10
DPR 180 180 MM Digital Strip Chart Recorder Specifications 43-DR-03-11 March 2010 Overview The DPR180 recorder offers the best price/performance in the market today of any 180mm (7 inch) wide chart recorder. The recorder is able to monitor up to 24 analogue inputs and up to 36 digital inputs. It produces clear, fully documented charts at any speed, and in different formats, providing the best, most flexible presentation of the process data. The large, bright display, with fluorescent chart illumination, provides easy viewing of the data and chart. The flexible product configuration in 5 languages makes it easy to set up and use. The DPR180 is especially suited to match the needs of chemical, pharmaceutical, power generation, metals processing, environmental monitoring, and other applications where the best chart resolution is required. Main Features 180 mm (7 inch) chart width. 0.05% accuracy full scale. Applicable on a wide choice of actuations and ranges. Each input span is adjustable within the selected range, with up to 2 ranges per input. Universal (T/C, RTD, mV, mA, V), or linear input (mV, mA, V). Fast input scanning (20/sec.) Fluorescent display of 2 row of 16 digits, with adjustable brightness. Roll or fan fold chart with same cassette. Fully documented chart with trace color assign, thin/thick trace, alarm in red tagging, zooming, zoning, trend, tabular, messages. Channel groups available. I/O capability : up to 24 analogue inputs, up to 36 output relays, up to 36 digital inputs, up to 8 retransmitted signals. Advanced math package Fully configurable through the front keys, front PC jack or communication link. 2 chart speeds configurable from 1 to 5000 mm/h (0.04 to 200 inch/hr). Up to 48 customer messages of 50 characters each. Firmware upgradable by PC (Flash memory). Input calibration traceable per channel, or channel group. Up to 2 custom-input characterizations available. Up to 48 alarm set points freely assignable on analogue inputs, maths, communication. Up to 36 internal output relays assignable on analogue inputs, maths, events, logic inputs. Configurable Periodic chart documentation. Periodic report. Universal power supply: 100 to 240 Vac/dc. Up to 8 retransmitting outputs (4 to 20 mA). Universal comm. output: ASCII in RS232, 422/485. MODBUS RTU in RS422/485. ETHERNET/MODBUS RTU Interface, Metal door/case, IP55 rated

DPR 180 180 MM Digital Strip Chart Recorder Specificationseneric.net/Honeywell/Technical-data/DPR180.pdf · 180 MM Digital Strip Chart Recorder Specifications ... CH07 2350 °C BURNER

  • Upload
    lykhanh

  • View
    217

  • Download
    0

Embed Size (px)

Citation preview

DPR 180 180 MM Digital Strip Chart Recorder Specifications 43-DR-03-11 March 2010

Overview The DPR180 recorder offers the best price/performance in

the market today of any 180mm (7 inch) wide chart

recorder. The recorder is able to monitor up to 24 analogue

inputs and up to 36 digital inputs.

It produces clear, fully documented charts at any speed,

and in different formats, providing the best, most flexible

presentation of the process data. The large, bright display,

with fluorescent chart illumination, provides easy viewing of

the data and chart. The flexible product configuration in 5

languages makes it easy to set up and use.

The DPR180 is especially suited to match the needs of

chemical, pharmaceutical, power generation, metals

processing, environmental monitoring, and other

applications where the best chart resolution is required.

Main Features

180 mm (7 inch) chart width.

0.05% accuracy full scale. Applicable on a wide

choice of actuations and ranges.

Each input span is adjustable within the selected

range, with up to 2 ranges per input.

Universal (T/C, RTD, mV, mA, V), or linear input

(mV, mA, V).

Fast input scanning (20/sec.)

Fluorescent display of 2 row of 16 digits, with

adjustable brightness.

Roll or fan fold chart with same cassette. Fully

documented chart with trace color assign,

thin/thick trace, alarm in red tagging, zooming,

zoning, trend, tabular, messages.

Channel groups available.

I/O capability : up to 24 analogue inputs, up to 36

output relays, up to 36 digital inputs, up to 8

retransmitted signals.

Advanced math package

Fully configurable through the front keys, front PC

jack or communication link.

2 chart speeds configurable from 1 to 5000 mm/h

(0.04 to 200 inch/hr).

Up to 48 customer messages of 50 characters

each.

Firmware upgradable by PC (Flash memory).

Input calibration traceable per channel, or channel

group.

Up to 2 custom-input characterizations available.

Up to 48 alarm set points freely assignable on

analogue inputs, maths, communication.

Up to 36 internal output relays assignable on

analogue inputs, maths, events, logic inputs.

Configurable Periodic chart documentation.

Periodic report.

Universal power supply: 100 to 240 Vac/dc.

Up to 8 retransmitting outputs (4 to 20 mA).

Universal comm. output: ASCII in RS232, 422/485.

MODBUS RTU in RS422/485.

ETHERNET/MODBUS RTU Interface,

Metal door/case, IP55 rated

HFS Catalog_Without Tab_HighRes.pdf 846 6/8/2011 12:41:40 PM

DPR 180 MM Digital Strip Chart Recorder 2

Clear and Fully Documented Chart – DPR180

Trend printing mode

The trend printing mode offers a highly flexible documentation which includes : Date and Time, Alarm reporting with : Time,

Alarm SP, Channel #, Set Point value, Alarm, Chart certification, Chart Speed with engineering unit , User defined message,

Range subdivision, Recorder identification, Red on alarm, Chart range, Channel reference with tag name (Configurable),

Thick channel trace, Process value, Channel tag name, Zone format, Channel reference, Engineering Unit, Tabular print out.

Tabular Printing Mode

_ 20.30 15 SEP 97 100 mm / h # 05

_ 20.35 AL01 (AN01) SP 100.0 ^ ON ADJUST OIL TEMPERATURE

0.000 400.0 800.0 1200 1600 2000(03) Furnace DEG C

21.00 15 SEP 97

CH11 30.23 RpmCH06 150.8 m3 / hCH01 70.20 °C

CH12 15.24 BAR CH07 2.350 °C CH02 45.89 mV

CH13 50.36 L/mn CH08 560.8 Rpm CH 03 12.66 Ohm

DI 01= OFF DI 02 = ON

21.15 DI02 = ON

0 (08) MOTOR K Rpm 2000

-100 0 100 (04) Pressure Psi 200 300 400

WATCH OIL PRESSURE_ 21.46 AL02 (04) SP 230.0 ^ ON

_ 22.00 15 SEP 97 GROUP A 100 mm / h # 05

_ 20.55 AL01 ( AN01) SP 100.0 ^ OFF

1 Heater

8 Motor B

2 Transmit

14

DI01= OFF DI02 = ON CH07 2350 °C BURNER CH08 560.0 Rpm MOTOR B CH09 127.3 Wh POWERCH04 258.1 PSI PRESSURE CH05 2358 °K FURNACE CH06 150.8 M3 / h FLOWCH01 70.20 °C HEATER CH02 45.90 mV TRANSMIT CH03 12.70 OHM COIL23.50 15 SEP 97

DI01= OFF DI02 = OFFCH07 2350 °C BURNER CH08 560.0 Rpm MOTOR B CH09 127.3 Wh POWERCH04 258.1 PSI PRESSURE CH05 2358 °K FURNACE CH06 150.8 M3 / h FLOWCH01 70.20 °C HEATER CH02 45.90 mV TRANSMIT CH03 12.70 OHM COIL23.40 15 SEP 97

DI01= OFF DI02 = ON CH07 2350 °C BURNER CH08 560.0 Rpm MOTOR B CH09 127.3 Wh POWERCH04 258.1 PSI PRESSURE CH05 2358 °K FURNACE CH06 150.8 M3 / h FLOWCH01 70.20 °C HEATER CH02 45.90 mV TRANSMIT CH03 12.70 OHM COIL23.30 15 SEP 97

HFS Catalog_Without Tab_HighRes.pdf 847 6/8/2011 12:41:40 PM

DPR 180 MM Digital Strip Chart Recorder 3

Rugged, Simple and Modular Construction - DPR180

Easy to install easy to use easy to maintain:

The DPR180 with its modular design and rugged

construction, simplifies maintenance. Many of

the electronic assemblies and mechanical parts

are common with the DPR250 thus reducing

spare parts inventory. Its operator - friendly

configuration keys, the sophisticated display,

easy product configuration and customized

charts insure accurate monitoring and recording

of the process.

Easy access: the access to the chart, and the

ink cartridge is very easy. The simple, modular

construction of plug-in modules, along with the

low cost and extra long life of consumables,

further reduces the maintenance cost.

Universal power supply module: the universal

switching mode power supply simplifies

installation of the recorder by accepting voltages

from 100 to 230 V ac/dc, 50/60 Hz.

Local configuration: A user friendly rogram

with local language prompts (English, French,

German, Italian or Spanish) permits full

configuration of the recorder using the front

keys. A multilevel password protects against

unauthorized changes of product configuration.

Digital Display: The Vacuum fluorescent dot

matrix display is 2 lines of 16 digits, 8.5 mm

(0.33”) high. This allows for display flexibility and

provides clear operator information. Display

illumination is configurable to allow for improved

viewing based on customer requirements.

Chart illumination: The chart illumination

makes traces and current printed values

immediately visible, even from a distance and in

any ambient light condition.

Two paper types: Either chart roll or fan fold

paper can be installed into the common chart

cassette. The large capacity cassette holds 35

meters (115ft) of chart paper, reducing the

maintenance time required between chart

changes. Uses the same ink cartridge as the

DPR250, thus providing for common

consumables.

Cassette for roll or fan fold chart

Alarm/digital boards

Power supply

Mother Board

Ink Cartridge

Case

Chassis

Input boards

Terminals

Door

MMI Configuration keys

PC Configuration

Jack

PC configuration: By using the front communication jack,

the recorder can be configured from a personal computer,

using an optional PC interface module. In addition to

configuration, the PC interface provides the ability to upload,

download, modify, store the recorder configuration and

initiate service diagnostics as well as being able to upgrade

the recorder’s product firmware. The PC Configuration

software allows the creation of a custom characterization of

up to 50 points for special ranges.

HFS Catalog_Without Tab_HighRes.pdf 848 6/8/2011 12:41:40 PM

DPR 180 MM Digital Strip Chart Recorder 4

DPR 180 Functional Specifications Technical Data – DPR180

Technology Microprocessor-based (32 bits), with non volatile memory.

Flash memory for product software upgrade, or specials, via the front jack.

Analogue inputs

No. of inputs From 4 up to 24 in groups of 4.

Input boards 2 types : 4 linear inputs per board : mV, V, mA

4 universal inputs per board : mV, V, mA, T/C, RTD, Ohms

Signal source Thermocouple with cold junction compensation, or with remote compensation temperature configurable between 0 to 80ºC (32 to 176ºF)

Line resistance up to 1000 Ohms for T/C, mV, mA, V

RTD Pt100 Ohms, 3 wire connections, 40 Ohms balanced max.

Basic math functions

Square root extraction or channel differential are standard.

Filter Digital filter configurable per input from 0 to 99 sec.

Field calibration Channel calibration 0 to 100% span (or calibration of a group of identical channels) can be made to certify sensor loop.

Burnout T/C, mV, V (except following ranges) configurable to upscale, downscale or none

Volt : -500, 0, 500 mV ; -1, 0, 1V ; -2, 0, 2V; -5, 0, 5V ; 0, 10V ; -10, 0, 10V :

Inherent to Zero volts.

RTD: inherent upscale ; mA : inherent downscale.

Scanning time 2 channels = 105 msec, 4 ch = 210 msec, 8 ch = 420 msec, 12 ch = 630 msec, 16 ch = 840 msec, 20 ch = 1 sec, 24 ch = 1.2 sec

Input impedance 10 MOhms for T/C and mV inputs; > 1 MOhm for V input

Stray rejection Series mode > 60 dB. Common mode at 120 Vac > 130 dB

Display Fluorescent display

2 rows of 16 digits, 8.5 mm (.33 inch) high, matrix display.

Can display 1 or 2 PV values (5 digits) per line, engineering units (5 digits), alarm status, tag name, math, speed, event messages etc.

Brightness The display brightness is configurable

Record Chart 180 mm (7.09”) width

Traces Up to 24 traces, configurable in 6 colors, thin or thick traces, plus digital traces

Trace assignment Traces are configurable on analogue inputs, math, communication or digital inputs

Scaling Per input, up to 2 analogue scales can be configured to be printed on the chart, with engineering units, channel reference and tag name. Each input can be configured independently. The scale can be linear, with up to 10 sub-divisions

Print mode Trend: Up to 24 traces, with periodic chart documentation configurable in time, from 1 minute to 24 hours with date, time, scales, digital PV print-out over traces or on blank paper, with channel reference, digital traces, alarm messages and customer message.

Tabular: Tabular print-out configurable in time from 1 to 1440 minutes with channel number, tag name, digital PV value, engineering unit, alarm status.

Zoning Each input can be scaled between 0 to 100% of the chart (minimum zone = 20%).

Printing group Up to 2 groups of channels can be defined, with printing selection by :

Alarm, logic inputs or keypad

Pen carriage speed

1.4 second full scale

HFS Catalog_Without Tab_HighRes.pdf 849 6/8/2011 12:41:41 PM

DPR 180 MM Digital Strip Chart Recorder 5

Technical Data – DPR180

Chart length Roll or fan fold chart 35 meters (115 ft)

Chart speed 1 or 2 chart speed, fully configurable, selected by : Logic input, alarm communication, front key.

Speed setting Speeds 1 and 2 are configurable from 1 up to 5000 mm/hr (0.04 to 200 in/hr)

Resolution Chart resolution is 0.19 mm (0.0075”)

Product configuration

Access The configuration can be accessed using front keys, PC configurator, or ASCII communication with LPCS software.

Protection 2 password levels protect the unit configuration from unauthorized access. Level 1 = limited access, Level 2 = full protection.

Front keyboard Configurable and alphanumeric keys allow the operator to change the recorder operation

PC configuration Through the front jack, the unit can be configured from a PC using a Honeywell PC interface. This provides the facility to copy the product configuration, modify, store, download or upload the configuration, access service diagnostics, and also to upgrade the recorder firmware.

Logic inputs (optional)

Number of inputs Up to 36 input contacts, organized in groups of 6 contacts per card

Dry contacts (5 mA - 5 Vdc)

Actions Change speed 1 to speed 2, tab interval 1 to 2, digital print-out, print message, print inhibit, event traces, print math calculations.

Change range, start/stop math operations

Change print group, actuate a relay output

Up to 20 event traces are configurable in color and position from 0 to 100% of the chart

Alarms Set points Up to 48 set points, freely assignable to analogue inputs, math or communication.

Alarm type High, low, change rate low, change rate high, change rate high-low or deviation with configurable alarm occurrence.

Actions Can trigger a message, print channel in red in alarm, print in alarm, change the range, change the speed/tabular, print digital PV's

Start/stop the math, select the print group, actuate a relay output

Relay output (optional)

Up to 36 internal relays: 2 A, 250 Vac on resistive load.

1 SPST contact output, normally closed contact (NC), configurable to normally open (NO). Configurable alarm relay acknowledgement.

Alarm event The recorder can be configured to display events such as : 1 alarm, 1 channel in burnout, paper out, battery fail, communication interrupted

Alphanumeric documentation

Messages Up to 48 freely assignable messages of 50 characters each

Can be printed with or without date and time over the traces, by alarms, logic inputs, communication, when alarm is ON, OFF or ON/OFF.

Process Values Periodic digital print-out at time intervals configurable from 1 minute to 24 hours or through alarms, digital inputs, communication.

Tag name Each channel can have up to an 8 character name

Chart scales each can be configured from 0 to 9 subdivisions

Periodic reports startup time and period configurable

Min, Max, average of selected channels or (math computation) are printed in alphanumeric. Report size max. = 20 lines.

HFS Catalog_Without Tab_HighRes.pdf 850 6/8/2011 12:41:41 PM

DPR 180 MM Digital Strip Chart Recorder 6

User-Defined Actuations

Up to 50 breakpoints can be used to define a custom range/actuation. Up to 2 ranges can be defined using the PC Configurator.

Polynomial characterization available as special.

Mathematic package (optional)

Many functions are available such as: Basic math, SqRt, Fo, mass flow totalization, energy consumption, averages, timers, min., max., carbon potential, alarm/logic pulse totalization, RH.

The calculations are stored during power interruption.

Actions The results can be recorded as a trace, a tabular print-out, a periodic report, sent to the communication link, or used to generate a current output signal

Communication

(optional)

Protocols ASCII in RS232, 422/485. MODBUS RTU in RS422/485. ETHERNET/MODBUS RTU Interface,

Interface configured with standard IP address and is utilized with 3rd party software that provides TCP/Modbus driver and OPC capability.

PCMCIA

(optional)

Actions Archiving of PV traces, alarms and events with file names, file size is 24Mbytes max. Logging time selectable from 1 second up to 30 minutes.

PC Analysis TrendManager Pro provides an easy and powerful way to analyze trend, alarm and event files as well as to export them in spreadsheet format (CSV).

Retransmitting signals (optional)

Current output Up to 8 signals, 4 to 20 mA dc, can be generated by the recorder

(Organized in blocks of 4 output signals)

Max. Line impedance = 800 Ohms

These can be configured for: analogue traces, math calculations, PV's from the communication link. The zero and span are configurable.

Clock timer Format Year, month, hour, minute can be set

Power interruption

Battery backed (10 years time, 3 years power off)

Accuracy 10-5 at reference conditions

Power supply 100 to 230 Vac/dc, (24 Vac/dc on request). Consumption = 100 VA max

Packaging Weight 18 Kg max. (38 lbs)

Front bezel 310 x 317 mm (12.2 x 12.5 inches)

Panel cutout 278 x 278 mm (10.9 x 10.9 inches)

Depth 320 mm (12.6 inch) including the rear cover

Front protection IP55

Lock Latch, optional key DIN 43832-N

Door Die cast aluminum : Dark gray or black (optional), door opens to 180º

Mounting Panel mounting 30º from the horizontal

Wiring Screw terminals : Terminal blocks plug on to the boards at the back of the recorder

HFS Catalog_Without Tab_HighRes.pdf 851 6/8/2011 12:41:41 PM

DPR 180 MM Digital Strip Chart Recorder 7

Noise immunity This product is in conformity with the protection requirements of the following European Council Directives:

73/23/EEC, the Low Voltage Directive and 89/336/EEC, the EMC Directive. Conformity of this product with any other “CE Mark” Directive(s) shall not be assumed.

EMC Classification: EN 50081-2-1993 Electromagnetic Compatibility – General Emission Standard, Part 2: Industrial Environment.

EN 50082-2-1995 Electromagnetic Compatibility – General Immunity Standard, Part 2:Industrial Environment.

Safety protection

Complies with EN61010-1 and UL 3121 for process control instrumentation. Pollution Degree 2. Installation Category II

Electrical insulation

Input/input

Input/logic/grd alarm relay/grd

Input/line;

Line/grd;

Cur output/grd

Continuous operation at 280 Vac or 400 Vdc (except for RTD)

Test voltage 2.1 kV dc for 1 minute

Test voltage 3,25kV dc for 1 minute

Test voltage 3,25kV dc for 1 minute

Test voltage 3,25kV dc for 1 minute

Test voltage 3,25kV dc for 1 minute

Test voltage 500 Vdc for 1 minute

Temperature Ambient 0 to 50ºC (32 to 132ºF), 0 to 40ºC (32 to 104ºF) for fan fold paper

Storage -40 to 70ºC (-40 to 160ºF)

Humidity Roll chart 10 to 90% RH non-condensing

Fan fold 15 to 80% RH non-condensing

Vibrations

Accuracy

Frequency 10 to 60 Hz, amplitude 0.07 mm, 60 to150 Hz acceleration1g

Reference conditions

Temperature = 23ºC 2ºC (73ºF 3ºF)

Humidity = 65% RH 5%

Line voltage = Nominal 1%

Source resistance = 0 Ohm

Series mode and common mode = 0 V

Frequency = Nominal 1%

Accuracy Field calibration accuracy 0.05% of the selected range (IEC 873),

Chart resolution: 0.18 mm (0.007”).

Cold junction accuracy : 0.5ºC (32.9ºF)

Rated limits

and associated drifts

Parameters Rated limits Influence on accuracy

Temperature 0 to 50ºC (32 to 120ºF) 0.15% per 10ºC (50ºF ) of change (note A) Cold junction 0.3ºC/10ºC (32.5ºF /50ºF)

Supply voltage 85 to 250 V No influence

Source resistance

T/C, mV 6 V per 400 Ohms of line resistance max. = 1000 Ohms.

RTD 0.1ºC (33.8ºF) per Ohm in each wire balanced leads. 40 Ohms max. (From 0 to 400 ºC (32 to 752ºF)

Humidity 10 to 90% RH at 25ºC 0.1% max

Long-term stability

0.1% per year

HFS Catalog_Without Tab_HighRes.pdf 852 6/8/2011 12:41:41 PM

DPR 180 MM Digital Strip Chart Recorder 8

Available Ranges DP4180

Linear RTD/Ohms Thermocouples

mV

0 to 10 mV -10, 0, +10 mV 0, 20 mV -20, 0, +20 mV 0, 50 mV -50, 0, +50mV 10, 50 mV 0, 100 mV -100, 0,+100mV 0, 500 mV -500, 0, +500mV

Pt 100 at 0ºC

-50, 0, 150ºC -58, 0, 302ºF 0, 100ºC** 32, 212ºF** 0, 200ºC 32, 392ºF 0, 400ºC 32, 752ºF -200, 0, 800ºC -328, 0, 1472ºF

J I S

-50, 0, 150ºC -58, 0, 302ºF 0, 100ºC** 32, 212ºF** 0, 200ºC 32, 392ºF 0, 400ºC 32, 752ºF -200, 0, 500ºC -328, 0, 932ºF

J -50, 0, 150ºC J -58, 0, 302ºF J 0, 400ºC J 32, 752ºF J -200, 0, 870ºC J -328, 0, 1598ºF

S 0, 1600ºC S 32, 2912ºF S -20, 0, 1760ºC S -4, 0, 3200ºF

U -50, 0, 150ºC U -58, 0, 302ºF U 0, 150ºC U 32, 302ºF U 50, 150ºC U 122, 302ºF U -200, 0, 400ºC U -328, 0, 752ºF

N 0, 400ºC N 32, 752ºF N 0, 800ºC N 32, 1472ºF N 0, 1200ºC N 32, 2192ºF N -200, 0, 1300ºC N -328, 0, 2372ºF

L -50, 0, 150ºC L -58, 0, 302ºF L 0, 400ºC L 32, 752ºF L -200, 0, 870ºC L -328, 0, 1598ºF

NiMo 0, 1400ºC NiMo 32, 2552ºF MoCo 0, 1400ºC MoCo 32, 2552ºF

Volt 0, 1 V 0, 2 V -2, 0, +2V 0, 5 V -5, 0, +5 V 1,5 V 0, 10 V -10, 0, +10 V

Ni 50 ohms Ref. range

-80, 0, 320ºC -112, 0, 608ºF

0, 320ºC 32, 608ºF

K 0, 400ºC K 32, 752ºF K 0, 800ºC K 32, 1472ºF K 0, 1200ºC K 32, 2192ºF K -200, 0, 1370ºC K-328, 0, 2498ºF

T -50, 0, 150ºC T -58, 0, 302ºF T 0, 150ºC T 32, 302ºF T 50, 150ºC T 122, 302ºF T -200, 0, 400ºC T -328, 0, 752ºF

W-W26-20, 0, 2320ºC -4, 0, 4208ºF

Ref. range400, 2300ºC 750, 4200ºF

Ni 508 ohms

-80, 0, 150ºC -112, 0, 302ºF

W5-W26-20, 0, 2320ºC -4, 0, 4208ºF

Ref. range 400, 2300ºC 750, 4200ºF

Cu 10 Ohms

-20, 0, 250ºC** -4, 0, 482ºF

PR 20-400, 1800ºC 32, 3272ºF

Ref. range 600, 1800ºC 1110, 3300ºF

mA

0, 20 mA 4, 20 mA

Ohms

0, 200 ohms 0, 2000 ohms

R -20, 0, 1760ºC R -4, 0, 3200ºF

Ref. range 400, 1820ºC 752, 3308ºF

B 40, 1820ºC B 104, 3308ºF

Notes: Ranges with ** have an accuracy of 0.25%.

For non linear temperature transmitter, the transmitter range MUST be identical to the input range of the recorder.

The mA inputs has to be connected on a 250 Ohms input across the input terminals.

0.5% per 10C on Cu 10 ohms; 0.3% per 10ºC on Pt100< 200ºC

The Reference range is the same as the stated range unless noted.

Minimum System Requirements for PC Software - DPR180 NOTE: Make sure you are an “Administrator” before installing the product.

Windows 7 Professional, Ultimate or Enterprise OS 32-bit or 64-bit edition requires 1 GHz Processor, 2GB RAM and 15GB Hard Disk Space

Windows XP SP1 professional requires a 233 Mhz CPU with 128 MB of RAM

Windows 2000 SP4 professional requires a Pentium 133 Mhz CPU with 64 MB of RAM

Windows NT Workstation 4.0 SP5 requires a 486 Mhz CPU with 32 MB of RAM

Windows 98SE requires a Pentium 150MHz processor with 32 MB of RAM

10MB free on your hard disk for the PC Configuration software.

Recommended video resolution: 800x600 or higher.

HFS Catalog_Without Tab_HighRes.pdf 853 6/8/2011 12:41:41 PM

DPR 180 MM Digital Strip Chart Recorder 9

Dimensions – DPR180

Millimeters/Inches

310

12.2

1

31712.48 40 max

1.57451.77

320

12.6

275x

275

10.8

8x1

0.8

8

278 x 278

10.95 x 10.95

75 min

3 min

PANELCUT OUT

17.50.67

HFS Catalog_Without Tab_HighRes.pdf 854 6/8/2011 12:41:41 PM

DPR 180 MM Digital Strip Chart Recorder 10

For More Information

Learn more about how Honeywell’s DPR 180 MM Digital

Strip Chart Recorder can produce clear and fully

documented charts at any speed, visit our website

www.honeywell.com/ps/hfs or contact your Honeywell

account manager.

Honeywell Process Solutions

1860 West Rose Garden Lane

Phoenix, Arizona 85027

Tel: 1-800-423-9883 or 1-800-343-0228 www.honeywell.com/ps

Warranty/Remedy

Honeywell warrants goods of its manufacture as being free of defective materials and faulty work-manship. Contact your

local sales office of warranty information. If warranted goods are returned to Honeywell during the period of coverage,

Honeywell will repair of replace without charge those items it finds defective. The foregoing is Buyer’s sole remedy and is

in lieu of all other warranties, expressed or implied, including those of merchantability and fitness for a particular

purpose. Specifications may change without notice. The information we supply is believed to be accurate and reliable as of

printing. However, we assume no responsibility for its use. While we provide application assistance personally, through our

literature and the Honeywell website, it is up to the customer to determine the suitability of the product in the application.

43-DR-03-11March 2010 © 2010 Honeywell International Inc.

HFS Catalog_Without Tab_HighRes.pdf 855 6/8/2011 12:41:41 PM