4
Suburban AP DynaPack-Dynaline PDS 06/2018 New Dynaline 3 Suburban Applied Products developed the first gas- fired Package Terminal Air Conditioner (PTAC), the Dynaline, in 1985. Now in its third generation design, Suburban is a leading supplier to the senior housing industry as well as other small commercial markets. Continuing the Suburban Applied Products tradition of providing year-round comfort in fully self-contained heating and cooling systems, we now offer the DynaPack family. DynaPack provides electric cooling with efficient gas heat. This vertical packaged air conditioner features cooling comfort along with 10 EER efficiency. Cooling efficiencies for all DynaPack models range from 10.0 to 10.7 EER. Classified as a Single Packaged Vertical Unit (SPVU), all DynaPacks are tested and rated to AHRI Standard 390 Gas Heating, Electric Cooling, PTAC Zone Control. Dynaline 3 Vertical Packaged Air Conditioner Featuring Gas Heat/Electric Cooling Dynaline and DynaPack Are Designed And Built To Perform With Efficient Reliability.

Dynaline 3

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Dynaline 3

Suburban AP DynaPack-Dynaline PDS 06/2018 New

Dynaline™ 3

Suburban Applied Products developed the first gas-fired Package Terminal Air Conditioner (PTAC), the Dynaline, in 1985. Now in its third generation design, Suburban is a leading supplier to the senior housing industry as well as other small commercial markets.

Continuing the Suburban Applied Products tradition of providing year-round comfort in fully self-contained heating and cooling systems, we now offer the DynaPack family. DynaPack provides electric cooling with efficient gas heat. This vertical packaged air conditioner features cooling comfort along with 10 EER efficiency.

Cooling efficiencies for all DynaPack models range from 10.0 to 10.7 EER. Classified as a Single Packaged Vertical Unit (SPVU), all DynaPacks are tested and rated to AHRI Standard 390

Gas Heating, Electric Cooling, PTAC Zone Control.

Dynaline™ 3Vertical Packaged Air Conditioner

Featuring Gas Heat/Electric Cooling

Dynaline and DynaPack Are Designed And Built To Perform WithEfficient Reliability.

Page 2: Dynaline 3

Ideal for Multi-Family Applications.

DynaPack SPVUCost Effective Multiple Room Conditioning

Featuring 1 to 3 Tons Cooling and Efficient 36 to 60 MBTU Gas Heat.

DynaPack is a Fully Self-Contained Heating and Cooling System to Provide Designers and Builders with a Cost Effective Way to Condition Multiple Rooms.

• S Series – Standard Efficiency–80% TE• H Series – High Efficiency–90%+ TE• 1 to 3 Tons Cooling• 36 – 60 MBTU Gas Heat

• No Outside Condensing Unit• R-410A Refrigerant• Insulated 16 GA Coated Steel Base Pan• Ideal For Multi-Family Applications

• Easy To Install In Almost Any Application

• Optional Washable Internal Filter Or MERV13 Filter

• Five-Speed ECM Motor for Higher Efficiency and Maintaining Proper Airflow

• One Unit May be Ducted for Multiple Room Conditioning

• Direct Vent System

• Pre-Wired and Pre-Charged at the Factory

• Individually Metered and Controlled

• Insulated 16 GA Coated Galvanized Steel Base Pan Eliminates Need for Field Added Platform

2Suburban AP DynaPack-Dynaline PDS 06/2018 New

Page 3: Dynaline 3

3

Ideal for senior housing, hotels/motels and apartments.

Dynaline™3 PTACA Proven Payback In Utility Savings

Economical Gas Heat Provides Comfort to Those Who Need it the Most.

Elderly senior housing and assisted living facility residents require controlled cool summers and warm winters. Because typical systems don’t readily adapt to extremes in temperature, warmer, dry gas heat is preferred for its therapeutic effect on residents’ respiratory systems. Electric cooling, in turn, is preferred for its rapid response to adjustments. Housing for seniors and the elderly remains expensive because of the necessity for near-hospital-quality security and facility extras not required in normal residential housing. Dynaline 3 adds the option of lowering utility expenses by using economical gas heating with electric cooling units.

Low Heating Amp Draw — The Dynaline 3 consumes about 1 amp during the heating cycle; while all-electric PTACs consume much more. In the event of a power failure, less power is used by the Dynaline 3 so the standby generator can be downsized, thus reducing construction costs. Compressor Lock-Out — The standard design provides means of locking out the A/C compressor when the standby power generator is operating. The electronic control board has 24V input terminals to receive the lock-out signal.Better Comfort for Residents — Faster increase in temperature than an all-electric unit.

High-Efficiency Rotary Compressor: Reliable and quiet-running design. Suburban’s gas heat PTAC design does not use the compressor during heating cycles. Copper & Aluminum Evaporator and Condenser Coils: For longer life and ease of repair. Coils use seamless copper tubing mechanically expanded into aluminum plate fins.Gas Heat Exchanger: Provides economical gas heating backed by a 5-year limited warranty.Digital Display: Room ambient and set point temperatures are easy to read.Condensate Removal: Condenser fan draws condensate from bottom. Warm condenser air, combined with coil temperature, accelerates the evaporation process. Positive drain kits are also available.Weather Seals: Sealing the chassis to the wall case, these prevent the infiltration of air, water and contaminants into the conditioned area.Air Vent: The manually-operated lever allows entry of 70 CFM of outside air into the conditioned area.

Return Air Filter: No tools are needed to install or remove the permanent electrostatic washable filter.Electrical Components: Located on the indoor side of the wall, they’re protected from the weather.Gas Connection (Inside or Outside): Available for Natural or LP gas, thus saving the cost of field conversion. An optional 2-lb. Natural gas regulator is available.Room Air Discharge: An attractive, durable grille constructed of extruded aluminum directs air laterally.Tangential Blower Wheel: Spans the length of the heating chamber and evaporator coil. Air flow is uniform over the system components, enhancing air distribution performance and system efficiency.Unit Controls: Each unit can be controlled by a built-in thermostat or reprogrammed to operate from an optional wall thermostat.Ignition: The standard in gas heating, an electronically controlled, ceramic hot surface ignites the burner without standing pilot lights. Gas is conserved and safety is ensured.

3 Standard Color OptionsWhite, Beige and Gray are the standard colors. Stainless Steel and custom powder coating are also available.

Suburban AP DynaPack-Dynaline PDS 06/2018 New

Page 4: Dynaline 3

H SERIESMODEL

HEATING COOLINGInputBtuh

OutputBtuh TE1 Btuh EER2 Refrigerant

DYPA12AC1A039H 39,000 36,000 92% 12,000 10.0 R-410ADYPA18AC1A039H 39,000 36,000 92%

17,500 10.0 R-410ADYPA18AC1A052H 52,000 47,300 91%DYPA24AC1A039H 39,000 36,000 92%

25,200 10.6 R-410ADYPA24AC1A052H 52,000 47,300 91%DYPA30AC1A039H 39,000 36,000 92%

30,200 10.6 R-410ADYPA30AC1A052H 52,000 47,300 91%DYPA36AC1A039H 39,000 36,000 92%

34,800 10.0 R-410ADYPA36AC1A039H 52,000 47,300 91%1Thermal Efficiency2Unit Tested to ANSI/AHRI Standard 390.

S SERIESMODEL

HEATING COOLINGInputBtuh

OutputBtuh TE1 Btuh EER2 Refrigerant

DYPA12AC1A036 35,500 28,40080% 12,000 10.0 R-410A

DYPA12AC1A048 47,500 38,000DYPA18AC1A036 35,500 28,400

80% 17,500 10.0 R-410ADYPA18AC1A048 47,500 38,000DYPA18AC1A060 59,000 47,200DYPA24AC1A036 35,500 28,400

80% 25,200 10.6 R-410ADYPA24AC1A048 47,500 38,000DYPA24AC1A060 59,000 47,200

DYPA30AC1A036 35,500 28,40080% 30,200 10.6 R-410ADYPA30AC1A048 47,500 38,000

DYPA30AC1A060 59,000 47,200DYPA36AC1A036 35,500 28,400

80% 34,800 10.0 R-410ADYPA36AC1A048 47,500 38,000DYPA36AC1A060 59,000 47,200

Suburban Applied Products DynaPack Specifications

Suburban Applied Products Dynaline™3 Specifications

Specifications Below Are the Same for S and H SeriesElectrical Data

Model DYPA12 DYPA18 DYPA24 DYPA30 DYPA36

Volts/Phase/Cycle 208/230-1-60

Minimum Circuit Ampacity 13.3 14.9 17.8 21.6 25.2

Maximum Fuse/HACR Breaker Size 15 20 25 30 40

Gas Controls and Additional DataModel DYPA12 DYPA18 DYPA24 DYPA30 DYPA36

Gas (specify) Natural

Ignition system: solid state Direct Spark

Gas connection size 1/2 inch NPT

Condensate connection size 3/4 inch NPT

Compressor DataModel DYPA12 DYPA18 DYPA24 DYPA30 DYPA36

Type Rotary Reciprocating

Refrigerant Type (HCFC) R410A

Unit Refrigerant Charge 35oz. 43oz. 85oz. 96oz. 96oz.

Rated Load Amps 5.2 8.3 10.9 13.1 16.0

Locked Rotor Amps 25 43 54 74 88

Motor DataModel DYPA12 DYPA18 DYPA24 DYPA30 DYPA36

Indoor motor (ECM) FLA/HP/RPM 4.0/.50/1050

Condenser motor FLA/HP/RPM 0.9/0.125/1075 1.3/0.25/1075

Combustion motor FLA 0.9

Dynaline™ 3

General DataModel DL3-1622 DL3-1220 DL3-0912 DL3-0712Rated Heating Input (BTU/h) 20,000 18,000 12,000 12,000Rated Heating Output (BTU/h) 16,000 14,580 9,840 9,840Thermal Efficiency (TE) 82% 82% 82% 82%Rated Cooling Capacity (BTU/h) 15,000 11,500 9,500 7,600Sensible/Latent Cooling 65/35 65/35 69/31 65/35EER 9.5 10.40 11.2 11.60

Minimum Installation ClearancesModel DL3-1622 DL3-1220 DL3-0912 DL3-0712Outside:Rear to nearest obstruction 3 feet 3 feet 3 feet 3 feetTop, sides to nearest obstruction 0 0 0 0Centerline vent to window 9” 9” 9” 9”Inside:Cabinet front to nearest obstruction 12”* 12”* 12”* 12”*Cabinet sides to nearest obstruction 1” 1” 1” 1”Cabinet bottom to floor (for return air) 0 0 0 0Cabinet top to ceiling 12” 12” 12” 12”*Obstruction must be removed for service of unit.

Electrical DataModel DL3-1622 DL3-1220 DL3-0912 DL3-0712Volts/Phase/Cycle 208/230-1-60Total Amps Cooling/Heating 7.5/1.2 5.1/1.0 3.8/1.0 3.3/1.0Total Watts Cooling/Heating 1550/260 1125/150 855/150 675/150

Compressor DataModel DL3-1622 DL3-1220 DL3-0912 DL3-0712Type Hermetic RotaryRefrigerant Type (HCFC) R410A R410A R410A R410ARated Load Amps 6.6 4.9 3.9 2.9Locked Rotor Amps 32 25 22 15Compressor Lock-Out Relay (Normally Closed 24V) 5VA Enrush - 4V Constant

Gas Controls and Additional DataModel DL3-1622 DL3-1220 DL3-0912 DL3-0712Gas (specify) Natural or LPIgnition System: Solid-State Hot SurfaceGas Connection Size 3/8”IPS 3/8”IPS 3/8”IPS 3/8”IPSGas Connection (LH) Front or Rear

Blower/EvaporatorModel DL3-1622 DL3-1220 DL3-0912 DL3-0712Air Vent-Manual 70 CFM 70 CFM 70 CFM 70 CFMFilter Type Electrostatic/Washable Media

Specifications subject to change without notice. Installation must be in accordance with local codes and regulations.

Please consult the Suburban Applied Products website at www.SuburbanHVACProducts.com for the latest product literature. Detailed dimensional data is available upon request. A complete warranty statement can be found in each product’s Installation/Operation Manual, on our website. As part of the Suburban AP continuous improvement program, specifications are subject to change without notice.

✆(229) 273-3636 www.SuburbanHVACProducts.com [email protected] by: 156 Seedling Drive Cordele, GA 31015