® DUAL Datasheet Double interlock Engineered system with Notifier NFS-320
1 of 14 FM-076D-0-16D
Optional
FireFlex® DUAL description
The FireFlex® DUAL integrated system consists of an integrated double interlock Electric/Pneumatic release preaction automatic sprinkler system combined with a clean agent fire extinguishing system, factory-assembled in a single cabinet. All the components necessary for both extinguishing systems are integrated. The FireFlex® DUAL is fully tested at factory. The FireFlex® DUAL System uses Engineered SEVO™ 1230 FORCE500™ Clean Agent Fire Suppression System for Class A, B and C fires. This clean extinguishing agent is based on sustainable technology and meets the most stringent actual and future environmental standards
Novec 1230 extinguishing agent description
Designed as per NFPA 2001, the extinguishing agent used in FireFlex® DUAL system is Dodecafluoro-2-methylpentan-3-one known as Novec 1230 Fire Protection Fluid (also known as FK-5-1-12, 3MTM NOVECTM 1230 Fire Protection Fluid, C6-F-ketone) produced by 3M.
Volumetric concentration varies from 4 - 6 % (not to exceed 10%)
Novec 1230 Fire Protection Fluid is a colorless fluid. It is stored as a pressurized liquid and injected into a room, area, or compartment that has the structural integrity to retain the agent that has been discharged. Novec 1230 is dispensed as an odorless, electrically non-conductive vapor. It leaves no residue.
Features
• FireFlex® DUAL system utilizes Novec 1230 extinguishing agent which is highly efficient for total flooding applications and a Preaction automatic sprinkler system.
• cULus Listed & FM Approved as an assembled unit • OSHPD certification pre-approval: OSP-0342-10 is
OPTIONAL
• ISO-9001 manufacturing and quality control procedures.
• Novec 1230 extinguishing agent has zero ozone depletion potential, an atmospheric lifetime of 0.014 year and a global warming potential of 1.
• No Observed Adverse Effect Level (NOAEL) of 10%.
• USA TSCA: product complies with chemical notification requirements. SNAP: approved for flooding (12/20/02) and streaming (1/23/03)
• Canada CDSL: product complies with chemical notification requirements
• Uses the Viking F1 Deluge Valves
• All trim piping is galvanized steel, Listed and Approved for 250 psi (1724 kPa) service maximum.
• Quick connections to water supply and drain on left side, and sprinkler riser on top of unit, available with grooved end or flanged fittings
• No open drain cups inside unit
• Separate unlocked access hatch to emergency manual release
® DUAL Datasheet Double interlock Engineered system with Notifier NFS-320
FM-076D-0-16D 2 of 14
System configurations
2” Double Interlock Preaction combined with single NOVEC cylinder, electric release 3” Double Interlock Preaction combined with single NOVEC cylinder, electric release
Size of cylinder (lbs) Cabinet width 40 76 164 322 601 850
36" 1 1 n/a n/a n/a n/a
46" n/a n/a 1 1 1 n/a
52" n/a n/a n/a n/a n/a 1
Sequence of operation
Automatic release 1. Actuation of a detector from one detection zone: a) “ZONE 1” (or “ZONE 2”) message appears on the
display. b) “FIRE ALARM” lamp flashes until acknowledged. c) "ALARM" audible devices activate. d) “ALARM” contacts activate. e) Preaction solenoid valve (F1) activates.
Note: Preaction piping network will not yet be filled with water.
2. Actuation of a detector from the other detection zone for crossed zones configuration):
a) “ZONE 2” (or "ZONE 1”) message appears on the display.
3. Discharge sequence occurs: a) “PRE-DISCHARGE” and "DISCHARGE" lamps
illuminate steady. b) “PRE-DISCHARGE NOVEC 1230” contacts activate. c) Pre-discharge delay starts (not exceeding 60 sec). d) "SECOND STAGE ALARM" audible devices activate.
Note: The abort station will prevent the NOVEC 1230 discharge as long as being maintained if activated during the pre-discharge delay.
4. After pre-discharge delay is completed: a) “PRE-DISCHARGE” lamp turns off. b) NOVEC 1230 electric actuator (C) activates. c) “DISCHARGE NOVEC 1230” contact activates. If NOVEC 1230 discharge switch option is selected: d) “DISCHARGE NOVEC” message appears on the
display. 5. After a preaction sprinkler head fuses: a) Deluge valve (A1) opens; water will flow into sprinkler
piping network and out of sprinklers and any openings on the system.
b) “WATERFLOW PREACTION” message appears on the display.
c) “WATERFLOW PREACTION” contact activates.
4.4.2 Manual release 1. Actuation of a manual release pull station within the
system: a) “MANUAL RELEASE” message appears on the
display. b) “FIRE ALARM” light flashes until acknowledged. c) "ALARM" audible devices activate. d) “ALARM” contacts activate. e) “PRE-DISCHARGE” and "DISCHARGE" lamps
illuminate steady. f) Preaction solenoid valve (F1) activates.
Note: Preaction piping network will not yet be filled with water.
g) “PRE-DISCHARGE NOVEC 1230” contacts activate. h) Pre-discharge delay starts (not exceeding 30 sec). i) "SECOND STAGE ALARM" audible devices activate. 2. After pre-discharge delay is completed: a) “PRE-DISCHARGE” lamp turns off. b) NOVEC 1230 electric actuator (C) activates. c) “DISCHARGE NOVEC 1230” contact activates. If NOVEC 1230 discharge switch option is selected: d) “DISCHARGE NOVEC” message appears on the
display. 3. After a preaction sprinkler head fuses: a) Deluge valve (A1) opens; water will flow into sprinkler
piping network and out of sprinklers and any openings on the system.
b) “WATERFLOW PREACTION” message appears on the display.
c) “WATERFLOW PREACTION” contact activates.
Note: At any time, if the optional mechanical activator (J) is activated, the NOVEC 1230 will be released.
At any time, if the emergency release valve (B10) is activated, the preaction piping network will be filled with water.
® DUAL Datasheet Double interlock Engineered system with Notifier NFS-320
3 of 14 FM-076D-0-16D
Standard equipment
Cabinet
The FireFlex® DUAL unit cabinet is made of sturdy 14 gauge steel. All surfaces are rust proof coated, inside and outside, with fire red, oven baked polyester powder on phosphate base. Cabinet is provided with one or two doors, all provided with a neoprene gasket to absorb vibrations. Electrical junction boxes are integrated inside the cabinet for connection of AC power, detection system, auxiliary contacts and signaling devices. Knockouts can be drilled by the installing contractor on-site. Cabinet doors are provided with hinges that can easily be disassembled on site to remove the door assemblies for servicing.
Control panel (Self-contained system only)
120 VAC / 60 Hz, 165VA. 220 VAC / 50 Hz, 185VA. 12VDC / 18Ah batteries. (factory installed) Single Zone detection
(Activated by Zone 1 or Zone 2) Crossed-Zone detection
(Activated by Zone 1 and Zone 2)
The release control panel integrated into the FireFlex® DUAL cabinet is Notifier's Model NFS-320. This panel includes two Class A or B, programmable detection zones; four Class B supervisory zones and four Class A or B, programmable output circuits. Programming of the control panel made by Fireflex System Inc and password protected. The panel is compatible with many types of fire alarm & supervisory devices such as linear heat detectors, spot-type heat and smoke detectors, water flow and release indicators, low and high air pressure switches, manual pull stations. The control panel also includes an alphanumeric display with 2 lines of 40 characters describing all the system conditions, as well as a set of red and yellow LED lamps individually indicating the alarm and trouble conditions of the system Easy to operate control buttons are also provided to activate and operate the system's various functions.
Standard SEVO SYSTEMS equipment
Agent storage cylinder
The agent storage cylinder by SEVO Systems is a steel pressure vessel manufactured, tested and stamped in accordance with DOT 4BW500 or DOT 4BA500, TC (Transport Canada). The agent storage cylinder is designed to hold the clean agent at a normal operating pressure of 500 psi (34.5 bar) at 70°F (21.1°C). The agent storage cylinders are suitable use at temperatures of 0°F (-17.8°C) to130°F (54.4°C). A rupture disc is connected to the cylinder body to serve as a pressure relief device to protect the cylinder against excessive internal pressure. The disc rupture point is in the range of 864 psi (59.5 bar) to 950 psi (65.5 bar) at 70°F (21.1°C).
Cylinder filling range
FireFlex® 1230 Cylinders Size Fill Capacity (lbs)
40 16 - 40
76 31 - 76
164 66 – 164
322 129 – 322
601 241 - 601
850 366 - 854
® DUAL Datasheet Double interlock Engineered system with Notifier NFS-320
FM-076D-0-16D 4 of 14
Standard SEVO SYSTEMS equipment (cont’d)
Discharge valve
The discharge valve is a Brass construction backpressure type valve. The piston in the valve bore is equipped with a copolymer seal that keeps the Novec 1230 under pressure within the cylinder. A small hole in the axis of the piston allows the cylinder pressure to equalize on both sides of the piston. Since the area at the top of the piston is greater than the area at the bottom of the piston, the net force seals the piston against the valve discharge outlet. When the cylinder pressure on the top of the piston is released by means of automatic or manual actuation, the cylinder pressure acting against the piston causes it to slide to its fully open position allowing agent discharge. The 40 lb and 76 lb cylinders are equipped with a 1” valve. The 164 lb cylinders are equipped with a 1 ¼” valve. The 322 lb. and 601 lb. cylinders are equipped with 2 ½” valves and the 850 lb cylinders are equipped with a 3” valve.
Electric actuator
The SEVO electrical actuator is mounted on the top plug of the cylinder valve. The 24 VDC electric actuator is required to discharge the system electrically from a releasing control panel. Power Requirements 24 Volts d.c. Current 0.2A at 24 Volt d.c.
WARNINGDO NOT INSTALL IF PLUNGER IS EXTENDED
+-
12
Nozzles
The Sevo® nozzles are designed to provide rapid and thorough vaporization and distribution of agent with the air in the protected space. Standard nozzles are made of aluminum. Engineered system nozzles are available in five pipe sizes, ½”, 1”, 1-½”, 2” and 2-½”, 180º and 360º discharge pattern. Each nozzle has a standard female pipe thread for attachment to discharge piping. Nozzle shall be spaced in accordance with the instructions in the “Engineered system design manual”. Each nozzle shall be marked with the Sevo® Systems part number.
1/2” @ 180º 1/2” @ 360º
1” @ 180º 1” @ 360º
1-1/2” @ 180º 1-1/2” @ 360º
2” @ 180º 2” @ 360º
2-1/2” @ 180º 2-1/2” @ 360º
The maximum nozzle height per layer of coverage is 16’-4”. Both 180º and 360º nozzles were tested for a maximum area coverage using a 32’ wide by 32’ long enclosure.
Pressure gauge integrated low pressure switch The pressure gauge integrated switch is a means for both visual and electronic monitoring of the pressure condition within the cylinder. Furthermore, the pressure gauge integrated switch eliminates the need for a separate pressure switch.
® DUAL Datasheet Double interlock Engineered system with Notifier NFS-320
5 of 14 FM-076D-0-16D
Standard SEVO SYSTEMS equipment (cont’d)
Liquid Level Indicator
The SEVO Liquid Level Indicator is a simple, manually operated device, which provides means to determine the fluid level in a vertically mounted cylinder. Use of this device allows for the content of fluid to be determined without removing cylinder from its bracketing and piping for weighing.
Provided and available only on 322, 601 & 850 Cyl.
1 in
Releasing circuit disable switch
The releasing circuit disable switch is used to disable the clean agent electrical actuator. When the key is set to “Disable”, the SEVO electrical actuator will be disconnected from the control panel’s releasing circuit, causing a trouble signal and preventing accidental discharge during maintenance or inspection.
Optional SEVO SYSTEMS equipment
Manual actuator (optional)
The manual actuator features a push lever that vents pressure through the top of the valve causing the piston to rise and allow for Novec 1230 to discharge through the valve outlet. The manual actuator also has the option to mount on top of the stackable electric actuator allowing electrical or manual system activation.
As per NFPA 2001 (2008 Edition), 4.3.3.5.1. A discharge pressure switch shall be required where mechanical system actuation is possible.
FM-076Z-0-2A
Discharge pressure switch (optional)
The discharge pressure switch is used to provide a means of detecting system activation. Upon activation of the cylinder valve, the discharge pressure switch contacts transfer to indicate discharge and/or to perform auxiliary functions required during system operation.
RED (+)WHITE (GROUND)
BLACK (-)
® DUAL Datasheet Double interlock Engineered system with Notifier NFS-320
FM-076D-0-16D 6 of 14
Standard Preaction equipment
Preaction valve
The Viking Model F-1 Deluge Valve is a quick-opening, differential diaphragm flood valve with one moving mechanism. The deluge valve is used to control water flow in preaction sprinkler systems. The valve is held closed by system water pressure trapped in the priming chamber, keeping the outlet chamber and system piping dry. In fire conditions, when the releasing system operates, pressure is released from the priming chamber. The deluge valve clapper opens to allow water to flow into the system
2” 3”
Preaction riser check valve
The Viking 2” spring loaded In-Line check valve is a general purpose rubber-faced check valve approved for use in fire-service systems. The Spring Loaded In-Line check valve is manufactured with a brass body, brass seat, and a rubber-faced clapper assembly. The Viking 3” Easy Riser® Swing check valve is a general purpose rubber-faced check valve approved for use in fire service systems. The valve is for use in preaction system risers.
2” 3”
Solenoid valve The high pressure solenoid valve is a two-way type with one inlet and one outlet. It is a packless, internal pilot operated valve, suitable for use in releasing water pressure from the priming chamber of Viking Deluge Valves. The solenoid valve has floating diaphragm construction, which requires a minimum pressure drop across the valve to operate properly.
IN OUT
Pneumatic actuator
Used in conjunction with the solenoid valve, the Viking Pneumatic Actuator is a spring loaded, rolling diaphragm and piston operated valve. It is used wherever a combination is required between the detection and system’s loss of air.
Low air supervisory switch
The low pressure switch monitors the pressure within the sprinkler piping should a loss of the air below 25 Psi occur. The pressure switch contacts transfer indicating supervisory signal.
POTTERPS40-1A
Alarm pressure switch
The alarm pressure switch monitors the water flow within the sprinkler piping. Should the Deluge Valve clapper opens to allow water to flow into the sprinkler piping. The alarm pressure switch will activate, indicating a water flow signal
POTTERPS10-1A
® DUAL Datasheet Double interlock Engineered system with Notifier NFS-320
7 of 14 FM-076D-0-16D
Preaction system - Air supply
Direct air compressor (Style “A”)
Used only for the sprinkler piping network of the preaction system. Air supply Style "A" includes the air compressor mounted inside the FIREFLEX® DUAL cabinet with its supervisory trim and options. Compressor is factory piped to the sprinkler piping system riser. It is available in three (3) sizes:
1/6HP 1/3HP 1/2HP All the above air compressors are oiless piston type without reservoir and have open, single phase motor with internal thermal protection and supply voltage of
120Vca, 60Hz 220Vca, 50Hz.
Compressor selection Table:
Compressor size
CFM @ 40 psi
120VAC System capacity to pump 40 psi in 30 minutes
220VAC System capacity to pump 40 psi in 30 minutes
1/6 HP 1.33 CFM 110 gallons 90 gallons
1/3 HP 2.61 CFM 215 gallons 170 gallons
1/2 HP 4.06 CFM 335 gallons 270 gallons
Compressor Amp rating
Compressor size Amp rating @ 120VAC, 60Hz
Amp rating @ 220VAC, 50/60Hz
1/6 HP 6.6 A 3.3 A
1/3 HP 6.6 A 3.3 A
1/2 HP 8 A 4 A
Air Pressure Maintenance Device (Style “B”)
Used only for the sprinkler piping network of preaction system, when an external air supply is provided by others (tank mounted compressor, plant air or dry nitrogen cylinders) and piped to the air inlet port of the unit. Air supply style "B" provides an Air Pressure Maintenance Device (APMD) trim, factory mounted in the FireFlex® DUAL cabinet.
Note: The external air supply must be restricted to insure that it cannot replace air as fast as it escapes when a releasing device or sprinkler operates.
® DUAL Datasheet Double interlock Engineered system with Notifier NFS-320
FM-076D-0-16D 8 of 14
Optional PREACTION equipment
Shut-off valve & sight glass (optional)
The Shut-off Valve & Sight Glass Option is intended to be used for applications where testing of the system operation without filling the sprinkler piping network is desirable and where it is critical that all functions of the preaction system be tested under actual discharge conditions.
Mainwater supplycontrol valve
Deluge valve
Shut-off valve
Riser check valve
Main drain valve
Sight glassassembly
Point flashlightHERE
FM-076Z-0-4B-1
Dehydrator (optional)
The Viking Dehydrator is a manually regenerated desiccant-type air dryer. The desiccant acts as a moisture indicator by changing color, and is visible through the required bowl guard and transparent plastic bowl.
FM-061H-0-124A
From Air Supply
To Air Option B Trim
E14
Canister Body
DessiccantSight Glass
B13
E12
2TO DRAIN COLLECTOR
To Air Option A Trim
From Air Supply
Canister Body
DessiccantSight Glass
Semi-flanged inlet / outlet (optional) When required by the user, FireFlex® DUAL units can be provided in a semi-flanged configuration. The semi flanged option provides flanged fittings only on the water inlet pipe (left side) and on the system riser outlet. The drain manifold is provided with a threaded connection (left side). The rest of the fittings are the same as usual with the main components being provided in the standard flanged / grooved configuration.
® DUAL Datasheet Double interlock Engineered system with Notifier NFS-320
9 of 14 FM-076D-0-16D
Details & field wiring diagrams
Cabinet with main components, shown without door(s)
FM-076Z-0-5C-5
Agent storage cylinder
Air compressor
Junction boxTBA, TBB & TBC
Air compressorIsolation switch
Water inlet
Drain outlet
Preaction assembly
Preaction outlet
Clean agent outlet
Releasing circuitdisable switch
Control panel
® DUAL Datasheet Double interlock Engineered system with Notifier NFS-320
FM-076D-0-16D 10 of 14
Wiring diagram
HEAT DETECTOR
SMOKE DETECTOR
PULL STATION DRY CONTACT
END OF LINE RESISTOR
SOLENOID VALVE
!
Cable size: 14AWG min with 600V isolation
LEGEND
12
34
TBA
56
7
89
10
1112
13
14151617
-
+2.2K1/2W
-
+
-
+2.2K1/2W
-
+
NAC1ALARM
NAC2SECOND STAGEALARM
ALARM
CNO
NC
TROUBLE
CNO
NC
SUPERVISORY
CNO
NC
+-
DATA LOOP
+-
24VDC RESETTABLE
BELL OR HORN
ABORTNOVEC 1230
MANUALRELEASE
47K1/4W
47K1/4W
XP10-MA
XP6-MA
DETECTIONZONE 2
DETECTIONZONE 1
3.9K1/4W
3.9K1/4W
PRE-DISCHARGENOVEC 1230
PRE-DISCHARGENOVEC 1230
WATER FLOWPREACTION
DISCHARGENOVEC 1230
ALARM
ALARM
XP6-RA
AC POWER SOURCE INPUTSCONTROL PANEL
[email protected]@220VAC
SILENCEABLEAUDIBLE DEVICES
Two (2) circuits are required.Control panel shall have a dedicated circuit breaker.
COMPRESSOR120/220VAC1/2 HP MAX UNUSED
CIRCUIT3.9K1/4W
1 2 3 4
TBB
5 6
LIN
E (L
1)
GR
OU
ND
NEU
TRAL
LIN
E (L
2)N
EUTR
AL
FM-061H-0-67B
GR
OU
ND120VAC, 60 Hz
220VAC, 50/60 Hz
CLASS B DETECTION XP6-MA
DETECTIONZONE 2
DETECTIONZONE 1
WITH A/B SELECTEDCLASS A DETECTIONWITH A/B UNSELECTED
UNUSEDCIRCUIT
Power limited (supervised) initiating device circuits
Detection Zone 1 and 2 (Class A or B) End of line resistor: 3.9KΩ, ¼W Loop resistance: 25Ω max. Leave EOL device (provided) on all unused circuits. Refer to the NFS-320 control panel manual for smoke detector compatibility.
Power limited (supervised) initiating device circuits Abort and Manual release circuits (Class B) End of line: 47KΩ, ¼W Max. loop resistance: 50Ω Leave EOL (provided) on all unused circuits. For dry contact supervisory devices only
Auxiliary relay contacts Rated 2A, 30VDC resistive Rated 1A, 30VDC (0.6pF) inductive Rated 0.5A, 125VCA (0.35pF) pilot duty
Power limited (supervised) notification appliance circuits NAC Circuit 1 and 2 (Class B) End of line resistor: 2.2KΩ, ½W Nominal operating voltage: 24VDC regulated Maximum wiring voltage drop into alarm: 1.2V Maximum usable current per circuit: 1.5A Maximum total current (including 24VDC): 3A Polarity is reversed in supervisory condition. Leave EOL device (provided) on all unused circuits. Refer to the NFS-320 control panel manual for device compatibility.
Auxiliary Power 24Vdc Regulated Source Nominal voltage: 24VDC, 176mVrms ripple Maximum available current: 1.25A for resettable 4 wires smoke detectors
® DUAL Datasheet Double interlock Engineered system with Notifier NFS-320
11 of 14 FM-076D-0-16D
Cabinet The FIREFLEX® DUAL cabinet is made of sturdy 14 gauge steel. Refer to table 8.1 and figure 8.2 for dimensions. All surfaces are rust proof coated, inside and outside, with fire red, oven baked polyester powder on phosphate base. Cabinet is provided with two doors, all provided with a neoprene gasket to avoid vibrations, giving the access to the pressure gauges reading and the manual emergency release. Cabinet doors are provided with hinges that can easily be disassembled on site to remove the door assemblies for installation and servicing. The cabinet assembly is pre-assembled, pre-wired, and factory tested under ISO-9001 conditions. Refer to tables 8.2 & 8.3 and figures 8.3 & 8.4 for installation and clearances details. Electrical junction boxes are integrated inside the cabinet for connection of detection system, auxiliary contacts and signaling devices. Knockouts can be drilled by the installing contractor on-site but must adhere to the restrictions indicated on figure 8.1.
Figure 8.1 - Drilling details
7½"Drilling zone
4½"
10½"
5"TBB
TBA&
LOWVOLT.
Top of Cabinet
FM-061H-0-66A-4
® DUAL Datasheet Double interlock Engineered system with Notifier NFS-320
FM-076D-0-16D 12 of 14
Table 8.1 - Cabinet dimensions
Size A B C D E F G 36" 35¾" 25" 77⅛" 39¾" 15" 37¾" 12¾"46" 46" 25" 77⅛" 50" 15" 48" 23" 52" 52" 31" 81" 56" 21" 54" 26"
Table 8.2 - Preaction piping installation
H J K L M N1 N2 O P Q 2" 11½" 8" 5" 9¾" 45" 48⅞" 4" 11½" 3½"
3" 11½" 9" 4" 9½" 45" 48⅞" 4" 12¾" 3"
Notes: 1. N1 refers to 36" or 46" cabinet. N2 refers to 52" cabinet. 2. Dimensions may slightly differ from real unit.
Table 8.3 - NOVEC 1230 piping installation
Lbs R S T U 40 1" 2¾" 6" 3¼"
76 1¼" 2¾" 6" 3¼"
164 1½" 2¾" 6" 1¾"
322 2" 6¾" 6" 4¾"
601 2½" 6½" 6" 3¾"
850 3" 9" 7" 5"
Note: Dimensions may slightly differ from real unit. Figure 2 - Cabinet dimensions
® DUAL Datasheet Double interlock Engineered system with Notifier NFS-320
13 of 14 FM-076D-0-16D
BA
C
D
M
S
Q
R Ø
L
FM-061H-1-49B-1
J
K
O
P
H Ø
2"Ø
U
N
T
J
Figure 3 - Floor anchoring template
FM-061H-1-49B-6
5''
E
G
Ø3/4"
F
Figure 4 - Required clearance
FM-061H-1-49B-7
12''MIN
12''MIN
22''MIN