Voltage regulator TAPCON® 240

Supplement 2398402/00Protocol description for IEC 60870-5-103

Page 2: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

© All rights reserved by Maschinenfabrik Reinhausen

Copying and distribution of this document and utilization and communication of its contents are strictly prohibited unless expressly authorized.

Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or ornamental design registration.

The product may have been modified after this document went to press.

We expressly reserve the right to make changes to the technical data, the design or the scope of delivery.

Generally, the information provided and the arrangements agreed during processing of the relevant quotations and orders are binding.

The original operating instructions were drawn up in German.

Page 3: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

Table of Contents

© Maschinenfabrik Reinhausen 2010 2398402/00 EN TAPCON® 240 3

Table of Contents

1 General notes ............................................................................... 5

1.1 About this document ................................................................................. 5

1.2 Information about the standard ................................................................. 5

1.3 Abbreviations used ................................................................................... 6

2 Voltage regulator connections .................................................... 7

3 Settings on the voltage regulator ............................................... 9

3.1 Communication interface RS232 .............................................................. 9

3.2 Communication interface RS485 ............................................................ 10

3.3 Fiber-optic cable (optional) ..................................................................... 10

4 Data points .................................................................................. 11

4.1 Message structure .................................................................................. 11

4.1.1 Function types ..................................................................................................... 11

4.1.2 Type codes ......................................................................................................... 11

4.1.3 Data types ........................................................................................................... 11

4.2 Monitoring direction ................................................................................. 12

4.2.1 General commands in monitoring direction ........................................................ 12

4.2.2 Signals at the digital input terminals ................................................................... 14

4.2.3 Generic data in monitoring direction ................................................................... 15

4.3 Control direction ...................................................................................... 15

4.3.1 System functions ................................................................................................. 15

4.3.2 General data in control direction ......................................................................... 16

4.3.3 Generic data in control direction ......................................................................... 17

Page 4: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

Table of Contents

4 TAPCON® 240 2398402/00 EN © Maschinenfabrik Reinhausen 2010

5 Sample sequences ..................................................................... 19

5.1 Time synchronization .............................................................................. 19

5.2 General query ......................................................................................... 20

5.3 General command .................................................................................. 21

5.4 General query, generic data ................................................................... 22

5.5 Generic command (write entry with version) .......................................... 23

6 Tap position telegram ................................................................ 25

6.1 Structure of telegram .............................................................................. 25

6.2 Examples of messages for tap position telegrams ................................. 27

6.3 Setting time and date settings ................................................................ 28

Page 5: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

1 General notes

© Maschinenfabrik Reinhausen 2010 2398402/00 EN TAPCON® 240 5

1 General notes

1.1 About this document

This document describes implementation of the interface protocol IEC60870-5-103 for the TAPCON® 240.

Read this description along with the technical file for the TAPCON® 240.

1.2 Information about the standard

The <Communication protocol> interface protocol was originally developed for communication between protective devices. The pre-defined function types and associated information numbers are not suitable for the information that the voltage regulator has to transfer.

A function type from the "private sphere" of the protocol is therefore used for all "non-generic data points".

The information numbers for all general commands and messages with the function type from the "private sphere" are specific.

Analog values are transferred in the control direction (command) and monitor-ing direction (message) using a generic message type. All measured values are assigned to class 2 and all parameters to class 1.

In addition to the 9.6 and 19.2 kilobaud rates required by the standard, baud rates of 38.4 and 57.6 kilobauds can also be selected on the voltage regula-tor.

Page 6: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

1 General notes

6 TAPCON® 240 2398402/00 EN © Maschinenfabrik Reinhausen 2010

1.3 Abbreviations used

Abbreviation Definition

ASDU Application Service Data Unit

BCD Binary Coded Decimal

CIC Communication Interface Card

GQ General query

GPI General Purpose Input

GPO General Purpose Output

Fiber-optic cab-le

Fiber-optic cable

MR Maschinenfabrik Reinhausen

RTC Real Time Clock

TAPCON®trol PC software for displaying regulator data

Table 1 Abbreviations

Page 7: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

2 Voltage regulator connections

© Maschinenfabrik Reinhausen 2010 2398402/00 EN TAPCON® 240 7

2 Voltage regulator connections

The physical interfaces RS232, RS485 and optional fiber-optic cables are provided on the voltage regulator for data transfer via the IEC60870-5-103 protocol.

Figure 1 CIC card

1 RS232 (9 pin female SUB-D connector)

2 RS485

3 Ethernet RJ45 (optional)

4 FH-ST or F-SMA fiber-optic cable in 850 nm or 660 nm (optional)

5 Reset key

6 TxD LED for transmit signal

7 RxD LED for receive signal

8 Clk LED for operating mode (flashes for 2 seconds)

9 Clip for connecting cable shield with functional ground

Page 8: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

2 Voltage regulator connections

8 TAPCON® 240 2398402/00 EN © Maschinenfabrik Reinhausen 2010

RS232

9 pin female SUB-D connector Pin 2: TxD Pin 3: RxD Pin 5: GND

RS485

3 pin connector from Phoenix (MC1.5/3 GF 3.5) Pin 1: GND (100 Ω ground resistance) Pin 2: B (inverted) Pin 3: A (not inverted) Polarity: A > B by 200 mV corresponds to 1. A < B by 200 mV corresponds to 0. An interrupted communication line corresponds to 1. The start bit has the designation 0. Recommended terminating resistor 120 Ω.

Fiber-optic cable (optional)

FH-ST (850 nm or 660 nm) F-SMA (850 nm or 660 nm)

Table 2 Interfaces available

Transfer on physical plane: Asynchronous with 8 data bits, even parity, 1 stop bit (8E1)

Page 9: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

3 Settings on the voltage regulator

© Maschinenfabrik Reinhausen 2010 2398402/00 EN TAPCON® 240 9

3 Settings on the voltage regulator

The following chapters describe how to set the parameters for communication at the relevant interface on the TAPCON® 240.

> Configuration > Next* > Comm. interface

Depending on the product version and software, you will need to press "Next" a varying number of times to reach the "Comm. interface" menu.

You will find more information on how to set the parameters in the technical file for TAPCON® 240.

3.1 Communication interface RS232

Communication interface RS232

Baud rate communication 9.6/19.2/38.4/57.6 kilobaud

Fiber-optic cable light ON/OFF

not used

Local SCADA address 1...255 (0 = Broadcast message)

Send delay time 0...254 ms*

Table 3 Interface settings RS232

Page 10: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

3 Settings on the voltage regulator

10 TAPCON® 240 2398402/00 EN © Maschinenfabrik Reinhausen 2010

3.2 Communication interface RS485

Communication interface RS485

Baud rate communication 9.6/19.2/38.4/57.6 kilobaud

Fiber-optic cable light ON/OFF

not used

Local SCADA address 0...254 (255 = Broadcast message)

Send delay time 0...254 ms*

Table 4 Interface settings RS485

*) e.g 2 ms, in order to compensate for the response time of an external con-verter RS485/RS232 when switching between transmit and receive operation.

3.3 Fiber-optic cable (optional)

Communication interface Fiber-optic cable

Baud rate communication 9.6/19.2/38.4/57.6 kilobaud

Fiber-optic cable light ON/OFF

ON (1 corresponds to light On) or OFF (1 corresponds to light Off)

Local SCADA address 0...254 (255 = Broadcast message)

Send delay time not used

Table 5 Interface settings Fiber-optic cable

In addition to the 9.6 and 19.2 kilobaud rates required by the standard, baud rates of 38.4 and 57.6 kilobauds can also be selected on the voltage regula-tor.

Page 11: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

4 Data points

© Maschinenfabrik Reinhausen 2010 2398402/00 EN TAPCON® 240 11

4 Data points

4.1 Message structure

The function types, type codes and data types which are listed in the data tables are explained below.

4.1.1 Function types

110 = function type from the private sphere (can be defined specifically) 254 = generic function type 255 = global function type

4.1.2 Type codes

1 = message with time stamp 6 = time synchronization 7 = general query 10 = generic data 20 = general command 21 = generic command

4.1.3 Data types

7 = short real

Page 12: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

4 Data points

12 TAPCON® 240 2398402/00 EN © Maschinenfabrik Reinhausen 2010

4.2 Monitoring direction

All spontaneous messages (in the event of changes) are transmitted with a time stamp. The time stamp always relates to when the message is sent. A message caused by a general query is sent without a time stamp.

4.2.1 General commands in monitoring direction

Type code

Info no. Byte 2

Info no. Byte 1

Class Description

1 110 16 1 Auto/manual (On = auto mode; Off = manual mode)

1 110 19 1 Desired voltage value 1 On

1 110 20 1 Desired voltage value 2 On

1 110 21 1 Desired voltage value 3 On

1 110 27 1 SI command 1 active*

1 110 28 1 SI command 2 active*

1 110 29 1 SI command 3 active*

1 110 31 1 Motor-drive unit running

Messages which can be parameterized: The TAP-CON® 240 has 4 messages which can be paramete-rized. These can be put on an input or relay. The messages are ON when there is a signal at the para-meterized input or the parameterized relay is acti-vated.

1 110 33 1 Message no. 1

1 110 34 1 Message no. 2

1 110 43 1 Message no. 3

1 110 39 1 Message no. 4

1 110 35 1 Parallel operation On Parallel operation is only active when all conditions for parallel operation are met.

1 110 36 1 Master parallel operation method On (feedback)

1 110 37 1 Follower parallel operation method On (feedback)

1 110 38 1 Circulating reactive current parallel operation method On (feedback)

1 110 40 1 Parallel operation error

1 110 49 1 Voltage regulator error ON when recording a parameterization error.

Page 13: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

4 Data points

© Maschinenfabrik Reinhausen 2010 2398402/00 EN TAPCON® 240 13

Type code

Info no. Byte 2

Info no. Byte 1

Class Description

4 110 118 1

Tap position This is an alternative way of recording the tap position. The value is the same as under GIN LSB 54 and GIN MSB 2.

204 110 54 1

Tap position This is another way for the control system to record the tap position. The value is the same as for the other tap position telegrams.

1 110 51 1 Function monitoring (a control deviation has existed for 15 minutes)

1 110 42 1 Local/Remote (On = Remote; Off = Local)

1 110 44 1 Overvoltage V>

1 110 45 1 Undervoltage V<

1 110 46 1 Overcurrent I>

Table 6 Data points in monitoring direction

Page 14: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

4 Data points

14 TAPCON® 240 2398402/00 EN © Maschinenfabrik Reinhausen 2010

4.2.2 Signals at the digital input terminals

Most signals can be transferred to the SCADA system via the digital input terminals.

When triggered, the interface addresses to the corresponding inputs behave as follows:

Type code

Info no. Byte 2

Info no. Byte 1

Class

Description

Card type Specification for hardware version I

Specification for hardware version III

1 110 65 1 IO X1/z20 X1/33

1 110 66 1 IO X1/d20 X1/31

1 110 67 1 UC1 X1/d30 X1/33

1 110 68 1 UC1 X1/b30 X1/32

1 110 69 1 UC1 X1/d28 X1/31

1 110 70 1 UC1 X1/b28 X1/30

1 110 71 1 UC1 X1/d26 X1/17

1 110 72 1 UC1 X1/b26 X1/16

1 110 73 1 UC1 X1/d24 X1/15

1 110 74 1 UC1 X1/b24 X1/14

1 110 75 1 UC1 X1/d22 X1/11

1 110 76 1 UC1 X1/b22 X1/12

1 110 77 1 UC2 X2/d30 X2/33

1 110 78 1 UC2 X2/b30 X2/32

1 110 79 1 UC2 X2/d28 X2/31

1 110 80 1 UC2 X2/b28 X2/30

1 110 81 1 UC2 X2/d26 X2/17

1 110 82 1 UC2 X2/b26 X2/16

1 110 83 1 UC2 X2/d24 X2/15

1 110 84 1 UC2 X2/b24 X2/14

1 110 85 1 UC2 X2/d22 X2/11

1 110 86 1 UC2 X2/b22 X2/12

Table 7 Signals at the digital input terminals

Page 15: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

4 Data points

© Maschinenfabrik Reinhausen 2010 2398402/00 EN TAPCON® 240 15

4.2.3 Generic data in monitoring direction

Type code

Func-tion type

GIN LSB

GIN MSB

Data type

Class Description

10 254 54 2 7 1 Tap position

Set values Since the set values are transferred as the "Short real" data type, deviations may arise be-tween the set value and the value transferred via the interface if the set value cannot be depicted accurately as a "Short real" value.

10 254 55 1 7 1 Desired voltage value 1

10 254 144 2 7 2 Actual voltage

10 254 145 2 7 2 Deviation

10 254 146 2 7 2 Active current

10 254 147 2 7 2 Reactive current

10 254 148 2 7 2 Apparent current

Table 8 Generic data in monitoring direction

4.3 Control direction

For commands from the control system to be executed on the Monitoring system, Remote mode must be set.

4.3.1 System functions

Type code Description

7 Start of general query

6 Time synchronization

21 Start of general query for generic data

Table 9 System functions

A message to indicate the end of the general query follows the last info mes-sage for the GQ cycle.

Page 16: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

4 Data points

16 TAPCON® 240 2398402/00 EN © Maschinenfabrik Reinhausen 2010

4.3.2 General data in control direction

Type code

Info no. Byte 2

Info no. Byte 1

Class Description

20 110 16 1 Auto/manual (On = auto mode; Off = manual mode)

20 110 17 1 Raise (On = raise; Off = lower; only in manual mode)

20 110 18 1 Lower (On = lower, Off = no function; only during ma-nual mode)

20 110 19 1 Raise/lower desired voltage value This function is optional. Parameterization is underta-ken by MR.

The desired voltage value function 1/2/3 is possible under the following conditions: - no inputs parameterized for selecting desired voltage values 2 and 3 - raise/lower desired voltage value function not parameterized Parameterization is undertaken by MR.

20 110 19 1 Desired voltage value 1

20 110 20 1 Desired voltage value 2

20 110 21 1 Desired voltage value 3

Each SI command sets a flag in the TAPCON® 240. The status of the flags can be used like an input for the I/O or UC modules to activate or deactivate a TAPCON® 240 function. Example: If the "Parallel group input" parameter is set to "SI:cmd1" for two TAPCON® 240, parallel control for these TAPCON® 240 can be activated or deactivated by setting the "SI command 1" on/off command for both TAPCON® 240.

20 110 27 1 SI command 1

20 110 28 1 SI command 2

20 110 29 1 SI command 3

20 110 35 1 Parallel operation (On = activate circulating reactive current parallel operation, Off = deactivate parallel op-eration)

20 110 36 1 Master parallel operation method (On = activate mas-ter parallel operation mode, Off = activate "Automatic synchronization" parallel operation mode)

20 110 37 1 Follower parallel operation method (On = activate fol-lower parallel operation mode)

Table 10 General data in control direction

The voltage regulator returns the command received with reason for trans-mission 20 if the message has been accepted.

Page 17: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

4 Data points

© Maschinenfabrik Reinhausen 2010 2398402/00 EN TAPCON® 240 17

The voltage regulator can only process generic commands with one data set per message.

4.3.3 Generic data in control direction

Type code

Func-tion type

GIN LSB

GIN MSB

Data type

Class Description

10 254 55 1 7 1 Voltage level

Table 11 Generic data in control direction

Page 18: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103
Page 19: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

5 Sample sequences

© Maschinenfabrik Reinhausen 2010 2398402/00 EN TAPCON® 240 19

5 Sample sequences

5.1 Time synchronization

Sample command for time synchronization: 68 f f 68 28 1 6 81 8 1 ff 0 77 9 2f 88 90 9 9 91 16

Code (hexadecimal)

Definition

68 f f 68 28 1 Start message

6 Type code = 6 (decimal) = Time synchronization command

8 Reason for transmission = 8 = Time synchronization

ff Function type = 255 = Global function type

0 Info number (or address of information object 2nd oc-tet) = 0 = Time synchronization

9 2f 88 90 9 9 Time structure CP56Time2a

91 16 End message

Figure 2 Sample command for time synchronization

After time synchronization, the voltage regulator returns the time synchroniza-tion feedback as positive confirmation. The reason for transmission is set to 8.

These time details are only used for display purposes in the TAPCON®trol vi-sualization software; internally the regulator uses a continuous RTC.

The time stamp in the regulator's telegrams is produced by the communica-tion card and is only set when the telegram is sent.

Page 20: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

5 Sample sequences

20 TAPCON® 240 2398402/00 EN © Maschinenfabrik Reinhausen 2010

5.2 General query

Sample command for general query (GQ): 68 9 9 68 43 1 7 81 9 1 ff 0 0 d5 16

Code (hexadecimal)

Definition

68 9 9 68 43 1 Start message

7 Typ code = 7 (decimal) = General query

9 Reason for transmission = 0 = not used

ff Function type (or address of information object 1st octet) = 255 = Global function type

0 Info number (or address of information object 2nd oc-tet) = 0

d5 16 End message

Figure 3 Sample command for general query (GQ)

After the last data message from the general query cycle, the "GQ complete" message is issued with type code 8 and reason for transmission 10.

Page 21: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

5 Sample sequences

© Maschinenfabrik Reinhausen 2010 2398402/00 EN TAPCON® 240 21

5.3 General command

Example of general command: 68 a a 68 43 1 14 81 14 1 ff 0 0 d5 16

Code (hexadecimal)

Definition

68 a a 68 43 1 Start message

14 Typ code = 20 (decimal) = General command

14 Reason for transmission = 20 (decimal) = General command

6e Function type = 110 (decimal) = Private sphere

10 Info number (or address of information object 2nd oc-tet) = 16 (decimal) = Auto/Manual

1 Value = OFF

6d 16 End message

Figure 4 Example of general command

Once it has received a valid command, the voltage regulator returns the command message as positive confirmation. The reason for transmission is set to 20.

Page 22: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

5 Sample sequences

22 TAPCON® 240 2398402/00 EN © Maschinenfabrik Reinhausen 2010

5.4 General query, generic data

Sample command for general query, generic data: 68 a a 68 43 1 15 81 9 1 fe f5 0 0 d7 16

Code (hexadecimal)

Definition

68 a a 68 43 1 Start message

15 Type code = 21 (decimal) = General query

9 Reason for transmission = 9 = not used

fe Function type (or address of information object 1st octet = 254 (decimal) = Generic funktion type

f5 Info number (or address of information object 2nd oc-tet) = 245 (decimal) = General query, generic data

d7 16 End message

Figure 5 Sample command for general query, generic data

After the last data transfer for the "General query", a message entitled "GQ complete" is transferred with type code 10, info number 245 and reason for transmission 10.

Page 23: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

5 Sample sequences

© Maschinenfabrik Reinhausen 2010 2398402/00 EN TAPCON® 240 23

5.5 Generic command (write entry with version)

Example of generic command (write entry with version): 68 14 14 68 43 1 a 81 28 1 fe fa 0 1 1 37 1 1 7 4 1 0 0 ca 42 42 16

Code (hexadecimal)

Definition

68 14 14 68 43 1 Start message

a Type code = 10 (decimal) = Generic Data

28 Reason for transmission = 40 = Generic write com-mand

fe Function type (or address of information object 1st octet) = 254 (decimal) = Generic function type

fa Info number (or address of information object 2nd oc-tet) = 250 (decimal) = Write entry

37 1 GIN LSB = 55 (decimal), GIN MSB = 1; 55 = Desired volatge value 1

7 Data type = 7 = Short real

0 0 ca 42 4 bytes of data

42 16 End message

Figure 6 Example of generic command (write entry with version)

Once it has received a valid command, the voltage regulator returns the command message as positive confirmation. The reason for transmission is set to 40.

If the command cannot be performed, the reason for transmission is 41.

The generic command "Write entry with confirmation" (info number 249) is not implemented.

Page 24: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103
Page 25: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

6 Tap position telegram

© Maschinenfabrik Reinhausen 2010 2398402/00 EN TAPCON® 240 25

6 Tap position telegram

6.1 Structure of telegram

The structure of the individual telegrams is described in the tables below.

Message type 10

Variable structure code 0x81

Reason for transmission 1 or 9

Shared address of ASDU Address set

Function type 254

Information number 244

RII 1

NGD 1

GIN LSB For tap position 54

GIN MSB For tap position message 2

KOD 1

Data type 7 (short real)

Number of data bytes 4

Quantity 1

Data (4 bytes, short real)

Table 12 Structure of type 10 telegram

Page 26: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

6 Tap position telegram

26 TAPCON® 240 2398402/00 EN © Maschinenfabrik Reinhausen 2010

Message type 4

Variable structure code 0x81

Reason for transmission 1 or 9

Shared address of ASDU Address set

Function type 110

Information number For tap position message 118

Data (4 bytes, short real) Tap position

Relative time ms (2 bytes) not used, always 0

Error number (2 bytes) not used, always 0

Time (2 bytes)

Table 13 Structure of type 4 telegram

Message type 204

Variable structure code 0x81

Reason for transmission 1 or 9

Shared address of ASDU Address set

Function type 110

Information number For tap position 54

Data (4 bytes, short real) Tap position Time (4 bytes) SIN (1 byte)

Table 14 Structure of type 204 telegram

Page 27: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

6 Tap position telegram

© Maschinenfabrik Reinhausen 2010 2398402/00 EN TAPCON® 240 27

6.2 Examples of messages for tap position telegrams

The examples were taken from various log files which recorded the telegram traffic between a PC and the voltage regulator. The voltage regulator address was set to 1.

Some of the tap positions in the sample telegrams selected are different in or-der to show examples with different values. The same tap position is normally reported in all three telegrams.

Telegram Comments

68 9 9 68 43 1 7 81 9 1 ff 0 0 d5 16 General query command from PC

68 a a 68 43 1 15 81 1 fe f5 0 0 d7 16 General query command for generic data from PC

68 14 14 68 28 1 4 81 9 1 6e 76 0 0 20 41 0 0 0 0 f3 9b 82 0 d 16

Type 4 telegram, sent during general que-ry

68 14 14 68 28 1 a 81 9 1 fe f4 0 81 36 2 1 7 4 1 0 0 20 41 d7 16

Type 10 telegram, sent during general query Tap position 0 is reported in bytes 0 20 41 10

68 11 11 68 28 1 cc 81 9 1 6e 36 0 0 0 0 c7 65 80 0 0 d0 16

Type 204 telegram, sent during general query Tap position 0 is reported in bytes 0 0 0 0

68 14 14 68 28 1 4 81 1 1 6e 76 0 0 80 3f 0 0 0 0 fd a4 27 8b a6 16

Type 4 telegram, sent due to a change in tap position Tap position 1 is reported in bytes 0 0 80 3f

68 14 14 68 28 1 a 81 1 1 fe f4 0 1 36 2 1 7 4 1 0 0 80 3f ad 16

Type 10 telegram, sent due to a change in tap position Tap position 1 is reported in bytes 0 0 80 3f

68 11 11 68 8 1 cc 81 1 1 6e 36 0 0 0 40 18 d5 27 8b 0 db 16

Type 204 telegram, sent due to a change in tap position Tap position 2 is reported in bytes 0 0 0 40

Table 15 Examples of messages for tap position message telegram

Page 28: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

6 Tap position telegram

28 TAPCON® 240 2398402/00 EN © Maschinenfabrik Reinhausen 2010

6.3 Setting time and date settings

The TAPCON® 240 has a counter module which counts the number of seconds after the supply voltage fails. Its supply is buffered by a large capaci-tor such that it continues to count for at least a few days even if the TAP-CON® 240 is switched off.

The time and date are set using an offset value which is converted into the time and date displayed in the measured value plotter screen along with the current counter reading.

The interface software sends the time and date from the IEC103 time syn-chronization telegram to the actual CPU with the regulator firmware. The regulator firmware uses this information to calculate the new offset value to display for time and date in the measured value plotter screen.

The counter in the TAPCON® 240 counts whole seconds. Because the fig-ures are rounded up or down, the time displayed in the measured value plot-ter screen may deviate from the time in the time synchronization telegram.

The TAPCON® 240's time and date will only be set from the control system's time synchronization telegram if both the interface software and firmware in the regulator support this.

The telegrams' time stamp at the interface is not affected by the setting for the time displayed by the TAPCON® 240. This time stamp is produced locally on the CIC card itself.

Page 29: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103
Page 30: Protocol description for IEC 60870-5-103 - Reinhausen · Voltage regulator TAPCON® 240 Supplement 2398402/00 Protocol description for IEC 60870-5-103

2398402/00 EN 12/10