Upload
noushad-p-hamsa
View
391
Download
17
Embed Size (px)
Citation preview
7/27/2019 Double Reg Valves.pdf
1/15
Section 4 : Double Regulating Valves
27
ECONOSTO - DOUBLE REGULATING VALVES (DRV)
General Design & Application:
The Double Regulating Valves are also called Balancing Valves.
Econosto Double Regulating and Commissioning Valves are installed in the pipework of chilled water air
conditioning and hot water central heating systems as well as pottable water systems and serve to achieve a
hydronic balance between the various circuits of the system. The balance is achieved by a pre-setting with memory
position. The required values of pre-setting can be obtained from the flow charts. All intermediate values are
infinitely adjustable.
The selected pre-setting can be read-off two scales (basic scale and fine adjustment scale). The Econosto double
regulating and commissioning valves have two threaded ports for fill and drain ball valves or pressure test points
for the measurement of differential pressure. The Econosto double regulating and commissioning valves are
delivered with 2 blind plugs as a standard unless test points are requested.
The Econosto double regulating and commissioning valves may be installed in either the supply or the return pipe.
The flow charts are valid for both cases provided the direction of flow conforms with the arrow marked on the valve
body.
Advantages of Econosto DRVs:
- One valve for 5 functions:
Pre-setting, measuring, isolating, filling and draining
- Low pressure loss (unique design and oblique pattern)
- Infinitely adjustable pre-setting, exact measurement of pressure loss by means of the pressure test points.
- Patented measuring channel designed around the stem assembly to the test points ensures the best
possible accuracy between differential pressure measured at the pressure test points and the actual
differential pressure of the valve.
Why do we need to Balance Air Conditioning Systems ?
Balancing of heating and chilled water air conditioning systems is necessary to avoid the following problems :
1. Some rooms almost never achieve the desired room temperature or are not cooled sufficiently. This problem
especially arises in case of influence of other heat sources.
2. After changing over from low temperature to heating operation, parts of the system are only heated after a
long time.
3. Fluctuating room temperatures especially arising during low demand periods.
4. High energy consumption although the required room temperature regulator is installed. Even high quality
regulators may not solve this problem.
Distribution of flow :
The main reason for these problems is that incorrect flows are available in the various circuits. If this is the case,
the problem may be solved by installing a double regulating and commissioning valves or flow regulators in the
corresponding pipes. The course of pressure in a circuit makes clear why this occurs.
7/27/2019 Double Reg Valves.pdf
2/15
Section 4 : Double Regulating Valves
28
The illustration shows that the pump has to produce a differential pressure of at least delta P - total to guarantee
a sufficient supply to appliance 4.This will however, inevitably result in a excessive differential pressure at the
appliances 1 to 3 leading to an increased flow at these appliances and thus to an increased energy consumption.
To remedy this, double regulating and commissioning are installed. The excess in differential pressure is now
absorbed by the double regulating and commissioning valves. The desired flow rate may be controlled and set.
To be able to control appliance 4 as well it is recommended to install a double regulating and commissioning valvehere too. The correct supply of each appliance is now guaranteed.
Energy Saving :
Wrong flow rates in the various circuits lead to an increased energy consumption. On the one hand, a higher pump
capacity must be provided to guarantee a sufficient supply of each appliance and on the other hand appliances
being installed at a favourable hydronic position are then over supplied. This will result in an increased room
temperature or, in chilled water air conditioning systems, in too low a room temperature. If the average
temperature in a building exceeds the nominal value by 1 degree C, the energy consumption is increased by 6 -
10 % . In chilled water air conditioning systems , temperatures being 1 degree C too low will result in an increase
in energy consumption of about 15%.
Course of pressure in circuit
7/27/2019 Double Reg Valves.pdf
3/15
Section 4 : Double Regulating Valves
29
ECON Bronze DoubleRegulating Valve, VariableOrifice; PN 25, Fig: 2601V
Specification:Bronze Double Regulating and Commissioning
Valve, Y pattern, Threaded ends to BS 21(BSPP),
PN 25 rated, Variable Orifice with linear
scale and circular scale (fine adjustment).
Maintenance free valve.
Low flow resistance due to unique design.
Complies to BS 7350 accuracy requirements.
Tight closure of valve is assured by use
of PTFE disc insert.
Hand wheel embraces a vernier scale for
accurate setting.
Valves have unique design which enables the
disc to be locked in the set position.
Valve can be sealed in the set position with the
sealing wire and lead seal.
Two points (inlet/outlet) are available on the body
of the DRV (Fig: 2601V). These points are for fixing
the measuring nipples or test plugs for the
measurement of flow / delta P (balancing).
Hydrostatic Test Pressure:Body : 37.5 barSeat : 27.5 bar
Pressure / Temperature Rating:25 bar at -10 to 120 Deg. C
Size Wt.
Inches mm mm m3/hr. Kg.
D L H Kv (Open)
1/2 90 90 2.6 0.46
3/4 102 90 4.3 0.52
1 110 90 6.6 0.66
11/4 121 116 14.5 0.96
11/2 142 116 22.5 1.31
2 161 116 33.1 1.88
Material Specification:
No. Component Material DIN BS
1 Body Bronze G-CuSn5ZnPb 1400LG2
2 Stem DZR Brass - 2874 CZ132
3 Disc DZR Brass - 2874 CZ132
4 Bonnet DZR Brass - 2874 CZ132
5 Seat Ring PTFE - -
6 O-Ring EPDM - -
7 Cap / Knob ABS - -
Dimensions and Weights:
Dimensions (millimeters)
**
**
Flowrate :
Brass Test Nipple Brass self closing Test Plug
DRV with Test Nipple or Test Plug
Fig: 2601V
7/27/2019 Double Reg Valves.pdf
4/15
Specification:Double Regulating and Commissioning
Valves. Conforms to BS 5152 (EN13789).
Y pattern,Flanged to BS 4504 / DIN PN 16
(EN1092). Variable Orifice with linear scale
and circular scale (fine adjustment).
Maintenance free valve
Low flow resistance due to unique design.
Complies to BS 7350 requirements
Tight closure of valve is assured by use ofsoft seating.
Hand wheel embraces a vernier scale
for accurate setting.
Valves have unique design which enables
the disc to be locked in the set position
with a screwdriver.
Valve is supplied with a screw driver
secured to the hand wheel.
Two points (inlet/outlet) are available on
the body of the valve for fixing the measuring
nipples / test plugs for measurement of flow
/ delta P(balancing).
Section 4 : Double Regulating Valves
ECON Cast Iron Double
Regulating Valve, Variable
Orifice; PN 16, Fig: 2920W
Material Specification:
No. Component Material DIN BS1 Body Cast Iron 1691GG25 1452GR260
2 Disc C I + EDPM Coated 1691GG25 1452GR260
3 Disc Nut Brass CuZn39Pb2 2874-CZ121
4 Stem Stainless Steel X10GR13 410S21
5 O-Ring EPDM CuSn 5ZnPb 1400LG2
6 Bonnet Cast Iorn 1691GGLS 1452GR260
7 Gasket Graphite - -
8 Hand Wheel GGG40 + Epoxy Coating - -
9 Gland Carbon Steel - -
10 Nut ASTM B 16 - -
11 Position indicator Plastic - -
12 Adjusting Bolt ASTM B 16 - -
13 Bolt Carbon - -
Fig: 2920W
Nom. Size
DN D L H W
Dimensions (millimeters)
Dimensions and Weights:
KgWeight
65 180 290 293 18
80 180 310 305 23
100 180 350 323 33.5
125 250 400 353 49
150 250 480 388 62
200 250 600 453 96
mm mm mm mm
Hydrostatic Test Pressure:Body : 24 bar
Seat : 17.6 bar
Face to Face Dimensions:
EN 558 - 1 Basic Series 1.
Pressure / Temperature Rating:16 bar at -10 to 120 Deg. C
Maximum Differential Pressure:DN 65 - DN 200 : 16 bar
Note:2920W is supplied with a screw
driver tied to the handwheel.
NEW
7/27/2019 Double Reg Valves.pdf
5/15
Section 4 : Double Regulating Valves
Specification:Double Regulating and Commissioning
Valves. Conforms to BS 5152 (EN13789).
Y pattern,Flanged to BS 4504 / DIN PN 16
(EN1092). Variable Orifice with linear scale
and circular scale (fine adjustment).
Maintenance free valve
Low flow resistance due to unique design.
Complies to BS 7350 requirements
Tight closure of valve is assured by use ofsoft seating.
Hand wheel embraces a vernier scale
for accurate setting.
Valves have unique design which enables
the disc to be locked in the set position
with a screwdriver.
Valve is supplied with a screw driver
secured to the hand wheel.
Two points (inlet/outlet) are available on
the body of the valve for fixing the measuring
nipples / test plugs for measurement of flow
/ delta P(balancing).
Dimensions and Weights:
Dimensions (millimeters)Nom. Size
HLDND
KgWeight
W
195
315
575
645
730
850
420
420
250
300
mm mm mm mm
Fig: 2920W
Material Specification:
No. Component Material DIN BS
1 Body Cast Iron 1691GG25 1452GR260
2 Disc SS + EDPM Ring
3 Disc Nut Brass CuZn39Pb2 2874-CZ121
4 Stem Stainless Steel X10GR13 410S21
5 O-Ring EPDM CuSn 5ZnPb 1400LG2
6 Bonnet Cast Iorn 1691GGLS 1452GR260
7 Gasket Graphite - -
8 Hand Wheel GGG40 + Epoxy Coating - -
9 Gland Carbon Steel - -
10 Nut ASTM B 16 - -
11 Position indicator Plastic - -
12 Adjusting Bolt ASTM B 16 - -
13 Bolt Carbon - -
Hydrostatic Test Pressure:Body : 24 barSeat : 17.6 barFace to Face Dimensions:EN 558 - 1 Basic Series 1.
Pressure / Temperature Rating:16 bar at - 10 to 120 Deg. C
Maximum Differential Pressure:DN 250 : 6 barDN 300 : 4 bar
Note:2920W is supplied with a screw driver tied to thehandwheel.
ECON Cast Iron Double
Regulating Valve, Variable
Orifice; PN 16, Fig: 2920W
7/27/2019 Double Reg Valves.pdf
6/15
Section 4 : Double Regulating Valves
32
PFM 2000Portable meter for measuring flow and pressure difference across Double Regulating valves.Description:
The PFM 2000 is a precision instrument for measuring pressure and flow (PFM = Pressure Flow Meter). It isdesigned for use in monitoring and documenting water flow in heating and cooling installations, (the PFM 2000
measures across the balancing valves in such installations).The instrument is built around a sensor with two interacting ceramic membranes which detect pressure differencesacross the balancing valve. This is a new system and operates by balancing, at a basic physical level, the plus andminus sides of the measuring membranes. The pressure differential range is factory calibrated to cover pressuresfrom 0 to 1.5 bar (150 kPa). The storage case containing the PFM 2000 and all accessories is as below.
TECHNICAL SPECIFICATION
Measurement range:Differential pressure: upto 150 kPa
at total pressure upto 1000 kPamax 2000 kPa
Static Pressure upto 1000 kPa
Resolution:Differential pressure: 0.01 kPa, at total pressure 100 kPa
Static Pressure 10 kPaFlow: 0.001 1/sAccuracy:Differential pressure: 10 kPa 1% of metered valueFlow: As for pressure + the valves deviationEnvironment:
Temperature, media: -10C to 100CTemperature, storage: -20C to 60CHumidity, (non-condensing): max 90% RH
Power supply:Capacity: 1500 mAhR6 rechargeable NiMH batteries (6)
The PFM 2000 (new) package comprises:
Part: Quantity:Digital Meter (electronic) 1Sensor unit 1Cable between meter and sensor unit 1Hoses and connectors 2Battery charger 1Storage case with carrying strap 1Operating Manual 1Calibration protocol (Certificate) 1Connecting probes 2Allen key - 3mm 1Allen key - 5mm 1
Model PFM 2000
7/27/2019 Double Reg Valves.pdf
7/15
Section 4 : Double Regulating Valves
33
7/27/2019 Double Reg Valves.pdf
8/15
Section 4 : Double Regulating Valves
34
7/27/2019 Double Reg Valves.pdf
9/15
Section 4 : Double Regulating Valves
35
Knob setting / No. of turns
1.0 - to - 4.0
7/27/2019 Double Reg Valves.pdf
10/15
Number ofRotations
0 1 2 3 4 5 6 7 8
0 9.0 14.5 22.7 33.1 44.7 59.9 67.3 74.5Kv-value
Section 4 : Double Regulating Valves
ECON BALANCING VALVE FIG.2920W : SIZE 65 mm
Kv-value according to VDI/VDE 2173Kv-value : flow in m3 / h at 1 bar headloss.
Number ofRotations
0 1 2 3 4 5 6 7 8
0 16.7 25.6 38.2 55.6 74.0 89.0 106.6 118.4Kv-value
ECON BALANCING VALVE FIG.2920W : SIZE 80 mm
Kv-value according to VDI/VDE 2173
Kv-value : flow in m3 / h at 1 bar headloss.
NEW
7/27/2019 Double Reg Valves.pdf
11/15
Number ofRotations
0 1 2 3 4 5 6 7 8
0 25.0 48.7 71.4 104.0 138.6 163.2 187.1 203.0Kv-value
Section 4 : Double Regulating Valves
ECON BALANCING VALVE FIG.2920W : SIZE 100 mm
Kv-value according to VDI/VDE 2173Kv-value : flow in m3 / h at 1 bar headloss.
Number ofRotations
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
0 33.7 57.2 71.4 91.0 115.5 141.2 159.9 178.5 195.0 213.6 237.5 257.8 281.0 296.2Kv-value
ECON BALANCING VALVE FIG.2920W : SIZE 125 mm
Kv-value according to VDI/VDE 2173Kv-value : flow in m3 / h at 1 bar headloss.
NEW
7/27/2019 Double Reg Valves.pdf
12/15
Number of
Rotations0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
0 50.00 80.1 92.8 112.5 137.5 169.8 197.7 233.5 270.3 303.1 338.7 377.5 399.2 415.9Kv-value
ECON BALANCING VALVE FIG.2920W : SIZE 150 mm
Kv-value according to VDI/VDE 2173Kv-value : flow in m3 / h at 1 bar headloss.
Number ofRotations
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
0 63.8 128.9 161.0 205.3 254.9 312.5 375.7 420.5 476.7 537.1 592.9 655.4 711.5 759.3Kv-value
ECON BALANCING VALVE FIG.2920W : SIZE 200 mm
Kv-value according to VDI/VDE 2173Kv-value : flow in m3 / h at 1 bar headloss.
Section 4 : Double Regulating Valves
7/27/2019 Double Reg Valves.pdf
13/15
Number of
Rotations
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
0 65.553.0 88.8 131.5 177.4 224.1 275.4 349.3 425.7 505.9 590.5 671.4 755.2 836.6 901.0 966.9 1030.6 1 058.8Kv-value
Number ofRotations
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
0 79.970.6 83.9 123.6 176.1 233.3 307.5 416.3 566.4 744.6 924.4 1049.0 1130.3 1182.21222.2 1276.91340.3 1422.6
19
1459.5Kv-value
ECON BALANCING VALVE FIG.2920W : SIZE 250 mm
Kv-value according to VDI/VDE 2173Kv-value : flow in m3 / h at 1 bar headloss.
ECON BALANCING VALVE FIG.2920W : SIZE 300 mm
Kv-value according to VDI/VDE 2173Kv-value : flow in m3 / h at 1 bar headloss.
Section 4 : Double Regulating Valves
7/27/2019 Double Reg Valves.pdf
14/15
Section 4 : Double Regulating Valves
40
Presetting of ECON - PN25 Balancing valve Fig. 2601V
Econosto DRV and commissioning valves are deigned for installation in hot water heating and chilled water air
conditioning systems and served to achieve a hydronic balance between the various circuits of the system. It is
important to note that the direction of flow must conform with the direction of the arrow on the valve body
and that the valve must be installed with a minimum of 3 D (3 x nominal pipe diameter) straight pipe in the
upstream side. The required preset value van be obtained by reference to the flow chart appropriate for the size
of valve. Any intermediate preset value is available. The selected preliminary setting can be made from the two-
part scale - the basic scale and the fine adjustment scale.
Presetting :
1. The preset valve of the valve is adjusted with the handwheel.
a. The display of the basic setting is shown in the lower windows by the sliding indicator.
Each turn of the handwheel is represented by a number inside the window.
b. The display of the fine setting is shown in the handwheel windows scale and each number indicates 1/10th
of a turn of the handwheel.
2. Carefully remove the cover plug in the centre of the handwheel by using a small screwdriver in the slot and
gently prising it off.
3. With the valve at the required preset value,using a 3 mm allen key, turn the inner screw clockwise until it seats.
The inner screw is located in the hole through the nut. The 3 mm allen key is supplied along with every valve.
4. Refit the cover plug.
Protecting the setting:
A sealing wire may be threaded through the hole in the handwheel and a lead seal fitted.
For presetting and fine adjustment of the flow volume (balancing), Econosto offers thePFM 2000 - Pressure and Flow Measuring Instrument.
The Econosto PFM-2000 - Pressure and Flow Measuring Instrument is an advanced programmable microprocessor
with memory store (please refer page 32 of this catalogue for more details).
7/27/2019 Double Reg Valves.pdf
15/15
Section 4 : Double Regulating Valves
Presetting of ECON Balancing valve Fig 2920W
6
64
CDBEA
Econ balancing valve are supplied with the suitable screw driver fixed to the hand wheel. The warning and instruction
leaflet (sticker) is fixed on the body of each valve which provides clear instructions for valve operation. The number
full revolutions is indicated on the linear scale C, fine adjustment is visible on the circular pitch D one turn is
divided into ten parts.
1) Remove the red plastic hand wheel cap A.
2) Close the valve completely & check if the linear scale C and circular pitch D indicate 0 0
adjustment.
3) Open the valve as required set the number of full revolutions on the linear scale C and tenth
of turn on the circular pitch D.
4) Insert enclosed screw driver E into the screw B, rotate the regulating screw anticlockwise to
set the double regulating feature, a positive stop will be felt.
5) Put the cap A on the head of bolt B.
MaintenanceEvery part of the valve is designed in such a way that the whole valve is maintenance free.The materials are carefully
matched with the parts to make the friction as small as possible. However, due to safety reasons, every valve should
be inspected regularly. Before valve removal from the plant or before service the suitable part of the pipeline should
be closed.
Installation
Take off the plastic covers from the flanges. Blow inside valve by compressed air. The pipeline should be placed insuch a way that valve body does not carry bending moments nor tension forces. The linear scale and the plastic set
should be protected against painting. The valves could be installed in every position in inlet and outlet pipelines with
the hand wheel in down direction. Attention should be paid to flow direction indicated by the arrow on the valve
body. Before starting pipelinework (especially after repairs) whole pipeline should be rinsed out by fully opeing the
valves in order to remove all solid residues which could be dangerous for sealing surfaces. Turning the hand wheel
clockwise (according to direction indicated on the hand wheel) can close the valve. The valve is opened by
anti-clockwise roation of the hand wheel. It is prohibited to use additional lever for turning the hand wheel.
For pressure and fine adjustment of the flow volume (balancing), Econosto offers the PFM- 2000 / 2050 pressure and
flow measurement instrument.
The econosto PFM 2000 / 2050 pressure and flow measuring instrument advance programmable microprocessor.