ds70pg

Embed Size (px)

Citation preview

  • 8/9/2019 ds70pg

    1/2

  • 8/9/2019 ds70pg

    2/2

    Solar Turbines IncorporatedP.O. Box 85376San Diego, CA 92186-5376

    FOR MORE INFORMATIONTelephone: (+1) 619-544-5352

    Telefax: (+1) 858-694-6715

    E-mail: [email protected]

    Internet: www.solarturbines.com

    Caterpillar is a trademark of Caterpillar Inc.

    Solar, Taurus, SoLoNOx  , and Turbotronic  are trademarks of Solar Turbines Incorporated.

    Specications subject to change without notice. Printed in U.S.A.

    © 2009 Solar Turbines Incorporated. All rights reserved.DS70PG/1109/EO

    Typical Service Connections

    Performance Available Power

    Steam (Unred) 15.6 tonnes/hr(34,400 lb/hr)

    Steam (Fired) 71.9 tonnes/hr(158,600 lb/hr)

    Chilling (Absorption) 3.47 Refrigeration Tons

    Nominal rating – per ISO At 15°C (59°F), sea level 

    No inlet/exhaust losses

    Relative humidity 60%

    Natural gas fuel withLHV = 35 MJ/nm3

     (940 Btu/scf)

    No accessory losses

    Engine efciency: 33.8% (measured at generator terminals)

    10,500

    9,000

    7,500

    6,000

    4,500

    12.0

    (11,370)

    11.5

    (10,900)

    11.0

    (10,430)

    10.5

    (9950)

    10.0

    (9480)-30.0

    (-22)

    -15.0

    (5)

    0.0

    (32)

    15.0

    (59)

    30.0

    (86)

    DS70GS-002MINLET AIR TEMPERATURE, °C (°F)

       H   E   A   T

       R   A   T   E ,

       M   J   /   k   W  e  -   h  r   (   B   t  u   /   k   W  e  -   h  r   )

       O   U   T   P   U   T   P   O   W   E   R ,

       k   W  e

    45.0

    (113)

    Output Power 

    Heat Rate

    Output Power 7520 kWe

    Heat Rate 10 650 kJ/kWe-hr

    (10,100 Btu/kWe-hr)

    Exhaust Flow 97 000 kg/hr

    (213,840 lb/hr)

    Exhaust Temp. 485°C

    (905°F)

    Package Dimensions Forward End• Turbine Control Box

    • Generator: Control Box, Terminal Box

    • Generator Drip Pan Drain

    • Package Ground Aft End• Drains: Air Inlet Duct, Combustor,

    Exhaust Diffuser 

    • Fuel: Inlet, Filter, Drain, Vent

    • Package Auxiliary Air Supply

    • Turbine Cleaning

    • Turbine Drip Pan Drain

    Left Side• Lube Oil Cooler: Drain, Vent

    • Lube Oil Tank Drain

    • AC Power: Start Motor, Pre/Post

    Lube Pump, Lube Oil Tank Heater,and Liquid Fuel Pump (for LiquidFuel Packages)

    • DC Power: Backup Lube Pump

    Right Side• Lube Oil Tank Vent

     Application Performance

    F 1 6F 1 5F 1 4F1 3F1 2F 11F 10F 9

    F 8F 7F 6F 5F 4F 3F 2F 1

    7 8 9

    4 5 6

    1 2 3

    . 0 -

    1 05 6 7 8 9

    1 2 3

    1 61 1 1 2 1 3 1 4 1 5

    2 21 7 1 8 1 9 2 0 2 1

    4

    2 82 3 2 4 2 5 2 6 2 7

    Length: 11.9 m (39' 0")

    Width: 2.9 m (9' 7")

    Height: 3.7 m (12' 1")

    Typical Weight: 62 935 kg (138,775 lb)

    Power Generation

    TAURUS 70Gas Turbine Generator Set