Duane Meyers ArchitectTexas badlands & beyond...
Send to:City of KellerChief Building Official/Building Services Manager1100 Bear Creek ParkwayKeller, TX 76244
Attention:Ryan Studdard
Project:Starbucks 962 Keller Parkway
October 3, 2016
Transmitting: No. Date Description Pages
2 10/3/2016 Construction Documents (2 full size sets) 28
1 10/3/2016 CD of Construction Documents na
1 10/5/2016 Plan Review Response 9
For Your: Remarks:
√ approval Mr. Studdard,
Attached are revised Construction Documents for the Starbucks Shell addressing the City of Keller’s comments. Please let us know if you have any additional items.
Thank you so much.
cc: Bennie Meyers, Duane Meyers Architect
√ review & comment
use
distribution to parties
√ record
√ information
other
By:
Duane Meyers Architect
560 PR 2422 Uncertain, TX 75661
903.484.4040
560 PR 2422 Uncertain, TX 75661
903.484.4040
Duane Meyers ArchitectTexas badlands & beyond...
5 Oct 2016
Ryan Studdard, Building Official City of KellerRe: Plan Review Comment Response for Starbucks Shell MISC16-0354
This is a response to your Fire-Rescue Comments, developed by Debra Crafton, Fire Marshal: 1. No reflective ceiling plan included with the submittal, please provide. COMPLY: Not Applicable (na), this project & permit is for the renovation of the shell building only, the Tenant (Starbucks) will submit Tenant Finish Plans that will include a Reflected Ceiling Plan.2. No finished floor plan included with the submittal, please provide. COMPLY: Not Applicable (na), this project & permit is for the renovation of the shell building only, the Tenant (Starbucks) will submit Tenant Finish Plans that will include a Finished Floor Plan.3. No information included in the submittal on the intent of hood and fixed extinguishing system. Please provide information on whether or not you intend to keep or remove the existing system. COMPLY: This project & permit is for the renovation of the shell building only. The existing Hood and Fire Suppression System is to be removed and discarded. The Tenant (Starbucks) will submit Tenant Finish Plans that will include their specific requirements for Kitchen Equipment.
This is a response to your Code Solutions Plan Review Check Sheet Comments: 1. Structural Plans not sealed. Please provide structural plans prepared and sealed by registered professional engineer. COMPLY: See attached S1.02 & S2.02.2. Please provide structural plans confirming roof framing is adequate for proposed mechanical equipment. NOTE: RTU specifications have not yet been developed by Starbucks who will be furnishing them as part of their Tenant Finish Plans. The Roof Framing Plan currently shows three 8 ton RTU’s that weigh 1,000 lbs each for Contractor pricing. The Tenant has been instructed to submit their RTU specifications to the Contractor so that the Wood Roof Truss Engineer can calculate the required truss sizes specifically for their units. The Contractor has been notified to submit the engineered truss submittal to the City of Keller for review and permit approval once Starbucks has selected their equipment. 3. Plans indicate the addition of the building area for drive through. Please provide site plan with dimensions to property lines and copy of the approved final plat filed with Tarrant County. The City of Keller, Unified Development Code, Section 4.04 requires an approved final plat prior to issuance of a building permit for new construction and additions. COMPLY: See attached newly issued A2.04 Architectural Site Plan and the Plat on Sheet A2.05.4. Sheet A4.02 indicated foundation information for the proposed addition. Please provide foundation plan prepared sealed by a professional engineer. COMPLY: Refer attached S1.02, detail 10 foundation detail.5. Please provide engineers structural framing plan for canopies including the wood framing supporting the canopies. COMPLY: Refer attached S1.02, detail 09 showing canopy framing detail.
�1
5 Oct 2016
Energy Code: 1. Provide COMCheck Envelope Compliance statement. Mechanical & lighting compliance statements to be provided at the time of tenant improvement. COMPLY: See attached Envelope Compliance Report.2. Provide on the revised plan the solar reflectance of the new TPO roofing shown to be installed. See 2015 IECC section C402.3. COMPLY: Refer revised A2.02 Roof Plan, Solar Reflectance to be 0.81.
Please let us know if you have any additional questions.
Duane Meyers Architect
�2
COMcheck Software Version COMcheck-Web
Envelope Compliance Certificate
Project Title:
2015 IECC
Project Type: New ConstructionVertical Glazing / Wall Area: 12%
Location: Keller, TexasClimate Zone: 3a
Construction Site:962 Keller ParkwayKeller, Texas 76248
Owner/Agent:Waylon LonginoNoble RE LLC4619 Insurance LaneDallas, Texas [email protected]
Designer/Contractor:Duane MeyersDuane Meyers Architect560 PR 2422Uncertain, Texas 75661903 484 [email protected]
Project Information
Energy Code:
Keller Starbucks Shell Conversion
Building Area Floor Area
1-Dining: Bar Lounge/Leisure : Nonresidential 2001
Envelope Assemblies
Assembly CavityR-Value
Cont.R-Value
ProposedU-Factor
Budget U-Factor(a)
Gross Areaor
Perimeter
Roof: Insulation Entirely Above Deck, 3-Year-Aged Solar Reflectance =0.79, Thermal Emittance = 0.75 (d), [Bldg. Use 1 - Dining: BarLounge/Leisure]
2000 --- 25.0 0.039 0.039
Floor: Unheated Slab-On-Grade, [Bldg. Use 1 - Dining: BarLounge/Leisure] (c)
185 --- --- 0.730 0.730
NORTHExt. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Dining: BarLounge/Leisure]
655 20.0 0.0 0.064 0.064
Window: Metal Frame: Fixed, Perf. Specs.: Product ID N Glazing,SHGC 0.37, PF 0.40, [Bldg. Use 1 - Dining: Bar Lounge/Leisure] (b)
163 --- --- 0.460 0.460
Door: , Perf. Specs.: Product ID N Door, SHGC 0.37, PF 0.40, [Bldg.Use 1 - Dining: Bar Lounge/Leisure] (b)
21 --- --- 0.600 0.770
EASTExt. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Dining: BarLounge/Leisure]
998 20.0 0.0 0.064 0.064
Window: Metal Frame: Fixed, Perf. Specs.: Product ID E Glazing,SHGC 0.30, PF 0.40, [Bldg. Use 1 - Dining: Bar Lounge/Leisure] (b)
130 --- --- 0.460 0.460
SOUTHExt. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Dining: BarLounge/Leisure]
655 20.0 0.0 0.064 0.064
Door: Insulated Metal, Swinging, [Bldg. Use 1 - Dining: Bar 21 --- --- 0.610 0.610
Additional Efficiency PackageHigh efficiency HVAC. Systems that do not meet the performance requirement will be identified in the mechanical requirements checklistreport.
Project Title:Data filename:
Keller Starbucks Shell Conversion 10/06/16Report date:91 ofPage
Assembly CavityR-Value
Cont.R-Value
ProposedU-Factor
Budget U-Factor(a)
Gross Areaor
Perimeter
Lounge/Leisure]
WESTExt. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Dining: BarLounge/Leisure]
942 20.0 0.0 0.064 0.064
Window: Metal Frame: Fixed, Perf. Specs.: Product ID W Glazing,SHGC 0.30, PF 0.40, [Bldg. Use 1 - Dining: Bar Lounge/Leisure] (b)
88 --- --- 0.460 0.460
(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.(c) Slab-On-Grade proposed and budget U-factors shown in table are F-factors.(d) High albedo roof requirement options: 1) 3-year aged solar reflectance >= 0.55 thermal emittance >= 0.75, 2) 3-year aged solar reflectance
index >= 64.0, 3) Initial year aged solar reflectance >= 0.70 thermal emittance >= 0.75, 4) Initial year aged solar reflectance index >= 82.0.
Envelope Compliance StatementCompliance Statement: The proposed envelope design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed envelope systems have beendesigned to meet the 2015 IECC requirements in COMcheck Version COMcheck-Web and to comply with the mandatoryrequirements listed in the Inspection Checklist.
Name - Title Signature Date
Envelope PASSES: Design 0.0% better than code
Project Title:Data filename:
Keller Starbucks Shell Conversion 10/06/16Report date:92 ofPage
Dua
ne M
eyer
s AIA
A
rchi
tect
Revisions
560
PR 2
422
Unc
erta
in, T
X 75
661
903.
484.
4040
drm
eyer
s@m
ac.c
om
Revisions
Oct 3 2016
Star
buck
s She
ll C
onve
rsio
nK
elle
r, Te
xas
0 1' 2' 3'
0 1' 2' 3'
0 1' 2' 3'
0 1' 2' 3' 0 1' 2' 3' 0 1' 2' 3'
RI
0 1' 2' 3'
4 1/2"
108'-0" max.
match existing
match existing
2"4"
truss span
per truss mfg per truss mfg per truss mfg per truss mfg
A B B B A
114'-0" brg
122'-0" top plate
122'-0" top plate
5 1/2"
114'-0" brg
122'-0" top plate 122'-0" top plate
5 1/2"5 1/2" 5 1/2"
108'-0" blocking max. 108'-0" blocking max.
match existing bottom of plate
match existing
1049'-5/8"-0" 2x6 blocking (typical)
5 1/2"
5'-0"
1'-0
"2'
-0"
4"5"
typ.
1'-6"
5 7/8"
4'-0"
eq. eq.
01 scale: 3/4" = 1'-0"
scale: NTSRoof Truss Notes & Bracing08
Load Bearing @ Truss Low Side Framing Detail
5/8" APA rated,exposure 1 plywoodsheathing on 2x6 studs@ 16" o.c.
5/8" APA rated,exposure 1 plywoodsheathing @ exteriorparapet
single slope wood truss@ 24" o.c.
wood truss roll blocking
Simpson H1 connection@ each truss
Simpson H35 @ eachparapet vertical to plateconnection, do not nailto wood truss
provide cont. 2x6 blocking @mid-height between roof deck &sill plate, max. spacing 8'-0"(omit @ storefront condition)
2x6/2x4 blocking @ roofdeck elevation
SF
line of finishrefer Architectural
cont. 2x6 decksupport, nail @ eachstud w/ 2 - 10d nailsmin.
3/4" APA rated, exposure 1plywood sheathing @ roofdeck
06 scale: 3/4" = 1'-0"GLB Brg @ Openings Elevation
3 - 2x6 stud brg under GLB
cont. 2x6 stud past GLB
2x6 blocking
2x6 studs @ 16" o.c. onplate on GLB
cont. 2x6 nailer under GLB
storefront opening
07 scale: 3/4" = 1'-0"GLB Brg @ Openings Section
3 - 2x6 stud brg under GLB
2x6 studs @ 16" o.c. onplate on GLB
cont. 2x6 nailer under GLB
storefront opening
GLB as scheduled(Grade 24F-V4-1.7E)
bottom of GLB
8" x 5" x 3/8" bent plate lintel(A36), flush at each side
3/4" x 5" hex lagbolt @ 24" o.c.(5 total)
GLB as scheduled(Grade 24F-V4-1.7E)
refer architectural WallSections for req'd blocking@ awnings
deck slope1/4" per 12" slope
top chord cont. bracing
bottom chord cont. lateralbracing, spacing per trussengineer
web bracing repeated @each end of the bldg & at20' intervals max., orient 45degrees to trussNOTE:1. All exterior lumber shall be treated.2. All truss & bearing wall connections shall be done with SimpsonHurricane Ties or heavy girder tie downs or equal. Submittal required.3. Truss manufacturer to provide & design all hurricane & heavy girdertiedowns to comply with the reactions determined from given loadrequirements4. Connection details shall be provided with truss shop drawings5. Metal Plate connected wood trusses @ 24" o.c. applied pressures: DL Roof T.C. = 10 psf DL Roof B.C. = 10 psf LL Roof T.C. = 25 psf LL Roof B.C. = 10 psf Net Wind Uplift = 14 psfShop Drawings and Calculations shall be submitted & sealed by aProfessional Engineer registered in the State of Texas
provide panel edge H Clips
5/8" APA rated, Exposure 1plywd sheathing
roof truss framing members
Typical Roof Shthg Nailing Pattern
Nailing Pattern Schedule:Wind Speed Mark Spacing Nail Type90 to 125 MPH A 6 inches 8d ring shank B 6 inches 8d ring shankRing Shank Minimum Dimensions0.113 inch nominal shank ring dia. of 0.012 over shank dia.16 to 20 rings per inch 0.28 inch full head dia.2 inch max. length
02 scale: 3/4" = 1'-0"Load Bearing @ Truss High Side Framing Detail 03 scale: 3/4" = 1'-0"
Non-Load Bearing Framing Detail
2x6 's @ 16" o.c. w/dbl top brg plate
dbl top 2x6 plate ontruss upright
trtd 2x blocking as perArchitectural drawings
5/8" plywd sheathingas specified
2x6 blocking top & bottom
5/8" APA rated,exposure 1 plywoodsheathing on 2x6 studs@ 16" o.c.
5/8" APA rated,exposure 1 plywoodsheathing @ exteriorparapet
single slope wood truss@ 24" o.c.
wood truss roll blocking
Simpson H1 connection@ each truss
Simpson H35 @ eachparapet vertical to plateconnection, do not nailto wood truss
provide cont. 2x6 blocking @mid-height between roof deck &sill plate, max. spacing 8'-0"(omit @ storefront condition)
2x6/2x4 blocking @ roofdeck elevation
line of finishrefer Architectural
3/4" APA rated,exposure 1 plywoodsheathing @ roof deck
2x6 's @ 16" o.c. w/dbl top brg plate
dbl top 2x6 plate ontruss upright
trtd 2x blocking as perArchitectural drawings
5/8" plywd sheathingas specified
2x6 blocking top & bottom
SFSF
refer S1.02-01 forTypical Notes
line of finishrefer Architectural
cont. cross bracing@ first set of rooftrusses @24" o.c.TYPICAL
cont. lateral truss bracing@ 32" o.c.cont. 2x4 ledger @ joistbearing elevation
2x6 studs cont. from sillplate (or header to topof parapet @ non-loadbearing conditions
refer S1.02-01/03 forTypical Notes
cont. 2x6 deck support, nail@ each stud w/ 2 - 10dnails min.cont. cross bracing @ firstset of roof trusses @24" o.c.TYPICAL
cont. lateral truss bracing@ 32" o.c.cont. 2x4 ledger @ joistbearing elevation
cont. 2x6 blocking top & bottom ofGLB
2x6 studs @ 16" o.c. onplate on GLB
GLB as scheduled(Grade 24F-V4-1.7E)8" x 5" x 3/8" bent plate
lintel (A36), flush withopening on sides
3/4" x 5" hex lagbolt @ 24" o.c.(5 total)
04 scale: 3/4" = 1'-0"Non-Load Bearing @ Opening Detail
SF
2x6 bracerefer Truss Profiles
2x6 bracerefer Truss Profiles
refer S2.02-03 for bracedetails & notes
refer S2.02-03 for bracedetails & notes
123'-4" top plate 123'-4" top plate 123'-4" top plate
SF
2x6 blocking
refer Elevations for brick color bandingwhich varies around the building,coordinate, check and double check
2x4 "X" bracing @ first trussinterval
bottom chord brg woodtruss @ 24" o.c.
cont. lateral truss bracingrefer Structural
cont. 2x4 ledger @ joist brgelevationrefer Structural
Simpson Strong TieCS16 @ every 3rd Studon side walls. Use 11-8Dnails top and bottom ofdouble plate as shown.
2x4 diagonal brace @ secondtruss interval
2x brace @48" o.c.
awning with struts bySuntec Signs & Awnings(214) 630-1116www.suntecindustries.com
2x8 blocking
scale: NTSTypical Awning Detail09
2 - #5 bars cont.top & bottom
SF
Grade Beam @ Drive Thru Extension10 scale: 3/4" = 1'-0"
1/2" dia. anchor bolt x 8" d.min. embed @ 32" o.c. max.,2 bolts per plate min, with 12"max. from end of plate
2x6 trtd plate set on sillplate sealant
slab reinforcing#3's @ 16" o.c. eachway
#3 dowels @ 16" o.c. x 2'-0"refer Civil for flatworkelevation
#3 ties @ 18" o.c.
omit curb @ doors &storefront
#3 dowel @ 18" o.c.
5 - #5's top & bottomeach way
S1.02
Dua
ne M
eyer
s AIA
A
rchi
tect
Revisions
560
PR 2
422
Unc
erta
in, T
X 75
661
903.
484.
4040
drm
eyer
s@m
ac.c
om
Revisions
Oct 3 2016
Star
buck
s She
ll C
onve
rsio
nK
elle
r, Te
xasGENERAL
1. THE CONTRACTOR SHALL VERIFY FIELD DIMENSIONS AND CONDITIONS BEFORE CONSTRUCTION AND NOTIFY THE ARCHITECT OF ANY DISCREPANCIES OR INCONSISTENCIES BEFORE PROCEEDING WITH THE WORK.
2. THE CONTRACTOR SHALL VERIFY LOCATIONS AND SIZES OF ALL OPENINGS IN FLOORS AND ROOFS AND ALL INSERTS AND EMBEDDED ITEMS WITH MECHANICAL, ELECTRICAL, AND ARCHITECTURAL DRAWINGS BEFORE PLACING CONCRETE, INSTALLING METAL DECKING OR ERECTING ANY STRUCTURAL LOAD BEARING MATERIAL. THE GENERAL CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL COORDINATION WITH SUB-CONTRACTORS.
3. ADEQUATE TEMPORARY BRACING WILL BE REQUIRED OF ALL STRUCTURAL PIECES OR UNITS UNTIL ALL MASONRY WALLS AND/OR FLOOR OR ROOF DECKS ARE IN PLACE, AND ALL CONCRETE HAS BEEN PLACED AND GAINED ITS ULTIMATE STRENGTH.
4. IN CASE OF DISCREPANCIES IN DIMENSIONS AND ELEVATIONS BETWEEN STRUCTURAL AND ARCHITECTURAL DRAWINGS, CONTRACTOR SHALL VERIFY WITH ARCHITECT PRIOR TO FABRICATION AND CONSTRUCTION.
5. THE LATEST EDITION OF ACI, AISC, AWS, CRSI AND SJI SPECIFICATIONS SHALL GOVERN ALL PHASES OF FABRICATION AND CONSTRUCTION.
6. DESIGN CODES AND GENERAL CRITERIA:a. 2015 INTERNATIONAL BUILDING CODE.b. ACI 318 BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE.c. AISC SPECIFICATION FOR STRUCTURAL STEEL FOR BUILDINGS – ALLOWABLE STRESS DESIGN AND PLASTIC DESIGN,
THIRTEENTH EDITION.d. ASCE 7-05 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES.
7. STRUCTURAL DESIGN CRITERIA:ROOF DEAD LOAD - 20 PSFROOF LIVE LOAD - 25 PSFFLOOR LIVE LOAD - 50 PSF
8. WIND DESIGN DATA:WIND LOAD - 115 MPH PER ASCE 7-10IMPORTANCE FACTOR - 1.00RISK CATEGORY - 2WIND EXPOSURE CATEGORY - 0.18
FOUNDATION1. EARTHWORK: ALL EXISTING PAVEMENTS, FOUNDATIONS, UTILITIES, VEGETATION, TOPSOIL CONTAINING ORGANIC MATERIALS AND ANY SOFT
SOILS SHALL BE CLEARED AND GRUBBED FROM THE BUILDING SITE. EXCAVATE FROM EXISTING GRADE AS REQUIRED. SLOPE FINAL CUT OF EXCAVATED SURFACE ON ONE PERCENT (1%) TO ALLOW DRAINAGE OF ANY WATER UNDER FOUNDATION. AFTER REMOVAL OF VEGETATION AND EXCAVATION, THE EXPOSED SURFACE SHALL BE PROOF ROLLED AND ANY SORT OF COMPRESSIBLE MATERIAL SHALL BE REMOVED OR IMPROVED BY DENSIFICATION AS RECOMMENDED FOR COMPACTED FILL BELOW FOUNDATIONS. AFTER COMPLETION OF PROOF ROLLING THE SURFACE SHALL BE SCARIFIED FOR A MINIMUM DEPTH OF TWELVE (12) INCHES AND RECOMPACTED AS PER COMPACTION NOTE.
2. EXPOSED SURFACE COMPACTION: EXPOSED SURFACE SOIL TO RECEIVE SELECT FILL SHOULD BE SCARIFIED TO A MINIMUM OF TWELVE (12) INCHES AND MOISTURE CONDITIONED TO A MINIMUM OF NINETY-FIVE PERCENT (95%) OF MAXIMUM DRY DENSITY AT MINUS ONE (-1%) PERCENTAGE POINTS BELOW TO PLUS THREE (+3%) PERCENTAGE POINTS ABOVE ITS OPTIMUM MOISTURE CONTENT AS DETERMINED BY THE STANDARD PROCTOR METHOD, ASTM SPECIFICATION D698.
3. AFTER SURFACE SOIL TO RECEIVE SELECT FILL HAS SCARIFIED AND COMPACTED THE SELECT FILL SHOULD BE PLACED PROMPTLY TO PREVENT DRYING OF THE SUBGRADE SOILS. REFER TO SOIL REPORT SECTION 4.6 FOR ADDITIONAL INFORMATION.
4. ALL SOIL USED AS FILL SHALL BE A NON-EXPANSIVE SANDY CLAY OR CLAYEY SAND WITH A MAXIMUM LIQUID LIMIT OF 35, PLASTICITY INDEX BETWEEN 5 AND 15 AND LESS THAN 40% PASSING THE #200 SIEVE. SAND CUSHION UNDER SLABS-ON-GRADE SHALL BE EITHER WELL-GRADED WASHED CONCRETE SAND OR PEA GRAVEL.
5. SELECT FILL COMPACTION: SELECT FILL PAD SHOULD EXTEND AT LEAST THREE (3) FEET BEYOND THE EDGE OF BUILDING. SELECT FILL REQUIRED BENEATH THE GRADE SLAB SHALL BE PLACED IN EIGHT (8) INCH THICK LOOSE LIFTS AND COMPACTED TO A MINIMUM OF NINETY-FIVE PERCENT (95%) OF MAXIMUM DRY DENSITY AS DETERMINED BY THE STANDARD PROCTOR METHOD, ASTM SPECIFICATION D698.
6. POSITIVE SURFACE DRAINAGE AWAY FROM THE STRUCTURES SHALL BE ESTABLISHED AND MAINTAINED AT ALL TIMES BOTH DURING AND AFTER CONSTRUCTION. WATER SHALL NOT BE ALLOWED TO COLLECT NEAR THE BUILDING SITE AT ANY TIME.
7. FINISH GRADES OF FILL: THE FINISH GRADES OF FILL AGAINST GRADE BEAMS SHALL SLOPE AWAY FROM THE BUILDING AND CARE SHALL BE TAKEN THAT NO LOW SPOTS EXIST IN FILL THAT ALLOWS WATER TO COLLECT.
8. CONTRACTOR SHALL PROVIDE ADEQUATE EXCAVATION SHORING TO PREVENT CAVE-INS.
9. ALL FOUNDATION EXCAVATIONS SHALL BE INSPECTED BY THE ARCHITECT PRIOR TO PLACEMENT OF REINFORCING STEEL OR CONCRETE.
10. EACH LIFT OF COMPACTED SOIL SHOULD BE TESTED AND INSPECTED BY THE SOILS ENGINEER OR HIS REPRESENTATIVE PRIOR TO PLACEMENT OF SUBSEQUENT LIFTS.
11. CONDUCT IN-PLACE DENSITY TESTS AT THE RATE OF NOT LESS THAN ONE (1) TEST PER 2500 SQUARE FEET OF SURFACE AREA OR MINIMUM OF FOUR (4) TESTS PER LIFT FOR EACH TESTED AREA.
12. CONFIRM SUITABILITY BY ATTERBERG LIMIT TESTS AT THE RATE OF AT LEAST ONE TEST PER 250 CUBIC YARDS.
13. CONTRACTOR SHALL PROVIDE FOR DEWATERING AT EXCAVATIONS FROM EITHER SURFACE WATER OR SEEPAGE.
CONCRETE1. ALL CONCRETE SHALL HAVE A MINIMUM ULTIMATE COMPRESSIVE STRENGTH OF 3000 P.S.I. AT 28 DAYS. ALL CONCRETE EXPOSED TO
WEATHER SHALL HAVE 5-1/2% (+/-) 1-1/2% AIR ENTRAINMENT. AIR ENTRAINMENT SHALL NOT EXCEED 3% FOR INTERIOR SLABS WITH A STEEL TROWEL FINISH.
2. MINIMUM CONCRETE 28 DAY COMPRESSIVE STRENGTH AND SLUMP:
a. FOOTINGS - 3000PSI SLUMP (MIN./MAX.) 4IN/6INb. GRADE BEAMS - 3000PSI SLUMP (MIN./MAX.) 3IN/5INc. SLABS ON GRADE - 3000PSI SLUMP (MIN./MAX.) 2IN/4IN
3. CONCRETE MIX DESIGNS FROM THE CONCRETE SUPPLIER AND TEST RESULTS FROM THE TESTING LAB SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER FOR EVALUATION AND APPROVAL.
4. ALL CAST-IN-PLACE CONCRETE WORK SHALL BE IN ACCORDANCE WITH ACI 301, LATEST EDITION.
5. ALL DETAILING, FABRICATION AND INSTALLATION OF STEEL REINFORCEMENT SHALL BE IN ACCORDANCE WITH ACI 315 AND ACI 318 (LATEST EDITIONS).
6. CONCRETE REINFORCING: REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615, GRADE 60 BARS.
7. MINIMUM COVERAGE ON REINFORCING STEEL:a. CONCRETE CAST AGAINST EARTH - 3IN CLEAR TO STIRRUPb. CONCRETE CAST AGAINST FORMS - 2IN CLEAR TO STIRRUPc. GRADE BEAMS - 0.75IN TOP, 3IN BOTTOM, 1.5IN ON PANEL FORMED SIDES
8. GRADE BEAMS SHALL BE ON SIZE AND WITH REINFORCEMENT AS INDICATED ON PLANS. VAPOR RETARDER SHALL BE FOLDED INTO TRENCH TO WITHIN 2 INCHES OF TRENCH BOTTOM WHEN SPECIFIED. DETAIL REINFORCING AND PROVIDE CORNER BARS AT GRADE BEAM INTERSECTIONS TO MATCH HORIZONTAL REINFORCING. SPLICE BOTTOM REINFORCING WHEN NECESSARY OVER SUPPORTS. SPLICE TOP REINFORCING WHEN NECESSARY AT MID-SPAN. ALL SPLICES SHALL BE ACCORDANCE WITH THE ACI 318 AND THE TYPICAL DETAILS CONTAINED ON THE DRAWINGS.
9. SLABS ON GRADE: SLABS ON GRADE SHALL BE OF THE THICKNESS AND WITH REINFORCEMENT AS SHOWN ON DRAWINGS. APPLY CURING COMPOUND IN ACCORDANCE WITH THE SPECIFICATIONS AND MANUFACTURER'S RECOMMENDATIONS. SLAB REINFORCING SHALL BE CENTERED IN SLAB. CARE SHALL BE TAKEN TO MAINTAIN SLAB REINFORCEMENT POSITION DURING PLACING OPERATION.
10. UNLESS NOTED OTHERWISE, PROVIDE 90 DEGREE CORNERS AT ALL EXPOSED EDGES AND CORNERS.
11. PROVIDE CONSTRUCTION JOINTS AS REQUIRED. COORDINATE JOINT LOCATIONS WITH ARCHITECT/ENGINEER.
REINFORCING STEEL1. ALL REINFORCING STEEL SHALL BE NEW BILLET, ASTM A615 GRADE 60 DEFORMED DOMESTIC BARS. ALL DETAILING, FABRICATION, PLACING
AND SUPPORTING SHALL BE IN ACCORDANCE WITH ACI 318 AND CRSI.
2. ALL DOWELS SHALL BE THE SAME SIZE AND SPACING AS ADJOINING MAIN BARS (MIN. LAP 30 BAR DIA.), UNLESS NOTED OR DETAILED OTHERWISE.
3. THE MINIMUM SPLICE OF ALL CONTINUOUS BARS SHALL BE 40 BAR DIA. (2'-0" MIN.). PROVIDE OUTSIDE CORNER BARS IN ALL BEAMS, BARS SHALL BE SAME SIZE AS MAIN BEAM STEEL; LAP 30 BAR DIA.
4. CLEAR MINIMUM COVERAGE OF CONCRETE OVER REINFORCING BARS SHALL BE AS FOLLOWS:
1.CONCRETE PLACED AGAINST EARTH --------------------------- 3"2.FORMED CONCRETE AGAINST EARTH -------------------------- 2"3.BEAMS TO TIES/STIRRUPS ------------------------------------------- 1-1/2"
5. ALL REINFORCING BARS, W.W.F., BOLTS, DOWELS, INSERTS, ETC., SHALL BE RIGIDLY SECURED IN POSITION PRIOR TO PLACING CONCRETE.
6. CONTRACTOR SHALL SUBMIT COMPLETE SHOP AND PLACING DRAWINGS AND OBTAIN APPROVAL PRIOR TO FABRICATION.
TIMBER FRAMING1. SAWN TIMBER MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF THE AMERICAN INSTITUTE OF TIMBER CONSTRUCTION STANDARDS,
A.I.T.C. LATEST EDITION.
2. SAWN LUMBER SHALL BE #2 K.D. SOUTHERN YELLOW PINE, MOISTURE CONTENT 15% WITH THE FOLLOWING ALLOWABLE STRESSES:
a. F(b) = 1500PSI, F(t) = 825PSI, F(c)(PARALLEL TO GRAIN) = 1650PSI, F(c)(PERPENDICULAR TO GRAIN) = 565PSI, F(v) = 90PSI, E = 1,600,000PSI
3. ALL TIMBER MEMBERS IN CONTACT WITH CONCRETE OR MASONRY SHALL BE PRESSURE TREATED WITH A WATER BORNE TREATMENT TO A NET RETENTION OF 0.3 POUNDS PER CUBIC FOOT.
4. PLYWOOD FOR ROOF SHEATHING SHALL BE 5/8" APA RATED, EXPOSURE 1 PLYWOOD. REFER TO TYPICAL DETAIL FOR NAILING PATTERN. BLOCK ALL PANEL EDGES AS REQUIRED.
5. ALL ROOF TRUSSES SHALL BE DESIGNED BY THE FABRICATOR TO SUPPORT 10 PSF DEAD LOAD ON THE TOP CHORD AND 10 PSF DEAD LOAD ON THE BOTTOM CHORD PLUS 25 PSF LIVE LOAD ON THE TOP CHORD PLUS 10 PSF LIVE LOAD ON THE BOTTOM CHORD, PLUS CODE WIND LOAD. GLULAM MEMBERS SHALL HAVE A STRESS GRADE OF 2.0E MINIMUM.
6. FABRICATOR SHALL SUBMIT CALCULATIONS WITH SHOP DRAWINGS STAMPED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF TEXAS TO THE ARCHITECT FOR REVIEW PRIOR TO FABRICATION OF TRUSSES.
7. TRUSS DIMENSIONS SHOWN ARE FOR ESTIMATING PURPOSES ONLY AND ARE NOT TO BE USED FOR FABRICATION. FABRICATOR SHALL BE RESPONSIBLE FOR ACTUAL DIMENSIONS OF TRUSSES.
8. TRUSS CONNECTIONS TO LOAD BEARING WALLS SHALL BE DESIGNED BY TRUSS MANUFACTURER.
9. BUILT-UP STUD COLUMNS AT EDGES OF ALL OPENINGS 3 MIN.
STRUCTURAL STEEL1. ALL WIDE FLANGE SECTIONS SHALL BE ASTM A992. ALL ANGLES, AND PLATES SHALL BE ASTM A36. ALL HOLLOW STRUCTURAL STEEL TUBE
SECTIONS SHALL BE ASTM A500 GRADE B.
2. STRUCTURAL STEEL SECTIONS SHALL BE DESIGNED, DETAILED FABRICATED AND ERECTED IN ACCORDANCE WITH THE AISC "MANUAL OF STEEL CONSTRUCTION", ALLOWABLE STRESS DESIGN, LATEST EDITION.
3. ALL BOLTED CONNECTIONS FOR STRUCTURAL STEEL SHALL USE MIN. 3/4" DIAMETER ASTM A325 HIGH STRENGTH BOLTS. CONNECTIONS SHALL BE BEARING TYPE WITH THREADS ALLOWED IN THE SHEAR PLANE.
4. ALL STRUCTURAL STEEL BOLTED CONNECTIONS WITH ASTM-A325 3/4" DIAMETER BOLTS SHALL BE TIGHTENED TO ACHIEVE A MINIMUM BOLT TENSION FOR CALIBRATED WRENCHES OF 30,000LBS. THE CONTRACTOR SHALL HAVE A QUALIFIED TESTING AGENCY CHECK ALL CONNECTIONS.
5. ALL WELDING SHALL CONFORM TO THE RECOMMENDATIONS OF THE AWS, AND ALL WELDS, INCLUDING FIELD, SHALL BE MADE ONLY BY CERTIFIED WELDERS USING E7OXX ELECTRODES.
6. ALL STRUCTURAL BOLTS SHALL BE ASTM A325-N, BEARING TYPE (3/4" DIA. UNLESS NOTED OTHERWISE). ANCHOR BOLTS SHALL BE ASTM A307.
7. ALL STRUCTURAL STEEL SHALL BE PAINTED WITH A SHOP PRIME COAT AND FIELD RETOUCHED WHERE THE SHOP COAT HAS BEEN DAMAGED DUE TO PLACING, HANDLING AND WELDING. ALL STEEL BEAMS SHALL BE FABRICATED WITH NATURAL CAMBER UP.
8. CONTRACTOR SHALL SUBMIT COMPLETE SHOP DRAWINGS AND OBTAIN APPROVAL PRIOR TO FABRICATION.
CONCRETE1. ALL CONCRETE SHALL HAVE A MINIMUM ULTIMATE COMPRESSIVE STRENGTH OF 3000 P.S.I. AT 28 DAYS. ALL CONCRETE EXPOSED TO
WEATHER SHALL HAVE 5-1/2% (+/-) 1-1/2% AIR ENTRAINMENT. AIR ENTRAINMENT SHALL NOT EXCEED 3% FOR INTERIOR SLABS WITH A STEEL TROWEL FINISH.
2. MINIMUM CONCRETE 28 DAY COMPRESSIVE STRENGTH AND SLUMP:
a. FOOTINGS - 3000PSI SLUMP (MIN./MAX.) 4IN/6INb. GRADE BEAMS - 3000PSI SLUMP (MIN./MAX.) 3IN/5INc. SLABS ON GRADE - 3000PSI SLUMP (MIN./MAX.) 2IN/4IN
3. CONCRETE MIX DESIGNS FROM THE CONCRETE SUPPLIER AND TEST RESULTS FROM THE TESTING LAB SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER FOR EVALUATION AND APPROVAL.
4. ALL CAST-IN-PLACE CONCRETE WORK SHALL BE IN ACCORDANCE WITH ACI 301, LATEST EDITION.
5. ALL DETAILING, FABRICATION AND INSTALLATION OF STEEL REINFORCEMENT SHALL BE IN ACCORDANCE WITH ACI 315 AND ACI 318 (LATEST EDITIONS).
6. CONCRETE REINFORCING: REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615, GRADE 60 BARS.
7. MINIMUM COVERAGE ON REINFORCING STEEL:a. CONCRETE CAST AGAINST EARTH - 3IN CLEAR TO STIRRUPb. CONCRETE CAST AGAINST FORMS - 2IN CLEAR TO STIRRUPc. GRADE BEAMS - 0.75IN TOP, 3IN BOTTOM, 1.5IN ON PANEL FORMED SIDES
8. GRADE BEAMS SHALL BE ON SIZE AND WITH REINFORCEMENT AS INDICATED ON PLANS. VAPOR RETARDER SHALL BE FOLDED INTO TRENCH TO WITHIN 2 INCHES OF TRENCH BOTTOM WHEN SPECIFIED. DETAIL REINFORCING AND PROVIDE CORNER BARS AT GRADE BEAM INTERSECTIONS TO MATCH HORIZONTAL REINFORCING. SPLICE BOTTOM REINFORCING WHEN NECESSARY OVER SUPPORTS. SPLICE TOP REINFORCING WHEN NECESSARY AT MID-SPAN. ALL SPLICES SHALL BE ACCORDANCE WITH THE ACI 318 AND THE TYPICAL DETAILS CONTAINED ON THE DRAWINGS.
9. SLABS ON GRADE: SLABS ON GRADE SHALL BE OF THE THICKNESS AND WITH REINFORCEMENT AS SHOWN ON DRAWINGS. APPLY CURING COMPOUND IN ACCORDANCE WITH THE SPECIFICATIONS AND MANUFACTURER'S RECOMMENDATIONS. SLAB REINFORCING SHALL BE CENTERED IN SLAB. CARE SHALL BE TAKEN TO MAINTAIN SLAB REINFORCEMENT POSITION DURING PLACING OPERATION.
10. UNLESS NOTED OTHERWISE, PROVIDE 90 DEGREE CORNERS AT ALL EXPOSED EDGES AND CORNERS.
11. PROVIDE CONSTRUCTION JOINTS AS REQUIRED. COORDINATE JOINT LOCATIONS WITH ARCHITECT/ENGINEER.
REINFORCING STEEL1. ALL REINFORCING STEEL SHALL BE NEW BILLET, ASTM A615 GRADE 60 DEFORMED DOMESTIC BARS. ALL DETAILING, FABRICATION, PLACING
AND SUPPORTING SHALL BE IN ACCORDANCE WITH ACI 318 AND CRSI.
2. ALL DOWELS SHALL BE THE SAME SIZE AND SPACING AS ADJOINING MAIN BARS (MIN. LAP 30 BAR DIA.), UNLESS NOTED OR DETAILED OTHERWISE.
3. THE MINIMUM SPLICE OF ALL CONTINUOUS BARS SHALL BE 40 BAR DIA. (2'-0" MIN.). PROVIDE OUTSIDE CORNER BARS IN ALL BEAMS, BARS SHALL BE SAME SIZE AS MAIN BEAM STEEL; LAP 30 BAR DIA.
4. CLEAR MINIMUM COVERAGE OF CONCRETE OVER REINFORCING BARS SHALL BE AS FOLLOWS:
1.CONCRETE PLACED AGAINST EARTH --------------------------- 3"2.FORMED CONCRETE AGAINST EARTH -------------------------- 2"3.BEAMS TO TIES/STIRRUPS ------------------------------------------- 1-1/2"
5. ALL REINFORCING BARS, W.W.F., BOLTS, DOWELS, INSERTS, ETC., SHALL BE RIGIDLY SECURED IN POSITION PRIOR TO PLACING CONCRETE.
6. CONTRACTOR SHALL SUBMIT COMPLETE SHOP AND PLACING DRAWINGS AND OBTAIN APPROVAL PRIOR TO FABRICATION.
TIMBER FRAMING1. SAWN TIMBER MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF THE AMERICAN INSTITUTE OF TIMBER CONSTRUCTION STANDARDS,
A.I.T.C. LATEST EDITION.
2. SAWN LUMBER SHALL BE #2 K.D. SOUTHERN YELLOW PINE, MOISTURE CONTENT 15% WITH THE FOLLOWING ALLOWABLE STRESSES:
a. F(b) = 1500PSI, F(t) = 825PSI, F(c)(PARALLEL TO GRAIN) = 1650PSI, F(c)(PERPENDICULAR TO GRAIN) = 565PSI, F(v) = 90PSI, E = 1,600,000PSI
3. ALL TIMBER MEMBERS IN CONTACT WITH CONCRETE OR MASONRY SHALL BE PRESSURE TREATED WITH A WATER BORNE TREATMENT TO A NET RETENTION OF 0.3 POUNDS PER CUBIC FOOT.
4. PLYWOOD FOR ROOF SHEATHING SHALL BE 5/8" APA RATED, EXPOSURE 1 PLYWOOD. REFER TO TYPICAL DETAIL FOR NAILING PATTERN. BLOCK ALL PANEL EDGES AS REQUIRED.
C
E GF1
H
I
2
3
D
SF SF
SF SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SFSF
4'-11 1/2" 8'-3" 4'-11 1/2" 7'-0"
1'-8" +/- 36'-2" +/- exisitng dimension Field Verify 3'-2" +/-
54' +
/- ex
istin
g di
men
sion
Fei
ld V
erify
36'-2" +/- existing dimension Feild Verify
14'-5
" +/-
exis
ting
dim
14'-1
0" +
/- ex
istin
g di
m
24'-7
" +/-
exis
ting
dim
20'-4
" +/-
exis
ting
dim
15'-0
" +/-
exis
ting
dim
4'-8
"
4'-8
"
14'-0
"2'
-6 5
/8"
2'-1
1 1/
2" +
/- (v
erify
w/ S
tarb
ucks
)5
1/8"
x 1
2 3/
8" G
LB
Roof Truss A@
24" o.c.
Roof Truss B@
24" o.c.
Roof Truss C@
24" o.c.
Roof Truss A@
24" o.c.
Roo
f Tru
ss H
drs
@ R
TU's
Roo
f Tru
ss H
drs
@ R
TU's
Roo
f Tru
ss H
drs
@ R
TU's
Roo
f Tru
ss H
drs
@ R
TU's
5 1/
8" x
11"
GLB
5 1/8" x 11" GLB
5 1/
8" x
11"
GLB
5 1/8" x 11" GLB
5 1/8" x 11" GLB
5 1/
8" x
11"
GLB
5 1/8" x 11" GLB
RTU-2 @ 8 ton(max)1,000 lbs
RTU-1 @ 8 ton(max.)1,000 lbs
line of top chordparapet braces
2x8's roof framing @top of tower wall @24" o.c.RTU-3 @ 8 ton
(max.)1,000 lbs
Rooftop Equipment CoordinationStarbucks is furnishing and installing their own RTU's. It is imperative that the Landlord's GCcoordinate location, dimensions (including height) as well as weight prior to the trusses beingfabricated to account for City required Rooftop Equipment Screening, RTU penetrations and RTUloading.
36'-2 1/4" +/- FIELD VERIFY
3'-0
"8'
-10"
3'-0
"8'
-10"
110'-2" ex. plate line
113'-2" bottom chord brg
122'-0" top plate 122'-0" top plate
3'-4
" max
Wood Truss A@ 24" o.c.
1/4"+ per 12"SLOPE
40'-2 5/8" +/- FIELD VERIFY3'
-0"
10'-2
"
3'-0
"10
'-2"
110'-2" ex. plate line
113'-2" bottom chord brg
123'-4" top plate 123'-4" top plate
5'-0
" max
.
Wood Truss B@ 24" o.c.
37'-10 5/8" +/- FIELD VERIFY
3'-0
"10
'-2"
3'-0
"8'
-10"
110'-2" ex plate line
113'-2" bottom chord brg
123'-4" top plate
5'-0
" max
. 122'-0" plate line2x6 No. 2 SYP
(TYPICAL)
Wood Truss C@ 24" o.c.
SCALE: 1/4" = 1'-0"01 Roof Framing Plan
SCALE: 1/4" = 1'-0"02 Roof Truss Profiles
S2.02
RI
RevisionsRevisions
3 Oct 2016
Star
buck
s She
ll C
onve
rsio
nK
elle
r, Te
xas
3 Oct 2016
Rev1: Response to Citycomments for permit andStarbucks Reviewcomments
ABSTRACT NO. 28
PAMELIA ALLEN SURVEY
P.R.T.C.T.
5' UTILITY EASEMENTCABINET A, SLIDE 2905
GRAPEVINE/WALL JOINT VENTURE
OVERHEAD UTILITY
D.R.T.C.T.VOLUME 12710, PAGE 2151
OWNER:
LOT 5RBLOCK 1
P.R.T.C.T.CABINET A, SLIDE 12656
TOWN CENTER EAST
CABINET A, SLIDE 2905P.R.T.C.T.
TOWN CENTER EAST
BLOCK 1LOT 4
PAVEMENTCONCRETE
D.R.T.C.T.VOLUME 12350, PAGE 944ACCESS EASEMENT NO. 2
TRACT 3
CONCRETE SIDEWALK
D.R.D.C.T.VOLUME 11621, PAGE 739
20' SANITARY SEWER EASEMENT
PAVEMENTCONCRETE
PAVEMENTCONCRETE
OHE
POWERPOLE
CONCRETE SIDEWALK
VAULTVERIZON
PEDESTALTELE.INLET
STORM DRAIN
962 KELLER PARKWAY
TRACT 3
P.R.T.C.T.CABINET A, SLIDE 2905
5' UTILITY EASEMENT
OWNER:
INST. NO. D204124965D.R.T.C.T.
KROGER TEXAS L.P.
ACCESS EASEMENT NO. 1VOLUME 12350, PAGE 944
D.R.T.C.T.
28,000 square feet0.643 ACRE
TOWN CENTER EAST
P.R.T.C.T.
BLOCK 1
CABINET A, SLIDE 1017
LOT 2
LOT 4BLOCK 1
P.R.T.C.T.CABINET A, SLIDE 2905
TOWN CENTER EAST
BLOCK 1
LOT 3
PAVEMENTCONCRETE
PAVEMENTCONCRETE
PAVEMENTCONCRETE
KELLER, TX. 76248
S 0
0°02
'00"
E
N 0
0°02
'00"
W
S 89°58'00" W 140.00'
RA
MP
RA
MP
23.3'
2 PA
RK
ING
SPA
CE
SS
PAC
ES
3 PA
RK
ING
NO
PA
RK
ING
STR
IPE
D F
OR14
PA
RK
ING
SPA
CE
S
(CM)
SRF5/8"SRF
1/2"
BIBHOSE
BIBHOSE
BOXELECTRIC
INTERCOM
BOARDMENU
ENCLOSUREDUMPSTER
CONC. BLOCK
BOLL
CONCRETE FLUME
RA
MP
WM
LIGHTPOLE
BOLL
BOLL
HCS
RA
MP
HCS
CO
SSMH
SSMH
CO
POLELIGHT
POLELIGHT
LIGHTPOLE
SIGN"DRIVE THRU"
ABANDONEDLIGHT POLE
POLELIGHT
POLELIGHT
POLELIGHT
BEGINNINGPOINT OF
PER ZONINGEASEMENT
30' LANDSCAPING/SIDEWALK
40' LANDSCAPE
PER ZONINGEASEMENT/SETBACK
P.R.T.C.T.CABINET A, SLIDE 2905
50' BUILDING LINE
CO
NC
RE
TE S
IDE
WA
LK
(BEARING BASE)
LINE OF RUFE SNOW366.85' TO THE WEST
CABINET A, SLIDE 2905P.R.T.C.T.
D.R.T.C.T.VOLUME 10789, PAGE 1824
VOLUME 4570, PAGE 4850' LONE STAR GAS EASEMENT
65'
65'
(A 130' WIDE RIGHT-OF-WAY ALSO KNOWN AS KELLER PARKWAY)
F.M. HIGHWAY NO. 1709
P.R.T.C.T.CABINET A, SLIDE 2905
ADDITIONTOWN CENTER EAST
CONCRETEPAVEMENT
200.
00'
200.
00'
140.00'N 89°58'00" E
50.0
'
23.3'
SPA
CE
S2
PAR
KIN
G
(CM)
SRF1/2"
SRF1/2"
TO BUILDINGGAS LINE
OHE
3(ea)CO
POLELIGHT
LINESOVERHEAD UTILITY
POWERPOLE
LIGHTPOLE
RAMP
MAILBOX
SSMH
FHWV
SIGN"TACO BELL"
TELE.PEDESTAL
WM
LINES
POLEPOWER GAS
METERWM
OVER FLUMEMETAL PLATE
CO
NC
RE
TE F
LUM
E
SIGN"EXIT"
"ENTER"SIGN
Scale 1" = 30'
30200 10 60
DEMO CURB
NEW CURBNEW PATIO
TO BE REMODELEDEXISTING BUILDING
STARBUCKS COFFEEAS
EXISTING
21'-75/8"
SCALE: 1" = 20'01 Architectural Site Plan
A2.04
This
doc
umen
t is
rele
ased
for t
he p
urpo
se o
f int
erim
revi
ew u
nder
the
auth
ority
of
Dua
ne M
eyer
s Ar
chite
ctre
gist
ratio
n no
. 859
9 in
the
Stat
e of
Tex
as a
nd is
not
tobe
use
d fo
r con
stru
ctio
n,bi
ddin
g or
per
mitt
ing.
RevisionsRevisions
5 Oct 2016
Star
buck
s She
ll C
onve
rsio
nK
elle
r, Te
xas
Rev1: Response to Citycomments for permit andStarbucks Reviewcomments
*ACS/TRC* TARRANT Doc: 0Z0112674 Date: 06/12/1996 Vol: 000000A Page: 02905 Page: 1 Of 2
*ACS/TRC* TARRANT Doc: 0Z0112674 Date: 06/12/1996 Vol: 000000A Page: 02905 Page: 2 Of 2
A2.05
RI
RevisionsRevisions
3 Oct 2016
Star
buck
s She
ll C
onve
rsio
nK
elle
r, Te
xas
3 Oct 2016
Rev1: Response to Citycomments for permit andStarbucks Reviewcomments
SF SF
SF SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SFSF
RI
4'-11 1/2" 8'-3" 4'-11 1/2" 7'-0"4'-8
"
4'-8
"
RIDGE
VALLEY
VALL
EY
VALLEY
4" d
ia p
rimar
y ro
of d
rain
tow
all c
avity
& d
ay li
ghte
dab
ove
grad
e
4" d
ia. s
econ
dary
roof
dra
in to
wal
lca
vity
& d
ay li
ghte
d ab
ove
grad
e
SLOPE
RIDGE
VALLEY
VALL
EY
VALLEYSLOPE
VALLEY
VALL
EY
VALLEY
SLOPE
SLOPE
SLOPE
SLOPE
bldg
dep
th d
ivid
ed b
y 6
equa
l spa
ces
for R
DSu
bcon
trac
tor t
o su
bmit
Shop
Dra
win
g Su
bmitt
al o
f tap
ered
roof
insu
latio
n to
com
ply
all I
BC
Cod
es
General Notes Roof Plan:1. TPO Roofing: Equal to Firestone 60 mil TPO roofing over 1/4" Dens Deck over R-25 rigid polyiso insulation
COLOR: white, solar reflectance value 0.81
2. Roof Drains: Firestone 4" dia.
3. All roof mounted equipment, locations & weights to beapproved by Landlord's Architect/Engineer prior to installation.Tenant providing RTU's, Landlord Contractor to coordinate allunit locations, weights, dimensions with Tenant prior toinstallation. All rooftop equipment to be screened by parapet.
4. Sheet Metal Awning: Berridge, Tee-Panel Roof, 24 ga., COLOR Kynar, Galvalume
botto
m c
hord
brg
@ 1
13'-2
" w/
3'-4
" tru
ss h
eel
botto
m c
hord
brg
@ 1
13'-2
" w/
2'-7
" tru
ss h
eel
3'-0" stem wall on existing10'-2" stud wall
top plate at 122'-0"
3'-0" stem wall on existing10'-2" stud wall
top plate at 122'-0"
3'-0
" ste
m w
all o
n ex
istin
g10
'-2" s
tud
wal
lto
p pl
ate
at 1
22'-0
"
3'-0
" ste
m w
all o
n ex
istin
g10
'-2" s
tud
wal
lto
p pl
ate
at 1
22'-0
"
3'-0" stem wall on existing10'-2" stud wall
top plate at 122'-0"
3'-0
" ste
m w
all o
n ex
istin
g10
'-2" s
tud
wal
lto
p pl
ate
at 1
23'-4
"
3'-0
" ste
m w
all o
n ex
istin
g10
'-2" s
tud
wal
lto
p pl
ate
at 1
23'-4
"
secureroof
access
daylight RD'sin wall face
daylight RD'sin wall face
daylight RD'sin wall face
cano
pySL
OPE
cano
pySL
OPE
1/4"+ per 12"SLOPE
awning struts(below)
awning struts(below)
awning struts(below)
canopySLOPE
canopySLOPE
metal coping 1top plate @
124'-8"
RTU-2 @ 8 ton(max)1,000 lbs
RTU-1 @ 8 ton(max.)1,000 lbs
RTU-3 @ 8 ton(max.)1,000 lbs
SCALE: 1/4" = 1'-0"01 Roof Plan A2.02