328
Power and Energy Series 68 Distribution System Analysis and Automation Juan M Gers

Distribution Systen Analysis Automatation

Embed Size (px)

Citation preview

  • Power and Energy Series 68

    Distribution System Analysis and Automation

    Distribution System

    Analysis and Autom

    ationG

    ers Juan M Gers

    The Institution of Engineering and Technologywww.theiet.org 978-1-84919-659-8

    Distribution System Analysis and Automation

    Juan M. Gers is President of GERS, a consulting engineering company specialized in power systems. He was lecturer at the University of Valle for more than 20 years He is now associated to Gonzaga Universtiy. He is co-author of Protection of Electricity Distribution Networks (IET, 2011), now in its third edition, and is the author/co-author of over 40 technical papers. Dr Gers is a Chartered Engineer of the IET and participates in several groups of the Power System Relaying Committee of the IEEE.

    Distribution systems analysis employs a set of techniques that allow engineers to simulate, analyse, and optimise power distribution systems. Combined with automation, these techniques underpin the emerging concept of the smart grid, a digitally-enabled electrical supply grid that can monitor and respond to the behaviour of all its components in real time.

    Distribution System Analysis and Automation provides a comprehensive guide to these techniques, with coverage including smart grid for distribution systems; introduction to distribution automation; network and radial load flow analysis; determination of the optimal topology for power electric systems; voltage VAR control and capacitor application; power quality and harmonics in distribution systems; harmonic filter design; distribution system restoration; short circuit analysis; arc flash concepts; numerical relaying and feeder protection; communication and control centres; and distributed energy resources. The book combines theoretical concepts with real-world applications, and includes MATLAB exercises.

    Distribution System Analysis and Automation.indd 1 09/10/2013 18:30:08

  • IET POWER AND ENERGY SERIES 68

    DistributionSystem Analysisand Automation

  • Other volumes in this series:

    Volume 1 Power circuit breaker theory and design C.H. Flurscheim (Editor)Volume 4 Industrial microwave heating A.C. Metaxas and R.J. MeredithVolume 7 Insulators for high voltages J.S.T. LoomsVolume 8 Variable frequency AC motor drive systems D. FinneyVolume 10 SF6 switchgear H.M. Ryan and G.R. JonesVolume 11 Conduction and induction heating E.J. DaviesVolume 13 Statistical techniques for high voltage engineering W. Hauschild and W. MoschVolume 14 Uninterruptible power supplies J. Platts and J.D. St Aubyn (Editors)Volume 15 Digital protection for power systems A.T. Johns and S.K. SalmanVolume 16 Electricity economics and planning T.W. BerrieVolume 18 Vacuum switchgear A. GreenwoodVolume 19 Electrical safety: a guide to causes and prevention of hazards J. Maxwell AdamsVolume 21 Electricity distribution network design, 2nd edition E. Lakervi and E.J. HolmesVolume 22 Artificial intelligence techniques in power systems K. Warwick, A.O. Ekwue and

    R. Aggarwal (Editors)Volume 24 Power system commissioning and maintenance practice K. HarkerVolume 25 Engineers handbook of industrial microwave heating R.J. MeredithVolume 26 Small electric motors H. Moczala et al.Volume 27 AC-DC power system analysis J. Arrillaga and B.C. SmithVolume 29 High voltage direct current transmission, 2nd edition J. ArrillagaVolume 30 Flexible AC transmission systems (FACTS) Y.-H. Song (Editor)Volume 31 Embedded generation N. Jenkins et al.Volume 32 High voltage engineering and testing, 2nd edition H.M. Ryan (Editor)Volume 33 Overvoltage protection of low-voltage systems, revised edition P. HasseVolume 34 The lightning flash V. CoorayVolume 36 Voltage quality in electrical power systems J. Schlabbach et al.Volume 37 Electrical steels for rotating machines P. BeckleyVolume 38 The electric car: development and future of battery, hybrid and fuel-cell cars

    M. WestbrookVolume 39 Power systems electromagnetic transients simulation J. Arrillaga and N. WatsonVolume 40 Advances in high voltage engineering M. Haddad and D. WarneVolume 41 Electrical operation of electrostatic precipitators K. ParkerVolume 43 Thermal power plant simulation and control D. FlynnVolume 44 Economic evaluation of projects in the electricity supply industry H. KhatibVolume 45 Propulsion systems for hybrid vehicles J. MillerVolume 46 Distribution switchgear S. StewartVolume 47 Protection of electricity distribution networks, 2nd edition J. Gers and E. HolmesVolume 48 Wood pole overhead lines B. WareingVolume 49 Electric fuses, 3rd edition A. Wright and G. NewberyVolume 50 Wind power integration: connection and system operational aspects

    B. Fox et al.Volume 51 Short circuit currents J. SchlabbachVolume 52 Nuclear power J. WoodVolume 53 Condition assessment of high voltage insulation in power system equipment

    R.E. James and Q. SuVolume 55 Local energy: distributed generation of heat and power J. WoodVolume 56 Condition monitoring of rotating electrical machines P. Tavner, L. Ran,

    J. Penman and H. SeddingVolume 57 The control techniques drives and controls handbook, 2nd edition B. DruryVolume 58 Lightning protection V. Cooray (Editor)Volume 59 Ultracapacitor applications J.M. MillerVolume 62 Lightning electromagnetics V. CoorayVolume 63 Energy storage for power systems, 2nd edition A. Ter-GazarianVolume 65 Protection of electricity distribution networks, 3rd edition J. GersVolume 66 High voltage engineering testing, 3rd edition H. Ryan (Editor)Volume 67 Multicore simulation of power system transients Fabian M. UriarteVolume 905 Power system protection, 4 volumes

  • DistributionSystem Analysisand Automation

    Juan M. Gers PhdAdjunct Professor, T&D Program,

    Gonzaga University, Spokane WA, USA

    Consultant Engineer,GERS USA, Weston FL, USA

    The Institution of Engineering and Technology

  • Published by The Institution of Engineering and Technology, London, United Kingdom

    The Institution of Engineering and Technology is registered as a Charity inEngland & Wales (no. 211014) and Scotland (no. SC038698).

    The Institution of Engineering and Technology 2014

    First published 2013

    This publication is copyright under the Berne Convention and the Universal CopyrightConvention. All rights reserved. Apart from any fair dealing for the purposes of researchor private study, or criticism or review, as permitted under the Copyright, Designs andPatents Act 1988, this publication may be reproduced, stored or transmitted, in anyform or by any means, only with the prior permission in writing of the publishers, or inthe case of reprographic reproduction in accordance with the terms of licences issuedby the Copyright Licensing Agency. Enquiries concerning reproduction outside thoseterms should be sent to the publisher at the undermentioned address:

    The Institution of Engineering and Technology

    Michael Faraday HouseSix Hills Way, StevenageHerts, SG1 2AY,United Kingdom

    www.theiet.org

    While the author and publisher believe that the information and guidance given in thiswork are correct, all parties must rely upon their own skill and judgement when makinguse of them. Neither the author nor publisher assumes any liability to anyone for anyloss or damage caused by any error or omission in the work, whether such an error oromission is the result of negligence or any other cause. Any and all such liability isdisclaimed.

    The moral rights of the author to be identified as author of this work have beenasserted by him in accordance with the Copyright, Designs and Patents Act 1988.

    British Library Cataloguing in Publication DataA catalogue record for this product is available from the British Library

    ISBN 978-1-84919-659-8 (hardback)ISBN 978-1-84919-660-4 (PDF)

    Typeset in India by MPS LimitedPrinted in the UK by CPI Group (UK) Ltd, Croydon

  • Contents

    List of figures xiList of tables xvii

    1 Smart Grid overview 11.1 Smart Grid for distribution systems 11.2 Definitions of Smart Grid 31.3 Benefits of the Smart Grid on distribution systems 6

    1.3.1 Enhancing reliability 61.3.2 Improving system efficiency 61.3.3 Distributed energy resources 61.3.4 Optimizing asset utilization and efficient operation 6

    1.4 Quality indices 61.4.1 System Average Interruption Duration Index (SAIDI) 71.4.2 System Average Interruption Frequency Index (SAIFI) 81.4.3 Customer Average Interruption Duration Index (CAIDI) 81.4.4 Momentary Average Interruption Frequency Index (MAIFI)

    and Momentary Average Interruption Event FrequencyIndex (MAIFIE) 9

    Proposed exercise 11

    2 Distribution automation functions 132.1 Electrical system automation 132.2 EMS functional scope 152.3 DMS functional scope 162.4 Functionality of DMS 16

    2.4.1 Steady-state performance improvement 162.4.2 Dynamic performance improvement 18

    2.5 Geographic information system 202.5.1 AM/FM functions 222.5.2 Database management 22

    2.6 Communication options 222.7 Supervisory control and data acquisition 22

    2.7.1 SCADA functions 232.7.2 System architecture 27

    2.8 Synchrophasors and its application in power systems 302.8.1 Definition 302.8.2 Application of PMUs 31

  • 3 Fundamentals of distribution system analysis 373.1 Electrical circuit laws 37

    3.1.1 Ohms law 373.1.2 Kirchhoffs voltage law 373.1.3 Kirchhoffs current law 38

    3.2 Circuit theorems 383.2.1 Thevenins theorem 383.2.2 Star/delta transform 383.2.3 Superposition theorem 39

    3.3 Power AC circuits 393.4 PU normalization 443.5 Load flow 48

    3.5.1 Formulation of the load flow problem 493.5.2 NewtonRaphson method 503.5.3 Type of buses 533.5.4 Application of the NewtonRaphson method to solve

    load flows 533.5.5 Decoupling method 56

    3.6 Radial load flow concepts 763.6.1 Theoretical background 763.6.2 Distribution network models 783.6.3 Nodes and branches identification 783.6.4 Illustration of nodes and branches identification 793.6.5 Algorithm to develop radial load flow 80

    Proposed exercise 83

    4 Short circuit calculation 854.1 Nature of short circuit currents 854.2 Calculation of fault duty values 924.3 Fault calculation for symmetrical faults 954.4 Symmetrical components 96

    4.4.1 Importance and construction of sequence networks 994.4.2 Calculation of asymmetrical faults using symmetrical

    components 1024.4.3 Equivalent impedances for a power system 1044.4.4 Supplying the current and voltage signals to protection

    systems 104Proposed exercise 111

    5 Reliability of distribution systems 1155.1 Network modeling 1165.2 Network reduction 119Proposed exercise 121

    vi Distribution system analysis and automation

  • 6 Reconfiguration and restoration of distribution systems 1236.1 Optimal topology 1236.2 Location of switches controlled remotely 130

    6.2.1 Considerations to increase flexibility 1306.2.2 Considerations to increase flexibility 138

    6.3 Feeder reconfiguration for improving operating conditions 1396.4 Feeder reconfiguration for service restoration 141

    6.4.1 Fault location, isolation, and servicerestoration (FLISR) 141

    6.4.2 Manual restoration vs. FLISR 1456.4.3 Restrictions on restoration 1466.4.4 FLISR central intelligence 1486.4.5 FLISR distributed intelligence 1496.4.6 FLISR local intelligence 152

    7 Volt/VAR control 1557.1 Definition of voltage regulation 1577.2 Options to improve voltage regulation 1577.3 Voltage regulators 1587.4 Capacitor application in distribution systems 160

    7.4.1 Feeder model 1637.4.2 Capacitor location and sizing 1667.4.3 Reduction in power losses with one capacitor bank 1667.4.4 Reduction in power losses with two capacitor banks 1687.4.5 Loss reductions with three capacitor banks 1697.4.6 Consideration of several capacitor banks 1707.4.7 Capacitor sizing and location using software 171

    7.5 Modeling of distribution feeders including VVC equipment 1727.6 Volt/VAR control considering SCADA 1737.7 Requirements for Volt/VAR control 1747.8 Integrated Volt/VAR control 174Proposed exercise 176

    8 Harmonic analysis 1798.1 General considerations about harmonics 1798.2 Mathematical background 1838.3 Verification of harmonic values 1848.4 Parallel resonance 1858.5 Series resonance 1868.6 Validation of harmonic values 187

    8.6.1 Harmonic limits 1878.6.2 Voltage distortion limits 1878.6.3 Current distortion limits 188

    8.7 Verification of harmonic values 188

    Contents vii

  • 8.8 Resizing and relocation of capacitor banks 1898.9 Models 191

    8.9.1 Harmonic sources 1918.9.2 System model 1928.9.3 Load model 1928.9.4 Branch model 192

    8.10 Derating transformers 198

    9 Modern protection of distribution systems 2019.1 Fundamentals of overcurrent protection 201

    9.1.1 Protection coordination principles 2019.1.2 Criteria for setting instantaneous units 2019.1.3 Setting time-delay relays 2029.1.4 Setting overcurrent relays using software techniques 205

    9.2 Coordination across Dy transformers 2069.3 Protection equipment installed along the feeders 211

    9.3.1 Reclosers 2119.3.2 Sectionalizers 2199.3.3 Fuses 223

    9.4 Setting criteria 2289.4.1 Fuse-fuse coordination 2289.4.2 Recloser-fuse coordination 2299.4.3 Recloser-sectionalizer coordination 2339.4.4 Recloser-sectionalizer-fuse coordination 2349.4.5 Recloser-recloser coordination 2369.4.6 Recloser-relay coordination 237

    9.5 Protection considerations when distributed generation is available 2379.5.1 Short circuit levels 2379.5.2 Synchronization 2389.5.3 Overcurrent protection 2389.5.4 Adaptive protection 238

    Proposed exercise 239

    10 Communications in Smart Grids 24310.1 ISO OSI model 24310.2 Communication solutions for the power system world 244

    10.2.1 Communication solutions in AMI 24510.2.2 Distribution network communications 246

    10.3 Transmission mediums 24810.3.1 Wired and electric mediums 24810.3.2 Wireless mediums 24810.3.3 Optical mediums 249

    10.4 Information security as the crucial element in smart networks 24910.5 IEC 61850 overview 250

    10.5.1 Standard documents and features of IEC 61850 25110.5.2 System configuration language 258

    viii Distribution system analysis and automation

  • 10.5.3 Configuration and verification of GOOSE messages 25910.5.4 Configuration of the system 26110.5.5 System verification test 26210.5.6 Substation IT network 26310.5.7 Process bus 264

    11 Interoperability concepts in power electric systems 26511.1 Elements required for interoperability 26611.2 Information exchange processes 26711.3 Data models and international standards 26811.4 Implementation of information models in the Power Electric

    System (PES) 271

    12 Maturity models 27512.1 Smart Grid maturity model definition 27512.2 Benefits of using a Smart Grid maturity model 27612.3 Genesis and components of SGMM 27612.4 Development process of an SGMM 27712.5 Levels and dominions of an SGMM 278

    12.5.1 Maturity levels of SGMM 27812.5.2 Domains of SGMM 279

    12.6 Results and analysis obtained by SGMM 28112.7 Example case 282

    Bibliography 287

    Index 299

    Contents ix

  • List of figures

    1.1 Power system as envisaged in 1982 (from Automated powerdistribution, published by IEEE Spectrum, April 1982) 2

    1.2 Smart Grid concept 51.3 Smart Grid components 51.4 Representation of events used in calculating indices 102.1 Typical installation of a switch on an overhead distribution feeder 142.2 Main benefits of distribution automation 142.3 Power system automation components 152.4 Network management EMS/DMS 152.5 Screen shots of a typical EMS 162.6 Screen shots of a typical DMS 172.7 Illustration of power line communication (PLC) 182.8 (a) Modulation for the outbound signal; (b) modulation for

    the inbound signal 182.9 Comparison of restoration time with and without DA 192.10 Trouble call system 202.11 Work order illustration 212.12 Example of a GIS 212.13 Typical communication methods 222.14 SCADA illustration 232.15 SCADA functions: supervisory control 242.16 SCADA functions: data acquisition 252.17 Relationship of SCADA with databases 252.18 Control center general scheme 282.19 Single master station, multiple RTU, radial circuit 292.20 Single master station, data concentrator, or gateway 292.21 Multiple master stations, LAN/WAN substation connection

    using routers 292.22 Sinusoidal waveform from its phasorial representation 312.23 PMUs integration with the current communication system 322.24 Transmission line model 332.25 Transferred power through a line 352.26 Integration of a distributed generation source using PMUs 363.1 (a) Circuit before using the Thevenins theorem; (b) circuit

    after using the Thevenins theorem 383.2 Star/delta equivalent 39

  • 3.3 (a) Circuit complete; (b) solution using superposition theorem 393.4 Relationship of current, voltage, and power in electrical circuits 403.5 Power losses for different voltage angles 433.6 Power losses for different voltage angles 443.7 Electrical system for example 3.3 463.8 Illustration of a power system board simulator 483.9 Representation of a three-node system with current sources 493.10 Illustration of the NewtonRaphson concept 513.11 Illustration of types of buses for load flow analysis 543.12 Flow chart for load flow analysis using NewtonRaphson algorithm 573.13 Two bus system with load at the end bus 573.14 Illustration of the relationship between P and q 583.15 Illustration of the relationship between Q and V 583.16 Power system for example 3.6 603.17 Load flow results in pu for the system of example 3.6 653.18 Load flow results in real magnitudes for the system of example 3.6 663.19 Single-line diagram for example 3.7 673.20 Portion of the power system of example 3.7 723.21 Bus voltage results considering a capacitor bank at 13.2 kV

    Willow bus 733.22 Bus voltage results of example 3.7 considering tap changer

    operation 743.23 Bus voltage results of example 3.7 considering a new line 753.24 Two-node systems 763.25 Two-feeder system with number and letter nomenclature 793.26 Two-feeder identification for the example system 803.27 Load flow for radial systems 813.28 Grounded WyeGrounded Wye step-down transformer with

    balanced load 824.1 L-R circuit 864.2 Impedance components 874.3 Variation of fault current due to the DC component 884.4 Results for example 4.1 904.5 Transient SC current at generator terminals 914.6 Variation of current with time during a fault at generator terminals 914.7 Variation of generator reactance during a fault 924.8 Multiplying factors for three-phase and L-L ground faults

    (from IEEE 551-2006) 934.9 Short circuit total current 954.10 Equivalent impedance for example 3.3 964.11 Excerpt of the famous paper by Charles L. Fortescue 974.12 Illustration of symmetrical components 974.13 Magnitudes of the positive-sequence network 984.14 Symmetrical components of an unbalanced three-phase system 1004.15 Representation of positive-, negative-, and zero-sequence

    impedances 102

    xii Distribution system analysis and automation

  • 4.16 Representation of sequence networks 1034.17 Sequence currents and voltages for different types of faults 1054.18 Single line diagram for example 4.4 1064.19 Positive-sequence diagram for example 4.4 1074.20 Sequence network connection for a single phase fault of example 4.4 1084.21 Solution of example 4.4 by using a software package for a

    three-phase fault 1094.22 Reduced diagrams for the fault analysis in example 4.5 1104.23 Impedance diagram for the three-phase fault in node

    The Ridges 115 kV 1114.24 Solution of example 4.5 by using a software package 1124.25 Diagram for exercise 4.2 1124.26 Diagram for exercise 4.3 1134.27 Diagram for exercise 4.4 1135.1 Repairable components in series both must work for success

    (taken from IEEE Standard 493-2007) 1175.2 Repairable components in parallel one or both must work

    for success (taken from IEEE Standard 493-2007) 1175.3 Diagram system for example 5.1 1185.4 Diagram system results for the first part of example 5.1 1185.5 Diagram system results for the second part of example 5.1 1195.6 An example of network reduction 1205.7 Minimal cut sets of a simple system of figure 5.6 1205.8 Elements of exercise 5.2 1216.1 Two-feeder system showing location of potential opening points 1256.2 Initial topology of case study 1296.3 Optimal topology considering loss reduction 1296.4 System diagram for example 6.2 1316.5 Results for scenario (a) of example 6.2 1336.6 Results for scenario (b) of example 6.2 1346.7 Results for scenario (c) of example 6.2 1356.8 Results for scenario (d) of example 6.2 1366.9 Results for scenario (e) of example 6.2 1376.10 Two-feeder system showing location of switches controlled

    remotely 1396.11 Location of switches in distribution systems 1406.12 Distribution system illustrating loss reduction 1406.13 Normal configuration 1426.14 Fault clearing by relay at B1 step 1 1426.15 Fault isolation by opening corresponding switches step 2 1436.16 Reclosing B1 step 3 (upstream restoration) 1436.17 Reconfiguration by operating switches NO and NC step 4

    (downstream restoration) 1446.18 Three-feeder system illustrating switch location for service

    restoration 1456.19 Time to fix faults for typical systems 145

    List of figures xiii

  • 6.20 Loading for normal condition 1466.21 Loading after reconfiguration 1476.22 Detection of a fault in a FLISR with central intelligence

    (reproduced by permission of ALSTOM) 1486.23 Fault isolation by opening corresponding feeder (reproduced by

    permission of ALSTOM) 1496.24 Upstream restoration (reproduced by permission of ALSTOM) 1496.25 Possible downstream restoration plan with FLISR (reproduced by

    permission of ALSTOM) 1506.26 Selection of the best option for restoration (reproduced by

    permission of ALSTOM) 1506.27 Downstream restoration of healthy distributed system section

    (reproduced by permission of ALSTOM) 1516.28 Example of a FLISR distributed intelligence solution 1516.29 Example of a distribution system with FLISR local intelligence 1526.30 Fault between R03 and R04 1536.31 Final topology after local intelligence operation 1537.1 Rated voltages specified for the United States 1567.2 Voltage regulation limits in the United States 1567.3 Schematic of a single phase 32-step voltage regulator 1587.4 Voltage profile with step-type voltage regulators 1597.5 Diagrams for example 7.1 1617.6 Voltage and current vector diagram for the base case 1627.7 Power diagram for the base case 1627.8 Current profiles for feeders with uniformly distributed loads 1657.9 Distribution feeder with one capacitor bank 1677.10 Distribution feeder with two capacitor banks 1697.11 Distribution system to illustrate application of capacitors 1717.12 Feeder used for the illustration 1727.13 Layout of the feeder used in the modeling 1737.14 Voltage regulator modeling 1747.15 Load flow run for the system used with VVC 1757.16 Components of a VVC assisted with SCADA 1767.17 Integrated Volt/VAR control including distributed generation 1777.18 Context diagram for centralized integrated Volt/VAR control 1777.19 Context diagram for decentralized integrated Volt/VAR control 1787.20 Diagrams for exercise 7.2 1788.1 Connection of equipment producing parallel resonance 1858.2 Connection of equipment producing series resonance 1868.3 Z vs. W in series resonance filters 1878.4 General flow of harmonic currents in radial power system:

    (a) without power capacitor; (b) with power capacitor 1898.5 System example to illustrate harmonic evaluation procedure 1908.6 Simplified diagram of the system 1938.7 (a) Model for fundamental frequency; (b) model for harmonic h 193

    xiv Distribution system analysis and automation

  • 8.8 Circuit for fundamental frequency 1958.9 Circuit for 5th harmonic 1959.1 Time-current operating characteristics of overcurrent relays 2029.2 Overcurrent relay coordination procedure in a distribution system 2039.3 Overcurrent inverse time relay curves associated with two

    breakers on the same feeder 2049.4 Typical ANSI/IEEE and IEC overcurrent relay curves 2069.5 Coordination of overcurrent relays for a Dy transformer 2079.6 Power system of example 9.1 2089.7 Specifications of relay Beckwith M-7651 (reproduced by

    permission of Beckwith Electric) 2099.8 Relay coordination curves for example 9.1 2129.9 Remote supervisory PMH models (reproduced by

    permission of S&C) 2129.10 PME Pad-Mounted Gear (reproduced by permission of S&C) 2139.11 Time-current curves for reclosers 2149.12 Typical sequence for recloser operation 2159.13 Single phase reclosers 2169.14 Three-phase reclosers 2179.15 COOPER Kyle Type VSA20A 2179.16 Option to locate reclosers 2189.17 Illustration of sectionalizers 2209.18 Untanked view of a sectionalizer 2219.19 Sectionalizer application where two feeders of system are protected 2229.20 Sectionalizer application where one branch system is protected 2239.21 Sectionalizer application where one branch system is protected 2269.22 Characteristics of typical fuse links: (a) 200K fuse link;

    (b) 200T fuse link 2279.23 Criteria for fuse-fuse coordination 2299.24 Time-current characteristics for fuse-fuse coordination 2309.25 Criteria for source-side fuse and recloser coordination 2329.26 Criteria for load-side fuse and recloser coordination 2349.27 Coordination of one recloser with three sectionalizers 2349.28 Portion of a distribution feeder 2359.29 Phase-current curves 2369.30 Example of adaptive protection setting with an RTU device 2389.31 Single line diagram for exercise 9.1 2399.32 Single line diagram for exercise 2 24010.1 MOSI model 24410.2 TCP/IP link applying OSI model 24510.3 Communication options in the Smart Grids 24610.4 Message communication OSI-7 stack 24710.5 Virtual and real world 25310.6 Physical and logical device 25310.7 Substation engineering process using SCL language 258

    List of figures xv

  • 10.8 System single line diagram 26010.9 Logic of breaker failure scheme 26110.10 Proprietary configuration tools used for the configuration of IEDs 26210.11 Test connections used for standalone IEC 61850based IED 26310.12 Substation network process bus and station bus 26411.1 Information exchange between two application elements (taken

    from IEEE 2030-2011) 26711.2 Example circuit (a) as a line diagram and (b) with full CIM

    mappings 26911.3 Transformer class diagram 27011.4 Example of (a) power system representation and (b) CIM/XML

    representation 27211.4 Continued 27311.5 Elements for implementing interoperability in information systems 27411.6 Stages in a CIM implementation 27412.1 Some organizations that use the SGMM (taken from the

    Carnegie Mellon Software Engineering Institute) 27712.2 Example of results obtained by applying the SGMM 27812.3 Example of results in Grid Operation (GO) domain 28312.4 Example of results in a radar chart 285

    xvi Distribution system analysis and automation

  • List of tables

    1.1 Example of outage data 81.2 International comparison of quality indices in 2007 101.3 Database for exercise 1.1 113.1 Values for example 3.5 533.2 Values of voltages for example 3.6 603.3 Values of impedances for example 3.6 603.4 Initial input data for example 3.6 613.5 Rated bus voltages for example 3.7 683.6 HV transformer data for power system of example 3.7 693.7 MV transformer data for power system of example 3.7 703.8 Generator data for power system of example 3.7 703.9 Bus data for power system of example 3.7 703.10 Line data for power system of example 3.7 716.1 Data of feeders encompassed within the prototype 1266.2 Result of reconfiguration analysis 1276.3 Options where the highest loss reductions are obtained 1286.4 Load data for example 6.2 1326.5 Line data for example 6.2 1326.6 Comparison of reliability data for node N11 under different

    scenarios 1386.7 Reconfiguration options for system of example 6.3 1446.8 Loading values of example 6.4 1477.1 Comparison of results for example 7.1 1647.2 Comparison between shunt capacitor and series capacitor 1657.3 Results of software simulation 1728.1 Summary of power quality variation categories (reproduced

    by permission of DRANETZ) 1808.2 Categories and typical characteristics of power system

    electromagnetic phenomena (taken from IEEE Standard1159-2009) 182

    8.3 Harmonic voltage distortion limits in percent of nominalfundamental frequency voltage (taken from IEEEStandard 519-1992) 187

    8.4 Current distortion limits (taken from IEEE Standard 519-1992) 1888.5 Summary of results for example 8.1 1978.6 Currents for different harmonic orders 199

  • 9.1 IEEE and IEC constants for standard, overcurrent relays 2059.2 Summary of fault conditions 2069.3 Short circuit calculation for power system of example 9.1 2109.4 Summary of relay settings for example 9.1 2119.5 Maximum fault current in amperes, rms in S&C Standard

    Speed Fuse Links 2319.6 K factor for the source-side fuse link 2329.7 K factor for the load-side fuse link 23310.1 Protection logical nodes defined by IEC 61850-7-4 Edition 25410.2 Protection logical nodes defined by IEC 61850-7-4 Edition 25511.1 Architecture of the principles of interoperability (taken from

    EPRI and NIST) 26612.1 Example of results after applying the SGMM 285

    xviii Distribution system analysis and automation

  • Chapter 1

    Smart Grid overview

    Smart Grid (SG) is a rather new concept that includes aspects of energy generation,transmission and distribution and aims for a more reliable service, higher effi-ciency, more security, two-way utility-user communications, and promotion ofgreen energy, among other goals.

    When the term Smart Grid was first used, some people associated it withremote metering, which was later called AMR (automatic meter reading). Theactivities of AMR were encompassed within those of a broader field that waseventually called AMI (advanced metering infrastructure). Clearly, the meteringsystem is one of the major elements of the Smart Grid, but certainly is not the onlyone. Many elements are included in the overall field of Smart Grids. Those per-taining to distribution systems and in particular to the automation of distributionsystems (or distribution automation) will be considered in this book.

    1.1 Smart Grid for distribution systems

    Distribution systems operated for many years autonomously, with only occa-sional manual setting changes and a rather primitive automation that is knowntoday as local intelligence. Automation in fact was first implemented ongeneration and transmission systems and gradually became popular also on dis-tribution systems.

    A good example of local intelligence is that used in reclosers operating incoordination with sectionalizers. After a local fault, reclosers start a set of reclosingoperations, before locking out. Other good example is the operation of capacitorbank switches which rely on local signals, such as voltage level, power factor, oreven time.

    Recently, in response to the growing demand to improve reliability andefficiency of the power system, more automation was introduced to distributionsystems.

    The Smart Grid policy requirements as outlined in the Energy Independenceand Security Act (EISA) of December 2007 give a better understanding of thebenefits and challenges of distribution automation for all of its stakeholders.

    The ideas behind Smart Grids evolved from greater attention that distributionsystems started to receive in the 1980s. Until then most of the attention was

  • given to generation and transmission systems. Figure 1.1, taken from the paperAutomated power distribution by Arthur C.M. Chen, published by IEEE spec-trum in April 1982, shows a representation of a projected distribution system. Thepaper anticipated immediate detection and isolation of a faulted feeder and areduction of the amount of time a line crew should spend to locate and fix it. It alsoreferred to the increase of more distributed generation, called by then as dispersedstorage and generation (DSG) systems. Finally, the paper made a point on theimportance of distribution automation for maintaining a reliable supply and toreduce operating costs. It is really interesting to see how all those provisions is nowa reality.

    Battery or fuel cells, 1 to 25 MW

    Solar or wind

    sources (100 kW to

    1 MW)

    Photovoltaic power supply, up

    to 100 kW

    Generation plants

    Step-up transformers

    Circuit breakers

    Transmission system

    Transformers in bulk powersubstation

    Dispersed storage and generation

    (DSG)

    Subtransmission system

    DSGDistribution substation

    Three-phase, primary feeder

    Sectionalizing switchPrimary

    circuits

    One-phase, lateral feeder

    Distribution transformer

    Services

    HomeDSG

    Figure 1.1 Power system as envisaged in 1982 (from Automated powerdistribution, published by IEEE Spectrum, April 1982)

    2 Distribution system analysis and automation

  • Governments and utilities funding the development and modernization of gridshave defined the functions required for Smart Grids. According to the United StatesDepartment of Energys Modern Grid Initiative Report, a modern Smart Grid mustsatisfy the following requirements:

    motivate consumers to actively participate in operations of the grid, be able to heal itself, resist attack, provide a higher quality power that will save money wasted during outages, accommodate all generation and storage options, enable electricity markets to flourish, run more efficiently, enable higher penetration of intermittent power generation sources.

    In order to achieve the goals of Smart Grid mentioned above and in particularthe improvement in reliability, security, and efficiency, it is essential to havea well-developed digital technology. Among the significant challenges facingdevelopment of a Smart Grid are the cost of implementing it, and the new standardsthat regulatory bodies have to enact. Interoperability standards certainly willallow the operation of highly interconnected systems that include distributed gen-eration plants.

    Another big difficulty that the implementation of Smart Grid and distributionautomation faces is the huge variety of technologies produced by multiple vendors.Establishing a proper development path is highly recommended to any utilitybefore embarking on a comprehensive project. Maturity models that are discussedin a latter chapter help to establish this plan.

    The implementation of the new technologies of Smart Grid will bring aboutchanges that need to be addressed. For example, the connection of small generationplants on distribution feeders will bring the possibility of having short circuit cur-rents in two ways, and therefore the feeders should not be regarded as radial anylonger. Problems with reclosing features should be closely examined to avoid out ofsynchronism closing. Likewise, the connection of charging stations for electricalvehicles (EV) will change the normal operation of the feeders.

    Smart Grid has the great advantage of allowing two-way communication, i.e.utility-user and user-utility. This will allow a more friendly and effective rela-tionship between the user and the utility. The latter will be able to monitor andcontrol small appliances of each user. The user will have in turn the great advantageof getting information regarding the consumption level, new rates available, andload management schemes. This of course would require powerful communicationsystems that need to be flexible and reliable.

    1.2 Definitions of Smart Grid

    Many definitions have been written to describe Smart Grids. Every utility mighthave its own definition. Some possible meaningful definitions are the following.

    Smart Grid overview 3

  • EPRI: The Intelligent GridAn intelligent electric power delivery infrastructure (Intelligent Grid) that

    integrates advances in communications, computing, and electronics to meetsocietys electric service needs in the future.

    Xcel Energy: The Smart GridWhile details vary greatly, the general definition of a Smart Grid is an

    intelligent, auto balancing, self-monitoring power grid that accepts any source offuel (coal, sun, wind) and transforms it into a consumers end use (heat, light, warmwater) with minimal human intervention.

    It is a system that will allow society to optimize the use of renewable energysources and minimize our collective environmental footprint.

    It is a grid that has the ability to sense when a part of its system is overloadedand reroute power to reduce that overload and prevent a potential outage situation,a grid that enables real-time communication between the consumer and utilityallowing us to optimize a consumers energy usage based on environmental and/orprice preferences.

    DOE (Department of Energy) DefinitionAn automated, widely distributed energy delivery network, the Smart

    Grid will be characterized by a two-way flow of electricity and information andwill be capable of monitoring everything from power plants to customerpreferences to individual appliances. It incorporates into the grid the benefitsof distributed computing and communications to deliver real-time informationand enable the near-instantaneous balance of supply and demand at the devicelevel.

    People are often confused by the terms Smart Grid and smart meters. Arethey not the same thing? Not exactly. Metering is just one of hundreds of pos-sible applications that constitute the Smart Grid; a smart meter is a good exampleof an enabling technology that makes it possible to extract value from two-way communication in support of distributed technologies and consumerparticipation.

    The BC Hydro Definition of Smart GridSmart Grid refers to a modern, intelligent electricity transmission and dis-

    tribution system that incorporates traditional and advanced power engineering toenhance grid performance and support a wide array of functionality for customersand the economy. In other words: modernization and automation of the currentpower delivery system.

    In summary, Smart Grid refers to a sustainable modernization of the electricitygrid, integrating information and communication technologies to intelligentlymanage and operate generation, transmission, distribution, consumption, or eventhe electric energy market. The components are shown in Figure 1.2.

    The Smart Grid concept comprises many or almost all of the elements ofthe utility and the relationships among the elements that constitute them. Figure 1.3includes some of these elements, like smart meters, generation, transmission, sub-station, and feeders.

    4 Distribution system analysis and automation

  • SmartGrid

    Electrical components

    ITCommunications

    Figure 1.2 Smart Grid concept

    Smart Grid

    Smart meters

    Smart generation Smart feeders

    Smart substationSmart transmission

    Figure 1.3 Smart Grid components

    Smart Grid overview 5

  • 1.3 Benefits of the Smart Grid on distribution systems

    The benefits of implementing a Smart Grid are many. They can be summarized inthe following categories.

    1.3.1 Enhancing reliabilityThe Smart Grid dramatically reduces the cost of power disturbances. This can beachieved by means of system reconfiguration using switches placed along thefeeders. Communications and control technologies greatly help to isolate faults andallow more rapid restoration of service.

    1.3.2 Improving system efficiencyThe reduction of losses in electrical systems, both technical and non-technical, is apurpose of every utility in the world. It not only reduces the demanded power butalso contributes to the environment. The reduction of system losses results in capitaldeferral which gives an attractive payback of the investments. Power capacitors,voltage regulators, and proper design criteria are required to achieve this.

    1.3.3 Distributed energy resourcesConstruction of generation plants at the user level is every day more frequent.These sources are referred to as distributed generation or distributed energyresources and are getting much attention from government authorities and envir-onmental institutions as they alleviate the pollution levels that some plants have, inparticular those burning coal and oil. Distributed energy resources also contributeto better operating conditions of distribution systems as they are sources connecteddirectly to the users loads, increasing control of the voltage.

    1.3.4 Optimizing asset utilization and efficient operationReal-time data makes it possible to more effectively utilize assets during bothnormal and adverse conditions and to reduce the costs of outages. This results in alonger service life of the assets.

    1.4 Quality indices

    Quality indices, also called reliability indices, measure the performance of a powersystem. The most important benefit of Smart Grids is that they improve reliabilityperformance of power systems. Given the importance of these indices to enhance aSmart Grid, a proper consideration to their meaning and application is explained inthis section.

    Several key definitions relating to distribution reliability include:

    Fault: an abnormal operating condition of an electrical system which normallydevelops a short circuit. It can be caused by natural events, rough weather

    6 Distribution system analysis and automation

  • conditions, animal presence, equipment failure, and even vandalism. Faults canbe categorized as self-clearing, temporary, and permanent. A self-clearingfault will extinguish itself without any external intervention. A temporary faultwill clear if de-energized and then re-energized. A permanent fault lasts untilrepaired by human intervention.

    Contingency: an unexpected event such as a fault or an open circuit. Anotherterm for a contingency is an unscheduled event.

    Outage: An outage occurs when a piece of equipment is de-energized. Outagescan be either scheduled or unscheduled. Scheduled outages are known inadvance (e.g., outages for periodic maintenance). Unscheduled outages resultfrom contingencies. Different utilities have different criteria to define an out-age. Some utilities consider outages those interruptions that exceed 1 min.Others use 2 min and other up to 5 min.

    Open circuit: a point in a circuit that interrupts load current without causingfault current to flow. An example of an open circuit is the false tripping of acircuit breaker.

    Momentary interruption: a momentary interruption occurs when a customer isde-energized for a very short time of period, usually less than a minute. Mostmomentary interruptions result from reclosing or automated switching. Mul-tiple reclosing operations result in multiple momentary interruptions.

    Sustained interruption: a sustained interruption occurs when a customer isde-energized for normally for more than one minute. Most sustained inter-ruptions result from open circuits and faults.

    Poor reliability on the part of the electrical utility is penalized based onquantification by reliability indices. Some utilities also pay bonuses to utility per-sonnel, based on outstanding performance. Commercial and industrial customersinquire about reliability indices when locating a new facility. Most regulatorybodies have established targets for reliability indices. If utilities do not fulfill them(have figures higher than those defined), they can be penalized. The most importantindices to measure the reliability performance are the following:

    1.4.1 System Average Interruption Duration Index (SAIDI)SAIDI is defined as the average interruption duration for customers servedspecific time period, which normally is a year. It is calculated by summing thecustomer minutes off for each interruption during a specified time period anddividing the sum by the average number of customers served during the period.The unit is minutes.

    The index enables the utility to report the time (normally in minutes) custo-mers would have been out of service if all customers were out at one time. Thebenchmarking survey SAIDI average for the United States is around 90 min.

    SAIDI P

    Customer Interruption DurationsTotal Number of Customers Served

    min 1:1

    Smart Grid overview 7

  • 1.4.2 System Average Interruption Frequency Index (SAIFI)SAIFI is defined as the average number of times that a customer is interruptedduring a specific time period, which also is a year. It is calculated by dividingthe total number of customers interrupted in that time period by the averagenumber of customers served. (This means outages per customer, not the number ofinterruptions.)

    The resulting unit is interruptions per customer. The benchmarking surveySAIFI average for the United States is around 1.2 interruptions per customer peryear.

    SAIFI Total Number of Customer InterruptionsTotal Number of Customers Served

    1:2

    1.4.3 Customer Average Interruption Duration Index (CAIDI)CAIDI is the ratio of the SAIDI over the SAIFI and is defined with the followingexpression:

    CAIDI P

    Customer Interruption DurationsTotal Number of Customer Interruptions

    min 1:3

    Example 1.1: Table 1.1 shows an excerpt from one utilitys customer informationsystem (CIS) database for feeder 25, which serves 1500 customers with a total loadof 3 MW. In this example, Feeder 25 constitutes the system for which the indicesare calculated. More typically the system combines all circuits together in aregion or for a whole company.

    Table 1.1 Example of outage data

    Date Time Time on Total time(min)

    Circuit Eventcode

    Number ofcustomers

    Load(kVA)

    Interruptiontype

    2/15 14:10:17 14:25:39 15.37 25 51 250 431 S4/20 17:20:39 17:38:41 18.03 25 306 368 800 S5/1 06:33:36 07:14:49 41.22 25 468 23 150 S6/2 23:18:10 23:18:57 0.78 25 522 590 1200 M6/8 02:39:52 03:55:34 76.63 25 634 87 200 S9/29 09:29:05 09:30:02 0.95 25 811 1500 3000 M11/14 17:15:49 17:16:18 0.48 25 963 700 1500 M12/4 12:16:32 13:01:44 45.2 25 1021 1000 1800 S

    S indicates a sustained interruption; M, a momentary interruption.

    8 Distribution system analysis and automation

  • Applying the previous equations it is possible to find these quality indices.

    SAIFI 250 368 23 87 10001500

    1:152

    SAIDI 15:37 250 18:03 368 41:22 23 76:63 87 45:2 10001500

    42:2 min

    CAIDI SAIDISAIFI

    42:21:152

    36:63 min

    1.4.4 Momentary Average Interruption Frequency Index (MAIFI)and Momentary Average Interruption Event FrequencyIndex (MAIFIE)

    The MAIFI as defined by IEEE Standard 1366-2003 indicates the average fre-quency of momentary interruptions. Mathematically, this is given in the followingequation:

    MAIFI P

    Total Number of Customer Momentary InterruptionsTotal Number of Customers Served

    1:4

    The MAIFIE, as defined by the same IEEE Standard, indicates the averagefrequency of momentary interruption events, not including the events immediatelypreceding a lockout. Mathematically, this is given by the following equation:

    MAIFIE P

    Total Number of Customer Momentary Interruption EventsTotal Number of Customers Served

    1:5To calculate these indices, the following equations can be used:

    MAIFI P

    IMiNmiNT

    1:6

    MAIFIE P

    IMENmiNT

    1:7

    where:

    IMi Number of momentary interruptionsIME Number of momentary interruption eventsNmi Number of interrupted customers for each momentary interruption event

    during the reporting periodNT Total number of customers served for the areas

    Smart Grid overview 9

  • Example 1.2: To better illustrate the concepts of momentary interruptions, sustainedinterruptions, and the associated indices, consider Figure 1.4. The figure illustrates acircuit composed of a circuit breaker (B), a recloser (R), and a sectionalizer (S).

    For this scenario, 1000 customers would experience a momentary interruptionand 500 customers would experience a sustained interruption. Calculations forSAIFI, MAIFI, and MAIFIE on a feeder basis are shown in the following equations.Notice that the numerator of MAIFI is multiplied by 2 because the recloser tooktwo shots. However, MAIFIE is multiplied by 1 because it only recognizes that aseries of momentary events occurred.

    SAIFI 5003000

    0:167

    MAIFI 215003000

    1

    MAIFIE 115003000 0:5

    Table 1.2, taken from the paper Electricity Reliability: Problems, Progressand Policy Solutions by Galvin Electricity Initiative, February 2011, presents agood comparison of reliability indices from European countries.

    1500 Customers 1000 Customers 500 Customers

    3 Operations 2 Operations

    Withoutinterruption

    MomentaryInterruption

    SustainedInterruption

    (B) (R) (S)

    Figure 1.4 Representation of events used in calculating indices

    Table 1.2 International comparison of quality indices in 2007

    Country SAIDI SAIFI

    United States 240 1.5Austria 72 0.9Denmark 24 0.5France 62 1.0Germany 23 0.5Italy 58 2.2Netherlands 33 0.3Spain 104 2.2UK 90 0.8

    10 Distribution system analysis and automation

  • Proposed exercise

    1. Table 1.3 shows database for feeder 43, which serves 3500 customers with atotal load of 5 MW. Complete the table and calculate the quality indices SAIFI,SAIDI, and CAIDI.

    Table 1.3 Database for exercise 1.1

    Date Time Time on Total time(min)

    Number ofcustomers

    Load(kVA)

    Interruptiontype

    1/23 13:24:28 14:45:43 343 5672/28 12:15:46 12:23:58 576 7763/11 04:06:09 04:07:02 102 1203/11 18:23:24 19:01:01 102 1203/18 01:03:43 01:53:24 432 6834/10 12:13:56 12:13:59 1500 24804/30 08:20:18 08:20:56 700 13155/02 05:40:11 05:44:23 1400 22696/29 03:56:32 04:38:12 1973 29848/12 17:48:39 17:59:04 2534 35428/13 13:08:02 14:09:01 28 358/13 13:25:36 13:56:26 28 359/22 23:49:27 23:54:24 1769 2647

    10/16 20:09:37 20:44:55 2046 301812/05 19:31:15 19:31:46 378 588

    Smart Grid overview 11

  • Chapter 2

    Distribution automation functions

    Distribution automation started in the 1970s. It allows utilities to implementmodern techniques in order to improve the reliability, efficiency, and quality ofelectric service. Distribution automation is also referred to as feeder automation. Ithas been defined by the IEEE as follows: Distribution Automation is a system thatenables an electric utility to remotely monitor, coordinate and operate distributioncomponents in a real-time mode from remote locations.

    Distribution automations main applications are categorized into four groups:the first group is fault location and automatic sectionalizing/service restoration,which primarily depends on a switchgear as illustrated in Figure 2.1. The second isVolt/VAR control and optimization, which mainly employs voltage regulators andcapacitors. The third is the integration of distributed generation, which requiresappropriate protection equipment and a robust SCADA system among other com-ponents. Finally, the last group is associated to the advanced asset management,where sensors and metering devices are necessary. Figure 2.2 shows the applica-tions and the benefits rendered by the implementation of the four groups.

    Distribution automation, commonly known as DA, has evolved into advanceddistribution automation, known as ADA, which incorporates advanced commu-nication schemes, new computer technology, state-of-the-art equipment techno-logies and high-speed power electronic devices.

    2.1 Electrical system automation

    Automation of power systems can be handled from control centers connected togeneration and transmission systems on one hand and to distribution systems on theother. It could be said that they meet at the HV/LV substations which also featuretheir own automation. This is shown in Figure 2.3.

    Control centers for generation/transmission systems and for distributionsystems are handled by using software applications customized for each appli-cation. They are referred to as energy management systems (EMS) and dis-tribution management systems (DMS), respectively. These are illustrated inFigure 2.4.

  • Figure 2.1 Typical installation of a switch on an overhead distribution feeder

    Distribution automation benefits

    AMI &reliability

    Fault location, isolation, and system

    restoration

    - Metering management- Reduce outage duration- Reduce number of outages- Improve quality indices

    System efficiency Volt/VAR control

    - Reduce line losses- Fulfill voltage profile regulation

    Effective DG integration

    Inverters, numerical protection, SCADA, and other technology

    options

    - Improve impact from ER- Improve power quality - Improve reliability

    Advanced asset management

    Sensors to determine maintenance program

    according to condition-based status

    - Reduce maintenance expenses- Reduce associated failure expenses- Deferral of replacement

    Figure 2.2 Main benefits of distribution automation

    14 Distribution system analysis and automation

  • 2.2 EMS functional scope

    The EMS is based on two main subsystems, supervisory control and data acquisi-tion (SCADA) and network analysis. Each one incorporates several applications asfollows:

    The SCADA subsystem incorporates applications like multiple remote terminalunit (RTU) protocols in a non-proprietary environment, load shed, sequence-switching management, and disturbance storage and analysis. The network analysis

    Generation and transmissionautomation

    Distributionautomation

    Controlcenter

    Controlcenter

    Substationautomation

    Communications

    Figure 2.3 Power system automation components

    Generation andtransmission

    Distribution

    EMSComprehensive set of applications dedicated to HV network operations

    DMSComprehensive set of applications dedicated to MV network operations

    Figure 2.4 Network management EMS/DMS

    Distribution automation functions 15

  • applications offer the possibility of obtaining power flow, state estimation,contingency analysis, short circuit, security enhancement, optimal power flow, andVolt/VAR dispatch information. Figure 2.5 presents a typical screen shot of an EMS.

    2.3 DMS functional scope

    The SCADA subsystem offers functions like feeder topology, coloring and circuittracing, and mesh detection. The network analysis offers functions like real-time andpower flow (balanced or unbalanced), short circuit, Volt/VAR control and optimalVVC, automatic online feeder reconfiguration, fault location and automatic servicerestoration, protection system, substation automation, customer load management,advanced metering infrastructure/automated meter reading, demand side manage-ment, and load management. Figure 2.6 presents a typical screen shot of a DMS.

    2.4 Functionality of DMS

    The functionality of DMS can be divided into steady-state performance improve-ment and dynamic performance improvement.

    2.4.1 Steady-state performance improvementIn this section the main functions associated with the analysis of the steady-stateperformance of the system are considered. These functions are characterized byfulfilling targets previously defined in planning studies.

    2.4.1.1 Volt/VAR controlVolt/VAR control deals mainly with the detection and prediction of voltageviolations which require close control of the relationship between the voltageand the reactive power equipment. The equipment involved includes mainly

    Figure 2.5 Screen shots of a typical EMS

    16 Distribution system analysis and automation

  • capacitor, static VAR control (SVC) devices, load tap changers and voltageregulator controls.

    2.4.1.2 Feeder reconfigurationFeeder reconfiguration refers to the operation of switches, breakers, or reclosers toreconfigure the topology of feeders and improve the operating condition of thesystem. It is done under normal conditions in order to reduce losses and increasereliability. It also helps to minimize voltage drop on the feeders. Feeder reconfi-guration represents great benefits. However, it is not always possible to achieve allthe objectives simultaneously.

    2.4.1.3 Demand side management (DSM)DSM refers to a method for controlling the load at the users premises, based on anagreement previously established with the utility.

    2.4.1.4 Advanced metering infrastructure (AMI)/automatic meterreading (AMR)

    AMI/AMR plays an important role as it aids utilities in establishing competitivestrategies that conduct load profile gathering in order to characterize the value ofindividual customers to the utility. It identifies the major customers (aggregatedload) and offers load information to customers as a special service.

    One of the technologies used by AMI is power line communication PLC that uses the wires of the distribution system including the customers incominglines. The signal rides on the fundamental power line frequency and modulationoccurs at the zero-cross. It does not require repeaters or line conditioningequipment, resulting in lower installation costs. This technology does not affectpower quality. Figure 2.7 illustrates a typical PLC system that uses the technol-ogy known as TWACS (two-way automatic communication system). This systemuses modulation for the outbound signals and modulation for inbound signals asshown in Figure 2.8.

    Figure 2.6 Screen shots of a typical DMS

    Distribution automation functions 17

  • 2.4.2 Dynamic performance improvementIn this section the main functions associated with the analysis of the dynamicperformance of the system are considered. These functions are characterized byactions to be taken during faults, unpredicted events, and emergency conditions.

    2.4.2.1 Fault location, isolation, and service restoration (FLISR)The use of automated feeder switching aids in detecting feeder faults, determiningthe fault location (between two or more switches), isolating the faulted section ofthe feeder, and providing the possibility of restoring service to healthy portionsof the feeder.

    Service restoration allows to find alternate options to quickly restore power tohealthy parts of the system making sure that voltage levels are within acceptedranges and that any overload is avoided. Cold load pickup has to be considered forlong outages in order to avoid tripping when re-energizing the feeders. Customerprioritization is carefully considered.

    Meter retrofittedwith module

    CSS

    Client workstations

    (PC)SCADA, meter data management, outage management systems and/or other platforms

    TWACS net server (TNS) master station Distribution

    substation

    Telecommunications link

    Powerlines

    TWACS substation control equipment

    Serviceto home

    PPL net

    Figure 2.7 Illustration of power line communication (PLC)

    V

    Outbound bit

    I1 3 5 7

    42 6 8

    Inbound bit

    (a) (b)

    Figure 2.8 (a) Modulation for the outbound signal; (b) modulation for theinbound signal

    18 Distribution system analysis and automation

  • Automating this process renders immense benefits as the outage time is greatlyreduced, as shown in Figure 2.9.

    2.4.2.2 Trouble call systemWhen a fault occurs, protective relays and fault locators should raise the corre-sponding alarms that outages have occurred. However, the report of users affectedis very important not only to reaffirm the fault occurrence but also to help locatingit more quickly.

    Utilities now have modern facilities where the calls from users are readilyreceived, classified, and matched with the database of the billing system to identifyother users who may be associated with the problem. Thus, they can achievesolution schemes that identify and involve all the customers affected by the event.These facilities are trouble call systems that are manned but assisted with state-of-the-art communication and software capabilities. A typical process of a TCS isillustrated in Figure 2.10, which requires a close relationship with the customerinformation system (CIS).

    2.4.2.3 Alarm triggeringAlarms are triggered by the operation of the protection relays. They send codedinformation to distribution control centers so that operators are aware of what ishappening on the network. Other alarms indicate the state of the power system, forexample, voltages at various locations and load flows on the more important cir-cuits. These alarms provide one of the main sources of information flowing in realtime into a distribution control center and are normally channeled to one printer inthe control room where a hard copy can be produced. The alarm streams are alsochanneled to the operators or control engineers console where they can be dis-played on computer screens.

    100

    50

    150100500

    Minutes

    25

    75

    Restoration time considering DA

    Restoration time with manual procedure

    Outage %

    Figure 2.9 Comparison of restoration time with and without DA

    Distribution automation functions 19

  • A third avenue for alarm streams is storage in a data logger where the principalfunction is to retain a history of the alarm streams. This can be used for post-systemfault analysis if it is needed later.

    It is worth nothing that, with this arrangement, the alarms are not processed.Several events may occur simultaneously, or at a close time proximity with respectto each other, and each incident may trigger many alarms resulting in a largenumber of alarms flowing into the control center in close succession. The operatorwould then have to use his judgment to determine what has happened to the system.Subsequent telephone calls from customers may also help to determine the exactlocation of these incidents such as a blackout in a certain district. The aim of analarm processor is to help the operator to arrive at a sensible conclusion speedilyand to discard redundant information in the alarm streams.

    2.4.2.4 Work ordersIn order to expedite the coordination of crews responsible for the maintenance orfeeder fixing, a proper work order system is essential. After a fault is reported, thesystem should be capable of automatically locating the most convenient crew andtraveling means, and to determine the essential elements required to reestablish serviceas quickly as possible. This requires a proper coordination with the DMS, the resourcescheduler, and the operation manager of the utility, as depicted in Figure 2.11.

    2.5 Geographic information system

    A geographical information system (GIS) can integrate, store, edit, and displaygeographically referenced information. A GIS may be linked to the online envir-onment of a DMS. An example is shown in Figure 2.12.

    T C S

    D M S

    Controls Data acquisition

    Call

    Callback

    Low voltagemaintenance

    crews

    Customers

    Phone operatorsand

    analysts

    Billing infoLV connectivity

    Call handling

    Problemanalysis

    and dispatch End of task

    Task assignment

    Medium voltagenetwork

    PotentialMV network

    problems

    Investigationresults

    and known outages

    CIS

    Figure 2.10 Trouble call system

    20 Distribution system analysis and automation

  • FM/Work orders

    D M SOperationplanning

    department

    Work crewssafety personnel

    MV network

    Status Controls

    Remote controlstagsOutages

    Operationmanager

    Resources scheduler

    Figure 2.11 Work order illustration

    Figure 2.12 Example of a GIS

    Distribution automation functions 21

  • 2.5.1 AM/FM functionsAutomated mapping/facility management (AM/FM) is a specific application of theGIS aimed at providing database query and graphical user interface (GUI) forefficient management of distribution system devices. It involves activities related togeographical and electrical maps.

    2.5.2 Database managementGIS systems require a computerized mapping system with the capability of storingand displaying the geographic locations of customers, feeder sections, substations,and/or pieces of equipment.

    2.6 Communication options

    DMS may employ a variety of communication mediums such as cooper wires, fiberoptics, VHF and UHF radio, satellites, microwaves, cellular communications, Wi-Fi,and WiMAX.

    Rapid advances in wireless, cellular, and satellite systems will soon providecost-effective solutions for enterprise connectivity. Figure 2.13 illustrates differenttypes of communication.

    2.7 Supervisory control and data acquisition

    SCADA is designed to achieve control and monitor processes remotely. This sys-tem is based on remote data acquisition.

    SCADA applications are globally accepted as a real-time power systemmonitoring and control tool, especially in generation, transmission and distribution

    Transmitterreceiver

    Transmitterreceiver

    Electrical telecom cables

    Fiber optic cables

    Radio systems

    Power and distribution line carrier

    Satellite

    Figure 2.13 Typical communication methods

    22 Distribution system analysis and automation

  • systems. The RTU collects telemetry analog data and the status of devices in thesubstations, and communicates control commands. It is installed in a central loca-tion such as the control center of the utility with GUI, engineering applicationsmanaging history software, and other components.

    SCADA describes a technique whereby computers are used to collect real-timedata from plant machinery and/or to control plant machinery in real time. Typicallythis is done through the use of programmable logic controllers (PLCs). Figure 2.14presents a common SCADA arrangement.

    Recent trends in SCADA systems provide greater situational awarenessthrough improved GUI, data presentation and information, intelligent alarm pro-cessing, improved integration with other engineering processes and business sys-tems, and enhanced security functions.

    2.7.1 SCADA functionsDMS/EMS integration with SCADA is a growing trend. The main functions ofSCADA systems are:

    supervisory control, data acquisition and processing, sequence of events (SOE) registry, misoperation revision, tagging, alarm processing, historical information system.

    Remoteworkstation

    Network control systemOffice network

    Workstations

    LAN

    Process units

    Process unitsProtection relays

    System servers hot stand -by

    Redundantcommunicationservers (front ends)

    Disconnector terminal unit

    Communicationgateway

    Substationautomation

    system

    Substationautomation

    system

    Figure 2.14 SCADA illustration

    Distribution automation functions 23

  • 2.7.1.1 Supervisory controlSCADA controls the operation equipment (switches, breakers) in locations remotefrom the control center. This includes operation, commands, open/close commands,and set point control.

    The control should include a selection sequence and verification beforeoperation (select-check-back-before-operate SCBO). In this case the user selectsthe equipment to be controlled using SCADA and the operation to be conducted.The operator observes the result of the operation in SCADA. The option to cancelthe command should be available. The user is able to manually update the state ofall control points that are not telemetry-related.

    Commands executed by the user are registered at the time they occur and theyare stored in a historic file for future use, and in the historical information system(HIS). Each event is identified by date, time, device name, device ID, and operationtime. All failed remote command actions are identified as alarms.

    The selected Intelligent Electronic Devices (IEDs) use a process that meets thesupervisory functional control requirements. The following factors should be takeninto consideration:

    The time delay after the command has been sent or received from a commu-nication point.

    The time delay after a command has been executed before another commandcan be initiated.

    The backup for multiple control points per command.

    Figure 2.15 is a good illustration of a SCADA operating on different pieces ofequipment in a distribution system, following orders received from applicationpackages.

    Distribution system

    Remote control switch (RCS)

    Line recloser AVR Capacitor bank

    Open-close On-off recloser Raise-lower tapSend set-point control On-off

    Figure 2.15 SCADA functions: supervisory control

    24 Distribution system analysis and automation

  • 2.7.1.2 Data acquisition and processingFigure 2.16 depicts a display of a SCADA system showing data acquisition in adistribution utility.

    SCADA systems require a reliable connection with databases that have infor-mation about the system and the users. Connection with packages having theintelligence or the software is essential to performing the appropriate operations.Figure 2.17 shows the interaction of a SCADA with other information packages ofthe system.

    Device status (e.g., on, off)

    Digital measurement, e.g.,binary code decimal (BCD) of transformers tap position

    Energy

    Acquisition capabilities Polling By exception By contention Forced scan

    Analog measurement (V, I, P, Q, PF)

    Figure 2.16 SCADA functions: data acquisition

    SCADA

    Energyaccounting

    Historicalinformation

    system

    Applications

    Externalcommunication

    Wireless alarming

    Alarmingtelecontrol monitoring

    Figure 2.17 Relationship of SCADA with databases

    Distribution automation functions 25

  • The data acquisition function is employed to supervise the state of the equip-ment, and measure different equipment parameters and external SCADA systems.These states and measurement data are viewable to the operators and also availablefor other functions.

    The SCADA/DMS/EMS/GMS system master station obtains data from thedata concentrators. Data acquisition is conducted through a private WAN dedicatednetwork for IEDs and SCADA/DMS/EMS communications and a wireless datanetwork with IP technology dedicated to IEDs.

    These two networks should support TCP/IP or UDP/IP protocols. IEC 60870-5-104 or IEC 61850 protocols are normally used for all substations. The substationdata concentrator in addition to obtaining data from auxiliary services should bedesigned to question the distribution network IEDs. The communication protocol istypically DNP 3.0 or IEC 61850.

    The data obtained from each IED includes:

    states (operation state, breaker position, switch position, recloser, alarms, etc.), SOE data (high precision event data timestamp), metering (currents, voltages, MW, MVAR, frequency, transformer MW and

    MVAR, transformer tap position, etc.), alarms (overvoltage, undervoltage, high frequency, low frequency, etc.), input change processing time.

    2.7.1.3 Sequence of events (SOE) registryThe distribution system SCADA has the ability to store SOE data for specificevents. The SOE information includes relay operation analysis and alarms aspart of the equipment operation analysis. The SOE events messaged are similar tothe alarm messages, but they will be accurate to the millisecond, for example17:31:19.509.

    The SOE data obtained are stored in chronological order in the HistoricalInformation System (HIS) database and reported individually.

    2.7.1.4 Misoperation revisionThe misoperation revision consists of the creation and continuous update of theevent file. Every 10 sec, a picture of the operator-selected points or the real-timedatabase is stored in the event file which consists of three files: the pre-event,event, and post-event period.

    The file size is determined by the time period covered by the recording, theamount of data to be stored, and the available space on the disk. The recommendedtime frame is 10 min for the pre-event, 15 for the event period, and 15 min for thepost-event period.

    2.7.1.5 TaggingThe control center SCADA labels each specific event, monitored or not, on a graph.Each label represents the attention of a device using a graphical symbol indicatingwhat the remote control is for such device. Different labels are normally used toclassify devices in a priority order that refers to the open and close controls.

    26 Distribution system analysis and automation

  • 2.7.1.6 Alarm processingThe alarms detected by the data acquisition functions are managed in such a waythat the predetermined alarm conditions are reported clearly and promptly only forthe work station that needs the information.

    The alarm management is supported by priority levels. When an alarm ispresented, its responsibility area and priority will be displayed.

    The alarms and events are saved daily and stored in the HIS for later reference.The alarms are presented in a single line diagram with screen visualization usingsymbols or color changes.

    2.7.1.7 Historical information systemTraditional methods to collect historical data included chart recorders, operatorlogs, and alarm printers. Trends and historical databases can be constructed withthe help of SCADA data. Reports, for example, can include compliance reports,operation reports, asset management, and work order generation.

    2.7.2 System architectureThe system architecture has a layout and several components which are presentedin the following paragraphs.

    2.7.2.1 Master station (control center)The master station has a distributed software and hardware architecture. Modernmaster station SCADA systems employ open architecture characteristics allowinginterconnection with other systems. Open system standards allow interaction withother products from suppliers.

    To ensure openness, the system must meet international standards or industrystandards like Microsoft Windows and computer applications related products, IEC60870-6 (TASE.2) for communications with other control centers, and IEEE 1379or IEC 61850 for the communications with RTU. IEEE has launched the IEEEStandard 2030 providing alternative approaches and best practices for achievingSmart Grid interoperability.

    The main SCADA system elements are shown in Figure 2.18 and shouldinclude the following components:

    2.7.2.2 Humanmachine interface (HMI)This interface consists of the mimic board and the multi-video display unit. Theboard map shows a simplified scheme of the power system. This board presents themost detailed representation of the electric system. It is organized to geographicallyrepresent the power system, which is useful for observing large disturbances thatcover an extended geographical area.

    The multi-video display interface is employed to observe the condition of thepower system devices in more detail. In modern SCADA systems, multiple screenworkstations offer operators easy access to a wide variety of application functionsand controls. These workstations combine graphical capabilities with multiplewindow functions like zoom, detachable menus, and drag-and-drop operations.

    Distribution automation functions 27

  • 2.7.2.3 Application servers Main SCADA subsystem: This server is mainly used for data processing

    functions and real-time process control. Database subsystem: This server backs up the historic database and other

    databases. Configuration and operation: This server is used for control, operation, and

    maintenance of the SCADA system. Front-end communication: This system is used for data acquisition from

    the RTU and field equipment. Besides RTU data acquisition functions, it alsoincludes protocol conversion, security check, digital and analog data tempor-ary storage, and analog values and digital state changes.

    External communications server: This server provides interchange with othercontrol centers. A standard protocol such as IEC 60870 (TASE.2) must be usedfor real-time interchange and data storage.

    2.7.2.4 Remote stationsRemote stations are measuring devices or IEDs connected to the plant that aremonitored and controlled using an interface.

    The remote station could be an RTU or PLC. The RTU is mainly used whencommunications are difficult. The RTU has digital and analog inputs, and outputsto an LED indicator (selected by channel), with optical insulation for protectionagainst overvoltage or short circuits.

    The remote station has RTU that collects the corresponding data for transmissionto the control center, and sends commands from the control center to the devices.Additionally, the data concentrators collect data from all IEDs, and, if necessary,provide data interchange with other systems (possibly with other SCADA systems).

    Mappingtable

    HMIHMITable mapcontroller

    Apps server 1

    Apps server 2

    LAN DUAL

    RTUTo othercontrol centers

    Front-endcommunication

    Communicationservers

    Figure 2.18 Control center general scheme

    28 Distribution system analysis and automation

  • 2.7.2.5 Architecture selectionThe architecture of the overall system control can have different levels of com-plexity according to the size of the system and the number of users and applica-tions. Not every system needs to have all the elements or the same number ofdevices. Figures below show different levels starting from simple systems based onRTUs to the more complex ones. Figure 2.19 shows a single master station withmultiple RTUs. Figure 2.20 shows a single master station with data concentrator orgateway, and Figure 2.21 shows a multiple master station, LAN/WAN substationconnection using routers.

    Masterstation

    RTU 1

    RTU 2

    RTU n

    Figure 2.19 Single master station, multiple RTU, radial circuit

    Gateway/data

    concentrator

    IED 1

    IED 2

    IED n

    Masterstation

    Figure 2.20 Single master station, data concentrator, or gateway

    Masterstation 1 Router

    Router

    Router

    LAN IED 1

    IED 2

    IED n

    SwitchWAN

    Masterstation n

    Figure 2.21 Multiple master stations, LAN/WAN substation connection usingrouters

    Distribution automation functions 29

  • 2.8 Synchrophasors and its application in power systems

    Due to the needs of the energy market and in order to better use company assets,key tools are employed. These include communication technology, signal proces-sing, global synchronization diffusion among monitoring, protection, and controlapplications in the electric power system aiming for efficient operations within theexisting electrical, economic, and regulatory margins.

    In the past, it was not possible to monitor in real time the relative phase angle inall voltages and intensities in the network due to processing constraints and diffi-culties in information collection, coordination, and network data synchronization.Changes have been made in new communications solutions, metering, digital dataprocessing, and data synchronization through satellites that accompanied by syn-chrophasors provide a new scenario to implement a great number of applications thatallow to increase network efficiency, tools to detect the power system networkconditions, and reliable operation near electrical and physical limits.

    In this sense, for example, the idea of real-time system monitoring is recom-mended to detect stability risk situations to make necessary and accurate decisionslimiting the impact on the affected areas avoiding total collapse of voltages in thesystem, increasing the efficiency of using transmission assets, and reducinginvestments in new circuits.

    New developments in synchronized phasor metering (synchrophasors) arepresented as an important evaluation tool for system operators for real-timemetering presenting the operator with sufficient information to take appropriateactions in the interconnection system when violations are presented and oscillationscould endanger the system stability.

    The first phasor measurement unit (PMU) was created in 1988 allowing datasynchronization using the clock pulses from a GPS; 7 years later the IEEE 1344Standard was developed where the GPS synchronized PMU is designated asthe synchrophasors. The IEEE 1344 denominated as the synchrophasor standardwas superseded by the IEEE C37-118 norm in 2005. This norm has been widelyaccepted as the preferred method for synchrophasors metering. The norm definesthe synchronized phasor samples employed in power system applications andprovides methods to quantify metering samples, test to guarantee metering samples,test error limits, and real-time data communication protocols.

    2.8.1 DefinitionA phasor is the electric network sinusoidal wave representations (voltages or cur-rents) through the projection in the real axis of a vector rotating at angular speed wat a moment t 0 producing an angle j with respect to the real axis. The timeinstant of the rotational vector picture defines the maximum values of a referencecosine wave in a way the phasor phase X represents the displacement between thereference wave and the observed cosine wave. In addition to obtaining a mathe-matical simplification, the system reduces complex electronic system needs andprocessing capabilities enabling network supervision employing PMUs. Figure 2.22shows the elaboration of the sinusoidal waveform using its phasorial representation.

    30 Distribution system analysis and automation

  • 2.8.2 Application of PMUsIn general terms, synchrophasors are phasor samples that are synchronized withUTC (Universal Time Coordinated) time that creates a nominal frequency (50 or60 Hz) cosine wave as reference. IEEE C37.118 norm from 2005 defines the syn-chrophasors as a phasor calculated from sampled data using a standard time signalas sampling reference such that phasors sampled in remote locations have a definedcommon phase relation.

    PMUs measure voltage and currents from the power system, using the instru-mentation transformers installed in substations, filter and attenuators are employedin the connection of this equipment. Once the phasor is metered, the PMU gen-erates a message with time stamp and phasor data in a format defined in 1995 bythe IEEE 1344 norm (replaced in 2005 by IEEE C37.118) in such a way that couldbe transmitted to a distant location across any available communications link. Theformat established by the IEEE C37.118 is not required for historic records ormonitoring activities, but it is required in real-time control systems.

    A simple phasorial network consists of two nodes, one is connected to a PMUlinked to a phasorial data concentrator (PDC) in the second node. The commu-nication, as illustrated in Figure 2.23, can be conducted employing any of thetechnologies currently available as direct wiring, radio network, microwave, tele-phone, digital radio, or the combination among the ones mentioned. The commu-nication protocol is described in the IEEE C37.118 Standard.

    Applications employing synchrophasors have been developed to detect synchloss, multi-area state estimation, oscillation mode identification, voltage stabilityprotection, and dynamic system monitoring. The latest application is real-timewide-area control. PMU offers attractive solutions for protection and control actionimprovements in modern power systems solving the distributed data time inco-herence including a time stamp to the data aligning samples with a common timefor processing.

    Wide area networks extent across large geographical areas like a country orcontinent. The main function is focused in network interconnection or terminals

    Re f

    f

    Im

    t1

    t0 = 0t0 = 0

    t1

    t2 t2

    t3 t3

    t4 t4

    Figure 2.22 Sinusoidal waveform from its phasorial representation

    Distribution automation functions 31

  • distantly located. The wide area networks operate based on commutation nodes thatconduct elements interconnection that allow a continuous large data flow.

    The wide area monitoring systems main purpose is to provide system opera-tors with a large information system with analysis tools that increase detectionspeeds and response time in the event of risky situations allowing the operatorsto make appropriate decisions efficiently preventing uncontrollable events orcascaded outages. This allows to convert such applications as components of pro-tection and control applications being the first step in Wide Area Monitoring Pro-tection and Control (WAMPC) projects.

    The wide area (WAMPC) protection and control schemes have not beenwidely applied yet and research groups continue to develop new applicationsgenerally divided into three groups: power systems monitoring, advanced networkprotections (wide area), and advanced control schemes.

    WAMPC applications comprehend two categories: applications in local sub-stations and applications in system or regional control centers. This classificationtakes advantage of local intelligence and the substation PMU decision power toconduct corrective actions locally in case power system events occur while main-taining general system control in control centers.

    2.8.2.1 Line parameter calculationFigure 2.24 shows the transmission line model and its parameters. Transmissionline impedance parameters can be calculated using PMU on both ends of the lineeliminating error sources. PMU measures voltage and current synchrophasors in theterminals: VS, VR, IS and IR. Line parameters R, XL, Y1 and Y2 can be calculated.Different load and ambient profiles can be obtained from these results calculating

    LAN

    WAN

    SuperPDC

    WANWAN

    PDCPMUFilter

    Router RouterRouter Router

    Router Router Router

    Router

    Switch

    Antenna

    Modem ModemCommunication

    circuit

    Web server

    Monitoring

    R. Monitoring

    1

    R. Monitoring

    2

    R. Monitoring

    3

    Line transmission

    Figure 2.23 PMUs integration with the current communication system

    32 Distribution system analysis and automation

  • distributed p sections allowing determining line voltage profiles in any transmis-sion conditions.

    2.8.2.2 State estimationThis application allows the operator to know relative angle values in differentnetwork zones making decisions with the objective of maintaining power systemintegrity during events that cause unexpected generation or transmission outagessince the increase in angle difference represents an increase in static voltagebetween two points resulting in instability and partial or total blackouts.

    2.8.2.3 Transmission line thermal monitoringLine resistance calculations based on PMU samples offer an economic approx-imation to thermal monitoring allowing efficient usage of the full transmissioncapability. By simply obtaining voltage magnitude and angle in the line connectionnodes and the current magnitude and angle flowing at the beginning and end points,the line impedance can be obtained. Based on the conductor resistance at 25 C or50 C (manufacturer data), the average conductor temperature can be calculatedextrapolating the resistance and temperature relation. With this data and in aneconomical manner, warnings can be received for overloads, transmission linecapacity dynamic control, and/or direct estimation of line depression.

    Z1 V2S V 2R

    IS VR IR VS Z1 R jX

    2.8.2.4 Voltage instabilityVoltage instability refers to power systems capacity to maintain stationary vol-tages in all busbars after a disturbance; this ability directly depends on a balancebetween power generated and demanded by loads. The instability is reflected asa continued deterioration of voltage magnitudes in certain busbars or nodes inthe system and it could be visualized as the relationship between voltagesand demanded power in the busbar; consequently, it can be determined thatvoltage stability phenomena are directly related to reactive power flow in thenetwork, load behavior in the event of voltage variations, and automatic voltageregulation device actions.

    Voltage stability deficiencies represent a high risk for safe and reliable powersystem operations; consequently, indicators have been established based on certaincalculations to determine system state in the event of a possible stability perturbance

    R

    Y2/2Y1/2

    XL IR

    VRVS

    IS

    Figure 2.24 Transmission line model

    Distribution automation functions 33

  • from the voltage point of view. However, complex mathematical processes neededto evaluate the power system state have been a limiti