baud rate of the connection and the correct background and cyclic periods for proper operation, which therefore determines the amount of data that may be transported using the available bandwidth.

2.1.2 ASDUs with Time Tags (events) There is an event list created for each relevant ASDU type. The following is a list of ASDU types for which events may be generated

• M_SP_NA_1 (Single Point Information)

• M_DP_NA_1 (Double Point Information)

• M_ST_NA_1 (Step Position Information)

• M_ME_NA_1 (Measured Value, Normalized)

• M_ME_NB_1 (Measured Value, Scaled)

• M_ME_NC_1 (Measured Value, Short Float)

• M_ME_ND_1 (Measured Value, Normalized (no qual.)).

The RTU allows for a maximum of 500 events for each supported ASDU type. If excess events are generated, the oldest events in that particular list are overwritten.

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

7

Page 9: E Series Iec 60870-5-101 Slave Technical Reference

3 Configuration The primary interface for configuring the E Series RTUIEC 60870-5-101 Slave is the E Series Configurator software. The 60870-5-101 Page in the E Series Configurator will only be displayed if 60870-5-101 Slave has been selected in the RTU Features Dialog, which can be displayed by selecting menu entry, View RTU Features... .

Figure 3-1 E Series Configurator -RTU Features Dialog

3.1 Serial Port Configurations The E Series RTU 60870-5-101 Slave functionality is only supported on RTU serial ports. In order to define a specific serial port as an IEC 60870-5-101 Slave port, the Port Function must be set to “60870-5-101 S”. The RTU must then be restarted before the 60870-5-101 driver is started.

Figure 3-2 E Series Configurator Ports Page

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

8

Page 10: E Series Iec 60870-5-101 Slave Technical Reference

Note that the Port Mode must be to RS-232 and the Port Data Mode must use even parity (as specified in the IEC 60870-5-101 Companion standard). Figure 3-2 shows an example configuration from the Ports Page in the E Series Configurator. Consult the E Series Configuration Technical Reference Manual for a detailed list of the serial port system points.

3.2 60870-5-101 System Configurations The IEC 60870-5-101 system configurations for the RTU allow a given Master session to be individually configured. Figure 3-3 shows a screen shot of the 60870-5-101 page in the E Series Configurator which shows that these configurations are duplicated for each supported Master session. The “Event Enabled ASDU type” configurations apply to all Master sessions. Note that the RTU’s 60870-5-101 Slave driver must be restarted for any changed system configurations to take effect. The 101 driver may be restarted by clicking on the “Restart 101” button in the E Series Configurator. These system configurations are mapped to RTU system points. Consult the E Series Configuration Technical Reference Manual for a detailed list of these system points.

Figure 3-3 RTUConfig - 60870-5-101 Page

Note that the 60870-5-101 page in the E Series Configurator allows for configuration of up to 2 Master sessions in the RTU. The following sections describe each field shown in Figure 3-3. The system points that correspond to these configuration fields are detailed in the E Series Configuration Technical Reference Manual.

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

9

Page 11: E Series Iec 60870-5-101 Slave Technical Reference

3.2.1 Master Enabled The Master Enabled checkbox determines whether the respective slave session (for the specified Master address) is enabled in the RTU. The default configurations are listed as follows

• Master 1 Enabled = ON

• Master 2 Enabled = OFF.

If a given Master session is NOT enabled, the RTU will NOT respond to any messages received on the specified COM port for that Master session.

3.2.2 Link and ASDU Address The IEC 60870-5-101 protocol allows for the Link and the ASDU (Common) addresses to be different. The RTU implementation of the IEC 60870-5-101 protocol requires that they both be the same. Therefore the single Link and ASDU Address configuration field is used to assign both the Link and ASDU (Common) addresses for the relevant Master session. The valid range of values for this configuration field is dependent on the Link Address Size field (see section 3.2.4-Link Address Size), i.e. 0 – 255 for 1 octet Link Address size and 0 – 65535 for 2 octet Link Address size.

3.2.3 COM Port This field specifies the serial COM port on the RTU for the relevant Master session. Note that for this configuration to be valid, the specified COM port must also be configured with a PORT FUNCTION of “60870-5-101 S”. If both Master sessions are enabled, they can only share a COM Port if they are both running in Unbalanced Mode (see section 3.2.5-Link Mode). The default configurations for the COM Port field are listed as follows

• Com Port (Master 1) = PORT 0

• Com Port (Master 2) = PORT 1.

3.2.4 Link Address Size This configuration determines the size of the Link Address field specified in all Link transactions for the relevant Master session. The Link Address may be set to one of the following options

• None (invalid in Unbalanced mode)

• 1 Octet

• 2 Octets (default).

Note the Common (or ASDU) Address Size can NOT be configured. It has a fixed length of 2 octets (bytes).

3.2.5 Link Mode This configuration field determines the Link Mode for the respective Master session. The Link Mode may be set to one of the following Options

• Unbalanced (default)

• Balanced.

When operating in Unbalanced mode, communications are initiated by the Master whereby the Master typically makes frequent requests for data (Class 1 or Class 2 polls). When operating in Balanced Mode, the Master does NOT initiate communications, and data is reported by the RTU as

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

10

Page 12: E Series Iec 60870-5-101 Slave Technical Reference

required by it’s configurations. In this mode, the RTU initiates communications typically with a Request Link Status message.

Irrespective of the Link Mode, the RTU (IEC 60870-5-101 Slave) presents data in responses according to it’s configurations whereby “background” data is reported every Background Period (see section 3.2.10-Background Period) and “cyclic” data is reported every Cyclic Period (see section 3.2.9-Cyclic Period). Event data is reported spontaneously as required.

3.2.6 Link Confirm Timeout The Link Confirm Timeout configuration field is specified in seconds, and is only relevant when in Balanced mode. This field specifies the time (in seconds) that the RTU’s 60870-5-101 Slave driver will wait for a response to a Link message before issuing a retry. The default value for this field is 2 seconds.

3.2.7 Link Retries The Link Retries configuration field is only relevant when in Balanced mode. This field specifies the number of link retries for a given message before failing that particular message. The default value for this field is 3.

3.2.8 Clock Valid Period This field determines the period of time for which timestamps are considered valid after receiving a clock synchronization command. Note that when the RTU’s 60870-5-101 driver starts, all timestamps are issued are identified as invalid until a clock synchronization command has been received for that specific master session. The default value for this field is 24 hours.

3.2.9 Cyclic Period The Cyclic Period configuration field is specified in seconds and determines the rate at which

Cyclic data is returned by the RTU’s 60870-5-101 driver. Cyclic data is identified as those analog RTU configuration points which have a valid non-zero Information Object Address, and whose IEC870 Cyclic attribute is set to TRUE (see section 3.3.2-Analog Points). This default value for this field is 60 seconds.

3.2.10 Background Period The Background Period configuration field is specified in seconds and determines the rate at which Background data is returned by the RTU’s 60870-5-101 driver. Background data is identified as all RTU configuration points which have a valid non-zero Information Object Address (IOA) and a valid ASDU Type. This default value for this field is 3600 seconds.

3.2.11 Short Pulse Duration The Short Pulse Duration configuration field is specified in milliseconds and determines the actual PULSE ON duration utilized when a valid binary control is received by the RTU, whereby the qualifier of command for the relevant control object specifies Short Pulse Duration. This default value for this field is 100 milliseconds.

3.2.12 Long Pulse Duration The Long Pulse Duration configuration field is specified in milliseconds and determines the actual PULSE ON duration utilized when a valid binary control is received by the RTU, whereby the

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

11

Page 13: E Series Iec 60870-5-101 Slave Technical Reference

qualifier of command for the relevant control object specifies Long Pulse Duration. This default value for this field is 1000 milliseconds (1 second).

3.2.13 Time Format The Time Format configuration field determines which timestamp format is included with generated event data. The Time Format may be set to one of the following options

• 56 bit (default)

• 24 bit.

The 56 bit Time Format is an absolute time format, whereas the 24 bit Time Format is an incremental time format that only specifies minutes and milliseconds.

3.2.14 Select Required The Select Required configuration field specifies whether or not a Select message is required before an Execute message in order to invoke the specified control. Note that if Select Required is set to TRUE, then a Select message must first be issued, and then followed by an Execute message. The Execute message must be received within the Select Timeout (see section 3.2.15-Select Timeout) period for the control to be invoked. If Select Required is set to FALSE, then an Execute message only is required for the control to be invoked.

3.2.15 Select Timeout The Select Timeout configuration field is specified in seconds. The Execute command must be received within this period after the Select command is received. If an Execute command (matching a recently received Select command) is not received within this period then the control operation is aborted. This default value for this field is 5 seconds.

3.2.16 Event Enabled ASDU Types These configurations determine whether 60870-5-101 events will be generated for RTU configuration points that have been assigned the respective ASDU types.

3.2.17 System Point Listing This section details the analog and binary system points for the IEC 60870-5-101 configurations.

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

12

Page 14: E Series Iec 60870-5-101 Slave Technical Reference

Table 3-1 Analog System Points (60870-5-101)

Point Number Analog System Point Name Start End

Point Type

Master 1 : Enabled 57000 16-bit Integer Master 1 : Link and ASDU Address 57001 16-bit Integer Master 1 : Com Port 57002 16-bit Integer Master 1 : Link Confirm Timeout (s) 57003 16-bit Integer Master 1 : Link Address Size 57004 16-bit Integer Master 1 : Link Mode * 57005 16-bit Integer Master 1 : Link Retries 57006 16-bit Integer Unused 57007 16-bit Integer Master 1 : Clock Valid Period (hours) 57008 16-bit Integer Master 1 : Cyclic Period (s) 57009 16-bit Integer Master 1 : Select Timeout (s) 57010 16-bit Integer Master 1 : Background Period (s) 57011 16-bit Integer Master 1 : Short Pulse Duration (ms) 57012 16-bit Integer Master 1 : Long Pulse Duration (ms) 57013 16-bit Integer Master 1 : Time Format ** 57014 16-bit Integer Master 1 : Select Required 57015 16-bit Integer Unused 57016 57029 16-bit Integer Master 2 : Enabled 57030 16-bit Integer Master 2 : Link and ASDU Address 57031 16-bit Integer Master 2 : Com Port 57032 16-bit Integer Master 2 : Link Confirm Timeout (s) 57033 16-bit Integer Master 2 : Link Address Size 57034 16-bit Integer Master 2 : Link Mode * 57035 16-bit Integer Master 2 : Link Retries 57036 16-bit Integer Unused 57037 16-bit Integer Master 2 : Clock Valid Period (hours) 57038 16-bit Integer Master 2 : Cyclic Period (s) 57039 16-bit Integer Master 2 : Select Timeout (s) 57040 16-bit Integer Master 2 : Background Period (s) 57041 16-bit Integer Master 2 : Short Pulse Duration (ms) 57042 16-bit Integer Master 2 : Long Pulse Duration (ms) 57043 16-bit Integer Master 2 : Time Format ** 57044 16-bit Integer Master 2 : Select Required 57045 16-bit Integer Unused 57046 57299 16-bit Integer

* 0 = Balanced

1 = Unbalanced

** 0 = 24 Bit Time

1 = 56 Bit Time

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

13

Page 15: E Series Iec 60870-5-101 Slave Technical Reference

Table 3-2 Binary System Points (60870-5-101)

Point Number Binary System Point Name Start End

Point Type

M_SP_NA_1 (SPI) Event Enabled 50700 Read / Write M_DP_NA_1 (DPI) Event Enabled 50701 Read / Write M_ST_NA_1 (Step Position) Event Enabled 50702 Read / Write M_ME_NA_1 (Measured Value, Normalised) Event Enabled 50703 Read / Write M_ME_NB_1 (Measured Value, Scaled) Event Enabled 50704 Read / Write M_ME_NC_1 (Measured Value, Short Float) Event Enabled 50705 Read / Write M_ME_ND_1 (Measured Value, Normalised – no qual.) Event Enabled 50706 Read / Write Not used 50707 50719 Read / Write

3.3 Individual Point Configurations The section describes the individual point configurations that can be used to “identify” RTU points as IEC 60870-5-101 Slave points. This section makes reference to the E Series Configurator interface. Consult the E Series Configuration File Format Manual for detailed description of the relevant configuration file mnemonics.

3.3.1 Binary Points The valid configuration attributes for a binary point are listed as follows

• Information Object Address (IOA). This attribute must be a unique non-zero value in the range of 1 – 65535.

• ASDU Type. Valid ASDU types for binary points are listed as follows

• Type ID 1: M_SP_NA_1 – Single Point Information • Type ID 3: M_DP_NA_1 – Double Point Information • Type ID 45 : C_SC_NA_1 – Single Command • Type ID 46 : C_DC_DA_1 – Double Command • Type ID 47 : C_RC_NA_1 – Regulating Step Command.

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

14

Page 16: E Series Iec 60870-5-101 Slave Technical Reference

Figure 3-4 Binary Point Configurations

Note that when a binary point is configured as a double point ASDU type, i.e. Type ID 3 or Type ID 46, two RTU configuration points are referenced with contiguous DNP point numbers. The configuration point with the lower index DNP point number must be configured with the valid IOA and the correct ASDU type. The other point (i.e. the next DNP point number) does NOT require any 60870-5-101 configurations, and must NOT have an assigned IOA, otherwise a configuration error is flagged using the system error code point (see section 3.5 Applying Configurations). Section 4.1.2-Double Point ASDU Types includes examples of double point configurations.

3.3.2 Analog Points The valid configuration attributes for an analog point are listed as follows

• Information Object Address (IOA). This attribute must be a unique non-zero value in the range of 1 – 65535.

• ASDU Type. Valid ASDU types for analog points are listed as follows

• Type ID 5: M_ST_NA_1 – Step Position Information • Type ID 9: M_ME_NA_1 – Measured Value, normalized value • Type ID 11: M_ME_NB_1 – Measured Value, scaled value

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

15

Page 17: E Series Iec 60870-5-101 Slave Technical Reference

• Type ID 13: M_ME_NC_1 – Measured Value, short floating point value • Type ID 21: M_ME_ND_1 – Measured Value, normalized value without quality descriptor • Type ID 48: C_SE_NA_1 – Set point command, normalized value • Type ID 49: C_SE_NB_1 – Set point command, scaled value • Type ID 50: C_SE_NC_1 – Set point command, short floating point value.

Figure 3-5 Analog Point Configuration

3.3.3 Counter Points The valid configuration attributes for a counter point are listed as follows

• Information Object Address (IOA). This attribute must be a unique non-zero value in the range of 1 – 65535.

• ASDU Type = ID 15 : M_IT_NA_1 – Integrated Totals. Note that this is the only ASDU type allowed for RTU counter points..

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

16

Page 18: E Series Iec 60870-5-101 Slave Technical Reference

Figure 3-6 Counter Point Configurations

3.4 Applying Configurations All required configurations may be included in a single configuration file. These configurations may be generated OFFLINE, and then applied to the RTU as required using the Write RTU Configuration facility in the E Series Configurator. The RTU configuration procedures are detailed in the E Series Configuration Technical Reference Manual.

The serial port configurations required to activate the IEC 60870-5-101 Slave driver are detailed in section 3.1-Serial Port Configurations. The RTU must be restarted after applying changed serial port configurations for them to take effect.

The IEC 60870-5-101 System configurations detailed in 3.2-60870-5-101 System Configurations require a restart of the RTU’s 60870-5-101 driver for these configurations to take effect. This driver restart may be issued by clicking on the Restart 101 button, which can be located on the 60870-5-101 page in the E Series Configurator. Consult the E Series Operation Reference Manual for other methods to restart the 101 driver in the RTU.

The individual point configurations detailed in section 3.3-Individual Point Configurations also require a restart of the RTU’s 60870-5-101 driver for these changed configurations to take effect. If these individual point configurations have been applied using the Write Record Exchange Process, a 30 second timer is started. If any subsequent Write Record Exchanges with modified 60870-5-101

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

17

Page 19: E Series Iec 60870-5-101 Slave Technical Reference

configurations, are received by the RTU within that 30 seconds, this timer is restarted. Once the timer expires, the 60870-5-101 driver is restarted.

3.5 Configuration Errors Any 60870-5-101 configuration errors are detected whenever the 60870-5-101 driver is restarted. On detection of a configuration error, the error code system point (analog 50020) is written with the value 3004. Consult the E Series Operation Reference Manual for detailed descriptions of all RTU error codes.

The following conditions may cause a 60870-5-101 configuration error

• memory allocation failure on driver start-up

• 60870-5-101 system configurations invalid

• invalid double point configuration, e.g. second point doesn’t exist OR seconds point has a non-zero Information Object Address (IOA)

• duplicate Information Object Address (IOA) detected

• invalid ASDU type for specified point type.

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

18

Page 20: E Series Iec 60870-5-101 Slave Technical Reference

4 ASDU Type – RTU Configuration Point Mapping The section describes how the different ASDUs correspond to RTU configuration points for both input types and controls, including double point configurations, analog point scaling, and quality descriptor support.

4.1 Binary Points

4.1.1 Single Point ASDU Types Note that single point types ASDUs include Information Objects that reference a single Information Object Address (IOA) which maps to a single binary configuration point.

4.1.1.1 ASDU Type ID 1: M_SP_NA_1 – Single Point Information For ASDU Type ID 1 (Single Point Information), the value reported in the SPI of the Information Object is derived from the Current State of the binary point. The IV bit of the quality descriptor (SIQ) is mapped to the Point Is Failed property of the binary configuration point. Note that the NT, SB, and BL bits in the quality descriptor (SIQ) are not referenced.

4.1.1.2 ASDU Type ID 45: C_SC_DA_1 – Single Command The following table determines how a binary output point is controlled for Single Command type ASDU.

Table 4-1 ASDU Type ID 45 : Control State Table

ASDU 45 Single Command

State (SCS) SCS

Description Qualifier of Command

(QU)

QU Description RTU Binary Output

0 No additional definition Latched OFF

1 Short pulse duration Pulsed ON (Short)

2 Long pulse duration Pulsed ON (Long) 0 OFF

3 Persistent Output Latched OFF

0 No additional definition Latched ON

1 Short pulse duration Pulsed ON (Short)

2 Long pulse duration Pulsed ON (Long) 1 ON

3 Persistent Output Latched ON

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

19

Page 21: E Series Iec 60870-5-101 Slave Technical Reference

4.1.2 Double Point ASDU Types Note that when a binary point is configured as a double point ASDU type, i.e. Type ID 3 or Type ID 46, two RTU configuration points are referenced with contiguous DNP point numbers. The configuration point with the lower index DNP point number must be configured with the valid IOA and the correct ASDU type. The other point (i.e. the next DNP point number) does NOT require any 60870-5-101 configurations, and must NOT have an assigned IOA, otherwise a configuration error is flagged using the system error code point (see section 3.5- Configuration Errors).

4.1.2.1 ASDU Type ID 3: M_DP_NA_1 – Double Point Information Consider the following configurations as an example

Derived Binary 41000 (i.e. DNP Index 41000)

• ASDU Type = 3 (Double Point Information)

• IOA = 22000

Derived Binary 41001 (i.e. DNP Index 41001)

• ASDU Type = 1 (Single Point Information)

• IOA = 0.

Note that the configurations for Derived Binary 41001 are default values. Note also that the “second” point configuration in a double point pair, is modified by the RTU on start-up whereby the ASDU type is changed from the default value (1) to be 3, i.e. Double Point Information.

The following state table determines how the data is returned for IOA 22000 as a Double Point Information type ASDU.

Table 4-2 ASDU Type ID 3 : State Table

Derived Binary 41000 (Current State)

Derived Binary 41001 (Current State)

DPI (Double Point Information)

Double Point Information Description

0 0 0 indeterminate or intermediate state

1 0 1 determined state OFF

0 1 2 determined state ON 1 1 3 indeterminate state

The IV bit of the quality descriptor (SIQ) is mapped to the logical OR of the Point Is Failed property of the two binary configuration points. Note that the NT, SB, and BL bits in the quality descriptor (SIQ) are not referenced.

4.1.2.2 ASDU Type ID 46: C_DC_DA_1 – Double Command Consider the following configurations as an example

Physical Binary Output 8 (i.e. DNP Index 8)

• ASDU Type = 46 (Double Command)

• IOA = 10600

Physical Binary Output 9 (i.e. DNP Index 9)

• ASDU Type = X (any value)

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

20

Page 22: E Series Iec 60870-5-101 Slave Technical Reference

• IOA = 0

Note that the configurations for Physical Binary Output 9 are default values, i.e. the second point in a double command pair does NOT have to be configured as a double command ASDU type. The following state table determines how the output points are controlled for IOA 10600 as a Double Command type ASDU.

Table 4-3 ASDU Type ID 46 : Control State Table (using example config)

ASDU 46 RTU Binary Outputs Double Command

State (DCS) DCS

Description Qualifier of Command

(QU)

QU Description Binary Output 8 (State)

Binary Output 9 (State)

0 Not permitted X (any value) - No action No action

0 No additional definition Latched ON Latched OFF

1 Short pulse duration Pulsed ON (Short) No action

2 Long pulse duration Pulsed ON (Long) No action 1 OFF

3 Persistent Output Latched ON Latched OFF

0 No additional definition Latched OFF Latched ON

1 Short pulse duration No action Pulsed ON (Short)

2 Long pulse duration No action Pulsed ON (Long) 2 ON

3 Persistent Output Latched OFF Latched ON

3 Not permitted X (any value) - No action No action

4.1.2.3 ASDU Type ID 47: C_RC_NA_1 – Regulating Step Command Consider the following configurations as an example

Physical Binary Output 15 (i.e. DNP Index 15)

• ASDU Type = 47 (Regulating Step Command)

• IOA = 10700

Physical Binary Output 16 (i.e. DNP Index 16)

• ASDU Type = X (any value)

• IOA = 0

Note that the configurations for Physical Binary Output 16 are default values, i.e. the second point in a regulating step (double command) pair does NOT have to be configured as a Regulating Step command ASDU type. The following state table determines how the output points are controlled for IOA 10700 as a Regulating Step type ASDU.

Table 4-4 ASDU Type ID 47 : Control State Table (using example config)

ASDU 47 RTU Binary Outputs Regulating Step Command State

(RCS)

RCS Description

Qualifier of Command

(QU)

QU Description Binary Output 15 (State)

Binary Output 16 (State)

0 Not permitted X (any value) - No action No action

0 No additional definition Latched ON Latched OFF

1 Short pulse duration Pulsed ON (Short) No action

2 Long pulse duration Pulsed ON (Long) No action 1 next Step LOWER

3 Persistent Output Latched ON Latched OFF

2 next Step 0 No additional definition Latched OFF Latched ON

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

21

Page 23: E Series Iec 60870-5-101 Slave Technical Reference

1 Short pulse duration No action Pulsed ON (Short)

2 Long pulse duration No action Pulsed ON (Long) LOWER

3 Persistent Output Latched OFF Latched ON

3 Not permitted X (any value) - No action No action

4.2 Analog Points Analog configuration points may be identified as either scaled, normalized or floating points in IEC 60870-5-101 slave responses. The following sections describe how the RTU point’s current value is represented in these ASDU types.

4.2.1 Normalized and Scaled ASDU Types The Normalized and Scaled ASDU types include a 16-bit value in the Information Object. The literal interpretation of this value varies according to that specified in the IEC 60870-5-101 standard, i.e. F16 and I16 standard information elements as defined in IEC 60870-5-4.

The Current Integer Value of the analog configuration point is mapped to this 16-bit value as shown as in the following table. Note that the Raw Min and Raw Max attributes are standard scaling parameters for RTU configuration points that default to values of 0 and 10000 respectively.

Table 4-5 Analog Point Scaling - Normalized and Scaled ASDU Types

Current Integer Value Normalized Value (F16) Scaled Value (I16)

Raw Min (default = 0) -1 -215

Raw Max (default = 10000) 1-2-15 215 – 1 Given the scaling and default values shown in Table 4-5, a current integer value of 5000 would map to a normalized and scaled value of 0 in the respective 101 Information Object.

Note that if the Current Integer Value is outside of the reportable 16-bit range, the included value is clamped appropriately and the OVERFLOW bit in the quality descriptor is set.

4.2.2 Floating Point ASDU Types The Floating Point ASDU types reference a short float value in the Information Object whereby the Current Engineering Value (float value) of the analog configuration point is mapped to the R32.23 information elements as defined in IEC 60870-5-4. 4.2.3 Step Position ASDU (M_ST_NA_1) The Current Integer Value of the analog configuration point is directly mapped to the 7-bit Value included on the Information Object. If the Current Integer Value is outside of the valid Value range, i.e. -64 to 63, the OVERFLOW bit in the quality descriptor (QDS) is set. The Transient bit in the VTI field is not referenced.

4.2.4 Quality Descriptor Support For all of the supported analog type ASDUs, there is limited support for quality descriptor fields.

• The IV bit of the quality descriptor (QDS) is mapped to the Point Is Failed property of the analog configuration point.

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

22

Page 24: E Series Iec 60870-5-101 Slave Technical Reference

• The OV bit is set if the current value of the point is beyond the reportable range according to the specific ASDU type.

• The NT, SB, and BL bits in the quality descriptor (QDS) are not referenced.

4.3 Counter Points The counter points may only be configured as ASDU type 15, i.e. M_IT_NA_1 (Integrated Totals). The counter values reported in this ASDU type are always frozen values. All counter (integrated total) values are retrieved from the RTU using Counter Interrogation Commands. For more details regarding counter support in the RTU’s 60870-5-101 Slave driver, refer to section 5.2-ASDU Type ID 101 : C_CI_NA_1 – Counter Interrogation Command.

4.3.1 ASDU Type ID 15: M_IT_NA_1 – Integrated Totals The information object in the Integrated Totals ASDU includes a signed 32-bit value, which is identified as a Binary Counter Reading (BCR). The Current Integer Value of the counter point (unsigned 32-bit) is copied into the cached frozen value for the particular Information Object Address (IOA) when a “Counter Freeze” request is made via a Counter Interrogation Command. For every COUNTER FEEZE command received from the relevant Master, the sequence number (SQ) for that IOA is incremented.

The invalid (IV) bit included in the information object is mapped to the Point Is Failed property of the counter configuration point.

The Counter Adjusted (CA) bit included in the information object is set if the counter value has been reset due to a COUNTER FREEZE request, and is only asserted for the first READ after the COUNTER FREEZE. The CA bit is also set on RTU start-up if the Counter Reset attribute of the counter configuration point was set to TRUE (see the E Series RTU Configuration Technical Reference Manual for more details regarding counter point attributes).

The Carry (CY) bit is not referenced by the RTU’s 60870-5-101 Slave driver.

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

23

Page 25: E Series Iec 60870-5-101 Slave Technical Reference

5 System Information Commands This section details the additional system commands supported by the RTU’s IEC 60870-5-101 Slave driver. The corresponding ASDU types are listed as follows

• Type ID 100: C_IC_NA_1 – Interrogation Command

• Type ID 101: C_CI_NA_1 – Counter Interrogation Command

• Type ID 103: C_CS_NA_1 – Clock Synchronization Command

• Type ID 104: C_TS_NA_1 – Test Command

• Type ID 105: C_RP_NA_1 – Reset Process Command

5.1 ASDU Type ID 100 : C_IC_NA_1 – Interrogation Command The RTU’s IEC 60870-5-101 Slave driver will present Background and Cyclic data as determined by the system configuration parameters Background Period and Cyclic Period. Note that this data may also be reported in response to an Interrogation Command (ASDU Type 100). Note that the only qualifier supported for the Interrogation Command is the Station Interrogation (20).

The Interrogation Command may be issued by the Master in order to synchronize information between the controlling station (Master) and the controlled station (RTU), or to update the controlling station database after an initialization procedure has taken place in the RTU.

5.2 ASDU Type ID 101 : C_CI_NA_1 – Counter Interrogation Command The RTU’s IEC 60870-5-101 Slave driver supports Counter Interrogations only in Mode C (Freeze and transmit by counter interrogation commands). The integrated totals (counter points) in the RTU can only be frozen, reset, or read using the Counter Interrogation Command. Note that the only qualifier supported for the Counter Interrogation Command is the General Request Counter (5) which references ALL counters in the RTU.

All counter values retrieved from the RTU are frozen values. If the Counter Interrogation Command specifies a FREEZE in the qualifier, the sequence number reported for subsequent READ is incremented. If the Counter Interrogation Command specifies a FREEZE WITH RESET in the qualifier, the Current Integer Value of the counter configuration point is set to 0, and the Counter Adjusted (CA) bit included in the information object is set for the first READ after the FREEZE WITH RESET.

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

24

Page 26: E Series Iec 60870-5-101 Slave Technical Reference

5.3 ASDU Type ID 103 : C_CS_NA_1 – Clock Synchronization Command The Clock Synchronization Command specifies a CP56Time2a object in the Information Object which will used to set the RTU’s real time clock. If the RTU is configured to use NTP time synchronization, the Clock Synchronization Command will NOT set the RTU’s real time clock but will still respond with a positive activation response to the Clock Synchronization Command.

IMPORTANT

Note that there are other methods of time synchronization in the RTU. If NTP Time Synchronization is NOT being used, ensure that ONLY ONE of the slave protocols is being used for time synchronization, as both the 60870-5-101 Slave and the DNP3 Slave driver in the RTU will accept and process time synchronization messages. 5.4 ASDU Type ID 104: C_TS_NA_1 – Test Command The Test Command is supported by the RTU’s 60870-5-101 Slave driver such that specified fixed bit pattern is included in the response to the Test Command.

5.5 ASDU Type ID 105: C_RP_NA_1 – Reset Process Command The Reset Process Command will be processed by the RTU and a positive activation response will be issued. Currently there is no support for restarting any of the RTU’s internal processes. Support for the Reset Process Command will be extended in future firmware releases.

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

25

Page 27: E Series Iec 60870-5-101 Slave Technical Reference

6 Multiple Master Support The RTU’s IEC 60870-5-101 Slave driver will support communications with up to 2 Masters. The default configuration enables only a single Master session. The 60870-5-101 system configurations are duplicated for each enabled Master session (see section 3.2-60870-5-101 System Configurations), allowing each Master session to be independently configured.

Each Master session has it’s own event list such that a given 60870-5-101 event will NOT be removed from the RTU’s 60870-5-101 event list until it has been retrieved by all enabled Master sessions.

The Integrated Totals sequence numbers (described in section 4.3.1- ASDU Type ID 15: M_IT_NA_1 – Integrated Totals) are maintained for each enabled Master session, i.e. a FREEZE Counter Interrogation Command received from Master 1 will only increment the sequence number returned to the next READ request from Master 1, and the sequence number for Master 2 will remain unmodified.

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

26

Page 28: E Series Iec 60870-5-101 Slave Technical Reference

7 Command Line Diagnostics The RTU provides a diagnostic display which can be used to verify IEC 60870-5-101 communications between the RTU (as a Slave) and the connected Master. These 60870-5-101 diagnostics can be obtained using one of the following methods

• direct serial connection to a CMDLINE port

• TELNET connection

• FILEDIAG (logged diagnostics to RTU File System).

Refer to the E Series Operation Reference Manual for more details on these methods of accessing RTU diagnostics.

The S101DIAG command is used to filter IEC 60870-5-101 diagnostics displays when in Diagnostic Session display mode (type DIAG at the command line to enter diagnostic mode).

The format of the S101DIAG command is: S101DIAG mode filter [filter ....] Where: mode = ENABLE DISABLE filter = * APPL BYTES LINK TIMESTAMP USER

Note that enabling IEC 60870-5-101 diagnostics can have some impact on system performance. It is suggested that these diagnostics be disabled when not in use.

The command filters can be individually enabled or disabled (all are retained in NV memory).

* All filters enabled / disabled

APPL 60870-5-101 Application Layer information

BYTES 60870-5-101 Link Layer packet bytes (requires LINK filter)

TIMESTAMP Time of 60870-5-101 message diagnostic

USER v7 user application response information

The following sections are examples of filtered diagnostic information where the RTU Link and ASDU (common) address is 21. These examples are time-stamped (i.e. TIMESTAMP filter has been enabled). Note that outbound link messages are indicated as <..., whereas inbound messages are indicated as ...>.

7.1 Link Layer Diagnostics (including Bytes) ...> PORT0 Primary Frame - Request User Data Class 2 DIR(0) PRM(1) FCV(1) FCB(0) ADDR(21) 10 5b 15 00 70 16 <... PORT0 Secondary Frame - Respond Data Not Available DIR(0) PRM(0) DFC(0) ACD(0) ADDR(21) 10 09 15 00 1e 16

7.2 Application Layer Diagnostics ~~~> Master 1 Addr(21) Sector(21) Application Header, Clock synchronization command Quantity(1) SQ(0) COT(6, activation) <~~~ Master 1 Addr(21) Sector(21) Application Header, Clock synchronization command Quantity(1) SQ(0) COT(7, positive activation confirmation)

7.3 User Layer Diagnostics

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

27

Page 29: E Series Iec 60870-5-101 Slave Technical Reference

<=== Master 1 Insert request in queue: Background Response

E Series IEC 60870-5-101 Slave Technical Reference May 29, 2006

28