HighPROTEC MRA4 APPLICATION The MRA4 is a protection relay which uses the latest Dual-Core- Processor Technology to provide precise and reliable protective functions and is very easy to operate. Its various protective func- tions are specifically tailored to the protection of incoming and outgoing feeders in MV systems. It also can be used for grid and generator protection. ALL INCLUSIVE: All protection features without extra charge Parameter setting and evaluation software Disturbance record analysis software SIX STAGES PHASE OVER- CURRENT PROTECTION Directional and non-directional overcurrent/short-circuit protection Tripping characteristics: DEFT ANSI: NINV, VINV, EINV IEC: NINV, VINV, LINV, EINV Thermal Flat, IT, I2T, I4T Voltage controlled and restraint FOUR STAGES EARTH FAULT PROTECTION Directional and non-directional earth fault protection Tripping characteristic: DEFT ANSI: NINV, VINV, EINV IEC: NINV, VINV, LINV, EINV Thermal Flat, IT, I2T, I4T Voltage controlled and restraint TWO STAGES UNBALANCED LOAD PROTECTION Supervision by definite time or tripping characteristic SIX STAGES VOLTAGE PROTECTION Under- and overvoltage Programmable undervoltage time depending characteristic TWO STAGES RESIDUAL VOLTAGE PROTECTION VE> SIX STAGES VOLTAGE ASYMMETRY SUPERVISION Under- and overvoltage in positive phase sequence system, overvoltage in negative phase sequence system DISTURBANCE RECORDER 120 s non volatile, 32 samples per cycles ADDITIONAL HIGHLIGHTS Automatic reclosing Inrush Thermal replica Four stages external protection Plausibility checks Adaptive parameter sets Energy counters Status display Comprehensive measured values and statistics Masking of unused functions PARAMETER SETTING SUPPORT BY SOFTWARE Copy parameter sets Compare parameter sets Setting files are up and down convertible (across versions) COMPREHENSIVE FREQUENCY PROTECTION PACKAGE Each of the six stages can be used as: f< or f> (over- and underfrequency supervision) df/dt (ROCOF) (f< and df/dt) or (f> and df/dt) combination of over-, under- and rate of change of frequency (ROCOF) (f< and DF/DT) or (f> and DF/DT) combination of over-, under- and increase of frequency Delta Phi (Vector surge) POWER PROTECTION PACKAGE Six stages power protection Each can be used as P>, P<, Pr, Q>, Q<, Qr, S>, S< Two stages power factor (PF) Q(V) PROTECTION Undervoltage directional reactive power protection with reclosing disengaging SUPERVISION Current transformer supervision Voltage transformer supervision Circuit breaker failure protection Trip circuit supervision Cold load pickup Switch onto fault Breaker Wear PROTECTION RELAY FOR FEEDER, GRID AND GENERATOR APPLICATIONS PROTECTION TECHNOLOGY MADE SIMPLE

Dok Fly Mra4e New

Embed Size (px)

DESCRIPTION

Informacion basica del relevador MRA4E de la marca Woodward

Citation preview

Page 1: Dok Fly Mra4e New

HighPROtecMra4

aPPlic ation the Mra4 is a protection relay which uses the latest dual-core-Processor technology to provide precise and reliable protective functions and is very easy to operate. its various protective func-tions are specifi cally tailored to the protection of incoming and outgoing feeders in MV systems. it also can be used for grid and generator protection.

all incluSive: all protection features without

extra charge Parameter setting and evaluation

software disturbance record analysis software

SiX StaGeS PHaSe over-current Protec tion

directional and non-directional overcurrent/short-circuit protection

tripping characteristics: deftansi: ninV, VinV, einViec: ninV, VinV, linV, einVthermal flat, it, i2t, i4t

Voltage controlled and restraint

Four StaGeS eartH Fault Protec tion

directional and non-directionalearth fault protection

tripping characteristic: deftansi: ninV, VinV, einViec: ninV, VinV, linV, einVthermal flat, it, i2t, i4t

Voltage controlled and restraint

t wo StaGeS unBalanceD loaD Protec tion

supervision by defi nite time or tripping characteristic

SiX StaGeS voltaGe Protec tion

Under- and overvoltage Programmable undervoltage

time depending characteristic

t wo StaGeS reSiDual voltaGe Protec tion

Ve>

SiX StaGeS voltaGe aSYmmetrY SuPerviSion

Under- and overvoltage in positive phase sequence system, overvoltage in negative phase sequence system

DiSturBance recorDer 120 s non volatile,

32 samples per cycles

aDDitional HiGHliGHtS automatic reclosing inrush thermal replica four stages external protection Plausibility checks adaptive parameter sets energy counters status display comprehensive measured values

and statistics Masking of unused functions

Parameter Set tinG SuPPort BY SoFt ware

copy parameter sets compare parameter sets setting fi les are up and down

convertible (across versions)

comPreHenSive FreQuencY Protec tion PacK aGeeach of the six stages can be used as:

f< or f> (over- and underfrequency supervision)

df/dt (rocof) (f< and df/dt) or (f> and df/dt)

combination of over-, under- and rateof change of frequency (rocof)

(f< and df/dt) or (f> and df/dt) combination of over-, under-and increase of frequency

delta Phi (Vector surge)

Power Protec tion PacK aGe

six stages power protectioneach can be used as P>, P<, Pr, Q>, Q<, Qr, s>, s<

two stages power factor (Pf)

Q(v) Protec tion Undervoltage directional reactive power

protection with reclosing disengaging

SuPerviSion current transformer supervision Voltage transformer supervision circuit breaker failure protection trip circuit supervision cold load pickup switch onto fault Breaker Wear

Protection relay for feeder,Grid and Generator aPPlications

Protection tecHnoloGyMade siMPle

Page 2: Dok Fly Mra4e New

w w w . w o o d w a r d . c o m

MRA4 Protection relay for feeder,Grid and Generator aPPlications

Func tional over vie w

elements anSi

Protective Functions

i, time overcurrent and short circuit protection, all stages can be configured for directional or non-directional supervision. tremendous reset options (instantaneous, definite time, reset characteristics according to iec and ansi).

Voltage controlled overcurrent protection by means of adaptive parameters.Voltage dependent overcurrent protection.negative phase sequence overcurrent protection

6

50P, 51P, 67P

51c51V51Q

i2>, unbalanced load protection with evaluation of the negative phase sequence currents 2 46

iB, overload protection with thermal replica and separate pick-up values for alarm and trip functions 1 49

iH2/in, inrush detection with evaluation of the 2nd harmonic 1 inrush

iG, earth overcurrent and short circuit protection, all stages can be configured for directional or non-directional supervision. tremendous reset options (instantaneous, definite time, reset characteristics according to iec and ansi).

Voltage controlled earth overcurrent protection by means of adaptive parameters. Voltage dependent earth overcurrent protection.

4

4 4

50n, 51n, 67n

51nV 51nc

V<, V>, V(t)<, under- and overvoltage protection, time dependent undervoltage protection 6 27, 59

Voltage asymmetry supervision (V012) V1, under and overvoltage in positive phase sequence system V2, overvoltage in negative phase sequence system

6 47

each of the six frequency protection stages can be used as:

f< or f> (over- and under frequency supervision) df/dt rate of change of frequency (rocof) (f< and df/dt) or (f> and df/dt) combination of over-, under- and rate of change of frequency (rocof) (f< and df/dt) or (f> and df/dt) combination of over-, under- and increase of frequency delta Phi (Vector surge)

6

81U/o81r

78

Ve, residual voltage protection 2 59n

ar, automatic reclosing 1 79

exP, external alarm and trip functions 4

PQs, Power protection 6 32, 37

Pf, Power factor 2 55

Q(V) Protection (undervolt. dep. directional reactive power protection with reclosing disengaging)

Supervision Functions

cBf, circuit breaker failure protection 1 50Bf

tcs, trip circuit supervision 1 74tc

Vts, voltage transformer supervision by comparing phase and residual voltages 1 60fl

Vts, fuse failure protection via digital input 1 60fl

cts, current transformer supervision 1 60l

clPU, cold load pickup 1

sotf, switch onto fault 1

Bwear, Breaker Wear 2

non volatile event recorder up to 120 s with 32 samples per cycles

Page 3: Dok Fly Mra4e New

3

1

4

MRA4

*

74TC79 50

BF 50P 51P 51Q46 37

81R60FL

81 U/O784759N

5927

50N 51N 51R

67PQ(U)

60L 49

32 5567N

51C*

51V

Inrush CLPU SOTF

Fault recorder

Event recorder

Disturbance recorder

V, VE, V012, I, IG, f, delta phi, theta , IH2, IGH2, I012, P, Q, S,

PF, cos phi, Wcurrent and voltage

phasors

Measured and calculated values

IRIG-B00X* = Via Adaptive Parameters

Func tional over vie w in anSi Form

connec tionS

Page 4: Dok Fly Mra4e New

Enabling Electrical Power Systems Integration

TM

MRA4 Protection relay for feeder,Grid and Generator aPPlications

orDer Form mr a4

Directional Feeder Protection mra4

Digital inputs

Binaryoutputrelays

Housing

816

713

B2B2

ad

Hardware variant 2standard 0

Housing and mountingdoor mountingdoor mounting 19“ (fl ush mounting)

aB

communication protocolWithout protocolrs485/terminals, Modbus rtU, iec60870-5-103ethernet (rJ45), Modbus tcP, iec61850* prepared (Hardware/interface)optic fi ber, Profi bus dPrs485/d-sUB, Profi bus dPoptic fi ber, Modbus rtU, iec60870-5-103rs485/d-sUB, Profi bus, Modbus rtU, iec60870-5-103

aBcdefG

available menu languagesenglish/German/russian

all devices are equipped with iriG-B interface.

the parameterizing and disturbance analyzing software is included in delivery of HighProtec devices.

* For information about additional cost for the software update tool IEC61850 per device, please contact our sales team. The devices can be updated via device front interface (RS232) and PC locally. Please ask for availability.

current inputs 4 (1 a and 5 a) with automatic short circuitersvoltage inputs 4 (0– 800 V)Digital inputs switching thresholds adjustable via softwarePower supply Wide range power supplyterminals all terminals plug typemounting door mountingtype of enclosure iP54Dimensions of housing 212.7 mm x 173 mm x 209 mm (W x H x d)weight (max. components) approx. 4 kg

contac t:

north & central america

Phone: +1 970 498 3634

e-mail: [email protected]

South america

Phone: +55 11 3034 1120

e-mail: [email protected]

europe

Phone: +49 2152 145-319

e-mail: [email protected]

middle east & africa

Phone: +971 2 6275185

e-mail: [email protected]

russia

Phone: +7 960 272 4205

e-mail: [email protected]

china

Phone: +86 512 8818 5515

e-mail: [email protected]

india

Phone: +91 22 2561 2256

e-mail: [email protected]

aSean & oceania

Phone: +49 711 78954-511

e-mail: [email protected]

© Woodward

all rights reserved | 03.2010 do

K_fl

y_M

ra4_

03.1

0_en