Duct Sizing-static Balance

Embed Size (px)

Citation preview

  • 7/28/2019 Duct Sizing-static Balance

    1/24

    STATIC BALANCE DUCT SIZING

    METHOD

    Author:

    Engr. K.H., Kong is Mechanical Engineer

    (IEM member, No: M21065)

    Bachelors Degree with Honors with Distinction in Mechanical Engineering

  • 7/28/2019 Duct Sizing-static Balance

    2/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 2 of 24

    STATIC BALANCE DUCT DESIGN METHOD

    ABSTRACT

    Generally, the duct design methods for low velocity supply air system that are

    currently used include

    1. Velocity reduction2. Equal Friction, and3. Static Regain

    In this write up, a novel duct design method, known as the static balance duct

    design method, is introduced. In this method, the duct looping or network principle is

    applied to achieve static balance. The Static balance method is an intelligent self-

    balance method to achieve minimum static losses across the ducting network. In turn,

    energy consumption is reduced.

    Static balance method is also well applicable to the variable air volume (VAV)

    system. It reduces the system response time, the operating static losses within the duct

    network system, and enhances the energy saving.

    1.0 INTRODUCTION

    In this write up, the description for the conventional and static balance duct

    design method is presented in chapter 2. The Equal friction and static balance

    methods are compared and discussed in detail. Chapter 3 discusses about the equal

    friction method. A few equations involved in the development of the equal friction

    method are presented. In chapter 4, the development and the principal of static

    balance method are discussed in relation to the equal friction method. Comparisons of

    the equal friction and static balance are discussed in chapter 5. Chapter 6 brings up the

    advantages of the static balance method for VAV system and followed by a final

    conclusion.

  • 7/28/2019 Duct Sizing-static Balance

    3/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 3 of 24

    2.0 DUCT DESIGN METHOD

    The conventional duct design method includes:

    1. the velocity reduction method2. the equal friction method, and3. the static regain method.

    The novel duct design method is static balance method.

    In the velocity reduction duct design method, the controlling factor is the air

    velocity in the duct. This is mainly to prevent noise due to high air velocity. Basically,

    the duct velocity is determined before the duct size is selected. With the air velocity,

    the duct diameter size is computed. Then, the actual round or rectangular duct size is

    selected and the relevant static loss is calculated accordingly.

    The Equal friction method is widely used due to its simplicity and flexibility.

    This method is based on the assumption that the friction loss per unit of length is

    consistent for the entire system. Usually, the initial friction loss per unit of length is

    determined. Then the duct size throughout the entire ducting system is selected

    according to the air flow rate relative to the determined friction loss. The total friction

    loss in the duct system is calculated based on the duct run with the highest resistance,

    including the friction loss through all elbows and fittings in the section. For any site

    coordination or adjustment, the duct size is changed based on the same static loss

    coefficient. However, the drawback of the equal friction method is that the system is

    difficult to balance if the design has a mixture of short and long runs. Where the

    pressure difference between short and long runs is large, and requires considerable

    dampering on system.

    In the static regain method, the duct is designed in such a way that at each

    branch, the available static pressure is used to offset the friction loss on the

    subsequent section of duct. The static pressure remains constant before each terminal

    and at each branch. This method requires more complicated and time consuming

    design procedures and methods. It also uses more duct materials as compared to the

    equal friction method.

  • 7/28/2019 Duct Sizing-static Balance

    4/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 4 of 24

    The Static balance duct design method presented here comprises a duct

    looping network, which consists of ducts of various sizes, geometric orientations, and

    fittings. It is designed based on the principle of equal friction method which offers

    lower friction losses but more duct work. Similarly to all networks system, this

    method implements the continuity and the work-energy principles throughout the

    network. The solution of the static balance method is obtained through a trial-and-

    correction or iteration process.

    3.0 EQUAL FRICTION DUCT DESIGN METHOD

    The Equal friction method uses the same friction loss per unit of length for the

    entire system. In any duct section in which the air is flowing through, there is a static

    loss. This loss is named as the friction loss which is related to the followings:

    1) Duct size,2) Interior surface roughness,3) Air flow rate, and4) Duct length

    The relationship of these factors is represented by the following equation:

    82.122.1

    1000

    118.67

    =

    V

    df

    L

    P

    e

    eq. 3.1

    or

    =

    86.4

    82.17

    103ed

    Qfx

    L

    P eq. 3.2

    where P = friction loss (Pa)

    f= interior surface roughness

    L = duct length (m)

    de = duct diameter or equivalent diameter for rectangular duct (mm)

    V= air velocity (m/s)

    Q = air flow rate (l/s)

    The equivalent diameter for a rectangular duct can be further related as follows:

  • 7/28/2019 Duct Sizing-static Balance

    5/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 5 of 24

    ( )

    ( ) 25.0

    625.0

    3.1ba

    abd

    e+

    =

    eq. 3.3

    where de = duct diameter or equivalent diameter for a rectangular duct (mm)

    a and b = duct size (mm)

    Another useful parameter derived from the velocity pressure is the velocity head,

    26137.0 Vhv = eq. 3.4

    or

    4

    26

    101e

    vd

    Qxh = eq. 3.5

    where hv = velocity head (Pa),

    V= air velocity (m/s)

    Q = air flow rate (l/s)

    de = duct diameter or equivalent diameter for rectangular duct (mm)

    The friction loss of fittings can be related to the velocity pressure by adding a

    multiplier or coefficient. The coefficient for various fittings is tabulated below:

    Fittings Coefficient, C

    Transition 0.25Elbow 0.27

    Wye 0.30

    Tee 0.37

    The static loss through fittings is represented by the following equation:

    vfChP = eq. 3.6

    where Pf= static loss through fittings, (Pa)

    hv = velocity head (Pa),

    C= fitting coefficient

    In any duct system for the equal friction method, the duct is sized based on a

    desired friction loss per unit length of duct. The equations shown above are used to

    calculate the static loss. The static loss of each section of the duct runs is

    accumulated. Only the duct runs with highest resistance is calculated, where this is the

  • 7/28/2019 Duct Sizing-static Balance

    6/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 6 of 24

    static required for the fan to overcome it. The highest static loss may not be the

    longest duct run, rather it can be a shorter duct with more bends and fittings.

    3.1 Example for Equal Friction Duct Design Method

    Figure 3.1 shows a simple duct system for hospital ward rooms. In this

    simulation, the ward rooms are located at perimeter whereas offices, the procedure

    room and the nurse station are located at center of the zone.

    Referring to figure 3.1, the fan discharge air flow rate is 4800 l/s and there are

    16 branches or air terminals with 300 l/s each. The friction loss is limited to 1 Pa/m.

    Duct is made of galvanized sheet with the interior surface roughness of 0.9.

    The duct runs with the highest static loss is from point O to P. The static loss

    calculation is tabulated in table 3.1 and the duct design is shown in figure 3.2. Here,

    the friction loss per unit length is selected to be 1 Pa/m. In actual situation, due to the

    limitation of discrete duct sizes, the friction loss is re-calculated according to the duct

    size selected.

    From calculation, the accumulated static loss is 64 Pa from point O to P.

  • 7/28/2019 Duct Sizing-static Balance

    7/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Item Point DescriptionAir

    Flow

    (L/S)

    Design

    Static

    Loss

    (Pa/m)

    Duct Size (mm)

    W x H

    AirVelocity

    (m/s)

    Calc.

    Static

    Loss / L

    (Pa/m)

    Straight

    Duct

    Length

    (m)

    StaticLoss

    (Pa)

    Chv

    (Pa)

    1 OA Straight duct Q0 4800 1.0 1,300 x 450 9.35 0.751 5.0 3.757 0.00 42.41

    2 Tee 0.37 42.41

    3 AF Straight duct Q5 2100 1.0 700 x 450 7.19 0.874 5.0 4.372 0.00 31.72

    4 FJ Straight duct Q8 1500 1.0 600 x 400 6.73 0.913 5.0 4.567 0.00 27.78

    5 Tee 0.37 27.78

    6 JK Straight duct Q11 1200 1.0 500 x 400 6.41 0.932 5.0 4.658 0.00 25.24

    7 KL Straight duct Q12 900 1.0 450 x 350 5.94 0.988 5.0 4.941 0.00 22.93

    8 LM Straight duct Q13 600 1.0 400 x 300 5.35 0.918 5.0 4.588 0.00 17.60

    9 MN Straight duct Q14 300 1.0 250 x 300 4.27 0.808 5.0 4.041 0.00 11.19

    10 Elbow 0.27 11.19

    11 NP Straight duct Q15 300 1.0 250 x 300 4.27 0.808 5.0 4.041 0.00 11.19

    Table 3.1 Static loss calculated result using equal friction duct design method.

  • 7/28/2019 Duct Sizing-static Balance

    8/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 8 of 24

    4.0 STATIC BALANCE DUCT DESIGN METHOD

    The Static balance duct design method uses the duct network principle. For all

    network problems, it satisfies the continuity and the work-energy principles

    throughout the network. The continuity principle states that the vector summation of

    air flow rate into any junction must be equal to zero. The continuity principle is

    represented by the following equation:

    = 0Q eq. 4.1

    The network-energy principle states that the vector summation of static loss

    around any single loop of the network must be equal to zero. The vector summation of

    static loss applies to any section of the duct within the loop. The static loss is additive

    if air flow direction is parallel with the loop direction, but deductive if air flow

    direction is opposite the loop direction. The network-energy is represented by the

    following equation:

    = 0P eq. 4.2

    Equation 4.2 can be further divided to two portions. The static loss through

    straight duct and fittings is shown as follows:

    ( ) ( ) =+ 0fittingsPductstraightPf eq. 4.3

    From equation 3.2, it is known that the static loss is related to 4 factors, which

    are the duct length, the friction factor, the duct size and the air flow rate. Thus, P is a

    function of (L, f, de and Q).

    Using the equal friction principle, the friction loss per unit of length is

    constant. The friction factor, f, is a constant depending on the duct material. Giving

    that the air flow rate, Q, the duct equivalent diameter, de can be calculated. Therefore,

    it can be summarized that the friction loss, P, is determined by the air flow rate, Q.

    As for all network problems, the solution of the static balance method is

    obtained through a trial-and-correction or iteration process. There are several ways to

  • 7/28/2019 Duct Sizing-static Balance

    9/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 9 of 24

    solve these flow rates, the simplest and easiest to understand being the Hardy Cross

    method.

    The essence of the method is to start with an estimated set of initial values, Q0,

    that fulfills the continuity at each junction. The difference between the estimated and

    the updated value is represented by a correction factor, L. The updated value is the

    summation of estimated value and the correction factor as shown below.

    LiQQ = 0 eq. 4.4

    where the sign () depends on the directions assumed for Q0.

    In cases where one duct is depending on two loops, the new air flow rate

    should include the summation of both correction factors from two loops.

    Then, the next iteration is carried out with a new successive set of values.

    Iterations are repeated until the iteration results are converged and satisfied.

    From equation 4.3, the static loss equation is,

    ( ) ( ) =+ 0fittingsPductstraightP f

    where the sign () depends on the directions assumed for Q0.

    The static loss through a straight duct is represented by equation (3.2), and the

    static loss through fittings is represented by equation (3.5) and (3.6). In general, a

    common equation as follows is obtained,

    == 0nKQP eq. 4.5

    where K is the coefficient of static loss, which depends on the duct length, the duct

    equivalent diameter and the friction factor.

    Introducing eq. 4.4 into eq. 4.5, and obtain

    ( ) == 00 nLQKP

  • 7/28/2019 Duct Sizing-static Balance

    10/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 10 of 24

    Expanding this equation by the binomial theorem and neglecting all terms

    containing L raised to a higher power, because L is presumed to be small. For the

    first iteration,

    ) =+= 0100 negligiblenQQKP Lnn

    Solving for L, the first correction factor becomes

    =

    1

    0

    0

    n

    n

    L

    nKQ

    KQ eq. 4.6

    The absolute value must be used in the denominator to ensure that the proper

    sign for L. This equation is used to compute the flow rate correction factor, L, for

    each loop in the network. From equation 4.6, it can be further simplified as follows to

    the satisfaction of usage,

    =

    0QPn

    PL

    eq. 4.7

    For iterative processes, the value of (1/n) is categorized as an over-relaxation

    factor, which can be varied within certain limit to enhance the iteration process. In

    this case, referring to eq. 3.2 and 3.5, due to the different value of n for straight duct

    and fittings, the value of 2 for n is selected to proceed with the iterative process.

    Hence, eq. 4.7 becomes

    =

    02 QP

    PL eq. 4.8

    In every iterative process, the air flow rate must be updated with a successive

    set of values computed until the values of Q converge with suitable accuracy to final

    values.

    Due to the limitation of discrete duct sizes, there will be residual where the

    value of Q may not converge to zero, but alter within a small value for the same duct

    sizes. In this case, the iteration is considered converged. The converged set value of Q

    will be used to determine the static loss across the ducting system.

  • 7/28/2019 Duct Sizing-static Balance

    11/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 11 of 24

    4.1 Example for Static Balance Duct Design Method

    Figure 4.1 shows a duct system which uses the static balance duct design

    method. Figure 4.1 has the same layout as described in figure 3.1, with a duct looping

    network. The friction loss is limited to 1 Pa/m. A set of initial air flow rate across

    each duct section is estimated and tabulated in table 4.1 below. The air flow rate must

    satisfy the continuity principle.

    Item Point Designation Air flow rate (l/s)

    1 OA Q0 4800

    2 AB Q1 2700

    3 BC Q2 2400

    4 CD Q3 1350

    5 DE Q4 10506 AF Q5 1800

    7 CG Q6 750

    8 EH Q7 750

    9 FJ Q8 1200

    10 GL Q9 150

    11 HN Q10 150

    12 JK Q11 900

    13 KL Q12 600

    14 LM Q13 450

    15 MN Q14 150

    Table 4.1 Initial estimated air flow rate across each section of duct.

    The first iteration is carried out and the static loss calculation is tabulated. The

    iteration for loop (I) is tabulated in table 4.2 and the iteration for loop (II) is shown in

    table 4.3.

    From eq. 4.8, the correction factor for loop I is,

    ( )

    =

    02 QP

    PIL

    ( )

    ++++++

    ++++++

    +++++=

    01085.000765.000523.000778.000388.000262.0

    00414.001556.002049.000548.000574.000204.000165.02

    5.66.47.43.97.47.49.193.21.31.48.139.44.4

  • 7/28/2019 Duct Sizing-static Balance

    12/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 12 of 24

    ( )

    ( )09311.02

    8.21=

    sl/117=

    Similarly, the correction factor for loop II is,

    ( )

    =

    02 QP

    PIIL

    ( )

    ++++++

    ++++++

    +++++=

    01556.002049.000828.001556.002049.000548.0

    00574.001556.002049.000548.000718.000479.000342.02

    3.21.37.33.21.31.48.133.21.31.45.70.56.4

    ( )( )14852.02

    8.5=

    sl/19=

  • 7/28/2019 Duct Sizing-static Balance

    13/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Item Point Description

    Air

    Flow(L/S)

    Design

    Static

    Loss(Pa/m)

    Duct Size (mm)

    W x H

    Air

    Velocity(m/s)

    Calc.

    Static

    Loss / L(Pa/m)

    Straight.

    Duct

    Length(m)

    Static

    Loss(Pa) C

    h

    (P

    First Iteration Loop I

    1 AB Straight duct Q1 2700 1.0 850 x 450 7.71 0.889 5.0 4.445 0.00 36

    2 BC Straight duct Q2 2400 1.0 850 x 400 7.79 0.978 5.0 4.891 0.00 37

    3 C Tee 2400 0.37 37

    4 CG Straight duct Q6 750 1.0 500 x 300 5.41 0.822 5.0 4.112 0.00 17

    5 GL Straight duct Q9 150 1.0 250 x 200 3.21 0.615 5.0 3.073 0.00 6

    6 L Tee 150 0.37 6

    7 A Tee 4800 0.37 53

    8 AF Straight duct Q5 1800 1.0 600 x 450 7.14 0.944 5.0 4.722 0.00 31

    9 FJ Straight duct Q8 1200 1.0 500 x 400 6.41 0.932 5.0 4.658 0.00 25

    10 J Tee 1200 0.37 2511 JK Straight duct Q11 900 1.0 400 x 400 5.99 0.942 5.0 4.710 0.00 22

    12 KL Straight duct Q12 600 1.0 400 x 300 5.35 0.918 5.0 4.588 0.00 17

    13 L Tee 600 0.37 17

    Table 4.2 First iteration for loop I.

  • 7/28/2019 Duct Sizing-static Balance

    14/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Item Point Description

    Air

    Flow(L/S)

    Design

    Static

    Loss(Pa/m)

    Duct Size

    (mm)W x H

    Air

    Velocity(m/s)

    Calc.

    Static

    Loss / L(Pa/m)

    Straight.

    Duct

    Length(m)

    Static

    Loss(Pa) C

    First Iteration Loop II

    14 CD Straight duct Q3 1350 1.0 550 x 400 6.58 0.923 5.0 4.614 0.00 2

    15 DE Straight duct Q4 1050 1.0 600 x 300 6.40 1.006 5.0 5.031 0.00 2

    16 E Wye 1050 0.30 2

    17 EH Straight duct Q7 750 1.0 500 x 300 5.41 0.822 5.0 4.112 0.00 17

    18 HN Straight duct Q10 150 1.0 250 x 200 3.21 0.615 5.0 3.073 0.00 6

    19 N Tee 150 0.37 6

    20 C Tee 2400 0.37 37

    21 CG Straight duct Q6 750 1.0 500 x 300 5.41 0.822 5.0 4.112 0.00 17

    22 GL Straight duct Q9 150 1.0 250 x 200 3.21 0.615 5.0 3.073 0.00 6

    23 L Tee 150 0.37 624 LM Straight duct Q13 450 1.0 350 x 300 4.57 0.745 5.0 3.726 0.00 1

    25 MN Straight duct Q14 150 1.0 250 x 200 3.21 0.615 5.0 3.073 0.00 6

    26 N Tee 150 0.37 6

    Table 4.3 First iteration for loop II.

  • 7/28/2019 Duct Sizing-static Balance

    15/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 15 of 24

    From the two correction factors obtained above, the estimated flow rate is

    updated and tabulated in table 4.4.

    Item Point DesignationInitial Air

    flow rate (l/s)Correction Updated Air

    flow rate (l/s)

    1 OA Q0 4800 Q0 4800

    2 AB Q1 2700 Q1 = Q1 +L(I) 2817

    3 BC Q2 2400 Q2 = Q2 +L(I) 2517

    4 CD Q3 1350 Q3 = Q3 +L(II) 1369

    5 DE Q4 1050 Q4 = Q4 +L(II) 1069

    6 AF Q5 1800 Q5 = Q5 - L(I) 1683

    7 CG Q6 750 Q6 = Q6 +L(I) - L(II) 848

    8 EH Q7 750 Q7 = Q7 +L(II) 769

    9 FJ Q8 1200 Q8 = Q8 - L(I) 1083

    10 GL Q9 150 Q9 = Q9 +L(I) - L(II) 248

    11 HN Q10 150 Q10 = Q10 +L(II) 169

    12 JK Q11 900 Q11 = Q11 - L(I) 783

    13 KL Q12 600 Q12 = Q12 - L(I) 483

    14 LM Q13 450 Q13 = Q13 - L(II) 431

    15 MN Q14 150 Q14 = Q14 - L(II) 131

    Table 4.4 Updated estimated air flow rate after first iteration.

    The iteration is continued and the correction factor is tabulated in table 4.5.

    The iteration is converged and the duct sizes are maintained from iteration of Ninth

    onwards. The converged value of Q is tabulated in table 4.6. The duct design is shown

    in figure 4.2.

    Item Iteration

    Number

    Correction factor Loop I,

    L(I) (l/s)

    Correction factor Loop II,

    L(II) (l/s)

    1 First 117 19

    2 Second 90 15

    3 Third 63 334 Forth 77 26

    5 Fifth 42 23

    6 Sixth 42 21

    7 Seventh 50 13

    8 Eighth 29 5

    9 Ninth 23 1

    Table 4.5 Correction factors obtained from iterations.

  • 7/28/2019 Duct Sizing-static Balance

    16/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 16 of 24

    At the eighth iteration, it is found that the air flow rate direction for duct

    section MN, Q14, is changed, from M->N to N->M. This is due to the accumulated

    static loss from O to N is lower than from O to M. The air flow rate across the duct

    section MN is very low, showing that the pressure at point M and N is almost balance

    or the air flow is almost stagnant.

    From the static balance duct design method, it is discovered that the highest

    static loss is from O to Q. This static loss shall be overcome by the supply fan. An

    interesting phenomenon is found that the static loss from O to Q is almost the same

    regardless of the paths of air flow, either through A-J, C-L or E-N. This complies with

    the work-energy principle. The static loss calculation is tabulated in table 4.7. The

    minor variation of static loss is due to the residual air in discrete duct sizes. The

    variation can be reduced with more iterations. The average accumulated static loss

    from O to Q is 56 Pa.

    Item Point Designation Air flow rate (l/s) Duct Size, W x H (mm)

    1 OA Q0 4800

    2 AB Q1 3234 950 x 450

    3 BC Q2 2934 900 x 450

    4 CD Q3 1507 600 x 400

    5 DE Q4 1207 600 x 350

    6 AF Q5 1266 450 x 4507 CG Q6 1127 650 x 300

    8 EH Q7 907 550 x 300

    9 FJ Q8 666 400 x 350

    10 GL Q9 527 350 x 300

    11 HN Q10 307 250 x 300

    12 JK Q11 366 300 x 300

    13 KL Q12 66 150 x 150

    14 LM Q13 293 250 x 300

    15 MN Q14 7 100 x 50

    Table 4.6 Converged air flow rate across each section of duct.

    The air flow rate through duct section KL and MN is small. For equal friction

    method, these sections can be neglected and omitted. However, they have advantages

    for the static balance duct design method. This will be discussed more in chapter 6.

  • 7/28/2019 Duct Sizing-static Balance

    17/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Item Point Description

    Air

    Flow(L/S)

    Design

    Static

    Loss(Pa/m)

    Duct Size (mm)

    W x H

    Air

    Velocity(m/s)

    Straight

    Duct

    Length(m)

    Static

    Loss(Pa)

    Chv

    (Pa)

    Fit

    St

    L(P

    Static Loss through path E-N

    1 OA Straight duct Q0 4800 1.0 1,300 x 450 9.35 5.0 5.000 0.00 53.66 0

    2 AB Straight duct Q1 3234 1.0 950 x 450 8.34 5.0 4.818 0.00 42.68 0

    3 BC Straight duct Q2 2934 1.0 900 x 450 7.95 5.0 4.550 0.00 38.78 0

    4 CD Straight duct Q3 1507 1.0 600 x 400 6.76 5.0 4.606 0.00 28.04 0

    5 DE Straight duct Q4 1207 1.0 600 x 350 6.23 5.0 4.335 0.00 23.86 0

    6 Wye 0.30 23.86 7

    7 EH Straight duct Q7 907 1.0 550 x 300 5.99 5.0 4.683 0.00 22.03 0

    8 HN Straight duct Q9 307 1.0 250 x 300 4.37 5.0 4.214 0.00 11.72 0

    9 Tee 0.37 11.72 410 NM Straight duct Q14 7 1.0 100 x 50 1.54 5.0 3.334 0.00 1.45 0

    11 Tee 0.37 1.45 0

    12 MQ Straight duct Q16 300 1.0 250 x 300 4.27 5.0 4.041 0.00 11.19 0

    Static Loss through path A-J

    1 OA Straight duct Q0 4800 1.0 1,300 x 450 9.35 5.0 5.000 0.00 53.66 0

    2 Tee 0.37 53.66 1

    3 AF Straight duct Q5 1266 1.0 450 x 450 6.66 5.0 4.945 0.00 27.23 0

    4 FJ Straight duct Q8 666 1.0 400 x 350 5.07 5.0 3.777 0.00 15.80 0

    5 Tee 0.37 15.80 5

    6 JK Straight duct Q11 366 1.0 300 x 300 4.33 5.0 3.707 0.00 11.52 0

    7 KL Straight duct Q12 66 1.0 150 x 150 3.13 5.0 4.765 0.00 5.99 08 LM Straight duct Q13 293 1.0 250 x 300 4.17 5.0 3.871 0.00 10.68 0

    9 Tee 0.37 10.68 4

    10 MQ Straight duct Q16 300 1.0 250 x 300 4.27 5.0 4.041 0.00 11.19 0

  • 7/28/2019 Duct Sizing-static Balance

    18/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Item Point Description

    Air

    Flow

    (L/S)

    Design

    Static

    Loss

    (Pa/m)

    Duct Size (mm)

    W x H

    Air

    Velocity

    (m/s)

    Straight

    Duct

    Length

    (m)

    Static

    Loss

    (Pa)

    Chv

    (Pa)

    Fit

    St

    L

    (P

    Static Loss through path C-L

    1 OA Straight duct Q0 4800 1.0 450 x 1,300 9.35 5.0 5.000 0.00 53.66 0

    2 AB Straight duct Q1 3234 1.0 450 x 950 8.34 5.0 4.818 0.00 42.68 0

    3 BC Straight duct Q2 2934 1.0 450 x 900 7.95 5.0 4.550 0.00 38.78 0

    4 Tee 0.37 38.78 1

    5 CG Straight duct Q6 1127 1.0 450 x 450 5.93 5.0 4.001 0.00 21.58 0

    6 GL Straight duct Q9 527 1.0 300 x 350 5.36 5.0 4.967 0.00 17.60 0

    7 Tee 0.370 17.60 6

    8 LM Straight duct Q13 293 1.0 300 x 250 4.17 5.0 3.871 0.00 10.68 0

    9 Tee 0.37 10.68 4

    10 MQ Straight duct Q16 300 1.0 300 x 250 4.27 5.0 4.041 0.00 11.19 0

    Table 4.7 Static loss calculated result using static balance duct design method from point O to Q.

  • 7/28/2019 Duct Sizing-static Balance

    19/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 19 of 24

    5.0 COMPARISON BETWEEN THE STATIC BALANCE AND THE EQUAL

    FRICTION DUCT DESIGN METHOD

    Chapter 3.1 and 4.1 show two examples of the duct design method for the same

    layout. The static balance duct design method uses the equal friction principle to develop

    the duct network.

    Table 5.1 shows a comparison of the total static loss for the two methods. The

    static loss across duct work for the equal friction method is 64 Pa. This represents the

    external static pressure that a supply fan needs to overcome. However, the static balance

    method is 56 Pa, indicating that the friction loss in the equal friction duct method is 12.5%

    higher than the static balance method. The total static loss inclusive of equipment and

    terminal pressure for the equal friction method is approximately 1.7% higher than the

    static balance method. The reduction of static loss for static balance method may be

    significant for a large duct network system.

    Item DescriptionEqual Friction

    method, (Pa)

    Static balance

    method, (Pa)

    1 Air Handling Unit 380 380

    2 Duct friction 64 55

    3 Terminal pressure 35 35Total 479 470

    Difference on friction across duct. (%) 12.5

    Difference on total static loss. (%) 1.7

    Table 5.1 comparison on the total static loss for two duct design method.

  • 7/28/2019 Duct Sizing-static Balance

    20/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 20 of 24

    Item Section Q

    Flow

    rate

    Duct size

    (mm) Length Qty

    Surface

    area Gauge Weight

    (l/s) W x H (m) (m2) (U.S.) (kg)

    1 OA Q0 4800 1300 x 450 5 1 17.5 22 120.40

    2 AB Q1 2400 750 x 450 5 1 12.0 22 82.56

    3 BC Q2 2100 750 x 400 5 1 11.5 24 65.05

    4 CD Q3 1200 500 x 400 5 1 9.0 26 39.90

    5 DE Q4 900 450 x 350 5 1 8.0 26 35.47

    6 AF Q5 2100 700 x 450 5 1 11.5 24 65.05

    7 CG Q6 600 400 x 300 5 1 7.0 26 31.03

    8 EH Q7 600 400 x 300 5 1 7.0 26 31.03

    9 FJ Q8 1500 600 x 400 5 1 10.0 26 44.33

    10 JK Q11 1200 500 x 400 5 1 9.0 26 39.90

    11 KL Q12 900 450 x 350 5 1 8.0 26 35.47

    12 LM Q13 600 400 x 300 5 1 7.0 26 31.03

    13 MN Q14 300 250 x 300 5 1 5.5 28 21.02

    14 NP Q15 300 250 x 300 5 16 88.0 28 336.30

    Total = 978.53

    15% scrap = 146.78

    Total weight = 1125.31

    Table 5.2 Duct size and weight for equal friction duct design method.

    Item Section Q

    Flow

    rate

    Duct size

    (mm) Length Qty

    Surface

    area Gauge Weight

    (l/s) W x H m m2 (U.S.) (kg)

    1 OA Q0 4800 1300 x 450 5 1 17.5 22 120.40

    2 AB Q1 3234 950 x 450 5 1 14.0 22 96.32

    3 BC Q2 2934 900 x 450 5 1 13.5 22 92.88

    4 CD Q3 1507 600 x 400 5 1 10.0 26 44.33

    5 DE Q4 1207 600 x 350 5 1 9.5 26 42.12

    6 AF Q5 1266 450 x 450 5 1 9.0 26 39.90

    7 CG Q6 1127 650 x 300 5 1 9.5 24 53.74

    8 EH Q7 907 550 x 300 5 1 8.5 26 37.68

    9 FJ Q8 666 400 x 350 5 1 7.5 26 33.25

    10 GL Q9 527 350 x 300 5 1 6.5 26 28.82

    11 HN Q10 307 250 x 300 5 1 5.5 28 21.02

    12 JK Q11 366 300 x 300 5 1 6.0 26 26.60

    13 KL Q12 66 150 x 150 5 1 3.0 28 11.46

    14 LM Q13 293 250 x 300 5 1 5.5 28 21.02

    15 MN Q14 7 100 x 50 5 1 1.5 28 5.73

    16 NP Q15 300 250 x 300 5 16 88.0 28 336.30

    Total = 1011.56

    15% scrap = 151.73

    Total weight = 1163.29

    Table 5.3 Duct sizes and weight for static balance duct design method.

  • 7/28/2019 Duct Sizing-static Balance

    21/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 21 of 24

    Table 5.2 and 5.3 show the duct sizes and weights established by the two methods

    respectively. The weight of sheet metal required for the system design by the static

    balance method is approximately 3.4% higher than the equal friction method. However,

    the minimal increase of cost is offset by the long-term operating cost.

    5.1 Alternative Equal Friction Duct Design Method

    From the static balance method, it is found that the duct orientation for equal

    friction can be changed to achieve lower static loss. The alternative duct design is shown

    in figure 5.1. The highest static loss is from point O to Q, which is 56 Pa. It has the same

    static loss obtained for the static balance method.

    This result is acceptable because the static balance method is developed based on

    the equal friction principle. Furthermore, this system is almost symmetrical, and therefore,

    the static variation is not significant. For a more complex system, the static balance

    method always has the lowest static loss.

    5.2 Site Coordination

    In general, the equal friction method is always the most popular among the 3

    conventional duct design methods. This is because the equal friction method is the

    simplest and fastest way to design, easy to change or modify to suit any site modification.

    The static balance method also uses equal friction principle in developing the duct network.

    Therefore, it possesses the same advantageous characteristics of the equal friction method

    for site modifications.

    In addition, the static balance method offers more advantages. Referring to figures

    3.2, for example, if the duct size at section F-J is modified to avoid obstruction, any

    changes on the duct size will increase the total static loss, which shall be overcome by the

    supply fan. The increase of the static loss may cause an insufficient air flow from point O

    to P and require a higher fan static.

    Referring to figure 4.2, if the static balance method is applied, with the same

    modification on section F-J, the air will achieve self-balancing so that more air will flow

  • 7/28/2019 Duct Sizing-static Balance

    22/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 22 of 24

    through section C-L and E-N to achieve static balance phenomenon. The increase of static

    loss is one-third of the equal friction method. Hence, the disturbance may not be

    significant and the increase of fan size may not be required.

    5.3 Testing and Commissioning

    The static balance method is easier to balance as compared to the equal friction

    method. The Equal friction method requires more commissioning time in the air balancing

    at branches, due to the air flow is limited within the same length of duct. For the static

    balance method, the air flow is self-balance within the duct network and the static

    variation by minor disturbances is not significant.

    6.0 THE STATIC BALANCE FOR VARIABLE AIR VOLUME (VAV) SYSTEM

    The Static balance duct design method offers many advantages and well applicable

    for the VAV system. For any partial loading of the VAV system, the air flow rate will self-

    balance to achieve the lowest static loss across the duct network. Therefore, it enhances

    energy saving on the fan operating cost. Furthermore, the response time of pressure

    variation for VAV system is much faster compared to the conventional system due to the

    shorter duct length.

    6.1 The Equal Friction Method for VAV system

    For a VAV system, the supply fan speed is controlled by a variable speed drive

    (VSD), corresponding to a pressure sensor located in the duct. Referring to figure 3.2, for

    example, the pressure sensor is located between sections L-M. If a VAV terminal unit

    located at H is shut off, the pressure sensor will sense the variation and feedback to the

    supply fan in reducing the speed. However, the static loss that is required to be overcome

    by the supply fan remains unchanged because the air supply from point O to P is

    unchanged. The fan reduces air flow rate and maintain the static.

    Furthermore, the response time of pressure variation from point H to point L is

    long because of the long duct works through path H-E-D-C-B-A-F-J-K-L.

  • 7/28/2019 Duct Sizing-static Balance

    23/24

    STATIC BALANCE DUCT DESIGN METHOD

    Copyright 2008 by Kok-Haw Kong

    All right reserved.

    Page 23 of 24

    6.2 The Static Balance Method for VAV System

    A Similar case of the equal friction method for VAV system is applied to the static

    balance method. Referring to figure 4.2, the pressure sensor is located at L-M. If the VAV

    terminal unit located at H is shut off, the pressure sensor will sense the variation and

    feedback to the supply fan in reducing the speed. In this case, the air flow within the duct

    network will perform self-balancing to reduce the total overall static loss. The air flow

    within each section of duct of the network is reduced. It reduces the overall static loss

    from point O to Q and the energy consumption.

    In addition, lower air flow through bigger duct size reduces the friction factor per

    unit of length. As a result, static balance method further reduces the static that required to

    be overcome by the supply fan. It further reduces the fan speed and enhances energy

    saving. In static balance method, the fan reduces the air flow and the static as well.

    The pressure variation response time of the pressure sensor from point H to point L

    is short through path H-N-M-L.

  • 7/28/2019 Duct Sizing-static Balance

    24/24

    STATIC BALANCE DUCT DESIGN METHOD

    CONCLUSION

    The static balance is a novel duct design method which has advantages over

    conventional duct design methods. The static balance is a duct network system that

    implements the continuity and work-energy principles throughout the network.

    The static balance method is an intelligent self-balance method by achieving

    minimum static losses across the ducting network. Although the initial cost for the static

    balance method is higher than the equal friction method, it is offset by the long term

    operating cost. The static balance method also minimizes the increase of static losses,

    which causes by site modifications, within the duct network. The commissioning of the

    static balance is easier and faster than the equal friction method.

    Furthermore, the static balance method is well applicable to the variable air volume

    (VAV) system. It enhances the functionality of VAV system. It reduces the system

    response time. Due to its intelligent self-static balance characteristic, it further reduces the

    overall static losses within the duct network system and achieves higher energy saving.

    REFERENCES

    1. Carrier, Handbook of Air Conditioning System Design. McGraw-Hill, New York.

    2. SMACNA, HVAC Duct Construction Standards. 1985. SMACNA, USA

    3. R.L. Street, Elementary Fluid Mechanicals. 1996. (7th Ed.) John Wiley & Sons, NewYork.